  • UNDERGROUND CONSTRUCTION MANUAL

    HV SWITCHGEAR Go to SECTION INDEX Back to MAIN INDEX

  • DESCRIPTION DWG

    INDEX31/5/11

    62 5254 11

    5229/1

    5229/3

    CONSTRUCTION CONSTRUCTION DESCRIPTION DWG

    5234/1

    5229/2

    HV SWITCHGEAR

    C. Noel

    A. Bletchly

    L. Burton

    Construction code guide - Foundation & site finish

    Construction code guide - 22kV Ring main unit

    Construction code guide - 11kV Ring main unit

    Location in council parklands

    Location in council parklands 5234/2

    Location in residential allotments 5233

    5230

    Site finish concrete suround

    Outdoor RMU with precast concrete fdn - 5217

    RING MAIN UNIT

    5232/1

    5232/2

    Culvert Foundation details - Material

    Culvert Foundation details - Construction

    11RMU/ASL

    5236/1

    5236/2

    ABB 11kV ring main unit Safelink - Material11RMU/O/ASL2S1F

    11RMU/O/ASL2S2F

    11RMU/O/ASL3S1F

    11RMU/O/ASL3S

    11RMU/O/ASL4S

    Construction

    ABB 11kV ring main unit Safelink -

    Maximum cut & fill

    Site preperation sloping site -

    5237/1

    5237/2

    5238/1

    5238/2

    5253/1

    HV switchgear schematic

    ABB 11kV Safeplus / Safering -

    ABB 11kV Safeplus / Safering - Material

    5243/1

    5243/2

    22RMU/O/FGA2S1F F & G 22kV ring main unit - Material

    F & G 22kV ring main unit - Construction22RMU/O/FGA2S2F

    22RMU/O/FGA3S1F

    22RMU/O/FGA2S1CB

    22RMU/O/FGA3S

    22RMU/O/FGA4S

    22RMU/O/FGA1S1CB1F

    22RMU/O/FGA1S1CB2F

    5252/1

    5252/2

    F & G 22kV ring main unit - Schematic

    F & G 22kV ring main unit - Schematic

    schematic

    ABB 11kV Safelink - HV switchgear

    schematic

    ABB 11kV Safelink - HV switchgear

    Construction

    ABB 11kV Safeplus / Safering5255/1Ring main unit installation

    5255/2Ring main unit installation

    5255/3Ring main unit installation

    5255/4Ring main unit installation

    B 14.01.14

    D

    5290Site requirement - separate earthing

    schematic

    ABB 11kV Safelink - HV switchgear 5237/3

    5308/1ABB 11kV RMU Safelink2 - Material

    ABB 11kV RMU Safelink2 - Material 5308/2

    5308/3

    schematic

    ABB 11kV Safelink2 - HV switchgear

    schematic

    ABB 11kV Safelink2 - HV switchgear 5308/4

    schematic

    ABB 11kV Safelink2 - HV switchgear 5308/5

    11RMU/O/ASL22S1F

    11RMU/O/ASL22S2F

    11RMU/O/ASL23S1F

    11RMU/O/ASL23S

    11RMU/O/ASL24S

    C 13.04.15

    D 19.01.17

    5253/2

    HV switchgear schematic

    ABB 11kV Safeplus / Safering -

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • DESCRIPTION DWG

    INDEX19/01/17

    62 5254 22

    CONSTRUCTION CONSTRUCTION DESCRIPTION DWG

    HV SWITCHGEAR

    C. Noel

    A. Bletchly

    22kV Outdoor RMU - site finish paved surround

    T. Borg

    5364

    5359/1F & G RMU - raised foundationgeneral arrangement

    5359/2

    5359/3

    5359/4general arrangement

    5359/5

    5359/6

    5359/7general arrangement

    F & G 3 switch switching stationraised blockwork foundation

    F & G 3 switch switching stationraised blockwork foundation

    F & G 3 switch switching station

    raised blockwork foundation

    raised blockwork foundation

    F & G 4 switch switching station

    F & G 4 switch switching station

    F & G 4 switch switching station

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • EXAMPLE:-

    CONSTRUCTIONSVOLTAGE

    CONSTRUCTION CODE GUIDE

    detail drawings in this manual.

    appears on relevant construction

    Code shown within dashed box

    A

    522962 5229 1

    T.Borg

    11kV RING MAIN UNIT CONSTRUCTION CODE

    11 RMU/O/ASL 2S1F

    11 = 11kV RMU = Ring Main Unit

    LOCATION

    O = Outdoor

    HV SWITCHGEAR

    ASL = ABB SafeLink

    ASP = ABB SafePlus

    ASR = ABB SafeRing

    CONFIGURATION

    2S1F = 2 switch + 1 fuse

    2S2F = 2 switch + 2 fuse

    3S = 3 switch

    4S = 4 switch

    3S1F = 3 switch + 1 fuse

    1S1CB1F = 1 switch + 1 circuit breaker + 1 fuse

    2S1CB = 2 switch + 1 circuit breaker

    11RMU/O/ASL2S1F = 11kV, Ring Main Unit, outdoor, ABB SafeLink, 2 switches + 1 fuse.

    C. Noel

    A. Bletchly

    1

    11kV RING MAIN UNIT

    9/9/10HV SWITCHGEARB 03.01.14

    C

    ASL2 = ABB SafeLink 2

    C 11.01.17

    2S2CB = 2 switch + 2 circuit breaker

    3S1CB = 3 switch + 1 circuit breaker

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • CONSTRUCTION CODE GUIDE

    5229 262 5229 2

    C. Noel

    A. Bletchly

    EXAMPLE:-

    is not provided by others.

    Required only where foundation

    detail drawings in this manual.

    appears on relevant construction

    Code shown within dashed box

    A

    FOUNDATION AND SITE FINISH

    3/5/11

    RING MAIN UNIT FOUNDATION & SITE FINISH CONSTRUCTION CODE

    11 RMUF / ASL

    11 = 11kV

    VOLTAGE RMU FOUNDATION

    RMUF = Ring Main Unit Foundation

    HV SWITCHGEAR

    ASL = ABB Safelink

    11RMUF/ASL = 11kV, Ring main unit foundation, ABB Safelink

    L. Burton

    HV SWITCHGEARHARD COPYUNCONTROLLED

    B 01.10.14

    B

    22 = 22kV FGA = Felton & Guillaume (F & G)

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 1 SITE

    INSTALLATION

    General1.1

    Stable (soil conditions)

    Free from steep batters

    Flood free

    Level (topography) where possible

    1.4

    1.2

    1

    1/6/11

    Site Size

    1.3

    URD

    Along coastal areas the site must be located as far as possible

    from the shoreline and sheltered from salt spray.

    Common earthing sites

    Level sites - 3000mm width x 2800mm depth.

    Retaining wall sites - 3400mm width x 3000mm depth.

    The site shall be to the satisfaction of Ergon Energy, including

    A site should not be located where impact by traffic is likely and,

    if at a truncated section of the street alignment or other non-regular

    shaped site the following shall apply:

    The specified rectangular size of the site shall not be reduced.

    a) In the Road Reserve:-

    The Developer shall obtain all necessary approvals from the

    Department of Transport or the Local Authority.

    b) On Freehold property (including residential or parkland):-

    The Developer shall provide Ergon Energy with a registered

    easement at no cost to Ergon Energy.

    HARD COPYUNCONTROLLED

    L. Burton

    A. Bletchly

    C. Noel

    62 5255 15255

    HV SWITCHGEAR

    RING MAIN UNIT

    The minimum area required to accommodate a ring main unit

    shall be:

    Ring Main Unit Orientation

    The developer shall provide a ring main unit site(s) as

    required by Ergon Energy at no cost to Ergon Energy. The site shall

    be included in the road reserve, or located on freehold property.

    No ring main units are to be located in Trustee Reserves.

    Where the developer required the ring main unit to be included:

    Acceptable separation of ring main unit to adjacent dwellings is

    provided if the front of dwellings are set back 6.0m from the R.P.

    Street Alignment and the padmount is located as shown in

    drawings No. 5233, 5234 Sheets 1 or 2.

    Developments including streets where the allowable dwelling set

    back is less than 6.0m will require ring main unit siting on either an

    alternative street, where the dwelling set back is 6.0m, or in Parklands.

    RING MAIN UNIT INSTALLATION

    Free from other services

    The front edge of the ring main unit shall be as near to

    parallel as possible to the R.P. Street Alignment.

    Ring main units shall be oriented such that the HV panels

    are easily accessible from the dedicated footpath.

    ���

    A ORIGINAL ISSUE

    ���

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 2

    1 SITE

    1.5

    (CONT’D)

    Commercial and Industrial or Landscaped Areas

    1.6 Parklands - for other than URD

    1.7

    Cabling Only

    Cabling and Access

    2 SITE PREPARATION

    Sites shall be prepared in accordance with the included

    construction drawings.

    3 CONSTRUCTION OF RETAINING WALLS

    4

    4.1 Uniculvert

    Cabling and Access Requirement

    A 3.0m wide easement, or road reserve, from the front of

    the site is required for cabling and access.

    ��

    62 5255 25255

    HV SWITCHGEAR

    INSTALLATION

    RING MAIN UNIT

    1/6/11

    C. Noel

    A. Bletchly

    L. Burton

    Whether the ring main unit is for the sole use of that

    complex, or is required as part of the distribution network, the

    owner is required to grant Ergon Energy an easement for the

    ring main unit site, access and cabling.

    Obtain the necessary approval for an easement to accommodate

    the ring main unit, cabling and access to site.

