58
UNIVERSITY OF DELAWARE BROWN & DRAKE LABORATORIES HVAC SYSTEMS ASSESSMENT February 16, 2016

UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

UNIVERSITY OF DELAWAREBROWN & DRAKE LABORATORIES

HVAC SYSTEMS ASSESSMENTFebruary 16, 2016

Page 2: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

 

 

 

UNIVERSITY OF DELAWARE 

BROWN & DRAKE LABORATORIES 

HVAC SYSTEMS ASSESSMENT 

 

 

 

 

 

 

DRAFT SUBMISSION 

   

February 16, 2016 

 

 

Page 3: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 1

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THIS PAGE INTENTIONALY LEFT BLANK

Page 4: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 1

   

 

 

TABLE OF CONTENTS

I. EXECUTIVE SUMMARY. ................................................................................................................ 3

II. EXISTING HVAC SYSTEMS DESCRIPTION ................................................................................ 8

A. Brown .......................................................................................................................................... 8 a. Supply Air ....................................................................................................................... 8 b. Laboratory Exhaust Air .................................................................................................... 9 c. Chilled Water, Steam & Pumps ...................................................................................... 10 d. Fume Hoods.................................................................................................................... 10

B. Drake ........................................................................................................................................... 11 a. Supply Air ....................................................................................................................... 11 b. Laboratory Exhaust Air .................................................................................................... 12 c. Chilled Water, Steam & Pumps ...................................................................................... 13 d. Fume Hoods.................................................................................................................... 13

III. EXISTING HVAC SYSTEMS ASSESSMENT & RECOMMENDATIONS ................................... 14

A. Brown .......................................................................................................................................... 15 a. Supply Air ....................................................................................................................... 15 b. Laboratory Exhaust Air .................................................................................................... 16 c. Chilled Water, Steam & Pumps ...................................................................................... 16 d. Fume Hoods.................................................................................................................... 16

B. Drake ........................................................................................................................................... 18 e. Supply Air ....................................................................................................................... 18 f. Laboratory Exhaust Air .................................................................................................... 19 g. Chilled Water, Steam & Pumps ...................................................................................... 19 h. Fume Hoods.................................................................................................................... 19

IV COST ANALYSIS .............................................................................................................................. 21

V APPENDIX ........................................................................................................................................ 23

A. AHU Zone Diagrams ................................................................................................................... 23 B. Primary HVAC Equipment Inventory .......................................................................................... ? C. Supply and Exhaust Airflow Diagrams .......................................................................................... ? D. Existing Fume Hood Assessment .................................................................................................. ? E. Laboratory Space Airflow Assessment ........................................................................................... ? F. Pressurization Diagrams ................................................................................................................ ?

Page 5: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 2

 

 

 

 

 

 

THIS PAGE INTENTIONALY LEFT BLANK

Page 6: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 3

I. EXECUTIVE SUMMARY

Purpose

The purpose of this study is to provide a high level HVAC conditions assessment for both Brown and Drake Laboratories to provide a roadmap for the University of Delaware Facilities and Chemistry and Biochemistry Department to use to manage the use of these systems. The study makes recommendations for long term facilities upgrades and provides guidance on the limitations and use of the existing systems and infrastructure for future changes and renovations. Rough order of magnitude (ROM) costs have been provided where applicable for capital funding requests and facilities planning purposes for future renovations.

Modern chemistry laboratory facilities are always constantly challenged by the need to keep up with new and improved scientific equipment, with changes in teaching protocols and with the constant inflow of new research projects. This study is intended to provide a masterplan for the University to use to ensure both Brown and Drake Laboratories continue to support the teaching and research needs of the Chemistry and Biochemistry Departments for many years to come, despite these challenges.

Summary

The HVAC systems associated with Brown and Drake Hall are in generally good condition and have been provided with upgrades over the life of the buildings and over the life of the HVAC systems that are present. The primary steam and chilled water services (which come from the Campus Boiler House and Campus Chilled Water Plant) appear adequate for current and future loads. Expansion or upgrades to these primary services is not needed unless significant changes in programmatic requirements or internal loads is expected.

The primary air-side equipment is in good condition and laboratory upgrades or renovations can be performed pretty much anywhere within the two buildings, with guidance needed on how and specifically where they are most easily executed. The major air-side equipment is in good condition within the buildings with the exception of AHU-1 serving Drake and AHU-1 and AHU-2 in the Brown South Wing. These units are in need of replacement due to age or lack of adequate capacity, and it is recommended that a long term capital plan be put in place to replace them. A more detailed explanation of the general capacities and limitations of and recommendations for the air-side systems is provided by building and by area below as each are served by distinctly different equipment and systems.

Drake

With the upgrades to the laboratory supply and exhaust systems completed in 2013 within Drake, Drake is an ideal candidate for cost effective laboratory renovations in the future. This is because each laboratory can now be isolated at the supply and exhaust air valves within the laboratory without impacting other spaces to perform simple modifications.

The limitations within Drake, however, are its air handling units. The existing air handling unit (AHU-1) in the basement is old, although it has been upgraded, and it is running very near its maximum capacity. Because many of the spaces being served by AHU-1 are currently underutilized it still has extra capacity to handle some

Page 7: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 4

upgrades to probably one or two laboratories within Drake to a higher utilization (based on Building Automation System readouts of operating conditions); however, it does not have enough capacity to serve all the existing older laboratories being renovated and taken to maximum utilization. It is recommended long term to either replace AHU-1 in-place with a custom unit that has slightly more capacity, to add a new air handling unit(s) indoors or outdoors in the courtyard between Brown and Drake, or to move spaces off AHU-1 and to AHU-2 in order to use extra capacity available from AHU-2 and maximize capacity of AHU-1. The new air handling unit AHU-2 that was installed on the roof of Drake in 2013 to serve just Laboratories 112, 318 and 320 has approximately 11,000 CFM additional air that can be utilized to serve future laboratories that are now being served by AHU-1.

Regardless of the options that the University decides to move forward with we recommend at a minimum they should prioritize the third option, and primarily for spaces on the third floor still served by AHU-1. Removing these third floor laboratories from AHU-1 and adding them to AHU-2 is a low cost way to provide additional capacity for AHU-1 with really only the addition of ductwork on the roof down to connections to the existing supply air valves. Approximately 5,000 sf of standard chemistry teaching laboratories or standard chemistry research laboratories or one additional 1200 sf organic chemistry teaching laboratory could be added to AHU-2 on the third floor with the additional capacity that is available. The other options of adding or modifying air handling units that could be executed within Drake were studied in greater detail by Jacobs in the Drake Hall Lab Renovation Feasibility Study dated October 10, 2014. The long term solution, however, will most likely need to be a combination of these options.

One of the additional challenges within Drake is the exhaust ductwork risers. The supply air system has fewer larger ductwork risers that can take advantage of diversity and as such have additional capacity available, however, the exhaust system was designed with multiple smaller ductwork risers which limits the ability to expand and take advantage of diversity on the floors. This means that any major increase in airflow required at the individual laboratory spaces may require new ductwork being run up through the building to the roof exhaust fans.

For laboratories where the supply airflow is load driven and not fume hood makeup air driven, another option could be considered. That option is to use a hybrid system, utilizing the primary AHU system to provide initial cooling capacity to the laboratories and to provide makeup air for fume hoods, but not provide all the sensible cooling that is required. The additional sensible cooling in each lab could then be handled by local fan coil units, radiant cooling ceiling panels or other local sensible cooling equipment. Keeping the supply airflow at the EH&S minimum criteria of 10 air changes per hour provides approximately 1.7 CFM/sf and can be handled with the existing AHU equipment. As indicated in the analysis section of the report, a standard chemistry teaching laboratory or chemistry research laboratory would normally require 2.1-2.2 CFM/sf to satisfy the internal heat loads. The additional cooling required beyond the 1.7 CFM/sf supplied by the existing AHU could be handled with local hydronic cooling equipment directly off the chilled water system. This approach, however, will not work for the organic chemistry teaching laboratories because they are fume hood makeup air driven, and as such they need more air from the central AHU system.

Page 8: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 5

Brown South Wing

The Brown South Wing HVAC systems are probably as a whole the most in need of major upgrade. The air handling units and general laboratory exhaust fans, although they provide adequate capacity to the spaces being served, they are at the end of their useful life and in need of replacement. The general supply and exhaust air ductwork systems themselves are also still operating in a constant volume reheat mode, which is not energy efficient and does not allow for diversity in the system. This lack of diversity means you can’t fully take advantage of the full CFM capacity of the AHU capacity the way a full VAV (variable air volume) system does.

It is recommended that before any major laboratory renovations are undertaken in the Brown South Wing that a full HVAC system upgrade be performed, which would include replacing air handling units AHU-1 & AHU-2, replacing exhaust fans EF-1, 2 & 3, replacing pumps and heat exchangers in the penthouse and converting the ductwork distribution system to a VAV system by installing supply and exhaust air valves (similar to what was done in Drake). This would also solve an issue that the Building Automation System (BAS) shop has, which is that they can’t monitor the older Staefa control system through their main BAS control panel. When these upgrades are performed all new controls should be installed and integrated with the campus BAS system so the entire Brown Building could be monitored and controlled through the single BAS system.

One of the additional challenges with Brown South Wing is the ductwork risers, both supply and exhaust. The system was designed with multiple smaller ductwork risers which limits the ability to expand and take advantage of diversity on the floors. This will require that any upgrade or renovation provide a careful review of the ductwork capacities on the floor and within the area being renovated before moving forward with the design.

Brown North Wing

The area within Drake and Brown that has the greatest potential for simple and cost effective renovations or laboratory upgrades at an individual laboratory or floor level is the Brown North Wing. This area has new primary air handling units and central laboratory exhaust fans with additional capacity for future loads. The area is served by this equipment has been provided with large primary vertical supply and exhaust risers, which makes upgrades on the floors easier to accomplish when loads increase because they can take advantage of the diversity within the system. The existence of larger equipment loads in the areas within Brown served by these units helps provide this overall greater system diversity.

