Upload
laiun1124
View
74
Download
8
Embed Size (px)
Citation preview
Symmetra® MW
System with ExternalBypass SSW - User Guide
Copyright 2004
2
Contents
Safety ......................................................................1
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . 1
User Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
System Overview......................................................3
UPS Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Inverter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Control Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Input/Output Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
External Bypass Static Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operational Modes...................................................5
On-line Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Battery Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Manual Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
UPS Display............................................................11
Display and Display Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . 11Navigation symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
System Start-Up from Manual Bypass Operation. . . . . . . . . . . . 13
Transfer to Manual Bypass Operation . . . . . . . . . . . . . . . . . . . 14
Input Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Symmetra MW with External Bypass Static Switch - User Guide - 990-1377B i
Output Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Bypass Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Battery Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operation/Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . . 19
Network Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
E-mail Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SNMP Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
APC ISX Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
APC Symmetra MW Remote Display Feature. . . . . . . . . . . . . . . 26Starting web-based remote session . . . . . . . . . . . . . . . . . . 27
UPS Alarms/Troubleshooting ................................. 29
Alarm Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Severe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
View active alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
UPS alarm messages/troubleshooting . . . . . . . . . . . . . . . . . 30
External Bypass Static Switch Display..................... 39Navigation symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Bypass Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Operation/Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
ii Symmetra MW with External Bypass Static Switch - User Guide - 990-1377B
Bypass SSW Alarms/Troubleshooting ......................43
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Severe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
View active alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Bypass SSW Alarm Messages/Troubleshooting . . . . . . . . . . . 44
Warranty and Life-Support Policy ...........................47
Factory Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Life-Support Policy for APC 3-Phase Systems. . . . . . . . . . . . . . . 48
Appendix A............................................................49
Air Filter Exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Technical Support...................................................51
Symmetra MW with External Bypass Static Switch - User Guide - 990-1377B iii
Safety
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
This guide contains important instructions that should be followed when handling the UPS, External Bypass Static Switch, Battery Enclosures, and Batteries.
Symbols used in this guide
WARNING!Risk of Electric Shock.
CAUTION!Read this important information to avoid equipment damage.
Note
Indicates important information.
Indicates that more information is available on this subject in a different section of this manual.
See also
Indicates that more information is available on the same subject in a different manual.
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 1
Safety: IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
User Safety
WARNING!User functions: For safety reasons the user may only- Remove the finishing panels for air filter exchange - Operate the UPS display.
CAUTION!The system is equipped with an optional auto-start function, enabling the system to start without any warning when power is applied.
Note
Typically, the UPS installation will be connected to an EPO (Emergency Power Off) button located on a wall near the entrance to the room. If activated, the EPO switches off power to the UPS, disconnects the UPS output, and switches off power to the entire room. This action may disconnect support to the load as well.
2 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
System Overview
UPS Sections
Inverter Section
The Inverter Section regulates the UPS output and operates from battery power in the event of utility input loss.
Control Section
The Control Section controls and monitors the UPS and the Static Switch Module (incorporated in the Control Section).
Input/Output Section
The Input/Output Section provides electrical connection of input and output.
ON OFF EMO
Control SectionInverter Section Input/Output Section
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 3
External Bypass Static Switch
The External Bypass Static Switch (External Bypass SSW) transfers the load (manually or automatically) from the UPS to an alternate source without interrupting the supply to the load.
~~
External Bypass SSW Section
4 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Operational Modes
On-line Operation
During on-line operation, the critical load is supported by the inverters. The main inverter controls the output voltage and the delta inverter controls the input current. The delta inverter also provides battery-charging current. While the UPS is running in this mode, a single-line diagram will appear on the screen. The green line indicates the power flow from the utility supply through the UPS to the load.
CAUTION!Do not open Q2, Q4, or Q6 when the UPS is in on-line operation, as it may result in a load drop.
Breaker Identification
Q1 UPS input breaker Q5 Static bypass input breaker
Q2 Output breaker (optional) Q6 Static bypass output breaker (optional)
Q3 Manual bypass breaker Q7 Battery breaker 1
Q4 System output breaker (optional) Q8 Battery breaker 2
Note
Only operate a breaker when the matching breaker lamp is on.
Battery
Main InverterDelta Inverter
External Bypass SSW
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 5
Battery Operation
During battery operation, the load is supported by the inverters. The inverters are supplied by battery power, ensuring uninterrupted support to the load.
While the UPS is running in battery operation, a single-line diagram will appear on the screen with a green line indicating the power flow from the batteries through the Main Inverter to the load for as long as the batteries are energized.
CAUTION!Do not open Q2, Q4, Q6, Q7 or Q8 when the UPS is in battery operation, as it may result in a load drop.
Breaker Identification
Q1 UPS input breaker Q5 Static bypass input breaker
Q2 Output breaker (optional) Q6 Static bypass output breaker (optional)
Q3 Manual bypass breaker Q7 Battery breaker 1
Q4 System output breaker (optional) Q8 Battery breaker 2
Note
Only operate a breaker when the matching breaker lamp is on.
External Bypass SSW
Battery
Delta Inverter Main Inverter
6 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Bypass Operation
During bypass operation, the critical load is supplied directly by utility power. A single-line diagram will appear on the screen with an orange line indicating the power flow through the External Bypass SSW to the load.
CAUTION!Do not open Q4, Q5 or Q6 when the UPS is in bypass operation, as it may result in a load drop.
Breaker Identification
Q1 UPS input breaker Q5 Static bypass input breaker
Q2 Output breaker (optional) Q6 Static bypass output breaker (optional)
Q3 Manual bypass breaker Q7 Battery breaker 1
Q4 System output breaker (optional) Q8 Battery breaker 2
Note
Only operate a breaker when the matching breaker lamp is on.
Main InverterDelta Inverter
Battery
External Bypass SSW
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 7
Manual Bypass Operation
During manual bypass operation, the critical load is supplied directly by utility power, making it possible to isolate the UPS and the External Bypass Static Switch for maintenance.
A single-line diagram will appear on the screen, with an orange line indicating the power flow from the utility to the load via the Q3 breaker.
Note
Battery power is not available as an alternate power source while the system is running in manual bypass operation.
CAUTION!Do not open Q3 when the UPS is in manual bypass operation, as it may result in a load drop.
Breaker Identification
Q1 UPS input breaker Q5 Static bypass input breaker
Q2 Output breaker (optional) Q6 Static bypass output breaker (optional)
Q3 Manual bypass breaker Q7 Battery breaker 1
Q4 System output breaker (optional) Q8 Battery breaker 2
Note
Only operate a breaker when the matching breaker lamp is on.
Main InverterDelta Inverter
Battery
External Bypass SSW
8 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Operational Modes: Manual Bypass Operation
CAUTION!To avoid equipment damage, do not close Q3 until the UPS is in bypass operation (see Transfer to Manual Bypass Operation).
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 9
UPS Display
Display and Display Symbols
The LCD touch-screen UPS display is the user interface. It is used to configure the UPS, monitor the system, and change the settings. The display also provides the user with audible and visual alarms.
Normal
~~
NormalUPS Summary
Normal
Operation/Configuration
Bypass Data Menu
Normal
Input Data Menu
Normal
Transfer to Bypass Menu
Normal
Operation Menu
Normal
Transfer to On-Line Menu
Normal
Battery Data Menu
Normal
Output Data Menu
View Bypass SSW Data
View Input Data
Operation/Configuration
View Battery Data
View Output Data
Operation/Configuration
Operation/Configuration
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 11
UPS Display: Display and Display Symbols
Navigation symbols
Symbols
Buttons
Note
The screens on the following pages are examples only. All values are not shown.
Go to previous screen.
Page Down. Page Up.
