UNIVERSITY OF MISSOURI - MEDICAL SCIENCE BUILDING 1ST FLOOR RESEARCH LABORATORY RENOVATION 1 Hospital Drive Columbia, MO 65212 PGAV Project #53474-00 MU Project #CP171091 ADDENDUM #2 November 27, 2017 This addendum is hereby made part of the Contract Documents for the above named project. It supplements and modifies the drawings and specifications dated November 6, 2017 prepared by Peckham Guyton Albers & Viets, Inc. (PGAV) and their consultants. This addendum is part of the Bid Documents and Contract Documents and shall govern in the performance of the work. Receipt of this addendum shall be acknowledged on the Bid Form. GENERAL Bidder’s questions (Q.) that have been received to date along with responses (R.) are as follows:
Q. What are the requirements for the construction of the temporary walls noted on sheet A100?
R. Temporary construction barriers noted as by GC on sheet A100 shall be constructed as ‘3G1/A-1’ partitions, with one layer of gypsum board on the public side of the partition. ¾” fire retardant treated plywood may be substituted for 5/8” drywall at these locations at contractor’s option. The temporary partitions need not be painted. Please refer to Special Conditions Paragraph 2.C.(1) for additional information regarding temporary protection requirements.
Q. Which of the lockers shown on sheet A301 are new, and which are existing to
remain? R. Only the lockers noted as ‘F1’ on sheet A301 are new, the others are existing to
remain. Q. On sheets M601 and E401, AHU-1 does not show a VFD nor motor starter for
control of the ECM motor. All I see is a disconnect. Is this correct? R. These are ECM motors and no VFD is required. The disconnect is correct. Q. Drawing M101 says all ductwork located in exposed ceiling space shall be
double wall construction, but it also says it is to be jacketed. The spec section 230700 3.11 note B states that exposed ductwork is to receive fiberglass duct board. Please clarify what type of insulation is required in these areas (if any).
R. Sheet M101, Ductwork General Notes 2 and 4 have been modified for clarity. Refer to the attached revised sheet M101. Specification section 230700 has not been modified.
Q. The field applied jacket schedule says that all ducts and plenums are to receive a
.016 smooth aluminum jacket unless that are concealed above a ceiling. Is this correct? Will all of the duct work and louvers in the mechanical room require .016 smooth aluminum?
Page 2 of 7
R. Specification section 230700 3.16 has been revised. Refer to Project Manual modifications below.
Q. Can you confirm that domestic water piping going through exposed areas require
no field applied jacket? R. A field jacket is not required for the domestic water piping in the exposed areas. Q. 233113-2.9 Shop Prime Paint. By the time this is applied, delivered, hung, etc
there will be little primer left. This is just an added cost. R. 233113-2.9 Shop Prime Paint has been deleted. Note 233113-2.6 C still remains
“All exposed ductwork shall be provided with paint grip finish to accept field applied paint.”
Q. 233113-3.3R, duct cleanliness-intermediate and LEED requirements sometimes
conflict. Please confirm which is required. R. Protect duct interiors per SMACNA’s “Duct Cleanliness for New Construction”
Intermediate Level. LEED is not required for this project. Q. 233113-3.8 is this required? If we follow duct cleanliness per spec can this be
eliminated? R. Specification requirements shall remain. Q. There appears to be some dual wall rectangular required. Please confirm. R. Please refer to attached revised M101 and M201 sheets for clarifications.
Double wall ductwork shall be round or flat oval. Q. Note EP016 on sheet E301 show the electrical to provide 120v power and a
disconnect switch in 7 locations. Detail 1 on sheet M703 says Div 26 is providing 120v and transformer in 18 locations. This is not shown on the electrical drawings. Is Div 26 providing 120v in each room needed and the controls taking low voltage wire to the phoenix devices?
R. See revisions to sheet E401 attached. Four total Phoenix valve power supplies (same as VAV power supplies) were added.
Q. There seems to be some discrepancies between the plans and site concerning
stainless steel cabinets. Are we responsible for surveying the quantity of work or is some of it still going to be removed by the Owner since some items on the drawing are no longer there?
R. Drawings indicate existing stainless steel cabinets to be salvaged and reinstalled, or salvaged and returned to Owner. Owner reserves the right to salvage any of these existing stainless steel cabinets themselves at their discretion, apart from the construction contract. Any existing stainless steel cabinets remaining in the project area at the time of demolition shall be removed by the Contractor and either reinstalled or returned to Owner per the drawings. Any existing stainless steel cabinets removed by Owner prior to submitting bids need not be included in the bid. Bidders are strongly encouraged to visit the project site prior to preparing their bid to familiarize themselves with existing conditions.
Q. The exterior guardrail on the stoop wall is not shown on A201 but is on A301.
A301 says reinstall removed guardrail. Is it up to contractor to determine if it is in the way of the hvac unit that must be removed or the new window unit? Also, the rail post is cast in place. Can you provide details as to how to remove and reinstall?
R. Yes, if the existing window replacement and mechanical equipment demo can be accomplished without removing the rail, then the existing rail can remain in place. If the rail is in conflict with either the window replacement or the mechanical equipment demo, then the rail shall be saw cut flush at the base and salvaged for
Page 3 of 7
reinstallation. Once the adjacent work is complete, the post holes shall be cored out a minimum of 1.5" greater than the post diameter. The rail posts shall be extended with galvanized steel pipe and epoxied into place at the cored post holes with a minimum 4” embedment.
Q. Please clarify the scope of work for the spec section 055000. R. Specification 055000 shall govern the exterior guardrail post extension (if
needed), and any other miscellaneous steel fabrications required throughout the course of the work.
Q. The only note saying to remove the suspended plaster ceiling is on B1/A501 but
field investigation shows it in M126 thru M131. Does it all have to be removed? R. Refer to Addendum 1 for clarification on suspended plaster ceiling demolition. Q. Some of the corridor walls have clay or salt glazed tile. Are these to be removed
as well as metal stud drywall? R. All existing partitions indicated to be removed on demolition plans shall be
removed, regardless of material. As noted at the prebid and in Addendum 1, Bidders are strongly encouraged to visit the project site prior to preparing their bid to familiarize themselves with existing conditions. Change orders will not be considered for work associated with conditions that are readily observable during the bid period.
The following requests for substitution were received, but were determined to not meet specification requirements, and are therefore NOT APPROVED for use on this project: 096723 - Florock FloroChip Epoxy Flake Flooring 224000 - Bradley Model S19-280D Emergency Eyewash Fixture PROJECT MANUAL Revise the following specification sections as described below: Section Modification 1.E Add paragraph 17.A.(4) to read “Upon completing demolition of existing ceilings
and overhead systems indicated to be removed, a pre-installation meeting shall be held on site to coordinate the work of the various trades. Attendees shall include the Architect, MEP Engineers, General Contractor, and all Subcontractors responsible for installing new work overhead including Mechanical, Electrical, Plumbing, and Fire Protection. The GC shall be responsible for documenting the discussion and distributing meeting minutes to the Owner and all attendees for record. MEPF coordination will be a standing agenda item for OAC meetings until the level of coordination deemed necessary by the General Contractor and the design team has been achieved.”
Revise paragraph 17.B. to indicate “Within sixty (60) days of Notice to
Proceed…” rather than “Within thirty (30) days of Notice to Proceed…” The timeline for coordination drawings has been extended to allow more time for demolition of existing ceilings and overhead systems indicated to be removed and the pre-installation meeting noted above.
Add paragraph 17.B.(4) to read “Coordination drawings may be compiled as
either a two-dimensional plan view or as a three-dimensional model.” Add paragraph 17.B.(5) to read “Representation of existing conditions may be
limited to major existing systems identified at the pre-installation meeting as
Page 4 of 7
representing a potential conflict with new work. Existing systems which do not represent a potential conflict with new work need not be represented.”
Add paragraph 17.B.(6) to read “Coordination drawings are intended to
demonstrate that the work of the various trades have been coordinated with each other and with existing conditions prior to installation. Each MEPF subcontractor shall review and sign-off on the coordination drawings prior to submitting to the design team for review.”
115313 Replace specification 115313 dated 11/06/17 in its entirety with revised
specification 115313 dated 11/27/17 attached. Subject to compliance with all other provisions of the specification, Bedcolab’s Vanguard Fume Hood, Hamilton Lab Solutions’ Concept Fume Hood, and Mott Manufacturing RFV2 Fume Hood are approved as equal to the specified manufacturers.
123553 Add paragraph 2.2A.6. to read “Hamilton Lab Solutions”. Hamilton Lab Solutions’
MAX Lab Bench System is approved as equal to the Basis of Design. 123554 Renumber paragraph 2.1A.a. and 2.1A.b. as “2.1A.2.” and “2.1A.3.” respectively. Add paragraph 2.1A.4. to read “Custom Stainless Products, inc.”. Subject to
compliance with all other provisions of the specification, Custom Stainless Products, inc. is approved as equal to the specified manufacturers.
Add paragraph 2.1A.5. to read “Kloppenberg.” Subject to compliance with all
other provisions of the specification, Kloppenberg Stainless Steel Lab Furnishings is approved as equal to the specified manufacturers.
123653 Add paragraph 2.1A.4. to read “American Epoxy Scientific.” Subject to
compliance with all other provisions of the specification, American Epoxy Scientific is approved as equal to the specified manufacturers.
Revise paragraph 2.3A. to read “Drop-in sinks molded from modified
thermosetting epoxy resin, specially compounded and oven cured and set with epoxy cement. Color shall match adjacent countertop. Physical properties shall be as described for epoxy resin countertops. Cove inside corners and pitch bottom to threaded drain outlet.” Sinks have been changed from undermount to drop-in installation.
Revise paragraph 2.3A.1. to read “SK-1: Size 25” long, 15” wide, 10” deep with
end outlet.” Revise paragraph 2.3A.2. to read “SK-2: Size 25” long, 15” wide, 10” deep with
end outlet.” 224000 Add paragraph 2.1F. to read “Emergency Eyewash”
1. Water Saver model #EWBF849R 2. Guardian Equipment model #GBF1849.”
230100 Delete paragraph 1.5A.15. which was added in Addendum #1. This paragraph
was interpreted as requiring a BIM model of all new and existing conditions, which was not the intent. See revisions to 1.E. Special Conditions section 17. “Project Coordination” above for further clarification on coordination requirements.
230700 Add paragraph 3.16D.2 to read “Ductwork located in Mechanical Room M130.”
Page 5 of 7
233113 Delete paragraph 2.9 Shop Prime Paint in its entirety. PROJECT DRAWINGS Revise the following Drawing Sheets as described below: Sheet Modification A150 Replace sheet A150 dated 11/06/17 in its entirety with revised sheet A150 dated
11/27/17 attached. Details E3 and C4 have been added to illustrate signage locations and installation requirements.
A201 Add a note at the existing exterior stair near Room M148A to read as follows:
“Existing guard rail to removed and salvaged for reinstallation if in conflict with window replacement or mechanical equipment demo indicated.”
A601 Revise detail A1 Level 1 RCP as per Sketch XA07 attached. RCP has been
revised to show Owner Furnished, Owner Installed Surgical Light Fixture. GC to coordinate new ceiling installation with OFOI fixture.
Add detail D5 as per Sketch XA09 attached. Exhaust piping tie-in in room M134A
has been clarified. A710 Revise detail C4 – Typ island casework U.C. lighting/ Pre installed electrical
outlets as per sketch XA05 attached. Elevation has been revised to coordinate lighting and power outlets on island casework.
Revise detail E6 – Typ island casework U.C. lighting/ Pre installed electrical
outlets as per sketch XA10 & XA11 attached. Elevation has been revised to coordinate lighting and power outlets on island casework.
A803 Revise detail E4 – North Elevation M144 as per Sketch XA08 attached. Elevation
has been revised to indicate Owner Furnished, Owner Installed control panel location for Owner Furnished, Owner Installed Surgical Light Fixture.
FPD103 Replace sheet FPD103 dated 11/06/2017 in its entirety with revised sheet
FPD103 dated 11/27/2017. Drawing has been revised to show the existing ceiling to remain, and adds General Note #1.
FP102 Replace sheet FP102 dated 11/06/2017 in its entirety with revised sheet FP102
dated 11/27/2017 attached. Relocation of an existing 6” Fire main will be required for renovation of Research Lab M148.
FP103 Add General Note #1 as follows: “1. The Contractor shall see Division #1 Special
Conditions for phasing of work schedule for this Alternate #2 Construction.” M101 Replace sheet M101 dated 11/06/17 in its entirety with revised sheet M101 dated
11/27/17 attached. Ductwork General Notes have been modified. Ductwork sizes have been added in Flex Research Lab M114.
M201 Replace sheet M201 dated 11/06/17 in its entirety with revised sheet M201 dated
11/27/17 attached. Ductwork General Notes have been modified. M602 Replace sheet M602 dated 11/06/17 in its entirety with revised sheet M602 dated
11/27/17 attached. General Exhaust Air Control Valve Schedule, Fume Exhaust Air Control Valve Schedule, and Supply Air Control Valve Schedule have been modified.
Page 6 of 7
M702 Replace sheet M702 dated 11/16/17 in its entirety with revised sheet M702 dated
11/27/17 attached. AHU 1-01 Control Diagram has been modified. M703 Replace sheet M703 dated 11/06/17 in its entirety with revised sheet M703 dated
11/27/17 attached. Laboratory Airflow Control System Schematic has been modified.
E301 Replace sheet E301 dated 11/06/17 in its entirety with revised sheet E301 dated
11/27/17 attached. Added note EP028 “Replacement of panel to occur after-hours during evenings, week-ends or during class break times listed elsewhere in the special conditions” to Panel P5. Removed note EP016 and device related to fume hoods phoenix controls from plan.
E401 Replace sheet E401 dated 11/06/17 in its entirety with revised sheet E401 dated
11/27/17 attached. Added device related to fume hood phoenix controls to plan. Added (2) Phoenix Valve Power Supply panels to Mechanical M130. Added (1) Phoenix Valve Power Supply panel to Mechanical M120. Added (1) Phoenix Valve Power Supply panels to existing electrical room adjacent to M148.
Revised note EH008: “PROVIDE 1 HP RATED TOGGLE STYLE, 120 V, 1
POLE, NEMA 1 SWITCH AS DISCONNECTING MEANS FOR PHOENIX VALVE POWER. PROVIDE ALL FINAL CONNECTIONS TO CONTROLLERS. REFER TO DETAIL 2, SHEET M703 FOR ADDITIONAL INFORMATION ON POWER SUPPLY.
Added note EH014 to fume hoods for phoenix controls: “PROVIDE TOGGLE
STYLE SWITCH AS DISCONNECTING MEANS AND MAKE FINAL CONNECTION TO PHOENIX VALVE CONTROLS. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF PHOENIX CONTROL PANEL PRIOR TO ROUGH-IN.”
Added note EH015 to differentiate between VAV power and phoenix valve power
supplies: “PROVIDE 1 HP RATED TOGGLE STYLE, 120 V, 1 POLE, NEMA 1 SWITCH AS DISCONNECTING MEANS FOR VAV UNITS. PROVIDE ALL FINAL CONNECTIONS TO CONTROLLERS. REFER TO DETAIL 2, SHEET M703 FOR ADDITIONAL INFORMATION.”
E801 Replace sheet E801 dated 11/06/17 in its entirety with revised sheet E801 dated
11/27/17 attached. Added approved equals to Luminaire Schedule for Fixture types C, XA, XB, XC, XD.
E802 Replace sheet E802 dated 11/06/17 in its entirety with revised sheet E802 dated
11/27/17 attached. Added circuit 35 to Panel 1PP-M148 E803 Replace sheet E802 dated 11/06/17 in its entirety with revised sheet E802 dated
11/27/17 attached. Added circuits 12, 14, and 16 to Panel 1PPA. ATTACHMENTS Specifications 115313 – Laboratory Fume Hoods Drawing Sketches (8.5x11) Sketch XA05 – Revise detail C4/A710 Sketch XA07 – Revise detail A1/A601 Sketch XA08 – Revise detail E4/A803
Page 7 of 7
Sketch XA09 – New detail D5/A601 Sketch XA10 – Revise detail E6/A710 Sketch XA11 – Revise detail E6/A710 Drawing Sheets (30x42) A150 – Typical Partitions, Signage & Interior Details FPD103 – Level 1 – East Zone Teaching Lab – Demolition Alternate Bid #2 FP102 – Level 1 – West Zone Fire Protection – New Work M101 – Level 1 Ductwork Plan – New Work M201 – Enlarged Mechanical Room Plans – New Work M602 – Schedules M702 – Controls M703 – Controls E301 – Level One – Power Floor Plan E401 – Level One – HVAC Power Floor Plan E801 – Lighting Schedules E802 – Panelboard Schedule E803 – Panelboard Schedule END OF ADDENDUM #2
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 1/9
SECTION 115313 – LABORATORY FUME HOODS
PART 1 - GENERAL
1.1 SUMMARY A. Section Includes:
1. Bench-top High-Performance Laboratory Fume Hoods. 2. Service fixtures (ie. water, gas, etc.) and electrical service fittings in fume hoods. 3. Piping and wiring within service fittings, light fixtures, switches, and other electrical devices. 4. Fume hood base support. Including acid storage and solvent storage cabinets. 5. Work Surfaces within fume hoods. 6. Laboratory sinks and cup sinks in fume hoods. 7. Filler panels for fume hoods.
B. Related Sections: 1. Division 22: Furnish and installation of plumbing utilities and final connections to fume hoods. 2. Division 23: Furnishing and installation of exhaust duct work and equipment, and final connection of
hoods. 3. Division 26: Furnishing and installation of electrical utilities and final connections to hoods.
C. This specification covers the requirements for the purchase of bench mounted laboratory fume hoods for use with remote exhaust blower systems.
1.2 SCOPE AND CLASSIFICATION 1. Bench-mounted laboratory fume hoods in widths as indicated on plans, minimum internal depth of
26.5”, and maximum external depth of 34.0” is required. 2. This specification sets the intent for quality, performance and appearance.
1.3 REFERENCES: A. The laboratory hoods must conform to the following regulations and standards.
1. SEFA 1-2010, Scientific Equipment and Furniture Association , Recommended Practices for Laboratory Fume Hoods
2. SEFA 8-2010, Recommended Practices for Laboratory Grade Metal Casework, 8.0 Cabinet Surface Finish Tests
3. NFPA 45-2011, National Fire Protection Association, Fire Protection for Laboratories Using Chemicals 4. ASTM E84-09C, ANSI 2.5, NFPA 255, UL 723, UBC 8-1 (42-1), Standard Test method for Surface
Burning Characteristics of Building Materials 5. ASHRAE 110-2016, American Society of Heating, Refrigerating, and Air-Conditioning Engineers,
Method of Testing Performance of Laboratory Fume Hoods 6. ANSI/AIHA Z9.5-2011, American Industrial Hygiene Association, Laboratory Ventilation 7. OSHA, Federal Register 29 CFR Part 1910, Occupational Safety & Health Administration, U.S.
Department of Labor, Occupational exposures to hazardous chemicals in laboratories. B. The laboratory fume hoods must carry the ETL listed mark for the following.
1. UL 61010-1 (formerly 3101-1), Underwriters Laboratories Inc., Electrical Equipment for Laboratory Use 2. CAN/CSA C22.2 No. 61010-1, Canadian Standards Association, Safety Requirements for Electrical
Equipment for Measurement, Control and Laboratory Use 3. UL 1805, Underwriters Laboratories Inc., Standard for Laboratory Hoods and Cabinets
1.4 PERFORMANCE REQUIREMENTS A. General Design Requirements (See Part 2 for details)
1. Fume hoods shall function as ventilated, enclosed workspaces, designed to capture, contain and exhaust fumes, vapors and particulate matter produced or generated within the enclosure.
2. Fume hood shall be factory designed to function as a variable air volume fume hood. 3. Structure and Materials of construction
a. Hoods are of double-wall construction b. Powder-coated, cold rolled steel exterior c. Galvanized steel support members d. Sheet molded composite panel internal liner
4. Baffles a. Baffle slot pattern designed to optimize face velocity profile. b. Moving or adjustable baffles are not acceptable
5. Sash a. Maximum opening is 28". b. Unobstructed viewing height is 37.5".
6. Airfoil:
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 2/9
a. Hoods are provided with an air foil across the bottom of the sash area to allow airflow into the hood regardless of sash position.