Brown West Wing

In general the HVAC systems within the Brown West Wing serve classrooms, auditorium and offices. Very few laboratory spaces exist within Brown West; however, those that do have been provided with upgraded laboratory supply/exhaust air valves and they are served by new air handling equipment in the penthouse of Brown West. The one unique aspect of the laboratories in Brown West is that all the laboratory exhaust from Brown West is routed through Brown North to be exhausted by the combined general exhaust fans on the roof of the courtyard infill between the Brown North Wing and Brown South Wing. There are some smaller dedicated laboratory exhaust systems within Brown West; however, they are smaller and aren’t expandable. The other challenge with the laboratory systems serving Brown West are that they were also designed with multiple smaller ductwork

Page 9: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 6

risers which limits their ability to expand and take advantage of diversity on the floors. This again will require that for any upgrade or renovation planned a careful review be performed of the ductwork capacities on the floor and within the area being renovated before moving forward with the design.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 10: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THIS PAGE INTENTIONALY LEFT BLANK

Page 11: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 8

II. EXISTING HVAC SYSTEMS Brown – Existing HVAC Systems

The original Brown building was constructed in 1938 as the Chemical Engineering Building. The South Wing addition was added as the Chemical Engineering Annex in approximately 1950. The North Wing addition was added in approximately 1960. The facility has continued to function as a teaching and research laboratory facility for Chemistry and Biochemistry and the older portion of Brown contains a major auditorium as well as administrative offices and general purpose classrooms. The North and South Wings contain primarily teaching and research laboratories. Major renovations happened throughout the three wings of the building thru the 1970’s and 1980’s. In the 1990s a major renovation was undertaken within the South Wing addition, and a recent laboratory exhaust system upgrade was implemented throughout the North and West Wings in the 2008 timeframe.

Supply Air

The supply air systems within Brown consist of a series of semi-custom double-wall and modular double-wall air handling units of various vintages. All units are generally in good condition, with the exception of the two older units serving the South Wing that are roughly 20-25 years old. These two air handling units are located in the penthouse of the South Wing and are probably the most in need of upgrade or planned replacement.

The air handling units serving the front portion of the existing building (West Wing) have all been installed in approximately 2008. Two units were installed in the West Wing penthouse (AHU-3, 4 & 5) and one was installed in a basement mechanical room (AHU-6). Two new units were installed at the same time to serve the North Wing and Infill area (AHU-1 & 2), and they are located outdoors on the roof of the infill between the North and South Wings. The units are all double-wall modular York Solution air handling units with steam preheat coils and chilled water cooling coils. Two of the units (AHU-3 and AHU-4) have been provided with steam humidifiers for winter humidification control. At the same time that the air handling units were replaced new ductwork and new VAV boxes were installed throughout the West North Wings.

The two air handling units (AHU-1-1 and AHU-2-1) that serve the South Wing are located in the penthouse of the South Wing and were installed with renovations in approximately 1995. These two units were installed along with three new central laboratory exhaust fans serving the South Wing and along with new chilled water pumps, heating hot water pumps and along with a laboratory exhaust heat recovery system. This laboratory exhaust energy recovery system is a glycol run-around loop system with coils in the exhaust air stream and in the OA stream within the air handling units, with all equipment located in the penthouse.

Reference the floor plans in Appendix A, AHU Zone Diagrams, for areas within Brown served by each AHU described above. These diagrams not only indicate the areas served by each air handling unit but also the square footage served by each AHU by floor.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the size of the primary air handling units with the estimate of how loaded the units currently are and what CFM they are currently

Page 12: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 9

operating at. This table also includes what the original design intent was for the % of OA that the units are designed for. This allows for an evaluation of whether the unit can accommodate serving up to 100% wet chemistry laboratories which require 100% exhaust of the laboratory air and 100% OA from the AHU.

Reference the diagrams in Appendix C, Supply and Exhaust Airflow Diagrams, for the general configuration of the primary air handling units and laboratory exhaust fans in Brown. The airflow diagrams also indicate the primary supply and exhaust ductwork risers that may be the limiting piece of infrastructure for future renovations or upgrades. These primary risers have been tagged with riser designations that are also indicated on the floor plans shown in Appendix A, AHU Zone Diagrams.

Reference the floor plans in Appendix F, Space Pressurization Diagrams, for the general space pressurization requirements by floor within Brown. The current transfer air quantities are shown for each laboratory at the door into the lab from the corridor or between laboratories. These diagrams show a basic design intent for guiding future changes and highlight where increases or decreases in transfer are recommended.

Laboratory Exhaust Air

The laboratory exhaust systems serving Brown include two primary combined laboratory exhaust systems. A combined laboratory exhaust system means that general laboratory exhaust air and fume hood exhaust air are combined in the same ductwork system and exhausted with the same exhaust fans. This system approach requires that no fume hood be connected to the combined exhaust system that exhausts any vapor, gas, fume, mist or dust of a type, rating or quantity that meets the definition of hazardous exhaust as defined by the mechanical code. Hazardous exhaust is required to be exhausted in an independent system with dedicated exhaust fans meeting the code requirements for hazardous exhaust systems. Dedicated exhaust systems would also be required where exhausting perchloric acids, radioisotopes or where exhausting biosafety cabinets requiring dedicated exhaust fans for isolation.

One combined exhaust system in Brown includes the three combined general laboratory exhaust fans located in the South Wing penthouse serving specifically the South Wing laboratories. These three general laboratory exhaust fans that discharge through exhaust ductwork stacks that extend up through brick chimney enclosures were installed in approximately 1995. These fans are in good condition and they have also been provided with energy recovery coils located in the ductwork upstream of the fans.

The second combined exhaust system in Brown includes three combined general laboratory exhaust fans located on the roof of the Infill area between the North Wing and South Wing. This combined laboratory exhaust system exhausts the North Wing laboratories and a select few laboratories in the West Wing. These fans were installed in approximately 2008 and are in excellent condition. This system, however, has not been provided with coils upstream in the ductwork for energy recovery.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the size of the general combined laboratory exhaust fans with the estimate of how loaded the fans currently are and what CFM they are currently operating at.

Page 13: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 10

Reference the diagrams in Appendix C, Supply and Exhaust Airflow Diagrams, for the general configuration of the primary air handling units and laboratory exhaust fans in Brown. The airflow diagrams also indicate the primary supply and exhaust ductwork risers that may be the limiting piece of infrastructure for future renovations or upgrades. These primary risers have been tagged with riser designations that are also indicated on the floor plans shown in Appendix A, AHU Zone Diagrams.

Chilled Water, Steam & Pumps

The Brown original West Wing, North Wing and the equipment in the Infill are all served by an existing 6” high pressure steam main (125 psig) that enters the Brown Building on the south side at the basement level. This high pressure steam line from the Campus Boiler House feeds a pressure reducing station serving these areas and is also cross connected to the existing south wing steam pressure reducing station. Both the new pressure reducing station serving the North and West Wings and the older pressure reducing station serving the South Wing are located in the basement mechanical room within the South Wing.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the capacities of the chilled water pumps and heating water pumps in Brown.

Fume Hoods

Brown laboratory includes sixty-nine (69) bench fume hoods, two (2) walk-in fume hoods, seven (7) canopy hoods and thirty-one (31) snorkel exhausts. These laboratory exhaust hoods are all generally in good condition and those that are operational are functioning safely and within environmental health and safety standards. The inventory of all fume hood types within Brown (bench hoods, walk-in hoods, canopy hoods and snorkel hoods) is included in Appendix D, Existing Fume Hood Assessment, along with a general conditions assessment and recommendations for upgrade or replacement. Where hoods are recommended for replacement ROM costs have been provided in the COST ANALYSIS portion of the report for future planning purposes.

Page 14: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 11

Drake – Existing HVAC Systems

The original Drake Laboratory Building was designed in 1971 as a classroom laboratory building. The building has been renovated over the years and contains a combination of teaching and research laboratories for use by the Departments of Chemistry and Biochemistry. The building is served by central chilled water and steam from the campus central steam & chilled water plant very near the building.

Supply Air

The original Drake building HVAC supply air system consisted of a field assembled custom air-handling unit (AHU-1) located in the basement. Outside air is drawn in through an areaway located (at grade) in the courtyard formed between Drake Laboratory Building and the three wings of Brown Laboratory. Also in the courtyard are air intakes for the previously renovated Brown south wing. These intakes are at the third floor of the south wing as opposed to at grade. This original AHU is 100% OA and has a single fan, filters, a steam preheat coil, a chilled water cooling coil and a steam humidifier. The unit was refurbished in approximately 2013, with the unit being rebuilt almost entirely, with the supply fan being refurbished, a new variable frequency drive (VFD) installed for capacity control, new controls installed, a new chilled water coil installed and a new humidifier installed. The unit, however, was never installed with a laboratory exhaust heat recovery system.

A second air handling unit (AHU-2) was installed in approximately 2013 to serve just the Organic Chemistry Laboratories 112, 318 and 320. This unit is a semi-custom double-wall 100% OA unit and is located on the roof. The unit has been provided with a steam preheat coil with face-and-bypass capacity control, a steam injection humidifier, a chilled water cooling coil and a single centrifugal fan with VFD for capacity control. This unit provides the increased makeup air needed for the high density of fume hoods required in these laboratories.

Supply air ductwork from AHU-1 includes the original medium pressure round sheet metal ductwork from the basement to two 40” diameter duct risers up through the building to supply the second and third floor laboratories. Airflow control is provided by laboratory supply air control valves installed with the Laboratory Renovation project in approximately 2013.

New rectangular medium pressure supply ductwork from AHU-1 was installed in 2013 from the roof to Organic Chemistry Laboratories 112, 318 and 320. New airflow control valves were installed at that time to provide capacity control associated with the laboratory fume hood and space pressurization system design.

Reference the floor plans in Appendix A, AHU Zone Diagrams, for areas within Drake served by each AHU described above. These diagrams not only indicate the areas served by each air handling unit but also the square footage served by each AHU by floor.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the size of the primary air handling units with the estimate of how loaded the units currently are and what CFM they are currently operating at. This table also includes what the original design intent was for the % of OA that the units are

Page 15: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 12

designed for. This allows for an evaluation of whether the unit can accommodate serving up to 100% wet chemistry laboratories which require 100% exhaust of the laboratory air and 100% OA from the AHU.

Reference the diagrams in Appendix C, Supply and Exhaust Airflow Diagrams, for the general configuration of the primary air handling units and laboratory exhaust fans in Drake. The airflow diagrams also indicate the primary supply and exhaust ductwork risers that may be the limiting piece of infrastructure for future renovations or upgrades. These primary risers have been tagged with riser designations that are also indicated on the floor plans shown in Appendix A, AHU Zone Diagrams.

Reference the floor plans in Appendix F, Space Pressurization Diagrams, for the general space pressurization requirements by floor within Drake. The current transfer air quantities are shown for each laboratory at the door into the lab from the corridor or between laboratories. These diagrams show a basic design intent for guiding future changes and highlight where increases or decreases in transfer are recommended.

