Upload
david-shannon
View
12
Download
0
Embed Size (px)
DESCRIPTION
fire resistance
Citation preview
Fire Resistance Ratings - ANSI/UL 263
Design No. X623 December 03, 1999
Ratings 1, 1-1/2, 2, and 2-1/2 Hr, 3 Hr (See Item 3)
1. Steel Column Min size W10x49. The column surfaces shall be free of dirt, loose scale and oil. Steel surfaces to be primed with polyamide-epoxy and zinc rich primers to an approximate dry film thickness of 0.003 in.
2. Glass Fiber Mesh 6 in. wide, weighing 4.5 oz per sq yd, embedded at approximately mid-depth of mastic coating. Glass fiber mesh must be applied for the 1-1/2, 2, 2-1/2 and 3 hr ratings.
3. Mastic Coating* Coating spray applied directly from containers to the appropriate thicknesses shown in the table below.
Rating Hr Material Thickness In.
1 0.19
1.5 0.26
2 0.34
2.5 0.42
3 0.53
PPG INDUSTRIES INC Type Pitt-Char XP. Investigated for Exterior Use.
*Bearing the UL Classification Mark