UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance) This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes. * Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer OWNER'S OPERATION AND INSTALLATION MANUAL CGG2618P, CGG3324P(T), and CGG3630P Thermostat and Variably-Controlled Models WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. m Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. -- WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your build- ing. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you cannot reach your gas sup- plier, call the fire department. -- Installation and service must be per- formed by a qualified installer, service agency, or the gas supplier. WARNING: Improper installation, adjust- ment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installa- tion and operational procedures. For assistance or additional information con- sulta qualified installer, service agency, or the gas supplier. WARNING: This gas log set is for instal- lation in a masonry solid fuel burning fireplace, a U.L. listed manufactured solid fuel burning fireplace or an AGA design certified vent-free firebox listed for use with these gas log models (in- cluding CGFB32NC and CGFB32C). WARNING: This is an unvented gas- fired heater. It uses air (oxygen) from the room in which it is installed. Provi- sions for adequate combustion and ven tilation air must be provided. Refer to Air for Combustion and Ventilation sec- tion in this manual. Save this manual for future reference.

UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

Embed Size (px)

Citation preview

Page 1: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE)PROPANE/LP GAS LOG HEATER

(Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

This appliance may be installed in an aftermarket* manufactured (mobile) home, wherenot prohibited by state or local codes.

* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer

OWNER'S OPERATION AND INSTALLATION MANUAL

CGG2618P, CGG3324P(T), and CGG3630PThermostat and Variably-Controlled Models

WARNING: If the information in this

manual is not followed exactly, a fire orexplosion may result causing propertydamage, personal injury, or loss of life.

m Do not store or use gasoline or otherflammable vapors and liquids in the

vicinity of this or any other appliance.

-- WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.• Do not touch any electrical switch;

do not use any phone in your build-ing.

• Immediately call your gas supplierfrom a neighbor's phone. Follow thegas supplier's instructions.

• If you cannot reach your gas sup-plier, call the fire department.

-- Installation and service must be per-formed by a qualified installer, serviceagency, or the gas supplier.

WARNING: Improper installation, adjust-ment, alteration, service, or maintenancecan cause injury or property damage.Refer to this manual for correct installa-tion and operational procedures. Forassistance or additional information con-

sulta qualified installer, service agency,or the gas supplier.

WARNING: This gas log set is for instal-lation in a masonry solid fuel burningfireplace, a U.L. listed manufacturedsolid fuel burning fireplace or an AGAdesign certified vent-free firebox listedfor use with these gas log models (in-cluding CGFB32NC and CGFB32C).

WARNING: This is an unvented gas-fired heater. It uses air (oxygen) fromthe room in which it is installed. Provi-sions for adequate combustion and ventilation air must be provided. Refer toAir for Combustion and Ventilation sec-tion in this manual.

Save this manual for future reference.

Page 2: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

SAFETYINFORMATION

WARNINGS

IMPORTANT: Read this owner'smanual carefully and completelybefore trying to assemble,operate, or service this heater.Improper use of this heater cancause serious injury ordeath fromburns, fire, explosion, electricalshock, and carbon monoxidepoisoning.

DANGER: Carbon monoxide

poisoning may lead to death!

Carbon Monoxide Poisoning: Early signsof carbon monoxide poisoning resemble theflu, with headaches, dizziness, or nausea. Ifyou have these signs, the heater may not beworking properly. Get fresh air at once!Have heater serviced. Some people are moreaffected by carbon monoxide than others.These include pregnant women, people withheart or lung disease or anemia, those underthe influence of alcohol, and those at highaltitudes.

Propane/LP Gas: Propane/LP gas is odor-less. An odor-making agent is added to thegas. The odor helps you detect a gas leak.However, the odor added to the gas can fade.Gas may be present even though no odorexists.

Make certain you read and understand allWarnings. Keep this manual for reference.It is your guide to safe and proper operationof this heater.

AaIWARNING: Any change to thisheater or its controls can be dan-

gerous.

1. This appliance is only for use with thetype of gas indicated on the rating plate.This appliance is not convertible for usewith other gases.

2. Do not place propane/LP supply tank(s)inside any structure. Locate propane/LPsupply tank(s) outdoors.

3. If you smell gas

• shut off gas supply

• do not try to light any appliance• do not touch any electrical switch; do

not use any phone in yourbuilding

• immediately call your gas supplierfrom a neighbor's phone. Follow thegas supplier's instructions

• if you cannot reach your gas supplier,call the fire department

4. This heater shall not be installed in a

bedroom or bathroom (except in ventedinstallation, see page 10).

5. Never install the heater• in a recreational vehicle

• where curtains, furniture, clothing, orother flammable objects are less than36 inches from the front, top, or sidesof the heater

• in nigh traffic areas• in windy or drafty areas

6. Before installing in a solid fuel burningfireplace, the chinmey flue and fireboxmust be cleaned of soot, creosote, ashesand loose paint by a qualified chimneycleaner. Creosote will ignite if highlyheated. Inspect chimney flue fordamage. If damaged, operate heaterwith flue damper closed.

7. If fireplace has glass doors, neveroperate this heater with glass doorsclosed. If you operate heater with doorsclosed, heat buildup inside fireplacewill cause glass to burst. Also iffireplace opening has vents at thebottom, you must open the vents beforeoperating heater.

8. You must operate this heater with afireplace screen in place. Make surefireplace screen is closed beforerunning heater.

9. This log heater is designed to besmokeless. If logs ever appear tosmoke, turn off heater and call aqualified service person. Note: Duringinitial operation, slight smoking couldoccur due to log curing and heaterburning manufacturing residues.

10. Do not allow fans to blow directly intothe fireplace. Avoid any drafts that alterburner flame patterns. Ceiling fans cancreate drafts that alter burner flame

patterns. Altered burner patterns cancause sooting.

11. Do not use a blower insert, heatexchanger insert or other accessory not

12.approved for use with this heater.

This heater needs fresh, outside airventilation to mn properly. This heaterhas an oxygen depletion sensor (ODS)pilot light safety system. The ODSshuts down the heater if not enoughfresh air is available. See Air forCombustion atul Ventilation, pages 4through 6. If heater keeps shutting off,see Troubleshooting, pages 19 through21.

13. Do not run heater

• where flammable liquids or vaporsare used or stored

• under dusty conditions

14. Do not use this heater to cook food orbum paper or other objects.

15. Never place any objects on the heater.

16. Heater base assembly becomes very hotwhen running heater. Keep children andadults away from hot surface to avoidbums or clothing ignition. Heater willremain hot for a time after shutdown.

Allow surface to cool before touching.

17. Carefully supervise young childrenwhen they are in the room with heater.

18. Do not use heater if any part has beenexposed to or under water. Immediatelycall a qualified service technician toinspect the room heater and to replaceany part of the control system and anygas control which has been under water.

19. Do not operate heater if any log isbroken. Do not operate heater if a logis chipped (dime-sized or larger).

20. Turn heater off and let cool before

servicing. Only a qualified serviceperson should service and repair heater.

21. Operating heater above elevations of4,500 feet could cause pilot outage.

22. To prevent performance problems, donot use propane tank of less than100 lbs. capacity.

Page 3: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

" OWNER'S MANUAL

PRODUCTIDENTIFICATION

Bottom MidLog (#2)

FrontBurner

PiezoIgnitor

Front Log (#3)

Control Knob

Top Log (#4) Rear Log (#1)

RearBurner

'_ Base Assembly

PRODUCTFEATURESOperation

This heater is clean burning. It requires no

outside venting. There is no heat loss out avent or up a chimney. Heat is generated by

both realistic flames and glowing coals.This heater is designed for vent-free opera-tion with flue damperelosed. State and localcodes in some areas prohibit the use of vent-

free heaters. You can operate heater as avented product by opening flue damper.

Safety Pilot

This heater has a pilot with an OxygenDepletion Sensor Shutoff System (ODS).The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts offthe heater if there is not enough fresh air.

Piezo Ignition System

This heater has a piezo ignitor. This systemrequires no matches, batteries, or othersources to light heater.

Figure 1 - Vent-Ft_e Gas Log Heater

LOCAL CODESInstall and use heater with care. Follow alllocal codes. In the absence of local codes,use the latest edition of The National FuelGas Code ANSI Z223, also known as NFPA54*.

*Available from:

American National Standards Institute,Inc.1430 Broadway

New York, NY 10018

National Fire Protection Association, Inc.Batterymarch Park

Quincy, MA 02269

Note: Where listed vented decorative logsare required, thermostat operation is not

permitted.

UNPACKING1. Remove logs and heater base assembly

from carton. Note: Do not pick upheater base assembly by burners. Thiscould damage heater. Always handlebase assembly by grate.

