© Energex Limited 2014
ABN 40 078 849 055
MANUAL 00305
Underground Distribution Construction
Manual
Section E5 – LV Joints and Terminations
Approved by: A Smith - de Perez
Uncontrolled Document When Printed
ELECTRICAL
SECTION E5 - LV JOINTS AND TERMINATIONS
Sub-Sect. Description Sheets
GENERAL
1.1 Selection Matrix 101.2 Overhead to Underground Service 2
JOINTS
2.1 Heatshrink (Straight PLY) 12.2 Heatshrink (Straight 3.5/4C Belted Paper) 22.3 Heatshrink (Straight 16 4C XLPE) 12.4 Repair Compound Box - 16 4C XLPE Cu 12.5 Heatshrink (Transition) 32.6 Parallel (3.5C PLYSWPVC 185) 22.7 Parallel (Branch) 22.8 Heatshrink (Live End) 22.9 Heatshrink (Tee) 4
TERMINATIONS
3.1 Heatshrink 16 4C Cu (Pole) 13.2 Heatshrink 16 4C Cu (Pole/Bridging) 33.3 120 & 240 sqmm 4C (Pole) 33.4 25, 70 & 185 sqmm (Pole) 53.5 185 sqmm 4C Al. (Pole) 13.6 LV Cubicle 120, 185 & 240 sqmm (PMT) 13.7 Supply Service Pit 1
Sub-Sect. Description Sheets
PILOT CABLE JOINTS
4.1 Straight - Resin Filled Body - 20 Pair 2
PILLARS
5.1 Construction - One Way (240 4C XLPE) 25.2 Construction - Two Way (240 4C XLPE) 25.3 Construction - Three Way (240 4C XLPE) 25.4 Construction - Four Way (240 4C XLPE) 25.5 Construction - Cross Road (4C cables) 15.6 Stripping Details 15.7 C & I use up to 200A. 45.8 Service Panel Fuse Details 45.9 Indoor Service Term. (4C 185 & 240sqmm) 25.10 Indoor Service Term. (4C 16, 25 & 70 Cu 2
& 35 to 120 Al)5.11 Large Commercial Industrial Sevices Pillar 1
with 14 fuse Panel5.12 AFLC Filter Pillars 25.13 LV Joints & Terms 2 + 1
2 Way Link Pillar 15.14 LV Joints & Terms 3 Way Link Pillar 15.15 LV Disconnect Box 2 & 4 Way 1
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 1 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV CABLE STRAIGHT & TRANSITION JOINTS
Conductor Size & Cable Type
Conductor Size &
Cable Type
16 Cu 4/c
XLPE/
PVC
25 Cu
PLY
25 Cu 4c
XLPE/
PVC
70 Cu
PLY
70 Cu 4c
XLPE/
PVC
/HDPE
185 Cu
PLY
185 Cu
XLPE/SWA
/HDPE
120 Al 4/c
XLPE/
PVC
240 Al 4/c
XLPE/PVC
300 Cu 1c
XLPE/PVC
300 Cu
XLPE/
SWA/
HDPE
300 Cu 1c
XLPE/PVC & SWS
22171 355
LJSC30PC18D
22172 356
LJSC30XC18D
22173 357
LJSC30XA24D
22174 358
LJSC30SC30D
22175 359
LJXC30SC30D
300 Cu
XLPE/SWA/HDPE
22176 360
LJXC30PC18D
22177 361
LJXC30XC18D
22178 362
LJXC30XA24D
22179 363
LJXC30XC30D
300 Al PLYPVC &
SWS
22180 364
LJPA30XC70D
22181 365
LJPA30XC18D