7. Besides the exhaust blower, no additional blowers are required for specified containment. 8. Access for maintenance is from both the front, interior, and exterior sides of the hood. 9. Services:
a. Furnishing and delivering all service outlets, accessory fittings, electrical receptacles and switches, as listed in these specifications, equipment schedules or as shown on drawings.
b. Plumbing fittings mounted on the fume hood superstructures shall be pre-plumbed. c. Final plumbing and electrical connections are the responsibility of those contractors fulfilling
requirements of Divisions 22 and 26. d. All electrical services are pre-wired to a single point internal junction box at the top right of the
hood. e. Refer to drawings for location of service fittings ensuring access for future maintenance.
10. Hoods without service fixtures pass through a 38” opening without disassembly.
1.5 CONTAINMENT A. The purpose of this section is to set a standard of performance for the bidder’s laboratory fume hood
before award of contract, and may not necessarily represent the operating conditions of the hoods after installation. Before or after award of contract, owners may require representative witness to said testing at their option, with failure to meet passing criteria as grounds for rejection of the bidder. Test data shall be provided at no cost to the owner.
B. Hood shall be tested to ASHRAE 110 test method. C. Average Face Velocity: Face velocity average shall be 60 fpm, plus or minus 5%. D. Efficiencies
1. The fume hood shall demonstrate a minimization of the volumetric rate of air (CFM) requirement at any given face velocity. Required CFM to achieve desired face velocity shall not exceed that which is noted on sheet M602.
2. The fume hood shall demonstrate a minimization of static pressure loss (inches of H2O) at any given CFM. Refer to sheet M602 for static pressures.
E. Illumination: Shall be a minimum average of 80 foot-candles inside the work area. Work area is defined as the area inside the lined portion of the fume hood, from the face of baffle to sash plane, from interior left to interior right, and from the work surface to a height of 28 inches.
F. Materials of Construction: Interior and Exterior materials of construction and finishes shall meet the requirements in Part 2 of this specification.
1.6 QUALITY ASSURANCE A. Fume hoods shall be designed, including comprehensive engineering analysis, by a qualified, licensed
Professional Engineer. B. Manufacturer’s Qualifications
1. ISO 9001 Certified manufacturing plant and processes. 2. Ten installations of equal or larger size and requirements. Provide contact at each.
C. Manufacturer's warranty against defects in material or workmanship on its fume hoods will be for 1 year from date of installation or 2 years from date of purchase, whichever is sooner, and includes replacement of parts (except lamps) and labor.
1.7 ACTION SUBMITTALS A. Laboratory hood specification sheets and product manuals shall be submitted by the hood manufacturer
upon request, and include safe and proper operation and maintenance information. B. Shop Drawings: Include plans, elevations, sections, and details.
1. Indicate details for anchoring fume hoods to permanent building construction including locations of blocking and other supports.
2. Indicate locations and types of service fittings together with associated service supply connection required.
3. Indicate duct connections, electrical connections, and locations of access panels. 4. Include roughing-in information for mechanical, plumbing, and electrical connections. 5. Provide face opening, volumetric rates, and static pressure drop data.
C. Submit a document detailing the information supplied on the Hood Safety Practices Label to verify compliance to specifications.
1.8 INFORMATIONAL SUBMITTALS A. Product Test Reports: Showing compliance with specified performance requirements, including NEBB
representative test report as defined previously. B. Independent validation:
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 3/9
1. Written verification that the laboratory fume hoods carry the ETL listed mark for the following. a. UL 61010-1 (formerly 3101-1), Underwriters Laboratories Inc., Electrical Equipment for Lab Use. b. UL 1805, Underwriters Laboratories Inc., Standard for Laboratory Hoods and Cabinets
2. Written verification that 230 volt model fume hoods carry the CE conformity marking as required by the Council of European Communities.
3. Written verification from an outside testing agency confirming coating compliance to SEFA 8-2010, Recommended Practices for Laboratory Grade Metal Casework, 8.0 Cabinet Surface Finish Tests
C. Documentation of ISO 9001 Certified manufacturing plant and processes. D. List of five installations (of equal or larger size and requirements) is available upon request. Provide
contact at each.
1.9 MATERIAL SUBMITTALS A. Samples for Verification: of the hood exterior wall material, interior liner and baffle material, epoxy work
surface material, and color selection chips are available from the hood manufacturer upon request.
1.10 PROJECT CONDITIONS A. Protect finished surfaces during handling and installation with protective covering of polyethylene film or
another suitable material. B. Schedule delivery of equipment so that spaces are sufficiently complete that equipment can be installed
immediately following delivery. C. Environmental Limitations: Do not deliver or install fume hoods until building is enclosed, wet work and
utility roughing-in are complete, and HVAC system is operating and maintaining temperature and relative humidity at occupancy levels during the remainder of the construction period.
PART 2 - MANUFACTURERS
2.1 Manufacturers: Subject to compliance with the requirements of this specification, available manufacturers offer products that may be incorporated into the Work include:
A. Kewaunee Scientific Corporation, Statesville, North Carolina. B. Labconco XL Hood, Kansas City, Missouri. C. AIR Master Systems Corp. D. CIF Ascent Lab APEX Fume Hoods, Vaughan, Ontario, Canada. E. Mott RFV2 High Efficiency Fume Hood, Brantford, Ontario, Canada. F. Bedcolab Vanguard Fume Hood, Laval, Quebec, Canada. G. Hamilton Laboratory Solutions Concept Fume Hood (no hook & loop), Manitowoc, Wisconsin.
2.2 MATERIALS A. Hood Interior Liner and Baffle
1. Liner material must comply with UL 1805, and be listed within NRTL test report as proof of compliance. 2. General Material Properties
a. Nonflammable, corrosion and chemical-resistant b. Sheet molded homogenous polyester panels c. Minimum thickness is 3/16" d. Smooth, white finish
3. Mechanical Properties a. Tensile Strength: 7,500 PSI b. Tensile Modulus: 1.7 x 10^6 PSI c. Flexural Strength: 21,000 PSI d. Flexural Strength at 130 degrees C: 12,900 PSI e. Compressive Strength: 32,500 PSI f. IZOD Impact Strength (Notched): 8.4 Ft Lb/in (4.5 J/cm)
4. Flame and Smoke Characteristics a. Flame retardant, self-extinguishing, with a flame spread rating of 25 or less in accordance with
ASTM-E84 b. Oxygen Index: 35% c. Smoke Density: 115
5. Physical Properties a. Water Absorption: 0.4% b. Specific Gravity: 4.81 c. Coefficient of Thermal Expansion: 2 In/in/ degree C x 10^-5 d. Thermal Conductivity: 1.9 BTU/Hr/Ft^2/In/degree F
6. Chemical Resistance a. Splash and Spill Resistance:
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 4/9
1) Suspend sample panel in a vertical plane 2) Apply five drops of each reagent listed with an eyedropper 3) Apply liquid reagents at top of panel and allow to flow down full panel height
7. Fume Resistance: a. Place 25 milliliters of reagent into 100 milliliters beakers and position panel over beaker tops in the
proper sequence. Ensure beaker pouring lip permits air to enter the interior atmosphere. b. After 24 hours remove panel, flush with water, clean with detergent, rinse, wipe dry and evaluate
8. Evaluation ratings: Change in surface finish and function shall be described by the following ratings a. No Effect: No change in color or gloss b. Excellent: Slight detectable change in color or gloss, but no change to the function or life of the
work surface material c. Good: Clearly discernible change in color or gloss, but no significant impairment of function or life d. Fair: Objectionable change in appearance due to surface discoloration or etch, possibly resulting in
deterioration of function over an extended period e. Failure: Pitting, cratering or erosion of work surface material; obvious and significant deterioration
9. Required minimum results for each reagent (Reagent: Fume Resistance Rating, Splash and Spill Resistance Rating) a. Hydrochloric Acid (37%): 2,1 b. Sulfuric Acid (33%): 2,1 c. Sulfuric Acid (77%): 1,1 d. Sulfuric Acid (96%): 1,2 e. Formic Acid (90%): 2,1 f. Nitric Acid (20%): 2,2 g. Nitric Acid (30%): 1,2 h. Nitric Acid (70%): 3,2 i. Hydrofluoric Acid (48%): 2,2 j. Phosphoric Acid (85%): 1,1 k. Chromic Acid (60%): 1,4 l. Acetic Acid (98%): 1,1 m. Ammonium Hydroxide (20%): 1,1 n. Sodium Hydroxide (10%): 1,1 o. Sodium Hydroxide (20%): 1,3 p. Sodium Hydroxide (40%): 1,3 q. Sodium Hydroxide Flake: 1,- r. Sodium Sulfide: 1,1 s. Zinc Chloride: 2,1 t. Tincture of Iodine: 3,3 u. Silver Nitrate: 2,1 v. Methyl Alcohol: 1,1 w. Ethyl Alcohol: 1,1 x. Butyl Alcohol: 1,1 y. Benzene: 1,1 z. Xylene: 1,1 aa. Toluene: 1,1 bb. Gasoline: 1,1 cc. Dichloro Acetic Acid: 2,2 dd. Dimethyl Formanide: 2,2 ee. Ethyl Acetate: 1,1 ff. Amyl Acetate: 1,1 gg. Acetone: 1,1 hh. Chloroform: 1,1 ii. Carbon Tetrachloride: 1,1 jj. Phenol: 2,2 kk. Cresol: 1,1 ll. Formaldehyde: 1,1 mm. Trichloroethylene: 1,1 nn. Ethyl Ether: 1,1 oo. Furfural: 1,3 pp. Methylene Chloride: 1,1 qq. Mono Chloro Benzene: 1,1 rr. Dioxane: 1,1
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 5/9
ss. Methyl Ethyl Ketone: 1,1 tt. Acid Dichromate: 1,2 uu. Hydrogen Peroxide: 1,1 vv. Napthalene: 1,1
B. Sheet Steel 1. Side panels and access panels 20-gauge (or heavier) sheet steel. 2. Hood corner posts are 16-gauge sheet steel. 3. Ceiling enclosure panels are 18 gauge sheet steel. 4. Cold-rolled, commercial steel (CS) sheet, complying with ASTM A 1008/A 1008M.
C. Chemical Resistant Finish 1. General: Prepare, treat, and finish welded assemblies after welding. Prepare, treat, and finish
components that are to be assembled with mechanical fasteners before assembling. 2. Chemical and Physical Resistance of Finish System: Finish complies with acceptance levels of cabinet
surface finish tests in SEFA 8. Third party validation required. 3. Powder-coat process required. Paint processes that release Volatile Organic Compounds (VOC) are
not acceptable 4. Color for Fume Hood Finish:
a. To be selected from manufacturer’s full range of standard colors. D. Safety Glass
1. Tempered a. Clarity and temper test to be as specified in latest edition of Glass Tempering Association,
Engineering Standards Manual, Section 8.1. b. Surface and interior visible quality to be as specified per ASTM C 1036, Standard Specification for
Flat Glass, Table 4, Quality level Q3. E. Superstructure:
1. Self-supporting, rigid structural assembly, to support inner wall consisting of fume hood liner and outer wall of sheet metal exterior.
2. Fabricated from galvanized steel. 3. Space shall accommodate fume hood wiring and plumbing components for service fixtures. 4. Access to fixture valves concealed in wall provided by exterior removable access panels, gasket
access panels on the inside liner walls, or through removable access panels on the front posts. F. Exterior
1. Fabricate from steel sheet with component parts screwed together. 2. Apply chemical-resistant finish to interior and exterior surfaces of component parts before assembly. 3. Interchangeable side panels shall lift off without the use of tools to allow access to plumbing lines,
service fittings, electrical wiring, counterbalance sash weights, and light fixtures. Exposed fasteners or hardware, and Velcro type fasteners, are not acceptable.
4. Corner posts a. Pre-punched and plugged to accommodate up to 4 service fixtures per side b. All services are accessible from the front of the hood. c. Aerodynamic shape d. Accommodate two electrical duplexes per side. e. Right hand corner post includes electrical switches and pre-cut for Airflow monitor installation. f. Un-used penetrations shall be plugged.
5. Top and sides of face opening to provide an aerodynamic shape to ensure smooth, even flow of air into fume hood.
6. Panel above header shall be removable without the use of tools to allow access to mechanical connection, electrical wiring, counterbalance sash weights, and light fixtures. Exposed fasteners or hardware, and “hook-and-loop” type fasteners, are not acceptable.
G. Dimensions 1. Overall exterior dimensions are as follows:
a. 6 foot nominal width: 72” w x 59” h x 34” max 2. Overall interior dimensions are as follows:
a. 6 foot nominal width: 62.1” w x 48” h x 26.5” min H. Hood Liner
1. Adhere interior liner components to superstructure. 2. Stainless steel fasteners shall be used on the interior ceiling for structural integrity. 3. Fasteners exposed to chemical environment are not acceptable. 4. Punch fume hood lining side panels to receive four service fittings, for use with remote controls, per
side. Provide removable plug buttons for holes not used for indicated fittings.
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 6/9
5. Each side wall shall include an oval interior access panel to provide access to the side wall of the fume hood for plumbing service access. Access panel material shall be that of the liner, and gasketed to form a vapor proof seal.
I. Hood Baffle 1. Baffle system shall be designed to optimize the face velocity profile, and to capture a wide range of
gaseous densities without adjustment or moving components. 2. Shall provide a continuous horizontal slot at the work surface. Baffle panels shall have multiple
horizontal slots, with a chamfered entry. Slot pattern shall be proven to optimize face velocity profile. 3. The baffle system shall be constructed with the same material as the fume hood liner. 4. The baffles shall be removable for cleaning. The primary baffles shall be three pieces to allow removal
without the use of tools. 5. Exposed components to be non-metallic. Metal components exposed to chemical environment are not
acceptable. 6. Moving parts or adjustment of any kind is not acceptable.
J. Exhaust Connection 1. 316 stainless steel with Chemical-Resistant Finish 2. 12.81" ID to accommodate any 12” nominal duct without the need for a transition adapter. Additional
components required to accommodate 12” nominal mechanical system are not acceptable. 3. Ducting shall go inside the duct collar to ensure condensate travels into the hood and evaporates. Duct
collars that allow duct connection over the collar are not acceptable. K. Airfoil
1. Cold Rolled Steel with Chemical-Resistant Finish. 2. Airfoil shall have an aerodynamic radius to sweep the air into the hood with minimal turbulence. Airfoil
directs airflow across work top to remove heavier-than-air gases. 3. Foil must extend back under the sash to prevent closure of the lower by-pass opening when the sash
is in the fully closed position, directly on top of the airfoil. L. Sash Assembly
1. Glass: Fully tempered safety glass with unobstructed, side-to-side view of fume hood interior and service fixture connections.
2. Dimensions: The full sash opening height is 28", the total unobstructed viewing height is 37.5" measured from the work surface.
3. Sash Tracks: Steel with Chemical Resistant Finish. Shall include bump stops for opening and closing. 4. Sash Handle: extruded aluminum with Chemical Resistant Finish. The handle is ergonomic in design
and is easy to grasp when operating 5. Sash guides: Corrosion resistant extruded poly-vinyl chloride. 6. Sash System
a. Vertical Sash with intelligence b. Hoods have a single vertical sash counterbalanced by a single weight. c. Sash and weight to be connected via #35 chains. d. Rear sprockets shall be connected via timing shaft to prevent sash tilting and permit operation at
any point along full width sash handle. e. Design system to hold sash at any position without creep and to prevent sash drop in the event of
chain failure. f. Sash shall only rise manually. g. Operating height shall be configurable in the field. h. Sash shall automatically close without occupancy after a user set delay period has elapsed. i. Optical sensor shall prevent sash from disturbing an obstruction to the plane of the sash upon
closure. j. Do not include a defeatable, and automatically resetting sash stop on hoods with sash intelligence.
M. Electrical Components 1. Lighting
a. Provide UL Listed, LED lighting systems. b. Vapor-Proof: all electrical components shall be outside of the contaminated air space. Lighting shall
be located behind a laminated safety glass shield, sealed to the top of the hood liner. c. The LED light assemblies shall be serviceable from outside the fume hood cavity, without the use
of tools. 2. Light switch to be included on the lower right corner post, at heights compliant with the Americans with
Disabilities Act (ADA). N. Blower Switch
1. Hoods shall be provided without a blower switch, as they will share a single mechanical system with other hoods.
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 7/9
O. Electrical Receptacles 1. The hoods shall accommodate up to four (two per corner post) electrical receptacles. 2. 115 volt, 60 Hz, three-wire polarized and grounded electrical duplex, with Ground Fault Circuit
Interruption (GFCI) 3. Receptacles shall be individually wired to field wiring box, and each rated at 20 Amperes. 4. Cover plates shall be acid resistant thermoplastic.
P. Wiring 1. Every electrical component shall be individually wired to a single point internal field wiring box
(including individual duplexes/receptacles). 2. Field wiring box to be 7” x 4” x 2.5”, grounded, and have (12) 7/8” diameter knock out penetrations. 3. Final wiring and circuit dedication is to be by others. 4. Each receptacle circuit shall accommodate being wired to a dedicated building circuit rated at 20A, or
the receptacles ganged together on a building circuit with the total load not exceeding 20 Amperes. Q. Fume hood to have third party validation of compliance to UL 1805 and UL 61010-1 by a Nationally
Recognized Testing Laboratory (NRTL) R. By-Pass Opening
1. Shall offer a significant restriction to the by-pass opening to allow the use of a VAV mechanical system. S. Hood Safety Practices Label: Corrosion resistant plate attached to the left corner post of the fume hood
with the following Hood Safety Practices: 1. For use with substances that produce hazardous levels of airborne chemicals: gas, fumes, vapors,
dust 2. Do not put your head in the hood. 3. Minimize drafts and sudden movements in front of the hood. 4. Work a minimum of six inches inside the hood. 5. Elevate equipment above the work surface. 6. Keep sill and baffle unobstructed. 7. Do not use the hood for storage. 8. Adjust the sash to smallest opening possible when in use. 9. Close sash when unattended. 10. Do not remove any of the hood components. 11. Do not place flammable solvents near heat, flame or sparks. 12. Do not evaporate large amounts of flammable liquids. 13. Wipe up spills immediately. 14. Routinely validate airflow. 15. If the ventilation system malfunctions, or airflow alarm indicates unsafe condition, close sash and
discontinue hood operation immediately-call for help. 16. Do not use with Biohazards or Perchloric Acid
2.3 FUME HOOD ACCESSORIES A. Service Fixtures: Color-coded hose nozzle outlets and valves mounted inside the fume hood and
controlled from the exterior with color-coded index handles 1. The hoods are equipped with cold water gooseneck on the left, and vacuum and air on right. 2. Hose connectors located inside the fume hood cavity are chemically-resistant, glass-filled
polypropylene with 6 serrations. 3. Service lines shall be factory installed from valve to outlet
a. Copper tubing unless otherwise noted b. Connections shall be made with quick-connect compression fittings on the inlet and outlet of the
valve body, soldered and brazed connections not easily disassembled are not acceptable. c. Services pre-piped to the top of the hood d. Refer to A710 for location of service fittings. Place services on end with access for maintenance –
see plans. 4. Valves
a. Extruded brass valve and rotating seat, TFE-coated silicone bronze stem and TFE packing. b. Fixture handles are plastic and color coded as well as labeled for the designated type of service. c. Fixtures are rated at maximum pressure of 200 psi. d. Coefficient of flow for the valve, Cv=0.43. e. Valves are front loaded, located on the fume hood corner post for remote use, and include:
1) Cold tap water with gooseneck (flow rate 3.5 GPM or 13.25 LPM at 67 psi at full open 2) Air (theoretical flow rate of 59 CFM at 100psi) 3) Vacuum (theoretical flow rate of 6 CFM at 10 psi)
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 8/9
B. Tissue Screen: Provide epoxy-coated, stainless-steel screen at bottom baffle opening to prevent paper from being drawn into the exhaust plenum behind baffles.
C. Ceiling Enclosure Panels: 1. Provide filler panels matching fume hood exterior to enclose space above fume hoods at front and
sides of fume hoods and extending from tops of fume hoods to ceiling. 2. Exposed fasteners are not acceptable. 3. Height adjustment to be within the following range.
a. 11.0” - 14.0” D. Face Velocity Monitor/Alarm
1. Variable Air Volume (VAV) Prepared a. Fume hoods shall come factory prepared with the proper cutouts and brackets to field mount air
flow monitor alarm provided and installed by Division 26.