    Acceptable separation of ring main unit to adjacent dwellings is

    shown in drawings No. 5234 Sheets 1 & 2.

    Should the cabling route not be available in conjunction with

    access, a 1.0m wide cable easement is required to the front

    of the ring main unit. Additionally 2.0m x 3.0m (ring main unit

    site width) is required immediately in front to allow spreading of

    cables for entry to the ring main unit and also include the buried

    earth cable.

    Retaining walls shall be constructed around the perimeter of a

    ring main unit site where:

    A change in ground level of 300mm or more occurs within 2.0m

    of the boundary of the ring main unit site.

    RING MAIN UNIT FOUNDATION

    Separation of 5.0m between ring main unit and the

    nearest room or habitable area should be provided

    where possible.

    Uniculvert foundations shall not be constructed where site and

    ground conditions do not provide an even or equal bearing

    capacity for the ring main unit.

    Uniculvert foundations for stable soil conditions shall

    be constructed in accordance with Drawing No. 5232.

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • INSTALLATION

    3

    BACKFILLING AND FINAL SITE FINISH

    ADDITIONAL REQUIREMENTS

    C. Noel

    A. Bletchly

    1/6/11

    L. Burton 62 5255 35255

    RING MAIN UNIT FOUNDATION

    Ring Main Units in Landscaped Areas

    HV SWITCHGEAR

    RING MAIN UNIT

    4.2

    HARD COPYUNCONTROLLED

    B 01.10.14

    B

    installation or replacement.

    Easy access for a mobile crane must be available for the purpose of

    sectioned with construction joints for ease of future removal.

    front of the substation cabinet shall be finished with a concrete slab

    with a concrete slab (refer to drawing No. 5004). The 2.0m apron in

    finished surface level. The substation site surface is to be finished

    foundation. Conduits shall be 750mm minimum depth below the

    foundation. No conduits shall pass through or under the uniculvert

    the substation site and shall pass down the sides of the uniculvert

    Ergon Energy cable conduits for the development may be placed in

    emergency operations.

    working platform and access around latched open doors for

    full width of the site (ie 4.8m depth). This will provide a safe

    An additional 2.0m apron shall be provided in front of, and for the

    accordance with the applicable drawing.

    All backfill of the site must be compacted before final site finish in

    5.2 Separate Earthing Sites

    5.3 Raised Blockwork Foundation - Common Earthing Sites

    No. 5290.

    extremeties shall be finished in accordance with drawing

    ground surface between the concrete surround slab and site

    In addition to the requirements of Clause 5.1 the remaining

    ground surface shall be in accordance with drawing No. 5217.

    and construction of the concrete surround slab over the

    Sealing of the cable apertures in the precast concrete plinth

    Ergon Energy.

    foundation construction shall be used without the approval of

    consideration. No special designs for ring main unit

    design from a Civil Engineer (RPEQ) for Ergon Energy’s

    In such circumstances, the developer shall obtain a certified

    and heavy equipment at all times.

    areas where clear, all weather access is provided for personnel

    Ring main units shall be located on the development in

    area (gardens) the following shall apply:

    Where the ring main unit is located in a landscaped

    (refer to drawing No. 5217).

    The ring main unit site surface is to be finished with a concrete slab

    removal.

    a concrete slab sectioned with construction joints for ease of future

    The 2.0m apron in front of the ring main unit site shall be finished with

    6

    6.1

    5.1

    5

    4

    6.2

    Commercial and Industrial Installation

    Common Earthing Sites

    Unstable Sites

    (CONT’D)

    be applied, a special design shall be required.

    construction techniques as described in this document cannot

    Where sites are very unstable, and conventional foundation

    not be provided.

    manufacturer’s installation specifications. A concrete slab shall

    approved by Ergon Energy) installed in accordance with the

    interlocking masonary paving (besser "interlock" or equivalent

    The ring main unit 3.0m x 5.2m site surface is to be finished with

    doors shall face the adjoining footpath.

    developments is at the real property street alignment. Switchgear cabinet

    The preferred location of ring main unit sites at commercial and industrial

    open doors for emergency operations.

    This will provide a safe working platform and access around latched

    be provided in front of, and for the full width of the site (ie 4.8m depth).

    between buildings, an additional minimum 2.0m of clear access shall

    Should the site be located in restricted areas such as carparks and

    5.4 Raised Blockwork Foundation - Separate Earthing Sites

    No. 5317 Sh. 3.

    extremities shall be finished in accordance with drawing

    surface between the barrier kerb (around the paving) and site

    In addition to the requirements of clause 5.3 the remaining ground

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • �INSTALLATION

    4

    6.2 (CONT’D)

    6.3

    7

    Ring Main Unit in Landscaped Areas

    When planting vegetation in landscaped areas and gardens,

    ensure vegetation does not encroach on the ring main unit

    site. Take into consideration the fully matured size

    of vegetation to allow continuing access to the site.

    Ergon Energy cable conduits for the development may be

    placed in the ring main unit site and shall pass down the sides

    of the uniculvert foundation. No conduits shall pass through

    or under the uniculvert foundation. Conduits shall be 750mm

    minimum depth below the finished surface level.

    Ring Main Units Installation in Parklands

    Where the ring main unit is located in Council

    Parklands, the installation shall be in accordance with the

    requirements of drawing No. 5234 Sheets 1 or 2.

    A 2.0m apron as specified in Clause 6.2 shall be provided.

    No buildings/residences, fences, including their foundations, LV

    switchboard earths, or metalic objects are permitted within the

    clearance zone around the RING MAIN UNIT.

    Clearance to Telstra assets shall be as noted on EARTHING

    drawing No. 5221 Sheet 1.

    62 5255 45255

    HV SWITCHGEAR

    RING MAIN UNIT

    1/6/11

    C. Noel

    A. Bletchly

    L. Burton

    SPACING BETWEEN RING MAIN UNIT AND OTHER

    METAL OBJECTS

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • ������

    �� L. Burton 523462 5234 1

    C. Noel

    A. Bletchly

    10.3.11

    NOTES:

    Parklands

    1.

    2.

    3.

    2.5m Min.

    2.5

    m M

    in.

    4.

    Apron

    PLAN

    Dwelling

    Real Property

    Boundary

    1.5m

    Min.

    R.P. Street

    Alignment

    FOOTPATH

    Kerb

    ROAD2.0

    m

    F

    F

    F

    F

    F

    F

    F

    F

    F

    F

    F

    F

    F

    F

    Dwelling

    1.5

    m

    Min

    .

    F

    F

    Site

    Boundary

    As Req’d

    3.0m

    Away from residential dwellings and surrounding

    properties to minimise visual and sound impact;

    As close as possible to the road kerb to allow 24 hour

    all weather access for personnel, a coventional crane

    and heavy equipment.

    Refer

    Note 4

    Refer

    Note 4

    F

    F

    F

    F

    RMU SET BACK FROM R.P. STREET ALIGNMENT

    When planting vegetation in parklands, ensure vegetation

    does not encroach on the ring main unit site.

    Take into consideration the fully matured size of vegetation

    to allow continuing access to the site.

    A ring main unit in parkland shall be located:

    The location of ring main unit sites is based on acceptable

    separation to adjacent dwellings located as shown.

    Any reduction in the 1.5m minimum dimension shown on

    the drawings requires a corresponding relocation of the

    ring main unit site to maintain the acceptable separation.

    LOCATION IN COUNCIL PARKLANDS

    A 3.0m wide cable and access easement or road reserve

    shall be provided between the ring main unit site and the

    R.P. Street Alignment.

    1

    HV SWITCHGEARHARD COPYUNCONTROLLED�

    ���

    A ORIGINAL ISSUE

    ���

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • ������

    �� L. Burton 523462 5234 2

    C. Noel

    A. Bletchly

    10.3.11

    FOOTPATH

    ROAD

    Parklands

    Kerb

    PLAN

    Dwelling

    R.P. Street

    Alignment

    6.0m Min.

    F

    Site

    Boundary

    F

    F

    F

    F

    F

    As Req’d

    Real Property Boundary

    FOOTPATH

    ROAD

    Parklands

    Kerb

    PLAN

    Dwelling

    F

    Site

    BoundaryF

    F

    F

    F

    F

    Real Property Boundary

    Less than

    6.0m2.5m Min.

    F

    F

    1.5m

    Min.

    F

    F

    Refer Note 4

    Sheet 1.

    R.P. Street

    Alignment

    RMU ADJOINING R.P. STREET ALIGNMENT

    LOCATION IN COUNCIL PARKLANDS

    2

    HV SWITCHGEARHARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • ������

    �� L. Burton 523362 5233 1

    8/3/11

    C. Noel

    A. Bletchly

    F

    F

    FO

    OT

    PA

    TH

    R.P. Street

    Alignment

    F

    6000

    F

    F

    3000

    NOTE:

    Real Property Boundary

    F

    F2800

    Dwelling

    Dwelling

    As

    Req’d

    As

    Req’d

    FF

    FF

    Ring main units

    may be in 1 or 2

    allotments

    F

    A reduction in dwelling setback

    of 6000mm from the R.P. Street

    Alignment will require relocation

    of the ring main unit to an

    alternative site to achieve

    the acceptable separation.

    LOCATION IN RESIDENTIAL ALLOTMENTS

    HV SWITCHGEARHARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • FO

    OT

    PA

    TH

    NOTES:

    ������

    ��

    PLAN

    L. Burton

    MAXIMUM CUT & FILL

    (shown dashed)

    3000

    800

    A_

    FIL

    L

    100 M

    AX

    R.P. Street

    Alignment

    _

    150 M

    AX

    CU

    T

    2800

    SECTION A

    2. Ergon Energy’s 3000mm x 2800mm (minimum) site

    shall be levelled and surrounding area graded to ensure

    NO PONDING of water occurs.

