VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 September 3, 2020 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNITS 1 AND 2 Serial No.: NRA/DEA: Docket Nos.: License Nos.: REVISED LICENSE RENEWAL COMMITMENT SUPPLEMENT PRESSURIZER SURGE LINE WELDS INSPECTION FREQUENCY 20-049A RO 50-338/339 NPF-4/7 By letter dated March 26, 2020, Virginia Electric and Power Company (Dominion Energy Virginia) requested NRC approval to revise the North Anna Units 1 and 2 pressurizer surge line welds inspection frequency from once every 40 months to once per 10-year inspection interval for the fifth and sixth ISi intervals. The attachment to the March 26, 2020 letter included the flaw tolerance evaluation for the North Anna Units 1 and 2 pressurizer surge line welds, which was prepared by Structural Integrity Associates, Inc. The purpose of this supplemental letter is to further assist the NRC staff in their review of Dominion Energy Virginia's commitment change request. Accordingly, Attachments 1 and 2 provide the results of the last examinations performed on the Unit 1 and Unit 2 pressurizer surge line welds during refueling outages N1 R25 (Fall 2016) and N2R26 (Spring 2018), respectively. There were no reportable indications identified as a result of the examinations. If you have any questions or require additional information, please contact Ms. Diane E. Aitken at (804) 273-2694. Respectfully, i,;(d.~f-6 Senior Vice President - Nuclear Operations and Fleet Performance Commitment made in this letter: None Attachments: 1. N1 R25 Unit 1 Pressurizer Surge Line Welds Examination Results 2. N2R26 Unit 2 Pressurizer Surge Line Welds Examination Results

United States Nuclear Regulatory Commission Serial No.: 20-049A … · 2020. 9. 16. · on the Unit 1 and Unit 2 pressurizer surge line welds during refueling outages N1 R25 (Fall

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • VIRGINIA ELECTRIC AND POWER COMPANY

    RICHMOND, VIRGINIA 23261

    September 3, 2020

    United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555

    VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNITS 1 AND 2

    Serial No.: NRA/DEA: Docket Nos.: License Nos.:

    REVISED LICENSE RENEWAL COMMITMENT SUPPLEMENT PRESSURIZER SURGE LINE WELDS INSPECTION FREQUENCY

    20-049A RO 50-338/339 NPF-4/7

    By letter dated March 26, 2020, Virginia Electric and Power Company (Dominion Energy Virginia) requested NRC approval to revise the North Anna Units 1 and 2 pressurizer surge line welds inspection frequency from once every 40 months to once per 10-year inspection interval for the fifth and sixth ISi intervals.

    The attachment to the March 26, 2020 letter included the flaw tolerance evaluation for the North Anna Units 1 and 2 pressurizer surge line welds, which was prepared by Structural Integrity Associates, Inc. The purpose of this supplemental letter is to further assist the NRC staff in their review of Dominion Energy Virginia's commitment change request. Accordingly, Attachments 1 and 2 provide the results of the last examinations performed on the Unit 1 and Unit 2 pressurizer surge line welds during refueling outages N1 R25 (Fall 2016) and N2R26 (Spring 2018), respectively. There were no reportable indications identified as a result of the examinations.

    If you have any questions or require additional information, please contact Ms. Diane E. Aitken at (804) 273-2694.

    Respectfully,

    i,;(d.~f-6 Senior Vice President - Nuclear Operations and Fleet Performance

    Commitment made in this letter: None

    Attachments: 1. N 1 R25 Unit 1 Pressurizer Surge Line Welds Examination Results 2. N2R26 Unit 2 Pressurizer Surge Line Welds Examination Results

  • Serial No. 20-049A Docket Nos. 50-338/339

    Revised License Renewal Commitment Supplement Page 2 of 2

    cc: U.S. Nuclear Regulatory Commission - Region II Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, GA 30303-1257

    NRC Senior Resident Inspector North Anna Power Station

    Mr. G. Edward Miller NRC Senior Project Manager - North Anna U.S. Nuclear Regulatory Commission One White Flint North Mail Stop 09 E-3 11555 Rockville Pike Rockville, MD 20852-2738

    Mr. Vaughn Thomas NRC Project Manager- Surry U.S. Nuclear Regulatory Commission One White Flint North Mail Stop 04 F-12 11555 Rockville Pike Rockville, MD 20852-2738

    Mr. Marcus Harris Old Dominion Electric Cooperative Innsbrook Corporate Center, Suite 300 4201 Dominion Boulevard Glen Allen, Virginia 23060

  • Attachment 1

    N1 R25 Unit 1 Pressurizer Surge Line Welds Examination Results

    Virginia Electric and Power Company (Dominion Energy Virginia)

    North Anna Power Station Unit 1

    Serial No.: 20-049A Docket No.: 50-338

  • Liquid Penetrant Examination

    Site/Unit: NAPS Procedure: ER-AA-NDE-PT-300 Outage No.: N1R25 -------Summary No.: N1.R1.11.310 Procedure Rev.: 7 Report No.: PT-16-019 -------

    Workscope: AUG Work Order No.: 59102983133 Page: 1 of 1

    Code: 2004 Edition Cat./ltem: R-A/R1.11 Location: C Loop

    Drawing No.: 11715-WMKS-0109D Description: r-,iozzle to Pipe

    System ID: RC ---- - - -------------=----------------------Component ID: 11715-WMKS-0109D / 14-RC-10 / 37

    Limitations: None·

    Light Meter Mfg.: N/A Serial No.: N/A

    Temp. Tool Mfg.: ATKINS Serial No. : 07

    Comparator Block Temp.: Side A: N/A °F Side B: N/A °F Resolution:

    Lo/Wo Locati~n: N/A Surface Condition: '

    Cleaner Visible Ii(]

    Penetrant Fluorescent 0 Remover

    Brand MAGNAFLUX MAGNAFLUX MAGNAFLUX

    Type SKC-S SKL-SP2 SKC-S

    Batch No. 13M12K 12A08K ' 13M12K

    Time Evap. 5 Min Dwell 10 Min Evap. 1 Min

    Time Exam Started: 0120 Time Exam Completed:

    Indication Loe Loe Diameter Length Type

    No. L w R/L

    N/A

    . - . . - -· -- ·-

    Comments:

    Flashligh use as illumination and Character Resolution Card Dom-2016-0001

    -Results: NRI ~ RI 0 Percent Of Coverage Obtained > 90%:

    Examiner Level Ill Odegard, Jeffrey D

    Examiner Level II

    Stevermer, Aaron J.

    Other Level N/A N/A

    Liquid Penetrant Examination

    Eval D N/A Reviewed Previous Data:

    Date Reviewer

    9/17/2016 Wayne Thomas Lv Ill

    Date

    9/17/2016

    Date

    Site Review Dennis Strickland Lv II

    ANII Review fv

    Mat/Thickness: ss / 1.3"

    Illumination: N/A

    Surface Temp.: _ ___;_8_0 __ °F

    0.044" Character Card

    Contour Ground

    Developer

    MAGNAFLUX

    Develop

    0201 ·

    Remarks

    --·

    N/A

    SKD-S2

    13F19K

    ..

