Upload
rishabh-bhagat
View
51
Download
9
Embed Size (px)
DESCRIPTION
UPS and battery presentation
Citation preview
5/22/2018 Ups & Battery
1/33
5/22/2018 Ups & Battery
2/33
Battery
A batteryis a combination of two or more electrochemicalGalvanic cells which store chemical energy which can beconverted into electric potential energy i.e. electricity.
5/22/2018 Ups & Battery
3/33
A battery is a device that converts chemical energy directlyto electrical energy.
It consists of one or more voltaic cells. Each voltaic cell consists of two half cells connected in
series by a conductive electrolyte. One half-cell is the negative electrode (cathode) and the
other is the positive electrode (anode).
In the redox reaction that powers the battery, reductionoccurs in the cathode, while oxidation occurs in the anode. The electrodes do not touch each other but are electrically
connected by the electrolyte, which can be either solid orliquid.
A voltaic cell for demonstration purposes.
In this example the two half-cells arelinked by a salt bridge separator thatpermits the transfer of ions, but not watermolecules.
Howbatteries work:
http://en.wikipedia.org/wiki/Cathodehttp://en.wikipedia.org/wiki/Image:ElectrochemCell.pnghttp://en.wikipedia.org/wiki/Cathode5/22/2018 Ups & Battery
4/33
Cont..
Each half cell has an electromotive force (emf), determinedby its ability to drive electric current from the interior to theexterior of the cell.
The nett emf of the battery is the difference between theemf,s of its half-cells, as first recognized by Volta a reknown
scientist. Thus, if the electrodes have emf,s and then the nett emf
is, in other words, the nett emf is the difference betweenthe reduction potentials of the half-reactions.
In many cells, the materials are enclosed in a container with
a separator, which is porous to the electrolyte and preventsthe electrodes from coming into contact.
5/22/2018 Ups & Battery
5/33
Conti
The electrical potential difference across the terminals of abattery is known as terminal voltageand is measured in volts.
The terminal voltage of a battery that is neither charging nordischarging is called the open-circuit voltage and equals theemf of the battery.
Because of internal resistance, the terminal voltage of adischarging battery is smaller in magnitude than the open-circuit voltage and the terminal voltage of a battery that is incharging action exceeds the open-circuit voltage.
An ideal battery has negligible internal resistance, so it wouldmaintain a constant terminal voltage until exhausted and thendropping to zero.
If such a battery maintains 1.5 volts and stores a charge ofone Coulomb then it would perform 1.5 Joule of work.
In practical batteries, the internal resistance will increase as itis discharged, and the open circuit voltage will also decreaseas the cell is discharged.
5/22/2018 Ups & Battery
6/33
Conti
If the voltage and resistance are plotted against time, theresulting graphs will typically not be a straight line, and theshape of the curve will vary with the chemical and the internalarrangement employed.
The voltage developed across a cell terminals depends on thechemicals used in it and their respective concentrations.
For example, alkaline and carbon-zinc cells both measureapproximately 1.5 volts, due to the energy release of theassociated chemical reactions.
Because of the high electrochemical potential changes in thereactions of lithium compounds, lithium cells can provide asmuch as 3 volts or more.
5/22/2018 Ups & Battery
7/33
Battery capacity and discharging
The more electrolyte and electrode material is there in thecell, the greater the capacity of the cell.
Thus a small cell has less capacity than a larger cell, giventhe same chemistry (e.g. alkaline cells), though they developthe same open-circuit voltage.
Because of the chemical reactions within the cells, thecapacity of a battery depends on the discharge conditionssuch as the magnitude of the current, the duration of thecurrent, the allowable terminal voltage of the battery,temperature and other factors.
The available capacity of a battery depends upon the rate atwhich it is discharged. If a battery is discharged relatively ata high rate, the available capacity will be lower thanexpected.
5/22/2018 Ups & Battery
8/33
The battery capacity that a battery manufacturers print on abattery, is the product of 20 hours multiplied by themaximum constant current that a new battery can supply for20 hours at 68 F (20 C), down to a predetermined terminal
voltage per cell. A battery rated at 100 Ah will deliver 5 A over 20 hour period
at room temperature.
However, if it is discharged at 50 A, it will run out of chargebefore the 2 hours as theoretically expected.
For this reason, a battery capacity rating is always related toan expected discharge duration.
Where
Qis the battery capacity (typically given in mAh). Iis the current drawn from battery (mA).
tis the amount of time (in hours) that a battery cansustain
5/22/2018 Ups & Battery
9/33
The relationship between current, discharge time, and capacityfor a lead acid battery is expressed by Peukert's law.
Theoretically, a battery should provide the same amount of
energy regardless of the discharge rate, but in real, batteriesinternal energy losses causes the efficiency of a battery at adifferent discharge rates.
When discharging at low rate, the battery's energy is deliveredmore efficiently than at higher discharge rates.
In general, the higher the ampere-hour rating, the longer thebattery will last for a particular load.
Installing batteries with different Ah ratings will not affect theoperation of a device rated for a specific voltage unless theload limits of the battery are exceeded.