Laboratory Exhaust Air

The laboratory exhaust system serving Drake includes a single combined laboratory exhaust system. A combined laboratory exhaust system means that general laboratory exhaust air and fume hood exhaust air are combined in the same ductwork system and exhausted with the same exhaust fans. This system approach requires that no fume hood be connected to the combined exhaust system that exhausts any vapor, gas, fume, mist or dust of a type, rating or quantity that meets the definition of hazardous exhaust as defined by the mechanical code. Hazardous exhaust is required to be exhausted in an independent system with dedicated exhaust fans meeting the code requirements for hazardous exhaust systems. Dedicated exhaust systems would also be required where exhausting perchloric acids, radioisotopes or where exhausting biosafety cabinets requiring dedicated exhaust fans for isolation.

The buildings laboratory exhaust system was modified in 2013 to create a new central combined laboratory exhaust system, with three central 35,000 CFM centrifugal exhaust fans installed on the roof of Drake Laboratory to exhaust all general exhaust and fume hood exhaust in the building. These new exhaust fans are single-width, single-inlet, centrifugal exhaust fans with airfoil fan blades. The exhaust fans have been provided with VFD’s for fan speed control and have discharge sound attenuators for acoustical noise control.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the size of the general combined laboratory exhaust fans with the estimate of how loaded the fans currently are and what CFM they are currently operating at.

Reference the diagrams in Appendix C, Supply and Exhaust Airflow Diagrams, for the general configuration of the primary air handling units and laboratory exhaust fans in Brown. The airflow diagrams also indicate the primary supply and exhaust ductwork risers that may be the limiting piece of infrastructure for future renovations or upgrades. These primary risers have been tagged with riser designations that are also indicated on the floor plans shown in Appendix A, AHU Zone Diagrams.

Page 16: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 13

Chilled Water, Steam & Pumps

Drake is served by an existing 6” high pressure steam main (125 psig) that enters the Drake Building on the southwest side at the basement level. This high pressure steam line from the Campus Boiler House feeds a pressure reducing station serving these areas and also is cross connected to the existing south wing steam pressure reducing station. Both the new pressure reducing station serving the North and West Wings and the older pressure reducing station serving the South Wing are located in the basement of the South Wing. Chilled Water (8” CHWS/CHWR) enters the Drake building along the west side of Drake at the basement level. The chilled water pumps and hot water pumps serving Drake are all located in the basement mechanical room.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the capacities of the chilled water pumps and heating water pumps in Drake.

Fume Hoods

Drake laboratory includes seventy-three (73) bench fume hoods, one (1) walk-in fume hood and one hundred and fourteen (114) snorkel exhausts. These laboratory exhaust hoods are all generally in good condition and those that are operational are functioning safely and within environmental health and safety standards. Many are currently inactive and those that have not been utilized in over a year should be more fully evaluated for workability and replaced if necessary. The inventory of all fume hood types within Drake (bench hoods, walk-in hoods and snorkel hoods) is included in Appendix D, Existing Fume Hood Assessment, along with a general conditions assessment and recommendations for upgrade or replacement. Where hoods are recommended for replacement ROM costs have been provided in the COST ANALYSIS portion of the report for future planning purposes.

Page 17: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 14

   

III. EXISTING HVAC SYSTEMS ASSESSMENT & RECOMMENDATIONS  

Assessment of Existing HVAC Systems

In order to assess the limitations of the primary laboratory HVAC equipment, rough calculations have been performed to better understand the general requirements for any current or future laboratory space within the two buildings. The three primary laboratory types that we performed calculations for and would expect to see in the buildings include the following:

Organic Chemistry Teaching Laboratory: Twelve hundred (1200) square feet, twenty four (24) students, 10 watts/square foot laboratory equipment load, six (6) 8-foot teaching fume hoods, two (2) 6-foot bench fume hoods.

General Chemistry Teaching laboratory: Twelve hundred (1200) square feet, twenty four (24) students, 10 watts/square foot laboratory equipment load, two (2) 6-foot bench fume hoods.

General Chemistry Research Laboratory: Six hundred (600) square feet, four (4) researchers, 10 watts/square foot laboratory equipment load, two (2) 6-foot bench fume hoods.

Utilizing the above criteria, the following will be utilized to evaluate the existing air systems capability and space airflows to serve future laboratory upgrades or renovations. The following airflows are a maximum airflow that we would expect to be required at the laboratory space level:

Organic Chemistry Teaching Laboratory: 9.9 CFM/SF

General Chemistry Teaching laboratory: 2.6 CFM/SF

General Chemistry Research Laboratory: 2.8 CFM/SF

Utilizing a standard diversity factor of 80%, the following airflows are a maximum airflow that we would expect to be required at the laboratory AHU or General Lab Exhaust Fans for the same three typical space types:

Organic Chemistry Teaching Laboratory: 7.9 CFM/SF

General Chemistry Teaching laboratory: 2.1 CFM/SF

General Chemistry Research Laboratory: 2.2 CFM/SF

Page 18: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 15

Brown

Supply Air

Utilizing the criteria listed above for future long term capacity requirements, the following is an assessment of the capacity of the existing air handling units serving Brown. Utilizing this assessment recommendations have been provided for each air handling unit, indicating which should remain and be reused as currently operating and which should be replaced in their entirety because they either do not provide the capacity required or because their condition is not adequate as indicated in the Appendix B, Primary HVAC Equipment Inventory.

Air Handling Unit Assessment

AHU SF Served Actual CFM

Max. CFM

Max.CFM/SF

Recommended CFM/SF

Reuse/Replace

AHU-1-1 9,458 21,875 21,875 2.3 2.2 Replace

AHU-2-1 9,458 21,875 21,875 2.3 2.2 Replace

AHU-1 16,278 40,000 40,000 2.5 2.2 Reuse

AHU-2 16,278 40,000 40,000 2.5 2.2 Reuse

AHU-3 18,142 26,000 27,000 1.5 1.4 (*) Reuse

AHU-4 18,117 25,000 26,000 1.4 1.4 (*) Reuse

AHU-5 2,284 8,200 8,200 3.6 - Reuse

AHU-6 4,128 7,000 7,000 1.7 - Reuse

(*) – Assumes 75% of spaces on this AHU unit in the future are classrooms or offices requiring only 1 CFM/SF and 25% of spaces on this AHU unit would be laboratories requiring 2.2 CFM/SF

An aspect of the air systems that can be a significant limiting factor for future renovation projects is the capacity of the ductwork airflow risers. These vertical risers are typically expensive to upgrade in order to perform small renovations on a floor. The general intent therefore, in order to keep individual renovation costs down, is to have the horizontal ductwork on the floor associated with the proposed renovation be all that is required to be modified. In order to better understand the limitations of the existing vertical supply risers currently in the building we have performed an assessment of each of the Major Ductwork Risers in the building, for future planning purposes. We have not looked at the numerous smaller vertical risers in the building as they are typically limited to serving the existing spaces in their current capacities. The following is our assessment of these major vertical risers:

Page 19: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 16

Major Ductwork Riser Assessment

Riser Service Size

(Inches) Floors Served

CurrentCFM

Maximum CFM (*)

Available CFM

DN-SA-1 Supply 48x48 GR, 1, 2, 3 45,996 40,000 0

DN-EA-1 Exhaust 48x48 GR, 1, 2, 3 42,510 40,000 0

DN-EA-2 Exhaust 48x48 GR, 1, 2, 3 18,340 40,000 21,660

DS-RA -1 Return 28x28 GR, 1, 2, 3 8,850 10,900 2,050

(*) - The estimates of maximum airflow CFM for the duct risers is an estimate based on utilizing a maximum duct velocity for acoustical criteria of 2500 fpm for medium pressure ductwork (supply & exhaust) and 2000 fpm for low pressure ductwork (return).

Laboratory Exhaust Air

The combined general laboratory exhaust fans serving the Brown South Wing appear to have adequate capacity for current and future loads; however, the units are getting near the end of their useful life and should be replaced soon. The combined general laboratory exhaust fans serving the Brown North Wind and Brown West Wing laboratories appear to have adequate capacity for current and future loads. Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the size of the general combined laboratory exhaust fans with the estimate of how loaded the fans currently are.

Chilled Water, Steam & Pumps

The primary steam and chilled water services (which come from the Campus Boiler House and Campus Chilled Water Plant) appear adequate for current and future loads. The chilled water and heating hot water pumps as well appear in good condition and adequate for current and immediate future loads.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the capacities of the chilled water pumps and heating water pumps in Brown.

Fume Hoods

All laboratory exhaust hoods in Brown are in generally in good condition, and those that are operational are functioning safely and within environmental health and safety standards. The inventory of all fume hood types within Brown (bench hoods, walk-in hoods and snorkel hoods) is included in Appendix D, Existing Fume Hood Assessment, along with a general conditions assessment and recommendations for upgrade or replacement.

Page 20: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 17

Where hoods are recommended for replacement ROM costs have been provided in the COST ANALYSIS portion of the report for future planning purpose

Page 21: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 18

   

Drake

Supply Air

Utilizing the criteria listed above for future long term capacity requirements, the following is an assessment of the capacity of the existing air handling units serving Drake. Utilizing this assessment recommendations have been provided for each air handling unit, indicating which should remain and be reused as currently operating and which should be replaced in their entirety because they either do not provide the capacity required or because their condition is not adequate as indicated in the Appendix B, Primary HVAC Equipment Inventory.

Air Handling Unit Assessment

AHU SF Served Actual CFM

Max. CFM

Max.CFM/SF

Recommended CFM/SF

Reuse/Replace

AHU-1 34,271 54,000 54,000 1.57 2.2 Replace

AHU-2 3,775 29,000 40,000 10.59 7.9 (*) Reuse

(*) – Subtracting the 29,000 CFM currently supplied to Organic Chemistry Labs 112, 318 & 320 leaves enough airflow to serve an additional 5,500 SF at a supply airflow density of 2.0 CFM/SF.