    10 Min

    Date

    9/18/2016

    Date

    9/22/2016

    Date

    ...

    I

  • ~, ~ Dominion' Site/Unit: NAPS

    UT Calibration/Examination 1 Procedure: FR-AA-NDE-I II-802 Outage No.: N1R25

    Summary No.: N1 .RU1.310 Procedure Rev.: 4 Report No.: UT-16-064

    Works cope: AUG Work Order No.: 59102983133 Page: of 4

    Code: 2004 Edition Cat./ltem: R-AJR1.11 Location: C Loop

    Drawing No.: 11715-WMKS-0109D Description: Nozzle to Pipe

    System ID: RC

    Component ID: -::1":'.11:-1:-:5:-:.w=:M::-K::s:-.o=-1:-:o-:9=D-:,-:1-:-4_-:R:-::C:--1:-:o:-,:-:3::7:------------------------------------------------Size/Length: 1.2" / 44.0" Thickness/Diameter: 1.25" / 14.0"

    Limitations: Limited on nozzle side, see attached. Start Time: 0211 Finish Time: 0243

    Instrument Settings Search Unit Cal. Axial Oriented Search Unit Time Date Serial No.: 140723507 Serial No.: 00H45N Checks

    Calibration Signal Sweep , Initial Cal. Sound Path Manufacturer: Olympus Manufacturer: KBA 0001 9/17/2016 Reflector Amplitude% Division

    Model: EPOCH 600 Linearity: L-16-020 Size: 0.50" Model: Comp-G Inter. Cal. 0211 6/17/2016 1.5" Notch I 81% 5.3 2.111"" Delay: 6.567 µs Range: 4.000" Freq.: 2.25 MHZ Center Freq.: N/A

    Inter. Cal. NIA I M'tl CalNel: 0.1237 in/µs Pulser: Sqaure Inter. Cal. 0243 9/17/2016 Exam Angle: 45° Squint Angle: N/A --- Final Cal. 0350 9/17/2016 I Damping: 4000 Reject: 0% Measured Angle: .45° Mode: Shear Rep. Rate: Auto Freq. : 2.25 Mhz --- Couplant

    Exit Point 0.4" # of Elements: 1 Filter: 0.5 -4.0 Mhz Mode: Fullwave -- Cal. Batch: 12J066 Circumferential Oriented Search Unit

    Config.: Single Focus: NIA Voltage: 400 Other: N/A Type: Sonotech Calibration Signal Swt:ep

    Sound Path Shape: Round Contour: N/A Mfg.: SONOTECH Reflector Amplitude% Division

    Wedge Style: MSWQC NIA Ax. Gain (dB): 10.0 Circ. Gain (dB): NIA Exam Batch: 12J066 Search Unit Cable

    10 Screen Div.= 4.0 in. of Sound Path Type: Sonotech -- -- Type: RG 174 Length: 6" No. Conn.: o - - Mfg.: SONOTECH Calibration Block Scan Coverage

    Cal. Block No. 10876 Upstream ~ Downstream ~ Scan dB: 28.0 Reference Block

    Reference/Simulator Block

    Thickness 2.25" Dia.: 0 Gain Signal Sweep Sound Path . cw~ CCW~ Scan dB:· 28.0 Serial No.: 05-6535 dB Reflector Amplitude% Division Cal. Blk. Temp. 70° Temp. Tool: 07 Type: SS Rompus Block 10.0 FSDH 16% 2.6 1.073" -- Ex 90%:

    Examiner Level 11-PDI

    Stevermer, Aaron J.

    Examiner

    NIA

    Other

    NIA

    Level NIA

    Level N/A

    UT Calibration/Examination

    Yes 'Reviewed Previous Data:

    Signature

    Yes

    Date I Reviewer 9/17/2016 Wayne Thomas Lv Ill

    Date I Sile Review Dennis Strickland Lv II

    Date I ANII Review

    N/A

    Date

    9/22/20116

    Date

    9/22/2016

    Date

  • ~l ;;,,p Dominion' Site/Unit: NAPS UT Calibration/Examination

    1 Procedure: ER-AA-NDE-UT-802 Outage No.: N1 R25

    Summary No.: N1.R1.11.310 Procedure Rev.: 4 Report No.: UT-16-064

    Workscope: AUG Work Order No.: 59102983133 Page: 2 of 4

    Code: 2004 Edition Cat./ltem: R-A/R1.11 Location: C Loop

    Drawing No.: 11715-WMKS-0109D Description: Nozzle to Pipe

    System ID: RC

    -----------------------------------------------------------------Component ID: 11715-WMKS-0109D / 14-RC-10 / 37 Size/Length: 1.2" / 44.0" Thickness/Diameter: 1.25'" / 14.0" Limitations: Limited on nozzle side, see a'ttached. Start Time: 0244 Finish Time: 0306

    Instrument Settings Search IJnit Cal. Time Date Axial Oriented Search Unit Serial No.: 140723507 Serial No.: O0F1DF Checks

    Calibration Signal Sweep Initial Cal. Sound Path Ma·nufacturer: Olympus Manufacturer: KBA 0010• 9/17/2016 Reflector Amplitude% Division

    Model: EPOCH 600 Linearity: L-16-020 Siz~: 0.50" Model: Comp-G Inter. Cal. 0244 9/17/2016 1.5" Notch 82% 5.4 2.704" I Inter. Cal. N/A Delay: 8.200 µs Range: 5.00" Freq.: 2.25 MHZ Center Freq.: 2.25 Mhz

    Inter. Cal. 0306 9/17/2016 M'tl CalNel: 0.1237 in/µs Pulser: Square Exam Angle: so· Squint Angle: N/A --- Final Cal. 0352 9/17/2016 Damping: 400 0 Reject: 0% Measured Angle: so· Mode: Shear -- Couplant Rep. Rate: Auto Freq.: 2.25 Mhz Exit Point C.45" # of Elements: 1 Filter: . 0.5 - 4.0 Mhz Mode: Fullwave -- Cal. Batch: 12J066 Circumferential Oriented Search Unit Config .: Single Focus: . NA Voltage: 400 Other: N/A Type: Sonotech Calibration Signal Sweep Sound Path Shape: Round Contour: N/A Reflector Amplitude% Division Mfg.: SONOTECH

    Wedge Style: MSWQC N/A Ax. Gain (dB): 30.5 Circ. Gain (dB): N/A Exam Batch: 12J066

    Search Unit Cable 10 Screen Div. = 5.0 in. of Sound Path No. Conn.: O ·

    Type : Sonotech Type: RG 174 Length: 6' -- -- - - Mfg.: SONOTECH

    Calibration Block Scan Coverage Cal. Block No. 10876

    I

    Reference Block Reference/Simulator Block lJps(ream ~ Downstream~ Scan dB: __:!i.:.:_ Gain Signal Sweep

    Sound Path Thickness 2.25" Dia.: 0 cw □ CCWO Scan dB: N/A Serial No. : 05-6535 dB Reflector Amplitude% Division Cal. Blk. Temp. 70° Temp. Tool: 07 -- SS Rompus Block Exam Surface: OD Type: 30.5 NSDH 86% 1.4 0.693" --Comp. Temp. ao· Temp. Tool: 07

    Surface Condition: Ground --Recordable lndication(s): Yes O No~ (lfYes, Ref. Altached Ultrasonic Indication Report.) Results: NRI ~ RI n Geom D Comments: None Percent Of Coverage Obtained > 90%:

    Examiner Level 11-PDI

    Stevermer, Aaron J .