Help.Press to access further details on current screen.
Home.Press to go to start screen.
Delta inverter Main inverter~ ~
Press this button to switch ON the UPS.
Press this button to switch OFF the UPS.
Emergency Module OFF button. To be used in emergency situations only. Pressing this button switches OFF all breakers, disabling AC/DC input and output in this section. This action may cut the supply to the load from the affected section.
See Alarms section for more details.
OFF
EMO
12 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
System Start-Up from Manual Bypass Operation
If the UPS has been operating in manual bypass operation and no power is connected to the UPS, the UPS display will be inactive. To re-start the system from manual bypass and achieve on-line operation, close Q1 in the external maintenance bypass panel. This will power up the internal power supply. Wait for the display to become active and follow the screen-prompted instructions.
CAUTION!Follow these instructions carefully. Failure to do so could result in equipment damage.
Normal
5.40 PM
Startup
Shutdown
Network Configuration
Display Configuration
View the Event Log
Static Bypass Online
Online Static Bypass
Transfer from manual bypass to online
Transfer from online to manual bypass
Transfer from online to static bypass
Transfer from static bypass to online
Operation
Normal
NormalNormal
UPS Startup5.40 PM
Close Q1
Charge DC Capacitors
Close battery breakers Q7 and Q8
Push UPS "ON" button
Close breaker Q2
Close breaker Q5
Close breaker Q6
Initiate transfer to static bypass
Close breaker Q4
Open breaker Q3
Initiate transfer to online mode
Display will be off until Q1 closed
Initiate Charge
Connect battery
UPS will power up
UPS output
SSW input
SSW output
Initiate transfer
System output
Manual bypass
Initiate transfer
Normal
~ ~
Q7 Q8
Manual Bypass/Off
0:00 AMUPS Summary
2
Select Operation/Configuration.
Select Start-up.
Follow the start-up instructions on the screen.
Active commands initially appear in red. Once a command has been carried out successfully, its text will change to green. Important: After pressing “Initiate charge” in step 2, wait until the green lights go on alongside battery breakers Q7 and Q8 on front of the Battery Breaker Box before closing the breakers.
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 13
Transfer to Manual Bypass Operation
To shut down the UPS (transfer from on-line operation to manual bypass operation), follow the screen-prompted instructions as illustrated.
CAUTION!Do not open Q3 when the UPS is in manual bypass operation, as it may result in a load drop.
Normal
~ ~
Q7 Q8
Normal
0:00 AM
Q2
UPS Summary
NormalNormal
UPS Shutdown5.40 PM
Initiate transfer to static bypass
Close breaker Q3
Open breaker Q4
Push UPS OFF then SSW OFF button
Open battery breakers Q7 and Q8
Open breaker Q5
Open breaker Q6
Open breaker Q2
Open breaker Q1
Initiate transfer
Load will be on manual bypass
System output
UPS power down
Isolate UPS from battery
SSW input
SSW output
UPS output
UPS input
Normal
Startup
Shutdown
Network Configuration
Display Configuration
View the Event Log
Static Bypass Online
Online Static Bypass
Transfer from manual bypass to online
Transfer from online to manual bypass
Transfer from online to static bypass
Transfer from static bypass to online
Operation
Normal
All instructions initially appear in red. Once a command has been carried out successfully, its text will change to green.
Select Operation/Configuration
Select Shutdown
Follow the shut-down instructions on the screen
14 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Input Data
The Input Summary screens provide input-specific status of voltage, power, current, frequency, etc.
NormalNormal
Input Summary5.40 PM
Page 1 of 3
587
522
456
391
326
262
196
130
65
L1 L2 L30
13 13 13
Current A
495
440
365
330
275
220
165
110
55
0450 453
Total PowerkW kVA
607
540
472
405
337
270
202
135
67
L1-2 L2-3 L3-10
VoltageV
259 264 263
55.0
54.0
53.0
52.0
51.0
50.0
49.0
48.0
47.0
45.0
46.0
FrequencyHz
259
Normal
~ ~
Q7 Q8
Normal
0:00 AM
Q2
UPS Summary
Output
Current Current highTHDTHD highTHD lowCrest factorCrest factor high
Active power Active power highApparent power Apparent power high Power factorTotal active power Total apparent power
FrequencyFrequency highFrequency lowTolerance
Mains SSWMains SSW high
Page 2 of 3
VoltageVoltage highVoltage lowTHDTHD highVoltage toleranceWaveform toleranceTolerance conditions
Temperature
22.690.2
4.01.0
2.242.17
4107003207001.0
4107003207001.0
4027013127021.0
700518
47.954.145.9
2.0
242.5260.2199.8
3.13.00.0
247.7265.1206.3
4.03.90.0
252.7270.1211.5
5.04.90.01010
17.477.8
4.91.0
2.272.2
12.472.4
6.15.91.0
2.372.3
Normal0:00 AM
NormalNormal
Input Summary5.40 PM
AA%%%
VVV%%%%%
kWkW
kVAkVA
kWkVA
HzHzHz%
129127
oFoF
Voltage
200.0
-200.0
0.0
Time (ms)
CurrentVoltage
200.0
-200.0
0.0
0.0 5.0 10.0Time (ms)
15.0
Current
NormalNormal
Input Summary5.40 PM
Page 3 of 3
Refresh Data
Yellow arrows represent the maximum values recorded to date. Blue arrows represent the minimum values recorded to date. The bars show the actual value.
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 15
Output Data
The Output Summary screens provide output-specific status of voltage, power, current, frequency, etc.
Voltage
200.0
-200.0
0.0
Time (ms)
CurrentVoltage
200.0
-200.0
0.0
0.0 5.0 10.0Time (ms)
15.0
Current
NormalNormal
Output Summary5.40 PM
Page 3 of 3
Refresh Data
Normal
~ ~
Normal
0:00 AMUPS Summary
NormalNormal
Output Summary5.40 PM
Page 1 of 3
587
522
456
391
326
262
196
130
65
L1 L2 L30
13 13 13
Current A
495
440
365
330
275
220
165
110
55
0450 453
Total PowerkW kVA
607
540
472
405
337
270
202
135
67
L1-2 L2-3 L3-10
VoltageV
259 264 263
55.0
54.0
53.0
52.0
51.0
50.0
49.0
48.0
47.0
45.0
46.0
FrequencyHz
259
L1 L2 L3 L1 L2 L3
L1-2 L2-3 L3-1
Output
Current Current highPeak currentPeak current highTHDTHD highCrest factorCrest factor high
Active power Active power highApparent power Apparent power high Power factorTotal active power Total apparent power
FrequencyFrequency highFrequency lowTolerance
LoadLoad highTotal loadTotal load high
Page 2 of 3
VoltageVoltage highVoltage lowTHDTHD highVoltage toleranceWaveform toleranceTolerance conditions
Load
57.060.020.059.4
3.93.82.1
2.03
3807007006900.92
3817016926820.81
3827026946840.82200150
51.454.245.8
2.0220.5260.0200.0
2.7
221.0261.0201.0
3.6
222.0262.0202.0
4.84.6
56
29
59.063.019.559.9
4.84.7
2.132.06
62.066.020.060.4
5.85.7
2.232.16
Normal0:00 AM
NormalNormal
Output Summary5.40 PM
A
A
A
A
%
%
VVV%%%%
kWkW
kVAkVA
kWkVA
HzHzHz%
60.058.0
68.066.0
78.076.0
142.0250.0
%%%%
Yellow arrows represent the maximum values recorded to date. Blue arrows represent the minimum values recorded to date. The bars show the actual value.
16 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Bypass Data
The Bypass Summary screens provide status of voltage, power, current, frequency, etc. when the system is operating in bypass operation.