Theoretically, a battery would operate at its Ah rating, butrealistically, high-drain loads like digital cameras can result inlower actual energy, most notably for alkaline batteries.
For example, a battery rated at 2000 mAh may not sustain acurrent of 1 A for the full two hours.
5/22/2018 Ups & Battery
10/33
VRLA BATTERY
VRLAstands for valve regulated lead acidand is the designationfor low maintenance lead-acid batteries, also called recombinantbatteries. VRLA batteries are commonly further classified as:Absorbent glass mat batteryGel battery
http://en.wikipedia.org/wiki/Lead-acid_batteryhttp://en.wikipedia.org/wiki/Lead-acid_batteryhttp://en.wikipedia.org/wiki/Lead-acid_batteryhttp://en.wikipedia.org/wiki/Lead-acid_battery5/22/2018 Ups & Battery
11/33
5/22/2018 Ups & Battery
12/33
VRLA (valve regulated lead acid)BATTERY
Manufactured in multi-cell blocks (called modules).
The cases are often made of ABS plastic material that do notpermit visual inspection of plates/ electrolyte levels.
The hydrogen & oxygen are not expelled but recombined.
Cells are sealed & require no water addition and specificgravity readings.
These cells are typically lead calcium pasted-plate type cellswith the electrolyte retained in gel fiberglass mats.
These cells are not flooded & dont effectively dissipate heat.
Maintaining the cells as close as possible to 77F is imperative.
Dont allow sunlight or other heat sources to rise the temp. ofindividual cells.
5/22/2018 Ups & Battery
13/33
Conti
These batteries are normally used for emergency lighting,telecommunication & other uninterrupted power supply service.
VRLA modules/ cells are typically shipped fully charged & dontrequire initial charge.
5/22/2018 Ups & Battery
14/33
Guidelines for maintenance of batteries
The points to be observed during the inspections are
summarized as below-
General conditions of battery room and cells
Specific gravity of electrolyte in the cells
Charging current
Cell voltage
Condition of the plates and extent of deposits
Inter-cell connectors and main battery terminals
5/22/2018 Ups & Battery
15/33
Specific gravity
Specific gravity is related to electrolyte temperature.
Should be maintained at about 1.210 at 27 degree C & when itdrops to 1.150 the cell may be considered as discharged.
Temperature correction hydrometer readings of specific gravityshall be made as follows-
a). For each 1 degree C above 27 degree C add 0.007 to theobserved readings
b). For 1 degree C below 27 degree C deduct 0.007 from theobserved readings.
5/22/2018 Ups & Battery
16/33
Pilot cells
One of the cells in each row of the battery set should beselected and kept as the pilot cell.
Readings should be taken on these cells at a sufficientfrequency to indicate its state of discharge and charge andserve as a guide to the condition of other cells.
The height of electrolyte should invariably be kept at a fixedpoint above top of plates by adding distilled water everyfortnight, if necessary.
5/22/2018 Ups & Battery
17/33
Trickle charging
A long life for battery is achievable if the battery is keptfloating on a battery charger so that the terminal voltage ofeach cell is maintained close to 2.15 v
This can be achieved if the battery is kept on a very low rateof charge, say 1 mA per Ah capacity of the battery.
The exact rate of charge should be fixed having regard tonormal and intermittent rates of discharge over a period of 24hours, so that the battery is always kept in fully chargedcondition and never overcharged or over-discharged.
5/22/2018 Ups & Battery
18/33
Cell voltage The voltage of cell at the end of charging is not fixed value
but will vary depending on the age of battery.
No cells should ever be discharged below the point where thecell voltage reaches 1.85 V as measured when the cell isdischarged at normal 10 hour rate.
Sulphated plates, lug corrosion, partial short circuit due tocracked separators & other defects of cell causes a noticeable
drop in terminal voltage with current flowing in the cell.
This drop varies with amount of current flowing and in orderto get voltages that can be compared from month to month,the voltages should be taken with same current flowing in thecell.
The cell testing voltmeters in use should be periodicallychecked and recalibrated, if necessary. When not in use theyshould be kept in safe place.
5/22/2018 Ups & Battery
19/33
Condition of plates & deposits Examine carefully the physical condition of the plates such as
cracks, distortions, accumulation of whitish deposits etc.
In healthy cells, deposit is brown in color but excessiveshedding of active material on positive plates indicates overcharging of battery. If this is noticed, reduce the charging rateimmediately.
If all cells shows whitish deposits immediate action should be
taken to give a boost charge at an appropriate rate & then toincrease the trickle charging rate sufficiently to keep thebattery in healthy condition at all time.
Weak cell should be immediately examined for any possibleshort circuit or metallic contact between positive & negative
plates. The short circuit should be removed and the cell should then
be given special additional charging by cutting it out andputting it back again when a healthy condition is regained,after it is attended to.
5/22/2018 Ups & Battery
20/33
Inter-cell connections The inter-cell connectors of the battery should be examined to
ensure that they are clean & tight, making perfect contact with
cell lugs and there is no corrosion taking place. Light vaiseline should be applied to prevent corrosion.