    Examiner

    N/A

    Other

    N/A

    Level N/A

    Level N/A

    UT Calibration/Examination

    Yes Reviewed Previous Data:

    Signc1ture

    Yes

    Date I Reviewer 9/17/2016 Wayne Thomas Lv Ill

    Date I Site Review Dennis Strickland Lv II

    Date I ANII Review N/A

    Date

    9/22/2016

    Date

    9/22/2016

    Date

  • ~ ~~ ~~ Dominion'

    Supplemental Report Report No.:

    Page:

    UT-16-064

    3 of 4

    Summary No.: N1.R1.11.310 -----------=~--:-----Examiner: Stevermer, Aaron J. ~ Level: 11-PDI Reviewer: i.J .L. ~-" ~ s (..e',J 1Ii- ~- Date: ~-2.'Z•IL Examiner: _N_/.;...A'---------------- Level: NIA Site Review:~~~ P .. ~Dl.."u ~ Date: q{2:r../u,.,

    Other: _N_/_A _____________ _ Level: N/A ANII Review: N/A Date:

    Comments:

  • ~ ',t,;il,••· Dominion" Report No: UT-16-064

    Summary# Nl.Rl.11.310

    Pg. 4 of 4

    Prepared by: W. Thomas~,_,v'![C..

    Date: 9/22/2016

    Weld Number

    Thickness 37 Weld Length

    Weld Width

    44" 1.25" 1.2"

    0.417' HT X 1, 1" WIDTH• 0.458SQ. IN. a TOTAL VOLUME REQUIRED EACH SIDE CF WELD

    ~ EXAMINED 100% OF REQUIRED VOLUME OS SIDE ~ EXAM LIMITED US SIDE AX DIRECTION FOR 0.02 SQ. IN.

    DUE TO NOZZLE CONFIGURATION .02/ .459 = 0.04 X 100 = 4%

    ~ NED 96% CF THE REOIJIRED VOLUME US SIDE /lJf. DIRECTION

    Examination Volume Dimensions - Height 0.417" Length 44" Width

    Coverage Summary Required Scans (each has a weighing factor of 100 for complete coverage)

    ANGLE UpSt-Ax UpSt-Circ DnSt-Ax DnSt-Circ

    45/60 96% 100% 100% 100%

    100+100+100+96=396/400=99 Code Coverage Total

    Notes: * Best Effort Coverage (Max 25%) Total

    1) Code Coverage refers to the maximum percentage of the required examination volume

    that is effectively examined with the qualified examination procedure.

    2) Best Effort Coverage refers to the required examination volume past the weld

    centerline that is examined in the axial beam direction with an Appendix VIII

    demonstrated procedure for single sided coverage.

    2.2"

    99%

    N/A

  • ~-~, wDJ Dominion' Site/Unit: NAPS

    Summary No.: N1 .R1.20.101

    Workscope: ISi

    Code: 2004 Edition

    Drawing No.: 11715-WMKS-0109G-2

    System ID: RC

    UT Calibration/Examination Procedure: ER-AA-NDE-UT-700

    Cat.lltem:

    Procedure Rev.:

    .Work Order No.:

    R-A/R1.20

    Description: P!PE-WELDOLET

    0

    59102983133

    Location:

    Outage No.: N1R25

    Report No.: UT-16-086

    Page: 1 of 3

    C-LOOP

    ________________ :.,_ ____________________________________________ _ Component 10: 11715-WMKS-0109G-2 / 29-RC•7 / SW-31 Size!Length: 2.5" / 80" Thickness/Diameter: 3.20" / 29"

    Limitations: See attached. Start Time: 1025 Finish Time: 1048

    Seriat No.:

    Manufacturer:

    Instrument Settings

    140723507

    Olympus

    Search Unit

    Serial No.: 021N2J

    Manufacturer: KBA

    Model: EPOCH 600 Linearity: L-16-020. Size: 1.0 om Model: Comp-G _ -------Delay: 13.830 µs Range: - 7.200" ____ Freq. : 1.0 M HZ Center Freq.: N/A --M'tl CalNel: 0.2330 infµs Pulser: sauare 45° Squint Angle: ~ ---- Exam Ang.le: Damping: 400 n Reject: 0% Measured Angle: 45° Mode: Longitudinal Rep. Rate: Auto Freq.: 1.0 Mhz Exit Point 0.90" # of Elements: 1 -Filter: 0.2-1.2 Mhz Mode: Fullwave --- Config.: Single Focus: F.D .• 2.44" Voltage: 400 Other: N/A '

    ---Shape: Round Contour: N/A

    sws

    Cal. Time Date Checks

    Initial Cal. 0700 9/20/2016 ·

    Inter. Cal. 1025 9/20/2016

    Inter. Cal. NIA

    Inter. Cal·. 1048 9/20/2016

    . Final Cal. 1142 . 9/20/2016

    Coupl.mt

    Cal. Batch: 12J066

    Type: Sonotech

    Mfg.: S ONOTECH Wedge Style:

    ----------- Exam Batch: 12J066 Ax. Gain (dB): 60.0 Circ. Gain (dB): N/A Search Unit Cable

    Sonotech 10 Screen Div.= 7.20 in. of Sound Path

    Type: ________ _

    Type: RG-174 - Length: ...£_ No. Conn.: ~ Mfg.: SONOTECH

    Calibration Block Scan Coverage

    Cal. Block No. VGB-33 Upstream-~ Downstream□ Scan dB: 66.0 Reference Block

    Thickness 2.580" Dia.: o · CW ~ CCW ~ Scan dB: 66.0 Serial No.: 05-6533

    Cal. Blk. Temp. 71° Temp. Tool: 1076BGCY I

    Exam Surface: OD Type: SS Rompus Block

    --------Surface Conditioo: Contour Ground

    Axia l Oriented Search Unit

    Calibration Signal Sweep Sound Path Reflector Amplitude% Division

    ID Notch 80% 5.0 3.600"

    Circumferential Oriented Search Unit

    Calibration Signal Sweep Sound Path Reflector Amplitude % Division

    N/A

    Reference/Simulator Block

    Gain Signal Sweep Sound Path dB Reflector Amplitude% Division

    50.0 FSDH 85% 1.5 1.060" ·

    r.

