Upgrading Existing ChW Systems

Embed Size (px)

Citation preview

  • 8/13/2019 Upgrading Existing ChW Systems

    1/68

    2008 Trane

    2010 Trane

    Upgrading ExistingChilled-Water

    Systems

    Kevin Rice, ComprehensiveSolutions Account Executive

  • 8/13/2019 Upgrading Existing ChW Systems

    2/68

    2010 Trane

    Existing Buildings Gordon Holness, 2009 ASHRAE President*

    75% to 85% of all the buildings that willexist in urban areas in 2030 exist today.

    Energy efficiency in existing buildings ourgreatest opportunity for a sustainablefuture.

    we can sustain our future by rebuildingour past.

    *Presidential address, June 2009

  • 8/13/2019 Upgrading Existing ChW Systems

    3/68

    2010 Trane

    Business Climate Budgets

    Capital budgets limited, meet ROI

    Pressure to reduce operating costs

    Maintenance

    Deferred (ignored?)

    Enhanced to keep equipment workinglonger

    Sustainability reduce energy use

  • 8/13/2019 Upgrading Existing ChW Systems

    4/68

    2010 Trane

    Upgrade Goals Use existing equipment and infrastructure

    whenever possible

    Reduce energy use but not at theexpense of comfort or the process

    Show internal rate of return consistentwith present internal requirements

  • 8/13/2019 Upgrading Existing ChW Systems

    5/68

    2010 Trane

    The Building HVACSystem

  • 8/13/2019 Upgrading Existing ChW Systems

    6/68

    2010 Trane

    Chilled-Water System

    pumpcoil

    controlvalve

    air-cooledchiller

  • 8/13/2019 Upgrading Existing ChW Systems

    7/68

    2010 Trane

    Existing Chilled-WaterSystems

    Chiller

    Pumps and pipes

    Chilled waterCondenser water

    Cooling towers and fans

    System controls

    Pictures

    http://localhost/var/www/apps/conversion/tmp/scratch_3/Pictureshttp://localhost/var/www/apps/conversion/tmp/scratch_3/Pictures
  • 8/13/2019 Upgrading Existing ChW Systems

    8/68

    2010 Trane

    Chiller Products

  • 8/13/2019 Upgrading Existing ChW Systems

    9/68

    2010 Trane

    Upgrade options

    Change the Chiller

    Retrofit

    Replace

    Select different design parameters

    Change system configuration

    Enhance controls

  • 8/13/2019 Upgrading Existing ChW Systems

    10/68

    2010 Trane

    Chiller Upgrade Options

    Comply with ASHRAE 90.1

    Add a variable speed drive

    Replace the chiller

    Size the new chiller properly

    Compare same-price new chiller options

    Variable speed drive

    High efficiency

  • 8/13/2019 Upgrading Existing ChW Systems

    11/68

    2010 Trane

    ASHRAE 90.1

    Two Paths in 90.1-2010

    Once a path is chosen, both full and part loadrequirements must be met

    Positive displacement chillers evaluated only atAHRI Standard 550/590 standard conditions

    Chilled water: 44F leaving, 2.4 gpm/ton

    Condenser water: 85F entering, 3.0 gpm/ton

    Centrifugal chiller requirements must be adjustedfor non-standard conditions

  • 8/13/2019 Upgrading Existing ChW Systems

    12/68

    2010 Trane

    ASHRAE 90.1Air-cooled Chillers

    Capacity

    (tons)

    2007 2010 Path A 2010 Path B

    Full

    Load

    IPLV Full

    Load

    IPLV Full

    Load

    IPLV

  • 8/13/2019 Upgrading Existing ChW Systems

    13/68

    2010 Trane

    ASHRAE 90.1Water-cooled positive Displacement Chillers

    Capacity

    (tons)2007 2010 Path A 2010 Path B

    Full

    Load

    IPLV Full

    Load

    IPLV Full

    Load

    IPLV

  • 8/13/2019 Upgrading Existing ChW Systems

    14/68

    2010 Trane

    ASHRAE 90.1Water-cooled Centrifugal Chillers

    Centrifugal chiller requirements must be adjusted for non-standardconditions

    All requirements in kW/ton.