    523062 5230 1

    8.3.11SITE PREPARATION SLOPING SITE

    Outline of RMU foundation over

    1. Refer drawing 5226 for installation requirements.

    3. No services other than the Ergon Energy’s electric cables

    shall pass through this RMU site.

    4. Clear access to the RMU shall be maintained for

    Ergon Energy’s personnel & heavy equipment.

    6. Mature landscaping (including trees, sprinklers etc) shall

    not encroach onto the RMU site.

    7. The finished surface of the adjacent footpath, in front

    of the RMU cabinet, shall be level to ensure that

    the cabinet doors will swing into the fully open position.

    FF

    F

    F

    F

    F

    F

    F

    F

    F

    F

    FF

    R.P. Street

    Alignment

    = =

    ==

    Site

    Boundary

    F

    5. After installation is complete the site surface is to be

    finished with a concrete slab. (Refer drawing 5217).

    HV SWITCHGEAR

    A.Bletchly

    C.Noel

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 5217

    � �

    ��

    � C.Lindsay

    23/11/01

    62 5217 1

    SITE FINISH CONCRETE SURROUND

    OUTDOOR RMU WITH PRECAST CONCRETE FDN

    F

    30

    00

    F

    F 2800F

    Concrete Edge

    Beam

    F

    Fall

    F

    F

    F

    Fall

    Fall

    F

    F

    surround slab cast

    F

    Site

    Boundary

    (Level Site)

    A_

    PLAN

    FO

    OT

    PA

    TH

    Alignment

    R.P. Street

    F

    Reinforced concrete

    around plinth

    between plinth and

    Abelflex sealant joint

    concrete slab

    NOTES:

    2. Reinforced concrete surround slab:

    a) 100/125mm thick slab:

    b) 11 TM trench mesh reinforcement in centre of slab:

    c) 25 MPa grade concrete:

    d) Finish by wood float or by nylon broom.

    4. The concrete slab is to slope away from plinth falling

    at a slope of 1 in 25.

    5. Cable apertures through the precast concrete plinth

    shall be backfilled to 50mm from the top of plinth.

    A 30mm deep layer of 1:16 ratio weak mix concrete

    shall be placed to seal aperture.

    6. The surface of the surround slab may be finished with

    a stencil pattern surface to match the surrounding

    pavements of the development. (Use Textcrete or

    equivalent product. Construct to supplier’s specifications).

    3. The top face of the concrete surround slab shall be

    100mm Min. above the final surface level (when turf is laid).

    Line

    Ground

    Finished

    _SECTION A

    Backfill

    Cable Pit

    Refer note 1.

    F

    Earth grid under

    concrete edge beam

    Fall

    F

    F

    Fall

    50 F

    F

    F

    F10

    0 M

    in.

    F

    F

    HV SWITCHGEAR

    _SECTION B

    Concrete edge

    beam to perimeter

    150 wide x 150

    deep below

    finished surface.Foundation

    Finish

    ground line

    _B

    F

    C. Noel

    A. Bletchly

    F

    Construction Type

    11RMUF/ASL

    Pre-cast foundation

    1. Backfill Cable Pit with bedding sand and compact in place.

    Refer TRENCHING Drawing No. 5227.

    B 02.11.11

    B

    Refer Note 7

    FF

    F

    7. Concrete slab to be cast in separate sections on side/s

    where cables enter/exit to allow future access.

    Provide ’Abelflex’ between sections and around plinth.

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • NOTES:

    ���������� �

    ��B� 1/2 �DISC

    ���� �

    � L. Burton

    1. Foundation design details are as follows:1

    ASSY QTYDESCRIPTION

    MATERIAL

    1523262 5232 1

    583-2 CulvertUnstable soils are soft clay to sandy gravel with a soil strength

    50-150 kPa.

    Stable soils are very stiff clay to shale/rock with soil strength of

    150kPa or higher.

    2. Lift the culvert separately with 4 x 1.3 tonnes

    Reid Swiftlift lifting eyes.

    3. Position the top face of the culvert at the finished ground level

    of the site, as detailed on the Project’s Civil Construction drawings.

    4. Do NOT remove the culvert end wall knockouts.

    5. The culvert shall be constructed level. Under no circumstances

    shall it be allowed to tilt forward towards the footpath.

    7. Refer drawing No. 5217 for site finish concrete surround.

    CULVERT FOUNDATION DETAILS

    A. Bletchly

    C. Noel

    4/5/11

    MATERIAL

    HV SWITCHGEARHARD COPYUNCONTROLLED�

    ���

    A ORIGINAL ISSUE

    ���

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • L. Burton62 5238 1

    5238

    C. Noel

    A. Bletchly

    ASSY DESCRIPTIONQTY

    NOTES:

    578-1

    578-5

    1

    1.

    MATERIAL - FREESTANDING RING MAIN UNIT

    For circuit breaker setting refer to protection.

    1S1CB1F 2S1CB

    1

    MATERIAL

    9/5/11

    1

    11kV ABB safeplus RMU 1 switch 1 circuit breaker 1 fuse c/w cubical and plinth

    11kV ABB safering 2 switch 1 circuit breaker c/w cubical and plinth

    ABB 11kV SAFEPLUS / SAFERING

    HV SWITCHGEARB 24.11.11

    C

    2.

    in consultation with system operations staff.* Ring feeders - determine the circuit arrangement with CFI unit(s)* Radial feeders - switch disconnector(s) provided as follows:cable circuits (Refer dwg 5253 for schematic) Designer to nominate the position(s) of the outgoing

    C 11.01.17

    ASSY QTY

    MATERIAL - DISTRIBUTION PADLOCK

    REGION

    Central

    595-4

    595-5

    4

    595-3

    595-2

    595-6

    595-7

    MENT

    ARRANGE

    SWITCH

    North

    Mackay

    Wide Bay

    South West

    3

    1

    595-8

    595-9

    Central

    595-4

    595-5

    5

    595-3

    595-2

    595-6

    595-7

    North

    Mackay

    Wide Bay

    South West

    4

    1

    595-8

    595-9

    3S

    2S1F

    4S

    3S1F

    2S2F

    555-4

    555-5

    555-7

    555-8

    555-9

    555-10

    ASSY DESCRIPTION QTY

    3

    MATERIAL - HV FUSE - EACH CIRCUIT

    Refer note 3

    555-2 Cartridge fuse link 10A HRC

    Cartridge fuse link 20A HRC

    Cartridge fuse link 25A HRC

    Cartridge fuse link 40A HRC

    Cartridge fuse link 50A HRC

    Cartridge fuse link 63A HRC

    Cartridge fuse link 80A HRC

    578-7 11kV ABB safering 2 switch 2 circuit breaker c/w cubical and plinth

    578-9 11kV ABB safering 3 switch 1 circuit breaker c/w cubical and plinth

    2S2CB

    1

    3S1CB

    1

    3.Designer to nominate HV fuse link current rating.

    4.Designer to nominate distribution padlock.

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • L. Burton62 5238 2

    5238

    C. Noel

    A. Bletchly

    9/5/11

    2

    CONSTRUCTION

    F

    Lifting point

    F

    Lifting pointF

    Lifting point

    F

    F

    ABB 11kV SAFEPLUS / SAFERING

    HV SWITCHGEARB 11.01.17

    B

    578-1, 5, 7 or 9

    Assy Selection

    F

    595-2 to 9

    Assy Selection

    F

    555-2 to 10

    Assy Selection

    F

    cable connections.

    drawing No. 5270 for

    Refer HV CONSTRUCTION

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • L. Burton62 5253 1

    5253

    C. Noel

    A. Bletchly

    HV SWITCHGEAR

    1

    9/5/11

    HV SWITCHGEAR - SCHEMATIC

    ABB 11kV SAFEPLUS / SAFERINGB 11.01.17

    B

    V FC

    1 switch, 1 circuit breaker, 1 fuse

    ABB Safeplus

    11kV Ring Main Unit

    (maintenance only)

    1 switch, 1 circuit breaker, 2 fuse

    ABB Safeplus

    11kV Ring Main Unit

    C V F F

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 62 5253 25253

    C. Noel

    A. Bletchly

    HV SWITCHGEAR

    2

    HV SWITCHGEAR - SCHEMATIC

    ABB 11kV SAFEPLUS / SAFERING

    CC

    11/01/17

    T. Borg

    2 switch, 1 vacuum circuit breaker

    ABB Safeplus

    11kV Ring Main Unit

    V

    F

    F

    Fault Indicator

    Shortcircuit & Earth

    CC V

    F

    F

    Fault Indicator

    Shortcircuit & Earth

    2 switch, 2 vacuum circuit breaker

    ABB Safeplus

    11kV Ring Main Unit

    V CC V

    F

    Fault Indicator

    Shortcircuit & Earth

    3 switch, 1 vacuum circuit breaker

    ABB Safeplus

    11kV Ring Main Unit

    C

    F

    FF

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • ASSY DESCRIPTIONQTY

    NOTES:

    22/12/14

    599-9

    62 5308 15308

    C. Noel

    A. Bletchly

    599-1

    599-5

    599-3

    599-7

    555-4

    555-5

    555-7

    555-8

    555-9

    555-10

    11kV ABB safelink2 3 switch c/w cubical and plinth

    11kV ABB safelink2 4 switch c/w cubical and plinth

    1

    2S1F 2S2F 3S1F3S 4S

    1.