2. Remove all protective packagingapplied to logs and heater for shipment.

3. Check all items for any shippingdamage. If damaged, promptly informdealer where you bought heater.

t_ 3

Page 4: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

SPECIFICATIONSModel CGG3324PT CGG2618P CGG3324P CGG3630P

Btu (Variable) 20,000133,000 16,000/26,000 20,000/33,000 21,500/36,000

Type Gas Propane/LP Only Propane/LP Only Propane/LP Only Propane/LP Only

Ignition Piezo Piezo Piezo Piezo

Manifold Pressure 7.9" W.C. 7.9" W.C. 7.9" W.C. 7.9" W.C.

Inlet Gas Pressure (in. of water)Maximum 14" 14" 14" 14"Minimum* 11" 11" 11" 11"* For purpose of input adjustment

Shipping Weight 38 lbs. 36 lbs. 38 lbs. 40 lbs.

AIR FORCOMBUSTION ANDVENTILATION

_[_ WARNING: This heater shallnot be installed in a confinedspace unless provisions are pro-vided for adequate combustionand ventilation air. Read the fol-lowing instructions to insureproper fresh air for this and otherfuel-burning appliances in yourhome.

Today's homes are built more energy effi-cient than ever. New materials, increasedinsulation, and new construction methodshelp reduce heat loss in homes. Home own-ers weather strip and caulk around windowsand doors to keep the cold air out and thewarm air in. During heating months, homeowners want their homes as airtight as pos-sible.

While it is good to make your home energyefficient, your home needs to breathe. Freshair must enter your home. All fuel-burningappliances need fresh air for proper com-bustion and ventilation.

Exhaust fans, fu:eplaces, clothes dryers, andfuel burning appliances draw air from thehouse to operate. You must provide ad-equate fresh air for these appliances. Thiswill insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATEVENTILATION

The following are excerpts from NationalFuel Gas Code. NFPA 54/ANSI Z223.1,Section 5.3, Air for Combustion and Venti-lation.

All spaces in homes fall into one of the threefollowing ventilation classifications: 1. Un-usually Tight Contruction; 2. UnconfinedSpace; 3. Confined Space.

The information on pages 4 through 6 willhelp you classify your space and provideadequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-

dows may provide enough fresh air for com-bustion and ventilation. However, in build-ings of unusually tight construction, youmust provide additional fresh air.

Unusually tight construction isdefined as construction where:a.walls and ceilings exposed to the

outside atmosphere have acontinuous water vapor retarderwith a rating of one perm (6x10""per pa-sec-m 2) or less withopenings gnsketed or sealed and

b.weather stripping has been addedon openable windows and doorsand

e. caulking or sealants are applied toareas such as joints aroundwindow and door frames, betweensole plates and floors, betweenwall-ceillng joints, between wallpanels, at penetrations forplumbing, electrical, and gas fines,and at other openings.

If your home meets all of the three criteriaabove, you must provide additional freshair. See Ventilation Air From Outdoors,page 6.

If your home does not meet all of the threecriteria above, proceed to page 5.

Confined and Unconfined Space

The National Fuel Gas Code (ANSIZ223.1,1992 Section 5.3) defines a confined spaceas a space whose volume is less than 50cubic feet per 1,000 Btu per hour (4.8 m3perkw) of the aggregate input rating of allappliances installed in that space and anunconfining space as a space whose volumeis not less than 50 cubic feet per 1,000 Btuper hour (4.8 m3per kw) of the aggregateinput rating of all appliances installed in thatspace. Rooms communicating directly withthe space in which the appliances are in-stalled*, through openings not furnishedwith doors, are considered a part of theunconfined space.

* Adjoining rooms are communicating onlyif there are doorless passageways or ventila-tion grills between them.

_WARNING: If thearea inwhich

the heater may be operated issmaller than that defined as anunconfined space, provide ad-equate combustion and ventila-tion air by one of the methodsdescribed in the National FuelGas Code, ANSI Z223.1, 1992,Section 5.3.

4 1o3425

Page 5: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

AIR FORCOMBUSTION ANDVENTILATIONContinued

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you wilt install heater plus any adjoining rooms with doorless passageways or ventilation grills betweenthe rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = cu. ft. (volume of space)

Example: Space size 20ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume ofthe space.

2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

(volume of space) + 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) + 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater Btu/HrGas water heater* Btu/HrGas furnace Btu/Hr

Vented gas heater Btu/HrGas fireplace logs Btu/HrOther gas appliances* + Btu/HrTotal = Btu/Hr

Example: Gas water heater 40,000 Btu/HrVent-free heater + 33,000 Btu/Hr

Total = 73,000 Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4. Compare the maximum Btu/I-Ir the space can support with the actual amount of Btu/Hr used.

Btu/Hr (maximum the space can support)

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoiningroom or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need noadditional fresh air ventilation.

lo.._ 5

Page 6: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

AIR FORCOMBUSTION ANDVENTILATIONContinued

VENTILATION AIR

Ventilation Air From InsideBuilding

This fresh air would come from an adjoiningunconfined space. When ventilating to anadjoining unconfined space, you must pro-vide two permanent openings: one within12" of the ceiling and one within 12" of thefloor on the wall connecting the two spaces(see options 1and 2, Figure 2). You can alsoremove door into adjoining room (see op-tion 3, Figure 2). Follow the National FuelGas Code NFPA 54/ANSI Z223.1, Section5.3, Air for Combustion and Ventilation forrequired size of ventilation grills or ducts.

_kWARNING:Rework work-

sheet, adding the space of theadjoining unconfined space. Thecombined spaces must haveenough fresh air to supply allappliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilationgrills or ducts. You must provide two per-manent openings: one within 12" of theceiling and one within 12" of the floor.Connect these items directly to the outdoorsor spaces open to the outdoors. These spacesinclude attics and crawl spaces.

IMPORTANT: Do not provide openings forinlet or outlet air into attic if attic has a

thermostat-controlled power vent. Heatedair entering the attic will activa_: the powervent.

VentilationGrills

Into Adjoining OrRoom, Remove

Option 1 Door into

AdjoiningRoom,

Option C3

12"

Ventilation Grills

Into Adjoining Room,Option 2

Figure 2 - Ventilation Air from Inside Building

OutletAir

Inlet Air

InletAir

I 1

VentilatedCrawl Space

To Attic

ToCrawlSpace

Figure 3 - Ventilation Air from Outdoors

6 1o3425

Page 7: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

INSTALLING

NOTICE: A qualified service per-son must install heater. Followall local codes.

NOTICE: State or local codes mayonly allow operation of this appli-ance in a vented configuration.Check your state or local codes.

WARNING: Before installingin a previously-used wood-burn-ing fireplace, clean chimney flueand firebox. Make sure flue isfree of any creosote. Creosotewill ignite if highly heated. In-spect chimney flue for damage. Ifdamaged, operate heaterwith fluedamper closed.

AJ& WARNING: Seal any fresh airvents or ash clean-out doors lo-cated on floor or wall of fireplace.If not, drafting may cause pilotoutage or sooting. Use a heat-resistant sealant. Do not sealchimney flue damper.

Aall WARNING: Never install theheater

in a bedroom or bathroom

(except in vented application,see page 10)

• in a recreational vehiclewhere curtains, furniture,clothing, or other flammableobjects are less than 36inches from the front, top, orsides of the heaterin high traffic areas

• in windy or drafty areas

CAUTION: This heater cre-ates warm air currents. These cur-rents move heat to wall surfacesnext to heater. Installing heaternext to vinyl or cloth wall cover-ings or operating heater whereimpurities in the air (such as to-bacco smoke) exist, may discolorwalls.

IMPORTANT."Vent-free heaters add mois-

ture to the air. Although this is beneficial,installing heater in rooms without enoughventilation air may cause mildew to formfrom too much moisture. See Air for Com-bustion and Ventilation, pages 4 through 6.

CHECK GAS TYPE

Use only prupane/LP gas. If your gas supplyis not propane/LP, do not install heater. Call

dealer where you bought heater for propertype heater.

INSTALLATION AND

CLEARANCES (Vent-FreeOperation Only)

_WARNING: Maintain the mini-

mum clearances. If you can, pro-vide greater clearances fromfloor, ceiling, and adjoining wall.

MINIMUM FIREPLACE CLEARANCETO COMBUSTIBLE MATERIALS

Loq Size Side Wall

18", 24", 30" 16"Ceilinq42

LOG SIZING REQUIREMENTS

Log Minimum Firebox Size! Size Height Depth Front Width

! 18" 17" 14" 20"

24" 17" 14" 26"

30" 17" 14" 32"

_o3,r_ 7

Page 8: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

INSTALLINGContinued

Carefully follow the instructions below. Thiswill ensure safe installation into a masonryor U.L. listed manufactured fireplace.