20440 366
LJPA30XA24D
22182 367
LJPA30SC30D
22183 368
LJPA30XC30D
258 Al PLYPVC &
SWS
22184 369
LJPA25XC70D
22185 370
LJPA25XC18D
20510 371
LVXNJ240/258
22186 372
LJXA25SC30D
22187 373
LJPA25XC30D
240 Al XLPE 3/c
N/S
22188 374
LJXA24XC25
20511 375
LVXNJ123/185
20512 376
LVJ185SWA243
20513 377
LVJ3240/4120
17711 378
LVJ240A1; LVJ4C240/120
22189 379
LJXA24SC30D
22190 380
LJXA24XC30D
240 Al XLPE 4/c ` 22191 381
LJXA24PC70D
22192 382
LJXA24XC25D
16457 383
EXJNT9MAT; LVXNJ120/185
20521 384
EXJNT7MAT; LVJ185SWA244
20515 385
LJXA24XA12D
17711 386
LVJ240A1; LVJ4C240/120
185 Cu PLYHDPE
& SWS
22193 387
LJPC18XC16D
22194 388
LJPC18PC25D
22195 389
LJPC18XC25D
22196 390
LJPC18PC70D
22197 391
LJPC18XC70D
16456 392
LVHSJ185; LVHSJ185L;
16457 393
EXJNT9MAT; LVXNJ120/185
22198 395
LJPC18SC30D
LEGEND XXXXX
xxx xxxxxxxx
STOCK CODE CONTRACT 09011 ITEM No. COMPATIBLE UNIT
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 2 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV CABLE STRAIGHT & TRANSITION JOINTS (CONTINUED)
Conductor Size & Cable Type
Conductor Size &
Cable Type
16 Cu
4/c
XLPE/
PVC
25 Cu
PLY
25 Cu
4c
XLPE/
PVC
70 Cu
PLY
70 Cu 4c
XLPE/
PVC
/HDPE
185 Cu
PLY
185 Cu
XLPE/
SWA
/HDPE
120 Al 4/c
XLPE/PVC
240 Al 4/c
XLPE/
PVC
300 Cu 1c
XLPE/
PVC
300 Cu
XLPE/
SWA/
HDPE
185 Cu
XLPE/SWA/HDPE
20517 396
LJXC18PC70D
22199 397
LJXC18XC70D
20518 398
EXJNT6MAT
20519 399
LVJ185SWA
20520 400
LVJ120/185
161 Cu PLYSWS 22200 401
LJPC61XC70D
16456 402
LVHSJ185; LVHSJ185/70; LVHSJ185/70L;
LVHSJ185L; LVHSJ70; LVHSJ70L;
20523 403
LVXNJ185/161
16457 404
EXJNT9MAT; LVXNJ120/185
16457 405
EXJNT9MAT; LVXNJ120/185
22201 406
LJPA15XC30D
150 Al PLYPVC &
SWS 22202
407
LJPA15XC70D
20526
408 LVXNJ120/150
129 Al CONSAC 20527 409
LJCA29PC70D
22203 410
LJCA29XC70D
20448 411
LVXNJ120/12C
129 Al PVC & SWS
4/c
16456 412
LVHSJ185; LVHSJ185/70; LVHSJ185/70L;
LVHSJ185L; LVHSJ70; LVHSJ70L
22204 413
LJPA29XC70D
20450 414
LVXNJ120/12P
120 Al XLPE 3/C +
N/S
20451 415
LVXNJ1203/70
22205 416
LJNA12XC70D
20452 417
LVJ1204C/3NS
LEGEND XXXXX
xxx xxxxxxxx
STOCK CODE CONTRACT 09011 ITEM No. COMPATIBLE UNIT
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 3 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV CABLE STRAIGHT & TRANSITION JOINTS (CONTINUED)
Conductor Size & Cable Type Conductor Size &
Cable Type
16 Cu 4/c
XLPE/PVC