    2.

    3.

    MATERIAL - FREESTANDING RING MAIN UNIT

    ASSY DESCRIPTION QTY

    3

    1

    1

    1

    1

    1

    MATERIAL

    MATERIAL - HV FUSE - EACH CIRCUIT

    Refer note 1

    555-2 Cartridge fuse link 10A HRC

    Cartridge fuse link 20A HRC

    Cartridge fuse link 25A HRC

    Cartridge fuse link 40A HRC

    Cartridge fuse link 50A HRC

    Cartridge fuse link 63A HRC

    Cartridge fuse link 80A HRC

    Designer to nominate HV fuse link current rating

    HV SWITCHGEAR

    4.Designer to nominate distribution padlock.

    ASSY QTY

    MATERIAL - DISTRIBUTION PADLOCK

    REGION

    Central

    595-4

    595-5

    4

    595-3

    595-2

    595-6

    595-7

    MENT

    ARRANGE

    SWITCH

    North

    Mackay

    Wide Bay

    South West

    3

    1

    595-8

    595-9

    Central

    595-4

    595-5

    5

    595-3

    595-2

    595-6

    595-7

    North

    Mackay

    Wide Bay

    South West

    4

    1

    595-8

    595-9

    3S

    2S1F

    4S

    3S1F

    2S2F

    HARD COPYUNCONTROLLED

    ABB 11kV RING MAIN UNIT SAFELINK2

    T. Borg

    11kV ABB safelink2 2 switch 1 fuse c/w cubical and plinth

    11kV ABB safelink2 2 switch 2 fuse c/w cubical and plinth

    11kV ABB safelink2 3 switch 1 fuse c/w cubical and plinth

    CONTRACT No. 10179B

    * Ring feeders - determine the circuit arrangement in consultation with system operations staff.

    * Radial feeders - switch disconnector(s) provided with CFI unit(s)

    (Refer sheets 3 to 5 for schematic) as follows:

    Designer to nominate the position(s) of the outgoing cable circuits

    and gland plates with RMU fitted.

    The HV cables must be fitted with cable glands as per construction standards

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • C. Noel

    A. Bletchly

    2

    Construction Type

    F

    F

    F

    Concrete plinth

    F

    for feeder cable connections

    drawing no. 5244 or 5245

    Refer HV CONSTRUCTION

    Side View Plan

    F

    4 x M12 ferrules

    Lifting points

    4 x M12 ferrules

    Lifting points

    CONSTRUCTION

    HV SWITCHGEAR

    F

    595-2 to 9

    Assy Selection

    HARD COPYUNCONTROLLED

    530862 5308 2

    ABB 11kV RING MAIN UNIT SAFELINK222/12/14

    T. Borg

    CONTRACT No. 10179B

    11RMU/O/ASL22S1F

    11RMU/O/ASL22S2F

    11RMU/O/ASL23S

    11RMU/O/ASL23S1F

    11RMU/O/ASL24S

    555-2 to 10

    599-1 to 9 and

    Assy Selection

    2

    SAFELINK SAFELINK SAFELINK SAFELINK

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 29/12/14

    62 5308 35308

    C. Noel

    A. Bletchly

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    3

    ABB 11kV SAFELINK2 - HV SWITCHGEAR

    SCHEMATIC

    HV SWITCHGEAR

    F F F

    FC C

    Slide cable boot down to expose

    Ø 8.5 Cable test point

    & Earth Fault

    Short Circuit

    F F F

    FC C

    Slide cable boot down to expose

    Ø 8.5 Cable test point

    & Earth Fault

    Short Circuit

    F

    F

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    F F

    HARD COPYUNCONTROLLED

    T. Borg

    2S1F 11kV ABB safelink2 RMU 2 switch 1 fuse 2S2F 11kV ABB safelink2 RMU 2 switch 2 fuse

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 29/12/14

    62 5308 45308

    C. Noel

    A. Bletchly

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    4

    ABB 11kV SAFELINK2 - HV SWITCHGEAR

    SCHEMATIC

    HV SWITCHGEAR

    F F

    C C

    Slide cable boot down to expose

    Ø 8.5 Cable test point

    & Earth Fault

    Short Circuit

    F

    & Earth Fault

    Short Circuit

    C

    F F F

    FC C

    F

    C

    Slide cable boot down to expose

    Ø 8.5 Cable test point

    & Earth Fault

    Short Circuit

    & Earth Fault

    Short Circuit

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    F F F F

    HARD COPYUNCONTROLLED

    T. Borg

    3S 11kV ABB safelink2 RMU 3 switch 3S1F 11kV ABB safelink2 RMU 3 switch 1 fuse

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 29/12/14

    62 5308 55308

    C. Noel

    A. Bletchly

    5

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    ABB 11kV SAFELINK2 - HV SWITCHGEAR

    SCHEMATIC

    HV SWITCHGEAR

    F F

    C C

    & Earth Fault

    Short Circuit

    F

    & Earth Fault

    Short Circuit

    C

    F

    C

    Slide cable boot down to expose

    Ø 8.5 Cable test point

    & Earth Fault

    Short Circuit

    T. Borg

    F F F

    HARD COPYUNCONTROLLED

    4S 11kV ABB safelink2 RMU 4 switch

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • ���������� �����

    L. Burton

    HARD COPYUNCONTROLLED

    62 5252 15252

    C. Noel

    A. Bletchly

    HV SWITCHGEAR

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    F

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    1

    SCHEMATIC

    9/5/11F & G 22kV RING MAIN UNIT

    2S1F 22kV F & G

    ring main unit

    2 switch, 1 fuse

    2S2F 22kV F & G

    ring main unit

    2 switch, 2 fuse

    3S1F 22kV F & G

    ring main unit

    3 switch, 1 fuse

    F F F

    ���

    A ORIGINAL ISSUE

    ���

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • ���������� �����

    L. Burton

    10/3/11HARD COPYUNCONTROLLED

    62 5252 25252

    C. Noel

    A. Bletchly

    HV SWITCHGEAR

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    2

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    FEEDER

    CABLE

    F

    Note:

    (CFI) on this switch disconnector unit

    Represents circuit fault indicator

    SCHEMATIC

    F & G 22kV RING MAIN UNIT

    4S 22kV F & G

    ring main unit

    4 switch

    3S 22kV F & G

    ring main unit

    3 switch

    F F F F

    A ORIGINAL ISSUE

    ��

    ��

    ����� �

    ��

    ��

    ���

    ������

    ��

    �DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 5359 162 5359 1

    C. Noel

    A. Bletchly

    27/07/16

    T. Borg

    GENERAL ARRANGEMENT

    HV SWITCHGEAR

    1.

    2.

    CONSTRUCTION NOTES

    1.

    2.

    CONDUITS

    3.

    4.

    5.

    6.

    All conduits to be sealed/fitted with caps before concrete pour.

    All conduits to have 50mm min. projection above fsl of concrete.

    All radius bends centreline radius to be 500mm min.

    Conduit to be located as determined on masonry plan.

    CONCRETE

    1.

    2.

    3.

    4.

    5.

    6.

    Supply and lay concrete in accordance with AS3600.

    Footings to be cast without construction joints unless otherwise indicated.

    Concrete strength to N32 min.

    Exposed concrete surfaces to be cured in accordance with AS3600.

    7.

    8.

    9.

    10.

    Supply & lay reinforcement in accordance with AS3600.

    Provide light broom finish to footings.

    specification for excavation.

    specification, standard specification for concrete and standard

    This drawing should be read in conjunction with specific civil works

    footing. Minimum 100kpa bearing capacity.

    Footings to be found in sound material with 98% srdd subgrade under

    with AS2053.

    All conduits to be (class H.D.) orange PVC electrical in accordance

    synthetic draw rope.

    Unless otherwise specified all conduits to be fitted with one 8mm diameter

    underlay the footing.

    Supply & lay vapour barrier in accordance with AS2870 to continuously

    to be class 3, true & free of blemishes & imperfections.

    Concrete formwork in accordance with AS3610, exposed concrete surfaces

    to ground.

    Maintain 40mm concrete cover to top reinforcement and 50mm cover

    1.

    MASONRY BLOCKWORK

    1.

    2.

    2.

    3.

    4.

    5.

    6.

    7.

    Mortar shall be class M3 in accordance with AS3700.

    Grout shalll be 20mpa at 28 days - 10mm max. aggregate size.

    Fill all cores with min 25mpa concrete.

    Vertical reinforcement to block walls shall be 1-N12 as shown.

    strength of 15mpa.

    Concrete blocks shall have a min. unconfined compressive

    with AS/NZS4455.

    Concrete masonry material and workmanship shall comply

    bars horizontally.

    Reinforce single course bond beam at top of wall with 2-N12

    BOLTS

    with AS1111.

    All bolts shall be of approved manufacture in accordance

    under all nuts.

    the thread from the shear plane. a suitable washer shall be used

    All bolts shall be galvanised and of sufficient length to exclude

    1.

    2.

    3.

    4.

    5.

    6.

    ALUMINIUM MATERIALS

    Aluminium sheet shall comply with AS/NZS1734.

    the drawing and shall be cleaned of all burrs and rough edges.

    All holes shall finish accurately to size and in the position shown in

    All holes shall be drilled.

    noted otherwise in the drawing.

    Bolts, nuts and washers shall be stainless steel grade 316 unless

    AS1664 and AS/NZS1665.