    Comp. Temp. 83° Temp. Tool: 1076BGCY

    Recordable lndication(s): Yes D No ~ Results: NRI ~ RI 0

    (If Yes, Ref. Attacf,ed Ultrasonic Indication Report.)

    Geom O Comments: Search unit #2 of tandem unit SN • 021 N29. Tandem

    wedge SN - 389-078-51C.

    Percent Of Coverage Obtained > 90%:

    Examiner Level U-PDI Fuechlmann, Gary P

    Examiner Level JIJ-PDI

    Popp, Darrell J.

    Other

    N/A

    Level N/A

    UT Calibration/Examination

    No Reviewed Previous Data: N/A

    Date I Reviewer 9/20/2016 w..l-.1J.1:,.,.,J\, f

    Date

    9/20/2016

    Date I ANII Review

    Signawre

    Signature

    ~~

    Date

    ~-Z2-11:, Date

    (. Date

    ~?#~

    I

    I

  • Supplemental Report

    Report No.: UT-16-086

    P~ge: 2 -of 3

    Summary No.: N1.R1 .20.101

    Examiner: -Fu_e_c_h-tm_a_n_n_, -G-ar_y_P_~----L-e-vel: 11-PDI Reviewer: vJ.t. ."jl:i\?M-1-:, f,f,~ fit 4/;l--Date: CJ'l•i/-2· 1i,. Examiner: Popp, Darrell J. er Level: II-POI Site Review: ~fl. ~2iut~ l-v ~ Date: 'f2.V2.df'

    Other: _N_/A _________ _ Level: NIA ANII Review: cM z Date: ?h.?ffe Comments:

    Sketch or Photo:

    ., 3, 3'

    --~-------1-------

    r PrP€ '3. 1."

    Additional - Supplemental Data

  • Report No: UT-16-086

    Summary# N1.R1.20.101

    Pg. 3 of 3

    Prepared by : W . Thomas

    Date: 9/22/2016

    Weld Number

    Thickness

    SW-31

    3.2"

    Weld Width

    Weld Length

    2.5"

    80"

    FLOW

    BRAN

    2 2 I I

    CL

    ~ SN-31

    5 I I

    / PIPE I

    I I

    I I

    EXAMINED 100% OF TI-iE REQUIRED VOLUME AXIAL DIRECTIOO

    NO CIRC EXAM BRANCH SIDE

    45

    Examination Volume Dimensions - Height 1.07" Length 80" Width 3.5"

    Coverage Summary

    Required Scans (each has a weighing factor of 100 for complete coverage)

    ANGLE UpSt-Ax UpSt-Circ DnSt-Ax DnSt-Circ

    45 100% 100% 100% 0%

    Code Coverage Total 75%

    100+100+100+0=300/400=75 * Best Effort Coverage (Max 25%) Total N/A Notes:

    1) Code Coverage refers to the maximum percentage of the required examination volume

    that is effectively examined with the qualified examination procedure.

    2) Best Effort Coverage refers to the required examination volume past the weld

    centerline that is examined in the axial beam direction with an Appendix VIII

    demonstrated procedure for single sided coverage. A. /)e,,tf'IU 4s~~ I.JI/( ,-~}A ·-· ~_/ 'll~!>por,

    ~ ewed

    D Witnessed

  • ~~

    ~~ ;,n, Domirviorf

    Liquid Penetrant Examination

    Sile/Unit: NAPS Procedure: ER-AA-NDE-PT-300 Outage No.: N1R25 -------Suri,mary No. : N1 .R1.20.101 Procedure Rev. : 7 Report No.: PT-16-023 ------------ -------

    Works cope: AUG Work Order No.: 59102983133 Page: 1 of 1

    Code: 2004 Edition Cat./ltem: R-A/R1.20 Location: C-LOOP

    Drawing No.: 11715-WMKS-0109G-2 Description: PIPE-WELDOLET

    System ID: RC ---~----------------==-------------------------.Compo n en I ID: 11715-WMKS-0109G-2 / 29-RC-7 / SW-31

    Limitations: None

    Light Meter Mfg. : N/A Serial No.: N/A

    Temp. Tool Mfg.: AEM0 Instruments Serial No.: 1076BGCY

    Comparator E)lock Temp. : Side A: N/A °F Side B: N/A °F Resolution:

    Lo/Wo Location: N/A Surface Condition:

    Visible~ Cleaner Penetrant Fluorescent 0 Remover

    Brand MAGNAFLUX MAGNAFLUX MAGNAFLUX -

    Type SKC-S SKL-SP2 SKC-S

    Batch No. 15J10K - 12A08K 15J10K

    Time Evap. 3 Min. Dwell 10 Min. Evap. 2 Min.

    Time Exam Started: 0935 Time Exam Completed:

    Indication Loe Loe Diameter Length Type

    No. L w R/L

    NIA

    ---- - - -

    Comments:

    Used flashlight for illumination . Character Resolution Card: DOM-2016-0163.

    Results: NRI ~ RID Eval D N/A Percent Of Coverage Obtained > 90%: N/A Reviewed Previous Data:

    Examiner Level 11 Date

    Shelton, James R. 9/20/2016

    Date viel.{; 9/20/2016 ; 1Ztu,,.,

    Examiner Level 11

    Thompson, Brenton R.

    other Level NIA Dale ANII Review N/A

    Liquid Penetranl Examination

    Mat.fThickness: ss / 3.20"

    Illumination: N/A·

    Surface Temp.: __ 8_3 __ °F

    0.044" Character Card

    Ground

    Developer

    MAGNAFLUX

    SKD-S2

    14K04K

    Develop 10 Min.

    1020

    Remarks

    .. -

    .

