UBBL 1984
Citation preview
This is the html version of the file http://rakan1.jkr.gov.my/ckba/images/Nota_PTK/Powerpoint/PTK_khusus/UNIFORM%20BUILDING%20BY-LAWS%201984.ppt.Google automatically generates html versions of documents as we crawl the web.
UBBL 1984 Part 1: PreliminaryPart 2: Submission of plansfor approvalPart 3: Space, light andventilationPart 4: Temporary works inconnection with buildingoperationsPart 5: StructuralrequirementsPart 6: ConstructionalRequirement
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
1 of 34 1/2/2009 21:06
Part 7: Fire Requirement
UBBL 1984 Part 8: Fire alarms, Firedetection, Fire extinguishment and Firefighting
access.Part 9: Miscellaneous
UBBL PERTAINING TODEVELOPMENT
Submitting personClause 3.1.(c) & Clause 3.2
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
2 of 34 1/2/2009 21:06
Defines the submitting persons being eitherthe registered building draughtsman or theregistered architect or theregistered engineer as per Form A.
Clause 5
Stipulates the supervision of the works by a
qualified person.
Clause 6 (1)
Stipulates the signature to the submittedplans
to from a qualified person.
UBBL PERTAINING TODEVELOPMENT
Submitting personQualified person
Clause 4.(1)
Stipulates that a local authority can withdraw
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
3 of 34 1/2/2009 21:06
a submission by a qualified person who acted
beyond his competence.
Clause 7
Stipulates that the submitting person beingfully
responsible for the works.
UBBL PERTAINING TODEVELOPMENT
Submitting personQualified person
Clause 7(a)
Stipulates that the substitute of anotherqualified person must be with the prioragreement of the local authority.
Clause 7(b)
Stipulates that the owner can make asubstituted qualified person provided that the
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
4 of 34 1/2/2009 21:06
works had not commenced on site.
UBBL PERTAINING TODEVELOPMENT
Submitting personQualified person
Clause 7.(2)
Stipulates that if the local authority agrees to asubstituted qualified person, works on siteshould not be continued till the replacementhad been made.
Clause 7.(3)
Stipulates that if the original qualified person isincapacitate the owner must produce evidenceprior to the appointment of a substitute.
PLAN SUBMISSIONS
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
5 of 34 1/2/2009 21:06
Clause 12. 1 stipulatesthat the requirement tosubmit a brief report toindicate character andstandard of building submitted.Clause 17 stipulates thatthe authority has the right toreject structural plans.
CERTIFICATION OF WORKS Clause 22.(1) stipulates that thesubmission of Form A for notification ofcommencement of works and Form B forcommencement/ resumption of works.Clause 23.(1) stipulates the submission ofForm C for Notification of Setting Out.Clause 24 stipulates the submission of
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
6 of 34 1/2/2009 21:06
Form D for Notification of Completion ofFoundation.Clause 25.(1) stipulates the submission ofForm E for Notification of Application forCertificate of Fitness.
TEMPORARY CF Clause 26.(1) stipulates the provision and conditions forthe issuance of a TemporaryCertificate of Fitness.
MALAYSIAN STANDARDS Clause 257 Stipulates thatMalaysian Standardsshall supersede that of the
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
7 of 34 1/2/2009 21:06
British Standards
BUILDING FAILURE Clause 258 Stipulates thatthe requirements ofcompliance by the submittingperson in the event of abuilding failure.Clause 258(5) Stipulatesthat in the event of abuilding failure thesubmitting person is alwaysheld responsible.
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
8 of 34 1/2/2009 21:06
BUILDING FAILURE Clause 258(1) stipulates thatin event of building failurewhether during or aftercompletion , qualified person shall within 1 week sent tolocal authority:
a) report of such failure b) explain the cause c) if under construction,state remedial action.
DESIGN REQUIREMENTS Open Space
Abutting a street and
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
9 of 34 1/2/2009 21:06
backlane Clause 32 (1)
Residential: Not less 1/3 of built area
Non-residential: Not less 1/10 of built area
DESIGN REQUIREMENTS Open Space (set-back)
Not abutting a backlane (Cl.32(3)
Min. clear dimension not less than 2.5m (exclude projections)
Abutting a street with no backlane (Cl.33)
Open space situated at rear of building
and extend across full width of lot.
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
10 of 34 1/2/2009 21:06
DESIGN REQUIREMENTS Open Space (set-back)
Detached Building Clause34(1)
Not less than 2m from projections toboundary lotNot less than 4m between buildingsunless same lot.
Projections over street forbalconies/verandah (Clause37)
Projection = width of street (m) 10 m
2
Max. projection 1.25 m clear of approvedline of street
- 5 m above level of road
- between 2.5m and 5m projectionsnot more than 500mm.