Inspection of copper inter-row connectors should also be madefor any signs of copper sulphate corrosion which should becleaned up.
Acid proof paint or enamel should be applied to all exposedcopper work in the battery room & any flaking of paint workbe given prompt attention.
5/22/2018 Ups & Battery
21/33
Maintenance New Battery Shift Monthly 3-Month 6-Month Annual
Visual
Inspection
General
Inspection
Battery FloatVoltage
Panel MeterFloat
Voltage
Battery FloatVoltage with
Digital Voltmeter
Cell Float
Voltage
All Cells with
Digital
Voltmeter
Pilot Cells with
Digital Voltmeter
All Cells with
Digital
Voltmeter
TemperatureReadings All Cells All Cells
Connection
Resistance
All
Connections
25 Percent
of All
Connections
All
Connections
Internal
Resistance
All Cells All Cells
Battery Testing Acceptance
Capacity
Testing
Capacity Test
6 months if
1-year test
5/22/2018 Ups & Battery
22/33
UPS System
5/22/2018 Ups & Battery
23/33
UPS (Uninterrupted power supply)
Also known as a continuous power supply
(CPS) or a battery backup is a device whichmaintains a continuous supply of electric power tothe connected equipment by supplying power from aseparate source when utility power is not available.
There are 3 distinct UPS systems:-
(a) off-line
(b) Line-interactive(c) On-line
5/22/2018 Ups & Battery
24/33
Common power problemsThere are various common power problems that UPS units are
used to correct. They are as follows:
Power failure
Voltage sag
Voltage spike
Under-voltage
Over-voltage
Line noise
Frequency variation
Switching transient
Harmonic distortion
5/22/2018 Ups & Battery
25/33
(a) Off-line UPS
Offline / standby UPS. Typical protection time: 0 - 20 minutes. Capacityexpansion: Usually not available
5/22/2018 Ups & Battery
26/33
Off-line UPS:-
Remains idle until a power failure occurs, and thenswitches from utility power to its own power source, almostinstantaneously.
An on-line uses are double conversion method ofaccepting AC input, rectifying to DC for passing throughbattery, then inverting back to AC for powering theprotected equipment.
when the incoming utility voltage falls below apredetermined level the UPS turns on its internal DC-ACinverter circuitry, which is powered from an internal storagebattery. The standby system then mechanically switchesthe connected equipment on to its DC-AC inverter out ofpower. The switchover time can be as long as 25 ms.Depending on the amount of time it takes the standby UPSto detect the lost utility voltage.
5/22/2018 Ups & Battery
27/33
(b) Line-interactive
Line-Interactive UPS. Typical protection time: 5 - 30 minutes. Capacity expansion:Several hours
5/22/2018 Ups & Battery
28/33
Line-interactive type:
A line-interactive UPS maintains the inverter in line &
redirects the batterys DC current path from the normalcharging mode to supplying current when power is lost.
The line-interactive UPS is similar in operation to astandby UPS, but with the addition of a multi-tap variable-voltage autotransformer. This is a special type of electrical
transformer that can add or subtract powered coils of wire,thereby increasing or decreasing the magnetic field & the output voltage of the transformer.
This type of UPS is able to tolerate continuous undervoltage brownouts & over voltage surges without consuming
the limited reverse battery power.
5/22/2018 Ups & Battery
29/33
(c)Double conversion / on-line UPS
5/22/2018 Ups & Battery
30/33
Double conversion / online:
The On-line UPS is ideal for environments where electrical
isolation is necessary for equipment that is very sensitive topower fluctuations.
It is called a Double-Conversion UPSdue to the rectifierdirectly driving the inverter, even when powered from normalAC current.
In an On-line UPS, the batteries are always connected tothe inverter, so that no power transfer switches are necessary.When power loss occurs, the rectifier simply drops out of thecircuit & the batteries keep the power steady & unchanged.When power is restored, the rectifier resumes carrying most of
the load & begins charging batteries, through the chargingcurrent may be limited to prevent the high-power rectifierfrom overheating the batteries & boiling off the electrolyte.
The main advantage to the on-line UPS is its ability toprovide an electrical firewall b/w the incoming utility power &
sensitive electronic equipment.
5/22/2018 Ups & Battery
31/33
UPS System Maintenance Periodic maintenance is extremely important to UPS
systems, as its reliability is crucial for the reliability
of the system it is supporting.
The small periodic time investment to checkbatteries, connections, fans, relays and sensors iswell spent compared to damage or lost data and
broken hardware after a power disturbance revealsa dead UPS system.
Records indicates that a properly maintained batterybackup system will last an average of five years.
Some units may fail because of lack of batterymaintenance, blocked air filters and fan failures.
Poor battery connections, dirt and dust within theunit also cause of premature failure and unexpected
added expenses.
5/22/2018 Ups & Battery
32/33
The single most expensive scheduled item on a UPS(other than initial purchase) is battery replacement.
UPSs can be equipped with maintenance-freecapacitors to extend service life.
5/22/2018 Ups & Battery
33/33