25 Cu
PLY
25 Cu 4c
XLPE/PVC
70 Cu
PLY
70 Cu 4c
XLPE/PVC
/HDPE
185
Cu
PLY
185
Cu
XLPE/
SWA
/HDPE
120 Al
4c XLPE/
PVC
240 Al
4c
XLPE/
PVC
300 Cu
1c
XLPE/
PVC
300 Cu
XLPE/
SWA/
HDPE
120 Al XLPE 4/c 22206 418
LJXA12XC16D
22207 419
LJXA12PC25D
22208 420
LJXA12XC25D
20453 421
LVXNJ120/70
22209 422
LJXA12XC70D
22210 423
LJXNA12XA12D
70 Cu PLYHDPE &
SWS
16456 424
LVHSJ70; LVHSJ70L
70 Cu 4c
XLPE/PVC/HDPE
22211 425
LJPC70XC70D
22212 426
LJXC70XC70D
35 Al CONSAC 22213 427
LJCA35XC16D
20530 428
LVXNJ25/35
22214 429
LJCA35XC25D
25 Cu PLYHDPE &
SWS
22215 430
LJPC25XC16D
20457 431
LJPC25PC25D
25 Cu 4c XLPE/PVC 22216 432
LJXC25XC16D
22217 433
LJXC25PC25D
22218 434
LJXC25XC25D
22219 435
LJXC25PC70D
22220 436
LJXC25XC70D
16 Cu PLYSWS 20458 437
LVXNJ16/16
22221 438
LJPC16PC25D
22222 439
LJPC16XC25D
22223 440
LJPC16XC70D
16 Cu 4c XLPE/PVC 20531 441
LJXC16XC16D
22224 442
LJXC16PC25D
LEGEND XXXXX
xxx xxxxxxxx
STOCK CODE CONTRACT 09011 ITEM No. COMPATIBLE UNIT
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 4 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV SERVICE TEE JOINTS (HEAT SHRINK TYPE)
Main Cable Service Tee Cable
LEGEND
120/240 mm2 Al XLPE/PVC 16/70 mm
2 Cu XLPE or PLY 17715
443 LVHSJ240T16; LVHSJ240T25; LVHSJ240T70; LVPBJ4C240
XXXXX xxx
xxxxxxxx
STOCK CODE CONTRACT 09011 ITEM No. COMPATIBLE UNIT
185 mm2 Cu PLYHDPE & SWS 16/70 mm
2 Cu XLPE or PLY 17714
444 LVHSJ185T16; LVHSJ185T25; LVHSJ185T70;
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 5 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV RE-ENTERABLE SERVICE TEE JOINTS (RESIN TYPE)
Main Cable Service Tee Cable
LEGEND
120/240 mm2 Al XLPE/HDPE 16/70 mm
2 Cu XLPE or PLY, or
240 mm2 Al XLPE, or
185 mm2 Cu PLY, or
185 mm2 Cu XLPE/SWA/HDPE,
21406 447 1x4L
EXJNT8MAT LVJ240T240
XXXXX xxx
xxxxxx xxxxxxxx
STOCK CODE CONTRACT 09011 ITEM No. No. OF BUCKETS OF RESIN REQUIRED COMPATIBLE UNIT
185 mm2 Cu PLYHDPE
&SWS
16/70 mm2 Cu XLPE or PLY, or
240 mm2 Al XLPE, or
185 mm2 Cu PLY, or
185 mm2 Cu XLPE/SWA/HDPE
21406 448 1x4L
EXJNT8MAT LVJ240T240
185 mm2 Cu
XLPE/SWA/HDPE
16/70 mm2 Cu XLPE or PLY, or
240 mm2 Al XLPE, or
185 mm2 Cu PLY, or
185 mm2 Cu XLPE/SWA/HDPE
21406 449 1x4L
EXJNT8MAT LVJ240T240
300 mm2 Cu
XLPE/SWA/HDPE
70 mm2 Cu XLPE or PLY, or
240 mm2 Al XLPE, or
185 mm2 Cu PLY, or
185 mm2 Cu XLPE/SWA/HDPE, or
300 mm2 Cu XLPE/SWA/HDPE