Minimum Wall and CeilingClearances (see Figure 4)A. Clearances from the side of the

fireplace opening to any combustiblewall should not be less than 16 inches.

B. Clearances from the top of the fireplace

opening to the ceiling should not be lessthan 42 inches.

NOTICE: Manual control heatersmay be used as a vented product.If so, you must always run heaterwith chimney flue damper open.If running heater with damperopen, non-combustible materialabove fireplace opening is notneeded. Go to Installing DamperClamp Accessory for VentedOperation, page 10.

Minimum Non CombustibleMaterial Clearances

If Not Using Mantel

Note: If using a mantel, go to page 9. If not

using a mantel, follow the information onthis page.

You must have non combustible material(s)

above the fireplace opening. Non combus-tible materials (such as slate, marble, tile,etc.) must be at least 1/2 inch thick. Withsheet metal, you must have non combustible

material behind it. Non combustible mate-

rial must extend at least 8" up (for all mod-els). If non combustible material is less than

12", you must install the fireplace hood

accessory (24" and 30" models only). Seechart below and Figure 5 for minimumclearances.

IMPORTANT: If you cannot meet these mini-

mum clearances, you must operate heaterwith chimney flue damper open. Go to In-stalling Damper Clamp Accessory forVented Operation, page 10.

Non-Combustible

Material Distance (A)

12" or more

Between 8" and 12"

Less than 8"

Requirements forSafe Installation

Non combustible material OK.

24" or 30" Models: Install fireplace hood accessory(GA6050 or GA6052, see Acsessodes, page 38).

18" Model: Non combustible matedal OK. No hood

accessory needed.

Non combustible matedal must be extended to at least

8". See Between 8" and 12",above. If you cannot extendmaterial, you must operate heater with flue damper open.

/

16"

_-2"

I" II

j LI I

Heat ResistantMaterial

_1_ mm

//

/ (A)//// 'r

Figure 4 - Minimum Clearance to Wall and Ceiling Figure 5- Heat Resistant Material(Slate, Marble, Tile,etc.) AboveFireplace

8 1o3425

Page 9: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

INSTALLINGContinued

Minimum Non CombustibleMaterial Clearances

If Using Mantel

You must have non combustible material(s)above the fireplace opening. Non combus-tible materials (such as slate, marble, tile,etc.) must be at least 1/2 inch thick. With

sheet metal, you amst have non combustiblematerial behind it. Non combustible mate-

rial must extend at least 8 inches up (for allmodels). If non combustible material is lessthan 12", you must install the fireplace hoodaccessory (24" and 30" models only). Evenif non combustible material is more than

12", you may need the hood accessory todeflect heat away from your mantel shelf.See chart below and Figures 6 and 7 forminimum clearances.

IMPORTANT:If you cannot meet these mini-mum clearances, you must operate heaterwith chimney flue damper open. Go to In-stalling Damper Clamp Accessory forVented Operation, page 10.

Mantel Clearances

In addition to meeting non-combustiblemateFlal clearances, you must also meetrequired clearances between fireplace open-

ing and mantel shelf. If you do not meet theclearances listed below, you will need ahood.

Determining Minimum Mantel Clearance

If you meet minimum clearance betweenmantel shelf and top of fireplace opening, ahood is not required (see Figure 6).

Determining Minimum Mantel ClearanceWhen Using a Hood

If minimum clearances in Figure 6 are notmet, you must have a hood. When using ahood there are still certain minimum mantelclearances required. Follow minimum clear-ances shown in Figure 7 when using hood.

If your installation does not meet the mini-mumclearances shown in Figure7, you must:

• operate the logs only with the fluedamper open, OR

• raise the mantel to an acceptableheight, OR

• remove the mantel.

Non Combustible

Material Distance (A)

12"or more

Between8" and 12"

Less than 8"

Requirements forSafe installation

Non combustible material OK.

24" or 30" Models: Install fireplace hood accessory(GA6050 or GA6052, see Accessories, page 38).

18" Model: Non combustible material OK. No hood

accessory needed.

Non combustible material must be extended to at least

8". See Between 8" and 12", above. If you cannot extendmaterial, you must operate heater with flue damper open.

Mantel Shelf

10'

Minimum Non-Combustible

Material 12" 20" 241,_" 27112 .

18112 M

Minimum Non- Distances toCombusiible Underside of

//_ Matedal Height Mantel

Figure 6 - Minimum Mantel Clearances Without Using Hood

Underside ofMantel Shelf

All minimum

distar_ces are

in inches

Log Set30" <_ 24'/30" Models

_0*-<_18"Model

• Top of FireplaceJ Opening

Mantel Shelf

Minimum Non-CombustibleMaterial

_" 112" 15" 18"_lin.

r

Hood Distances to(GA6050, GA6052) Underside of

Mantel

Underside ofMantel Shelf

All minimumd_stancesarein inches

Log Sets

_0"_18", 24",& 30" Models

Top of Fireplace-'/ Opening

Figure 7- Minimum Mantel Clearances When Using Hood

I034Z5 9

Page 10: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

INSTALLINGContinued

Floor Clearances

A. ff installing appliance on the floor level,you must maintain the minimumdistance of 14" to combustibles (seeFigure 8).

B. If combustible materials are less than

14" from the fireplace, you must installappliance at least 5" above thecombustible flooring (see Figure 9).

]

/_ Combustible14n. ' _/aterial

_\ Non-Combustible

Material

Figure 8 - Minimum Fireplace Clearances If Installed at Floor Level

INSTALLING DAMPERCLAMP ACCESSORY FORVENTED OPERATION

Note: When used as a vented beater, appli-ance must be installed only in a solid-fuelburning fueplace with a working flue andconstructed of non combustible material.

ffyour heater is amanually controlled model,you may use this heater as a vented product.There are three reasons for operating yourheater in the vented mode.

1. The fireplace does not meet theclearance to combustibles requirementsfor vent-free operation.

2. State or local codes do not permit vent-free operation.

3. You prefer vented operation.

If reasons number 1 or 2 above apply to you,you must permanently open chimney fluedamper. You must install the damper clampaccessory (to order, see Accessories, page25). This will insure vented operation (seeFigure 10). The damper clamp will keepdamper open. Installation instructions areincluded with clamp accessory.

See chart below for minimum permanentflue opening you must provide. Attachdamper clamp so the minimum permanentflue opening will be maintained at all times.

Heath

Min.

Figure 9 - Minimum Fireplace Clearances Above Combustible Flooring

Chimney Minimum Permanent

Height (ft.) Flue Opening (sq. ins.)

6' to 15' 39 sq. inches15' to 30' 29 sq.inches

Area of Various Standard Round Flues

Diameter (ins.) Area (sq. ins.)

5" 20 sq. inches6" 29 sq. inches7" 39 sq. inches8" 51 sq. inches

Damper /Clamp Damper

Damper

Damper...

Clamp _--x.-'_\\\

\\\

\\\

\\\

\\\

\ \ \

\\\

\\\\ \ \

\\\\ \ \

_Damper

Masonry Fireplace Manufactured Fireplace

Figure 10 - Attaching Damper Clamp

10 103425

Page 11: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

INSTALLINGContinued

INSTALLING HEATER BASEASSEMBLY

WARNING: You must secure

this heater to fireplace floor, ifnot, heater will move when youadjust controls. Moving heatermay cause a gas leak.

_lb WARNING: If installing in asunken fireplace, special care isneeded. You must raise the fire-place floor to allow access toheater control panel. This will in-sure adequate air flow and guardagainst sooting. Raise fireplacefloor with non-combustible ma-terial. Make sure material is se-cure.

_ CAUTION: Do not pick up

heater base assembly by burn-ers. This could damage heater.Only handle base assembly bygrates.

IMPORTANT: Make sure the heater burners

are level. If heater is not level, heater will notwork properly. For thermostat models, avoid

damage to thermostat bulb. Avoid nicks orsharp bonds in thermostat bulb wire. Keepthermostat bulb in mounting bracket.

Installation Items Needed

• hardware package (provided with heater)• approved flexible gas hose (not provided)

(if allowed by local codes)• sealant (resistant to LP gas, not provided)• electric drill with 3/16" masonry drill bit

1. Apply pipe joint sealant lightly to malethreads of gas connector and install into

regulator. Connect approved flexiblegas hose to gas regulator of heater (seeFigure 11).

IMPORTANT: Hold gas regulator with

wrench when connecting fittings.

2. Position heater base assembly infireplace.

exeasoo euroaS :allowed by local codes)

Figure 11 - Attaching Flexible Gas Hose to Heater Gas Regulator

MasonryScrew

\

Figure 12 - Attaching Heater to Fireplace Floor

3. Mark screw locations through holes infront of base. If installing in a brick-bottom fireplace, mark screw locations

in mortar joint of bricks.