Normal
Page 1 of 2
Normal
Bypass Summary2:04 PM
Output
Current Peak currentTHDCrest factor
Active power Apparent power Power factorTotal active power Total apparent power
Frequency
LoadTotal load
Page 2 of 2
VoltageTHD
Load
For more detailed information about Bypass, see the display on the Bypass panel
42.25.05.00.5
00
0.5
00
0.5
00
0.56896
45.8227.5
5.0229.0
5.0231.0
5.0
44.45.05.00.5
46.45.05.00.5
Normal0:00 AM
NormalNormal
Bypass Summary2.07 PM
AA%
V%
kWkVA
kWkVA
Hz
5.0 5.0 5.05.0
%%
Normal
~ ~
Normal
0:00 AMUPS Summary
Yellow arrows represent the maximum values recorded to date. Blue arrows represent the minimum values recorded to date. The bars show the actual value.
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 17
Battery Data
The Battery Summary screens provide battery-specific status of voltage, current, run-time remaining, temperature, power, etc.
NormalNormal
2:08 PM
Page 1 of 3
Current Voltage
Runtime remaining
12 m 0 s
Battery Summary
Normal
~ ~
Normal
0:00 AMUPS Summary
Output
Battery 1VoltageVoltage highVoltage lowCurrentCurrent high dischargeBattery 2VoltageVoltage highVoltage lowCurrentCurrent high dischargeSettingsMin. voltage: warningMin. voltage: shutdownMax voltage: warningMax voltage: shutdown
Boost chargeAuto boost chargeNominal chargeBoost chargeEstimated charge timeEstimated charge %Batt 1 charge current highBatt 2 charge current high
BatteryMax batteryBattery highBattery low
Battery chargeTime on batteryRuntime remainingTotal time on batteryTotal # of times on battery
Page 2 of 3
Statistics
Charge
Temperature
Voltage and Current
falsefalse
420450
65100
-90.0-90.0
10086
10486
440.0450.0420.0
57.2119.5
451.0460.0420.0
51.5120.0
370320460475
Normal0:00 AM
NormalNormal
2.08 PM
VVVAA
VVVAA
VVVV
VVm%AA
oFoFoFoF
Battery powerBattery power high dischargeBattery power high charge
Power000
kWkWkW
Floating0
300 m 000
ss
m
Battery Summary
100.0
0.0
50.0
0.0 50.0 100.0
Time (hours)
Tem
per
atu
re (
¡F)
NormalNormalNormal
Battery Summary5.40 PM
Page 3 of 3
Refresh Data
Yellow arrows represent the maximum values recorded to date. Blue arrows represent the minimum values recorded to date. The bars show the actual value.
18 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Operation/Configuration Data
The Operation screen permits system operation and monitoring, and provides the ability to change display settings (as illustrated in the following menus).
Normal
Initiate transfer to online
Static Bypass to Online
Normal
0:00 AM
Initiate transfer
Initiate transfer to static bypass
In static bypass the load is powered directly by utility power.There will be no UPS backup.
NormalNormal
0:00 AMOnline to Static Bypass
Initiate transfer
NormalNormal
UPS Shutdown5.40 PM
Initiate transfer to static bypass
Close breaker Q3
Open breaker Q4
Push UPS OFF then SSW OFF button
Open battery breakers Q7 and Q8
Open breaker Q5
Open breaker Q6
Open breaker Q2
Open breaker Q1
Initiate transfer
Load will be on manual bypass
System output
UPS power down
Isolate UPS from battery
SSW input
SSW output
UPS output
UPS input
NormalNormal
Operation5.40 PM
Startup
Shutdown
Network Configuration
Display Configuration
View the Event Log
Static Bypass Online
Online Static Bypass
Transfer from manual bypass to online
Transfer from online to manual bypass
Transfer from online to static bypass
Transfer from static bypass to online
Normal
~ ~
Q7 Q8
Normal
0:00 AM
Q2
UPS Summary
NormalNormal
UPS Startup5.40 PM
Close Q1
Charge DC Capacitors
Close battery breakers Q7 and Q8
Push UPS "ON" button
Close breaker Q2
Close breaker Q5
Close breaker Q6
Initiate transfer to static bypass
Close breaker Q4
Open breaker Q3
Initiate transfer to online mode
Display will be off until Q1 closed
Initiate Charge
Connect battery
UPS will power up
UPS output
SSW input
SSW output
Initiate transfer
System output
Manual bypass
Initiate transfer
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 19
UPS Display: Operation/Configuration Data
NormalNormal
Network Configuration
Network settings
5.39 PM
Page 1 of 4
IP address
Subnet mask
Gateway
DNS server primary
DNS server secondary
Hostname
Domain name
Enable network
Apply Changes
777.111.111.000
111.111.111.0
200.200.200.1
200.200.200.200
200.200.200.200
company.com
UPS1
8888
111.111.111.111
123
rms
BMS Modbus RTU Address
Enable APC RMS Use Proxy
Proxy Server IP Address
Proxy Server Port
Use Authentication
Proxy Server Login
Proxy Server Password *****
SeveritySeveritySeveritySeverity Event DescriptionEvent DescriptionEvent DescriptionEvent Description ParamParamParamParam Date TimeDate TimeDate TimeDate Time
Download complete
UPS state: Burn inUPS state: Extended self testUPS state: Basic self testUPS state: Battery testUPS state: Bypass operationUPS state: InitializeUPS state: Battery operationUPS state: OffUPS state: System setupUPS state: DC chargeUPS state:Normal operationEMO/EPO activatedInput fault, low voltage
1111111111111
06—27—2003 11:24:41.006—27—2003 11:24:41.006—27—2003 11:24:41.006—27—2003 11:24:41.006—27—2003 11:24:41.006—27—2003 11:24:41.006—27—2003 11:24:41.006—27—2003 11:24:41.006—27—2003 11:24:42.006—27—2003 11:24:42.006—27—2003 11:24:42.006—27—2003 11:24:42.006—27—2003 11:24:42.0
WarningWarningInfoWarningWarningInfoSevereWarningInfoInfoInfoSevereInfo
DataDataDataData
NormalAlarm: Severe
3:51 PMEvent Log
Refresh
The event log contains a detailed record of the system’s last 1024 events which include operation mode changes, alarms, etc. When pressing the Refresh button, the Event Log is updated. During the update, the Refresh button changes to a Stop button.
To change brightness or contrast, touch the relevant indicator and slide to desired percentage point.The backlight mode’s default setting is on at all times. For switch off after a pre-defined period of inactivity, select 5, 10, 15, 30, or 60 minutes.
Normal
0 100%
Brightness
43 %
0 100%
Contrast
Backlight timeout (in minutes)
Backlight mode
35%
Normal
Display Configuration2:27 PM
Off after inactivity
5
20 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Network Settings
All network settings information must be provided before any network functions (e-mail settings, SNMP settings) can be used.
• Touch the Enable Network field to connect or disconnect the UPS from the network.
• Touch the IP address field to assign an IP address for the UPS.
• Assign the Subnet Mask, Gateway, Primary and Secondary DNS Servers, Hostname, and Domain Name in the same way.
• Use the BMS Modbus RTU address field to monitor the UPS with a Building Management System, using the modbus RTU protocol. For more information on system monitoring using BMS, contact APC Technical Support.
•
• HTTP Proxy Server Connection Settings (for RMS): The APC RMS uses the HTTP Protocol to post information to the APC RMS database. If the internet connection is a proxy server, then enter the required Proxy Server Connection Settings on the Network Configuration screen. A
Note
Selecting the Enable APC RMS checkbox will cause the UPS to send information to APC’s Remote Monitoring Service. Visit www.apc.com to learn more about this service.