2.4 WORK SURFACE A. 1.25” thick, molded from solid modified epoxy resin, with smooth, non-specular, black finish. B. One inch radius front edge for optimal fume hood performance. C. 3/8” dished area to match the fume hood interior work space and form a water tight pan for spill
containment. D. Include a 2.5” diameter hole on each side for service pass-through and piping. Hole to be covered by
hood superstructure upon installation. E. Include two 1.5” diameter penetrations to accommodate base cabinet venting. Holes to be located outside
of dished area and under the fume hood baffles. Include plugs. F. Physical Properties:
1. Flexural Strength: Not less than 10,000 psi. 2. Modulus of Elasticity: Not less than 2,000,000 psi. 3. Hardness (Rockwell M): Not less than 100. 4. Water Absorption (24 Hours): Not more than 0.02 percent. 5. Heat Distortion Point: Not less than 260 deg F (127 deg C). 6. Flame-Spread Index: 25 or less per ASTM E 84.
G. Cupsink 1. 3” x 6” dimension, polypropylene construction 2. Provide with strainers and tailpieces, NPS 1-1/2 (DN 40)To sit flush with dished area of work surface 4. Cupsink to be located:
a. Refer to A710 for location of services.
2.5 SUPPORTING BASE CABINETS A. Base cabinets shall be in depths of 22", widths, quantities, and types called out in the drawings, and meet
the requirements of this specification. B. Construction requirements for all cabinets
1. Exterior construction is 18 gauge (or heavier) cold rolled sheet steel with Chemical Resistant Finish. 2. Hinges are 10 gauge (or heavier) plate with self-clinching pilot pin. Knuckle, bullet, or piano type hinges
are not accepted. 3. The rear panel will feature a 12" x 8" removable plumbing access panel. 4. Units 24" wide or less have only one door. 5. Each cabinet includes four leveling feet. 6. Capable of supporting up to 800 pounds. 7. A filler panel is required to increases the cabinet depth to work surface depth.
C. Acid Storage 1. Overall exterior dimensions:
a. 36" w x 22" d x 34” max. 2. Completely lined with a polyethylene corrosion resistant liner. The liner is 3/16" thick, with a vacuum
formed PVC liner pan at the bottom to contain spills. Each door has a 3/16" sheet polyethylene liner. 3. The cabinet is labeled: "ACID". 4. Flush pull handles are ABS, low gloss black. 5. Each cabinet is vented into the fume hood with a 1-1/2" vent pipe. It should provide a positive airflow
directly into the fume hood exhaust system. 6. Supply an epoxy coated steel shelf with PVC liner pan if indicated in the schedule. 7. Acid cabinets with louvers are not acceptable
D. Solvent Storage 1. Overall exterior dimensions:
a. 36" w x 22" d x 34” max. 2. Solvent storage cabinets are specifically designed for the storage of flammable & combustible liquids.
MU Medical Science Building Addendum 2 First Floor Research Laboratory Renovation November 27, 2017 CP171091
LABORATORY FUME HOODS 115313 - 9/9
3. Solvent Storage Cabinet must be compliant with NFPA 30 “Flammability and Combustible Liquids Code.”
4. Cabinets 30" wide and greater shall be tested and approved by Factory Mutual to meet Factory Mutual Approval Standard 6050.
5. The bottoms, top, sides, and doors are fabricated of 18 gauge steel and are all double panel construction with a 1-1/2" air space between panels.
6. All joints are welded or screwed to provide a rigid enclosure. A 2" deep liquid tight pan that covers the entire bottom of the cabinet is furnished to contain liquid leaks and spills.
7. A full-depth, 18 gauge steel, adjustable shelf is also provided. Shelves are sealed leak tight. 8. Two diametrically opposed flame arrestor vents with spark screens are provided in the back of the
cabinet, as well as a grounding screw. 9. The cabinet has an interior finish same as the exterior. 10. The cabinet is labeled: "FLAMMABLE - KEEP FIRE AWAY". 11. The right hand door shall have a three point latching device. 12. Door handles include a key lock. Handles are locking lever handles with bright chrome finish.
PART 3 - EXECUTION
3.1 EXAMINATION A. Examine areas, with installer present, for compliance with requirements for installation tolerances and
other conditions affecting performance of fume hoods. B. Coordinate with other trades for the proper and correct installation of plumbing and electrical rough-in and
for rough opening dimensions required for the installation of the hood. C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION A. General: Install fume hoods according to shop drawings and manufacturer's written instructions. B. Install level, plumb, and true; shim as required, using concealed shims, and securely anchor to building
and adjacent laboratory casework. C. Securely attach access panels, but provide for easy removal and secure reattachment. Where fume
hoods abut other finished work, apply filler strips and scribe for accurate fit, with fasteners concealed where practical.
D. Neighboring splash blocks shall not be attached directly to the hood. E. Install according to standards required by authority having jurisdiction. F. Sequence installations to ensure utility connections are achieved in an orderly and expeditious manner. G. Touch up minor damaged surfaces caused by installation. Replace damaged components as directed by
Architect.
3.3 FIELD QUALITY CONTROL A. NFPA 45 requires that fume hoods be field tested when installed. B. Field test installed fume hoods according to ASHRAE 110 to verify compliance with performance
requirements. C. Adjust fume hoods, hood exhaust fans, building's HVAC system, and make other corrections until tested
hoods perform as specified in fume hood schedule. D. After making corrections, retest fume hoods that failed to perform as specified. E. Coordinate commissioning/field testing sequence with control valve programmer and Owner to ensure
fume hood sash settings and control valves are operating as intended.
3.4 ADJUSTING AND CLEANING A. Adjust moving parts for smooth, near silent, accurate sash operation with one hand. Adjust sashes for
uniform contact of rubber bumpers. Verify that counterbalances operate without interference. B. Clean finished surfaces, including both sides of glass; touch up as required; and remove or refinish
damaged or soiled areas to match original factory finish, as approved by Architect. C. Clean adjacent construction and surfaces that may have been soiled in the course of installation of work in
this section. D. Provide all necessary protective measures to prevent exposure of equipment and surfaces from exposure
to other construction activity. E. Advise contractor of procedures and precautions for protection of material and installed equipment and
casework from damage by work of other trades.
END OF SECTION 115313
123553 FIXED PANEL FOR OUTLETS
123553PATHWAY INSIDE CASEWORK FOR U.C.LIGHTING TOPLUG INTO NEW OUTLET.
123553 FIXED PANEL FOR OUTLETS
123553 POWER WIREMOLD
123553 REAGENT SHELVING
MEPELECTRICAL POWER TO BE RUN TO OUTLETS,COORDINATE WITH ELECTRICAL DRAWINGS 1&2 ONE301 FOR CIRCUITS
123553REMOVEABLE AS REQUIRED TO ACCESS CHASE BEHINDCASEWORK
1
MEP
ELECTRICAL RACEWAY WITH PREINSTALLEDELECTRICAL OUTLETS - INCLUDES CORD AND PLUGDOWN UNDER COUNTER TOP TO KNEE SPACE.ELECTRICAL CONTRACTOR TO PROVIDE OUTLETSUNDER COUNTER TOP.
123553 FRONT LIP, NO BACK
12355312" WIDE VERTICAL SUPPORT. SUPPORT NOTREQUIRED TO GO TO FLOOR.2'
-0"
123553MIRROR THIS SIDE FOR OUTLETS, U.C. LIGHTS, POWERPLUGS, ETC...
2
2
1
1
1
PROJECT NUMBER:
1900 W. 47th PlaceSuite 300Westwood, Kansas66205p: 913.362.6500www.pgav.com
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/27/1753474
Medical Science First Floor Research Laboratory Renovation
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP171091
ADDENDUM 02
XA05
1" = 1'-0" C4/A710PRE INSTALLED ELEC OUTLETS
ANATOMY
CADAVER LAB
M144
2' x 2' ACT
+8'
- 0
"
439
438
OW
NE
R F
UR
NIS
HE
D, O
WN
ER
INS
TA
LLE
D S
UR
GIC
AL
LIG
HT
FIX
TU
RE
. G
.C. T
O C
OO
RD
INA
TE
NE
W C
EIL
ING
INS
TA
LLA
TIO
NW
ITH
OF
OI F
IXT
UR
E A
ND
AN
Y N
EW
/ EX
IST
ING
ME
P IT
EM
ST
HA
T IM
PE
DE
ST
RU
CT
UR
E F
OR
LIG
HT
.
1
CO
NT
RO
LLE
R, R
E: E
LEV
AT
ION
1
PROJECT NUMBER:
1900 W. 47th PlaceSuite 300Westwood, Kansas66205p: 913.362.6500www.pgav.com
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/27/1753474
Medical Science First Floor Research Laboratory Renovation
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP171091
ADDENDUM 02
XA07
3/1
6"
= 1
'-0"A
1/A
601
LE
VE
L 1
RC
P P
LA
N
OFOI
OFOI
NOTE: PICTURES FORREFERENCE OFEXISTING LIGHT
FREEZE
R A
OFO
I
123554
RELO
CATED S.S. C
ASEWORK FROM 148
TV, O
FOI
MEP
NEW ELE
CTRICAL RACEWAY
123554
NEW S.S. C
SWK & COUNTERTOP (6'-3")
123554
NEW S.S. C
SWK
123554
NEW S.S. C
OUNTERTOP - F.V. E
XISTING
A710
B6
CONTROLLER, R
E:
PICTURE BELO
WCOORDINATE W
/ELE
CTRICAL
1
PROJECT NUMBER:
1900 W. 47th PlaceSuite 300Westwood, Kansas66205p: 913.362.6500www.pgav.com
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/27/1753474
Medical Science First Floor Research Laboratory Renovation
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP171091
ADDENDUM 02
XA08
1/4
" =
1'-0"E
4/A
803
NO
RT
H E
LE
VA
TIO
N -
M144
Owner Furnished, Owner
Installed (OFOI) control panel
location for Owner Furnished,
Owner Installed (OFOI)
Surgical Light Fixture
1
M
7
8
* NOTE EXISTING EXHAUST SHAFTSSCOPE OF WORK:
1. EXHAUST DUCTWORK TO BESECURED AT FLOOR AS REQUIREDFOR NEW INSTALLATION. RE:MECH FOR MORE INFORMATION.2. REMOVE WALL AS REQUIRED TOINSTALL NEW MEP WORK.3. PATCH/ REPAIR EXISTING WALLBACK TO MATCH EXISTING.4. PAINT BACK WALL FROMCORNER TO CORNER AT NEW WORK.
M250
OFFICE
M250
514
436
1
EXHAUST PIPINGTIE-IN - 1STFLOOR NEWROOM M134A
PROJECT NUMBER:
1900 W. 47th PlaceSuite 300Westwood, Kansas66205p: 913.362.6500www.pgav.com
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/27/1753474
Medical Science First Floor Research Laboratory Renovation
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP171091
ADDENDUM 02
XA09
3/16" = 1'-0" D5/A601LEVEL 2 - EXHAUST PIPING TIE IN
C4A710
6"1/2"
LA
LV
123553LED U.C.LIGHTING BY CASEWORK MANUFACTURER,PLUG IN PER DIAGRAM.
MEP
ELECTRICAL RACEWAY WITH PREINSTALLEDELECTRICAL OUTLETS - INCLUDES CORD AND PLUGDOWN UNDER COUNTER TOP TO KNEE SPACE.ELECTRICAL CONTRACTOR TO PROVIDE OUTLETSUNDER COUNTER TOP.
MEPELECTRICAL POWER TO BE RUN TO OUTLETS,COORDINATE WITH ELECTRICAL DRAWINGS 1&2 ONE301 FOR CIRCUITS
45"WD
PNL
123553REMOVEABLE AS REQUIRED TO ACCESS CHASE BEHINDCASEWORK, TYP AT ISLAND CASEWORK
123553 FIXED PANEL FOR OUTLETS
2
PROJECT NUMBER:
1900 W. 47th PlaceSuite 300Westwood, Kansas66205p: 913.362.6500www.pgav.com
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/27/1753474
Medical Science First Floor Research Laboratory Renovation
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP171091
ADDENDUM 02
XA10
1" = 1'-0" E6/A710TYP ISLAND CASEWORK
NOTE: OUTLETS AND CORDS FOR LIGHTING REMOVED ATTHIS LOCATIONS, RE: XA11 FOR LOCATION OF OUTLETFOR LIGHTING. LIGHTING TO HAVE ROCKER SWITCHFOR INDIVIDUAL ABILITY TO TURN ON AND OFF LIGHTS
AT ALL EACH REAGENT SHELVING SECTION.
123553SERVICE CHASE
LA
LV
LG
123553LED U.C.LIGHTING BY CASEWORK MANUFACTURER,PLUG IN PER DIAGRAM.
MEPELECTRICAL POWER TO BE RUN TO OUTLETS,COORDINATE WITH ELECTRICAL DRAWINGS 1&2 ONE301 FOR CIRCUITS
MEP
ELECTRICAL RACEWAY WITH PREINSTALLEDELECTRICAL OUTLETS - INCLUDES PRE WIRING DOWNUNDER COUNTER TOP TO KNEE SPACE ELECTRICALOUTLEY/ CONNECTION BOX / HARD WIRES
MEPELECTRICAL POWER TO BE RUN TO JUNCTION BOX,COORDINATE WITH ELECTRICAL DRAWINGS
123553PATHWAY INSIDE CASEWORK FOR U.C.LIGHTING TOPLUG INTO NEW OUTLET. DAISY CHAIN LIGTHS ANDPROVIDE ROCKER SWITCH AT EACH SECTION.
42"WD
PNL
123553REMOVEABLE AS REQUIRED TO ACCESS CHASE BEHINDCASEWORK, TYP AT ISLAND CASEWORK
123553 FIXED PANEL FOR OUTLETS
2
PROJECT NUMBER:
1900 W. 47th PlaceSuite 300Westwood, Kansas66205p: 913.362.6500www.pgav.com
Plumbing and Mechanical Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
(816) 421-0950
11/27/1753474
Medical Science First Floor Research Laboratory Renovation
UNIVERSITY OF MISSOURIFOR: The Curators of the University of Missouri - Project No: CP171091
ADDENDUM 02
XA11
1" = 1'-0" E6/A710TYP ISLAND CASEWORK
NOTE: OUTLETS AND CORDS FOR LIGHTING REMOVED ATTHIS LOCATIONS, RE: XA11 FOR LOCATION OF OUTLETFOR LIGHTING. LIGHTING TO HAVE ROCKER SWITCHFOR INDIVIDUAL ABILITY TO TURN ON AND OFF LIGHTS
AT ALL EACH REAGENT SHELVING SECTION.
CYLCYL
CFH
01
CYL
CFH
02
CYLCF
H 01
CYL
CYL
CFH 01
CFH 01
CYL
CYL
CYLCYL
CYLCYL
CYLCYL
CYLCYL
1/2"
NOTE: CONTROL JOINTS ONLY SHOWN ON PLANS &ELEVS. WHERE LOCATION-CRITICAL. REFER TO SPECSFOR PRESECRIPTIVE REQUIREMENTS FOR PLACEMENTOF ADDITIONAL CONTROL JOINTS.
GYP. WALL DETAIL - CONTROL JOINT "CJ"
092216 WALL PER TYPE
079200 PAINTABLE SEALANT, PAINT TOMATCH WALL U.N.O.
092216 1/2" CONTROL JOINT SIM. TOUSG #093
092216 FRAMING PER WALL TYPE
PERSPEC.
PER
SPEC
.
GYP. WALL DETAIL - CORNER GUARD "CG"
079200SEALANT
10260042" SS CORNER GUARD,ADHERE WITH SILICONEADHESIVE
102600MILLED EDGE
092900WALL FINISH CONTINUESUNDER C.G.
102600 MILLED EDGE
092216 WALL PER TYPE
079200 SEALANT
6" M
IN.
TYP. FOR HEAD CONDITION "A"
092216 WALL PER TYPE
095113 CEILING PER RCP'S
092116 DEFLECTION TRACK
HEAD DETAIL - WALL UP TO STRUCTURE ABOVE
092116 WALLTYPE PER PLAN
092116 DEFLECTION TRACK092900WHERE EXPOSED TO VIEW,PROVIDE CONT.J-MOLDFINISHED EDGE
STRUCTURE ABOVE
079200ACOUSTIC CAULK EA SIDECONTINOUS (PER PARTITIONTYPE)
HEAD CONSTRUCTIONA - EXTEND TO 6" ABOVE CEILING HEIGHT.B - FULL-HEIGHT WALL, EXTEND TO DECK OR BEAM ABOVE.C - FULL-HEIGHT WALL, FRAMED WITH COLD-FORMED METAL STUDS PER SPEC. 054000.P - PARTIAL-HEIGHT WALL. HEIGHT AS NOTED ON PLAN OR ON DETAIL.R - FULL-HEIGHT, FIRE-RATED WALL, SEALED TO STRUC. ABOVE PER FIRE ASSEMBLY.S - SPECIAL HEAD CONDITION, PER DETAIL.
WALL ADDITIONS (WHERE APPLICABLE)1 - ACOUSTIC ASSEMBLY W/ BATT INSULATION & SEALANT (TOP & BTM OF WALL)2 - THERMAL INSULATION, FULL-DEPTH OF STUD CAVITY U.N.O.3 - SMOKE PARTITION, SEAL WALL PERIMETER & PENETRATIONS.4 - SPECIAL TREATMENT, PER NOTES.
PARTITION DESIGNATIONS
3G2X-#
3G13G1A
4 1/4"4 7/8"
WALL VARIANTSPECIFIC VARIANT (1, 2, 3... ETC.)
WALL MATERIALCONCRETE - C
GYP. BOARD ON METAL STUDS - GCONC. MASONRY (CMU) - M
GYP. BOARD ON SHAFTWALL - S
WALL CORE THICKNESSTHICKNESS PER WALL TYPEEXAMPLES: 3 = 3-5/8" STUD
3G2X-#
PARTITION TAG
'G' PARTITIONS3G2
3G2 / R
4 7/8"
RATED 1-HRPER UL-U419
'G' PARTITIONS6G16G1A
6 5/8"7 1/4"
6G26G2 / R
7 1/4"
RATED 1-HR PER UL-U419
2G1
'S' PARTITIONS
4S1 / R
4 5/8"
4S2 / R
5 1/4"
RATED 2-HRPER UL-U415
2S1 / R2S2 / R
3 3/4"
RATED 2-HRPER UL-U415
3 1/8"
GYPSUM BOARD
GYPSUM BOARD IS TYPICALLY 5/8" TYPE 'X', UNLESS NOTED OTHERWISE.
PROVIDE MOISTURE-RESISTANT OR CEMENTITOUS BOARDS WHERE REQUIREDIN GYPSUM BOARD SPECIFICATION 092900 AND WHERE NOTED IN THE DRAWINGS.
PROVIDE IMPACT-RESISTANT BOARDS WHERE REQUIRED IN THE GYPSUMBOARD SPECIFICATION 092900 AND WHERE NOTED IN THE DRAWINGS.
GENERAL PARTITION NOTES
FIRE-RATED & SMOKE-RATED WALLS
FIRE/SMOKE SEALANTS AND/OR FIRE SAFING IS REQUIRED AT RATEDPARTITIONS WHERE THE PARTITION JAMB CONDITIONS INTERFACE WITHDISSIMILAR MATERIALS OR WHERE FIRE TAPING AT THE INTERFACE OFMATERIALS IS NOT POSSIBLE.
FIRE SEALANTS ARE NOT REQUIRED AT THE BASE/SILL CONDITION OFPARTITIONS.
WHERE A FIRE-RATED PARTITION IS ALSO NOTED TO HAVE ACOUSTICALELEMENTS, FIRE SEALANTS AND/OR FIRE SAFING SHALL BE PROVIDED IN LIEU OFACOUSTICAL SEALANTS. ACOUSTICAL SEALANT SHALL BE PROVIDED AT THEBASE/SILL OF PARTITIONS.
APPLIED FINISH MATERIALS
APPLIED FINISHES INCLUDE, BUT ARE NOT LIMITED TO:PAINT, RESINOUS COATINGS, ACOUSTICAL WALL PANELS, AND WOODMILLWORK TRIM.