22239 450 1x4L
LVJ300T300
RE-ENTERABLE RESIN
COMPOUND
STOCK CODE
4.0 Litres 21407
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 6 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV PARALLEL BRANCH JOINTS (RESIN TYPE)
Branch Cable
Main Cable (may be
joined)
16 mm2
Cu XLPE
or PLY
70 mm2 Cu
XLPE or
PLY
120 mm2 Al
XLPE/PVC
185 mm2
Cu
PLYHDPE
& SWS
185 mm2
Cu
XLPE/SWA
/HDPE
240 mm2 Al
XLPE/PVC
300 mm2
Cu
XLPE/SWA
/HDPE
LEGEND
120 mm2 Al
XLPE/PVC
21406 451
4x7.5L LVCAV5CAV
6
21406 451
4x7.5L LVCAV5CAV6
21406 452
4x7.5L LVCAV5CAV6
XXXXX xxx
xxxxxx xxxxxxxx
STOCK CODE CONTRACT 09011 ITEM No. No. OF BUCKETS OF RESIN COMPATIBLE UNIT
240 mm2 Al
XLPE/PVC
21406 453
4x7.5L LVCAV5CAV
6
21406 453
4x7.5L LVCAV5CAV6
21406 454
4x7.5L LVCAV5CAV6
21406 456
4x7.5L LVCAV5CAV6
21406 457
4x7.5L LVCAV5CAV6
21406 455
4x7.5L LVCAV5CAV6
185 mm2 Cu
PLYHDPE & SWS
21406 458
4x7.5L LVCAV5CAV
6
21406 458
4x7.5L LVCAV5CAV6
21406
459 4x7.5L
LVCAV5CAV6
21406 460
4x7.5L LVCAV5CAV6
21406 461
4x7.5L LVCAV5CAV6
185 mm2 Cu
XLPE/SWA/HDPE
21406 462
4x7.5L LVCAV5CAV
6
21406 462
4x7.5L LVCAV5CAV6
21406
463 4x7.5L
LVCAV5CAV6
21406 464
4x7.5L LVCAV5CAV6
21406 465
4x7.5L LVCAV5CAV6
300 mm2 Cu
XLPE/SWA/HDPE
22240 466
5x7.5L
LVC30CAV6
22240
467
5x7.5L
LVC30CAV6
22240 468
5x7.5L
LVC30CAV6
22240 469
5x7.5L
LVC30CAV6
22240 470
5x7.5L
LVC30CAV6
NON RE-ENTERABLE RESIN
COMPOUND
STOCK CODE
4.0 Litres 14250
7.5 Litres 16478
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 7 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV PARALLEL JOINTS (BUTT JOINTS) - (RESIN TYPE)
Cable 1 Cable 2
Cable 1 Cable 2 185 mm
2 Cu PLYHDPE or
SWS
185 mm2 Cu PLYHDPE or
SWS
21406 471
4x7.5L LJPCAV4PCAV4
185 mm2 Cu
XLPE/SWA/HDPE
240 mm2 Al XLPE/PVC 21406
477 4x7.5L
LJPCAV4PCAV4 185 mm
2 Cu PLYHDPE or
SWS
185 mm2 Cu
XLPE/SWA/HDPE
21406 472
4x7.5L LJPCAV4PCAV4
300 mm2 Cu
XLPE/SWA/HDPE
300 mm2 Cu
XLPE/SWA/HDPE 22240
478 6x7.5L
LJXCAV2XCAV2 185 mm
2 Cu PLYHDPE or
SWS
300 mm2 Cu
XLPE/SWA/HDPE
21406 473
4x7.5L LJPCAV4PCAV4
300 mm2 Cu
XLPE/SWA/HDPE 240 mm
2Al XLPE/PVC 22240
479 6x7.5L
LJXCAV2XCAV2 185 mm
2 Cu PLYHDPE or
SWS
240 mm2 Al XLPE/PVC 21406
474 4x7.5L
LJPCAV4PCAV4
240 mm2 Al XLPE/PVC 240 mm
2 Al XLPE/PVC 21406
480 4x7.5L
LJPCAV4PCAV4 185 mm
2 Cu
XLPE/SWA/HDPE
185 mm2 Cu
XLPE/SWA/HDPE
21406 475
4x7.5L LJPCAV4PCAV4
300 mm2 Cu XLPE/PVC 300 mm