    Chiller performance must be less than or equal to the requirements inthe table

    Capacity

    (tons)

    2007 2010 Path A 2010 Path B

    Full

    Load

    IPLV Full

    Load

    IPLV Full

    Load

    IPLV

  • 8/13/2019 Upgrading Existing ChW Systems

    15/68

    2010 Trane

    Chiller Upgrade Options

    Comply with ASHRAE 90.1

    Add a variable speed drive

    Replace the chiller

    Size the new chiller properly

    Compare same-price new chiller options

    Variable speed drive

    High efficiency

  • 8/13/2019 Upgrading Existing ChW Systems

    16/68

    2010 Trane

    Overhauled Chillers

  • 8/13/2019 Upgrading Existing ChW Systems

    17/68

    2010 Trane

    Adding a VSD to anExisting Chiller

    Comply with ASHRAE 90.1 requirementsfor retrofits

    Ensure that modification will not result in anincrease in annual energy consumption

    Understand how a drive may benefitchiller performance

    Perform return on investment analysis

  • 8/13/2019 Upgrading Existing ChW Systems

    18/68

    2010 Trane

    Drive impact on existingchiller performance

    Demand rises 2-4% at design conditions

    Largest benefit at lower condenser water

    temperatures

  • 8/13/2019 Upgrading Existing ChW Systems

    19/68

    2010 Trane

    2006AmericanStand

    ardInc.

    Lift versus Load

    lift

    lvg evaporator water

    lvg condenser water

    lift PcndPevp

    lift Tlvg cndTlvg evp

    load gpm (Tent evpTlvg evp)

    800 gpm

    load = 500 tons

    2 gpm/ton

    58F(T)

  • 8/13/2019 Upgrading Existing ChW Systems

    20/68

    2010 Trane

    compressorwork

    2006AmericanStand

    ardInc.

    Compressor Work and Chiller Efficiency

    cooling capacity/load

    head/li

    ft

    lvg evapwater

    lvg cond

    water

    500 tons

    58F

  • 8/13/2019 Upgrading Existing ChW Systems

    21/68

    2010 Trane

    Lessons Learned

    To reduce lift:

    Decrease condenserpressure by reducingleaving-tower water

    temperature

    Increase evaporatorpressure by raisingchilled water setpoint

    VSDs optimize chiller liftefficiency 41Flvg evap

    water

    lvg condwater

    45F

    73F

    99F

    compressorwork

  • 8/13/2019 Upgrading Existing ChW Systems

    22/68

    2010 Trane

    Drive impact on existingchiller performance

    700-Ton Chiller VSD Retrofit

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 200 400 600 800

    Tons

    kW

    Existing-85F

    VSD-Retrofit-85F

    Existing-75F

    VSD-Retrofit-75F

    Existing-65F

    VSD-Retrofit-65F

    No savings at constant ECWT

    Savings at reduced ECWT

  • 8/13/2019 Upgrading Existing ChW Systems

    23/68

    2010 Trane

    Drive Retrofit:Issues to consider

    Utility rates? DemandCharge? Ratchet?

    VSD adds inefficiency

    If chiller was oversized the demandmay be lower

    How often will it operateat advantageousconditions?

    24/7 operation may be beneficial

    Economizer reduces the loads atadvantageous conditions

    How much energy isconsumed by the coolingtower?

    Need to balance tower and chillerenergy

    Is the chiller oversized forthe load?

    Load reduction in conjunction withreduced CW temperatures may offersignificant savings

  • 8/13/2019 Upgrading Existing ChW Systems

    24/68

  • 8/13/2019 Upgrading Existing ChW Systems

    25/68

    2010 Trane

    Chiller Plant Analyzer

  • 8/13/2019 Upgrading Existing ChW Systems

    26/68

    2010 Trane

    Chiller Upgrade Options

    Comply with ASHRAE 90.1

    Add a variable speed drive

    Replace the chiller

    Size the new chiller properly

    Compare same-price new chiller options

    Variable speed drive

    High efficiency

  • 8/13/2019 Upgrading Existing ChW Systems

    27/68

    2010 Trane

    Chiller Replacement

    Correctly size the new chiller

    Determine actual building load

    Downsize chiller if possible

    If more tonnage is needed, higher efficiencyallows present electrical system to serve

    Replace with higher efficiency chiller

    Reduce demand and consumption

    Constant speed or variable speed?