GENERALLY, WALL TYPES DO NOT INCLUDE OR SHOW ANY APPLIED FINISHES;(WALL TYPES WITH WOOD PANEL AND/OR OTHER VENEERS MAY BE CREATED).SEE FINISH SCHEDULE AND INTERIOR ELEVATIONS FOR MATERIALS TO BEINSTALLED OVER THE BASIC PARTITION ASSEMBLY.
THE CONTRACTOR SHALL COORDINATE DIMENSIONAL LAYOUT WITH APPLIEDFINISH THICKNESS WHERE CLEAR OR MINIMUM CLEAR DIMENSIONS AREREQUIRED
THE CONTRACTOR SHALL COORDINATE ANY ADDITIONAL REQUIREMENTSWITHIN WALL FRAMING NECESSARY FOR APPLIED FINISH MATERIALS.
092900 5/8" TYPE 'X' GYP BD
092216 2 1/2" MTL FRAMING
079200 ACOUSTIC SEALANT FORACOUSTIC TYPE
096513 BASE PER SCHEDULE
072100ACOUSTIC BATT INSULATIONWHERE NOTED ON PLANS ORSPECIFICATIONS
092900 5/8" TYPE 'X' GYP BD
092216 3 5/8" MTL FRAMING
072100ACOUSTIC BATT INSULATIONWHERE NOTED ON PLANS ORSPECIFICATIONS
079200 ACOUSTIC SEALANT FORACOUSTIC TYPE
096513 BASE PER SCHEDULE
092900ADDL LAYER OF 5/8" TYPE XGYP BD WHERE SPECIFIED AS'3G1A' WALL
092900 5/8" TYPE 'X' GYP BD
092216 3 5/8" MTL FRAMING
072100ACOUSTIC BATT INSULATIONWHERE NOTED ON PLANS ORSPECIFICATIONS
079200 ACOUSTIC SEALANT FORACOUSTIC TYPE
096513 BASE PER SCHEDULE
092900 5/8" TYPE 'X' GYP BD
092216 6" MTL FRAMING
072100ACOUSTIC BATT INSULATIONWHERE NOTED ON PLANS ORSPECIFICATIONS
079200 ACOUSTIC SEALANT FORACOUSTIC TYPE
096513 BASE PER SCHEDULE
092900ADDL LAYER OF 5/8" TYPE XGYP BD WHERE SPECIFIED AS'6G1A' WALL
092900 5/8" TYPE 'X' GYP BD
092216 6" MTL FRAMING
072100ACOUSTIC BATT INSULATIONWHERE NOTED ON PLANS ORSPECIFICATIONS
079200 ACOUSTIC SEALANT FORACOUSTIC TYPE
096513 BASE PER SCHEDULE
092900 5/8" TYPE 'X' GYP. BD. TYP.
092116 4" C-H SHAFTWALL STUDS
072100 BATT INSUL
079200 SEALANT
096513 BASE FINISH PER SCHED.
092900 1" TYPE 'X' GYP. PANEL
092900 2ND LAYER OF 5/8" TYPE 'X'GYP. BD.
092900 5/8" TYPE 'X' GYP. BD. TYP.
092116 2 1/2" C-H SHAFTWALL STUDS
072100 BATT INSUL
079200 SEALANT
096513 BASE FINISH PER SCHED.
092900 1" TYPE 'X' GYP. PANEL
092900 2ND LAYER OF 5/8" TYPE 'X'GYP. BD.
0G1
092900 5/8" TYPE 'X' GYP BD LAMINATEDTO CMU
079200 ACOUSTIC SEALANT FORACOUSTIC TYPE
096513 BASE PER SCHEDULE
1G1
092900 5/8" TYPE 'X' GYP BD
092216 1 5/8" MTL FRAMING
079200 ACOUSTIC SEALANT FORACOUSTIC TYPE
096513 BASE PER SCHEDULE
072100ACOUSTIC BATT INSULATIONWHERE NOTED ON PLANS ORSPECIFICATIONS
RATED 1-HRPER UL-U415
RATED 1-HRPER UL-U415
5/8" TYPE "X" GYP BD. (2) LAYERSAROUND INSIDE OF CAB RECESS,ATTACH TO MET STUDS & MET ANGLESW/ #8 SELF-TAP SM SCREWS @ 12" O.C.
RECESSED FLUSH MTD TEL CABINET,COORD SIZE OF FRAMED PNG W/MANUFACTURER
1-1/2" X 3" X 20GA MET ANGLE @ ALL (4)SIDES OF ATED PARTN TYPEOPNG, ATTACH TO MET STUDS W/ #8SELF-TAP SM SCREWS @ 12" O.C.
ACOUSTIC INSULATION,WHERE SCHEDULED
AS S
CHED
ULED
1 HR
PART
N TY
PE
60" U
.N.O
.
48" M
AX.
FEC ELEVATION
ELEVATION
L
PLAN
NON-RATED PARTITION TYPE RATED PARTITION TYPE
C
PARTITION TYPE AS SCHED
SEMI RECESSED METAL FIRE EXTINGUISHER CAB,COORD OPNG SIZE & DEPTH W/ MANUFACTURER
3-5/8" X 20 GA METALSTUDS AROUND FEC OPNG
5/8" GYP BD
100
ROOM NAME/TITLE
IN FIRE EMERENCY,DO NOT USE
ELEVATOR. USE EXITSTAIRS
.. ..
5"
2 1/4"
.. .... ..
3/8"3/8
"3/8
"3/4"
3/8"
7 7/8"
10"
6" M
IN. B
Y CO
DE
STAIRS.. ... ... .
7 7/8"
EQ EQ
7 7/8"TRANSPARENTINSERT
COLORED LENS, T.B.D. ,W/ BRAILLE & TACTILE TEXT
LENS W/ BRAILLE& TACTILE TEXT &GRAPHICS,
8 1/2"
6" M
IN. B
Y CO
DE
8 1/2"
LENS W/ BRAILLE& TACTILE TEXT &GRAPHICS,
.. ... ... . .. ... ... . .. ... ... ... ... ... ... ... ... .
D1
D5D3
PROVIDE ONE AT EACH STAIR ENTRANCE
D1
D1
D1
D5
D1
D1
D1 D1
D3
D1
D1
D1
D1
D1
D1
D1D1
D1
D1
D1
D1
D1 D1D1
5'-0"
TOP
OF
SIGN
TO
FINI
SH F
LOOR
, TYP
.
9"
1'-6" MIN CLR
EQ EQ
1'-6"
MIN
CLR
1'-6"
1'-0"
TACTILE CHARACTERSTO BE RESTRICTED TOTHIS AREA, ADJUST TYP.MOUNTING ELEV ASNEEDED
4'-0"
C.L. OF SIGN TO DOORFRAME, LATCH SIDE
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
0" 1"
Original Size: 1 1/2" Drawing may have been reduced.
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/27
/2017
5:43
:28 P
MC:
\Us e
rs\jas
on. tip
pie\D
ocum
ents\
5347
4 UM
S OM
L1 R
e nov
ation
_j aso
n.tipp
ie .rvt
A150
11/27/2017
53474
TYPICALPARTITIONS,SIGNAGE &
INTERIOR DETAILS
JRT
ADDENDUM #2
04 A
RC
HIT
ECTU
RAL
BID
DO
CU
MEN
TS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
JRT
CP171091
PGAV
Medical ScienceFirst FloorResearch
LaboratoryRenovation
1 1/2" = 1'-0" C2GYP WALL - CONT. JOINT "CJ" 1 1/2" = 1'-0" C1GYP WALL - CORNER GUARD "CG"
1 1/2" = 1'-0" A4GYP HEAD OF WALL - SUSPENDED CEILING
1 1/2" = 1'-0" A5GYP HEAD OF WALL TO STRUCTURE
1 1/2" = 1'-0" C3RECESSED ELEC CAB.
1 1/2" = 1'-0" B5FIRE EXTINGUISHER CAB
3" = 1'-0" E1SIGNAGE TYPES
# DATE DESCRIPTION1 11/27/2017 Addendum 02
3/32" = 1'-0" C4SIGNAGE PLAN
3/4" = 1'-0" E3SIGNAGE INSTALLATION
1
Q R
5
5.5
7
8
K.2
9
6
10
5.9
525
524
523
423
424
425
FO
R C
ON
TIN
UA
TIO
N,
SE
E S
HE
ET
FP
D101
EX 2 1/2"FEX 2 1/2"F
EX 4"F-UP
EX 4"F
EX 4"F
2
2
2
TYP.
2
TYP.
EX. SPR.PIPING (TYP.)
2
EX 1-1/2" EX 1-1/2"
EX 1-1/2" EX 1-1/2"
3
1
1 EX 4"F
FF
F
F
F
EX 4"F 1
EX 4"S.P.-UP 1
EX. CAPPED2-1/2" SPR. MAIN
STORAGEROOM
STORAGEROOM
CORRIDOR
M122
DRY STORAGE
M126
EXISTING IT CLOSET
M125
DARK ROOM
M128
STORAGE/ RISER
M125B
4
4
4
4
41
1
1
1
1
EXISTING LAY-IN CEILING. CONTRACTORSHALL FIELD VERIFY EXISTING LAYOUT.
1
ALTERNATE BID #2
SCALE: 3/16" = 1'-0"
1 THE CONTRACTOR SHALL SEE DIVISION #1 SPECIAL CONDITIONS FOR PHASING OF WORK SCHEDULEFOR THIS ALTERNATE #2 CONSTRUCTION.
GENERAL NOTE:
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/2
7/20
1 7 1
0:37
:10
AM
C:\U
sers
\phe
itert
\Doc
umen
ts\2
45-3
2_P
LUM
B_C
EN
TR
AL_
v16_
phei
tert
. rvt
FPD103
11/06/2017
53474
LEVEL1 – EASTZONE TEACHING
LAB – DEMOLITIONALTERNATE BID #2
PJH
BID DOCUMENTS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
PJH
CP171091
MSM
Medical ScienceFirst FloorResearch
LaboratoryRenovation
3/16" = 1'-0"1LEVEL1 – EAST ZONE TEACHING LAB – DEMOLITION – ALTERNATE BID #2
KEYED NOTES:
1 THE INSTALLATION OF THE FIRE MAIN IS UNDER CONTRACT AND TO BE INSTALLED. THE CONTRACTOR FORTHIS FIRST FLOOR RESEARCH LAB PROJECT SHALL COORDINATE NEW WORK WITH THE FIRE MAINCONTRACTOR FOR INSTALLATION.
2 THE CONTRACTOR SHALL DISCONNECT AND REMOVE THE EXISTING CAPS ON THE SPRINKLER PIPES. SEERENOVATION DRAWING FOR NEW SPRINKLER HEAD INSTALLATION.
3 THE EXISTING SPRINKLER PIPING SYSTEM WAS DESIGNED AND INSTALLED FOR A LIGHT HAZARD DESIGNAT A 0.10 GPM PER 1500 SQ.FT.
4 EXISTING HARD CEILING TO REMAIN.
#
NORTH
PLA
N
0
SCALE:
0
6' - 0"
12' - 0"
18' - 0"
1" = 6' - 0"
# DATE DESCRIPTION
1 11/27/2017 ADDENDUM 2
1
F G
H I J
KD.7D.2
5.5
7
8
K.2
9
6
1
10
5.9
504
448
447 444
445
506 507
442
443 446
449
450
501
FIRST FLOOR
WEST SPRINKLER ZONE
FIRST FLOOR
EAST SPRINKLER ZONE
FO
R C
ON
TIN
UA
TIO
N,
SE
E S
HE
ET
FP
101
EX 4"F
EX 4"F
EX 2"F
EX 2 1/2"F
EX FHC
EX 6"F
EX 6"F
EX 4"F
EX 2 1/2"F
ZONE VALVE
IN VERTICAL
4" SPR MAIN BLIND FLANGE
FOR FUTURE CONNECTION ORDINARY HAZARD,
CLASS 2
WEST RESEARCH LAB
M148
ANATOMY CADAVER LAB
M144
HALLWAY
M144
CORRIDOR
M124
CORRIDOR
M124
SPR
F
EX 6"F
SP
RS
PR
SP
R
NEW 4" SPR MAIN
1
2
EX FHC
EX 6"F-UP&DN
EX 6"FEX 6"F
LIGHT HAZARD
LIGHT HAZARD
EX FHC
FF
FF
F
F F
F
INSTALL INSPECTOR'S
TEST AND DRAIN FOR
WEST ZONE FIRST FLOOR.
EX JAN. SINK
IN THIS CORRIDOR, INSTALL
SIDEWALL SPRINKLER HEADS.
2'-0"
INTERIOR WALLRELOCATE EXIST 6"F
MAIN AT 10'-2" BOP
EX. 6"F MAIN
F F
INSTALL AT 10'-2" AFF
TO BOTTOM OF PIPE
EX. 6"F MAIN
EX. 6"F MAIN
1
EX 6"F MAIN
AT 10'-2" BOP
1
SCALE: 3/16" = 1'-0"
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/2
7/20
1 7 1
0:37
:59
AM
C:\U
sers
\phe
itert
\Doc
umen
ts\2
45-3
2_P
LUM
B_C
EN
TR
AL_
v16_
phei
tert
. rvt
FP102
11/06/2017
53474
LEVEL 1 -WESTZONE FIRE
PROTECTION –NEW WORK
PJH
BID DOCUMENTS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
PJH
CP171091
MSM
Medical ScienceFirst FloorResearch
LaboratoryRenovation
3/16" = 1'-0"1LEVEL 1 -WEST ZONE FIRE PROTECTION – NEW WORK
KEYED NOTES:
1 THE CONTRACTOR SHALL FURNISH AND INSTALL A ZONE VALVE SUPERVISORY
SWITCH ON EXISTING VALVE. COORDINATE INSTALLATION WITH ALL
SUB-CONTRACTORS.
2 SEE DIAGRAM ON SHEET FP501 FOR FLOOR CONTROL ASSEMBLY.
#
NORTH
PLA
N
0
SCALE:
0
6' - 0"
12' - 0"
18' - 0"
1" = 6' - 0"
# DATE DESCRIPTION
1 11/27/2017 ADDENDUM 2
CYLCYL
CF
H 0
1
CYL
CF
H 0
2
CY
L
CF
H 0
1
CY
L
CYL
CFH 01
CFH 01
CY
L
CY
L
CYLCYL
CYLCYL
CYLCYL
CYLCYL
G H I J K L M N P Q R
D.7D.2 N.8M.8L.91.15
5
5.5
7
8
K.2
9
4
3
2
6
1
10
5.9
EX. 12" EA TRANSITEDUCT UP (VR-58)
EX. 12" DIA EATRANSITE UP
EX. 16" DIA EATRANSITE UP(VR-37)
EX. 10" DIA EATRANSITE UP(VR-55)
9
2
FEV
1-04
FEV
1-02
BCU
1-03
FREEZER STORAGE / SUPPORT
M132
TISSUE CULTURE
M134C
EAST RESEARCH LAB
M134
MECHANICAL
M130
DARK ROOM
M128
DRY STORAGE
M126
STORAGE/ RISER
M125B
EXISTING IT CLOSET
M125
CORRIDOR
M122
FLEX RESEARCH LAB
M114
FREEZER STORAGE / SUPPORT
M112
DARK ROOM
M134B
TISSUE CULTURE
M134A
CORRIDOR
M122
CORRIDOR
M145
WEST RESEARCH LAB
M148
TISSUE CULTURE
M148BVAV
1-142
VAV
1-138
VAV
1-141
LSV
1-01
RHC
1-01
GEV
1-01
LSV
1-03
LSV
1-05
LSV
1-07
GEV
1-02
GEV
1-06
VAV
1-140
EAV
1-135
EAV
1-143
EF
1-02
RHC
1-02
RHC
1-03
RHC
1-04
RHC
1-06
RHC
1-07
ELEVATORS
50x20 SA
50x22 SA
26x10 SA
48x14 EA
14ø SA
18x18
26x10 SA
36x14 SA
12ø EA 18x10
18x10 EA
8ø SA
8x8 SA
10x10 EA
24x12 EA
8ø
14ø
MECH ROOM M120
M201
1
BCU
1-04
VAV
1-137
LSV
1-06
36x18 EAUP (VR-14)
22x14 EA
24x8 EA
10ø SA
S-2
315
S-2
315S-2
315
S-2
315
12ø EA
S-2
315
S-2
315S-2
315
E-7
710
24x12 EA
E-1
100
S-1
200
6ø EA
GEV
1-0320x8 E
A
E-8
765
20x8 EA
E-8
760
24x12 EA
E-8
635
E-8
630
24x12 EA
VAV
1-136 20x7 SA
S-6
600
S-1
155
7ø SA
7ø EA
8ø SA E-2
155
8ø EA
VAV
1-143
S-4
100
S-4
100
12ø EA
E-4
100
E-4
100
8ø EA
10ø SA
28x14 SA 24x14
S-2
350
S-2
350
S-1
200
E-2
200
8ø EA
12ø EA
S-1
210
E-1
110
E-5
2200
30x18 EA
26x12 EA
EXISTING48x12LOUVER
28x12 EA
24x14 S
A
4ø SA
LSV
1-04
50x14 S
A
S-2
350
12ø EA
32x14 EA
1450 CFM FROMSHOWER/LOCKERROOM
CAP EXISTINGABANDONED DUCT
36x12 RA
6ø EA
8ø EA
GEV
1-04
8ø
EAV
1-138
S-1
220
E-1
120
8ø SA
S-3
775
8ø SA
18x8
8ø
8ø
FEV
1-05
S-2
385
15x12 SA
E-3
530
12ø EA
GEV
1-05
8ø EA
30x15 SA
FEV
1-03
12ø EA
VAV
1-139
12ø SA
EAV
1-139
RHC
1-05
28x14 SA
50x20 S
A
7ø SA
10ø SA
12ø EA
18x18 EA
ANATOMY CADAVER LAB
M144
25x17 SA
S-5
2200
58x29 RA
E-6
475
12ø
7ø
12ø EA
12x12 EA
20x8 EA
20x8 EA
12ø EA
S-5
2200
25x17 SA
48x11
28x16 SA
S-1
225 8ø
S-1
225
S-1
225
S-1
225
14x12 SA
12ø EA
SP
2
2
2
2
22x14 SA
R-1
1100
R-1
1100
VENDING
58x29 RA
44x16 RETURN TRANSFERDUCT ABOVE CEILING
R-1
1100
R-1
1100
3
3
4
4
5
EXIST. 24x18EA UP(VR-A)
FEV
1-01
7ø
AP
AP
12ø EA
AP
AP
12x9 SA
8ø
APAP
AP
12x9 SA12x9 SA
APAP
APAP
S-2
38510ø SA 10ø SA
D
D
D
R
D R
D
DD
RDR
D
DD
D
D
R
R
D D R
R
D
D
R
3
6
1
24x8 EA
FTU
1-446
R
D
10ø SA
D
10ø SA
D
D
10ø SAD
10ø SA
D
12ø EA
10ø SA
E-7
700
10x10 SA8ø SA
AP AP
8ø SA
10ø SA
S-2
35010ø SA
10ø SA
10ø SA
S-2
350
(VR-39)
(VR-38)
12ø SA
SD
1-03
SD
1-02
SD
1-03
FD
1-01
FD
1-02
CWP
1-01
HX
1-01
6
D
24x12 EA
24x18 EA
FD
1-05
FD
1-04
FD
1-06
28x12 EA
AP
FD
1-11
FD
1-12
R
8
8ø
12ø
FD
1-03
7
7
12ø EA
12ø EA
GEV
1-07
7
LSV
1-02
10ø SA
10ø
24x12 SA
8ø SA
S-2
350
TYPOF 5
10ø SA
10ø SA
10ø SA
8ø SA
S-2
350
10ø SA
10ø SA
S-2
315
D
R
6ø EA
EAV
1-144
16x12
14ø EA
E-7
710
24x12 EA
24x6 EA
S-3
700
D
25x16 SA
10ø SA
D
R
R-1
700
4
M503
5
M5036
M503
88x8 EA
AP
APAP
GRAVITY BACKDRAFTDAMPER
GRAVITY BACKDRAFTDAMPER
FD
1-07
FD
1-08
AP
AP
AP
FD
1-09
AP
EX.RELOCATEDSA DIFFUSER
R
E-2
300
E-2
300
E-2
300
8ø8ø
8ø8ø
10
18x12 EA
30x15 SA
24x14 SA
22x14
AP
FD
1-10
6ø EA
28x9 SA
BOTTOM OFGRILLE 8" AFF
BOTTOM OFGRILLE 6'-10"AFF
BOTTOM OFGRILLE 8" AFF
36x14 SA
50x14 SA
12ø EA12ø EA
1
1.