NormalNormal
Network Configuration
Network settings
5.39 PM
Page 1 of 4
IP address
Subnet mask
Gateway
DNS server primary
DNS server secondary
Hostname
Domain name
Enable network
Apply Changes
777.111.111.000
111.111.111.0
200.200.200.1
200.200.200.200
200.200.200.200
company.com
UPS1
8888
111.111.111.111
123
rms
BMS Modbus RTU Address
Enable APC RMS Use Proxy
Proxy Server IP Address
Proxy Server Port
Use Authentication
Proxy Server Login
Proxy Server Password *****
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 21
UPS Display: Network Settings
Proxy Server acts as an agent between a workstation user or other networked device and the Internet so that the security, administrative control and caching service can be regulated.
• Use Proxy: Select this checkbox if the Internet connection method uses an HTTP Proxy Server to connect to the Internet. Enter the following values (required):
– Proxy Server IP Address: Enter the fully qualified IP address of the Proxy Server in this field if the internet connection is a Proxy Server, e.g. 159.215.123.116
– Proxy Server Port: Enter the port number of the Proxy Server in this field if a Proxy Server is used. If you do not know the server address or port number, contact the network administrator.
– Use Authentication: Select this checkbox if the Proxy Server requires authentication. Supply a login (username) and password. Enter these values in the Proxy Server Login and Proxy Server Password fields.
• Select the Apply Changes button when all information has been entered.
To view the other network settings screens, press the arrow down button.
Note
RMS is not available on the External Bypass Static Switch.
22 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
E-mail Settings
The UPS can send E-mail messages when UPS alarms occur. The E-mail messages will list the active alarm conditions on the UPS. First, configure the Network Settings information.
• The E-mail function can be enabled or disabled using the Enable E-mail field.
• An existing SMTP server on the Network is required to send an E-mail. Touch the SMTP Server field, and enter the name of the SMTP Server (for example, mail.server.com).
• Messages sent by the UPS require a From Address. The From Address appears as the sender of the E-mail. Touch the From Address field and enter a valid E-mail address.
• Touch the Recipient Address field to enter the addresses of the E-mail recipient(s).
• In the Minimum Severity field, specify the severity of alarms that will cause an E-mail to be sent.
• Touch the Add/Update Entry button to add a new recipient to the list.
• To change an existing address, touch the address on the list. This address will then appear in the Recipient Address field; touch it again to edit and select the Add/Update Entry button.
• To remove an address from the list, touch the address. The address will then appear in the Recipient Address field. Select the Remove button to delete it.
• Select the Apply Changes button after all changes have been made.
• Use the Test E-mail button to ensure that the E-mail configuration is correct. Touching this button will cause a test E-mail to be sent to all configured E-mail recipients.
NormalNormal
Network Configuration5.34 PM
Page 2 of 4
Remove
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 23
SNMP Settings
The UPS can be set to send SNMP traps if UPS alarms occur. Each trap contains a description of the alarm condition. The trap receiver must have the APC PowerNet MIB (version 3.6.1 or later). Available from www.apc.com.
• Touch the Enable SNMP field to enable or disable the SNMP Trap function.
• Touch the Recipient Address field to enter IP addresses of trap receivers. Use the Minimum Severity field to specify the severity of alarms that will cause a trap to be sent to that recipient. Use the Add/Update Entry button to add a new recipient to the list.
• To change an existing trap receiver, touch the IP address on the list. The selected IP address will appear in the Recipient Address field. Touch this field to make edits. Select the Add/Update Entry button to update.
• To remove a trap receiver from the list, touch the IP address. The selected address will appear in the Recipient Address field. Select the Remove button to delete the address.
• Select the Apply Changes button after amendments have been completed.
• Select the Send Test Trap button to ensure that the trap configuration is correct. Selecting this button will cause a test trap to be sent to all configured trap receivers.
Note
Configure the Network Settings (as described in the Network Settings section) prior to configuring the SNMP Settings.
Note
By default the community string is set to public.
NormalNormal
Network Configuration
SNMP settings
5.34 PM
Page 3 of 4
Enable SNMP
Minimum severity
123.234.123.150 [Severe]
123.234.123.144 [Warning]
Remove
24 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
APC ISX Manager
The following settings have to be configured for the Symmetra MW to be discovered by the APC ISX Manager
• Check off the Enable ISX Manager Discovery check-box
• Community Name
• System Location (optional)
• System Contact (optional)
Note
Select the Apply Changes button after the APC ISX Manager screen has been completed.
NormalNormal
Network Configuration
APC ISX Manager
5.34 PM
Page 4 of 4
Enable ISX Manager Discovery
Community Name
System Location
System Contact
xxxxxx
xxxxxx
xyzs vb
Apply Changes
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 25
APC Symmetra MW Remote Display Feature
The read-only display screens can be accessed via an Internet Browser by typing the IP address of the Symmetra MW display into the browser’s address field. The remote display feature provides a subset of the Symmetra MW display screens. Configuration of the Symmetra MW or the display through the remote display is not supported.
The remote display feature requires Microsoft Internet Explorer 6 SP1 or greater. For best results we recommend that the Sun JVM version 1.4.2_03 or greater be installed. This is available from Sun’s website.
The Netscape browser is not supported.•
Note
All Input, Output, Battery and Bypass screens can be seen in a remote session. Operation/configuration must be done at the UPS. The event log screen can be accessed through the Operation screen. Only the 50 most recent events in the Event Log screen can be downloaded.
Note
Network settings must be configured before the remote display feature can be used.
26 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
UPS Display: APC Symmetra MW Remote Display Feature
Starting web-based remote session
• Start the web-based remote session by entering the IP address of the UPS in the web browser Address field. After a few seconds, a new window will open and display the below screen.
• After a few seconds, the UPS display is shown on the screen.
• Use the mouse to touch the buttons to see other screens.
• Close the window or the web browser to end the remote session.
Note
For security reasons, there is a time limit of 30 minutes for a remote session. The connection will be disconnected after 30 minutes and reconnection is required.
Note
Only one remote session at a time is allowed.
XXX.XXX.XXX.XX
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 27
UPS Alarms/Troubleshooting
Alarm Types
The color of the top of the screen switches from blue to red when an alarm situation occurs and the alarm symbol is shown at the top of the screen.
Info
Informational Alarm. No immediate need to take action. Check the cause of the alarm at next maintenance visit.
Warning
Minor Alarm. Example: The UPS system may have gone into bypass. The load remains supported, but action must be taken. Call Technical Support. The area in the right side of the top screen alternates between blue and red.
Severe
Major Alarm. Take immediate action. Call Technical Support. The red area of the top of the screen alternates between blue and red.
Alarm button. Pressing the alarm button will take the user to a screen showing all active alarms and how each alarm should be addressed. The 3 different alarm levels are described below. Hitting the alarm symbol or any other display button will automatically silence the alarm.
3:51 PM
3:51 PM
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 29
UPS Alarms/Troubleshooting: Alarm Types
View active alarms
Press the red triangular alarm symbol to view active alarms. Only active alarms will appear on the screen. Pressing the alarm symbol will also mute acoustic alarms.
Previous alarms are stored in the Event Log, which contains a detailed record of the system’s last 1024 events.
UPS alarm messages/troubleshooting
Following is a list of alarm messages that may appear in the active alarm screen and/or in the event log. Each alarm type contains a description and the user-action needed to rectify the problem.