  • 8/13/2019 Upgrading Existing ChW Systems

    28/68

    2010 Trane

    Chiller Replacement:Constant or Variable Speed?

    Different than retrofit where only VSDmakes economic sense

    Compare same price VSD chiller andhigher full load efficiency chiller

    Make sure each chiller meets ASHRAE 90.1full and part-load requirements

    Use comprehensive analysis to determinewhich to purchase

  • 8/13/2019 Upgrading Existing ChW Systems

    29/68

  • 8/13/2019 Upgrading Existing ChW Systems

    30/68

    2010 Trane

    Same-price Chiller:Example Performance

    600-ton Replacement Chiller Performance

    0

    50

    100

    150

    200

    250

    300

    350

    400

    0% 20% 40% 60% 80% 100%

    % Load

    kW

    High_efficiency_85F

    VSD_85F

    High_efficiency_75F

    VSD_75F

    High_efficiency_65F

    VSD_65F

  • 8/13/2019 Upgrading Existing ChW Systems

    31/68

  • 8/13/2019 Upgrading Existing ChW Systems

    32/68

    2010 Trane

    Guidance:VSD or High Efficiency?

    High efficiency

    Significant demandcharges

    Humid climates

    Multiple chillers in theplant

    Economizer that

    reduces low load/lowlift operating hours

    VSD

    Many hours at lowcondenser water

    temperature and lowload

    Perhaps only on onechiller

    Factor in replacement

    of VSD whenperforming life cycleassessment

  • 8/13/2019 Upgrading Existing ChW Systems

    33/68

    2010 Trane

    Upgrade options

    Change the Chiller

    Retrofit

    Replace

    Change design parameters

    Change system configuration

    Enhance controls

  • 8/13/2019 Upgrading Existing ChW Systems

    34/68

    2010 Trane

    chilled water plant design

    ProvocationAre our rules of thumb

    44 F chilled water supply

    10 F T for chilled water system

    3 gpm/ton condenser water flow

    in need of repair?

  • 8/13/2019 Upgrading Existing ChW Systems

    35/68

    2010 Trane

    Design Parameters

    Many chilled watersystems selected at:

    Chilled water

    44F 2.4 gpm/ton (10F T)

    Condenser water

    85F Entering

    3 gpm/ton (9.4F T)

    ASHRAE GreenGuideGuidance

    Chilled water

    12F to 20F T 2.0 to 1.2 gpm/ton

    Condenser water

    12F to 18F T

    2.5 to 1.6 gpm/ton

  • 8/13/2019 Upgrading Existing ChW Systems

    36/68

    2008 Trane

    High PerformanceDesign Parameters

    Kelly and Chan

    Chilled water DT: 18F

    Condenser water DT: 14.2F

    (3.6 - 8.3% energy savings in variousclimates)

  • 8/13/2019 Upgrading Existing ChW Systems

    37/68

    2008 Trane

    a history of

    Chiller Performance8.0

    ASHRAE Standard 90

    ch

    illerefficiency

    ,COP

    6.0

    4.0

    2.0

    0.0NBI best

    available90-75(1977)

    90-75(1980)

    90.1-89 90.1-99

    centrifugal>600 tons

    screw150-300 tons

    scroll

  • 8/13/2019 Upgrading Existing ChW Systems

    38/68

    2008 Trane

    Efficiency changesin the past 35 years

    Chiller COP increased up to 75%

    Pumps? motors more efficient

    Cooling towers? motors more efficient,fill design has changed

  • 8/13/2019 Upgrading Existing ChW Systems

    39/68

    2008 Trane

    Retrofit applicationsand reduced flow - evap

    Chilled water side

    Coil

    Its a simple heat transfer device

    Reacts to colder entering waterby returning it warmer

    Ideal for system expansion

  • 8/13/2019 Upgrading Existing ChW Systems

    40/68

  • 8/13/2019 Upgrading Existing ChW Systems

    41/68

    2010 Trane

    Retrofit applicationsand reduced flow - cond

    Condenser side retrofit opportunity

    Chiller needs to bereplaced

    Cooling needs haveincreased by 50%

    Cooling tower wasreplaced two years ago

    Condenser pump andpipes are in good shape

  • 8/13/2019 Upgrading Existing ChW Systems

    42/68

    2010 Trane

    Retrofit applicationsand reduced flow - cond

    Existing Retrofit

    Capacity (tons) 500 750

    Flow rate (gpm) 1500 1500Condenser Entering Water

    Temperature (F)