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
11 of 34 1/2/2009 21:06
DESIGN REQUIREMENTS FOOTWAY Clause 38(1)Width of verandahway/footway
- not less than 2.25m - columns max depth withinthe footway- 600mm. - change in level steps notmore than 150mm(riser)275mm(tread). - pedestrian ramp not lessthan 1:10
DESIGN REQUIREMENTS
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
12 of 34 1/2/2009 21:06
NATURAL LIGHTING &VENTILATION Clause 39
Not less 10% floor area WindowsNot less 5% floor area Openings
Not less 15% floor area WindowsNot less 10% floor area Openings
Not less 20% floor area WindowsNot less 10% floor area Openings
0.2m2 per w.c, Urinal - Toilets
Residential
Hospital
School
DESIGN REQUIREMENTS AIR WELLS Clause40(1)
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
13 of 34 1/2/2009 21:06
Minimum size:
2 Storey building 7m2
4 Storey building 9m2
6 Storey building 11m2
8 Storey building 13m2
> 8 Storey building 15m2 Min width 2.5m
DESIGN REQUIREMENTS
AIR WELLS Clause 40(2) Minimum size for W.C,Toilets, Bathrooms
2 Storey building 3.5m2
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
14 of 34 1/2/2009 21:06
4 Storey building 4m2
6 Storey building 4.5m2
8 Storey building 5m2
> 8 Storey building 5.5m2
Min width 2.0m
DESIGN REQUIREMENTS MIN AREAS OF ROOMSRESIDENTIAL HABITABLEROOM (Cl.42)
1st room min. area 11m2
2nd room min. area 9.3m2
Others min. area 6.5m2
Kitchen min. area
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
15 of 34 1/2/2009 21:06
4.5m2 Min width 1.5m2
DESIGN REQUIREMENTS
MIN. DIMENSIONS OF ROOMS(CL. 43)
W.C, Toilet Bathroom Minwidth 0.7m2
Min Length 1.5m2 Toilet with bathroom Minarea 2m2
Min width 0.7m2 Bathroom - Min Area
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
16 of 34 1/2/2009 21:06
1.5m2
Min width 0.75m2
DESIGN REQUIREMENTS MIN. HEIGHT OF ROOMS Clause 44 RESIDENTIAL Living / Bedroom min. height 2.5m
Kitchen min. height 2.25m
Toilet/Verandah/
Porch/ Garage min. height 2.0m
SHOPHOUSE Ground floor min. height 3.0m
1st Floor above min. height 2.5m
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
17 of 34 1/2/2009 21:06
DESIGN REQUIREMENTS MIN. HEIGHT OF ROOM -Clause 44SHOPHOUSE - Depth >10.5m Ground floor min. 3.0m
1st floor above min.2.55m SCHOOL/HOSPITAL/FACTORY Ground Floor min. 3.0m
1st Floor above min. 3.0m
DESIGN REQUIREMENTS
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
18 of 34 1/2/2009 21:06
MIN. HEIGHT OF ROOMPUBLIC RESORT (Clause 45) Ground Floor min. 3.5m Balcony, Toilet, Corridors min. 3.0m OTHER BUILDINGS (Clause46) Ground floor min. 3.0m
1st floor above min.2.75m
DESIGN REQUIREMENTS Clause 46 - MIN. HEIGHT OFROOMS IN OTHER
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
19 of 34 1/2/2009 21:06
BUILDINGS HABITABLE ROOMS Min. Height 2.0m BASEMENT/COVEREDCARPARK, COVEREDGARDEN Min Height 2.5m VERANDAHWAY Min. height 3.0m
PART 6 CONSTRUCTIONALREQUIREMENTS
Clause 81 - FILLING UPGROUND
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
20 of 34 1/2/2009 21:06
On rubbish dump ground etc
clear debri & fill up with hill earth 0.305mthick
Clause 86(1) - PARTY WALLMasonry, insitu concrete min. width200mmRC, protected steel frame min. width100mmLoad bearing wall - min. width 100mm
Min. Height Not less 230mm
CONSTRUCTIONALREQUIREMENTS
Clause 88 RECESSRecess made in external/party wall. Wall at back of recess min.
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
21 of 34 1/2/2009 21:06
100mm thick 200mm party wallTotal area recess - max. of superficial areaof wallSide of recess - max.300mm
CONSTRUCTIONALREQUIREMENTS
STAIRCASEClause 106 Dimension ofstaircaseRiser < 180mm
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
22 of 34 1/2/2009 21:06
Thread < 255mm Width of staircase accordingto 7th schedule min 700mm(fire staircase)Depth of landing > width ofstaircase
CONSTRUCTIONALREQUIREMENTS
STAIRCASEClause 107 -Handrail
Staircase > 4 risers 1 Handrail min.