4. Remove heater base from fireplace.

5. Drill holes at marked locations using3/16" drill bit. Drill at a 45 ° angle.

6. Attach base to fireplace floor usingmasonry screws in hardware

package (see Figure 12).

7. Connect to gas supply. See ConnectingTo Gas Supply below.

CONNECTING TO GASSUPPLY

NOTICE: A qualified service per-son must connect heater to gassupply. Follow all local codes.

CAUTION: Never connect

heater directly to the propane/LPsupply. This heater requires anexternal regulator (not supplied).Install the external regulator be-tween the heater and propane/LPsupply.

Installation Items Needed

Before installing heater, make sure you havethe items listed below.

• external regulator (supplied byinstaller, see page 12)

• piping (check local codes)• sealam (resistant to propane/LP gas)• manual shutoff valve *

• test gauge connection *• sediment trap• tee joint• pipe wrench

• An A.G.A. design-certified manual shutoffvalve with 1/8" NPT tap is an acceptablealternative to test gauge connection. Pur-chase the optional A.G.A. design-certifiedmanual shutoff valve from your dealer. SeeAccessories, page 25. Continued

103425 11

Page 12: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

INSTALLINGContinued

The installer must supply an external regu-

lator. The external regulator will reduceincoming gas pressure. You must reduceincoming gas pressure to between 11 and 14

inches of water, ffyou do not reduce incom-ing gas pressure, heater regulator damagecould occur. Install external regulator withthe vent pointing down as shown in Figure

13. Pointing the vent down protects it fromfreezing rain or sleet.

_IL WARNING: Never connectheater to private (non-utility) gaswells. This gas is commonlyknown as wellhead gas.

_k CAUTION: Use only new,black iron or steel pipe. Inter-nally-tinned copper tubing maybe used in certain areas. Checkyour local codes. Use pipe of 1/2"diameter or greater to allowproper gas volume to heater. Ifpipe is too small, undue loss ofpressure will occur.

Installation must include a manual shutoff

valve, union, and plugged 118" NPT tap.Locate NPT tap within reach for test gaugehook up. NPT tap must be upstream fromheater (see Figure 14).

Apply pipe joint sealant lighdy to malethreads. This will prevent excess sealantfrom going into pipe. Excess sealant in pipecould result in clogged heater valves.

_k CAUTION: Use pipe joint seal-ant that is resistant to liquid pe-troleum (LP) gas.

Install sediment trap in supply line as shownin Figure 14. Locate sediment trap where itis within reach for cleaning. Locate sedi-ment trap where trapped matter is not likelyto freeze. A sediment trap traps moistureand contaminants. This keeps them fromgoing into heater controls. If sediment trapis not installed or is installed wrong, heatermay not run properly.

Propane/LPSupplyTank

External

Regulator

Figure 13 - External Regulator With Vent Pointing Down

From ExternalRegulator(11" W.C.** to14" W.C. Pressure)

A.G.A. Design-CertifiedManual Shutoff Valve With1/8" NPT Tap*

Approved Flexible Gas Hose(if allowed by tocal codes)

i ee JointPipe -

Nipple

CapSedimentTrap

Figure 14 - Gas Connection

3" Minimum

GasRegulator

_ CAUTION: Avoid damage to

regulator. Hold gas regulator wRhwrench when conneeting it to gaspiping and/or fittings.

* Purchasethe optional A.G.A. design-cer-tiffed manual shutoffvalve fromyourdealer.See Accessories, page 25.** Minimum inlet pressure for purpose ofinput adjustment.

12 t0342s

Page 13: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

INSTALLINGContinued

CHECKING GASCONNECTIONS

_1= WARNING: Test all gas pip-ing and connections for leaksafter installing or servicing. Cor-rect all leaks at once.

_kWARNING: Never useanopenflame to check for a leak. Apply amixture of liquid soap and waterto all joints. Bubbles formingshow a leak. Correct all leaks atonce.

_k CAUTION: Make sure exter-

nal regulator has been installedbetween propane/LP supply andheater. See guidelines under Con-necting to Gas Supply, page 15.

3. Check all joints from propane/LPsupply tank to manual shutoff valve(see Figure 16).Apply mixture of liquidsoap and water to gas joints. Bubblesforming show a leak.

4. Correct all leaks at once.

Pressure Testing Heater GasConnections

1. Open manual shutoff valve (see Figure15).

2. Open propane/LP supply tank valve.

3. Make sure control knob of heater is in

the OFF position.

4. Check all joints from manual shutoffvalve to thermostat gas valve(thermostat-controlled models) or

5.

6.

7.

control valve (variably-controlledmodels) (see Figure 16)Apply mixtureof liquid soap and water to gas joints.Bubbles forming show a leak.

Correct all leaks at once.

Light heater (see Operating Heater,pages 14 through 16 [Thermostat-

Controlled Models] or pages 16through 17 [Variable Manually-Controlled Models]). Check all other

internal joints for leaks.

Turn off heater (see To Turn Off Gas to

Appliance, page 16 [Thermostat-Controlled Models] or page 17[Variable Manually-ControlledModels]).

Pressure Testing Gas SupplyPiping SystemTest Pressures In Excess Of 1/2 PSlG

1. Disconnect heater and its individual

manual shutoff valve from gas supplypiping system. Pressures in excess of1/2 psig will damage heater regulator.

2. Cap off open end of gas pipe wheremanual shutoff valve was connected.

3. Pressurize supply piping system byeither using compressed air or

opening propane/LP supply tank valve.

4. Check all joints of gas supply pipingsystem. Apply mixture of liquid soapand water to gas joints. Bubblesforming show a leak.

5. Correct all leaks at once.

6. Re-connect heater and manual shutoff

valve to gas supply. Check re-connected fittings for leaks.

/_ Open

sMatu_flvalve_---_-/ / Jk____&___i:

_r_? Closed

Figure 15 - Manual Shutoff Valve

Propane/LPSupply Tank

ManualShutoff

I Valve

I

Thermostat Gas Valve orControl Valve Location

Test Pressures Equal To orLess Than 1/2 PSIG

1. Close manual shutoff valve (see Figure15).

2. Pressurize supply piping system byeither using compressed air or openingpropane/LP supply tank valve.

Figure 16 - Checking Gas Joints

103_5 13

Page 14: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

INSTALLINGContinued

INSTALLING LOGS

WARNING: Failure to positionthe parts inaccordance with thesediagrams or failure to use onlyparts specifically approved withthis heater may result in propertydamage or personal injury.

Each log is marked with a number. Thesenumbers will help you identify the log wheninstalling. It is very important to installthese logs exactly as instructed. Do notmodify logs. Only use logs supplied withheater.

1. Slide rear log (#1) into place behindrear burner. Make sure flat areas at

bottom of log are behind front burner(see Figure 16).

2. Slide bottom mid log (#2) into place inbehind front burner. Make sure tabs atbottom of log are behind rear burner(see Figure 16).

3. Place front log (#3) into place in frontof bottom mid log (#2) (see Figure 16).Make sure notches on bottom rest on

4.

grate prongs.

Finally place top log (#4) over bottommid log (#2) by matching the notchesunder log (#4) with the raised blocksof log (#2) (see Figure 19).

Rear Log (#1)

Rgure 16 - Installing Rear Log

Bottom Mid Log (#2)/

Figure 17- Installing Bottom Mid Log

Front Log (#3)

Figure 18 - Installing Front Log

Figure 19 - Installing Top Log

OPERATINGHEATERThermostat-ControlledModels

FOR YOUR SAFETY IREAD BEFORE

LIGHTING

_lh WARNING: If you do not fol-low these instructions exactly, afire or explosion may result caus-ing property damage, personalinjury or loss of life.

A. This appliance has a pilot which mustbe lightedby hand. When lighting thepilot, follow these instructionsexactly.

B. BEFORE LIGHTING smell all

around the appliance area for gas. Besure to smell next to the floor becausesome gas is heavier than air and willsettle on the floor.

C.

D.

WHAT TO DO IF YOU SMELLGAS

• Do not try to light any appliance.• Do not touch any electric switch;

do not use any phone in yourbuilding.

• Immediately call your gas supplierfrom a neighbor's phone. Followthe gas suppHer's instructions.

• If you cannot reach your gassupplier, call the fire department.

Use only your hand to push in or turnthe gas control knob. Never use tools.If the knob will not push in or turnby hand, don't try to repair it, call aqualified service technician or gassupplier. Force or attempted repairmay result in a fire or explosion.