    All aluminium components shall be fabricated in accordance with

    flat surfaces.

    to produce clean straight bends with no distortion in the adjacent

    Bending of aluminium plate or sheet shall be carried out in a press

    Reinforcement supported by chairs for spacers appropriate to achieve cover.

    F & G RING MAIN UNIT - RAISED FOUNDATIONHARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 5359 262 5359 2

    C. Noel

    A. Bletchly

    27/07/16

    T. Borg

    HV SWITCHGEAR

    RAISED BLOCKWORK FOUNDATION

    540

    F

    560

    F

    1:30

    345

    F

    290

    F

    F

    360

    F

    F

    1350

    F

    F

    F

    50200

    PLAN VIEW 1:20

    SIDE ELEVATION

    555

    F

    F

    290

    F

    F

    345

    F

    F

    610

    F

    F

    200

    F

    200

    F

    F

    F

    bars @ min 400mm cts.

    M12 reinforcing

    1800

    F

    F

    1400

    F

    F

    50

    F

    F

    900

    FF

    F

    See Detail ’A’ Sh 4

    Aluminium cover platerF

    200 series blockwork

    F

    200mm thick

    Concrete base

    A

    FGL FGL

    F(760 radius)

    150mm conduit (3 off)

    F

    200 series blockwork

    B3

    3

    F & G 3 SWITCH SWITCHING STATIONHARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 5359 362 5359 3

    C. Noel

    A. Bletchly

    27/07/16

    T. Borg

    HV SWITCHGEAR

    RAISED BLOCKWORK FOUNDATION

    FSL

    1:20

    1:20

    50

    F

    F900

    F

    F200F

    F

    25

    F

    F

    200F

    F

    200

    F

    F

    200

    F

    F

    F

    ste two component epoxy pain system

    blockwork surface with "dulux" durebild

    Paint the stirrup to extend 100mm below

    Fishtail stirrups - HDG

    embedment 75mm

    Chemset "REO 502" minimum

    Pryda FS400/12 - 400 x 6mm M12 - 4.6/S

    1400

    F

    F

    200

    F

    F

    F

    50mm cover

    SL82 mesh top and bottom

    F

    bedding sand 95% SRDD

    Compacted, well graded course

    400

    90

    60

    200 1000 200FF

    F F

    1298 F

    FF

    F

    centrally placed at end & cts.

    N12 vertical starter bar

    continuous 500 lap

    2-N12 bond beam

    F

    and orientation

    refer plan for location

    F

    refer detail ’A’ sh 4

    & support angles

    Aluminium cover plate

    protection conduit

    F

    F

    50mm cover

    top and bottom

    SL82 mesh

    Fblockwork

    200 series

    SECTION B

    SECTION A

    F & G 3 SWITCH SWITCHING STATIONHARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 5359 462 5359 4

    C. Noel

    A. Bletchly

    27/07/16

    T. Borg

    HV SWITCHGEAR

    GENERAL ARRANGEMENT

    1:20

    ELEVATION

    1:5

    DETAIL ’A’

    F

    blockwork

    200 series

    F

    F

    F

    Refer detail ’A’

    Aluminium cover plate

    approx 300kg

    F & G RMU

    45F

    F

    25F

    F

    5

    F

    F

    390

    F

    F

    5

    F

    F

    100F

    F40

    F

    F

    20

    F

    F

    35

    F

    F

    285

    F

    F

    35

    F

    F

    20

    F

    F

    5

    F

    F 990

    F

    F 5F

    F

    F

    blockwork

    200 series

    F

    F

    F

    masonry anchors

    M10 316 s/s dynabolt

    alum. angle 355 long

    75 x 50 x 6 marine grade

    CFW all round

    Weld cover plate to angle

    & supplied by Ergon

    in blockwork by contractor

    alum support angles at opening

    alum cover plate weld to the

    415 x 990 x 3 marine grade

    each corner

    200mm from

    concrete plinth

    to secure RMU

    Fishtail stirrup (4 total)

    F

    CFW to alum. angle for earthing

    F

    F & G 3 SWITCH SWITCHING STATIONHARD COPYUNCONTROLLED

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    A ORIGINAL ISSUE

    ABN 50 087 646 062

    OVERHEAD DISTRIBUTION

    Dwg ShFILE: 5

  • 5359 562 5359 5

    C. Noel

    A. Bletchly

    27/07/16

    T. Borg

    HV SWITCHGEAR

    RAISED BLOCKWORK FOUNDATION

    1:30

    PLAN VIEW 1:20

    SIDE ELEVATION

    540F

    560

    F

    1350

    F

    F

    F

    50200

    1800

    F

    F

    50

    F

    F

    2200

    F

    F

    345

    F

    290

    F

    F

    380

    F

    F

    345

    F

    F

    440

    F

    F

    200

    F

    555

    F

    290

    F

    F

    345

    F

    F

    610

    F

    F

    F

    900

    FF

    200F

    F

    F

    200 series blockwork

    F

    200mm thick

    Concrete base

    F

    See Detail ’B’ Sh 7

    Aluminium cover plater

    D

    F

    bars @ min 400mm cts.

    M12 reinforcing

    F

    200 series blockwork

    (760 radius)

    150mm conduit (3 off)F

    FGL FGL

    C 6

    6

    F & G 4 SWITCH SWITCHING STATIONHARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 5359 662 5359 6

    C. Noel

    A. Bletchly

    27/07/16

    T. Borg

    HV SWITCHGEAR

    RAISED BLOCKWORK FOUNDATION

    1:20

    200

    F

    F

    F

    and orientation

    refer plan for location

    F

    refer detail ’B’ sh 7

    & support angles

    Aluminium cover plate

    protection conduit

    F

    F

    50mm cover

    top and bottom

    SL82 mesh

    Fblockwork

    200 series

    200

    F

    F 900 F

    F

    50F

    F

    25

    F

    F

    FSL

    1:20

    200F

    F

    200

    F

    F

    F

    1400

    F

    F

    200

    F

    F

    F

    50mm cover

    SL82 mesh top and bottom

    F

    bedding sand 95% SRDD

    Compacted, well graded course

    400

    90

    60

    200 1000 200FF

    F F

    1298 F

    F

    F

    F

    centrally placed at end & cts.

    N12 vertical starter bar

    continuous 500 lap

    2-N12 bond beam

    F & G 4 SWITCH SWITCHING STATION

    SECTION C

    SECTION Dtwo component epoxy pain system

    blockwork surface with "DULUX" Durebild STE

    Paint the stirrup to extend 100mm below

    Fishtail stirrups - HDG

    embedment 75mm

    Chemset "REO 502" minimum

    Pryda FS400/12 - 400 x 6mm M12 - 4.6/S

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

  • 5359 762 5359 7

    C. Noel

    A. Bletchly

    27/07/16

    T. Borg

    HV SWITCHGEAR

    GENERAL ARRANGEMENT

    1:20

    ELEVATION

    1:5

    DETAIL ’B’

    F

    blockwork

    200 series

    F

    F

    F

    Refer detail ’B’

    Aluminium cover plate

    approx 300kg

    F & G RMU

    45F

    F

    25F

    F

    5

    F

    F

    390

    F

    F

    5

    F

    F

    100F

    F40

    F

    F

    20

    F

    F

    35

    F

    F285

    F

    F

    35

    F

    F

    20

    F

    F

    5

    F

    F 990

    F

    F 5F

    F

    F

    blockwork

    200 series

    F

    F

    F

    masonry anchors

    M10 316 s/s dynabolt

    alum. angle 355 long

    75 x 50 x 6 marine grade

    CFW all round

    Weld cover plate to angle

    & supplied by Ergon

    in blockwork by contractor

    alum support angles at opening

    alum cover plate weld to the

    415 x 990 x 3 marine grade

    each corner

    200mm from

    concrete plinth

    to secure RMU

    Fishtail stirrup (4 total)

    F

    CFW to alum. angle for earthingF

    F & G 4 SWITCH SWITCHING STATIONHARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062

    OVERHEAD DISTRIBUTION

    Dwg ShFILE: 5

  • 5364

    05.10.16

    62 5364 1

    F

    3000

    F

    F 2800F

    A_

    PLAN

    FO

    OTP

    AT

    HNOTES:

    _SECTION A

    F

    F

    F

    F

    F

    F

    HV SWITCHGEAR

    C. Noel

    A. Bletchly

    Construction Type

    F

    T. Borg

    22kV OUTDOOR RMU

    SITE FINISH PAVED SURROUND

    BARRIER KERB

    BARRIER KERB

    BA

    RRIE

    R K

    ER

    B

    BA

    RRIE

    R K

    ER

    B

    Refer note 1

    Drainage slot

    22RMUF/FGA

    and on sloping sites at 2m max. spacing on ’down hill’ sides.

    On flat sites provide slots at 2m max. spacing on all sides

    level to drain sand bedding under paving.

    Provide approx. 5mm wide slots down to finished ground

    1. Drainage Slots:-

    2. For foundation and cover plate details refer Drawing 5359.

    storm tide or flooding (1:100 year risk) level for that location.

    3. The base of the RMU is to be above tidal inundation,

    surface level (when turf is laid).

    4. The top face of barrier kerb shall be 50mm above the final

    at a slope of 1 in 50.