    N/A

    Signature Dale

  • Attachment 2

    N2R26 Unit 2 Pressurizer Surge Line Welds Examination Results

    Virginia Electric and Power Company (Dominion Energy Virginia)

    North Anna Power Station Unit 2

    Serial No.: 20-049A Docket No.: 50-339

  • ~Dominion"' Site/Unit:

    UT Calibration/Examination NAPS 2 Procedure: ER-AA-NDE-UT-706 Outage No.: N2R26

    Summary No.: N2.R1.11 .314 Procedure Rev.: Report No.: UT-19 -072

    Workscope: ISi Work Order No.: 59203136641 Page: 1 of

    Code: 2004 Edition Cat./ltem: R-AIR1 .11 Location: \ C-LOOP

    Drawing No.: 12050-WMKS-0109D Description: Weldolet to Elbow \

    System ID: RC \

    Component ID: 12050-WMKS-0109D / 14-RC-410 / 3 Size/Length: 1.30" / 43.75" \

    Limitations: None Start Time: 2239

    Thickness/Diameter:

    Finish Time:

    1.406" I 14.0"

    2254 I

    Instrument Settings Search Unit Cal. Axial Oriented Search Unit Time Date I Serial No.: 140723807 Serial No.: 57 461-52980 Checks Calibration I Signal Sweep Sound Path Manufacturer: Olympus Manufacturer: GE Initial Cal. 2032 3/8/2019 Reflector Amplitude% Division

    Model: EPOCH 600 Linearity: L-16-001 Size: 3.5X10mm Model: MSEB2 Inter. Cal. 2239 3/8/2019 Backwall \ BO 7.0 1.416"

    Delay: 9.851 µs Range: 2.0" Inter. Cal. N/A

    Freq.: 2.0 MHZ Center Freq.: N/A Inter. Cal. 2254 3/8/2019

    M'tl CalNel: 0.2270 in/µs Pulser: Square Exam Angle: o· Squint Angle: N/A Final Cal. 3/8/2019 --- --- 2349 Damping: 4000 Reject: 0% Measured Angle: NIA Mode: Longitudinal -- Couplant Rep. Rate: Auto Freq.: 2.0 Mhz Exit Point N/A # of Elements: 2

    Circum1ferential Oriented Search Unit -- Cal. Batch: 17F0B7 Filter: 0.5 - 4.0 Mode: Ful!wave Config.: Dual Focus: N/A

    I

    Type: Sonotech Calibration I Signal Sweep Voltage: 400 Other: N/A Shape: Round Contour: Flat Reflector Amplitude% Division Mfg.: Sonotech - , Wedge Style: N/A NIA I Exam Batch: 17F0B7

    I Ax. Gain (dB): 38 Circ. Gain (dB}: N/A Search Unit Cable Type: Sonotech I 1 Screen Div."' 0.20 in. of Sound Path Type: RG 174 Length: 6' No. Conn.: ~ Mf . Sonotech -- -- - g .. I

    Calibration Block Scan Coverage I

    Cal. Block No. Part under test Upstream O Downstream~ Scan dB: 50 Reference Block Reference/Simulator Block Gain I Signal Sweep --Thickness 1.406" Dia.: 14.0" cw □ CCWQ ScandB: NIA Serial No. : 08-7832 dB Reflector Amplitude% Division

    Cal. Blk. Temp. 72° Temp. Tool: ATK-2 Exam Surface: OD -- Type: 2.0" SS Step Wedge 38 1.0 I 80 5 --

    2.0 I Comp. Temp. so· Temp. Tool: ATK-2 Surface Condition: Smooth 38 45 10 --Recordable lndication(s).

    Results: NRI ~ □

    RI 0 0~ (If Yes, Ref. Attached Ultrasonic Indication Report.)

    Geom D

    I Comments: Lamination Scan. I

    See UT-19-073 for angle beam inspection.

    Percent Of Coverage Obtained > 90%:

    Examiner Level 11-PDI

    Wertman, Justin

    Examiner

    NIA

    Other

    NIA

    Level NIA

    Level NIA

    UT Calibration/Examination

    Yes Reviewed Previous Data: NIA

    Signature

    Date

    318/2018

    l

    ZJJ/2 ·- -~

    Sound Path

    Sound Path

    1.00"

    2.00"

    Date

    .3,/D•t.if

  • ~ UT Calibration/Examination

    .,;,J►tDominion' Site/Unit: NAPS 2 Procedure: ER-AA-NDE-UT-802 Outage No.: N2R26 Summary No.: N2.R1 .11.314 Procedure Rev.: 5 Report No.: UT-19 -073

    Workscope: ISi Work Order No.: 59203136641 Page: 1 of 5

    Code: 2004 Edition Cat./ltem: R-A/R1 .11 Location: \ C-LOOP

    Drawing No.: 12050-WMKS·0109D Description: Weldolet to Elbow \

    System ID: RC \

    Component ID: 12050-WMKS-0109D / 14-RC-410 / 3 Size/Length: 1.25" / 44.0" \

    Limitations: Single sided due to weld-o-let. See attached Start Time: 1258

    Thickness/Diameter: 1.406" / 14.0"

    1313 Finish Time:

    Instrument Settings Search Unit Cal. ..a!xial Oriented Search Unit Time Date Serial No.: 140723807 Serial No. : 01CXBL Checks

    I

    Initial Cal. Calibration \ Signal Sweep Sound Path Manufacturer: Olympus Manufacturer: KBA 1015 3/9/2019 Reflector Amplitude% Division

    Model: EPOCH 600 Linearity: L-19 -001 Size: 0.5" Model: Comp-G Inter. Cal. ' 1258 3/9/2019 1.50" Notch 1 80 5.3 2.11" Delay: 6.611 Range: 4.00 Freq.: 2.25 MHZ Center Freq.: N/A Inter. Cal. ' N/A

    M'tl CalNel: 0.1230 Pulser: Square Inter. Cal. 1313 3/9/2019 Exam Angle: 45 Squint Angle: N/A Damping: 400 Reject: 0 --- --- Final Cal. 1559 3/9/2019 Measured Angle: 45 Mode: Shear Rep. Rate: Auto Freq.: 2.25 -- Couplant

    Exit Point 0.20 # of Elements: 1 Circurriferential Oriented Search Unit Filter: 0.5-4.0 Mode: FW -- Cal. Batch: 17F087

    Config.: Single Focus: N/A Voltage: 400 Other: NIA Type: Sonotech Calibration \ Signal Sweep Shape: Round Contour: Flat Reflector Amplitude% Division Sound Path Mfg.: Sonotech

    Wedge Style: MSWQC N/A I Ax. Gain (dB): 13.0 Circ. Gain (dB): N/A Exam Batch: 17F087 I 10 Search Unit Cable Screen Div. = 4.00 in. of Sound Path Type: Sonotech \ -- -- Type: RG 174 Length: 6 No. Conn.: o - - Mfg.: Sonotech I Calibration Block Scan Coverage

    Cal. Block No. 05-8514 Reference Block Reference/Simulator Block

    Thickness 2.25" Dia.: 0 Upstream O Downstream@ Scan dB: 25.0

    Gain I Signal Sweep CW@ CCW@ Scan dB: · 25.0 Serial No.: 05-6533 dB Reflectqr Amplitude% Division Sound Path Cal. Blk. Temp. 71 Temp. Tool: ATK-2 Type: SS Rompus Block S□HI -- Exam Surface: OD 13.0 22 2.6 1.054 Comp. Temp. 86 Temp. Tool: ATK-2 I -- Surface Condition: Ground Smooth Recordable lndication(s): Yes O No@ (If Yes, Ref. Attached Ultrasonic Indication Report.) I Results: NRI@ RID Geom O Comments: None