    85 88

    Condenser Leaving Water

    Temperature (F)

    95 103

    Design Wet Bulb (F) 78 78

  • 8/13/2019 Upgrading Existing ChW Systems

    43/68

    2010 Trane

    Upgrade options

    Change the Chiller

    Retrofit

    Replace

    Change design parameters

    Change system configuration

    Enhance controls

  • 8/13/2019 Upgrading Existing ChW Systems

    44/68

    2010 Trane

    Variable Primary FlowSystems

  • 8/13/2019 Upgrading Existing ChW Systems

    45/68

    2010 Trane

    VPF System RetrofitBenefits

    Reduced pumping costs

    Ability to respond to Low T Syndrome

  • 8/13/2019 Upgrading Existing ChW Systems

    46/68

    2010 Trane

    Flow requirementsVPF System

    Limits (consult manufacturer)

    Absolute flows - Minimum and maximum

    Always need a method to allow minimum flow(bypass)

    Flow rate changes 2% of design flow per minute

    not good enough

    10% of design flow per minute borderline 30% of design flow per minute

    many comfort cooling applications

    50% of design flow per minutebest

  • 8/13/2019 Upgrading Existing ChW Systems

    47/68

    2010 Trane

    Chiller Control

    Variable Water Flow

    30

    40

    50

    60

    70

    80

    90

    100

    110

    120

    130

    3:50:00 3:55:00 4:00:00 4:05:00 4:10:00

    Time (hour:min:sec)

    WaterTemp[degF]

    -500

    -300

    -100

    100

    300

    500

    700

    900

    1100

    1300

    1500

    Flow[gpm]Evaporator Water Flow

    Evap Entering Water Temp

    Evap Leaving Water Temp

  • 8/13/2019 Upgrading Existing ChW Systems

    48/68

    2010 Trane

    Specify and install properflow control devices

  • 8/13/2019 Upgrading Existing ChW Systems

    49/68

    2010 Trane

    Conversion: Constantto Variable Flow

    Confirm existing chillers and controls canoperate with variable evaporator flow

    Ensure evaporator flow rate can stayabove minimum

    New bypass or 3-way valves

    Ensure flow rate changes are belowallowable chiller allowances

  • 8/13/2019 Upgrading Existing ChW Systems

    50/68

  • 8/13/2019 Upgrading Existing ChW Systems

    51/68

    2010 Trane

    Convert Primary Secondaryto Variable PrimaryVariable Secondary

    Placeholder for

    Manifolded P-S

    System picture

    (Beth to supply)

    VFDs

    T

    DP

    DP

  • 8/13/2019 Upgrading Existing ChW Systems

    52/68

    2010 Trane

    More informationVPF System

    Http:/trane.com/commercial/library/newsletters.asp (1999 and 2002)

    Dont Ignore Variable Flow, Waltz, Contracting

    Business, July 1997

    Primary-Only vs. Primary-Secondary Variable FlowSystems, Taylor, ASHRAE Journal, February 2002

    Comparative Analysis of Variable and ConstantPrimary-Flow Chilled-Water-Plant Performance,Bahnfleth and Peyer, HPAC Engineering, April 2001

    Campus Cooling: Retrofitting Systems,Kreutzmann, HPAC Engineering, July 2002

  • 8/13/2019 Upgrading Existing ChW Systems

    53/68

    2010 Trane

    Upgrade options

    Change the Chiller

    Retrofit

    Replace

    Change design parameters

    Change system configuration

    Enhance controls

  • 8/13/2019 Upgrading Existing ChW Systems

    54/68

    2010 Trane

    Control Options

    Proper number of chillers

    Pump control

    Chiller-tower optimization

  • 8/13/2019 Upgrading Existing ChW Systems

    55/68

    2010 Trane

    Number of chillersoperating

    Operate one at nearly full load or two atpart load?