2 Cu XLPE/PVC 22241
481
1x4L
LJQC30QC30
185 mm2 Cu
XLPE/SWA/HDPE
300 mm2 Cu
XLPE/SWA/HDPE
21406 476
4x7.5L LJPCAV4PCAV4
300 mm2 Cu XLPE/PVC 300 mm
2 Cu
XLPE/SWA/HDPE
22240 482
6x7.5L
LJXCAV2XCAV2
LEGEND
XXXXX
xxx xxxxxx
xxxxxxxx
STOCK CODE CONTRACT 09011 ITEM No. No. OF BUCKETS OF RESIN COMPATIBLE UNIT
NON RE-ENTERABLE RESIN
COMPOUND
STOCK CODE
4.0 Litres 14250
7.5 Litres 16478
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 8 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV STOP-END JOINTS (LIVE END SEALS - (HEAT-SHRINK)
Cable LEGEND
To suit cable from 70 mm2 up to 185 mm
2 Cu or Al PLYHDPE or PLYSWS, or XLPE/PVC/HDPE,
or XLPE/SWA/HDPE
17146 483
LVDEJ185; LVEJ185; LVE170
XXXXX xxx
xxxxxx
STOCK CODE CONTRACT 09011 ITEM No. COMPATIBLE UNIT
To suit cable from 16 mm2 up to 65 mm
2 Cu or Al PLYHDPE or PLYSWS, or XLPE/PVC/HDPE 17147 484
LVDEJ16; LVDEJ25; LVDEJ70; LVEJ25
To suit cable from 240 mm2 up to 300 mm
2 Cu or Al PLYHDPE or PLYSWS, or XLPE/PVC/HDPE
or XLPE/SWA/HDPE
22225 485
LSJPCAV2D
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 9 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
LV INDOOR & OUTDOOR TERMINATION TYPES
Conductor mm
2 & Type Cable Type Outdoor termination Indoor Termination
1c 300 stranded Cu XLPE/PVC 22226 486
LTSC30D
22227 487
LESC30D
3.5 c 300 stranded copper XLPE/SWA/HDPE 22228 488
LTQC30D
22229 489
LEQC30D
4c 240 stranded or solid Al XLPE/PVC 20540 490
LTSA24D
20540 491
LTSA24D
4c 185 stranded copper XLPE/PVC/HDPE 20358 492
EXTERM8MAT
20358 493
EXTERM8MAT
3.5c 185 stranded copper PLYHDPE & PLYSWS 20544 494
LTPC18D
20544 495
LTPC18D
120 stranded or solid Al XLPE/PVC 20546 496
LTSA12D
20546 497
LTSA12D
70 stranded copper PLYHDPE & PLYSWS 20548 498
LTPC70D
20548 499
LTPC70D
4c 70 stranded copper XLPE/PVC/HDPE 22230 500
LTWC70D
22231 501
LEWC70D
25 stranded copper PLYHDPE & PLYSWS 20548 502
LTPC70D
20548 503
LTPC70D
16 stranded copper PLYSWS 20552 504
LTPC16D
20553 505
LEPC16D
4c 16 stranded copper XLPE/PVC 20554 506
LTSC16D
20554 507
LTSC16D
LEGEND
Uncontrolled Document When Printed
udc-E5-1.1C.doc
© COPYRIGHT 2011 ENERGEX
This drawing must not be reproduced
in part or whole without written
permission from ENERGEX G. Treagle
6229-A4 D ELECTRICAL
LV JOINTS AND TERMINATIONS SELECTION MATRIX
D.Taylor
SUB-SECT.
WORD
Added P10 connectors for repairs.