2.
3.
4.
5.
FUME EXHAUST AIR DUCTWORK (INDICATED BY CROSSHATCHING)SHALL BE CONSTRUCTED OF FULLY WELDED STAINLESS STEELPER SPECIFICATIONS.
ALL EXPOSED DUCTWORK SHALL BE ROUND OR FLAT OVALUNLESS OTHERWISE NOTED. EXPOSED SUPPLY AIRDUCTWORK SHALL BE DOUBLE-WALL CONSTRUCTION. REFERTO SPECIFICATIONS FOR MORE INFORMATION. THIS DOES NOTAPPLY TO DUCTWORK LOCATED IN MECHANICAL ROOMS.
ALL AIRFLOW CONTROL VALVES SHALL BE INSTALLED WITHCONTROLS FACING OUTWARD OR DOWNWARD FOR EASY ACCESS.
ALL DUCTWORK LOCATED IN EXPOSED CEILING SPACES SHALL BEPAINTED (REFER TO ARCHITECTURAL CEILING PLANS FOR ALLEXPOSED CEILING SPACES):
- FIELD PAINTING OF DUCTWORK, ASSOCIATED AIRDEVICES, AIR TERMINAL UNITS, AND HANGERS ANDSUPPORTS SHALL BE BY CONTRACTOR AND SHALLMATCH COLOR APPROVED BY ARCHITECT DURINGSHOP DRAWING PROCESS. ALL DUCTWORK ANDEQUIPMENT TO BE PAINTED SHALL HAVE A PAINT GRIPFINISH.
- LABORATORY AIRFLOW CONTROL VALVES SHALL NOTBE PAINTED. CONTRACTOR SHALL PROTECT AIRFLOWCONTROL VALVES THROUGHOUT PAINTING PROCESS.
ALL OPENINGS THROUGH RATED WALLS MUST BE PATCHED ANDSEALED AIR TIGHT TO MEET THE RATING OF THE WALL AND TOMAINTAIN AIR PRESSURE RELATIONSHIPS TO ADJACENT SPACES.
DUCTWORK GENERAL NOTES:
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/2
7/20
1 7 3
:03:
59 P
MC
:\Use
rs\r
diem
er\D
ocum
ents
\245
-32_
ME
CH
_CE
NT
RA
L_v1
6_rd
iem
er.r
vt
1 Hospital Drive, Columbia, MO65212
M101
11/06/2017
53474
LEVEL 1DUCTWORK PLAN
NEW WORK
NLP
BID DOCUMENTS
University of Missouri -Columbia
NLP
CP171091
RJD
Medical ScienceFirst FloorResearch
LaboratoryRenovation
1/8" = 1'-0"1
LEVEL 1 DUCTWORK PLAN - NEW WORK
KEYED NOTES:
1 REMOVE AND REINSTALL CEILING AS REQUIRED TO INSTALL NEWBLOWER COIL UNIT ABOVE EXISTING VENDING ROOM CEILING.
2 TRANSITION AS REQUIRED TO CONNECT TO FUME HOOD OUTLET.
3 SUPPLY AIR DUCT DOWN IN WALL CAVITY TO SIDEWALL DIFFUSER.
4 DASHED LINE INDICATES CLEAR AREA REQUIRED FOR FILTERACCESS.
5 CAP EXISTING TRANSITE EXHAUST DUCT AIR-TIGHT.
6 HATCHING INDICATES EXPOSED CEILING AREA. SEE DUCTWORKGENERAL NOTES FOR ADDITIONAL INFORMATION.
7 CONNECT NEW EA DUCT TO EXISTING TRANSITE EA DUCT.CONNECTION SHALL OCCUR WITHIN EXISTING CHASE ABOVE 2NDLEVEL SLAB. COORDINATE WITH ARCHITECTURAL DRAWINGS.
8 PROVIDE A MINIMUM 12" LONG x 0.060" THICK STEEL SLEEVECENTERED IN EACH DUCT OPENING. THE SLEEVE SHALL BESECURED TO BOTH SIDES OF THE WALL AND ALL FOUR SIDES OFTHE SLEEVE WITH MINIMUM 1 1/2" x 1 1/2" x 0.060" STEEL RETAININGANGLES. THE RETAINING ANGLES SHALL BE SECURED TO THESLEEVE AND THE WALL WITH NO. 10 SCREWS. THE ANNULAR SPACEBETWEEN THE STEEL SLEEVE AND THE WALL OPENING SHALL BEFILLED WITH ROCK (MINERAL) WOOL BATTING ON ALL SIDES. DUCTINSULATION SHALL NOT PENETRATE THE ASSEMBLY.INSTALL DUCT INSULATION OVER THE ASSEMBLY ANDTERMINATE AT WALL.
9 DUCT STATIC PRESSURE SENSOR FOR AHU 1-01.
10 APPROXIMATE LOCATION OF FUTURE SURGICAL LIGHT ANDSUPPORT STRUCTURE ABOVE CEILING. AVOID ROUTING NEWDUCTWORK IN THIS AREA.
KEYPLAN
OPENCOURTYARD
TO CLINICALSUPPORT AND
EDUCATIONBLDG
TO NURSINGSCHOOL
TO HOSPITAL
PLANNORTH
1
04 8 16268
SCALE: 1/8"=1'-0"
# DATE DESCRIPTION
1 11/27/17 ADDENDUM 2
1
1
Q R
5
4
2
M201
EF
1-01
AHU
1-01
EAV
1-135
VAV
1-135
1 1
/4"L
PR
70x116 OA
50x22 SA
50x22 S
A
30x18 EA
47x42 E
A
30x110 O
A
12ø
EA
EX. 12" DIA EATRANSITE UP
EX. 16" DIA EATRANSITE UP
MECHANICAL
M130
DARK ROOM
M128
FREEZER STORAGE / SUPPORT
M132
MD
1-01
62x36 SA
HWRP
1-01
2 1/2"HWS
2 1/2"HWS
4"C
WS
4"C
WR
L
1-02
L
1-01
100x66 INSULATEDPLENUM BEHINDLOUVER
BLANK OFF UNUSEDPORTION OF LOUVER(APPROX. 92x66) WITHINSULATEDSHEETMETALSANDWICH PANELS.
BLANK OFF UNUSEDPORTION OF LOUVER(APPROX. 47x26) WITHINSULATED SHEETMETALSANDWICH PANELS.
47x42 INSULATED PLENUMBEHIND LOUVER
4"CWS
4"CWR
1 1
/2"C
WR
1 1
/2"C
WS
12ø EA
7ø EA
16ø EA
1"CD
1"C
D
1" CDTO FLDR
S-5
47512x12 SA
E-6
475
E-5
2200
R-1
1100
R-1
1100
3
M201
1
2
3
4
45
INSULATED "WALK-THRU" PLENUM.
11' -
10"
6
7
1 1/4"LPS
4"LPS
4"L
PS
4"L
PS
1 1/4"LPS
1 1/4"LPS
4"L
PS
4"L
PS
8
2"L
PR
9
TVAV 1-135
7ø SA
AP
LEVEL ONE0' - 0"
54
AHU
1-01
EF
1-01
116x70
1 1/4"LPR
FILTER SECTION
OUTSIDE AIR INTAKEPLENUM. SLOPEFLOOR OF PLENUMTOWARDCONDENSATE DRAINCONNECTION.
PREHEAT COIL SECTION
STEAM HUMIDIFIER SECTION
SUPPLY FAN SECTION
COOLING COIL SECTION
MECHANICAL
M130
FREEZER STORAGE / SUPPORT
M132
MD
1-01
22x50 SA
36x62 SA
18x30 EA
1 1/2"CWR
1 1/2"CWS
3
M201
4"LPS4"LPS4"LPS4"LPS
1 1/4"LPS
1 1/4"LPS
1 1/4"LPS
ACCESS SECTION
ACCESS SECTION
ACCESS SECTION
1.
2.
3.
4.
5.
FUME EXHAUST AIR DUCTWORK (INDICATED BY CROSSHATCHING)SHALL BE CONSTRUCTED OF FULLY WELDED STAINLESS STEELPER SPECIFICATIONS.
ALL EXPOSED DUCTWORK SHALL BE ROUND OR FLAT OVALUNLESS OTHERWISE NOTED. EXPOSED SUPPLY AIRDUCTWORK SHALL BE DOUBLE-WALL CONSTRUCTION. REFERTO SPECIFICATIONS FOR MORE INFORMATION. THIS DOES NOTAPPLY TO DUCTWORK LOCATED IN MECHANICAL ROOMS.
ALL AIRFLOW CONTROL VALVES SHALL BE INSTALLED WITHCONTROLS FACING OUTWARD OR DOWNWARD FOR EASY ACCESS.
ALL DUCTWORK LOCATED IN EXPOSED CEILING SPACES SHALL BEPAINTED (REFER TO ARCHITECTURAL CEILING PLANS FOR ALLEXPOSED CEILING SPACES):
- FIELD PAINTING OF DUCTWORK, ASSOCIATED AIRDEVICES, AIR TERMINAL UNITS, AND HANGERS ANDSUPPORTS SHALL BE BY CONTRACTOR AND SHALLMATCH COLOR APPROVED BY ARCHITECT DURINGSHOP DRAWING PROCESS. ALL DUCTWORK ANDEQUIPMENT TO BE PAINTED SHALL HAVE A PAINT GRIPFINISH.
- LABORATORY AIRFLOW CONTROL VALVES SHALL NOTBE PAINTED. CONTRACTOR SHALL PROTECT AIRFLOWCONTROL VALVES THROUGHOUT PAINTING PROCESS.
ALL OPENINGS THROUGH RATED WALLS MUST BE PATCHED ANDSEALED AIR TIGHT TO MEET THE RATING OF THE WALL AND TOMAINTAIN AIR PRESSURE RELATIONSHIPS TO ADJACENT SPACES.
DUCTWORK GENERAL NOTES:
LEVEL ONE0' - 0"
Q R
2
M201
AHU
1-01
HWRP
1-01
4"CWS4"CWR
L
1-01
66x100INSULATEDPLENUM BEHINDLOUVER
30x110 INSULATED "WALK-THRU"PLENUM. SLOPE FLOOR OF PLENUMTOWARD CONDENSATE DRAINCONNECTION.
10" BASE RAIL
2-1/2"HWS/R
MECHANICAL
M130 AREAWAY
1 1/4"LPS
4"LPS
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/2
7/20
1 7 3
:04:
00 P
MC
:\Use
rs\r
diem
er\D
ocum
ents
\245
-32_
ME
CH
_CE
NT
RA
L_v1
6_rd
iem
er.r
vt
1 Hospital Drive, Columbia, MO65212
M201
11/06/2017
53474
ENLARGEDMECHANICAL
ROOM PLANS -NEW WORK
NLP
BID DOCUMENTS
University of Missouri -Columbia
NLP
CP171091
RJD
Medical ScienceFirst FloorResearch
LaboratoryRenovation
1/4" = 1'-0"1
ENLARGED MECHANICAL ROOM PLAN
1/4" = 1'-0"2
SECTION THROUGH MECH ROOM
1/4" = 1'-0"3
SECTION THROUGH MECH ROOM 2
KEYED NOTES:
1 ROUTE 1-1/4" CONDENSATE TO FLOOR DRAIN. SEE PLUMBINGDRAWING FOR LOCATION OF FLOOR DRAIN.
2 EMCS PANEL. MAINTAIN 4'-0" IN FRONT OF PANEL.
3 MAINTAIN MANUFACTURER'S RECOMMENDED SERVICECLEARANCE SPACE ON SIDE OF AIR HANDLING UNIT.
4 PROVIDE 2'-0" WIDE X 7'-0" HIGH INSULATED DOOR IN END OFINSULATED OA PLENUM.
5 UNIT SHALL SIT DIRECTLY ON MANUFACTURER PROVIDED BASERAIL. POSITION UNIT SO THAT COIL PULL SPACE IS IN LINE WITHMECHANICAL ROOM DOOR OPENING.
6 1-1/4' DRAIN FROM OUTSIDE AIR INTAKE PLENUM. ROUTE NEARFLOOR TO FLOOR DRAIN.
7 INSULATE EXISTING STEAM CONDENSATE RETURN PIPING PERSPECIFICATION.
8 CONNECT NEW 1-1/2" LPS TO EXISTING 4" LPS AND ROUTE DOWNTO STEAM HUMIDIFIER IN UNIT.
9 ROUTE NEW 2" LPR FROM HUMIDIFIER IN UNIT AND CONNECT TOEXISTING ?" LPR DOWN THROUGH FLOOR.
02 4 8134
SCALE: 1/4"=1'-0"
02 4 8134
SCALE: 1/4"=1'-0"
02 4 8134
SCALE: 1/4"=1'-0"
PLANNORTH
1
# DATE DESCRIPTION
1 11/27/17 ADDENDUM 2
1
1
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/2
7/20
1 7 3
:04:
00 P
MC
:\Use
rs\r
diem
er\D
ocum
ents
\245
-32_
ME
CH
_CE
NT
RA
L_v1
6_rd
iem
er.r
vt
1 Hospital Drive, Columbia, MO65212
M602
11/06/2017
53474
SCHEDULES
NLP
BID DOCUMENTS
University of Missouri -Columbia
NLP
CP171091
RJD
Medical ScienceFirst FloorResearch
LaboratoryRenovation
EXHAUST AIR TERMINAL UNIT SCHEDULEPLAN MARK
MFR. MODEL TYPE SERVICE LOCATIONINLET DUCT
SIZE (IN RND)
PRIMARY AIRFLOW (CFM) DESIGN INLETSTATIC
PRESSURE (INWC)
OUTLET DUCTSIZE WxD (IN)
MAX NC LEVEL @ MAX CFM
NOTESMAX MIN DISCHARGE RADIATED
EAV 1-135 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT MECH ROOM M130 MECH ROOM M130 7 475 105 1.0 12x10 30 30
EAV 1-138 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT DARK ROOM M134B DARK ROOM M134B 4 200 45 1.0 12x8 30 30
EAV 1-139 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT ANATOMY CADAVER LAB M144 ANATOMY CADAVER LAB M144 12 900 325 1.0 16x15 30 30
EAV 1-143 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT DARK ROOM M128 DARK ROOM M128 7 355 105 1.0 12x10 30 30
EAV 1-144 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT EXISTING SHOWER/LOCKER ROOM WEST RESEARCH LAB M148 14 1450 1450 1.0 20x17.5 30 30
SUPPLY AIR CONTROL VALVE SCHEDULEPLAN MARK
MANUFACTURER MODEL TYPE SERVICE SIZE
AIRFLOW
APD NOTES
OCCUPIED UNOCCUPIED
MAX MIN MAX MIN
LSV 1-01 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE TISSUE CULTURE M134C 8" 200 100 200 100 0.3 1, 2, 3,4
LSV 1-02 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE EAST RESEARCH LAB M134 (2) 12" 1750 665 1750 225 0.3 1, 2, 3,4
LSV 1-03 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE EAST RESEARCH LAB M134 (2) 12" 1750 665 1750 225 0.3 1, 2, 3,4
LSV 1-04 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE TISSUE CULTURE M134A 8" 210 105 210 100 0.3 1, 2, 3,4
LSV 1-05 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE TISSUE CULTURE M148A 8" 220 110 220 100 0.3 1, 2, 3,4
LSV 1-06 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE WEST RESEARCH LAB M148 (2) 14" 2520 1250 2520 400 0.3 1, 2, 3,4
LSV 1-07 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE FLEX RESEARCH LAB M114 12" 770 585 770 240 0.3 1, 2, 3,4
GENERAL EXHAUST AIR CONTROL VALVE SCHEDULEPLAN MARK
MANUFACTURER MODEL TYPE SERVICE SIZE
AIRFLOW
APD NOTES
OCCUPIED UNOCCUPIED
MAX MIN MAX MIN
GEV 1-01 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE TISSUE CULTURE M134C 8" 100 0 100 0 0.3 1,2
GEV 1-02 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE EAST RESEARCH LAB M134 (2) 12" 1265 180 1525 0 0.3 1,2
GEV 1-03 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE EAST RESEARCH LAB M134 (2) 12" 1265 180 1525 0 0.3 1,2
GEV 1-04 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE TISSUE CULTURE M134C 8" 110 0 110 0 0.3 1,2
GEV 1-05 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE TISSUE CULTURE M134C 8" 110 0 110 0 0.3 1,2
GEV 1-06 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE WEST RESEARCH LAB M148 (2) 12" 1450 180 2120 0 0.3 1,2
GEV 1-07 PHOENIX CONTROLS ACCEL II PRESSURE INDEPENDENT VENTURI VALVE FLEX RESEARCH LAB M114 8" 185 0 530 0 0.3 1,2
FUME EXHAUST AIR CONTROL VALVE SCHEDULEPLAN MARK
MANUFACTURER MODEL TYPE SERVICE SIZE
AIRFLOW
APD (IN WC) NOTES
OCCUPIED UNOCCUPIED
MAX MIN MAX MIN
FEV 1-01 PHOENIX CONTROLS ACCEL II LOW PRESSURE TISSUE CULTURE M134C 12" 735 735 475 475 0.3 1,2
FEV 1-02 PHOENIX CONTROLS ACCEL II LOW PRESSURE EAST RESEARCH LAB M134 12" 735 735 475 475 0.3 1,2
FEV 1-03 PHOENIX CONTROLS ACCEL II LOW PRESSURE WEST RESEARCH LAB M148 12" 735 735 400 400 0.3 1,2
FEV 1-04 PHOENIX CONTROLS ACCEL II LOW PRESSURE WEST RESEARCH LAB M148 12" 735 735 400 400 0.3 1,2
FEV 1-05 PHOENIX CONTROLS ACCEL II LOW PRESSURE FLEX RESEARCH LAB M114 12" 735 735 390 390 0.3 1,2
AIR DEVICE SCHEDULE
PLAN MARK MFR. MODEL TYPE LOCATION NECK SIZE (IN)FACE SIZE (IN
x IN) MATERIAL FINISHMAX TPD (IN
WC) MAX NOISE (NC)
MAX CFM @LISTED
CONDITIONSMIN THROW(FT) 50 FPM NOTES
S-1 TITUS OMNI SQUARE PLAQUE CEILING 8 24x24 STEEL WHITE 0.1 30 300 12 1, 2, 3, 6
S-2 TITUS OMNI SQUARE PLAQUE CEILING 10 24x24 STEEL WHITE 0.1 30 400 13 1, 2, 3, 6
S-3 TITUS OMNI SQUARE PLAQUE CEILING 15 24x24 STEEL WHITE 0.1 30 775 16 1, 2, 3, 6
S-4 TITUS S301FL LOUVERED FACE DUCT 12x3 14x5 STEEL WHITE 0.1 30 100 15 1, 3, 5, 7, 8
S-5 TITUS 301RL LOUVERED FACE WALL 24x24 26x26 STEEL WHITE 0.1 30 2200 28 1, 3, 6
S-6 TITUS 301RL LOUVERED FACE WALL 18x10 20x12 STEEL WHITE 0.1 30 600 15 1, 3, 6
R-1 TITUS 350RL LOUVERED FACE CEILING 22x22 24x24 STEEL WHITE 0.1 30 1100 -
E-1 TITUS OMNI SQUARE PLAQUE CEILING 6 24x24 STEEL WHITE 0.1 30 175 - 1, 3, 6
E-2 TITUS OMNI SQUARE PLAQUE CEILING 8 24x24 STEEL WHITE 0.1 30 300 - 1, 3, 6
E-3 TITUS OMNI SQUARE PLAQUE CEILING 12 24x24 STEEL WHITE 0.1 30 530 - 1, 3, 6
E-4 TITUS S301FL LOUVERED FACE DUCT 12x3 14x5 STEEL WHITE 0.1 30 100 - 1, 3, 5, 7, 8
E-5 TITUS 350RL LOUVERED FACE WALL 30x18 32x20 STEEL WHITE 0.1 30 2200 - 1, 3, 6
E-6 TITUS 350RL LOUVERED FACE WALL 12x12 14x14 STEEL WHITE 0.1 30 475 - 1, 3, 5, 7
E-7 TITUS 350RL LOUVERED FACE CEILING 22x22 24x24 STEEL WHITE 0.1 30 1065 - 1, 3, 4, 6
E-8 TITUS 350RL LOUVERED FACE CEILING 18x18 24x24 STEEL WHITE 0.1 30 765 - 1, 3, 4, 6
NOTES:1. PROVIDE WITH FACTORY SOUND ATTENUATING "NEUTRALIZER" TO MATCH VALVE SIZE.2. VARIABLE VOLUME VALVE WITH PRESSURE ALARM.3. OCCUPIED MAX IS BASED ON COOLING MAX AIRFLOW.4. PROVIDE WITH HIGH SPEED ACTUATOR.