    5. The paving is to be sloped away from plinth / foundation

    200

    F

    F150

    Min. Fall 1 in 50

    F

    specification.

    in accordance with manufacturers

    Besser "Interlock" pavers laid

    course bedding sand.

    of compacted, well graded,

    40mm min. levelling layer

    2 N12 bars min. 600 lap, 40 cover

    HARD COPYUNCONTROLLED

    A ORIGINAL ISSUE

    DRAWN

    DATE

    PASSED

    APPROVED

    Ergon Energy Corporation Ltd

    ABN 50 087 646 062Dwg Sh

    FILE: 5

    UNDERGROUND DISTRIBUTION

    MAIN_INDEXISSUE_14_CHANGESINTRODUCTIONConstruction Manual IntroductionProcedure for reporting a problem NA000303R100Construction Standards Feedback Form NA000303F100 - Sh 1Construction Standards Feedback Form NA000303F100 - Sh 25369/1 EO Terminology Changes5369/2 EO Terminology Changes

    ASSEMBLIESAssemblies Index Sheet 1Assemblies Index Sheet 2Assemblies Index Sheet 3Assemblies Index Sheet 4Assemblies Index Sheet 5Assemblies Index Sheet 6Assemblies Index Sheet 7 Assemblies Index Sheet 8500 Electricity supply pillars500-1 Pillar (tall) electricity supply500-2 Pillar (short) electricity cross road500-3 Pillar (large) electricity

    501 LV supply pillar 1 way connection501-1 Connection cable 1 way501-2 Connection cable 1 way insect protected

    502 LV supply pillar 2 way connection502-1 Connection cable 2 way502-2 Connection cable 2 way insect protected

    503 LV supply pillar 3 way cable connection503-1 Connection cable 3 way503-2 Connection cable 3 way insect protected

    504 Lug set504-1 Lug set Al 240mm² sector cable504-5 Lug set bi-metal 240mm² sector cable504-9 Lug set 16mm² cross road cable504-11 Lug set 50mm² cross road cable

    505 Earthing MEN to LV pillar and LV distribution cabinet505-1 Earth MEN to LV pillar505-2 Earth MEN to LV distribution cabinet

    506 LV pillar fuse panel506-4 Additional fuse, street light506-5 Panel, 6 fuse cross - road pillar506-6 Panel, 6 fuse supply pillar

    507 Low voltage fuse links507-3 Cartridge fuse link 32A HRC507-6 Cartridge fuse link 63A HRC507-7 Cartridge fuse link 80A HRC507-8 Cartridge fuse link 100A HRC507-11 Link solid din size 1 (250A)507-12 Link solid din size 2 (400A)

    508 Cable termination and connection to transformer508-1 Term. & conn. to transformer 22kV 35mm² cable insect protected508-4 Term. & conn. to transformer 22kV 185mm² cable

    509 Uniculvert and base slab509-1 Uniculvert509-2 Base slab

    510 Earth connection elbow connector to station earth510-1 Earth connection elbow connector to station earth510-6 Earth extension elbow connector to station earth

    511 Trefoil clamping arrangements to pole termination bracket511-1 Clamp trefoil to pole term. bracket suit 11kV 35mm² cable511-1 Clamp trefoil to pole term. bracket suit 11kV 35mm² cable insect protected511-2 Clamp trefoil to pole term. bracket suit 22kV 35mm² cable insect protected511-3 Clamp trefoil to pole term. bracket suit 11kV 185mm² cable511-3 Clamp trefoil to pole term. bracket suit 11kV 185mm² cable insect protected511-6 Clamp trefoil to pole term. bracket suit 22kV 185mm² cable511-8 Clamp trefoil to pole term. bracket suit 11kV 400mm² cable insect protected511-10 Clamp trefoil to pole term. bracket suit 11kV 400mm² Al cable 511-10 Clamp trefoil to pole term. bracket suit 11kV 400mm² Al cable insect protected511-11 Clamp trefoil to pole term. bracket suit 33kV 300mm² 3 cable 511-12 Clamp trefoil to pole term. bracket suit 22kV 630mm² cable

    512 Cable termination & connection to RMU512-1 Term. & conn. to RMU 22kV 35mm² cable insect protected512-4 Term. & conn. to RMU 22kV 185mm² cable512-7 Term. & conn. to RMU 22kV 630mm² cable

    513 Connection earth bar to cover plate and service platform513-1 Connection earth bar to cover plate513-5 Connection earth bar to service platform

    514 11kV ABB SD series RMU cable termination & connection 514-1 Term. & conn.(ABB SD) 11kV 35mm² cable514-2 Term. & conn.(ABB SD) 11kV 185mm² cable514-3 Term. & conn.(ABB SD) 11kV 35mm² cable insect protected 514-4 Term. & conn.(ABB SD) 11kV 185mm² cable insect protected

    515 Cable clamping arrangements515-1 Clamp cable to P1000 channel515-2 Clamp cable to P3300 channel515-3 Clamp cable to wood pole bracket515-4 Clamp cable to wood pole

    516 11kV magnefix MD series RMU & transformer. Cable termination & connection516-1 Term. & conn.(Magnefix MD & Transf.) 11kV 35mm² cable516-2 Term. & conn.(Magnefix MD & Transf.) 11kV 185mm² cable516-3 Term. & conn.(Magnefix & Transf.) 11kV 35mm² cable insect protected516-4 Term. & conn.(Magnefix & Transf.) 11kV 185mm² cable insect protected

    517 LV pillar (large) support frame, neutral bar & fuse panel518 LV pillar (large) CFS unit phase connection518-1 Connection phase terminal CFS unit & fuse panel518-2 Connection phase terminal CFS unit & fuse panel insect protected518-3 Connection phase terminal CFS unit

    519 LV pillar (large) neutral bar connection519-1 Connection neutral bar (large pillar)519-2 Connection neutral bar (large pillar) insect protected

    520 Switch/fuse mounting pole & switch/fuse cable connection520-1 Switch/fuse mounting to wood pole520-2 Connection switch/fuse to open wire - 150mm² cable520-3 Connection switch/fuse to LVABC520-4 Connection switch/fuse to open wire - 95mm² cable

    521 LV pole termination dropper connection521-1 Connection 240mm² sector cable to 150mm² Cu insulated521-2 Connection 240mm² sector cable to 95mm² Cu insulated521-6 Connection 240mm² sector cable to 95mm² LVABC

    522 LV outdoor termination 240mm² Al & 16mm² Cu 4 core cable522-1 Termination outdoor 240mm² LV522-11 Termination outdoor 16mm² LV

    523 Underground cable warning signs523-1 Warning sign 1 and post U/G cable523-2 Warning sign 2 and post U/G cable

    524 Earth rod - additional524-1 Earth rod additional524-2 Earth rod additional depth524-3 Earth rod additional depth - suit 70mm² cable524-4 Additional earthing cable joint, 35mm²524-5 Additional earthing cable joint, 70mm²524-6 Additional earth connector 'C' type

    525 Padmounted substation earth rod and connection525-1 Earth padmounted substation525-2 Earth connector additional525-3 Earth padmounted auto transformer

    526 Grid to earth bar connection & earth - deep drilled526-1 Connection grid to earth bar - 35mm²526-2 Earth - deep drilled - 35mm²526-3 Connection grid to earth bar - 70mm²526-4 Earth - deep drilled - 70mm²

    527 LV pillar (large) fuse mounting527-1 3 fuse527-2 6 fuse527-3 6 fuse insect prot.527-4 Additional fuse, S/L

    528 LV pillar (large) CFS unit & link holder528-1 CFS unit528-2 Insulating Shroud (large)528-3 Insulating Shroud (small)

    529 Low voltage fuse links529-2 Fuse link 80A din size 1529-3 Fuse link 100A din size 1529-4 Fuse link 125A din size 1529-5 Fuse link 160A din size 1529-6 Fuse link 200A din size 1529-7 Fuse link 250A din size 1529-10 Fuse link 100A din size 2529-11 Fuse link 125A din size 2529-13 Fuse link 200A din size 2529-14 Fuse link 250A din size 2529-15 Fuse link 315A din size 2529-16 Fuse link 355A din size 2529-17 Fuse link 400A din size 2529-23 Fuse link 500A din size 3529-24 Fuse link 630A din size 3529-26 Fuse link 35A din size 00

    530 Insulation piercing connectors530-1 Connector I.P.C. 25/95mm² main to 6/35mm² tap530-6 Connector tap-off bare Al main 16.8/210mm² to 6/35mm² tap530-7 Connector tap-off bare Cu main 5.5/135mm² to 6/35mm² tap

    531 Cable guard to pole531-1 Guard polymeric to wood pole531-2 Guard polymeric (small) to wood pole531-6 Guard metal (100) to wood pole531-7 Guard metal (130) to wood pole531-8 Guard metal (180) to wood pole

    532 Saddle to pole, bracket cable support to x-arm532-1 Saddle (20mm) to wood pole532-2 Saddle (25mm) to wood pole532-6 Bracket cable support to x-arm

    533 LV pole termination overhead mains connection\533-1 Connector Al./I.P.C. 95/240mm² Al. main to 35/95mm² ABC tap533-2 Connector Al./I.P.C. 50/150mm² Al. main to 35/95mm² ABC tap533-3 Connector Cu./I.P.C. 7/95mm² Cu. main to 35/95mm² ABC tap533-6 Connector I.P.C. 35/95mm² main to 35/95mm² tap533-11 Connector P.G. 95/240mm² Al. main 70/185mm² Cu. tap533-16 Connector P.G. 16/150mm² Cu. main to 16/150mm² Cu. tap

    534 Distribution cabinet 6 module cast in situ foundation535 Distribution cabinet 6 module precast concrete foundation 536 Clamps to suit 3 x 1c 35mm² & 630mm cable fixings536-1 Clamps to suit 3x1 core 35mm² cable536-5 Clamps to suit 3x1 core 630mm² cable536-6 Fixings