Staircase > 2225mm width to providehandrail
@ equal space
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
23 of 34 1/2/2009 21:06
Staircase > 1100mm width to
(other than residential) provide handrail on
each side of staircase
CONSTRUCTIONALREQUIREMENTS
STAIRCASEClause 107 - Handrail < 100mm from face offinished wall surface - Height 825mm 900mmfrom nosing of thread > 900 at landing
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
24 of 34 1/2/2009 21:06
CONSTRUCTIONALREQUIREMENTS
STAIRCASEClause 108(1) - MAX FLIGHT
Residential Landing depth less than1.8m shall provide verticalintervals max. 4.25m
Other buildings - max. 16risers
CONSTRUCTIONALREQUIREMENTS
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
25 of 34 1/2/2009 21:06
STAIRCASEClause 168 staircaseEvery upper floor shall havemeans of egress via at least 2staircase Except provided inCl.194.Width should be maintainedthroughout its length incl.landingDoors giving access tostaircase shall not encroachthe width of staircase orlandingHandrail within the staircasemax width 75mm
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
26 of 34 1/2/2009 21:06
CONSTRUCTIONALREQUIREMENTS
STAIRCASE
CLAUSE 194 -Single Staircase
Max. height of building 12mComply with;
a) Element of structure FRP min. 1hr
b) Office and domestic purposes only
Except:
Ground storey used for shops/carpark
Provided:
i) Wall enclosure staircase main entrance
returned to dist min. 450mm alongfrontage
ii) Max travel dist. 12m
iii) Staircase from grd to 1st flr separated byall min FRP 2hrs.
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
27 of 34 1/2/2009 21:06
PART 7 (Fire Requirements) Clause 137 Compartment floorrequirement. a) building height more than 30m
b) floor height more than 9m
Clause 138 Walls and floorsconstructed as compartmentwall/floors a) institutional building
b) wall/floor separating flat/maisonette
c) wall/floor separating part of building fromany part of same building.
d) floor over a basement storey
PART 7 (Fire Requirements) Clause 148 Requirement to
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
28 of 34 1/2/2009 21:06
compartment wall & floorNo opening shall be made except:
a) Doors used complies:
FRP hr for wall separating flat/maisonette
FRP as required
b) Opening for a protected shaft
c) opening for ventilation duct
d) opening for a pipe to comply Cl.141
e) opening for refuse chutes min. FRP 1hr.
PART 7 (Fire Requirements) Clause 165 Travel distance measured along the centre lineof natural path of travel ,starting 0.3m from most remotepoint of occupancy, curving
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
29 of 34 1/2/2009 21:06
obstruction with 0.3m clearanceand ending at the storey exit.
Open space dist. to exitmeasured from most remotepoint of occupancy providedthe direct distance not exceed2/3 travel distance.Individual rooms (max. 16person)- travel distance max.15m
PART 7 (Fire Requirements) Clause 173 Exit doors
All exit doors shall beopenable from the inside
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
30 of 34 1/2/2009 21:06
without use of a key or effort.Exit doors shall closeautomatically when releasedand all door devices shallrelease the doors upon powerfailure or actuation of firealarm.
PART 7 (Fire Requirements) Clause 197 Protected lobbies
Provided to serve staircasesin buildings exceeding 18mwhere staircase enclosuresnot ventilated.Buildings exceeding 45mprotected staircase shall be
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
31 of 34 1/2/2009 21:06
pressurised.Protected lobbies may beomitted if staircasepressurised.
PART 8 (fire alarm/ detection/ extinguishment & access)
Clause 229 means of egressand firefighting buildingheight exceed 18.3m. Shall provided:
Fire fighting lobbiesFire fighting staircaseFire fighting fire liftFire fighting dry/wet
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
32 of 34 1/2/2009 21:06
PART 8 (fire alarm/ detection/ extinguishment & access)
Clause 230 - Installation of Dryrising system > 8.3m (Height of building)< 30.3m (Height of building) Clause 231 - Installation ofWet rising system> 30.3m (Height of building)
PART 8 (fire alarm/ detection/ extinguishment & access)
Clause 232 Wet or dry rising
UBBL 1984 http://72.14.235.132/search?q=cache:oJrs-23lMzIJ:rakan1.jkr.gov.my/...
33 of 34 1/2/2009 21:06
system for building underconstruction.Where rising system required at least 1riser shall be installed when building underconstruction reached a height above thelevel of bomba pumping inlet. Location to beadjacent to useable staircase.Where height building requires wet risersystem shall provide:
Fire pumpWater storage tanksWater main connections