    Percent Of Coverage Obtained > 90%: No Reviewed Previous Data: N/A

    Examiner Level 11r,01 Signature Date Reviewer w.!II-- ~ Date

    Johnson, Jeffrey M. """ j

    3/9/2019 v..}L~OMA, S s~10-1t.t I/ Examiner Level t< ~ ~ ~ Signature Date ~e Rev/4ewP.Stt wu ~f\1,. 51 J~\ure rv-i , ) ¥~~ate Zollner, Brian D

    _a. ~ • 3/9/2019 kJNlS • 1r,Lr 4.u{) ..: .. ...... µ..~ ('i Other Level I C Signature Date ANII Review d~

    - Date NIA N/A 3~~9

    UT Calibration/Examination

  • ,~ . . Dom1n1on' Site/Unit: NAPS

    UT Calibration/Examination 2 Procedure: ER-AA-NDE-UT-802 Outage No. : N2R26

    Summary No.: N2.R1.11.314 Procedure Rev.: 5 Report No.: UT-19 -073

    Workscope: 151 Work Order No.: 59203136641 Page: 2 of 5

    Code: 2004 Edition Cal./ltem : R-A/R1.11 Location: C-LOOP

    Drawing No.: 12050-WMKS-01090 Description: Weldolet to Elbow

    System ID: RC

    ------------------------------------------------+---------------Component ID: 12050-WMKS-01090 / 14-RC-410 / 3 Size/Length: 1.25" / 44.0" 1 Thickness/Diameter: Limitations: Single sided due to weld-o-let. See attached. Start Time: 131f Finish Time:

    1.406" / 14.0"

    1328

    Instrument Settings Search Unit Cal. Time Date kial Oriented Search Unit I Serial No.: 140723807 Serial No.: 00F1DL Checks Calibration \ Signal Sweep Sound Path Manufacturer: Olympus Manufacturer: KBA Initial Cal. 1034 3/9/2019 Reflector Amplitude% Division

    Model: EPOCH 600 Linearity: L-19 -001 Size: 0.50" Model: Comp-G Inter. Cal. 1314 3/9/2019 1.50" Notch ' 80 5.3 2.634 Delay: 8.311 Range: 5.00 Freq.: 2.25 MHZ Center Freq.: N/A Inter. Cal. N/A

    Inter. Cal. 1328 3/9/2019 M'II CalNel: 0.1230 Pulser: Square Exam Angle: 60 Squint Angle: N/A --- --- Final Cal. 1601 3(9(2019 Damping: 400 Reject: 0 Measured Angle: 60 Mode: Shear -- Couplant Rep. Rate: Auto Freq.: 2.25 Exit Point 0.30 # of Elements: 1 Circum

    1ferential Oriented Search Unit Mode: FW - - Cal. Batch: 17F087 Filter: 0.5-4.0 Config.: Single Focus: NIA I

    Voltage: 400 Other: N/A Type: Sonotech Calibration I Signal Sweep Sound Path Shape: Round Contour: Flat Reflector Amplitude% Division Mfg.: Sonotech Wedge Style: MSWQC NIA l

    Ax. Gain (dB): 30.0 Gire. Gain (dB): N/A Exam Batch: 17F087 I Search Unit Cable 5.00 in. of Sound Path Length: No. Conn.: o Type: Sonotech I 10 Screen Div. = Type: RG 174 6 -- -- - - Mfg.: Sonotech I Calibration Block Scan Coverage

    Reference/Simulator Block Cal. Block No. 05-8514 Upstream O Downstream~ Scan dB: 42.0 Reference Block Gain l Signal Sweep Sound Path Thickness 2.25" Dia.: 0 CW~ CCW ~ Scan dB: 42.0 Serial No.: 05-6533 dB Reflectqr Amplitude% Division

    Cal. Blk. Temp. 71 Temp. Tool: ATK-2 Exam Surface: OD Type: SS Rompus Block 30.0 FSDHI 75 2.9 1.483 --

    Comp. Temp. 86 Temp. Tool: ATK-2 Surface Condition: Ground Smooth I --

    Recordable lndication(s): Yes D No~ /If Yes. Ref. Attached Ultrasonic Indication Reoort.\ I Results: NRI ~ RI 0 Geom O Comments: Effective coverage uking the 60 Deg search unit has

    been verified by the bresence of the weld root response Percent Of Coverage Obtained > 90%:

    Examiner Level

    Johnson, Jeffrey M.

    Examiner Level

    Zollner, Brian D

    Other

    N/A

    Level

    UT Calibration/Examination

    No Reviewed Previous Data:

    Signature

    N/A during the required ~cans.

    Date I Reviewer Lt,""'\J~

    Date I ANII Review

    J'/~

    Date

    3,Jo.,;r=, -...J f Date q~ >O("r

    Date

  • ,Dominion"' Site/Unit: NAPS

    UT Calibration/Examination 2 Procedure: ER-AA-NDE-UT -802 Outage No. : N2R26

    Summary No.: N2.R1 .11 .314 Procedure Rev.: 5 Report No.: UT-19 -073

    Workscope: ISi Work Order No. : 59203136641 Page: 3 of 5

    Code: 2004 Edition Cat./ltem: R-A/R1 .11 Location: C-LOOP

    Drawing No.: 12050-WMKS-0109O Description: Weldolet to Elbow \

    System ID: RC \

    Component ID: 12050-WMKS-0109O/14-RC-41013 Size/Length: 1.25" / 44.0" \

    Limitations: Single sided due to weld-o-let. See attached

    Thickness/Diameter: 1.406" / 14.0"

    1350 Start Time: 1342 Finish Time: I

    Instrument Settings Search Unit Cal. Date .kcial Oriented Search Unit . Time I Serial No. : 140723807 Serial No.: 06-109 Checks Calibration I Signal Sweep Sound Path Manufacturer: Olympus Manufacturer: RTD Initial Cal. 1105 3/912019 Reflector Amplitude% Division

    Model: EPOCH 600 Linearity: L-19 -001 Size: 2(15X25) Model: TRL2-AUST Inter. Cal. 1342 319/2019 1.50" Notch I 80 5.0 2.669 Range: 5.700 Center Freq.: NIA Inter. Cal. NIA I ' Delay: 10.211 Freq. : 2.0 MHZ

    Inter. Cal. 1350 31912019 I M'tl CalNel: 0.2320 Pulser: Square Exam Angle: 60 Squint Angle: NIA --- --- Final Cal. 1604 3/9/2019 Damping: 400 Reject: 0 Measured Angle: 61 Mode: Longitudinal -- Couplant Rep. Rate: Auto Freq.: 2.0 Exit Point .75 # of Elements: 2

    Circu~ferential Oriented Search Unit Filter: 0.5-4.0 Mode: FW -- Cal. Batch: 17F087 Config.: D-SBS Focus: FD.1.3" Voltage: 400 Other: NIA Type: Sonotech Calibration Signal Sweep Sound Path Shape: Retangular Contour: FLAT Reflector Amplitude% Division Mfg.: Sonotech