    Examine IPLV assumptions

  • 8/13/2019 Upgrading Existing ChW Systems

    56/68

    2010 Trane

    VSDs and centrifugal chillers

    A Closer Look at IPLV

    VSDs improve part-lift performance, so running two chillerswith VSDs at part load seems more efficient than one chiller atdouble the same load, but is dependent on condenser watertemperature

    Load ECWTWeighting kW/Ton

    100% 0.01 85F 0.572

    75% 0.42 75F 0.420

    50% 0.45 65F 0.308

    25% 0.12 65F 0.372

  • 8/13/2019 Upgrading Existing ChW Systems

    57/68

    2010 Trane

    Chiller power only

    45% Plant load

  • 8/13/2019 Upgrading Existing ChW Systems

    58/68

    2010 Trane

    Chillers plus pumps

    45% Plant load

  • 8/13/2019 Upgrading Existing ChW Systems

    59/68

  • 8/13/2019 Upgrading Existing ChW Systems

    60/68

    2010 Trane

    Chilled Water PumpControl

    Valve positionPump

    Pressure

    Sensor

    Communicating

    BASPump Speed

    pump-pressure optimization

  • 8/13/2019 Upgrading Existing ChW Systems

    61/68

    2010 Trane

    Position (% open)

    of critical valve

    75%

    65%

    Increase pump static pressure setpoint

    Reduce pump static pressure setpoint

    No action

    p p p p

    Control Logic90.1-2007 Addendum ak

    This will be required for many systems by 90.1-2010

  • 8/13/2019 Upgrading Existing ChW Systems

    62/68

    2010 Trane

    optimal condenser water control

    ChillerTower Interaction

    condenser water temperature, F

    400

    74

    energyconsumption,

    kW

    76 78 80 8272

    300

    200

    100

    084

    tower

    chiller

    total

    optimalcontrol point

  • 8/13/2019 Upgrading Existing ChW Systems

    63/68

    2010 Trane

    chillertower optimization

    An Example

    720,000 ft hotel

    2 chillers, 2 tower cells

    Control strategies Make leaving-tower water cold

    as possible (55F)

    Optimize system operation

    Entering-condenser setpointequals design 85F for humid climates,80F for dry climates

  • 8/13/2019 Upgrading Existing ChW Systems

    64/68

    2010 Trane

    chillertower control strategies

    North America350K

    annu

    aloperatingcost,

    $USD

    300K

    250K

    200K

    150K

    100K

    50K

    0Mexico City Orlando San Diego Toronto

    55F lvg tower

    optimal control

    design ECWT

    control strategy:

  • 8/13/2019 Upgrading Existing ChW Systems

    65/68

    2010 Trane

    annu

    aloperatingcost,

    $USD

    500K

    400K

    300K

    200K

    100K

    0Dubai Paris Sao Paulo Singapore

    55F lvg tower

    optimal control

    design ECWT

    control strategy:

    chillertower control strategies

    Global Locations

  • 8/13/2019 Upgrading Existing ChW Systems

    66/68

    2010 Trane

    chillertower optimization

    Operating Cost Savings

    operatingcostsavin

    gs,chiller

    +tow

    erannualcosts,

    %

    14

    0

    12

    10

    8

    6

    4

    2

    location

    Dubai

    Paris

    SaoPa

    ulo

    Singap

    ore

    Mexico

    City

    Orland

    o

    SanDiego

    Toront

    o

  • 8/13/2019 Upgrading Existing ChW Systems

    67/68

    2010 Trane

    Upgrading chilledwater systems

    Retrofit or replacechiller

    Comply with 90.1requirements

    Consider same-pricehigh efficiencyreplacement

    Select different designparameters

    Reduce flow rates byincreasing T

    Chilled water

    Condenser water

    Consider VPF

    Update controls

    Number of chillers

    operating

    Pump pressureoptimization

    Chiller-tower

    optimization

    Perform analysis

  • 8/13/2019 Upgrading Existing ChW Systems

    68/68

    References

    Upgrading Chilled-Water Systems,ASHRAE Journal, November 2009.