Do not use this appliance if any parthas been under water. Immediatelycall a qualified service technician toinspect the appliance and to replaceany part of the control system andany gas control which has been underwater.

14 to,._€_

Page 15: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

OPERATINGHEATERThermostat-ControlledModelsContinued

l LIGHTINGINSTRUCTIONS l

4,

_lb WARNING:

• If fireplace has glass doors,never operate this heater withglass doors closed. If you op-erate heater with doors closed,heat buildup inside fireplacewill cause glass to burst. Alsoif fireplace opening has ventsat the bottom, you must openthe vents before operatingheater.

• You must operate this heaterwith afireplace screen in place.Make sure fireplace screen isclosed before running heater.

5.

6.

Wait five (5) minutes to clear out anygas. Then smell for gas, includingnear the floor. If you smell gas,STOP! Follow "B" in the safetyinformation on page 16. If you don'tsmell gas, go to the next step.Turn control knob counterclockwise

to the PILOT position.Press in control knob for five (5)seconds (see pages 16 and 17).

If control knob does not pop outwhen released, contact a qualifiedservice person or gas supplier forrepairs.

Note: You may be running thisheater for the first time after hook-

ing up to gas supply. If so, thecontrol knob may need to bepressed in for 30 seconds or less.This will allow air to bleed fromthe gas system.

With control knob pressed in, pressand release ignitor button. This willlight pilot. The pilot is attached to thefront burner. If needed, keeppressing ignitor button until pilotlights.

Note: If pilot does not stay lit,contact a qualified service personor gas supplier for repairs. Untilrepairs are made, light pilot withmatch. To light pilot with match,see Manual Lighting Procedure,page 16.

7. Keep control knob pressed in for 30seconds after lighting piloL After 30seconds, release control knob.

Note:If pilot goes out, repeat steps3 through 7. This heater has asafety interlock system. Wait one(1) minute for system to reset be-fore lighting pilot again.

8. Turn control knob counterclockwiseto desired heating level. The

burners should light. Set controlknob to any heat level between HIand LO.

ACAUTION: Do not try to adjust

heating levels by using themanual shutoff valve.

NOTICE: During initial operationof new heater, burning logs willgive off a paper-burning smell.Orange flame will also be present.Open damper or window to ventsmell. This will only last a fewhours.

Note: Homeowners generally prefer tooperate their heater with the chimneydamper closed. This will put all the heatinto the room. However there may betimes you will desire the full flames of theHi heat setting but will find the heatoutput excessive. You can open the chim-ney damper (if you have one) fully orpartially to release some of the heat.WARNING: Damper handle will be hotif heater has been running.

1. STOP! Read the safety informationabove.

2. Make sure manual shutoff valve isfullyopen.

3. Turn control knob clockwisetO the OFF position.

IgnitorButton\

Figure 21 - Control Knob and Ignitor Button Location

litorElectrode

Rgure 22 - Pilot

Control Knob

m34_ 15

Page 16: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

OPERATINGHEATER

Thermostat-ControlledModelsContinued

OPERATINGHEATER

Variable Manually-ControlledModels

I TOTURNOFFGASI I FORYOUR ITO APPLIANCE SAFETY READ

Shutting Off Heater BEFORE LIGHTING1. Turn control knob clockwise

/F"" A to the OFF position.

Shutting Off Burners Only (pilotstays lit)1. Turn control knob clockwise

to the PILOT position.

I THERMOSTATCONTROL OPERATIONI

(Thermostat-ControlledModels Only)

The thermostat control knob can be set toany comfort level between Hi and Lo.The thermostat will gradually modulatethe heat output and flame height fromhigher to lower settings, or pilot, in orderto maintain the comfort level you select.The ideal comfort setting will vary byhousehold depending upon the amountof space to be heated, the output of thecentral heating system, etc.

Note." Selecting the Hi setting with thecontrol knob will cause the burner to

remain fully on, without modulating downin most cases.

MANUAL LIGHTINGPROCEDURE 1

1. Follow steps 1 through 5 underLighting Instructions, pages 20 and21.

2. Depress control knob and light pilotwith match.

3. Keep control knob pressed in for 30seconds after lighting pilot. After 30

• seconds, release control knob. Nowfollow step 8, page 21.

_1= WARNING: If you do not fol-low these instructions exactly, afire or explosion may result caus-ing property damage, personalinjury or loss of life.

A. This appliance has a pilot whichmust be lighted by hand. Whenlighting the pilot, follow theseinstructions exactly.

B. BEFORE LIGHTING smell allaround the appliance area for gas.Be sure to smell next to the floor

because some gas is heavier than airand will settle on the floor.

C.

V.

WHAT TO DO IF YOU SMELLGAS• Do not try to light any appliance.• Do not touch any electric switch;

do not use any phone in yourbuilding.

• Immediately call your gas supplierfrom a neighbor's phone. Followthe gas supplier's instructions.

• If you cannot reach your gassupplier, call the fire department.

Use only your hand to push in or turnthe gas control knob. Never use tools.If the knob will not push in or turnby hand, don't try to repair it, call aqualified service technician or gassupplier. Force or attempted repairmay result in a fire or explosion.

Do not use this appliance if any parthas been under water. Immediatelycall a qualified service technician toinspect the appliance and to replaceany part of the control system andany gas control which has beenunder water.

LIGHTING

WARNING:

• If fireplace has glass doors,never operate this heater withglass doors closed. If you op-erate heater with doors closed,heat buildup inside fireplacewill cause glass to burst. Alsoif fireplace opening has ventsat the bottom, you must openthe vents before operatingheater.

• You must operate this heaterwith afireplace screen in place.Make sure fireplace screen isclosed before running heater.

NOTICE: During initial operationof new heater, burning logs willgive off a paper-burning smell.Orange flame will also be present.Open damper or window to ventsmell. This will only last a fewhours.

Note: Homeowners generally prefer tooperate their heater with the chimneydamper closed. This will put all the heatinto the room. However there may betimes you will desire the full flames of theHigh heat setting but will find the heatoutput excessive. You can open the chim-ney damper (if you have one) fully orpartially to release some of the heat.WARNING: Damper handle will be hotif heater has been running.

1. STOP! Read the safety informationabove.

2. Make sure manual shutoff valve is

fully open.

3. Press in and turn control knob

clockwise _ to the OFFposition.

16 _034_

Page 17: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

OPERATINGHEATER

Variable Manually-ControlledModels

Continued

4. Wait five (5) minutes to clear out anygas. Then smell for gas, includingnear the floor. If you smell gas,STOP! Follow "B" in the safetyinformation above. If you don't smellgas, go to the next step.

5. Press in control knob and turn

counterclockwise _ to thePILOT position. Keep control knobpressed in for five (5) seconds (seeFigure 23).• If control knob does not pop out

when released, contact a qualifiedservice person or gas supplier forrepairs.

Note: You may be running this heaterfor the first time after hooking up togas supply. If so, the control knobmay need to be pressed in for 30seconds. This will allow air to bleed

from the gas system.

6. With control knob pressed in, pressand release ignitor button. This willlight pilot. The pilot is attached to thefront burner. If needed, keeppressing ignitor button until pilotlights.

Note: If pilot does not light, contacta qualified service person or gassupplier for repairs. Until repairs aremade, light pilot with match. To lightpilot with match, see ManualLighting Procedure below.

7. Keep control knob pressed in for 30seconds after lighting pilot. After 30seconds, release control knob.

8.

Note: If pilot goes out, repeat steps 3through 7.Push in and turn control knobcounterclockwise _ to theHIGH position. Both burners shouldlight. Set control knob to desiredsetting.

Ignitor ButtonControl Knob

Figure 23 - Control Knob and Ignitor Button Location

Ignitor Electrode

Figure 24 - Pilot

IVARIABLE CONTROLII 2OPERATION • 3

The variable control valve can be set to

any heat setting and flame height desiredbetween high and low by simply turningthe control knob until that setting is at-tained. Even the lowest setting providesrealistic flames and glowing embers fromtwo burners. Selecting higher settings pro-duces greater heat output. This results inincreased heating comfort.

" _ WARNING: Do not operateheater between pilot and high. _-

_k CAUTION: Do nottrytoadjustheating levels by using themanual shutoff valve.

Turn the control knob clockwise

to the PILOT position.Press in control knob and turn

clockwise _ to the OFFPosition.

Shutting Off Burners Only (pilot stays

lit)

1. Turn the control knob clockwise

to the HIGH position.2. Press in and turn control knob

clockwise _ to the pilot_ition.

MANUAL LIGHTINGPROCEDURE 1

1. Follow steps 1 through 5 underLighting Instructions, page 15.

2. Depress control knob and light pilotwith match.

ITO TURN OFF GASll ,TO APPLIANCE

Shutting Off Heater1. Press in and turn control knob

clockwise _ to the HIGHposition.