J.Lansley
A.Smith de Perez
D.Taylor
31.03.10
FILE
29.10.14 DATE R.English
SHEET 10 OF 10
D
ATHR
CKD APP’D
AUTHR
APP’D
CKD
- DATE
REC’D
SECTION
E5 1.1
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
Cable Size LUGS FOR CABLE TERMINATIONS
Metric (mm2) Imperial (sq in)
Copper Compression Lug
Aluminium Compression Lug
Bi-metallic Shear Bolt Lug
16 15125 N/A
25 0.04 17700
22847
35 17660 39 0.06 65 0.1 70 77 0.12 95 11239 / 17702 17661 97 0.15
23929
161 0.25 185 11238 / 17705 240 11976 / 17706 17631
240 sector (LV URD) 15507
23926
258 0.4 300 12187 / 17707 323 0.5 400 10887 630 10888
1000 10889
RANGE TAKING SHEAR BOLT FERRULES FOR JOINTING
25-95 mm2 Cu or Al 23932 95-240 mm2 Cu or Al 18109 185 - 400 mm2 Cu or Al 23942
NOTES 1. Because of the significant increased cost for a mechanical bolted connector over a compression connector, the use of shear bolt connectors should be limited to staff who do not have suitable crimpers (eg Rapid Response staff attending a burnt off lug at pillar), or as an alternative for imperial cables where they can cover a range of sizes. 2. Conductor sizes are based on circular stranded conductors - sector type conductors will have a lower range of conductor sizes.
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
Uncontrolled Document When Printed
This drawing must not be
C COPYRIGHT 2012 ENERGEX
whole without writtenpermission from ENERGEX
reproduced in part or
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
ORIGIN
AL IS
SUE
DATE
APP’D
SECTION SUB-SECT.
CAD
RECD
CKD
DWN
SHT OF
FILE
LV JOINTS & TERMINATIONS
2 + 1/2 WAY LINK PILLAR
CONNECTIONS - 185 Cu PLY & 240 Al XLPE
6229-A4 B
E5 5.131 1
UDC-E5-5.13-1B.DWG
F.Zaini
28/5/14
B.BRUNSMANN
J.LANSLEYA
LVSP57STOCK
01081
01053
11
22
00412
CODE
11
MATERIAL
- 2+1/2 WAY LINK PILLAR 240 MM CABLELVSP572
Bolt & Washer
15865
Base
15197
Assembly M10
06677
Cover
3 Way Link Pillar
6844
6507
Neutral Bar
06844
06677
1
1
06507 1
21298
15197
9
415507 12
Sleeve (150mm)
Heatshrink
21298
Bolt, Machine Washer Flatx2
412 1053
Washer Lock
1081
Terminal Lug
15507
SIDE ELEVATION - 3 WAY PANEL
Plan View (Links
Removed)
(only 1 phase shown connected for clarity)
Additional 400A Links
16448
11
22
11
1
1
1
9
4
LVSP53
- 2+1/2 WAY LINK PILLAR 185 MM CABLELVSP532
17705 12
B
WA
TER
MA
RK
AD
DE
D
A.
BLET
CHL
Y
T.
BO
RG
APP’D
CK
D
AT
HR
DA
TE
20.08.18
LEGA
CY - F
OR
MAIN
TENANC
E O
NLYB.
BR
UNS
MA
NN
This drawing must not be
C COPYRIGHT 2014 ENERGEX
whole without writtenpermission from ENERGEX
reproduced in part or
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
ORIGIN
AL IS
SUE
DATE
APP’D
SECTION SUB-SECT.
CAD
RECD
CKD
DWN
SHT OF
FILE
LV JOINTS & TERMINATIONS
3 WAY LINK PILLAR
CONNECTIONS - 185 Cu PLY & 240 Al XLPE
6229-A4 C
E5 5.141 1
UDC-E5-5.14-1C.DWG
A.SmithdePerez
21/5/14
B.BRUNSMANN
J.LANSLEYA
LVSP58STOCK
01081
01053
12
24
00412
CODE
12
MATERIAL
- 3 WAY LINK PILLAR 240 MM CABLELVSP582
06932
06511
1
1
04889 1
15197 415507 12
Additional 400A Links
16448
12
24
12
1
1
1
4
LVSP59
- 3 WAY LINK PILLAR 185 MM CABLELVSP592
17705 12
Bolt & Washer
6511
Base
15197
Assembly M10
06932
Cover
3 Way Link Pillar
4889
Neutral Bar
06507
Service Fuse
(if reqd)
Set screw M10 x 25
903 M10 Washer
1052
00903 4 4
01052 4 4
06507 1 1
Additional Service Fuses
1043-1
Bond Frame to MEN Link
1033-3 11
Top frame mounting bar
to be insulated
MEN pillar earth required at all
link pillars as per Section E7.