    537 11kV padmounted substation with LV switchgear537-1 Padmounted substation 100kVA with LV switchgear537-2 Padmounted substation 200kVA with LV switchgear537-3 Padmounted substation 315kVA with LV switchgear537-4 Padmounted substation 500kVA with LV switchgear537-5 Padmounted substation 750kVA with LV switchgear537-6 Padmounted substation 1000kVA with LV switchgear (Transformer disconnector only)

    538 11kV padmounted substation HV switchgear538-1 RMU Magnefix 3 switch 1 fuse538-2 RMU ABB 2 switch 1 fuse538-3 RMU Magnefix 2 switch 1 fuse538-4 SFU Magnefix 1 switch 1 fuse

    539 Bracket termination (11kV, 22kV & 33kV) mounting to wood pole540 11kV & 22kV pole termination arrester mounting to bracket540-1 Arrester 11kV mounting to bracket540-2 Arrester 22kV mounting to bracket (M12)540-3 Arrester 22kV mounting to bracket (M16) - 630mm² cable only540-4 Arrester 11kV mounting to bracket (M16) - 400mm² cable540-2 Arrester 33kV mounting to bracket (M12)

    541 Trefoil clamp to channel541-4 Clamp trifoil to channel suit 11kV 35mm² cable541-4 Clamp trifoil to channel suit 11kV 35mm² cable insect protected541-5 Clamp trifoil to channel suit 22kV 35mm² cable insect protected541-7 Clamp trifoil to channel suit 11kV 185mm² cable541-7 Clamp trifoil to channel suit 11kV 185mm² cable insect protected541-9 Clamp trifoil to channel suit 22kV 185mm² cable541-12 Clamp trifoil to channel suit 11kV 400mm² cable541-12 Clamp trifoil to channel suit 11kV 400mm² cable insect protected

    542 22kV padmounted substation with LV switchgear542-1 Padmounted substation 3.7m long. 500kVA with LV switchgear542-2 Padmounted substation 3.7m long. 1000kVA with LV switchgear542-3 Padmounted substation 4.1m long. 500kVA with LV switchgear542-4 Padmounted substation 4.1m long. 1000kVA with LV switchgear542-5 Padmounted substation 4.1m long. 315kVA with LV switchgear

    543 22kV padmounted substation HV switchgear543-2 Ring Main Unit - 2 switch, 1 fuse543-3 Ring Main Unit - 2 switch, 2 fuse543-4 Ring Main Unit - 3 switch, 1 fuse534-5 Ring Main Unit - 3 switch534-6 Ring Main Unit - 4 switch

    544 22kV padmounted substation transformer to RMU cable connection545 Earth connections545-1 Connection LV earth to earth bar545-2 Connection 35mm² earth bridge

    546 11kV & 22kV outdoor termination triplex & 1 core XLPE cable546-1 Termination outdoor 11kV 35mm² cable546-2 Termination outdoor 11kV 185mm² cable546-3 Termination outdoor 11kV 35mm² cable insect protected546-4 Termination outdoor 11kV 185mm² cable insect protected546-6 Termination outdoor 11kV 400mm² cable546-7 Termination outdoor 11kV 400mm² cable insect protected546-10 Termination outdoor 22kV 185mm² cable546-11 Termination outdoor 22kV 630mm² cable546-12 Termination outdoor 22kV 35mm² cable insect protected

    547 11kV & 22kV pole termination wildlife protection548 LV distribution cabinet 548-1 Distribution cabinet 6 module 1 isolator 2 fuse switch548-2 Distribution cabinet 2 module 2 fuse switch548-3 Distribution cabinet flood zone 9 fuse

    549 LV distribution cabinet 6 module wall mounting support550 LV isolator and fuse switch550-1 Isolator550-6 Fuse switch550-7 Fuse switch - 630A Merlin Gerin

    551 Insulating glove, heatshring tubing and heatshrink lug seal set551-1 Glove insulating 16mm² 4C cable551-2 Glove insulating 240mm² 4C cable551-3 Glove insulating 50mm² 4C cable551-6 Heatshrink lug seal set 240mm² cable551-11 Heatshrink tubing

    552 Separate HV & LV earth modifications insulator busbar & labels552-1 Insulator busbar standoff552-2 Warning label552-3 Caution label

    553 35mm² insect protected cable bonding brass tape to cable screens554 11kV fuse links - oil immeresed554-3 Cartridge fuse link 16A HRC - oil immersed554-5 Cartridge fuse link 25A HRC - oil immersed554-6 Cartridge fuse link 31.5A HRC - oil immersed554-8 Cartridge fuse link 50A HRC - oil immersed554-9 Cartridge fuse link 63A HRC - oil immersed554-11 Cartridge fuse link 80A HRC - oil immersed

    555 11kV fuse links555-2 Cartridge fuse link 10A HRC555-4 Cartridge fuse link 20A HRC555-5 Cartridge fuse link 25A HRC555-7 Cartridge fuse link 40A HRC555-8 Cartridge fuse link 50A HRC555-9 Cartridge fuse link 63A HRC555-10 Cartridge fuse link 80A HRC

    556 22kV fuse links556-3 Cartridge fuse link 16A HRC556-4 Cartridge fuse link 20A HRC556-7 Cartridge fuse link 40A HRC

    557 Trefoil clamping arrangements557-8 Clamp trefoil to wood pole to suit 400mm² cable 11kV 1 core557-12 Clamp trefoil to wood pole to suit 630mm² cable 22kV 1 core557-20 Spring nut suit P1000 channel557-21 Spring nut suit P3300 channel

    558 Conduit bends558-10 Conduit bend H.D. 40 dia.300R 90°558-20 Conduit bend L.D. 80 dia. 450R 90°558-30 Terminator conduit PVC flexible 16mm558-31 Terminator conduit PVC flexible 20mm558-32 Terminator conduit PVC flexible 25mm558-40 Conduit PVC flexible 16mm558-41 Conduit PVC flexible 20mm558-42 Conduit PVC flexible 25mm558-43 Conduit PVC flexible 50mm

    559 Communications conduits & bends559-10 Conduit communication 50 dia.(white)559-55 Conduit bend communication 304 Rad. 50 Dia. 90 Deg.559-75 Conduit bend communication 304 Rad. 50 Dia. 45 Deg.

    560 Communications splicing enclosure for fibre optic cable560-5 Splicing enclosure for 48/48 fibre optic cable communications560-10 Splicing enclosure for 36/36 fibre optic cable communications560-15 Splicing enclosure for 96/96, 48/48, and 36/36 fibre optic cable communications

    561 Pits562 Communications HFT cable guard to pole562-1 HFT cable guard (25mm) single FOC to concrete pole562-6 HFT cable guard (25mm) double FOC to concrete pole562-11 HFT cable guard (25mm) FOC to wood pole

    563 11kV padmounted substation with LV switchgear & RMU ABB SDAF3 2S1F563-3 Padmounted substation 315kVA with LV switchgear & RMU ABB SDAF3 2S1F563-4 Padmounted substation 500kVA with LV switchgear & RMU ABB SDAF3 2S1F563-5 Padmounted substation 750 kVA with LV switchgear & RMU ABB SDAF3 2S1F563-6 Padmounted substation 1000kVA with LV switchgear & RMU ABB SDAF3 2S1F

    564 Conduits564-20 Conduit UPVC 80 dia. L.D. orange564-50 Conduit UPVC 40 dia. H.D. orange

    565 11kV padmounted substation with LV switchgear 565-3 Padmounted substation 315kVA with LV switchgear565-4 Padmounted substation 500kVA with LV switchgear565-5 Padmounted substation 750kVA with LV switchgear565-6 Padmounted substation 1000kVA with LV switchgear

    566 11kV padmounted substation with LV switchgear & ABB safelink RMU 2S1F566-3 Padmounted substation 315kVA with LV switchgear & RMU ABB SafeLink 2S1F566-4 Padmounted substation 500kVA with LV switchgear & RMU ABB SafeLink 2S1F566-5 Padmounted substation 750kVA with LV switchgear & RMU ABB SafeLink 2S1F566-6 Padmounted substation 1000kVA with LV switchgear & RMU ABB SafeLink 2S1F

    567 11kV safelink ring main unit outdoor enclosure567-1 11kV ABB safelink 2 switch 1 fuse c/w cubical & plinth567-3 11kV ABB safelink 2 switch 2 fuse c/w cubical & plinth567-5 11kV ABB safelink 3 switch c/w cubical & plinth567-7 11kV ABB safelink 3 switch 1 fuse c/w cubical & plinth567-9 11kV ABB safelink 4 switch c/w cubical & plinth567-12 11kV ABB safelink 2 switch 1 fuse (RMU only)

    569 Communications cable guard with bandit strap569-1 Guard metal (100) to concrete pole569-2 Guard metal (130) to concrete pole

    570 11kV ABB safelink RMU in padmounted substation 1 core 400mm² Cu. cable term. & connection571 11kV ABB safelink RMU in padmounted substation cable termination & connection571-1 Term. & conn. (ABB SafeLink) 11kV 35mm² cable571-2 Term. & conn. (ABB SafeLink) 11kV 185mm² cable571-3 Term. & conn. (ABB SafeLink) 11kV 35mm² cable insect protected571-4 Term. & conn. (ABB SafeLink) 11kV 185mm² cable insect protected571-8 Term. & conn. (ABB SafeLink) 11kV 400mm² Cu cable 571-9 Term. & conn. (ABB SafeLink) 11kV 400mm² Cu cable insect protected