SeveritySeveritySeveritySeverity Alarm DescriptionAlarm Description Suggested ActionSuggested ActionSuggested ActionSuggested Action Date TimeDate TimeDate TimeDate Time
Download complete
Mains static switch fan comm. faultBattery temperature highBypass unavailableOutput off
Call APC for serviceCheck temperature in the battery roomCall APC for serviceNo output from UPS
06-11-2003 15:45:11.47506-11-2003 15:45:04.27606-11-2003 15:44:48.71906-11-2003 15:44:48.718
WarningWarningSevereSevere
UPS offAlarm: Severe
3:51 PMActive Alarms
Event Log Refresh
~ ~
Q7 Q8
Q2
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
High temperature on battery.
A high battery temperature will result in a reduced lifetime of the batteries.
2 Check temperature in the battery room.
14.1.1
Low temperature on battery.
A low battery temperature can destroy the battery and result in malfunction of the UPS when operated in battery operation.
1 Check temperature in the battery room.
14.1.2
Battery Breaker 1 open.
The UPS will not be able to operate in normal and battery operation.
3 Battery 1 disconnected from UPS.
14.3.1
Battery Breaker 2 open.
The UPS will not be able to operate in normal and battery operation.
3 Battery 2 disconnected from UPS.
14.4.1
30 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
UPS Alarms/Troubleshooting: Alarm Types
Low battery voltage warning.
The battery voltage is low and the UPS will shut down in pre-defined time if running in battery operation.
3 UPS will shut down shortly.
14.5.1
Battery cabinet fuse fault.
A battery cabinet fuse is blown.
3 UPS will shut down shortly.
14.6.1
High battery voltage warning.
The battery voltage is too high.
2 Call APC for service. 14.7.1
Low battery voltage shut down.
Battery voltage is too low. The UPS will shut down immediately, and transfer to bypass if possible.
3 UPS will shut down. 14.9.1
High battery voltage shut down.
Battery voltage is too high. The UPS will shut down immediately, and transfer to bypass if possible.
3 Call APC for service. 14.11.1
Battery weak. Battery capacity below 75%. 2 Charge battery for 24 hours, and repeat test.
14.13.1
Battery defective. Critical battery capacity. Service needed.
3 Call APC for service. 14.13.2
Battery test running. UPS is performing a battery test.
1 None. 14.14.1*
Battery test completed.
UPS has completed the battery test.
1 None. 14.14.2*
Battery test aborted. Battery test has been aborted.
1 None. 14.14.3*
Battery capacity test running.
UPS is performing a battery capacity test.
1 None. 14.15.1*
Battery capacity test completed.
UPS has completed the battery capacity test.
1 Read the obtained backup time in the event log.
14.15.2*
Battery capacity test aborted.
Battery capacity test has been aborted.
1 None. 14.15.3*
Battery temperature sensor fault.
Battery temperature sensor fault.
2 Call APC for service. 14.16
DC collapse present. Fast low DC shutdown present.
3 Call APC for service. 14.17
Input fault, low voltage.
Input voltage too low. 3 Utility is out of tolerance or missing.
24.1.1
Input fault, high voltage.
Input voltage too high. 2 Utility is out of tolerance.
24.1.2
Input fault phase sequence.
Input voltage incorrect phase sequence.
3 Wrong input phase sequence.
24.7.1
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 31
UPS Alarms/Troubleshooting: Alarm Types
Input fault, fast detector.
Input voltage fast voltage error detected.
3 Utility is out of tolerance.
24.8.1
Mains synchronization error.
The input frequency is outside the selected tolerance.
3 Input frequency is out of tolerance.
24.2.1
Main SSW fan weak. A weak fan is approaching failure.
1 Fan is approaching failure.
24.4.1
Replace Main SSW fan.
A fan must be replaced 2 Call APC for service. 24.4.2
Main SSW fan fault. A fan is no longer working. 3 Call APC for service. 24.4.3Input fuse fault. One or more of the input
main fuses are blown.3 Call APC for service. 24.5.1
Input section fuse fault.
One or more of the input section fuses are blown.
3 Call APC for service. 24.6.1
Mains Bypass SSW temperature too high.
Mains Bypass SSW temperature too high.
3 Call APC for service. 24.9
Input contactor fault. Input contactor fault. 3 Call APC for service. 24.10Input frequency fault. Input frequency fault. 3 None. 24.11Output voltage low. The output voltage is out of
tolerance.3 Call APC for service. 34.2.1
Output voltage high. The output voltage is out of tolerance.
3 Call APC for service. 34.2.2
Output off. The UPS output is OFF. 3 No output from UPS. 34.3.1Output fuse fault. One or more of the output
fuses are blown.3 Call APC for service. 34.5.1
Section output fuse fault.
Inverter section fuse fault detected.
3 Call APC for service. 34.6.1
Output contactor fault.
Output contactor fault. 3 Call APC for service. 34.7
Output fast error detected.
Fast error detected. 3 None. 34.8
Parallel comm. error, cable 1.
Parallel communication fault on cable 1.
2 Call APC for service. 54.1.1
Parallel comm. error, cable 2.
Parallel communication fault on cable 2.
2 Call APC for service. 54.1.2
Parallel comm. error, cable 1 and 2.
Parallel communication fault on cable 1 and 2.
3 Call APC for service. 54.1.3
Normal and battery operation.
The units are in different operation modes
0 None. 54.2
UPS number error present.
The stated UPS number is not available.
3 Call APC for service. 54.3
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
32 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
UPS Alarms/Troubleshooting: Alarm Types
No master present. No master in the parallel system.
3 Call APC for service. 54.4
Parallel units disabled.
Parallel unit disabled. 3 Call APC for service. 54.5
PBUS Termination fault on cable 1.
PBUS Termination fault on cable 1
2 Call APC for service. 54.7
PBUS Termination fault on cable 2.
PBUS Termination fault on cable 2
2 Call APC for service. 54.7
PBUS Termination fault on cable 1 and 2.
PBUS Termination fault on cable 1 and 2.
3 Call APC for service. 54.7
Number of parallel UPS’s error present.
Error in the stated number of UPS units in the parallel system.
3 Call APC for service. 54.8
Inverter module high temperature.
The temperature of an inverter module is too high.
3 Call APC for service. 64.1.1
Overload on UPS. The UPS load is greater than the nominal load.
2 Remove overload from the UPS.
64.3.1
Off button pushed. The OFF button has been activated.
2 The OFF button has been pushed.
64.5.1*
Inverter fan is approaching failure.
A weak fan is approaching failure.
1 Fan is approaching failure.
64.6.1
Replace inverter fan. Inverter fan must be replaced.
2 Call APC for service. 64.6.2
Inverter fan fault. Inverter fan is no longer working.
3 Call APC for service. 64.6.3
Inverter fuse blown. A main inverter fuse is blown.
3 Call APC for service. 64.7.1
The ambient temperature high or low.
The ambient temperature is too high or too low.
2 Check room temperature.
64.10.1
Bypass unavailable. Bypass input outside tolerance, or Static Switch faulty.
3 Call APC for service. 64.12.1
EMO/EPO activated. The EMO or EPO has been activated.
3 UPS is shut down. 64.13.1*
Output current limiter active.
The load on the output of the UPS is exceeding the nominal load.
2 Remove overload from the UPS.
64.14.1
MC to PMC’s communication error.
Communication error between the Main Controller (MC) and the Power Module Controllers (PMC).
3 Call APC for service. 64.17.1
Inverter section fault. Fault in an inverter section. 3 Call APC for service. 64.20.1
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 33
UPS Alarms/Troubleshooting: Alarm Types
Battery cubicle CAN I/O fault.
Error in communication with battery CAN I/O board.
2 Call APC for service. 64.21.1
Switch gear CAN I/O fault.
Error in communication with MBP (Maintenance Bypass Panel) CAN I/O board.
2 Call APC for service. 64.22.1
Main SSW fan CAN I/O fault.