An aspect of the air systems that can be a significant limiting factor for future renovation projects is the capacity of the ductwork airflow risers. These vertical risers are typically expensive to upgrade in order to perform small renovations on a floor. The general intent therefore, in order to keep individual renovation costs down, is to have the horizontal ductwork on the floor associated with the proposed renovation be all that is required to be modified. In order to better understand the limitations of the existing vertical supply risers currently in the building we have performed an assessment of each of the Major Ductwork Risers in the building, for future planning purposes. We have not looked at the numerous smaller vertical risers in the building as they are typically limited to serving the existing spaces in their current capacities. The following is our assessment of these major vertical risers:

Page 22: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 19

Major Ductwork Riser Assessment

Riser Service Size

(Inches) Floors Served

CurrentCFM

Maximum CFM (*)

Available CFM

DN-SA-1 Supply 40” dia. GR, 1, 2, 3 26,960 21,800 0

DN-SA-2 Supply 40” dia. GR, 1, 2, 3 19,895 21,800 1,905

DN-SA-3 Supply 40x14 1 6,510 9,700 3,190

DS-SA -4 Supply 40x14 1 6,510 9,700 3,190

(*) - The estimates of maximum airflow CFM for the duct risers is an estimate based on utilizing a maximum duct velocity for acoustical criteria of 2500 fpm for medium pressure ductwork (supply & exhaust) and 2000 fpm for low pressure ductwork (return).

Laboratory Exhaust Air

The combined general laboratory exhaust fans serving the Drake appear to have adequate capacity for current and future loads. If additional organic chemistry teaching laboratories are added to Drake, however, an additional exhaust fan would need to be added to the system as indicated in the Drake Hall Lab Renovation Feasibility Study performed by Jacobs dated October 10, 2014. Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the size of the general combined laboratory exhaust fans with the estimate of how loaded the fans currently are.

Chilled Water, Steam & Pumps

The primary steam and chilled water services (which come from the Campus Boiler House and Campus Chilled Water Plant) appear adequate for current and future loads. The chilled water and heating hot water pumps as well appear in good condition and adequate for current and immediate future loads.

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the capacities of the chilled water pumps and heating water pumps in Drake.

Fume Hoods

All laboratory exhaust hoods in Drake are in generally in good condition, and those that are operational are functioning safely and within environmental health and safety standards. Many are currently inactive and those that have not been utilized in over a year should be more fully evaluated for workability and replaced if necessary. The inventory of all fume hood types within Drake (bench hoods, walk-in hoods and snorkel hoods) is included in Appendix D, Existing Fume Hood Assessment, along with a general conditions assessment and recommendations for upgrade or replacement. Where hoods are recommended for replacement ROM costs have been provided in the COST ANALYSIS portion of the report for future planning purposes.

Page 23: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 26546.000    Page 20

 

 

 

 

 

 

 

THIS PAGE INTENTIONALY LEFT BLANK

Page 24: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 21

IV. COST ANALYSIS  

Supply Air

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the rough order-of-magnitude (ROM) replacement costs for the primary air handling units recommended to be replaced within the next 10 year capital funding period.

Exhaust Air

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the rough order-of-magnitude (ROM) replacement costs for the primary combined general laboratory exhaust fans recommended to be replaced within the next 10 year capital funding period.

Chilled Water, Steam & Pumps

Reference the table in Appendix B, Primary HVAC Equipment Inventory, for the rough order-of-magnitude (ROM) replacement costs for the primary chilled water and heating hot water pumps recommended to be replaced within the next 10 year capital funding period.

Fume Hoods

The fume hood assessment determined that none of the existing fume hoods needed to be replaced immediately. It is recommended that those fume hoods shown with a “fair” or “poor” condition assessment be replaced during any future renovation of the specific laboratory they reside in. This would be done in order to change the type, size or configuration of fume hoods in the laboratory to fit a new program requirement. In order to help plan for these future changes in fume hoods, rough order-of-magnitude (ROM) costs have been provided on the next page for various fume sizes and types.

Page 25: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 22

Fume Hoods Replacement Costs

Rough order-of-magnitude (ROM) costs for 4’ Bench Fume Hood:

Demo Existing Fume Hood & Associated Base Cabinet $750 (**) Disconnect Utilities (power, water, drain, gas) $500 Install New Fume Hood & Associated Base Cabinet $9,500 Connect Utilities (power, water, drain, gas) $500 Demo and Install new Air Valves $1,000 Rebalance & Adjust Controls $750 Total Cost (4’ Fume Hood and Base Cabinet) $13,000

Rough order-of-magnitude (ROM) costs for 6’ Bench Fume Hood:

Demo Existing Fume Hood & Associated Base Cabinet $750 (**) Disconnect Utilities (power, water, drain, gas) $500 Install New Fume Hood & Associated Base Cabinet $11,000 Connect Utilities (power, water, drain, gas) $500 Demo and Install new Air Valves $1,500 Rebalance & Adjust Controls $750 Total Cost (6’ Fume Hood and Base Cabinet) $15,000

Rough order-of-magnitude (ROM) costs for 8’’ Bench Fume Hood:

Demo Existing Fume Hood & Associated Base Cabinet $750 (**) Disconnect Utilities (power, water, drain, gas) $500 Install New Fume Hood & Associated Base Cabinet $12,500 Connect Utilities (power, water, drain, gas) $500 Demo and Install new Air Valves $2,000 Rebalance & Adjust Controls $750 Total Cost (8’ Fume Hood and Base Cabinet) $17,000

Rough order-of-magnitude (ROM) costs for 6’’ Walk-in Fume Hood:

Demo Existing Fume Hood & Associated Base Cabinet $750 (**) Disconnect Utilities (power, water, drain, gas) $500 Install New Fume Hood & Associated Base Cabinet $18,500 Connect Utilities (power, water, drain, gas) $500 Demo and Install new Air Valves $2,500 Rebalance & Adjust Controls $750 Total Cost (6’ Walk-in Hood and Base Cabinet) $23,500

(**) – Demolition does not include any hazardous abatement costs

Page 26: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 23

V. APPENDIX

A. AHU ZONE DIAGRAMS

Page 27: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page
Page 28: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page
Page 29: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page
Page 30: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page
Page 31: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page
Page 32: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 24

B. PRIMARY HVAC EQUIPMENT INVENTORY

Page 33: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

UNIVERSITY OF DELAWARE

BROWN/DRAKE LABORATORY HVAC ASSESSMENTMAIN HVAC EQUIPMENT INVENTORY

# Building Equipment Capacity / Size Operating / Size % OA Install DateExpected Useful 

Life

Replace 

Date

Life 

Remaining

Replace Cost 

($)

1 Drake AHU‐1 (Labs) 54,000 CFM 54,000 CFM 1001971 (2008 

Upgraded)25 2026 10 (*) $225,000

2 Drake AHU‐2 (Labs) 40,000 CFM 29,000 CFM 100 2013 25 2038 22

3 Drake EF‐1 45,000 CFM 42,000 CFM ‐ 2013 25 2038 22

4 Drake EF‐2 45,000 CFM 0 CFM ‐ 2013 25 2038 22

5 Drake EF‐3 45,000 CFM 40,000 CFM ‐ 2013 25 2038 22

6 Drake HWP‐1 170 GPM 170 GPM ‐ 2013 20 2033 17

7 Drake HWP‐2 170 GPM 0 GPM ‐ 2013 20 2033 17

8 Drake CHWP‐3 500 GPM 500 GPM ‐ 2013 20 2033 17

9 Drake CHWP‐4 500 GPM 0 GPM ‐ 2013 20 2033 17

10 Brown AHU‐1‐1, South (Labs) 21,875 CFM 21,875 CFM 100 1995 25 2021 5 $140,000

11 Brown AHU‐2‐1, South (Labs) 21,875 CFM 21,875 CFM 100 1995 25 2021 5 $140,000

12 Brown EF‐1, South 16,725 CFM 16,725 CFM ‐ 1995 25 2021 5 $25,000

13 Brown EF‐2, South 16,725 CFM 16,725 CFM ‐ 1995 25 2021 5 $25,000

14 Brown EF‐3, South 16,725 CFM 0 CFM ‐ 1995 25 2021 5 $25,000

15 Brown P‐CH‐1, South 500 GPM 500 GPM ‐ 1995 20 2017 0 $15,000

16 Brown P‐CH‐2, South 500 GPM 500 GPM ‐ 1995 20 2017 0 $15,000

17 Brown P‐H‐1, South 160 GPM 160 GPM ‐ 1995 20 2017 0 $10,000

18 Brown P‐H‐2, South 160 GPM 160 GPM ‐ 1995 20 2017 0 $10,000

19 Brown AHU‐1, Infill (Labs) 40000 CFM 40000 CFM 70 2008 25 2033 17

20 Brown AHU‐2, Infill (Labs) 40000 CFM 40000 CFM 85 2008 25 2033 17

21 Brown AHU‐3, West (Labs/Office) 27,000 CFM 27,000 CFM 55 2008 25 2033 17

22 Brown AHU‐4, West (Classrooms) 26,000 CFM 26,000 CFM 65 2008 25 2033 17

23 Brown AHU‐5, West (Auditorium) 6,000 CFM 6,000 CFM 100 2008 25 2033 17

24 Brown AHU‐6, West (Mech Rm) 7,000 CFM 7,000 CFM 100 2008 25 2033 17

25 Brown EF‐1, Infill 30,000 CFM 30,000 CFM ‐ 2008 25 2033 17

26 Brown EF‐2, Infill 30,000 CFM 30,000 CFM ‐ 2008 25 2033 17

27 Brown EF‐3, Infill 30,000 CFM 0 CFM ‐ 2008 25 2033 17

28 Brown P‐1 (chilled wtr), West 2200 GPM 2200 GPM ‐ 2008 20 2028 12

29 Brown P‐2 (chilled wtr), West 2200 GPM 2200 GPM ‐ 2008 20 2028 12

30 Brown P‐3 (hot water), West 450 GPM 450 GPM ‐ 2008 20 2028 12

(*) ‐ AHU‐1 has been upgraded with new coils, new fan and VFD, new humidifier and new controls.