Keep control knob pressed in for 30seconds after lighting pilot. After 30

seconds, release control knob. Nowfollow step 8, page 15.

1034_ 17

Page 18: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

INSPECTINGBURNERSCheck pilot flame pattern and burner flame

patterns often.

PILOT FLAME PATTERN

Figure 25 shows a correct pilot flame pat-tern. Figure 26 shows an incorrect pilotflame pattern. The incorrect pilot flame isnot touching the thermocouple. This willcause the thermocouple to cool. When thethermocouple cools, the heater will shutdown.

Thermocouple Pilot Burner

FRONT BURNER FLAMEPATTERN

Figure 27 shows correct front burner flamepattern. Figure 28 shows incorrect frontburner flame pattern. The incorrect burnerflame pattern shows yellow tipping at top ofblue flame.

_1= WARNING: If yellow tippingoccurs, your heater could pro-duce increased levels of carbonmonoxide. If front burner flamepattern shows yellow tipping, fol-low instructions at bottom of thispage. Yellow flame on rear burneris normal.

CLEANING ANDMAINTENANCE

WARNING: Turn off heater

and let cool before cleaning.

_k CAUTION: You must keepcontrol areas, burners, and cir-culating air passageways ofheater clean. Inspect these areasof heater before each use. Haveheater inspected yearly by a quali-fled service person. Heater mayneed more frequent cleaning dueto excessive lint from carpeting,bedding material, etc.

Figure 25 - Correct Pilot Flame Pattern

Thermocouple Pilot Burner

NOTICE: Do not mistake orangeflames with yellow tipping. Dirtor other fine particles are burnedby heater, causing brief patchesof orange flame.

ff front burner flame pattern is incorrect, asshown in Figure 28

• turn heater off (see To Turn OffGastoAppliance [Thermostat-ControlledModels] page 16 or [VariableManually-Controlled Models] page17)

• see Troubleshooting, pages 19through 21

ODS/PILOT AND BURNERS• Use a vacuum cleaner or small, soft

bristled brush to clean.

LOGS• If you remove logs for cleaning, refer

to Installing Logs, page 19, toproperly replace logs.

• Replace log(s) if broken or chipped(dime-sized or larger).

Ftgure 26 - Incorrect Pilot Flame Pattern

If pilot flame pattern is incorrect, as shownin Figure 26

• turn heater off(see To Turn OffGastoAppliance [Thermostat-ControlledModels] page 16 or [VariableManually-Controlled Models]above)

• see Troubleshooting, pages 19through 21

CORRECT FLAME PA'I-rERNAT HIGH POSITION

Figure 27 - Correct Front Burner Flame Pattern

Yellow3qpping AtTop ofBlueFlame

INCORRECTFLAME PATTERNAT HIGH POSITION

Figure 28 _ Incorrect Front Burner Flame Pattern

18 103425

Page 19: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

TROUBLE-SHOOTINGNote: All Troubleshooting items are listedin order of operation.

OBSERVED PROBLEM

_IL WARNING: Turn off and unplug heater and iet cool before servicing.Only a qualified service person should service and repair heater.

_1_ CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/pilot unit.

POSSIBLE CAUSE REMEDY

• When ignitor button is pressed, there is nospark at ODS/pilot

l.

2.

3.

Ignitor electrode not connected to ignitorcable

Ignitor cable pinched or wet

Piezo ignitor nut is loose

4. Broken ignitor cable5. Bad piezo ignitor6. Ignitor electrode broken7. Ignitor electrode positioned wrong

1. Reconnect ignitor cable

2. Free ignitor cable if pinched by anymetal or tubing. Keep ignitor cable dry

3. Tighten nut holding piezo ignitor to basepanel of log set. Nut is located behindbase panel.

4. Replace ignitor cable5. Replace piezo ignitor6. Replace piezo ignitor7. Replace piezo ignitor

When ignitor button is pressed, there isspark at ODS/pilot but no ignition

1. Gas supply turned off or manual shutoffvalve closed

2. Control knob not in PILOT position3. Control knob not pressed in while in

PILOT position4. Air in gas lines when installed

5. Depleted gas supply6. ODS/pilot is clogged

7. Gas regulator setting is not correct

1. Turn on gas supply or open manualshutoff valve

2. Turn control knob to PILOT position3. Press in control knob while in PILOT

position4. Continue holding down control knob.

Repeat igniting operation until air isremoved

5. Contact local propane/LP gas company6. Clean ODS/pilot (see Cleaning and

Maintenance, page 18) or replace ODS/pilot assembly

7. Replace gas regulator

ODS/pilot lights but flame goes out whencontrol knob is released

1. Control knob not fully pressed in2. Control knob not pressed in long enough

3. Safety interlock system has beentriggered (thermostat models only)

4. Manual shutoff valve not fully open5. Pilot flame not touching thermocouple,

which allows thermoconple to cool,causing pilot flame to go out. Thisproblem could be caused by one or bothof the following:A) Low gas pressureB) Dirty or partially clogged ODS/pilot

6. Thermocouple connection loose atcontrol valve

7. Thermocouple damaged8. Control valve damaged

1. Press in control knob fully2. After ODS/pilot lights, keep control

knob pressed in 30 seconds3. Wait one minute for safety interlock

system to reset. Repeat ignitionoperation

4, Fally open manual shut-off valve5. A) Contact local propane/LP gas

company

B) Clean ODS/pilot (see Cleaning andMaintenance, page 18) or replace ODS/pilot assembly

6. Hand tighten until snug, then tighten 1/4 turn more

7. Replace thermocoupleg. Replace control valve

_ 19

Page 20: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

TROUBLE-SHOOTINGContinued

OBSERVED PROBLEM POSSIBLE CAUSE REMEDY

One or both burners do not light after ODS/pilot is lit

1. Burner orifice(s) clogged

2. Inlet gas pressure is too low3. Mistocated crossover tube4. Burner orifice(s) diameter is too small

1. Clean burner(s) (see Cleaning andMaintenance, page 18) or replaceburner orifice(s)

2. Contact local propane/LP gas company3. Contact qualified service person4. Replace burner orifice(s)

Delayed ignition of one or both burners 1. Manifold pressure is too low 1. Contact local propane/LP gas company2. Burner orifice(s)clogged 2. Clean burner(s) (see Cleaning and

Maintenance, page 18) or replaceburner orifice(s)

3. Mislocated crossover tube 3. Contact qualified service person

Burner backfiring during combustion 1. Burner orifice is clogged or damaged 1. Clean burner (see Cleaning andMaintenance, page 18) or replaceburner orifice

2. Damaged burne_" 2. Replace damaged burner3. Gas regulator defective 3. Replace gas regulator

Yellow flame in front burner during burner 1. Not enough air 1. Check burner(s) for dirt and debris. Ifcombustion found, clean burner(s) (see Cleaning

and Maintenance, page 18)2. Gas regulator defective 2. Replace gas regulator

Slight smoke or odor during initial opera- 1. Residues from manufacturing processes 1. Problem will stop after a few hours oftion and logs curing operation

Moisture/condensationnoticedonwindows 1. Not enough combustion/ventilation air 1. Refer to Air for Combustion andVentilation requirements (page 4)

Heater produces a whistling noise when 1. Turning control knob to HI position 1. Turn control knob to LO position andburners are lit when burners are cold let warm up for a minute

2. Air in gas line 2. Operate burners until air is removed

3. Air passageways on heater blocked 3.

4. Dirty or partially clogged burner 4.orifice(s)

from line. Have gas line checked bylocal propane/LP gas companyObserve minimum installation

clearances (see pages 8-10)Clean burners (see Cleaning andMaintenance, page 18) or replaceburner orifice(s)

Page 21: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

TROUBLE-SHOOTINGContinued

WARNING: If you smell gas

• Shut off gas supply.• Do not try to light any appliance.• Do not touch any electrical switch; do not use any phone in your

building.• Immediately callyour gas supplier from a neighbor's phone. Follow the

gas supplier's instructions.• If you cannot reach your gas supplier, call the fire department.

IMPORTANT: Operating heater where im-purities in air exist may create odors. Clean-ing supplies, paint, paint remover, cigarettesmoke, cements and glues, new carpet ortextiles, etc., create fumes. These fumesmay mix with combustion air and createodors. These odors will disappear over time.