    Wedge Style: Integral NIA Ax. Gain (dB): 54.0 Circ. Gain (dB): N/A Exam Batch: 17F087

    I Search Unit Cable 5.70 Sound Path No. Conn.: O

    Type: Sonotech I 10 Screen Div. = in. of Type: RG 174 Length: 6 -- -- - - Mfg.: Sonotech I Calibration Block Scan Coverage Cal. Block No. 05-8514 Upstream 0 Downstream O Scan dB: 60.0 Reference Block R~,ferencelSimulator Block

    Gain I Signal Sweep Sound Path Thickness 2.25" Dia.: 0 cwo CCW O Scan dB: NIA Serial No.: 05-6533 dB Reflector Amplitude% Division Cal. Blk. Temp. 71 Temp. Tool: ATK-2

    Exam Surface: OD Type: SS Rompus Block 48.0 FSDH\ 45 2.7 1.556 --Comp. Temp. 86 Temp. Tool: ATK-2

    Surface Condition: Ground Smooth I --Recordable lndication(s}: Yes O No0 (If Yes, Ref. Attached Ultrasonic Indication Report.) I Results: NRI 0 RID Geom O Comments: None.

    Percent Of Coverage Obtained > 90%:

    Examiner Level 11-PDI Johnson, Jeffrey M.

    Examiner Level

    Zollner, Brian D

    Other

    NIA

    Level

    UT Calibration/Examination

    No Reviewed Previous Data:

    Signature

    NIA

    Date

    3/9/2019

    Date

    3/9/2019

    Date ANII Review

    '; ~~7 ~

    Date

    J/ ZJ 4)

  • ,Dominion·

    Summary No.: N2.R1 .11.314

    Examiner: Johnson, Jeffrey M.

    Examiner: Zollner, Brian D

    Other: _N....;/.;...A;._, ____________ _

    Comments:

    Sketch or Photo:

    ,.

    Supplemental Report Report No.: UT-19 -073

    Page: 4 of 5

    t..e;J,:JJC' \ Level: 11-PDI Reviewer:

    Level : 11-PDI Site Review: _.,,'3':'.f-'-',. '-"c ... •-u:..--;-,-...

  • • • Report No: UT-19-073

    Summary# N2.R1.11.314 , Dom1n1on

    Pg. 5 of 5 ~, _ t 1A Prepared by: W. Thomas7~

    Weld Number

    Thickness

    3

    1.283"

    Date: 3/10/2019

    Weld Width

    Weld Length

    FLOW

    60L 3

    ----~---,--~--WELDCl.ET \ ELBOW

    - ~

  • ,Dominion'

    Liquid Penetrant Examination

    Site/Unit: · NAPS 2 Procedure: ER-AA-NDE-PT-300 Outage No.: N2R26 ------Summary No.: N2.R1.11.314 Procedure Rev. : 7 Report No.: PT-19 -012 ------------

    Workscope: AUG Work Order No.: 59203136641 Page: 1 of 1

    Code: 2004 Edition Cat./ltem: R-A/R1 .11 Location: C-LOOP ------Drawing No.: 12050-WMKS-0109D Description: WELDOLET-TO-ELBOW

    System ID: ~R:C~:-;:~-:;::;:;:--;-:~:=:-::::::===================~~~==--JSS~·t,f=;-':=•'/(!!-~~~"--ComQonent ID: 12050~WMKS-0~090-/-14•RG=4t0·/-3 Mat/Thickness: 140G" f 1416

    ---Li-m-itations: None . . ~1'

    Light Meter Mfg.: N/A Serial No.: NIA

    Temp. Tool Mfg.: ATKINS Serial No. : ATK-2

    Comparator Block Temp.: Side A: N/A °F Side B: N/A °F Resolution:

    Lo/Wo Location: TDC I Weld Center Line Surface Condition:

    Illumination: N/A

    Surface Temp.: __ 8_0 __ °F

    0.044" Character Card

    Ground Smooth ---------------Visible~

    Cleaner Penetrant Fluorescent 0 Remover

    Brand MAGNAFLUX

    Type SKC-S

    Batch No. 18C21K

    Time Evap. 3 Min Dwell

    Time Exam Started: 2151

    Indication Loe Loe Diameter Length

    No. L w

    NRI

    Comments:

    DOM-2016-0156 Flashlight used to resolve character card

    Results: NRI ~ RI 0 Percent Of Coverage Obtained > 90%:

    Examiner Level

    Flood, Steven

    Examiner

    N/A

    Other

    N/A

    Level N/A

    Level N/A

    Liquid Penetrant Examination

    Signature

    Signature

    MAGNAFLUX MAGNAFLUX

    SKL-SP2 SKC-S

    15J02K 18C21K

    10 Min Evap. 1 Min

    Time Exam Completed:

    Type

    R/L

    -

    ...

    Eval □ NIA Yes Reviewed Previous Data:

    Date Reviewer

    3/8/2019 N/A

    Date Site Review

    3/8/2019 Dennis Strickland lv II

    Date ANII Review

    fl N

    Developer

    MAGNAFLUX

    SKD-S2

    14K04K

    Develop 10 Min

    2225

    Remarks

    NIA

    Signature Date

    Date

    3/18/2019

    Date

  • ~ 6Dominion' Site/Unit: NAPS

    UT Calibration/Examination

    2 Procedure: ER-AA-NDE-UT-700 Outage No.: N2R26

    Summary No.: N2.R1 .20.0404 Procedure Rev.: 0 Report No.: UT-19 -017

    Workscope: AUG Work Order No.: 59203136641 Page: of 2

    Code: 2004 Edition Cat./ltem: R-A/R1.20 I

    Location: ~-LOOP

    Drawing No.: 12050-WMKS-0109G-2 Description: Pipe to Branch Connection weld

    System ID: RC

    Component ID: 12050-WMKS-0109G-2 / 29-RC-407 / SW-36

    Limitations: 1

    Adjacent loop stop valve. See attached.