    572 11kV outdoor termination 1 core 400mm² Cu. cable573 Cast aluminium single cable clamp to channel573-2 Clamp to channel suit 11kV 35mm² cable573-2 Clamp to channel suit 11kV 35mm² cable insect protected573-4 Clamp to channel suit 11kV 185mm² cable573-4 Clamp to channel suit 11/22kV 185mm² cable insect protected573-6 Clamp to channel suit 11kV 400mm² cable insect protected573-9 Clamp to channel suit 11kV 400mm² cable 573-9 Clamp to channel suit 11kV 400mm² cable insect protected573-11 Clamp to channel suit 22kV 35mm² cable

    576 22kV padmounted substation with LV switchgear and F & G RMU576-2 Padmounted substation 315kVA 4.1m long with LV switchgear and RMU F & G 2 switch 1 fuse576-3 Padmounted substation 315kVA 4.1m long with LV switchgear and RMU F & G 3 switch 1 fuse576-4 Padmounted substation 315kVA 4.1m long with LV switchgear and RMU F & G 2 switch 2 fuse576-5 Padmounted substation 500kVA 4.1m long with LV switchgear and RMU F & G 2 switch 1 fuse576-8 Padmounted substation 1000kVA 4.1m long with LV switchgear and RMU F & G 2 switch 1 fuse576-9 Padmounted substation 1000kVA 4.1m long with LV switchgear and RMU F & G 3 switch 1 fuse

    577 ABB bushing boots 16-300mm² cable - ABB safelink only. Raychem bushing boots 35-400mm² cable577-1 ABB bushing boots 16-300mm² cable (ABB safelink only)577-5 Raychem bushing boots 35-400mm² cable

    578 11kV ABB safeplus & safering ring main unit - outdoor enclosure578-1 11kV ABB safeplus RMU 1 switch 1 circuit breaker 1 fuse c/w cubical & plinth578-5 11kV ABB safeplus RMU 2 switch 1 circuit breaker c/w cubical & plinth578-7 11kV ABB safering RMU 2 switch 2 circuit breaker c/w cubical & plinth578-9 11kV ABB safering RMU 3 switch 1 circuit breaker c/w cubical & plinth

    579 22kV F & G ring main unit - outdoor enclosure579-1 22kV F & G RMU 2 switch 1 fuse c/w cubical & plinth579-3 22kV F & G RMU 2 switch 2 fuse c/w cubical & plinth579-5 22kV F & G RMU 3 switch c/w cubical & plinth579-7 22kV F & G RMU 3 switch 1 fuse c/w cubical & plinth579-9 22kV F & G RMU 4 switch c/w cubical & plinth579-11 22kV F & G RMU 1 switch 1 circuit breaker 1 fuse c/w cubical & plinth579-13 22kV F & G RMU 1 switch 1 circuit breaker 2 fuse c/w cubical & plinth579-11 22kV F & G RMU 2 switch 1 circuit breaker c/w cubical & plinth

    580-1 Cable separation mounting bracket for termination leads581 Sign, asset identification numerals and letters581-0 Asset identification number '0'581-1 Asset identification number '1'581-2 Asset identification number '2'581-3 Asset identification number '3'581-4 Asset identification number '4'581-5 Asset identification number '5'581-6 Asset identification number '6'581-7 Asset identification number '7'581-8 Asset identification number '8'581-9 Asset identification number '9'581-A Asset identification letter 'A'581-B Asset identification letter 'B'581-C Asset identification letter 'C'581-D Asset identification letter 'D'581-E Asset identification letter 'E'

    582 Sign, asset identification label tray582-2 Asset identification backing plate to polymeric / powder coated assets582-4 Asset identification backing plate to steel / aluminium assets

    583-2 Concrete culvert - ABB safelink ring main unit584 33kV outdoor termination triplex & 1 core XLPE cable584-1 termination outdoor 33kV 50mm² cable584-3 termination outdoor 33kV 300mm² cable

    586 LV Circuit Breaker586-1 Circuit Breaker, 1200A including busbar sub assembly to suit Webber 750kVa586-2 Circuit breaker, 1600A including busbar sub assembly to suit Webber 1000kVA586-3 Circuit breaker, 1600A, to suit Opus LV board in Schneider 22kV 1000kVA Padmount586-4 Circuit breaker, 1250A including busbar sub assembly - suit Jean Muller 750kVA Padmount LV Board586-5 Circuit breaker, 1600A including busbar sub assembly - suit Jean Muller 1000kVA Padmount LV Board

    587 11kV Padmounted Substation with LV switchgear & Schneider Electric FBX RMU 2S1F587-3 Padmounted Substation 315kVA with LV switchgear & Schneider Electric FBX RMU 2S1F587-4 Padmounted Substation 500kVA with LV switchgear & Schneider Electric FBX RMU 2S1F587-5 Padmounted Substation 750kVA with LV switchgear & Schneider Electric FBX RMU 2S1F587-6 Padmounted Substation 1000kVA with LV switchgear & Schneider Electric FBX RMU 2S1F587-7 Padmounted Substation 1500kVA with LV switchgear & HV switchgear 2S1CB

    588 Termination & Connection to 11kV HV Switchgear588-1 Term. & Conn. to HV switchgear 11kV 35mm² cable588-4 Term. & Conn. to HV switchgear 11kV 185mm² cable588-7 Term. & Conn. to HV switchgear 11kV 400mm² cable

    589 Cover cable entry - retro fit kit590 22kV Padmount Substation with LV switchgear and Schneider Electric RM6590-1 200kVA 4.1m long with LV switchgear & RM6 1 switch 1 fuse590-2 315kVA 4.1m long with LV switchgear & RM6 2 switch 1 fuse590-3 315kVA 4.1m long with LV switchgear & RM6 3 switch 1 fuse590-4 315kVA 4.1m long with LV switchgear & RM6 2 switch 2 fuse590-5 500kVA 4.1m long with LV switchgear & RM6 2 switch 1 fuse590-6 500kVA 4.1m long with LV switchgear & RM6 3 switch 1 fuse590-7 500kVA 4.1m long with LV switchgear & RM6 2 switch 2 fuse590-8 1000kVA 4.1m long with LV switchgear, circuit breaker & RM6 2 switch 1 fuse590-9 1000kVA 4.1m long with LV switchgear, circuit breaker & RM6 3 switch 1 fuse590-10 1000kVA 4.1m long with LV switchgear, circuit breaker & RM6 2 switch 2 fuse

    591 Gland Plate Kit591-1 Gland plate kit & glands to suit 35mm² cable - 3 unit config. 591-2 Gland plate kit & glands - 35mm² cable - additional for LHS of 4 unit config.591-3 Gland plate kit & glands to suit 630mm² cable - 3 unit config591-4 Gland plate kit & glands - 630mm² cable - additional for LHS of 4 unit config591-5 Gland kit with glands to suit 185mm² cable

    592 Asset Identification Number592-0 Asset Identification Number '0'592-1 Asset Identification Number '1'592-2 Asset Identification Number '2'592-3 Asset Identification Number '3'592-4 Asset Identification Number '4'592-5 Asset Identification Number '5'592-6 Asset Identification Number '6'592-7 Asset Identification Number '7'592-8 Asset Identification Number '8'592-9 Asset Identification Number '9'

    593 Adapter Fuse Link HV594 Paralleling Kits for fuse strips594-1 Paralleling kit to suit Jean Muller - (suits 630A Jean Muller strips only)594-2 Paralleling kit to suit Opus Schnieder - (suits 630A Opus & Fuseway 1260A only)594-3 Phase segregation device retrofit to Jean Muller ganged switch adapter

    595 Distribution Padlock596 Anti-Galling Paste597 Service Fuse bracket to pole597-1 Bracket 32mm x 8mm to wood pole597-2 Fuse holder 100A to bracket

    598 Distribution cabinet floodzone precast concrete foundation599 11kV Safelink2 RMU outdoor enclosure599-1 11kV ABB Safelink2 - 2 switch 1 fuse c/w cubical & plinth599-3 11kV ABB Safelink2 - 2 switch 2 fuse c/w cubical & plinth599-5 11kV ABB Safelink2 - 3 switch c/w cubical & plinth599-7 11kV ABB Safelink2 - 3 switch 1 fuse c/w cubical & plinth599-9 11kV ABB Safelink2 - 4 switch c/w cubical & plinth

    600 Cable gland for ABB Safelink2 freestanding RMU600-1 Cable gland to suit 185mm² IP & Non IP Al cable 600-3 Cable gland with heatshrink to suit 400mm² Al non IP & 240mm² Cu IP cable 600-5 Cable gland to suit 400mm² Cu IP & 400mm² Al IP cable

    601 LV Distribution cabinet base and floodzone extension601-1 Distribution cabinet base601-2 Distribution cabinet flood zone extension

    602 Neutral Voltage Displacement - ABB REF 615 IED602-1 Neutral voltage displacement ABB ref 615 IED

    603 Parallel cable adapter to suit Weber fuse switch603-1 Parallel cable adapter - to suit Weber fuse switch

    604 Cable insulated604-5 Cable insulated 6mm² 2C Cu

    605 Neutral Voltage Displacement Voltage Sensor605-1 Neutral voltage displacement voltage sensor - suits Prysmian & Elastamold type c connectors605-3 Neutral voltage displacement voltage sensor - suit Tyco (TE) Raychem type c connectors

    606 11kV Padmounted substation with LV switchgear & RMU 2S1F606-1 Padmounted Substation 315kVA with LV switchgear & RMU 2S1F606-2 Padmounted Substation 500kVA with LV switchgear & RMU 2S1F606-3 Padmounted Substation 750kVA with LV switchgear &