Error in communication with Main SSW (Static Switch Module) CAN I/O board.
2 Call APC for service. 64.23.1
Main Controller to display comm. fault.
Error in communication between Main Controller and display.
2 Call APC for service. 64.25.1
Crowbar trigged. A crowbar has been triggered.
3 Call APC for service. 64.26.1
Ground fault detected.
Ground fault detected. 2 Call APC for service. 64.27.1
Neutral bonding choke fault.
Over-temperature on bonding choke.
3 Call APC for service. 64.28.2
Top fan weak. A weak fan is approaching failure.
1 Fan is approaching failure.
64.29.1
Replace top fan. Top fan must be replaced. 2 Call APC for service. 64.29.2Top fan fault. Top fan no longer working. 3 Call APC for service. 64.29.3Main inverter peak current limiter on.
Overload on UPS. 2 Remove overload from the UPS.
64.30.1
Delta inverter peak current limiter on.
Delta inverter in peak current limitation due to overload.
2 Remove overload from the UPS.
64.31.1
Main PSU fault. Fault on main PSU (Power Supply) Module.
2 Call APC for service. 64.32.1
Main controller SELV PSU fault.
Fault on Main Controller SELV PSU (Power Supply).
2 Call APC for service. 64.33.1
Power module PSU fault.
Fault on Power Module PSU (Power Supply).
2 Call APC for service. 64.34.1
Main inverter current sense fault.
Current sense fault on main inverter module.
2 Call APC for service. 64.35.1
PMC to power module comm. fault.
Error in communication between PMC (Power Module Controller) and Power Module.
2 Call APC for service. 64.36.1
Inverter DC 1 fuse fault.
Fuse blown on battery 1 (positive battery).
3 Call APC for service. 64.37.1
Inverter DC 2 fuse fault.
Fuse blown on battery 2 (negative battery).
3 Call APC for service. 64.38.1
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
34 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
UPS Alarms/Troubleshooting: Alarm Types
System locked in bypass operation.System locked in battery operation.
System locked in bypass or battery operation.
1 Push ON to release. 64.40
Neutral Bonding Choke Earth Fault.
Neutral Bonding Choke Earth Fault.
2 Call APC for service. 64.41
Breaker Q1 open. Breaker Q1 open. 1 Not required. 64.42*Breaker Q1 closed. Breaker Q1 closed. 1 Not required. 64.42*Breaker Q2 open. Breaker Q2 open. 1 Not required. 64.43*Breaker Q2 closed. Breaker Q2 closed. 1 Not required. 64.43*Breaker Q3 open. Breaker Q3 open. 1 Not required. 64.44*Breaker Q3 closed. Breaker Q3 closed. 1 Not required. 64.44*Breaker Q4 open. Breaker Q4 open. 1 Not required. 64.45*Breaker Q4 closed. Breaker Q4 closed. 1 Not required. 64.45*Breaker Q5 open. Breaker Q5 open. 1 Not required. 64.46*Breaker Q5 closed. Breaker Q5 closed. 1 Not required. 64.46*Breaker Q6 open. Breaker Q6 open. 1 Not required. 64.47*Breaker Q6 closed. Breaker Q6 closed. 1 Not required. 64.47*System started by auto restart.
Auto restart. 1 Not required. 64.48*
AC input capacitor temperature high.
Inverter AC input capacitor temperature fault.
2 Call APC for service. 64.49
AC output capacitor temperature high.
Inverter AC output capacitor temperature fault.
2 Call APC for service. 64.50
DC capacitor temperature high.
Inverter DC Capacitor temperature high.
2 Call APC for service. 64.51
Power module choke temp. switch fault.
Power Module choke temperature switch fault.
3 Call APC for service. 64.52
Power module heatsink temp. switch fault.
Power Module heatsink temperature switch fault.
3 Call APC for service. 64.53
Delta transformer temp. switch fault.
Delta transformer temperature switch fault.
3 Call APC for service. 64.54
Section locked by section manager.
Section locked by section manager.
3 Call APC for service. 64.55
Switch gear earth fault.
Switch gear earth fault. 2 Call APC for service. 64.56
Load is disconnected. Load disconnected. 3 None. 64.57IGBT high switch fault.
IGBT high switch fault. 3 Call APC for service. 64.58
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 35
UPS Alarms/Troubleshooting: Alarm Types
* These alarms will only be logged in the event log and will not appear in the active alarms list.
IGBT low switch fault.
IGBT low switch fault. 3 Call APC for service. 64.59
IGBT DC high fault. IGBT DC high fault. 3 Call APC for service. 64.60IGBT DC low fault. IGBT DC low fault. 3 Call APC for service. 64.60Section DC high. Section DC high. 3 Call APC for service. 64.61CBUS terminator fault.
CBUS terminator fault. 3 Call APC for service. 64.62
Initialization completed after powerup.
Init completed after powerup.
1 Not required. 64.63*
Unit setting changed. One of the unit settings has been changed. See table under Unit Setting to see the different settings.
1 Not required. 64.64*
Unit setting reset to default.
Genes reset to default. 1 Not required. 64.65*
Event log cleared. Event log cleared. 1 Not required. 64.66*Section is disabled. One of the sections is
disabled.3 Call APC for service. 64.67
Max/min values cleared.
Max/min values cleared. 1 Not required. 64.68*
Q3 breaker closed - going into bypass.
Reason for bypass - Q3 closed.
1 Not required. 64.69*
Requested bypass. Reasons for bypass - Req bypass.
1 Not required. 64.69*
Output error - going into bypass.
Reasons for bypass - output error.
3 Not required. 64.69*
DC error - going into bypass
Reasons for bypass - DC error.
3 Not required. 64.69*
Internal fault - going into bypass.
Reasons for bypass - Internal fault.
3 Not required. 64.69*
On button pushed. On button pushed. 1 Not required. 64.70*Bypass requested from display.
Bypass requested from display.
1 Not required. 64.71*
Discharging batteries. Discharging batteries. 3 Call APC for service. 64.72ABUS terminator fault.
ABUS terminator fault. 3 Call APC for service. 64.73
MC Isolated SELV PSU Fault
MC Isolated SELV PSU Fault
3 Call APC for service. 64.74
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
36 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
UPS Alarms/Troubleshooting: Alarm Types
Unit Settings.