OBSERVED PROBLEM POSSIBLE CAUSE REMEDY

Heater produces a clicking/ticking noise 1. Metal expanding while heating or l. This is common with most heaters. Ifjust after burners are lit or shut off contracting while cooling noise is excessive, contact qualified

service person

Heater produces unwanted odors 1. Heater burning vapors from paint, hair 1. Open window to ventilate room. Stopspray, glues, cleaners, chemicals, new using odor causing products while heatercarpet, etc. (See IMPORTANTstatement is runningabove)

2. Low fuel supply3. Gas leak. See Warning statement at

top of page

2. Refill supply tank3. Locate and correct all leaks (see

Checking Gas Connections, page 13)

Heater shuts off in use (ODS operates) 1. Not enough fresh air is available 1. Open window and/or door for ventilation2. Low line pressure 2. Contact local propane/LP gas company3. ODS/pilot is partially clogged 3. Clean ODS/pilot (see Cleaning and

Maintenance, page 18)

GasodorevenwhencontrolknobisinOFF 1. Gas leak. See Warning statement at 1. Locate and correct all leaks (seeposition top of page Checking Gas Connections, page 13)

2. Control valve defective 2. Replace control valve

Gas odor during combustion 1. Foreign matter between control valve 1. Take apart gas tubing and removeand burner foreign matter

2. Gas leak. See Warning statement at 2. Locate and correct all leaks (seetop of page Checking Gas Connections, page 13)

Thermostat Models Only: 1. Thermostat sensing bulb needs to be 1. Reposition thermostat sensing bulb (seeLog set cycles to pilot, but room tempera- repositioned Instructions for Optional Positioning ofture drops to a lower than ideal level before Thermostat Sensing Bulb, page 23)log set comes back on

_ 21

Page 22: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

OPTIONALPOSITIONING OFTHERMOSTATSENSING BULB

For Masonry andFactory-built MetalFireplace

If your log set cycles to pilot, but theroom temperature drops to a lower thanideal comfort level before the log setcomes back on, you may want to reposi-tion the thermostat sensing bulb.

The thermostat sensing bulb is located onthe gas valve assembly. This location al-lows the thermostat to keep the room tem-perature at an ideal comfort level for most

fireplace applications. For positioning thethermostat sensing bulb elsewhere, an ad-

hesive-backed mounting clip has been pro-vided.

Tools needed: 5/16" hex driver or socket

1. Locate the gas valve assembly andthermostat sensing bulb (see Figure 29).

2. The adhesive-backed mounting clip(see Figure 30) is attached to thethermostat sensing bulb. Remove theadhesive-backed mounting clip.

3. With 5/16" hex driver or socket, loosenthe thermostat screw. Carefully slidethe thermostat sensing bulb out of theretaining clamp (see Figure 31).Note: Do not remove the screw. Make

sure you tighten the screw afterremoving the thermostat sensing bulb.

4.

IMPORTANT: Do not force or bend the

thermostat sensing bulb or capillary. Acrimped capillary will not allow ther-

mostat to operate properly. It cannot berepaired, the valve must be replaced.

The thermostat sensing bulb may belocated to the lower right front side offireplace. Determine location of sens-ing bulb, but do not mount sensing bulbuntil step 5. If you have a masonryfireplace, see Figure 32 for location.

Figure 29 - Location of Gas Valve Assembly and Thermostat Sensing Bulb

Figure 30 - Adhesive-backed Mounting Clip

Capillary

Screw Thermostat Sensing Bulb

Retaining Clamp

Figure 31 - Removing Thermostat Sensing Bulb

ThermostatSensing Bulb

Adhesive-backedMounting Clip

Figure 32 - Locating Thermostat Sensing Bulb on Masonry Fireplace

22 1o3425

Page 23: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

OPTIONALPOSITIONING OFTHERMOSTATSENSING BULB

For Masonry andFactory-built MetalF,replaceCon_nued

SERVICE HINTSWhen gas pressure is too low

• pilot will not stay lit• burners will have delayed ignition

• heater will not produce specifiedheat

• propaneFLP gas supply may be low

When gas quality is bad

• pilot will not stay lit•bumers will produce flames and

soot• heater will backfire when lit

You may feel your gas pressure is too low orgas quality is bad. If so, contact your localpropane/LP gas supplier.

If you have a factory-built metal fireplace,see Figure 33 for location.

If your fireplace has glass doors, positionsensing bulb directly behind door gap onright bottom side (see Figure 34).

5. The mounting clip must be a minimumof 3" from bottom of fireplace toprevent crimping of capillary. Once youhave decided on a location, clean thearea thoroughly. Remove the paperbacking from the adhesive on back ofmounting clip. Press the clip into thenew location so that the thermostat

sensing bulb will be positionedvertically with the capillary at thebottom (see Figure 35). Slide thethermostat sensing bulb into the clip.IMPORTANT."Do not crimp capillary.

TECHNICALSERVICE

You may have further questions about in-stallation, operation, or troubleshooting.

If so, contact DESA International's Techni-cal Service Department at

1-g00-DESA LOG (1-800-337-2564).

ThermostatSensing Bulb

Adhesive-backedMounting Clip

Figure 33 - Locating Thermostat Sensing Bulb on Factory-built Metal Fireplace

ThermostatSensing Bulb

Adhesive-backed

Mounting Clip

GlassDoors

Figure 34 - Installing Thermostat Sensing Bulb behind Glass Doors

i Thermostat

------'----- Sensing Bulb

Adhesive-backedMounting Clip

tt Do Not Crimp Capillary

Figure 35 - Positioning the Thermostat Sensing Bulb in the Vertical Positionwith the Capillary at the Bottom

103425 23

Page 24: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

PARTSCENTRALSThese Parts Centrals are privately owned businesses. They have agreed to support our customer's needs by providing original replacementparts and accessories. When calling a Parts Central, ask for the Parts Department.

Baltimore Electric Washer Equipment Co.1348 Dixwell Avenue 1715 Main StreetHamden, CT 06514 Kansas City, MO 641081-800-397-7553 KS, MO, AR203-248-7553 816-842-3911Parts Depadment Parts Department

Portable Heater Parts342 N. County Rd. 400 EastValparaiso, IN 46383All States219-462-74411-800-362-6951Parts Department

East Coast EnergyProducts707 BroadwayW. Long Branch, NJ 07764908-870-88091-800-755-8809Parts Department

FBDP. O. Box 10961720 Kummer RoadFranklin, KY 42134502-586-19221-800-654-8534

Tarantin Tank Co.P.O. Box 6129Freehold, NJ 07728908-780-93401-800-922-0724Parts Department

Dayton HardwareP.O. Box 275

North Dayton StationDayton, OH 45404All States513-258-3721OH 1-800-762-3426

Parts Department

Halco Enterprises208 Carter Drive, Unit 21West Chester, PA 19382610-430-7717US 1-800-368-0803Parts Department

LA Porte's Parts & Service2444 North 5th StreetHartsville, SC 29550803-332-0191Parts Department

Four Flags Power Products1115 Stateline RoadNile3, Ml 49120616-684-2697Parts Only

Master Parts Distributors1184 Wilson Ave. NWWalker, MI 49504616-791-0505U S 1-800-446-1446Fax: 616-791-8270Parts Department

Albany Ladder1586-90 Central AvenueAlbany, NY 07728NY, MA, VT1-800-354-7368518-869-5335Parts Department

Cans Unlimited, Inc.P.O. Box 645Taylor, SC 29687All States803-879-30091-800-845-5301Parts Department

REPLACEMENTPARTS

Note: Use only original replacement parts.This will protect your warranty coverage forparts replaced under warranty.

Parts Under Warranty

Contact authorized dealers of this product.If they can't supply original replacementpart(s), call DESA International's Techni-cal Service Department at 1-800-323-5190.

When calling DESA International, haveready

• your name• your address• model number of your heater• how heater was malfunctioning• type of gas used (propane/LP ornatural gas)• purchase date

Usually, we will ask you to return the defec-tive part to the factory.

Parts Not Under Warranty

Contact authorized dealers of this product.If they can't supply original replacementpart(s), either contact your nearest PartsCentral (see above) or call DESAInternational's Parts Department at 1-800-972-7879 for referral information.

When calling DESA International, haveready

• model number of your heater

• the replacement part number

24 I034_

Page 25: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

ACCESSORIESPurchase these heater accessories from your local dealer. If they can not supply theseaccessories, call DESA International's Parts Department at 1-800-972-7879 for information.

You can also write to the address listed on the back page of this manual.

MANUAL SHUTOFF VALVE - GA5010

For all models. Manual shutoff valve with 1/8"NPT rap. Fits 1/2" NPT pipe.

BLACK FIREPLACE HOOD -GA6050

For all models. Helps deflect heat awayfrom mantel or wall above fireplace.

BRASS FIREPLACEHOOD - GA6052

For all models. Helps de-flect heat away from mantelor wall above fLreplace.

DAMPER CLAMP - GA6080

For variablycontrolled models. Permanentlyopens chinmey flue damper for vented op-eration.