1 OF 1

Page 34: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 25

C. SUPPLY AND EXHAUST AIRFLOW DIAGRAMS

Page 35: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page
Page 36: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page
Page 37: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 26

D. EXISTING FUME HOOD ASSESSMENT

Page 38: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (in) (fpm) (cfm)

Brown Lab 004 001 4 18 124 589 Good Low

002 sn 2472 0 Good Low

005 001 sn 369 0 Fair High

002 sn 555 0 Fair High

003 sn 1185 0 Fair Low

010 001 sn 670 0 Good Medium

002 sn 1654 0 Good Medium

011 001 canopy 0 Good Low

002 canopy 0 Good Low

003 canopy 1016 0 Good Medium

012 001 6 18 119 922 Good Medium

002 4 18 119 565 Good Low

003 6 18 105 814 Good Medium

004 6 18 113 876 Good  Medium

005 6 111 0 Good Low

006 sn 981 0 Good Low

007 sn 193 0 Good Medium

013 001 4 18 116 551 Good Low

002 6 18 108 837 Good Medium

003 6 18 106 822 Good Low

004 6 18 124 961 Good Medium

005 6 109 0 Good Low

006 sn 561 0 Good Medium

007 sn 612 0 Good Medium

030 001 sn * Good Medium

031 001 canopy 347 0 Good  Medium

002 canopy 706 Good Medium

043 001 6 18 123 953 Good Low

044 001 6 18 117 907 Good Low

071 001 sn * Good Low

074 001 6 16 118 813 Fair Low

Existing Fume Hood Assessment

Building Room Hood Number Condition Utilization

Width Test Measurements Flow

Page 1 of 4

Page 39: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (in) (fpm) (cfm)

Existing Fume Hood Assessment

Building Room Hood Number Condition Utilization

Width Test Measurements Flow

101A 001 4 18 121 575 Good Low

138 001 4 18 110 523 Good Low

002 sn 710 0 Good  Low

003 sn 711 0 Good Low

139 001 4 20 121 639 Good Low

002 4 18 165 784 Good Low

003 4 18 116 551 Good Low

004 4 18 113 537 Good Low

005 sn 681 0 Good Low

006 sn 678 0 Good Low

007 sn 878 0 Good Low

008 sn 684 0 Good Low

140 001 4 17 715 3208 Good Medium

002 4 18 111 527 Good Low

003 4 18 125 594 Good Medium

004 4 16 270 1140 Good Medium

005 sn 534 0 Good Low

006 sn 452 0 Good Low

007 sn 817 0 Good Low

008 sn 683 0 Good Low

162 001 6 18 176 1364 Good Low

163 001 6 18 115 891 Good Low

164 001 6 18 109 845 Good Low

Bio Safety * Good Low

165 001 6 18 113 876 Fair Low

166 001 6 18 103 798 Good Low

002 6 18 108 837 Good Low

240A 001 4 18 115 546 Good Low

002 sn 205 0 Good Low

240B 001 4 18 121 575 Good Low

002 sn 847 0 Good Low

Page 2 of 4

Page 40: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (in) (fpm) (cfm)

Existing Fume Hood Assessment

Building Room Hood Number Condition Utilization

Width Test Measurements Flow

241 001 sn 721 0 Good Low

002 sn 675 0 Good Low

003 sn 717 0 Good Low

004 sn 752 0 Good Low

005 canopy slot 721 0 Good Low

242 001 sn 779 0 Good Low

002 sn 708 0 Good Low

003 6 20 114 982 Good Low

004 6 20 113 973 Good Low

262 001 8 18 110 1183 Fair Medium

002 8 18 117 1258 Fair Medium

003 8 18 108 1161 Fair Medium

263 001 8 18 110 1183 Fair Medium

002 8 18 117 1258 Fair Medium

003 8 18 111 1193 Fair Medium

264 001 8 18 110 1183 Good Medium

002 8 18 120 1290 Good Medium

003 8 18 140 1505 Good Medium

004 canopy * 0 Good Medium

265 001 8 18 121 1301 Good Medium

002 8 18 116 1247 Fair Medium

003 8 18 120 1290 Fair Medium

266 001 8 18 116 1247 Good Medium

002 8 18 115 1236 Fair Medium

003 8 18 109 1172 Good Medium

269 001 8 18 106 1140 Fair Medium

002 8 18 111 1193 Fair Medium

270 001 8 18 107 1150 Good Medium

002 8 18 112 1204 Good Medium

336 001 sn 313 0 Good  Low

337 001 6 18 123 953 Good  Medium

Page 3 of 4

Page 41: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (in) (fpm) (cfm)

Existing Fume Hood Assessment

Building Room Hood Number Condition Utilization

Width Test Measurements Flow

002 6 18 120 930 Good  Medium

003 6 17 112 820 Good  Medium

004 6 18 116 899 Good  Medium

338 001 6 18 114 884 Good Medium

002 6 18 123 953 Good Medium

003 6 18 121 938 Good Medium

004 6 17 108 791 Good Medium

005 6 18 121 938 Good Medium

006 6 17 119 871 Good Low

339 001 6 17 111 812 Good Medium

002 6 18 116 899 Good Medium

003 6 18 111 860 Good Medium

004 6 17 114 834 Good Medium

005 6 18 120 930 Good Medium

006 6 18 121 938 Good Medium

007 6 18 119 922 Good Medium

008 6 18 116 899 Good Medium

* No certified data available 

Excellent/Good Condition ‐ Reuse 

existing hood in its current 

configuration

Fair Condition ‐ Requires repair or 

upgrade over time to continue use

Poor Condition ‐ Replace with future 

upgrade or renovation

Key for Recommendations:

Page 4 of 4

Page 42: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (ft) (fpm) (cfm)

Drake 006 001 4 18 103 489 Poor High

002 4 18 113 537 Poor High

003 sn * Poor Not Used

004 sn * Poor Not Used

005 sn * Poor Not Used

006 sn * Poor Not Used

007 sn * Poor Not Used

008 sn * Poor Not Used

009 sn * Poor Not Used

010 sn * Poor Not Used

011 sn * Poor Not Used

012 sn * Poor Not Used

013 sn * Poor Not Used

014 sn * Poor Not Used

015 sn * Poor Not Used

016 sn * Poor Not Used

017 sn * Poor Not Used

022 001 4 18 121 575 Poor High

002 4 18 107 508 Poor High

003 sn * Poor Not Used

004 sn * Poor Not Used

005 sn * Poor Not Used

006 sn * Poor Not Used

007 sn * Poor Not Used

008 sn * Poor Not Used

009 sn * Poor Not Used

010 sn * Poor Not Used

011 sn * Poor Not Used

012 sn * Poor Not Used

013 sn * Poor Not Used

014 sn * Poor Not Used

015 sn * Poor Not Used

Existing Fume Hood Assessment

UtilizationHood NumberRoomBuilding

Width Test Measurements Flow

Condition

Page 1 of 6

Page 43: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (ft) (fpm) (cfm)

Existing Fume Hood Assessment

UtilizationHood NumberRoomBuilding

Width Test Measurements Flow

Condition

016 sn * Poor Not Used

017 sn * Poor Not Used

054 001 4 18 117 556 Poor High

002 4 18 124 589 Poor High

003 sn * Poor Not Used

004 sn * Poor Not Used

005 sn * Poor Not Used

006 sn * Poor Not Used

007 sn * Poor Not Used

008 sn * Poor Not Used

009 sn * Poor Not Used

010 sn * Poor Not Used

011 sn * Poor Not Used

012 sn * Poor Not Used

013 sn * Poor Not Used

014 sn * Poor Not Used

015 sn * Poor Not Used

016 sn * Poor Not Used

017 sn * Poor Not Used

018 sn * Poor Not Used

019 sn * Poor Not Used

020 sn * Poor Not Used

058 001 4 17 106 476 Poor Low

002 sn * 100 Poor Not Used

061 001 3 17 119 365 Poor Low

063 001 4 17 120 538 Poor High

002 sn * Poor Not Used

003 sn * Poor Not Used

004 sn * Poor Not Used

005 sn * Poor Not Used

006 sn * Poor Not Used

007 sn * Poor Not Used

Page 2 of 6

Page 44: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (ft) (fpm) (cfm)

Existing Fume Hood Assessment

UtilizationHood NumberRoomBuilding

Width Test Measurements Flow

Condition

008 sn * Poor Not Used

009 sn * Poor Not Used

010 sn * Poor Not Used

064 001 4 17 117 525 Poor High

002 4 17 104 467 Poor High

003 sn * Poor Not Used

004 sn * Poor Not Used

005 sn * Poor Not Used

006 sn * Poor Not Used

007 sn * Poor Not Used

008 sn * Poor Not Used

009 sn * Poor Not Used

010 sn * Poor Not Used

011 sn * Poor Not Used

012 sn * Poor Not Used

013 sn * Poor Not Used

014 sn * Poor Not Used

015 sn * Poor Not Used

016 sn * Poor Not Used

017 sn * Poor Not Used

018 sn * Poor Not Used

019 sn * Poor Not Used

020 sn * Poor Not Used

070 001 4 17 124 556 Poor High

002 4 17 107 480 Poor High

003 sn * Poor Not Used

004 sn * Poor Not Used

005 sn * Poor Not Used

006 sn * Poor Not Used

007 sn * Poor Not Used

008 sn * Poor Not Used

009 sn * Poor Not Used

Page 3 of 6

Page 45: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (ft) (fpm) (cfm)

Existing Fume Hood Assessment

UtilizationHood NumberRoomBuilding

Width Test Measurements Flow

Condition

010 sn * Poor Not Used

011 sn * Poor Not Used

012 sn * Poor Not Used

013 sn * Poor Not Used

014 sn * Poor Not Used

015 sn * Poor Not Used

016 sn * Poor Not Used

017 sn * Poor Not Used

018 sn * Poor Not Used

019 sn * Poor Not Used

020 sn * Poor Not Used

103 001 5 16 110 611 Poor Low

002 4 18 114 542 Poor Low

106 001 4 17 119 534 Poor High

002 4 18 109 518 Poor High

003 sn * Poor Not Used

004 sn * Poor Not Used

005 sn * Poor Not Used

006 sn * Poor Not Used

007 sn * Poor Not Used

008 sn * Poor Not Used

009 sn * Poor Not Used

010 sn * Poor Not Used

011 sn * Poor Not Used

012 sn * Poor Not Used

013 sn * Poor Not Used

014 sn * Poor Not Used

015 sn * Poor Not Used

016 sn * Poor Not Used

017 sn * Poor Not Used

018 sn * Poor Not Used

019 sn * Poor Not Used

Page 4 of 6

Page 46: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (ft) (fpm) (cfm)