No. Setting No. Setting
0 Device Type 30 Battery High Temperature Warning Level
1 Unit Number 31 Battery Equalization Charge Time
2 Serial Number 32 Battery Equalization Charge Voltage
3 Battery Calibration Temp1 33 Battery Boost Charge Time
4 Battery Calibration Temp2 34 Not implemented
5 Battery Calibration Temp3 35 Not implemented
6 Battery Calibration Temp4 36 Input Calibration Voltage L1
7 Battery Calibration Temp5 37 Input Calibration Voltage L2
8 Battery Calibration Positive Voltage 38 Input Calibration Voltage L3
9 Battery Calibration Negative Voltage 39 Input Calibration Current L1
10 Battery Calibration Positive Current 40 Input Calibration Current L2
11 Battery Calibration Negative Current 41 Input Calibration Current L3
12 Battery Manufacturer 42 Input Number of Phases
13 Battery Type 43 Isolation Transformer on Input
14 Expected Backup Time 44 Nominal Mains Voltage
15 Battery Capacity 45 Nominal Input Frequency
16 Battery Install Date 46 Number of Temperature Sensors on Main SSW
17 Battery Nominal Life Time 47 Number of Fans on Main SSW
18 Battery No. of Temperature Sensors 48 Number of Main Input Fuse Sensors
19 Battery Automatic Test Month 49 Number of Section Fuse Sensors
20 Battery Automatic Test Day 50 Input Voltage RMS Tolerance
21 Battery Automatic Test Time 51 Input Voltage Wave Tolerance
22 Activate/Deactivate Battery Boost Charge 52 Input Frequency Tolerance
23 Automatic Battery Boost Charge 53 Maximum Input Isolation Temperature
24 Nominal Charge Voltage 54 Output Calibration Voltage L1
25 Battery Boost Charge Voltage 55 Output Calibration Voltage L2
26 Battery Low Voltage Warning Level 56 Output Calibration Voltage L3
27 Battery Shut Down Low Voltage Level 57 Output Calibration Current L1
28 Battery High Voltage Warning Level 58 Output Calibration Current L2
29 Battery Shut Down High Voltage Level 59 Output Calibration Current L3
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 37
UPS Alarms/Troubleshooting: Alarm Types
No. Setting No. Setting
60 Output Nominal Voltage 83 No of UPS in Parallel
61 Output Nominal Frequency 84 Part of Parallel System
62 Output Frequency Tolerance 85 UPS Number
63 Output Nominal Power VA 86 Battery Connection in Parallel System
64 Output Nominal Power W 87 Bypass Switch Type
65 Number of Output Fuse Sensors 88 Total Nominal Output Power W
66 Output Voltage RMS Tolerance 89 Total Nominal Output Power VA
67 Output Voltage Wave Tolerance 90 Advanced Power Management
68 Not implemented 91 Real Time Clock Synchronized
69 Bypass Calibration Voltage L1 92 Normal/Battery Detection
70 Bypass Calibration Voltage L2 93 Number of Inverters per Section
71 Bypass Calibration Voltage L3 94 Number of Sections
72 Bypass Type 95 Number of Temperature Sensors per Inverter
73 Bypass Nominal Voltage 96 Number of Fans per Inverter
74 Bypass Number of Fans 97 Number of Top Fans per Section
75 Bypass Nominal Frequency 98 Main SSW Orientation
76 Bypass Number of Fuse Sensors 99 UPS Automatic Restart ON/OFF
77 Bypass Nominal Power in VA 100 Not implemented
78 Bypass Nominal Power in W 101 Delta Soft Start Time
79 Bypass Voltage RMS Tolerance 102 Synchronization Speed
80 Bypass Volt Wave Tolerance 103 Remote Startup Allowed
81 Bypass Frequency Tolerance 104 Under Voltage Timer
82 Bypass Watchdog Enabled
38 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
External Bypass Static Switch Display
The LCD touch-screen External Bypass SSW display is the user interface. It is used to configure the External Bypass SSW, monitor the system and change the settings. The touch-screen display also provides the user with audible and visual alarms.ONOFF EMO
NormalNormalBypass Static Summary
0:00 AM
ON ONOFF EMO
NormalNormalBypass Static Summary
0:00 AM
ON
Q7 Q8
Q2~ ~
NormalNormalBypass Summary
0:00 AM
Bypass Data Menu
Operation/Configuration
Menu
Operation/Configuration
View External Bypass SSW Data
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 39
External Bypass Static Switch Display:
Navigation symbols
Symbols
Buttons
Go to previous screen.
Page Down. Page Up.
Help.Press to access further details on current screen.
Home.Press to go to start screen.
Delta inverter Main inverter~ ~
The External Bypass SSW is controlled by the UPS. Do not touch this button when the UPS is in normal operation. Press this button to activate manual control of the External Bypass SSW.
Press this button to deactivate the External Bypass SSW.
Emergency Module OFF button. To be used in emergency situations only. Pressing this button switches OFF Q5 and Q6, disabling AC input and output in this section. This action may cut the supply to the load from the affected section.
See Alarms section for more details.
OFF
EMO
40 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Bypass Data
The Bypass Summary screens provide input specific status of voltage, power, current, frequency, etc.
L1 L2 L3
L1 L2 L3
L1 L2 L3
L1-2 L2-3 L3-1
Output
Current Current highPeak currentPeak current highTHDTHD highCrest factorCrest factor high
Power factorActive powerActive power high Apparent powerApparent power high Total active powerTotal active power high Total apparent powerTotal apparent power high
FrequencyFrequency highFrequency lowLoad
Load highTotal loadTotal load high
Page 2 of 2
VoltageVoltage highVoltage lowTHDTHD high
Load
Temperature
16.221.213.030.0
0.00.0
1.041.91
0.130201
0.060001
0.0701010112
59.359.559.1
481.1487.4473.3
0.00.0
479.9486.6472.1
0.00.0
480.0486.7472.1
0.00.0
15.019.717.030.0
0.00.0
1.111.95
13.218.913.026.0
0.00.0
97.01.99
Normal0:00 AM
NormalNormal
Bypass Summary2.40 PM
AAAA%%
VVV%%
kWkW
kVAkVAkWkW
kVAkVA
HzHzHz
Mains SSWMains SSW High
3938
oCoC
1.31.6
1.21.6
1.11.41.21.4
%%%%
NormalNormal
Bypass Summary2:39 PM
Page 1 of 2
23.3
20.7
18.1
15.5
13.0
10.4
7.8
5.2
2.6
L1 L2 L3
0.0164 154 132
Current A
1.1
1.0
0.9
0.7
0.6
0.5
0.4
0.2
0.1
01.0
Total PowerkW kVA
607
540
472
405
337
270
202
135
67
L1-2 L2-3 L3-10
VoltageV
481 480 480
70.0
67.8
65.6
63.3
61.1
58.9
56.7
54.4
52.2
50.0
FrequencyHz
59.2
Normal
~ ~
Q7 Q8
Q2
Bypass SummaryNormal
0:00 AM
Yellow arrows represent the maximum values recorded to date. Blue arrows represent the minimum values recorded to date. The bars show the actual value.
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 41
Operation/Configuration
This screen permits system operation and monitoring, and provides the ability to change display settings (as illustrated in the following menus).
SeveritySeveritySeveritySeverity Event DescriptionEvent Description ParamParamParamParam Date TimeDate TimeDate TimeDate Time
Download complete
Info Mains Synchronization OK 0 0 11-11-2002 12:01:27.723Info Fast error detect cleared 0 0 11-11-2002 12:01:30.723Warning Fast error detect 0 0 11-11-2002 12:01:40.383
Warning Fast error detect 0 0 11-11-2002 12:01:40.383
Info Bypass voltage ok 0 0 11-11-2002 12:11:02.011Severe Bypass voltage low 0 0 11-11-2002 12:11:27.335
Severe Mains Synchronization error 0 0 11-11-2002 12:11:27.335Info Fast error detect cleared 0 0 11-11-2002 12:11:30.550
DataDataDataData
NormalNormal
Event Log2:27 PM
Refresh
NormalNormal
Operation5.40 PM
Network Configuration
Display Configuration
View the Event Log
The event log contains a detailed record of the system’s last 1024 events, including mode changes, alarms, etc. When pressing the Refresh button, the Event Log is updated. During the update, the Refresh button changes to a Stop button.
Normal
~ ~
Q7 Q8
Q2
Bypass SummaryNormal
0:00 AM
Normal
0 100%
Brightness
43 %
0 100%
Contrast
Backlight timeout (in minutes)
Backlight mode
35%
Normal
Display Configuration2:27 PM
Off after inactivity
5
To change brightness or contrast, touch the relevant indicator and slide to desired percentage point.The backlight mode’s default setting is on at all times. For switch off after a pre-defined period of inactivity, select 5, 10, 15, 30 or 60 minutes.