NOTES:
1. VARIABLE VOLUME EXHAUST VALVE WITH PRESSURE ALARM.2. PROVIDE WITH HIGH SPEED ACTUATOR.
NOTES:1. PROVIDE WITH FACTORY SOUND ATTENUATING "NEUTRALIZER" TO MATCH VALVE SIZE.2. PROVIDE WITH HIGH SPEED ACTUATOR.
NOTES:1. REFER TO MECHANICAL PLANS FOR CFM OF INDIVIDUAL DEVICES.2. PROVIDE DIFFUSER WITH FOUR-WAY THROUGH PATTERN UNLESS NOTED ON MECHANICAL PLANS. IF NOTED ON PLAN MANUFACTURER SHALL PROVIDE DIRECTIONAL BLOW CLIPS.3. MAXIMUM NC LEVEL AND MAXIMUM PD INCH W.C. IS SCHEDULED FOR THE RATED CFM RANGE AS SCHEDULED OR RATED CFM LISTED.4. PROVIDE FRAME WITHOUT SCREW HOLES (TO BE MOUNTED AS LAY-IN CEILING DEVICE).5. CONNECT GRILLE DIRECTLY TO DUCTWORK.6. STANDARD WHITE FINISH.7. MILL FINISH.8. PROVIDE WITH MANUFACTURERS OPPOSED BLADE DAMPER. DAMPER SHALL BE CONSTRUCTED OF SAME MATERIAL AS GRILLE. DAMPER SHALL BE ACCESSIBLE THROUGH FACE OF GRILLE.
AIR TERMINAL UNIT SCHEDULEPLAN MARK
MFR. MODEL TYPE SERVICE LOCATIONINLET DUCT
SIZE (IN RND)
PRIMARY AIRFLOW (CFM) DESIGN INLETSTATIC
PRESSURE (INWC)
OUTLET DUCTSIZE WxD (IN)
AUXILIARY HOT WATER HEATNG COIL MAX NC LEVEL @ MAX CFM
NOTESMAX MINMAX HTG AIRFLOW
(CFM)CAPACITY
(MBH) EAT (°F) LAT (°F) EWT (°F) FLOW (GPM)MAX WPD (FT
HD)MAX APD(IN
WC)CONTROL
VALVE DISCHARGE RADIATED
VAV 1-135 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT MECH ROOM M130 MECH ROOM M130 7 475 105 1.0 12x10 300 12.9 55 95 180 0.60 GPM 2.0 0.15 2-WAY 30 30 1
VAV 1-136 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT CORRIDOR M122 CORRIDOR M122 8 600 145 1.0 12x10 300 12.2 55 93 180 0.60 GPM 2.0 0.15 2-WAY 30 30 1
VAV 1-137 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT FREEZER STORAGE SUPPORT M132 FREEZER STORAGE SUPPORT M132 14 2200 450 1.0 20x17.5 0 0 55 55 0 0.00 GPM 0 0 0 30 30 2
VAV 1-138 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT DARK ROOM M134B DARK ROOM M134B 4 200 45 1.0 12x8 100 2.7 55 81 180 0.30 GPM 2.0 0.15 2-WAY 30 30 1
VAV 1-139 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT ANATOMY CADAVER LAB M144 ANATOMY CADAVER LAB M144 12 900 325 1.0 16x15 450 15.4 55 87 180 0.80 GPM 2.0 0.15 2-WAY 30 30 1
VAV 1-140 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT CORRIDOR M145 CORRIDOR M145 8 775 145 1.0 12x10 390 13.9 55 88 180 0.70 GPM 2.0 0.15 2-WAY 30 30 1
VAV 1-141 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT FREEZER STORAGE SUPPORT M112 FREEZER STORAGE SUPPORT M112 14 2200 450 1.0 20x17.5 0 0 55 55 0 0.00 GPM 0 0 0 30 30 2
VAV 1-142 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT CORRIDOR M122 CORRIDOR M122 7 350 105 1.0 12x10 250 10.2 55 93 180 0.50 GPM 2.0 0.15 2-WAY 30 30 1
VAV 1-143 TITUS DESV PRESSURE INDEPENDENT SINGLE DUCT DARK ROOM M128 DARK ROOM M128 7 355 105 1.0 12x10 355 15.8 55 96 180 0.80 GPM 2.0 0.15 2-WAY 30 30 1
NOTES:
1. PROVIDE NUMBER OF COIL ROWS NECESSARY TO MEET SCHEDULED PERFORMANCE.2. COOLING ONLY AIR TERMINAL.
DUCT MOUNTED COIL SCHEDULEPLAN MARK
MFR. TYPE MODEL & SIZE SERVICE AIR FLOW (CFM) APD (IN WC)
HOT WATER HEATING
NOTESCAPACITY
(MBH) EAT/LAT (F) EWT (F) LWT (F) FLOW (GPM) MAX WPD (FT)
RHC 1-01 USA COIL & AIR DUCT-MOUNTED HW58BH 12" L x 7.5" H TISSUE CULTURE M134C 200 0.08 8.5 55/94 180 129 0.3 0.04
RHC 1-02 USA COIL & AIR DUCT-MOUNTED HW58BH 28" L x 13.5" H EAST RESEARCH LAB M134 1750 0.25 71.4 55/92 180 131 3.0 4.79
RHC 1-03 USA COIL & AIR DUCT-MOUNTED HW58BH 28" L x 13.5" H EAST RESEARCH LAB M134 1750 0.25 71.4 55/92 180 131 3.0 4.79
RHC 1-04 USA COIL & AIR DUCT-MOUNTED HW58BH 12" L x 9" H TISSUE CULTURE M134A 210 0.06 9.6 55/97 180 126 0.4 0.05
RHC 1-05 USA COIL & AIR DUCT-MOUNTED HW58BH 12" L x 9" H TISSUE CULTURE M148A 220 0.06 9.6 55/97 180 126 0.4 0.05
RHC 1-06 USA COIL & AIR DUCT-MOUNTED HW58BG 30" L x 18" H WEST RESEARCH LAB M148 2520 0.25 101 55/91 180 140 5.0 4.0
RHC 1-07 USA COIL & AIR DUCT-MOUNTED HW58BH 14" L x 12" H FLEX RESEARCH LAB M114 770 0.24 29.0 55/90 180 134 1.3 0.65
FIRE DAMPER & SMOKE DAMPER SCHEDULEPLAN MARK
MFR. MODEL TYPE LOCATION SLEEVEDUCT SIZEWxH (IN)
DAMPERRATINGS (HR)
FUSIBLE LINKTEMP (°F) NOTES
FD 1-01 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE FREEZER STORAGE M132 STANDARD 22X14 1-1/2 165
FD 1-02 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE MECHANICAL M130 STANDARD 50X22 1-1/2 165
FD 1-03 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE EAST RESEARCH LAB M134 STANDARD 50X20 1-1/2 165
FD 1-04 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE EXIST. MECH ROOM M120 STANDARD 26X10 1-1/2 165
FD 1-05 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE FLEX RESEARCH LAB M114 STANDARD 26X10 1-1/2 165
FD 1-06 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE FREEZER STORAGE M112 STANDARD 28X16 1-1/2 165
FD 1-07 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE FREEZER STORAGE M112 STANDARD 44X16 1-1/2 165
FD 1-08 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE FREEZER STORAGE M112 STANDARD 25X17 1-1/2 165
FD 1-09 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE TISSUE CULTURE M134A STANDARD 28X9 1-1/2 165
FD 1-10 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE FREEZER STORAGE M132 STANDARD 22X14 1-1/2 165
FD 1-11 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE TISSUE CULTURE M148A STANDARD 12X9 1-1/2 165
FD 1-12 RUSKIN DIBD20 DYNAMIC CURTAIN TYPE WEST RESEARCH LAB M148 STANDARD 24X14 1-1/2 165
SD 1-01 RUSKIN SD60 CLASS 1 GALV. AIRFOIL CORRIDOR M122 STANDARD 20X7 1-1/2 0
SD 1-02 RUSKIN SDRS25 CLASS 1 GALV. TRUE ROUND CORRIDOR M122 STANDARD 10" DIA 1-1/2 0
SD 1-03 RUSKIN SD60 CLASS 1 GALV. AIRFOIL CORRIDOR M145 STANDARD 18X8 1-1/2 0
NOTES:1. MOUNTED HORIZONTALLY IN DUCT THROUGH FLOOR.
# DATE DESCRIPTION
1 11/27/17 ADDENDUM 2
1
1
1
MR M130MR M120MR M112
METASYS (SF-C)
SUPPLY FAN CT
R3
METASYS (SF-S)
METASYS (LT-A)
METASYS (HS-A)
R5
R4
R3STATUSRELAY
R2RSF-C
R1RFA
CONTACTS R4
R5
R4HS
RELAY
HIGHSTATICSWITCH
R1R RUNENAB
SF ECM
(SF-O)
LT-A R5LT-A
RELAY
R2R
SAFETY
24 VAC
HTG
RELAY
CONTACTS
ON R3DMP
RELAY
2MA ECM START CIRCUITNO SCALE 3
FC BUS SCHEMATIC DIAGRAMNO SCALE
R1RR2RR3R4R5DMP RELAYHTG RELAY
24VAC RIB1UC24VAC RIB1UC24VAC CONTROL RELAY -2POLE24VAC CONTROL RELAY -2POLE24VAC CONTROL RELAY -2POLE24 VAC CONTROL RELAY -2POLE24 VAC CONTROL RELAY -2POLE
1.
2.
3.
4.
5.
KEEP ALL LOW VOLTAGE CONTROL WIRING
(UNDER 25V) AND LOW VOLTAGE POWER WIRING
(OVER 25V) SEPARATED. (RUN IN SEPARATE
CONDUIT.)
PROVIDE RELAYS WITH MULTIPLE CONTACTS AS
REQUIRED.
ANY DISCONNECT WITH AUX CONTACTS WILL BE
ADDED TO SAFETY CIRCUIT
CURRRENT TRANSFORMER REQUIRED FOR
STATUS
R1, R2, AND R4 MOUNTED ON/NEAR I/O PANEL.
COORDINATE WITH OWNER REPRESENTATIVE.
FC BUS TO BE CONTINUOUS DAISY CHAIN. SEE PLANS FOR QUANTITY
AND LOCATIONS OF VAV/FCU CONTROLLERS.
OWNER WILL MAKE TERMINATION CONNECTIONS AT PANELS. LOCATE
PANELS IN SAME ROOM AS EQUIPMENT SERVED.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED,
TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING,
DESCRIPTED AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY
WINDY CITY WIRE, CONSTRUCTED BY CABLE-TEK, OR APPROVED
EQUIVALENT.
COORDINATE FIELD ROUTING WITH OWNERS REPRESENTATIVE.
KEEP EXISTING FC BUS INTACT THROUGHOUT CONSTRUCTION.
1.
2.
3.
4.
5.
FIRST FLOOR
SECOND FLOOR
VAVVAV PHOENIX
RMIAH85
2PIPE
1
INSTALL J-BOX ABOVE CEILING IN ROOM M112 FOR FC BUS SPLICEWHERE EXISTING 2-PIPE SYSTEM CONTROLLER WAS REMOVED.
1
(SEE SPECS):DEVICES
GENERAL NOTES:
KEYED NOTES:
GENERAL NOTES:
113
SF
-S
ECM
M
115
HWS
HWR
NC
LT
-A
SMK
111
PH
T-O
M
118114
PH
P-S
PH
P-C
110
CLG
-O
CO
OL
ING
CWS
CWR
NC
CO
IL
35 F
102
PH
T-T
SF
-C
DM
109
SF
-O
FILTERS
117
PR
EH
EA
T
CO
IL
OUTSIDEAIR
116
HS
-A
DPS
SEE AHU START CIRCUIT DETAIL ON SHEET THIS SHEET.
LOCATE AS SHOWN ON MECHANICAL DRAWINGS.
1. SEE SPECIFICATIONS FOR DEVICE SPECIFICATIONS.
2.ANY DEVICE REQUIRING POWER MUST BE POWERED BY
CONTRACTOR.
GENERAL NOTES:
KEYED NOTES:1
1
1
112
ST
M-O
ST
EA
M
LPS
NC
HU
MID
IFIE
R
SF
108
SA
-PR
S
DPT
SUPPLY
AIR
2
103
CLG
-T
119
ST
M-I
SO
2
TAG #100101102103104105106107108109110111112113114115116117118119
TYPEAIAIAIAIAIAIAIAIAIAOAOAOAOBIBIBIBIBOBOBO
POINT NAMEZN-H3OA-TPHT-TCLG-TSA-TSA-RHZN-H1ZN-H2SA-PRSSF-OCLG-OPHT-OSTM-OSF-SPHP-SLT-AHS-ASF-CPHP-CSTM-ISO
DESCRIPTIONZONE AIR HUMIDITYOUTSIDE AIR TEMPHEATING AIR TEMPCOOLING AIR TEMPSUPPLY AIR TEMPSUPPLY AIR HUMIDITYZONE AIR HUMIDITYZONE AIR HUMIDITYSUPPLY AIR STATIC PRESSURESUPPLY FAN SPEED OUTPUTCOOLING OUTPUTHEATING OUTPUTSTEAM OUTPUTSUPPLY FAN STATUSPREHEAT PUMP STATUSLOW TEMP ALARMHIGH STATIC ALARMSUPPLY FAN COMMANDPREHEAT PUMP COMMANDHUMIDIFIER ISOLATION VALVE
DEVICEHUMIDITY SENSORSOFTWARE INPUTRTD/DUCT AVERAGINGRTD/DUCT AVERAGINGRTD/DUCT AVERAGINGHUMIDITY SENSORHUMIDITY SENSORHUMIDITY SENSORDIFF PRESSURE TRANSMITTERECMELECT ACTUATOR W/SPRING RETURNELECT ACTUATOR W/SPRING RETURNELECT ACTUATOR W/SPRING RETURNCURRENT SWITCHCURRENT SWITCHFREEZE STATDIFF PRESS SWITCHCONTROL RELAYCONTROL RELAYELECT ACTUATOR W/SPRING RETURN
106
ZN
-H1
107
ZN
-H2
WALL MOUNTEDWALL MOUNTED
HUM
105
SA
-RH
104
SA
-T
117
SF
-C
ESHHL
100
ZN
-H3
WALL MOUNTED
2
2
NOTES
FRONT VIEW
DDC CONTROLLERS ARE SUPPLIED BY OWNER AND MOUNTED BY
CONTRACTOR.
KEEP ALL LOW VOLTAGE CONTROL WIRING ( UNDER 25V) AND LOW
VOLTAGE POWER WIRING (OVER 25V) SEPARATED. (RUN IN SEPARATE
CONDUIT).
PLYWOOD SIZE IS BASED ON THE NUMBER OF CONTROLLERS IN EACH
LOCATION. COORDINATE WITH OWNERS REPRESENTATIVE.
4/0 BOX WITH PULL CHAIN.18W LED LIGHT WITH GUARD.
4'x4'x3/4" PLYWOOD (MIN)(PAINT FRONT AND
ENDS MACHINE GRAY.)
1-1/2" UNISTRUTCHANNEL (2)
1.
2.
3.
6" x 6" WIRE TROUGH
FLOOR
3/4" CONDUIT
120 VAC INPUT POWER
DEDICATED 15A CIRCUIT
1" CONDUITMINIMUM
I/O
6"x6" WIRETROUGH
FLOOR
EXP. ANCHORS
1-1/2" UNISTRUTCHANNEL (2)
4'x4'x3/4" PLYWOOD (MIN)(PAINT FRONT AND ENDSMACHINE GRAY)
3/4" CONDUIT
4/0 BOX WITHPULL CHAIN. 18WLED WITH GUARD.
WA
LL
ASC ASC
BY DIVISION 16
2" MIN. CONDUIT (2)
3'-6
" T
YP
ICA
L
3' MIN DISTANCE
POSTBASE (2)
BRACEFITTING (2)
OPTIONAL FLOOR MOUNT
SIDE VIEW
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/2
7/20
1 7 3
:04:
01 P
MC
:\Use
rs\r
diem
er\D
ocum
ents
\245
-32_
ME
CH
_CE
NT
RA
L_v1
6_rd
iem
er.r
vt
1 Hospital Drive, Columbia, MO65212
M702
11/06/2017
53474
CONTROLS
NLP
BID DOCUMENTS
University of Missouri -Columbia
NLP
CP171091
RJD
Medical ScienceFirst FloorResearch
LaboratoryRenovation
NTS1
AHU 1-01 CONTROL DIAGRAM
NTS4
ASC PANEL MOUNTING DETAIL1
# DATE DESCRIPTION
1 11/16/17 ADDENDUM 1
2 11/27/17 ADDENDUM 2
2
OCCUPANCYSENSOR
S
T
KEYED NOTES:
1
2 OCCUPANCY SENSORS PROVIDED AND INSTALLED BY DIV. 26 CONTRACTOR. CONTROL WIRING
BETWEEN OCCUPANCY SENSOR AND LACS BY DIV. 23 CONTRACTOR. NOTE THAT MULTIPLE OCCUPANCY
PRESSURE INDEPENDENT CONTROL VALVE.3
3
6
5
4
SERVICE DISCONNECT/SWITCH. LOCATED WITHIN EYESIGHT OF LACS CONTROL PANELS.
ACTUATOR. COORDINATE FUSE SIZE WITH DIV. 26 CONTRACTOR AND LACS SUPPLIER.
INLINE FUSE ON SECONDARY OF 24VAC TRANSFORMER. LOCATED WITHIN EYESIGHT OF ELECTRIC
COIL DISCHARGE.
VAV SUPPLY TEMP SENSOR PROVIDE BY LACS SUPPLIER, LOCATED APPROX. 8 FT. FROM REHEAT
T4
SA
GE
A
FE
A
FE
A
HWS
HWR
VAV FUME
EXHAUST
AIR VALVE
PSPS
GENERAL
EXHAUST
AIR VALVE
SUPPLY
AIR VALVE
24VAC TRANSFORMER, PROVIDED AND INSTALLED BY DIV. 26 CONTRACTOR.
DAISY CHAIN WITH OTHER
DEVICES ON THE SAME
ROOM LEVEL NETWORK,
COORDINATE EXACT QUANTITY
OF DEVICES PER ROOM LEVEL
NETWORK WITH LABORATORY
AIRFLOW CONTROL SYSTEM
SUPPLIER
65
1
LINE VOLTAGE
WIRE (TYPICAL)
VAV FUME
EXHAUST
AIR VALVE (TYPICAL)
VAV
FUME
HOOD
VAV
FUME
HOOD
COORDINATE ALL
CABLING WITH LACS
SUPPLIER (TYPICAL)
PROVIDE LACS REPEATERS
IN COMMUNICATION NETWORK
AS NECESSARY (TYPICAL)
LACS COMMUNICATION
NETWORK, TWISTED
SHIELDED PAIR 22 AWG
CAT-4 CABLE (TYPICAL)
DAISY CHAIN WITH OTHER
ROUTERS IN BUILDING
ZONE SENSOR, WITH CAPABILITY
TO ACCESS ALL LACS POINTS
IN A GIVEN ZONE THROUGH
ZONE SENSOR RJ45 CONNECTOR
FC BUS REFERTO DETAIL 3SHEET M702
FUME HOODMONITOR MOUNTEDON FUME HOOD(TYP)
FUME HOODMONITOR POWERSUPPLY (TYP)
SENSORS WILL BE INSTALED IN LABS.