Existing Fume Hood Assessment

UtilizationHood NumberRoomBuilding

Width Test Measurements Flow

Condition

020 sn * Poor Not Used

108 001 sn * Poor Not Used

112 001 6 16 107 749 Good High

002 6 16 105 735 Good High

003 6 16 107 749 Good High

004 6 16 111 777 Good High

005 6 16 116 812 Good High

006 6 16 108 756 Good High

007 6 16 109 763 Good High

008 6 16 119 833 Good High

009 6 16 110 770 Good High

010 6 16 114 798 Good High

011 6 16 107 749 Good High

012 6 16 112 784 Good High

013 6 16 104 728 Good High

014 6 16 117 819 Good High

015 6 16 113 791 Good High

116c 001 4 17 121 543 Poor Medium

116d 001 6 17 118 864 Fair Low

002 4 17 114 511 Fair Medium

204 001 5 16 118 629 Good Low

206 001 4 18 125 594 Good Low

208 001 6 18 109 845 Good Low

002 6 0 Good Low

212 001 5 18 121 726 Good Low

303 001 4 18 105 499 Good Low

002 4 18 116 551 Good Low

003 6 47 0 Good Low

304 001 4 18 118 561 Fair Low

305 001 4 18 112 532 Fair Low

306 001 4 18 113 537 Poor Low

307 001 6 18 112 854 Poor Low

Page 5 of 6

Page 47: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Bench (ft) walk‐in (ft) snorkel Sash Opening (ft) (fpm) (cfm)

Existing Fume Hood Assessment

UtilizationHood NumberRoomBuilding

Width Test Measurements Flow

Condition

318 001 6 18 105 827 Good High

002 6 18 110 935 Good High

003 6 18 101 859 Good High

004 6 18 100 850 Good High

005 6 18 102 867 Good High

006 6 18 108 918 Good High

007 6 18 110 935 Good High

008 6 18 104 884 Good High

009 6 18 110 935 Good High

010 6 18 111 944 Good High

011 6 18 102 867 Good High

012 6 18 110 866 Good High

320 001 6 18 120 945 Good High

002 6 18 106 835 Good High

003 6 18 111 874 Good High

004 6 16 110 831 Good High

005 6 16 107 808 Good High

006 6 16 109 824 Good High

007 6 16 110 831 Good High

008 6 16 114 861 Good High

009 6 16 110 831 Good High

010 6 16 112 846 Good High

011 6 16 117 884 Good High

012 6 16 114 861 Good High

013 6 16 116 876 Good High

014 6 16 114 861 Good High

015 6 16 107 808 Good High

* No certified data available 

Key for Recommendations:

Excellent/Good Condition ‐ Reuse 

existing hood in its current configuration

Fair Condition ‐ Requires repair or 

upgrade over time to continue use

Poor Condition ‐ Replace with future 

upgrade or renovation

Page 6 of 6

Page 48: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 27

E. LABORATORY SPACE AIRFLOW ASSESSMENT

Page 49: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA Revised SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

001A (W) Corridor 609 10.0 VS-22 (010) 150 150.0 1.5 0.2

0001D (S) Corridor 994 10.0 - 3840 3840.0 23.2 3.9

001E (N) Corridor 720 10.0 CS-25 1440 1440.0 12.0 2.0

001H (W) Corridor 494 10.0 VS-22 (006/008) 400 400.0 4.9 0.8

001J (W) Corridor 538 10.0 VS-24 (002) 150 150.0 1.7 0.3

001M (W) Corridor 226 10.0 VS-24 (003) 150 150.0 4.0 0.7

2(W) Exist. 240 10.0 300 300.0 7.5 1.3

2A (W) Ext. Admin Storage 604 10.0 300 300 0.0 3.0 0.5

2B (W) Exist. 240 10.0 300 300 0.0 7.5 1.3

003A (W) Office 125 10.0 VS-21 150 150 0.0 7.2 1.2

0003 (W) Lab Computer 429 10.0 VS-24 1020 1020 0.0 14.3 2.4

4 (W) Lab 718 10.0 VS-27 2000 1170 589 241.0 16.7 2.8

4 (S) Elec Rm 68 10.0 - 350 1000 -650.0 30.9 5.1

4A (S) Phone Rm 37 10.0 - 260 260.0 42.2 7.0

5 (W) Exist. Electronics Shop 1253 10.0 VS-25 1000 1000.0 4.8 0.8

5 (W) Electronics Shop Office 121 10.0 VS-21 150 150.0 7.4 1.2

5 (S) Cylinder Storage 168 10.0 - 180 510 -330.0 6.4 1.1

6 (W) Toilets 168 10.0 VS-22 200 300 -100.0 7.1 1.2

6 (S) Jan 25 10.0 - 60

7 (W) Resoutce Rm 675 10.0 VS-27 2000 2000 0.0 17.8 3.0

8 (S) Chemical Storage 531 10.0 - 200 140 60.0 2.3 0.4

8 (W) Toilets 168 10.0 VS-22 200 300 -100.0 7.1 1.2

9 (W) Mach. Shop Stor 242 10.0 - 0.0 0.0 0.0 No supply air.

9 (S) Storage 1266 10.0 - 750 1100 -350.0 3.6 0.6

10 (W) Machine Shop Office 130 10.0 VS-22 150 150.0 6.9 1.2

10A (W) Machine Shop 1102 10.0 VS-25 1000 1000.0 5.4 0.9

11 (W) Glassblowing Shop 1051 10.0 VS-4 (2) 2000 1700 300.0 11.4 1.9

11 (S) Office 115 10.0 - 260 260.0 13.6 2.3

12 (W) Synthesis Lab 550 10.0 VS-7 3820 300 3177 343.0 41.7 6.9

12 (S) Office 131 10.0 - 250 380 -130.0 11.5 1.9

13 (W) Synthesis Lab 545 10.0 VS-7 3820 300 3171 349.0 42.1 7.0

13 (S) Office 154 10.0 260 260.0 10.1 1.7

14 (S) Mech Rm 516 10.0 1620 -1620.0 0.0 0.0

16 (S) Bulk Storage 529 10.0 510 810 -300.0 5.8 1.0

17 (S) Toilets 120 10.0 320 -320.0 0.0 0.0

ActualNotes

LABORATORY SPACE AIRFLOW ASSESSMENT - BROWN

Room Number Room Type Square Footage

Ceiling Height VAV

Future

VS-24

Page 50: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA Revised SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

ActualNotes

LABORATORY SPACE AIRFLOW ASSESSMENT - BROWN

Room Number Room Type Square Footage

Ceiling Height VAV

Future

18 (S) Toilets 120 10.0 320 -320.0 0.0 0.0

30 (N) Research Lab Services 330 10.0 VS-24 760 610 150.0 13.8 2.3

31 (N) Autoclave Glassware Washer 150 10.0 CS-23 510 900 -390.0 20.4 3.4

32 (N) Office 155 10.0 VS-21 200 200 0.0 7.7 1.3

33 (N) Office 155 10.0 VS-21 200 200 0.0 7.7 1.3

34 (N) Office 155 10.0 VS-21 200 200 0.0 7.7 1.3

35 (N) Office 155 10.0 VS-21 200 200 0.0 7.7 1.3

36 (N) Office 155 10.0 VS-21 200 200 0.0 7.7 1.3

37 (N) NMR Electronics Shop 180 10.0 VS-22 390 390 0.0 13.0 2.2

39 (N) Faculty Mach Shop 265 10.0 VS-22 800 800 0.0 18.1 3.0

40 (N) Tank Storage 96 10.0 - 250 -250.0 0.0 0.0

41 (N) NMR Grad Workstations 550 10.0 VS-26 1760 1760 0.0 19.2 3.2

41A (N) Compressor Rm. 73 10.0 - 0.0 0.0 0.0 Unknown exhaust

42 (N)Electron

Paramagnetic Resonance Lab

180 10.0 VS-23 410 410 0.0 13.7 2.3

43 (N) NMR/Cell Culture Prep Lab 835 10.0 VS-24 1710 1080 953 -323.0 12.3 2.0

44 (N) NMR Prep Lab 550 10.0 VS-23 1160 525 907 -272.0 12.7 2.1

45 (N) NMR Service Lab 560 10.0 VS-25 1245 960 285.0 13.3 2.2

45A (N) Compressor Rm. 59 10.0 0.0 0.0 0.0 Unknown exhaust

46 (N) Tel/Data 200 10.0 VS-21 125 370 -245.0 3.8 0.6

47 (N) Jan Cl 22 10.0 100 -100.0 0.0 0.0

48 (N) Elec Closet 107 10.0 VS-22 235 235.0 13.2 2.2

049/049A Magnets 4305 20.0 VS-27 (6) 11190 10400 790.0 7.8 2.6

71 (010) (S) Computer Shop 309 10.0 - 440 90 350.0 8.5 1.4

74 (003) (S) Elec Repair Shop 321 10.0 - 1465 813 652.0 27.4 4.6

100 (W) Entry Vestibule 1222 10.0 FB-1 (2) 800 800.0 3.9 0.7

100A (W) Corridor 636 10.0VS-22

(104A)/VS-24 (104)

400 1000 -600.0 3.8 0.6

100C (N) Corridor 1040 10.0 CS-23 600 600.0 3.5 0.6

100D (S) Corridor 1038 10.0 - 970 970.0 5.6 0.9

100F (W) Corridor/Vending 336 10.0 VS-22 350 100 250.0 6.3 1.0

100G (W) Corridor 491 10.0 VS-26 (109) 200 200.0 2.4 0.4

100H (W) Corridor 592 10.0 VS-27 (116) 400 550 -150.0 4.1 0.7

100J (W) Corridor 205 10.0 VS-27 (115) 150 150.0 4.4 0.7

101 (W) Auditorium 2077 10.0 - 6000 6000 0.0 17.3 2.9

101A (W) Prep Room 232 10.0 CS-2 400 575 -175.0 10.3 1.7

102 (S) Office 150 10.0 - 290 290.0 11.6 1.9

Page 51: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA Revised SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