NormalNormal
Network Configuration
Network settings
5.39 PM
Page 1 of 3
IP address
Subnet mask
Gateway
DNS server primary
DNS server secondary
Hostname
Domain name
Enable network
Apply Changes
123.234.123.100
255.255.155.0
123.234.100.1
123.234.100.222
123.234.110.222
company.com
UPS1
123BMS Modbus RTU Address
42 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Bypass SSW Alarms/Troubleshooting
Alarm Types
The color of the top of the screen switches from blue to red when an alarm situation occurs.
Info
Informational Alarm. No immediate need to take action. Check the cause of the alarm at next maintenance visit.
Warning
Minor Alarm. Call Technical Support. The light blue area in the right side of the top of the screen alternates between blue and red.
Severe
Major Alarm. Take immediate action. Call Technical Support. The red area of the top of the screen alternates between blue and red.
Alarm button. Pressing the alarm button will take the user to a screen showing all active alarms and how each alarm should be addressed. The 3 different alarm levels are described below. Hitting the alarm symbol or any other display button will automatically silence the alarm.
Bypass Summary
Bypass Summary
Bypass Summary
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 43
Bypass SSW Alarms/Troubleshooting: Alarm Types
View active alarms
Press the red triangular alarm symbol to view active alarms. Only active alarms will appear on the screen. Pressing the alarm symbol will also mute acoustic alarms.
Previous alarms are stored in the Event Log, which contains a detailed record of the unit’s last 1024 events.
Bypass SSW Alarm Messages/Troubleshooting
Following is a list of alarm messages that may appear in the active alarm screen and/or in the event log. Each alarm type contains a description and the user-action needed to rectify the problem.
Bypass Summary
SeveritySeveritySeveritySeverity Alarm DescriptionAlarm DescriptionAlarm DescriptionAlarm Description Suggested ActionSuggested ActionSuggested ActionSuggested Action Date TimeDate TimeDate TimeDate Time
Download complete
Input frequency is out of toleranceCall APC for Service
09-01-2003 12:43:25.57309-01-2003 12:43:25.570
SevereSevere
Mains Synchronization errorBypass Static Switch fault
NormalAlarm: InfoActive Alarms
2:27 PM
Event Log Refresh
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
Bypass synchronization error.
Bypass input frequency is out of tolerance.
3 Bypass input frequency is out of tolerance.
44.1.1
Bypass voltage low. Bypass voltage is out of tolerance.
3 Bypass voltage too low.
44.2.1
Bypass voltage high. Bypass voltage is out of tolerance.
3 Bypass voltage too high.
44.2.2
Bypass SSW fan weak. A weak fan is approaching failure.
1 Fan is approaching failure.
44.4.1
Replace Bypass SSW fan. Bypass Static Switch fan must be replaced.
2 Call APC for service. 44.4.2
Bypass SSW fan fault. A fan is no longer working.
3 Call APC for service. 44.4.3
44 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Bypass SSW Alarms/Troubleshooting: Alarm Types
Bypass SSW fuse fault. One or more of the bypass fuses are blown.
3 Call APC for service. 44.5.1
Bypass SSW backfeed protection activated.
The Bypass Static Switch Module backfeed protection is activated.
3 Call APC for service . 44.7.1
Bypass SSW PSU fault. Bypass Static Switch Module power supply is failing.
2 Call APC for service. 44.8.1
Bypass SSW fault. BSS Module is not working correctly.
3 Call APC for service. 44.9.1
Bypass SSW temperature fault.
Over temperature of the Bypass Static Switch Module heat sink.
2 Check BSS air filters. 44.10.1
Input frequency fault. Bypass input frequency fault.
3 None. 44.11
Fast error detected. Bypass fast error detected.
3 Call APC for service. 44.12
Bypass operation mode - fault.
Bypass operation mode - fault.
3 Not required. 44.13
Bypass SSW fuse blown. One or more of the External Bypass SSW fuses are blown.
3 Call APC for service. 44.14
Bypass SSW fan CAN I/O board fault.
Error in communication with Bypass Static Switch Module CAN I/O board.
2 Call APC for service. 64.24
Display Message Alarm Description
Alarm Severity0=None1=Info
2=Warning3=Severe
Alarm or User Action Alarm #
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 45
Warranty and Life-Support Policy
Factory Warranty
APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installation or maximum 18 months after manufacturing. In the event that the unit fails to meet the foregoing warranty, APC shall for a period of one (1) year repair or replace any defective parts, without charge for on-site labor and travel if trained & authorized APC personnel has conducted start-up of the unit.
An APC Start-Up Service must be performed/completed by APC or by service personnel authorized by APC. If not, the on-site factory warranty will be voided and replacement of defective parts only will be covered. APC shall have no liability and no obligation to repair the installed unit if non-authorized APC personnel performed the start-up and such start-up caused the unit to be defective.
APC shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by purchaser’s or any third person’s misuse, negligence, improper installation or testing, unauthorized attempts to repair or modify, or any other cause beyond the range of the intended use, or by accident, fire, lightning or other hazard.
There are no warranties, expressed or implied, by operation of law or otherwise, of products sold, serviced or furnished under this agreement or in connection herewithin. APC disclaims all implied warranties of merchantability, satisfaction and fitness for a particular purpose. APC’s express warranties will not be enlarged, diminished, or affected by and no obligation or liability will arise out of, APC rendering of technical or other advice or service in connection with the products. The foregoing warranties and remedies are exclusive and in lieu of all other warranties and remedies. The warranties set forth above, constitute APC’s sole liability and purchaser’s exclusive remedy for any breach of such warranties. APC’s warranties apply only to purchaser and are not extended to any third parties.
In no event shall APC, its officers, directors, affiliates or employees be liable for any form of indirect, special, consequential or punitive damages, arising out of the use, service or installation, of the products, whether such damages arise in contract or tort, irrespective of fault, negligence or strict liability or whether APC has been advised in advance of the possibility of such damages.
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 47
Life-Support Policy for APC 3-Phase Systems
American Power Conversion Corporation (APC) and its affiliates and subsidiaries worldwide do not recommend the use of any of their products in life-support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life-support device or to significantly affect its safety or effectiveness. APC does not permit the use of any of its products in direct patient care. APC will not knowingly sell its products for use in such applications unless the life-support system or direct patient care device is part of a whole facility/building into which the UPS is integrated, and unless APC receives, in writing, assurances satisfactory to APC that:
a. The UPS system will be configured in a manner that will provide N+1 power redundancy to the critical load,
b. The end-user customer assumes all risks and signs the APC System Configuration and Use Form, and
c. The customer and operators of the APC UPS system agree to indemnify and hold APC and its affiliates and subsidiaries harmless for any and all claims arising out of the systems use in such applications.
The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), autotransfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults and infants), anesthesia ventilators, infusion pumps, and any other devices designated as “critical” by the U.S. FDA.
Hospital-grade wiring devices and leakage current protection may be ordered as options on many APC UPS systems. APC does not claim that units with these modifications are certified or listed as hospital-grade by APC or any other organization. Therefore these units do not meet the requirements for use in direct patient care.
48 Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B
Appendix A
Air Filter Exchange
Check air filters at regular intervals (every 3 months under normal working conditions) for accumulated dust on the surface facing the finishing panels. Change all filters at the same time.
Pull upper finishing panel free of the dead front panel.
Lift finishing panel free of the dead front panel and remove.
Follow this procedure to remove the next finishing panel down, until all panels in one row have been removed. Use the same procedure for the next row of panels until all panels have been removed from the UPS system.
Remove the air filter and install the new filter.
Refit finishing panels in reverse order.
Dead front panel
Finishing panel
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 49
Technical Support
Note the UPS serial number ________________________________ before calling technical support.Note
For technical support, call APC at 877-287-7835.
Symmetra® MW with External Bypass Static Switch - User Guide - 990-1377B 51