LAVA ROCK - GA6060

For all models. Order when additional rockis desired. (3 lb. bag)

1o_s 25

Page 26: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

ILLUSTRATEDPARTSBREAKDOWN

Variable Manually-Controlled Models

4

27 27-1[ 27-2

--21

7 6

10

29

8

I

11

13

CGG2618P 1, _ .CGG3324P '_CGG3630P

18

19

20

26 i_4_

Page 27: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

PARTS LISTVariable Manually-Controlled Models

This list contains replaceable parts used in your heater. When ordering parts, follow theinstructions listed under Replacement Parts on page 24 of this manual.

KEY

NO.

1

2

3

4

5

6

7

7-1

7-2

8

910

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

27-1

27-2

PART NUMBER FOR

CGG2618P

103681-04

103681-02

103681-01

103681-03

098249-01

101006-01

101330-04

101008-01101007-01

100999-01

101331-10098271-07

102446-01

098867-10M 11084-38

101011-01

098354-01

098462-03

098325-01

098506-01

102568-02

101005-01

Ml1084-26

101004-10

101004-10

102258-01

099387-08

098276-01

099059-02

098594-01

098593-01

CGG3324P CGG3630P

103682-04 103683-04

103682-02 103683-02

103682-01 103683-01

103682-03 103683-03

098249-01 098249-01

101006-01 101006-01

101330-05 101330-06

101008-01 101008-01

101007-01 101007-01

100999-02 100999-03

101331-08 101331-09

098271-06 098271-06

102445-01 102445-01

098867-10 098867-10

Ml1084-38 Ml1084-38

101011-02 101011-03

098354-01 098354-01

098462-03 098462-03

098325-01 098325-01

098508-01 098508-01102568-02 102568-02

101005-01 101005-01

Ml1084-26 Ml1084-26

101004-01 101004-02

101004-02 101004-06

i 102258-01 102258-01

099387-08 099387-08

098276-01 098276-01

099059-02 099059-02

098594-01 098594-01

098593-01 098593-01

DESCRIPTION QTY.

Rear Log (#t) 1

Bottom Mid Log (#2) 1

Front Log (#3) 1

Top Log (#4) 1Nut 4

Pilot Bracket 1

Front Burner Assembly 1Crossover Burner Gasket 1

Crossover Burner 1

Rear Burner Assembly 1

Base Assembly (Includes Decals) 1

Ignitor Cable 1Piezo Ignitor 1

Gas Regulator 1Screw 2

Inlet Tube 1

Control Knob 1

Control Rod 1

Roll Pin 1

Valve Retainer Nut 1Gas Valve 1

Valve Bracket 1

Screw 4

Rear Burner Injector 1

Front Burner InjectorBurner Tube 1

Pilot Tube 1

1/8" Plug 1O.D.S. Pilot 1

Ignitor Electrode 1

Thermocouple 1

PARTS AVAILABLE -- NOT SHOWN

100563-01

101054-01

100565-01

100639-01

101137-03

101416-28

GA6060

100563-01

101054-01

100565-01

100639-01

101137-03

101416-28

GA6060

100563-01

101054-01

100566-01100639-01

101137-03

101416-28GA6060

Warning Plate

Ughting Instructions Plate

Warning Plate FastenerCaution Decal

Hardware Kit

Information Video

Lava Rock

1

1

1

1

1

11

_ 27

Page 28: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

ILLUSTRATEDPARTSBREAKDOWNThermostat-

Controlled Models

13

10

CGG3324PT

12

27

28 fo34_

Page 29: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

PARTS LISTThermostat-Controlled Model

CGG3324PTKEY

NO.

1

2

3

4

5

6

7

7-1

7-2

8

910

10-1

10-2

11

12

1314

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

3O

This list contains replaceable parts used in your heater. When ordering parts, follow theinstructions listed under Replacement Parts on page 24 of this manual.

PART

NUMBER DESCRIPTION

103682-04

103682-02

103682-01

103682-03

102764-01

Ml1084-26

099059-02

098594-01

098593-01

098249-01

101006-01101330-05

101008-01

101007-01

100999-02

101331-08

098271-06

102445-01

O98867-10

Ml1084-38

102810-02

098354-01

102013-01

100000-01

101053-01

099211-01

098544-01

101329-18

100994-01101004-01

101004-02

102811-01

099387-09

102255-01

QTY,

Rear Log (#1) 1

Bottom Mid Log (#2) 1

Front Log (#3) 1

Top Log (#4) 1Heat Shield 1

Screw 5

O.D.S. Pilot 1

Ignitor 1

Thermocouple 1Nut 4

Pilot Bracket 1

Front Burner Assembly 1

Gasket, Crossover Burner 1Crossover Burner 1

Rear Burner Assembly 1

Base Assembly (with decals) 1

Ignitor Cable 1

Piezo Ignitor 1

Gas Regulator 1Screw 2

Inlet Tube 1

Control Knob 1

Control Rod 1

Cotter Pin 1

Adapter 1Screw I

Thermostat Clamp 1

Thermostat Gas Valve Assy. 1Thermovalve Bracket 1

Rear Burner Injector 1

Front Burner Injector 1Thermostat Burner Tube 1

Pilot Tube 1

Strap

PARTS AVAILABLE -- NOT SHOWN

100563-01

101054-01

100565-01

100639-01

101137-03

101416-28

GA6060

Waming Plate 1

Ughting Instructions Plate 1

Warning Plate Fastener 1Caution Decal 1

Hardware Kit 1

Information Video 1

Lava Rock 1

lo3,_ 29

Page 30: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

UNVENTED (VENT-FREE) GAS LOG HEATER

NOTES

30 _os,_

Page 31: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

OWNER'S MANUAL

Page 32: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER · UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Variably Controlled Models Also Designed Certified as Vented Decorative Appliance)

WARRANTY INFORMATION

KEEP THIS WARRANTY

Model

Serial No.

Date Purchased

i

LIMITED WARRANTYCOMFORT GLOW VENT-FREE PROPANE/LP GAS LOG HEATERS

Always specify model and serial numbers when communicating with the factory.

We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make nouther warranty, expressed or implied,

DESA International warrants this product to be

free from defects in materials and componentsfor two (2) years from the date of first purchase,

provided that the product h_s been properlyinstalled, operated and maintained in accordance

with all applicable instructions. To make a clairnunder this warranty the Bill of Sale or cancelled

check must be presented.

This warranty is extended only to the original

retail purchaser. This warranty covers the cost ofpart(s) required to restore this heater to proper

operating condition and an allowance for laborwhen provided by a DESA Authorized Service

Center. Warranty pert(s) MUST be obtainedthrough autborized dealers of this ptoduct and/orDESA International who will provide original

factory replacement parts. Failure to use original

factory replacement parts voids this warranty.['he heater MUST be installed by a qualified

installer in accordance with all local codes and

nstructions furnished with the unit.

This warranty does not apply to parts that are notin original condition because of normal wear andtear, or par_ that fail or become damaged as aresult of misuse, accidents, lack of proper main-

tenance or defects caused by improper installa-tion. Travel, diagnostic cost, labor, transporta-

tion and any and all such other costs related torepairing a defective heater will be the responsi-

bility of the owner.

TO THE FULL EXTENT ALLOWED BY THE

LAW OF THE JURISDICTION THAT GOV-ERNS THE SALE OF THE PRODUCT; THIS

EXPRESS WARRANTY EXCLUDES ANYAND ALL OTHER EXPRESSED WARRAN-

TIES AND LIMITS THE DURATION OF ANY

AND ALL IMPLIED WARRANTIES, IN-CLUDING WARRANTIES OF MER-CHANTABILITY AND FITNESS FOR A PAR-

TICULAR PURPOSE TO TWO (2) YEARS

FROM THE DATE OF FIRST PURCHASE;

AND DESA INTERNATIONAL'S LIABIL-

ITY 1S HEREBY LIMITED TO THE PUR-

CHASE PRICE OF THE PRODUCT AND

DESA INTERNATIONAL SHALL NOT BE

LIABLE FOR ANY OTHER DAMAGES

WHATSOEVER INCLUDING INDIRECT,

INCIDENTAL OR CONSEQUENTIAL

DAMAGES.

Some states do not allow a limitation on how

long an implied warranty lasts or an exclusionor limitation of incidental or consequential

damages, so the above limitation on impliedwarranties, or exclusion or limitation on dam-

ages may not apply to you.

This warranty gives you specific legal rights,and you may also have other fights that varyfrom state to state.

For information about this warranty write:

DESAINTERNATIONAL

27Ol IndustrialDriveP.O. Box 90004BowlingGreen, KY 42102-9004

103425-01Rev. B

........... 05/97