ActualNotes

LABORATORY SPACE AIRFLOW ASSESSMENT - BROWN

Room Number Room Type Square Footage

Ceiling Height VAV

Future

102 (W) Admin 730 10.0 FB-1/FB-*3 1150 570 580.0 9.5 1.6

102A (W) Exec Office 183 10.0 FB-1 360 360 0.0 11.8 2.0

102B (W) Conf Rm 107 10.0 FB-1 300 300 0.0 16.8 2.8

102C (W) Exec Office 278 10.0 FB-2 600 600 0.0 12.9 2.2

103 (S) Office 146 10.0 - 290 290.0 11.9 2.0

104 (S) Elec Rm 68 10.0 - 350 1000 -650.0 30.9 5.1

104A (S) Phone Rm 37 10.0 - 260 260.0 42.2 7.0

104 (W) Admin 1190 10.0 VS-24 1440 1200 240.0 7.3 1.2

104A (W) Office 119 10.0 VS-22 150 150 0.0 7.6 1.3

104B (W) Office 188 10.0 FB-1 300 300 0.0 9.6 1.6

104C (W) Kitchenette 194 10.0 FB-2 520 520 0.0 16.1 2.7

104D (W) Facility Manager 131 10.0 FB-1 275 275 0.0 12.6 2.1

105 (W) Mail/Copy Rm 152 10.0 VS-22 450 450 0.0 17.8 3.0

105 (S) Office 146 10.0 - 290 290.0 11.9 2.0

107 (S) Office 146 10.0 - 290 290.0 11.9 2.0

108 (W) Toilets 222 10.0 VS-21 200 300 -100.0 5.4 0.9

109 (W) GTA 569 10.0 VS-26 1500 1500 0.0 15.8 2.6

109 (S) Office 146 10.0 - 290 290.0 11.9 2.0

110 (S) Office 146 10.0 - 290 290.0 11.9 2.0

110 (W) Toilets 222 10.0 VS-21 200 300 -100.0 5.4 0.9

111 (S) Office 146 10.0 - 290 290.0 11.9 2.0

113 (S) Office 146 10.0 - 290 290.0 11.9 2.0

114 (S) Office 146 10.0 - 290 290.0 11.9 2.0

115 (W) Lab 846 10.0 VS-27 2100 2100 0.0 14.9 2.5

116 (S) Office 146 10.0 - 290 290.0 11.9 2.0

116 (W) Registar 571 10.0 VS-27 2000 2000 0.0 21.0 3.5

118 (W) Admin 469 10.0 FB-2 560 560 0.0 7.2 1.2

118A (W0 Existing 76 10.0 VS-21 100 100 0.0 7.9 1.3

118B (W) Office 158 10.0 FB-1 280 280 0.0 10.6 1.8

118C (W) Office 109 10.0 FB-1 230 230 0.0 12.7 2.1

118D (W) Exist Computers 158 10.0 FB-2 630 630 0.0 23.9 4.0

119 (W) Conf Rm 366 10.0 FB-3 890 890 0.0 14.6 2.4

119 (S) Toilets 120 10.0 - 320 -320.0 0.0 0.0

120 (S) Toilets 120 10.0 - 320 -320.0 0.0 0.0

130 (N) Research Cold Room 350 10.0 CS-21 300 300 0.0 5.1 0.9

131 (N) Centrifuge 154 10.0 VS-22 360 360 0.0 14.0 2.3

132 (N) Office 315 10.0 VS-22 330 330 0.0 6.3 1.0

133 (N) Grads 316 10.0 VS-23 620 620 0.0 11.8 2.0

Page 52: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA Revised SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

ActualNotes

LABORATORY SPACE AIRFLOW ASSESSMENT - BROWN

Room Number Room Type Square Footage

Ceiling Height VAV

Future

134 (N) Office 158 10.0 VS-21 190 190 0.0 7.2 1.2

135 (N) Office 158 10.0 VS-21 190 190 0.0 7.2 1.2

136 (N) Office 158 10.0 VS-21 190 190 0.0 7.2 1.2

137 (N) Grads 315 10.0 VS-24 735 735 0.0 14.0 2.3

138 (N) Biochemistry Lab 545 10.0 VS-25 1290 1010 523 -243.0 14.2 2.4

139 (N) Biochemistry Lab 1120 10.0 VS-25 2640 930 2510 -800.0 14.1 2.4

140 (N) Organic & Biochem Lab 1190 10.0 VS-25 2640 930 5469 -3759.0 13.3 2.2

141 (N) Tel Data 100 10.0 VS-21 125 -245.0 7.5 1.3

144 (N) Elec Closet 138 10.0 VS-22 235 235.0 10.2 1.7

142 (N) Jan Cl 22 10.0 - 100 -100.0 0.0 0.0

162 (S) Analytical Lab 456 10.0 - 1190 880 1364 -1054.0 15.7 2.6

163 (S) Analytical Lab 456 10.0 - 1190 880 891 -581.0 15.7 2.6

164 (S) Analytical Lab 456 10.0 - 1190 880 845 -535.0 15.7 2.6

165 (S) Physical Lab 456 10.0 - 1190 880 876 -566.0 15.7 2.6

166 (S) Physical Lab 675 10.0 - 1800 880 1635 -715.0 16.0 2.7

200 (W) Corridor 567 10.0 VS-24 (2-201) 400 400.0 4.2 0.7

200A (W) Corridor 681 10.0 VS (208) 400 650 -250.0 3.5 0.6

200C (N) Corridor 800 9.5 SR1-1 520 520.0 4.1 0.7

200D (S) Corridor 1072 10.0 - 2775 2775.0 15.5 2.6

200F (W) Corridor 178 10.0 VS-23 (222) 200 200.0 6.7 1.1

200G (W) Corridor 410 10.0 VS 700 700.0 10.2 1.7

200H (W) Corridor 649 10.0VS-23

(216)/VS-24 (215)

400 650 -250.0 3.7 0.6

200J (W) Corridor 230 10.0 VS-25 (220) 150 150.0 3.9 0.7

201 (W) Under-Grad Study 475 10.0 VS-24 (2) 1200 1200 0.0 15.2 2.5

202 (W) Library 1933 10.0 VS-23 (2)/ VS-25(2) 3340 3200 140.0 10.4 1.7

202B (W) Work Rm 91 10.0 VS-23 (202) 300 300 0.0 19.8 3.3

202 (S) Office 150 10.0 340 340.0 13.6 2.3

203 (W) Office 226 10.0 VS 350 350 0.0 9.3 1.5

204 (W) Office 259 10.0 VS-22 350 350 0.0 8.1 1.4

204 (S) Elec Rm 68 10.0 350 1000 -650.0 30.9 5.1

204A (S) Phone Rm 37 10.0 260 260.0 42.2 7.0

205 (S) Office 145 10.0 340 340.0 14.1 2.3

205 (W) Registar Clrm 960 10.0 VS-28 2300 2400 -100.0 14.4 2.4

206 (S) Office 145 10.0 340 340.0 14.1 2.3

206 (W) Registar Rm 1045 10.0 VS-27 2300 2300 0.0 13.2 2.2

207 (W) Registar Rm 991 10.0 VS-27 1950 1900 50.0 11.8 2.0

370

Page 53: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA Revised SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

ActualNotes

LABORATORY SPACE AIRFLOW ASSESSMENT - BROWN

Room Number Room Type Square Footage

Ceiling Height VAV

Future

208 (S) Office 145 10.0 340 340.0 14.1 2.3

208 (W) Resource Rm 448 10.0 VS 1600 1600 0.0 21.4 3.6

209 (W) Toilets 182 10.0 VS-21 200 300 -100.0 6.6 1.1

210 (S) Office 145 10.0 340 340.0 14.1 2.3

210 (W) IT Dept 190 10.0 VS-22 300 300.0 9.5 1.6

211 (S) Office 145 10.0 340 340.0 14.1 2.3

211 (W) Dept Servers 326 10.0 0.0 0.0 0.0

212 (W) Toilets 180 10.0 VS-21 200 300 -100.0 6.7 1.1

213 (W) Study Rm 122 10.0 260 260 0.0 12.8 2.1

214 (W) Study Rm 122 10.0 260 260 0.0 12.8 2.1

215 (W) Study Rm 122 10.0 260 260 0.0 12.8 2.1

216 (W) Study Rm 150 10.0 VS-23 640 375 265.0 25.6 4.3

217 (W) Office 251 10.0 VS-22 350 350 0.0 8.4 1.4

218 (W) Office 240 10.0 VS-22 350 350 0.0 8.8 1.5

218 (S) Toilets 120 10.0 320 -320.0 0.0 0.0

219 (S) Toilets 120 10.0 320 -320.0 0.0 0.0

219 (W) Seminar Rm 956 10.0 VS-28 2400 800 1600.0 15.1 2.5

220 (W) Seminar Rm 587 10.0 VS-25 1000 1000 0.0 10.2 1.7

221 (W) E-Calc Lab 836 10.0 VS-27 2000 2000 0.0 14.4 2.4

222 (W) Lab Service 154 10.0 VS-23 300 300 0.0 11.7 1.9

230 (N) Cell Culture 330 9.5 VS-24 870 770 100.0 16.7 2.6

231 (N) Cell Culture 325 9.5 VS-24 850 650 200.0 16.5 2.6

232 (N) Office 160 9.5 VS-21 170 170 0.0 6.7 1.1

233 (N) Office 160 9.5 VS-21 170 170 0.0 6.7 1.1

234 (N) Office 160 9.5 VS-21 170 170 0.0 6.7 1.1

235 (N) Office 160 9.5 VS-21 170 170 0.0 6.7 1.1

236 (N) Office 160 9.5 VS-21 170 170 0.0 6.7 1.1

237 (N) Office 160 9.5 VS-21 170 170 0.0 6.7 1.1

238 (N) Office 160 9.5 VS-21 170 170 0.0 6.7 1.1

239 (N) Office 160 9.5 VS-21 330 330 0.0 13.0 2.1

240A/B (N) Physical Chem Lab 1395 9.5 VS-26 3600 2965 1121 -486.0 16.3 2.6

241 (N) Instrument Lab 800 9.5 VS-25 2190 1785 600 -195.0 17.3 2.7

242 (N) Analytical Lab 660 9.5 VS-26 1660 300 1955 -595.0 15.9 2.5

243 (N) Tel. / Data 100 9.5 VS-21 125 -245.0 7.9 1.3

246 (N) Elec Closet 138 9.5 VS-22 235 235.0 10.8 1.7

244 (N) Jan Cl 22 10.0 - 100 -100.0 0.0 0.0

262 (S) Organic Lab 456 10.0 - 2770 300 3601 -1131.0 36.4 6.1

263 (S) Organic Lab 456 10.0 - 2770 300 3634 -1164.0 36.4 6.1

370

VS-24

Page 54: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA Revised SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