AIR VALVEDIFFERENTIALPRESSURE SWITCH(TYPICAL)
SASH SENSOR,COORDINATE WITHFUME HOODREQUIREMENTS(TYP)
LABORATORY AIRFLOW CONTROL DIAGRAM TYPICAL PER LAB ROOM.NOT INTENDED TO BE DAISY CHAINED TO MULTIPLE ROOMS. NOTE:
ALL VALVES ARE HIGH SPEED ACTUATORS AND SHALL BE INSTALLEDIN A HOME RUN CONFIGURATION. NO OTHER VALVES CAN BE DAISY-
CHAINED FROM THIS POWER. BUS POWER CONFIGURATIONS ARENOT ALLOWED BETWEEN HIGH-SPEED VALVES. FOR LOADS UP TO 96VA, USE A DEDICATED 14 AWG CABLE WITH A MAXIMUM LENGTH OF
110 FEET (33 METERS) HOME-RUN BETWEEN THE TRANSFORMER ANDTHE VALVE.
RMI
ROOM INTEGRATOR (RIM) LACSCONTROL PANEL (LCP).LOCATE ABOVE ACCESSIBLECEILING. PROVIDE MINIMUMONE ROUTER PER VAVPRESSURIZATION ZONE.
POWER - 14 AWG FROM500 VA POWER SUPPLY.REFER TO DETAIL 2 ONTHIS SHEET.
POWER - 14 AWG FROM500 VA POWER SUPPLY.REFER TO DETAIL 2 ONTHIS SHEET.
POWER - 14 AWG FROM500 VA POWER SUPPLY.REFER TO DETAIL 2 ONTHIS SHEET.
POWER - 14 AWG FROM500 VA POWER SUPPLY.REFER TO DETAIL 2 ONTHIS SHEET.
PROXIMITY SENSOR(TYP)
FUME HOOD MONITOR POWER SUPPLY PROVIDED AND INSTALLED BY DIV. 26 CONTRACTOR.7
100 VA
PSH500A
100 VA
100 VA
100 VA
100 VA
DISCONNECT
SWITCH
24V
COM
24V
COM
24V
COM
24V
COM
24V
COM
480
277
240
120
COM
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
RIB AC
BREAKER
SWITCH
ENCLOSED AC POWER SUPPLY
POWER
SUPPLY/TRANSFORMER
(FUSE)
GENERAL NOTES: KEYED NOTES:EACH SECONDARY OUTPUT LINE CAN POWER 3-5 VAV CONTROLLERS
MAXIMUM. (100 VA).
PRIMARY LINE INFO: 480/277/240/120 Vac, #12 AWG MINIMUM.
SECONDARY LINE INFO: 24 Vac, #12-26 AWG, 100 VA. MAX LENGTH 175 FEET
USING #14 AWG.
DISCONNECT SWITCH REQUIRED, EXTERNALLY MOUNTED WITHIN 12
INCHES OF RIB POWER SUPPLY.
500VA POWER SUPPLY - RIB MODEL# PSMN500A OR APPROVED
EQUIVALENT.
ALL SECONDARY LINES MUST BE LABELED IN ENCLOSURE AS TO WHICH
VAV'S THEY POWER PRIOR TO ENERGIZING POWER SUPPLY.
A SEPARATE 3 AMP FUSE IS REQUIRED WITHIN 3 FEET OF EACH VAV.
1. SECONDARY LINE CAN BE RAN IN SAME CONDUIT AS FC.
2. ENCLOSED POWER SUPPLY MUST BE LOCATED IN ELECTRICAL ROOM,
MECHANICAL ROOM, OR JANITOR'S CLOSET AND BE ACCESSIBLE. ANY OTHER
LOCATION MUST BE APPROVED BY THE OWNER'S REPRESENTATIVE.
1
2
3
4
5
6
7
5
67
3
2
4
1
FAN RELAY AND CONTROL VALVE WIRING SHALL BE CONNNECTED TO A TERMINALSTRIP IN THE BCU AT THE FACTORY.
8 CONDUCTOR, 22 GAUGE, TWISTED, SHIELDED, STRANDED WIRE. ROUTE FROMBCU TERMINAL STRIP TO THE VAV BOX CONTROLLER SERVING SAME ROOM.
XXX XX X X X
CWR
CWS
AIR
OU
T
XX
RE
TU
RN
AIR
IN
BLOWERCOILUNIT (BCU)
M
KEYED NOTES:1
2
1
2
TYPEAOBIBO
POINT NAMECLG-OFAN-SFAN-C
DESCRIPTIONCOOLING VALVE OUTPUTFAN STATUSFAN COMMAND
DEVICENC MOD ELECT ACTUATORCURRENT SWITHCCONTROL RELAY
LOCATE DPT AS SHOWNON MECH PLANS
DPT
H L
NORTH FACING WALL
DAMPENER
ROUTE TO SPACE
12X12X6 J-BOX
REQUIRED POWER BY TCC
OA PRESSURE STATION
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
11/2
7/20
1 7 3
:04:
01 P
MC
:\Use
rs\r
diem
er\D
ocum
ents
\245
-32_
ME
CH
_CE
NT
RA
L_v1
6_rd
iem
er.r
vt
1 Hospital Drive, Columbia, MO65212
M703
11/06/2017
53474
CONTROLS
NLP
BID DOCUMENTS
University of Missouri -Columbia
NLP
CP171091
RJD
Medical ScienceFirst FloorResearch
LaboratoryRenovation
12" = 1'-0"1
LABORATORY AIRFLOW CONTROL SYSTEMSCHEMATIC1
NO SCALE2
500 VA POWER SUPPLY DIAGRAM
NTS3
BLOWER COIL UNIT DETAIL
NTS4
SPACE DIFF PRESSURE TRANSMITTER1
# DATE DESCRIPTION
1 11/27/17 ADDENDUM 2
1
CR
WAP
WAP
WAP
WAPWAP
WAP
WAP
WAP
WAP
WAPWAPWAP
WAP WAP
WAPWAP
WAPWAP WAP
WAP
CR
CR
CR
CR
CRCR
CR
WAPWAPWAPWAP
WAP
WAP
J
J
J J
J
J
J
J
J
J
JJ
J
3
4
5
5.5
7
8
9.1
RPN
MLKJIHGF
2
Q
PANEL 1EPA
PANEL 1PPA
PANEL 1PPC
XFRMR T-1EPA
PANEL 1HPA
EXISTINGPANEL LP-144
PANEL P5
EXISTINGPANEL PL21E
CORRIDOR
M122
EAST RESEARCHLAB
M134
FREEZERSTORAGE /SUPPORT
M132
DRY STORAGE
M126
TISSUE CULTURE
M134A
EXISTING ITCLOSET
M125
FREEZERSTORAGE /SUPPORT
M112
FLEX RESEARCHLAB
M114
TISSUE CULTURE
M148B
WEST RESEARCHLAB
M148
TISSUE CULTURE
M134C
DARK ROOM
M134B
DARK ROOM
M128
MECHANICAL
M130
STORAGE/ RISER
M125B
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCIGFCI
GFCI
GFCI
E301
2
GFCI
E301
4
E301
3
EP005EP005
EP003ETRETRETR
ETRETRETR
ETR
ETR
ETR
CORRIDOR
M145
CORRIDOR
M122
ETR
EP005
EP005
EP005
EP005
EP005
1PP-M148
2
1PP-M148
6 8 10
1PP-M148
4
12
43
1PP-M148
34/36
1PP-M148
26/28
1PP-M148
30/32
1PP-M14818
1PP-M148
24
1PP-M14822 1PP-M14820
51535557
59
61
63
71
1PP-M148
69
1PP-M148
67
1PP-M148
65
1PPB
31
1PPB
27
1PPB
25
1PPB
21
1PPB
23
1PPB12
1PPB6
1PPB
14/16
1PPB
10
1PPB8
1PPC
2
1PPC
6
1PPC
4
1PPC
8
1PPB
18
1PPB
201PPB
34/36
1PPB32
1PPB30
1PPB28
1PPB26
1PPC
10
1PPC
46
1PPC
44
1PPC 14
1PPC16
1PPC
18
1PPC
20/22
1PPC
12
1PPC
41
1PPC
39
1PPC
24
1PPC
38
1PPC
36
D1
D1
D1
D1
D1
1PPC
40
1PPC
34
1PPA
1
1PPA
3
1PPA
5
1PPA
7
1PPB
1
1PPB
3
1PPB
13
1PPB11
1PPB
17/19
PANEL1PP-M148
PANEL 1PPB
1PP-M148 1PP-M148 1PP-M148
1PP-M148
1PP-M148
1PP-M148
1PP-M148 1PP-M148 1PP-M148
1PP-M148
1PP-M148
1PP-M148
1PP-M148
PANELCIRCUIT #
1PP-M148135
PANELCIRCUIT #
1PP-M1489
111315
PANELCIRCUIT #
1PP-M14817192123
PANELCIRCUIT #
1PP-M14825272931
EP009
EP008
PANELCIRCUIT #
1PPC1357
PANELCIRCUIT #
1PPC9
111315
PANELCIRCUIT #
1PPC17192123
PANELCIRCUIT #
1PPC25272931
PANELCIRCUIT #
1PPC333537
45
1PP-M14844
1PP-M14846
1
S T
10
D1
1PPB
15
D1
1PPB
9
D1
1
E301
EXISTINGTRANSFORMER
T41W-T4
EXISTINGPANEL EP21W
EXISTINGPANEL D41W
EXISTINGPANEL D21W
VAV POWERSUPPLY
ETR
ETR
ETR
ETR
ETR
ETR
ETR
EP010
EP010
EP015
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETRETR
ETR
ETRETR ETR
ETR
ETR
ETR
D1
LP-144
2
LP-144
15
LP-14417
EP008
EP005
LP-14418/20
ETR
LP-144
4
LP-144 12
EP014
EP014EP014
EP014
EP014
EP014
P5
13
ETR
1PP-M148
33
EP002ANATOMY
CADAVER LAB
M144
EP020
EP021
EP021
EP021
EP021
EP021
EP021
EP021
1PPB
42
1PPB
40
1PPB38
1PPB37
1PPB
39
1PPB
41
EP022EP022
EP024
EXISTING FIREALARMPOWER
EXTENDERPANEL
ELECTRICAL ROOM M159
+36"+36"
+36"
+36"
+36"
+36"
+36"
+36"
+36"
+36"
+36"+36"
+36"
MECHANICALROOM
M120
+36"
+36"
+36"
+36"
+36"
6"x
4"
12"x4"
6"x
4"
+36"
+36"+36"
+36"
+36"
+36"
+36"
+36"
GFCI
GFCI
LP-144
LP-144
12
14
EP031EP031
METASYSPANEL
1PPB2
LP-14419
GFCI
LP-144
21
LP-144
23
EP032
EP033EP034
EP023
EP023
EP023
EP023
EP023
1PPB43
EP023
EP023
EP023
1PPC
43
1PPC45
EP026
EP027
EP0281
1
1
1
1
1
1
PHOENIXVALVE POWER
SUPPLY
PHOENIXVALVE POWER
SUPPLY
PHOENIXVALVE POWER
SUPPLY
PHOENIXVALVE POWER
SUPPLY
1PP-M148
16
47
1PP-M148
1PPB
33
1PPB
7
1PPB
22
1PPC
26
1PPC
32
EP007
EP007
EP007
EP007
EP007
EP007
EP007
5.5
7
EP001EP001
EP001 EP001
EP001
EP001
VUUU
(TYP)(TYP)
UUU
Y
(TYP) (TYP)
(TYP)
(TYP)
LEGEND:
UUU - DENOTES PANELBOARD NAME
V - DENOTES 1ST CIRCUITW - DENOTES 2ND CIRCUITX - DENOTES 3RD CIRCUITY - DENOTES 4TH CIRCUIT
PANELCIRCUIT #
PANELCIRCUIT #
UUUVWXY
1
E301
UUU
X
UUU
W
EP011 EP011
EP011
EP011
EP018
EP018
EP018
EP025
9.1
M
EP005
EP005
EP005
EP005
GFCIEP006D1
1EPA
29/31
1EPA
33/35
1EPA23
1EPA25
1EPA21
1EPA19
1EPA11/13
1EPA15/17
1EPA1
1EPA3
1EPA5
1EPA7
1EPA9
1EPA27
1EPA
37GFCI
(TYP)
EP004
EP019
EP019
GFCI
EP023
EP023
EP023
EP0233EP005
EP005
EP005
EP005
1EPA20
1EPA22
1EPA24
1EPA26
1EPA28
1EPA
30/32
1EPA
16/18
1EPA
12/141EPA2
1EPA4
1EPA6
1EPA8
34/361PPA
11
1EPA
1EPA38
(TYP)EP019
EP019
EP004
+18"
EP023
EP023
EP023
EP023
5.57 65.9
LEVEL ONE0' - 0"
LEVEL TWO13' - 8"
5.57 5.57 65.9 5.57 65.9
UUUY
UUUX
UUUW
EP011
EP012
EP013
EP014(TYP)
(TYP)EP011
EP017EP030
MONICASANTOYOSANTOS
NUMBERE-2000174546
IRU
OSSIMFO
ET
AT
S
PROFE
SSIONAL EN
G
INEER
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
0" 1"
Original Size: 1 1/2" Drawing may have been reduced.
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
MONICA S. SANTOS - ELECTRICALMO# E-2000174546
11/06/2017
11/2
7/20
1 7 5
:10:
03 P
MC
:\Use
rs\B
en.A
nder
son\
Doc
umen
ts\A
217-
13 E
LEC
v16
_ban
ders
onT
T9 L
U.r
vt
E301
11/06/2017
53474
LEVEL ONE -POWER FLOOR
PLAN
BP
A
BID DOCUMENTS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
BPA
CP171091
MSS
Medical ScienceFirst FloorResearch
LaboratoryRenovations
PLAN NOTESEP018 PLUG INTO OUTLET WITH MATCHING CIRCUIT NUMBER.
EP019 PROVIDE JUNCTION BOX WITH EMPTY 3/4" CONDUIT EXTENDED TO PANEL 1EPA FOR FUTURECIRCUIT. PROVIDE WITH PULL STRING AND LABEL FUTURE.
EP020 PROVIDE ALL REQUIRED FITTINGS TO RE-ARRANGE WIREMOLD IN A LINEAR CONFIGURATION.CONNECT TO EXISTING SECTION.
EP021 PROVIDE ROUGH-IN FOR CARD READER. CONTRACTOR SHALL PULL WIRING FOR CARDREADER. OWNER SHALL INSTALL CARD READER AND MAKE FINAL TERMINATIONS. REFER TODETAIL 4 ON SHEET E602 FOR ADDITIONAL INFORMATION.
EP022 MOUNT DEVICES TO CEILING PANEL.
EP023 PROVIDE 3 #10 AWG AND 1 #10 GROUND IN 3/4" CONDUIT.
EP024 MOUNT BOTTOM OF CABLE TRAY AT 7'-11" AFF.
EP025 EXTEND DATA CONDUIT FROM DESKTOPS THROUGH PIPE CHASE UP TO ACCESSIBLE CEILINGAND BUSH FOR WIRING PATHWAY. PROVIDE EITHER INDIVIDUAL HOMERUNS OR CONDUITSIZED FOR NUMBER OF CABLES PER TABLE ON SHEET E001. COORDINATE MOUNTING WITHOTHER TRADES USING SAME PIPE CHASE.
EP026 PROVIDE HOUSEKEEPING PAD FOR TRANSFORMER. REFER TO DETAIL 7 ON SHEET E601 FORADDITIONAL INFORMATION.
EP027 RE-CONNECT NEW WIREMOLD TO EXISTING WIREMOLD CIRCUIT.
EP028 REPLACEMENT OF PANEL TO OCCUR AFTER-HOURS DURING EVENINGS, WEEK-ENDS ORDURING CLASS BREAK TIMES LISTED ELSEWHERE IN THE SPECIAL CONDITIONS.
EP030 REFER TO PLANS FOR CIRCUIT TO OUTLET SERVING REFRIGERATOR.
EP031 RE-CONNECT NEW RECEPTACLE TO EXISTING CIRCUIT SERVING WIREMOLD. FIELD VERIFYCIRCUIT ASSIGNMENT IN EXISTING PANELBOARDS.
EP032 PROVIDE POWER CONNECTION FOR SURGICAL LIGHT IN CEILING. COORDINATE EXACTREQUIREMENTS WITH OWNER PRIOR TO ROUGH-IN.
EP033 PROVIDE POWER CONNECTION TO SURGICAL LIGHT COMPUTER. COORDINATE EXACTREQUIREMENTS WITH OWNER PRIOR TO ROUGH-IN.
EP034 EXTEND 2" CONDUIT FROM 18" AFF TO ABOVE ACCESSIBLE CEILING AND BUSH FOR OWNERINSTALLED SURGICAL LIGHT CONTROLS. COORDINATE EXACT REQUIREMENTS WITH OWNERPRIOR TO ROUGH-IN.
PLAN NOTESEP001 WIREMOLD TO BE PROVIDED WITH WHIP AND PLUG TO BE PLUGGED INTO RECEPTACLE
MOUNTED BELOW COUNTER. REFER TO TYPICAL LAB WORKSTATION ELEVATION, THISSHEET, FOR LOCATION OF OUTLET AND CIRCUITING.
EP002 FEED WIREMOLD FROM NEW WALL. PROVIDE CONDUIT SIZED AS REQUIRED TOACCOMMODATE CABLE FILL.
EP003 PROVIDE DUAL CHANNEL ALUMINUM RACEWAY (WIREMOLD AL4000 SERIES ORPRE-APPROVED EQUAL) AND REQUIRED ACCESSORIES FOR MOUNTING DEVICES. PROVIDEGRAY DEVICES TO MATCH. CONTRACTOR TO VERIFY CABLE FILL DOES NOT EXCEED RATINGOF RACEWAY. MOUNT AT 36" AFF.
EP004 MOUNT DEVICES IN FREEZER STORAGE AT 36" AFF UNLESS NOTED OTHERWISE.
EP005 PROVIDE NEMA 6-30R RECEPTACLE.
EP006 POWER CONNECTION FOR POLISHER. CONFIRM MOUNTING HEIGHT AND INSTALLATIONREQUIREMENTS WITH ARCHITECT PRIOR TO ROUGH-IN.
EP007 MOUNT JUNCTION BOX ABOVE FUME HOOD ON WALL. MAKE FLEXIBLE CONNECTION TO THETOP OF THE FUME HOOD. COORDINATE CONNECTION WITH HOOD MANUFACTURER ANDINSTALLER.
EP008 EXISTING EQUIPMENT WITHIN THIS AREA TO REMAIN UNLESS NOTED OTHERWISE. MAINTAINCONTINUITY OF CIRCUITS TO ENSURE DEVICES ARE FULLY FUNCTIONAL.
EP009 REMOVE EXISTING PANEL AND REPLACE WITH NEW IN THE SAME LOCATION. RECONNECTALL EXISTING CIRCUITS TO NEW BREAKERS AND UPDATE PANELBOARD DIRECTORY WITHCIRCUITS BEING SERVED.
EP010 EXISTING WIREMOLD TO REMAIN. MAINTAIN CONTINUITY OF CIRCUIT TO ENSURE DEVICESARE FULLY FUNCTIONAL.
EP011 MOUNT DATA ON VERTICAL POST OF LAB WORKSTATION. REFER TO ARCHITECTURALELEVATION A1 ON SHEET A801 FOR ADDITIONAL INFORMATION.
EP012 PRE-WIRED WIREMOLD WHIP PROVIDED WITH FURNITURE. REFER TO ARCHITECTURALDRAWINGS FOR ADDITIONAL INFORMATION.
EP013 WIREMOLD PROVIDED WITH FURNITURE. REFER TO ARCHITECTURAL DRAWINGS FORADDITIONAL INFORMATION.
EP014 RECEPTACLE TO BE MOUNTED ON 6" FIXED SECTION OF FURNITURE BACKPLATE. REFER TOARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
EP015 PROVIDE NEW WIREMOLD TO MATCH EXISTING. PROVIDE ALL REQUIRED FITTINGS TOATTACH TO REMAINING LINEAR SECTION. RECONNECT ALL CIRCUITS AND ENSURE ALLDEVICES ARE ENERGIZED.
EP017 PROVIDE OUTLET TO BE CONTROLLED BY MOTION SENSORS. OUTLET DEDICATED TO TASKLIGHTING. REFER TO LIGHTING PLANS FOR CIRCUITRY.