    Size/Length: 2.2" I 50"

    Start Time:

    Thic'kness/Diameter:

    1352 .I Finish Time:

    2.58" /29"

    1410

    Instrument Settings Search Unit Cal. I

    Time Date Axial Oriented Search Unit Serial No. : 140723807 Serial No.: 97-733 Checks

    I

    Calibration Signal Sweep Manufacturer: Olympus Manufacturer: RTD Initial Cal. 0930 3/9/2019 Reflector Ampli~ude % Division

    Sound Path

    Model: EPOCH 600 Linearity: L-19 -001 Size: 2(20X34) Model: TRL 1-AUST Inter. Cal. 1352 3/9/2019 ID Notch 80 5.3 3.760" Delay: 12.811 Range: 7.200 Freq.: 1.0 MHZ Center Freq.: NIA Inter. Cal. I M'tl CalNel: 0.2320 Pulser: Square Inter. Cal. 1410 3/9/2019 I Exam Angle: 45 Squint Angle: SAS Damping: 400 Reject: 0 --- --- Final Cal. 1610 3/9/2019 I Measured Angle: 45 Mode: Long

    I Rep. Rate: Auto Freq.: 1.0 -- Couplant Exit Point 0.9 # of Elements: 2

    Circumferentikt Oriented Search Unit Filter: .2 -10 Mode: Dual -- Cal. Batch: 17F087 Config .: Dual Focus: FS-80 I

    Voltage: 400 Other: NIA Type: Sonotech Calibration Signal Sweep Shape: Rect. Contour: Flat Reflector Ampli~ude % Division Sound Path Mfg.: Sonotech Wedge Style: Integral ID Notch

    I 4.260" Ax. Gain (dB}: Circ. Gain (dB): 8,0 5.8 68.0 NIA Exam Batch: 17F087 I Search Unit Cable

    10 Screen Div. = 7.20 in. of Sound Path Type: Sonotech I -- -- Type: RG 174 Length: 6 No. Conn.: O - - Mfg.: Sonotech I Calibration Block Scan Coverage Cal. Block No. VGB-33

    Upstream ~ Downstream O Scan dB: 74 Reference Block Referenc~/Simulator Block Thickness 2.580" Dia.: 0 -- Gain Signal Sweep Sound Path cw~ CCW~ ScandB: · 74 Serial No.: 05-6533 dB Reflector Amplitude% Division Cal. Blk. Temp. 71 Temp. Tool: ATK-2 Type: SS Rompus Block I 20 -- Exam Surface: OD 50.0 FSDH 1.4 1.05" Comp. Temp. 86 Temp. Tool: ATK-2 I -- Surface Condition: Ground Smooth Recordable lndication(s): Yes O No~ (If Yes, Ref. Attached Ultrasonic Indication Report.) I Resulls: NRI ~ RI 0 Geom O Comments: None

    Percent Of Coverage Obtained> 90%: No Reviewed Previous Data: Yes

    Examiner Level 1-PDI Signature Date Reviewer 1£,14' ~LJ ~111/z:~~ Johnson, Jeffrey M. 'L-v i-,.,-- 3/9/2019 W l. :,C:,o.,,.AA Examiner Level G I-POI R:..~ Signature Date Sile Review ~x • Date Zollner, Brian D 3/9/2019 ~ex:/e_~ Lv~ ;;,- "./' ./. I i 1~1.1,.,, Other Level N/A - !·o Signature Date ANII Review ;if A 1..----"' Signat6re I Date N/A UT Calibration/Examination

    I

  • ftD .. ~,- om1n1on Report No: UT-19-017

    Summary# N2.R1.20.0404

    Pg. 2 of 2

    Prepared by: W. Thomas .f{l' t..~ll r:a:: Date: 3/11/2019 ~~v~

    Weld Number

    Thickness

    SW-36 Weld Width 2S!' T ~ 2.58"

    I BRANCll COHN.

    I I I I L

    Weld Length

    S1!-36

    45

    PIPE

    • 86- HEIGHT X 3. Z- 1110TH = 2. 75 SO. IN X 50- LENGTH = 137. 5 CU. IN = REQUI RED VOLUIIE

    ~ u,~ ,.~ w.'""' "ff "''"""'" ,,. •~ ~ m ~ •-•

    .. OM"" o. ,o ~ '" ~ ''"""'" "'mo, o,e E ~ '""" NO EXAM AX OR CI RC FOR 25S OF THE WELD LENGTH

    Examination Volume Dimensions -

    DUE TO LOOP SIOP VAVE

    CIRC EXAII LIMITED TO 30% COVERNJE FOR 75~ OF THE WELD LENO Tlt

    DUE TO WELD TAPER

    Height 0.86" Length 50"

    Coverage Summary

    Width

    Required Scans (each has a weighing factor of 100 for complete coverage)!

    ANGLE AXIAL I CIRC 45 64% I 22.5%

    Code Coverage Total I 64+22.5=86.5/200=.4325 * Best Effort Coverage (Max 25%) Total I Notes:

    50"

    3.2"

    43.25%

    N/A

    1) Code Coverage refers to the maximum percentage of the required examination volume

    that is effectively examined with the qualified examination procedure.

    2) Best Effort Coverage refers to the required examination volume past the weld

    centerline that is examined in the axial beam direction with an Appendix VIII

    demonstrated procedure for single sided coverage.

  • Liquid Penetrant Examination

    Site/Unit: NAPS 2 Procedure: ER-AA•N DE-PT-300 Outage No.: N2R26 ------Summary No.: N2.R1 .20.0404 Procedure Rev.: 7 Report No.: PT-19 -013 ------

    Workscope: AUG Work Order No. : 59203136641 Page: 1 of 1

    Code: 2004 Edition Cat./ltem: R-A/R1.20 Location: C-LOOP

    ___ D_ra_w_ing No.: 12P_50-WMKS.:0.:1.09.G=~---Descriplion; -Pipe-to-Branch-Gonnection·weld--------~-:-3=-/ul ,.,,--System ID: RC ,,

    Component ID: 12050-WMKS-0109G-2 / 29-RC-407 / SW-36

    Limitations: None

    Light Meter Mfg.: N/A Serial No.: NIA

    Temp. Tool Mfg.: ATKINS Serial No.: ATK-2

    Comparator Block Temp.: Side A: N/A °F Side B: N/A °F Resolution:

    Lo/Wo Location: TDC I Weld Center Line Surface Condition:

    Visible~ Cleaner Penetrant Fluorescent 0 Remover

    Brand MAGNAFLUX MAGNAFLUX

    Type SKC-S SKL-SP2

    Batch No. 18C21K 15J02K

    Time Evap. 3 Dwell 10

    Time Exam Started: 2151

    Indication Loe Loe Diameter Length Type

    No. L w R/L

    NRI

    Comments: DOM-2016-0156 Flashlight used to resolve character card

    Results : NRI ~ RI 0 Percent Of Coverage Obtained > 90%:

    Eval O ~ Yes

    Examiner Level II Date Flood, Steven 3/8/2019

    Examiner Level N/A Signature Date N/A 3/8/2019

    Other Level N/A Signature ... Date N/A

    Liquid Penetrant Examination

    MAGNAFLUX

    SKC-S

    18C21K

    Evap. 1

    Time Exam Completed:

    N/A

    Reviewed Previous Data:

    Reviewer , ,,. L---~ u:;..v-.µi.

    Mat/Thickness: SS/4-,400!.l.

    Illumination: N/A --------Surface Temp.: __ 8_0 __ °F

    Not Used

    Ground Smooth

    Developer

    MAGNAFLUX

    SKD-S2

    14K04K

    Develop 10

    2225

    Remarks

    N/A