ActualNotes

LABORATORY SPACE AIRFLOW ASSESSMENT - BROWN

Room Number Room Type Square Footage

Ceiling Height VAV

Future

264 (S) Organic Lab 456 10.0 - 2770 300 3978 -1508.0 36.4 6.1

265 (S) Organic Lab 456 10.0 - 2770 300 3838 -1368.0 36.4 6.1

266 (S) Organic Lab 683 10.0 - 3615 1140 3655 -1180.0 31.8 5.3

269 (S) Organic Lab 271 10.0 - 1730 2333 -603.0 38.3 6.4

270 (S) Organic Lab 275 10.0 - 1730 2354 -624.0 37.7 6.3

330 (N) Toilets 130 9.5 125 250 -125.0 6.1 1.0

331 (N) Toilets 130 9.5 125 250 -125.0 6.1 1.0

332 (N) Grads 165 9.5 VS-23 480 480 0.0 18.4 2.9

333 (N) Office 165 9.5 VS-21 290 290 0.0 11.1 1.8

334 (N) Office 80 9.5 VS-21 140 140 0.0 11.1 1.8

335 (N) Grads 190 9.5 VS-23 580 580 0.0 19.3 3.1

336 (N) ResearchLab Services 135 9.5 VS-23 460 460 0.0 21.5 3.4

337 (N) Synthesis Lab 715 9.5 VS-4 (2) 2530 1425 3602 -2497.0 22.3 3.5

338 (N) Synthesis Lab 830 9.5 VS-4 (2) 3790 1090 5374 -2674.0 28.8 4.6

339 (N) Cobre Lab 1215 9.5 VS-4 (4) 6740 1420 7095 -1775.0 35.0 5.5

340 (N) Tel. / Data 100 9.5 VS-21 135 -235.0 8.5 1.4

343 (N) Elec Closet 135 9.5 VS-22 235 235.0 11.0 1.7

341 (N) JC 20 9.5 - 100 -100.0 0.0 0.0

300B (N) Corridor 550 9.5 CVS-24 765 765.0 8.8 1.4

300C (N) Corridor 800 9.5 SR1-1 1000 1000.0 7.9 1.3

Sub - Totals: 79959 172185 0 65665

370

CS-21

Page 55: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

0001 Corridor 1668 10.0 SBP-1 0 0.0 0.0 0.0 0.00 Unknown supply

0002 Lab SVC 49 10.0 0 0.0 0.0 No supply air.

0004 Classroom 380 10.0 VS-1 590 390 200 9.3 1.6

5 Mech Rm. 2756 10.0 0 0.0 0.0 No supply air.

0005A Mach 61 10.0 0 0.0 0.0 No supply air.

006 Class Lab 1498 10.0 VS-4/SBP-1 3110 1870 1026 214 12.5 2.1

0010 Women's RR 145 10.0 0 0.0 0.0 No supply air.

0010A Women Lounge 79 10.0 0 0.0 0.0 No supply air.

0012 Storage 117 10.0 0 0.0 0.0 No supply air.

0014 Solvent Storage 210 10.0 0 0.0 0.0 No supply air.

0016 Jan Supply 93 10.0 0 0.0 0.0 No supply air.

0018 Men's RR 142 10.0 0 0.0 0.0 No supply air.

0021 Jan 65 10.0 0 0.0 0.0 No supply air.

0022 Class Lab 1498 10.0 VS-1/VS-4 3110 1870 1083 157 12.5 2.1

0024 Classroom 380 10.0 VS-1 590 390 200 9.3 1.6

0026 Equip. Storage 50 10.0 0 0.0 0.0 No supply air.

051 Corridor 1559 10.0 SBP-1 (2) 300 300 1.2 0.2

051N Vestibule 59 10.0 0 0.0 0.0 No supply air.

051S Vestibule 55 10.0 0 0.0 0.0 No supply air.

052 Storage 389 10.0 0 0.0 0.0 No supply air.

054 Class Lab 1498 10.0 VS-4 (2) 3110 1955 1145 10 12.5 2.1

058 Lab SVC 378 10.0 VS-3 1100 1020 576 -496 17.5 2.9

061 Lab SVC 830 10.0 VS-3 1055 1020 365 -330 7.6 1.3

063 Class Lab 782 10.0 VS-4 1850 1230 538 82 14.2 2.4

064 Class Lab 1506 10.0 VS-4/SBP-1 3500 2440 991 69 13.9 2.3

70 Class Lab 1487 10.0 VS-4 (2) 3200 1960 1036 204 12.9 2.2

71 Jan 65 10.0 0 0.0 0.0 No supply air.

74 Classroom 391 10.0 VS-1 620 420 200 9.5 1.6

100 Corridor 2038 10.0 VS-1/SBP-1 (2) 1370 1370 4.0 0.7

101 Freezer Rm 137 10.0 0 0.0 0.0 No supply air.

102 Comm Closet 10 10.0 0 0.0 0.0 No supply air.

103 Lab SVC 826 10.0 VS-3 1060 980 1153 -1073 7.7 1.3

103A Lab SVC 295 10.0 VS-2 1000 920 80 20.3 3.4

104 Office 185 10.0 295 385 -90 9.6 1.6

104A Office 175 10.0 290 290 9.9 1.7

105 Office 136 10.0 350 500 -150 15.4 2.6

105A Office 336 10.0 350 350 6.3 1.0

106 Class Lab 1498 10.0 VS-4 (2) 3530 2290 1052 188 14.1 2.4

LABORATORY SPACE AIRFLOW ASSESSMENT -DRAKE

NotesRoom Number Room Type Square Footage

Ceiling Height VAV

Actual Future

VS-1

VS-1

Page 56: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

LABORATORY SPACE AIRFLOW ASSESSMENT -DRAKE

NotesRoom Number Room Type Square Footage

Ceiling Height VAV

Actual Future

107 Jan 65 10.0 0 0.0 0.0 No supply air.

108 Lab 378 10.0 VS-1 600 600 100 -100 9.5 1.6

109 Men 130 10.0 0 0.0 0.0 No supply air.

112 Class Lab 1506 10.0 VS-7 (4) 13055 11613 1442 52.0 8.7

116A Lab 168 10.0 Vs-4 (116C) 65 65 2.3 0.4

116B Cold Rm 182 10.0 0 0.0 0.0 No supply air.

116C Lab 747 10.0 VS-4 1465 1150 543 -228 11.8 2.0

116D Lab 742 10.0 VS-4 1670 1305 1375 -1010 13.5 2.3

116E Storage 98 10.0 0 0.0 0.0 No supply air.

200 Corridor 1914 10.0 VS-1 (2)/SBP-1 (2) 905 905 2.8 0.5

201 Freezer Rm 137 10.0 0 0.0 0.0 No supply air.

202 Comm. Rm. 10 10.0 0 0.0 0.0 No supply air.

203A Office 165 10.0 210 265 -55 7.6 1.3

203B Office 151 10.0 210 265 -55 8.3 1.4

203C Lab 230 10.0 420 530 -110 11.0 1.8

204 Lab 751 10.0 VS-4 1580 1600 629 -649 12.6 2.1

204A Conf. 238 10.0 230 265 -35 5.8 1.0

204B Office 136 10.0 235 235 10.4 1.7

205 Lab 391 10.0 VS-1 620 620 0 9.5 1.6

206 Lab 750 10.0 VS-4 1670 1690 594 -614 13.4 2.2

206A Office 84 10.0 0 0.0 0.0 No supply air.

207 Office 391 10.0 VS-1 620 620 0 9.5 1.6

208 Lab 959 10.0 VS-4 1750 1380 845 -475 10.9 1.8

209 Jan Closet 65 10.0 0 0.0 0.0 No supply air.

210 Lab 944 10.0 VS-4 1750 1550 200 11.1 1.9

210A Office 84 10.0 SBP-1 (200) 130 130 9.3 1.5

211 Women RR 130 10.0 0 0.0 0.0 No supply air.

212 Lab 743 10.0 VS-4 1670 1690 726 -746 13.5 2.2

214 Lab 750 10.0 VS-4 1580 1780 -200 12.6 2.1

214A Office 284 10.0 235 265 -30 5.0 0.8

214B Corridor 91 10.0 230 230 15.2 2.5

216 Mech Rm. 16 10.0 0 0.0 0.0 No supply air.

300 Corridor 1890 10.0 SBP-1 (3) 1770 1770 5.6 0.9

301 Women RR 137 10.0 0 0.0 0.0 No supply air.

302 Mech Rm. 16 10.0 0 0.0 0.0 No supply air.

302A Comm. Rm. 10 10.0 0 0.0 0.0 No supply air.

303 Lab 448 10.0 SBP-1 1050 -1050 0.0 0.0 Unknown supply

304 Lab 788 10.0 SBP-1 1930 1130 561 239 14.7 2.4

SBP-1

VS-1

VS-1

Page 57: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

SA RA GEX FHEX Pressurization AC/HR CFM/SF SA RA GEX FHEX Pressurization AC/HR CFM/SF

LABORATORY SPACE AIRFLOW ASSESSMENT -DRAKE

NotesRoom Number Room Type Square Footage

Ceiling Height VAV

Actual Future

304A Office 301 10.0 320 320 0 6.4 1.1

304B Passage 96 10.0 320 320 20.0 3.3

305 Lab 683 10.0 SBP-1 1075 532 543 9.4 1.6 Unknown exhaust

305A Closet 21 10.0 0 0.0 0.0 No supply air.

306 Lab 790 10.0 SBP-1 2000 1200 537 263 15.2 2.5

306A File 85 10.0 0 0.0 0.0 No supply air.

307 Lab 181 10.0 854 -854 0.0 0.0 Unknown supply

307A Lab SVC 149 10.0 0 0.0 0.0 Unknown supply

307B Lab SVC 149 10.0 0 0.0 0.0 Unknown supply

308 Seminar Room 391 10.0 SBP-1 715 715 0 11.0 1.8

309 Jan Closet 65 10.0 0 0.0 0.0 No supply air.

310 Office 232 10.0 215 215 5.6 0.9 Unknown exhaust

310A Office 162 10.0 220 220 8.1 1.4

311 Men RR 130 10.0 0 0.0 0.0 No supply air.

312 Office 231 10.0 320 320 8.3 1.4 Unknown exhaust

312A Office 162 10.0 320 320 11.9 2.0

314 Comp 197 10.0 SBP-1 215 215 6.5 1.1

314A Xray Rm 197 10.0 SBP-1 440 435 5 13.4 2.2

316 Office 277 10.0 SBP-1 360 360 0 7.8 1.3

316A Office 103 10.0 SBP-1 360 360 21.0 3.5

318 Lab 981 10.0 10880 10686 194 66.5 11.1

318A Office 85 10.0 0 0.0 0.0 No supply air.

320 Lab 1000 10.0 13545 12778 767 81.3 13.5

Sub - Totals: 47213 96285 0 38660 53103 4522

SPB-1

SPB-1

SBP-1

SBP-1

Page 58: UNIVERSITY OF DELAWARE BROWN & DRAKE … Hall/2-HVAC.pdfBrown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware SG Project No.: 21101.000 Page

Brown & Drake HVAC Assessment Study Draft Submission 16 February 2016 University of Delaware

SG Project No.: 21101.000 Page 28

F. LABORATORY SPACE PRESSURIZATION DIAGRAMS