POWER GENERAL NOTES1 DEVICES SHALL BE ALIGNED VERTICALLY. REFER TO TYPICAL WALL MOUNTING DEVICE
DETAIL 6 ON SHEET E601.
2 ALL DATA OUTLETS TO BE TERMINATED IN EXISTING IT CLOSET M125.
4'0 8' 16'
NO
RT
H
SCALE: 1/8" = 1'-0"
LEVEL ONE - POWER PLAN
0 2' 4' 8'SCALE: 1/4" = 1'-0"
TYPICAL LAB WORKSTATION2
0 2' 4' 8'SCALE: 1/4" = 1'-0"
M112 - FREEZER STORAGE/SUPPORT3
0 2' 4' 8'SCALE: 1/4" = 1'-0"
M132 - FREEZER STORAGE/SUPPORT4
0 2' 4' 8'SCALE: 1/4" = 1'-0"
TYPICAL LAB WORKSTATION ELEVATION1
# DATE DESCRIPTION
1 11/27/17 ADDENDUM 2
1
J
J
J
J
J
J
J
3
4
5
5.5
7
8
9.1
RPN
MLKJIHGF
2
Q
CORRIDOR
M122
EAST RESEARCHLAB
M134
FREEZERSTORAGE /SUPPORT
M132
DRY STORAGE
M126
TISSUE CULTURE
M134A
EXISTING ITCLOSET
M125
FREEZERSTORAGE /SUPPORT
M112
FLEX RESEARCHLAB
M114
TISSUE CULTURE
M148B
WEST RESEARCHLAB
M148
TISSUE CULTURE
M134C
DARK ROOM
M134B
DARK ROOM
M128
EAST RESEARCHLAB
M134
MECHANICAL
M130
STORAGE/ RISER
M125B
BCU
1-03
EF
1-01
AHU
1-01
BCU
1-04
EF
1-02
HWRP
1-01
1HPA2/4/6
XFRMR T-1EPA
PANEL 1EPA
PANEL 1PPA
PANEL 1HPAPANEL 1PPC
PANEL 1PPB
EXISTINGPANEL LP-144
PANEL1PP-M148
PANEL P5
EXISTINGPANEL PL21E
EH001
EH002EH002
1PPA
2EH003
1HPA
26/28/30
EH003
EH004
1HPA20/22/24
1HPA
8/10/12
EH009
EH005EH005
EXISTINGPANEL D21W
EXISTINGPANEL D41W
EXISTINGPANEL EP21W
EXISTINGTRANSFORMER
T41W-T4
1
S T
10
EH004
FTU
1-44
EH011
1PP-M148
7
EH005
1PPA
4 EH007
EH015 1PPA
6
VAV POWERSUPPLY
EXISTING FIREALARMPOWER
EXTENDERPANEL
MECHANICALROOM
M120
CWP
1-01
VENDING
M111
1HPA
14/16/18EH006
EH005EH005
EH005EH010
EH010
METASYSPANEL
1PPA10
EH012
SD
1-03
SD
1-02
SD
1-03
1PP-M148
14
1
EH014
49
1PP-M148
1
EH014
1PPB
24
1
EH014
1PPC28
1PPC
30
1
EH014
EH014
1PPB
35
EH014
1
1PPA
8
1PPB
5
EH014
1
PHOENIXVALVE POWER
SUPPLYPHOENIX
VALVE POWERSUPPLY
PHOENIXVALVE POWER
SUPPLY
1PPA
EH008
(TYP)
12
1PPA
14
EH008
1PPA
16
1
1
PHOENIXVALVE POWER
SUPPLYEH008
1PP-M148
35
MONICASANTOYOSANTOS
NUMBERE-2000174546
IRU
OSSIMFO
ET
AT
S
PROFE
SSIONAL EN
G
INEER
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
0" 1"
Original Size: 1 1/2" Drawing may have been reduced.
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
MONICA S. SANTOS - ELECTRICALMO# E-2000174546
11/06/2017
11/2
7/20
1 7 5
:10:
09 P
MC
:\Use
rs\B
en.A
nder
son\
Doc
umen
ts\A
217-
13 E
LEC
v16
_ban
ders
onT
T9 L
U.r
vt
E401
11/06/2017
53474
LEVEL ONE - HVACPOWER FLOOR
PLAN
BP
A
BID DOCUMENTS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
BPA
CP171091
MSS
Medical ScienceFirst FloorResearch
LaboratoryRenovations
PLAN NOTESEH001 PROVIDE 60 AMP, 480 V, 3 POLE, FUSIBLE DISCONNECT SWITCH FUSED AT 60 AMP IN NEMA 1
ENCLOSURE.
EH002 PROVIDE 3 #6 AWG AND 1 #10 GROUND IN 1" CONDUIT.
EH003 PROVIDE TOGGLE STYLE 1 HP RATED MANUAL STARTER WITH MOTOR THERMAL OVERLOADSIN NEMA 1 ENCLOSURE. MAKE ALL FINAL CONNECTIONS TO EF.
EH004 PROVIDE 30 AMP, 480 V, 3 POLE, FUSIBLE DISCONNECT SWITCH FUSED AT 15 AMP IN NEMA 1ENCLOSURE.
EH005 PROVIDE 3 #12 AWG AND 1 #12 GROUND IN 3/4" CONDUIT.
EH006 PROVIDE 30 AMP, 480 V, 3 POLE, UL/NEMA TYPE 1, NEMA SIZE 0, FUSIBLE, FULL VOLTAGETYPE, NON-REVERSING, COMBINATION STARTER/DISCONNECT SWITCH WITH INTEGRALCLASS 20 SOLID-STATE OVERLOAD RELAY ADJUSTED PER MANUFACTURER'SREQUIREMENTS. FUSE AT 15 AMP. COORDINATE INSTALLATION AND FINAL CONNECTIONWITH THE MECHANICAL CONTRACTOR.
EH007 PROVIDE FINAL CONNECTION TO FACTORY PROVIDED LIGHT FIXTURE(S) AND GFCIRECEPTACLE(S) IN AIR HANDLING UNIT. COORDINATE EXACT WIRING REQUIREMENTS ANDLOCATIONS WITH MECHANICAL CONTRACTOR/EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
EH008 PROVIDE 1 HP RATED TOGGLE STYLE, 120 V, 1 POLE, NEMA 1 SWITCH AS DISCONNECTINGMEANS FOR PHOENIX VALVE POWER. PROVIDE ALL FINAL CONNECTIONS TO CONTROLLERS.REFER TO DETAIL 2, SHEET M703 FOR ADDITIONAL INFORMATION ON POWER SUPPLY.
EH009 PROVIDE 30 AMP, 480 V, 3 POLE, UL/NEMA TYPE 1, NEMA SIZE 00, FUSIBLE, FULL VOLTAGETYPE, NON-RESERVING, COMBINATION STARTER/DISCONNECT SWITCH WITH INTEGRALCLASS 20 SOLID-STATE OVERLOAD RELAY ADJUSTED PER MANUFACTURER'SREQUIREMENTS. FUSE AT 15 AMP. COORDINATE INSTALLATION AND FINAL CONNECTIONWITH THE MECHANICAL CONTRACTOR.
EH010 PROVIDE 2 #10 AWG AND 1 #10 GROUND IN 3/4" CONDUIT.
EH011 PROVIDE 1 POLE, 1 HP RATED TOGGLE STYLE SWITCH IN NEMA 1 ENCLOSURE. PROVIDE ALLFINAL CONNECTIONS TO FTU.
EH012 PROVIDE 1 HP RATED TOGGLE STYLE, 120 V, 1 POLE, NEMA 1 SWITCH AS DISCONNECTINGMEANS. PROVIDE ALL FINAL CONNECTIONS TO METASYS PANEL.
EH014 PROVIDE TOGGLE STYLE SWITCH AS DISCONNECTING MEANS AND MAKE FINAL CONNECTIONTO PHOENIX VALVE CONTROLS. CONTRACTOR SHALL COORDINATE EXACT LOCATION OFPHOENIX CONTROL PANEL PRIOR TO ROUGH-IN.
EH015 PROVIDE 1 HP RATED TOGGLE STYLE, 120 V, 1 POLE, NEMA 1 SWITCH AS DISCONNECTINGMEANS FOR VAV UNIT POWER SUPPLY. PROVIDE ALL FINAL CONNECTIONS TOCONTROLLERS. REFER TO DETAIL 2, SHEET M703 FOR ADDITIONAL INFORMATION ON POWERSUPPLY.
4'0 8' 16'
NO
RT
H
SCALE: 1/8" = 1'-0"
LEVEL ONE - HVAC POWER PLAN
# DATE DESCRIPTION
1 11/27/17 ADDENDUM 2
1
1
MONICASANTOYOSANTOS
NUMBERE-2000174546
IRU
OSSIMFO
ET
AT
S
PROFE
SSIONAL EN
G
INEER
A
B
C
D
E
6 5 4 3 2 1
1900 w.47th Place, #300, Westwood, KS 66205(913) 362-6500 www.PGAV.COM
DRAWN: CHECKED:
DATE:
PGAV # CLIENT #
SHEET #:
0" 1"
Original Size: 1 1/2" Drawing may have been reduced.
PECKHAM GUYTON ALBERS & VIETS, INC.
Electrical Engineers1600 Genessee St, Suite 260Kansas City, MO 64102
ANTELLA CONSULTING ENGINEERS, INC.
Plumbing, Mechanical & Fire Protection Engineers6 South Old OrchardSt Louis, MO 63119
ROSS & BARUZZINI, INC.
(314) 918-8383
(816) 421-0950
THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENT TOWHICH THEY ARE AFFIXED, AND EXPRESSLY DISCLAIM ANYRESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS,
ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTSRELATING TO OR INTENDED TO BE USED FOR ANY PART OR PARTS
OF THE ARCHITECTURAL OR ENGINEERING PROJECT.
PECKHAM GUYTON ALBERS & VIETS, INC.MO STATE CERTIFICATE OF AUTHORITY #000086
MO STATE CERTIFICATE OF AUTHORITY #E-2005013590
MO STATE CERTIFICATE OF AUTHORITY #000148
MONICA S. SANTOS - ELECTRICALMO# E-2000174546
11/06/2017
11/2
6/20
1 7 8
:29:
28 P
MC
:\Use
rs\M
onic
a.S
anto
s\D
ocu m
ents
\A21
7-13
ELE
C v
16_M
onic
aSan
tos 5
192.
rvt
E801
11/06/2017
53474
LIGHTINGSCHEDULES
Aut
hor
BID DOCUMENTS
University of Missouri -Columbia
1 Hospital Drive, Columbia, MO65212
Author
CP171091
Checker
Medical ScienceFirst FloorResearch
LaboratoryRenovations
LUMINAIRE SCHEDULETYPE MOUNTING LAMPS LUMENS
COLORTEMP.
CRI WATTS VOLTAGE MANUFACTURER DESCRIPTION EQUALS
A RECESSEDGRID
LED 3800 lm 3500 K 80 44 277 H.E. WILLIAMS - HETHET-G-S14-L38/835-A-DIM-UNVOR PRE-APPROVED EQUAL
1X4 BY 3-5/8" DEEP RECESSED TROFFERWITH FROSTED ACRYLIC SHIELDING0-10V DIMMING
B SURFACEGRID
LED 3400 lm 3500 K 80 32 277 EATON - METALUX22SP-34-35OR PRE-APPROVED EQUAL
2X2 BY 7/8" DEEP SURFACE-MOUNTED TROFFERWITH WHITE FROST LENS0-10V DIMMING
C PENDANT LED 3800 lm 3500 K 80 20 277 H.E. WILLIAMS - 75 LED75S-4-L40/835-DRV-UNVOR PRE-APPROVED EQUAL
4FT SUSPENDED LINEAR DIRECT3" TALL
NULITE - SA LED SERIESSA-4-10L35-UNV-D-SQ
D PENDANT LED 4170 lm 3500 K 80 42 277 COOPER LIGHTING - CORELITERZL-W-B-2-L35-1-D-UNV-A-C-48-ST-4-STD-WOR PRE-APPROVED EQUAL
4FT SUSPENDED LINEAR 85% DIRECT / 15% INDIRECT3-1/2" TALLWITH PRISMATIC LENS WITH MICRO BAFFLE0-10V DIMMING
E8 RECESSEDFLANGE
LED 569 lm 3500 K 80 39 277 NULITE - REGOLORF4-05-L35-UNV-D-1C-ST-F-WH-8'OR PRE-APPROVED EQUAL
8FT RECESSED LINEAR DIRECT5-1/2" TALL0-10V DIMMING
F PENDANT LED 8340 lm 3500 K 80 84 277 COOPER LIGHTING - CORELITERZL-W-B-2-L35-1-D-UNV-A-C-48-ST-8-STD-WOR PRE-APPROVED EQUAL
8FT SUSPENDED LINEAR 85% DIRECT / 15% INDIRECT3-1/2" TALLWITH PRISMATIC LENS WITH MICRO BAFFLE0-10V DIMMING
G RECESSED LED 1900 lm 3500 K 80 22 277 H.E. WILLIAMS - HETHET-G-S12-L19/835-A-DIM-UNVOR PRE-APPROVED EQUAL
1X2 BY 3-5/8" DEEP RECESSED TROFFERWITH FROSTED ACRYLIC SHIELDING0-10V DIMMING
H WALL LED 413 lm 3500 K 80 26 277 IO LIGHTING - LINE .750-03-I-35KVHO-91-102-1-10-12-4OR PRE-APPROVED EQUAL
5FT WALL-MOUNTED LINEAR ASYMMETRIC3/4" TALL0-10V DIMMING
J RECESSED LED 1000 lm 3500 K 80 11 277 EATON - PORTFOLIOLD4B-10-D010-EU4B-1020-80-35-4LB-M-0-HOR PRE-APPROVED EQUAL
4IN RECESSED DOWNLIGHT5-1/2" TALL0-10V DIMMING
K RECESSED LED 1450 lm 3500 K 84 20 277 FINELITE - HP-4HP-4 WW-R-K-4'-HO-3500K-277V-SC-C1OR PRE-APPROVED EQUAL
4FT RECESSED LINEAR WALL WASH4" TALL
XA WALL/CEILING LED 5 277 DUAL-LITE - SE SERIESSE-S-R-W-E-IOR PRE-APPROVED EQUAL
DIE-CAST LED EXIT SIGNSINGLE FACEINTEGRAL BATTERYSELF DIAGNOSTICS
EATON - SURE-LITESCX71WHSD
XB WALL/CEILING LED 5 277 DUAL-LITE - SE SERIESSE-D-R-W-E-IOR PRE-APPROVED EQUAL
DIE-CAST LED EXIT SIGNDOUBLE FACEINTEGRAL BATTERYSELF DIAGNOSTICS
EATON - SURE-LITESCX72WHSD
XC WALL/CEILING LED 652 lm 12 277 DUAL-LITE - EVHCEVHC-12-IOR PRE-APPROVED EQUAL
THERMOPLASTIC LED EMERGENCY LIGHTHIGH MOUNTING APPLICATIONSINTEGRAL BATTERYSELF DIAGNOSTICS
EATON - SURE-LITESSEL60R4SD
XD WALL/CEILING LED 290 lm 4 277 DUAL-LITE - EVHCEV-4-I-02LOR PRE-APPROVED EQUAL
THERMOPLASTIC LED EMERGENCY LIGHTARCHITECTURAL APPLICATIONSINTEGRAL BATTERYSELF DIAGNOSTICS
EATON - SURE-LITESSEL50SD
LIGHTING CONTROL DEVICE SCHEDULETYPE MOUNTING DESCRIPTION MANUFACTURER MODEL COVERAGE COLOR
LD WALL DIGITAL LIGHTING MANAGEMENT SYSTEM (DLM) SWITCHLOW VOLTAGE PUSHBUTTON SWITCH
WATTSTOPPER LMDM-101 - GREY OR ASNOTED BYARCHITECT.
MS-1 CEILING DUAL TECHNOLOGY ULTRASONIC AND PASSIVE INFRARED CEILING SENSOR.IT IS A DIGITAL SENSOR PART OF A DIGITAL LIGHTING MANAGEMENT SYSTEM(DLM) BY WATTSTOPPER.
WATTSTOPPER LMDC-100 1000 SQFT WHITE
MS-2 CEILING DIGITAL PASSIVE INFRARED SENSOR WITH 360 DEGREE PATTERNS.COMPONENT OF DIGITAL LIGHTING MANAGEMENT INTEGRATED CONTROLSYSTEM.
WATTSTOPPER LMPC-100 1000 SQFT WHITE
PS CEILING MULTI-ZONE DAYLIGHT PHOTOSENSOROPEN LOOP WITH CONTINUOUS DIMMINGCOMPONENT OF DIGITAL LIGHTING MANAGEMENT INTEGRATED CONTROLSYSTEM
WATTSTOPPER LMLS-500 - WHITE
RC-D ABOVE ACCESSIBLECEILING
PLENUM RATED CONTROLLER WITH LINE VOLTAGE RELAY(S) AND ON/OFF0-10V DIMMING POWER SUPPLY.COMPONENT OF DIGITAL LIGHTING MANAGEMENT INTEGRATED CONTROLSYSTEM.CONNECT TO COMPONENTS WITH CAT 5E CABLES WITH RJ45 CONNECTORS.PROVIDE WITH ISOLATED RELAY INTERFACE FOR HVAC CONTROL (PROVIDEONE PER ROOM)
(SEE NOTE BELOW)
WATTSTOPPER LMRC-211LMRC-212LMRC-213
LMRL-100
- -
RC-PL ABOVE ACCESSIBLECEILING
PLENUM RATED CONTROLLER WITH LINE VOLTAGE RELAY AND SWITCHINGPOWER SUPPLYCOMPONENT OF DIGITAL LIGHTING MANAGEMENT INTEGRATED CONTROLSYSTEMCOMPONENT OF DIGITAL LIGHTING MANAGEMENT INTEGRATED CONTROLSYSTEMDIGITAL PLUG LOAD ROOM CONTROLLERPLUG INTO COMPONENTS WITH CAT 5ECABLES WITH RJ45 CONNECTORS
WATTSTOPPER LMPL-101 - -
TS WALL TIMER SWITCHTIME-OUT ADJUSTMENTS FROM 5 MIN TO 12 HOURS.STAND ALONE, NOT PART OF DLM
- GREY OR ASNOTED BYARCHITECT.
NOTES:1. PRE-APPROVAL FOR EQUALS MUST BE SUBMITTED PRIOR TO BIDS PER THE FRONT END DOCUMENTATION. SUBSTITUTIONS WILL NOT BE ENTERTAINED POST BIDS.2. CONTRACTOR SHALL SUBMIT INDIVIDUAL PRICING. LOT PRICING WILL NOT BE ACCEPTED.3. CONTRACTOR SHALL COORDINATE ALL LUMINAIRES WITH THE CEILINGS THEY ARE TO BE MOUNTED IN. PROVIDE ALL MATERIAL AND EQUAL AS REQUIRED TO MOUNT IN THE CEILING TYPE WHERE SHOWN. REFER TO ARCHITECTURAL PLANS FOR CEILINGTYPES.4. LIGHT FIXTURE VOLTAGES SHALL MATCH THE CIRCUIT VOLTAGE AS SHOWN PER PLANS.
NOTES:1. PROVIDE REQUIRED NUMBER OF ROOM CONTROLLERS AND RELAYS TO ACCOUNT FOR THE PROPER SWITCHING CONFIGURATION OF LOADS. ONLY ONE SYMBOL IS SHOWN IN PLAN FOR CLARITY.2. CABLING USED TO INTER-CONNECT DLM SYSTEM DEVICES TO BE WHITE (OR PRE-APPROVED COLOR BY OWNER).3. PROGRAM ALL MOTION SENSORS TO BE OCCUPANCY SENSORS. THEY ARE TO TURN ON AUTOMATIC AND SHUT OFF WITHIN 30 MINUTES OF AN OCCUPANT LEAVING SPACE.4. WATTSTOPPER IS A BASIS OF DESIGN. CONTRACTOR SHALL SUBMIT ANY EQUALS PRIOR TO BID FOR PRE-APPROVAL PER FRONT END DOCUMENTS. SUBSTITUTIONS WILL NOT BE ENTERTAINED POSTBIDS.
# DATE DESCRIPTION
2 11/27/17 ADDENDUM 2
2