40
Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

Revision V1R0 • 10/2020

Alarm Control unit for flammable gases

INSTRUCTION MANUAL

Page 2: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

2

www.dalemans.com |

Copyright © 2020 by DALEMANS s.a.

Revision V1R0 • 10/2020

Any reproduction, partial or full, of this document by means of any process whatsoever without prior written consent from

DALEMANS s.a. is strictly prohibited.

Warning

All information contained in this document is non-contractual

and subject to change without notice.

We also encourage you to regularly check the availability of a new version on our website: http://www.dalemans.com Please contact your distributor in case of doubt,

Dalemans s.a.

Rue Jules Mélotte, 27 • B-4350 Remicourt (Belgium)

Tel. +32(0)19 33 99 43 • Fax +32(0)19 33 99 44

Email: [email protected]

Page 3: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

3

www.dalemans.com |

CONTENTS

1. GENERAL REMARKS ................................................................................. 5

1.1 RESPONSIBILITIES – GUARANTEES ................................................... 5

1.2 SAFETY INFORMATION ............................................................ 6

1.3 ENVIRONMENT ....................................................................................... 7

1.4 U•H1 CONTROL UNIT ............................................................................. 7

2. INSTALLATION OF THE CONTROL UNIT ........................................... 10

2.1 PRECAUTIONS FOR USE .................................................................... 10

2.2 PLACEMENT OF THE U•H1 CONTROL UNIT ..................................... 10

2.3 CONNECTING THE CONTROL UNIT ................................................... 11

2.4 CONNECTING THE DETECTOR ........................................................... 12

2.5 POWER CONNECTION ......................................................................... 12

2.6 CONNECTING THE SIREN ................................................................... 13

2.7 CONNECTING THE RELAYS ............................................................... 13

3. INSTALLATION CONTROL ..................................................................... 14

4. INSTALLATION CONFIGURATION ....................................................... 14

4.1 FACTORY CONFIGURATION ............................................................... 14

4.2 GENERAL MENU .................................................................................. 15

System information ..........................................................................................15

History .....................................................................................................16

Ages of the calibration parameters ........................................................16

Date and time ..........................................................................................16

Configuration of the U•H1 control unit ..................................................17

• Basic standard configuration ................................................................... 17

• Alarm thresholds ..................................................................................... 18

• Relay failsafe mode configuration ........................................................... 18

• Reset mode for level 1 alarms ................................................................ 18

• “Siren” mode ............................................................................................ 18

• Behaviour of the external alarm .............................................................. 19

• Normal state of the external alarm .......................................................... 19

• Errors reset mode .................................................................................... 19

Page 4: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

4

www.dalemans.com |

Status of the system’s elements .................................................................. 20

System tests ................................................................................................. 21

4.3 SERVICE MODE .................................................................................... 21

Entering the password .................................................................................. 21

Service menus ............................................................................................... 22

Advanced system tests ....................................................................... 22

• Output tests ............................................................................................. 22

• Detector simulation ................................................................................. 23

Configuration of the measurement channel ....................................... 24

• Location of the detector ............................................................................ 24

• Predefined locations ................................................................................. 24

• Customised location ................................................................................ 25

• Putting the detector out of service............................................................ 25

Configuration of the external alarm .................................................... 26

• Behaviour of the external alarm .............................................................. 26

• Normal state of the external alarm .......................................................... 27

Maintenance management ............................................................................ 27

• Maintenance interval ............................................................................... 27

• Renewal of the validity of the calibration parameters ............................. 28

Initialization of the detector ............................................................................29

5. SPARE PARTS AND OPTIONS .............................................................. 30

6. TECHNICAL CHARACTERISTICS ........................................................ 31

6.1 General remarks ..................................................................................... 31

6.2 Detectable gases .................................................................................... 31

6.3 Product characteristics ........................................................................ 32

7. ANNEXES ...................................................................................................... 33

Page 5: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

5

www.dalemans.com |

1. GENERAL REMARKS

1.1 RESPONSIBILITIES - GUARANTEES

The installer is required to respect standards and installation provisions.

The installation must be carried out by qualified personnel.

All our equipment is tested and inspected in our workshops before shipping.

This manual must be read carefully by anyone who is or will be responsible for the installation, use

and/or maintenance of this equipment. The guarantee offered by DALEMANS SA will be void if this

equipment is not installed, used and maintained in compliance with these instructions, warnings and

limits of use.

By following these instructions, you guarantee the proper working of the equipment. Please contact

DALEMANS SA for any information about the use or maintenance of this product.

ONLY use original DALEMANS SA parts when performing maintenance on the equipment as described

in this manual. Otherwise you may seriously alter the equipment’s performances.

Any repair or maintenance performed without respecting the procedures described in this manual or

without help from our after-sales service may prevent the equipment from working correctly and, as a

result, prevent guaranteeing the safety of the occupants of the building and installations.

This equipment must be installed indoor, in a clean and dry area. Please use a screen (box) to avoid

any projections of water of polluting agents. Don’t hesitate to contact DALEMANS SA for any additional

information concerning the use of maintenance of this product.

DALEMANS SA cannot be held responsible for any direct or indirect damage as well as any direct and

indirect monetary damages resulting from the failure to comply with these guidelines.

DALEMANS SA guarantees that the U•H1 control unit is free from manufacturing defects and agrees,

at its sole discretion, to repair or replace any component which is defective or likely to become so in the

context of normal use during the warranty period specified in the general terms of sale.

This guarantee does not cover elements such as fuses or any other component provided by a third

party.

Claims concerning the DALEMANS SA product guarantee must be made in the guarantee period

specified above and within 5 calendar days of the discovery of the problem. Please contact your

DALEMANS SA after-sales service to register your claim.

For any additional information, please refer to DALEMANS SA general conditions available on request.

Page 6: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

6

www.dalemans.com |

1.2 SAFETY INFORMATION

Symbol Description

Protective ground terminal

Warning : risk of electric shock

Warning : refer to instruction manual

The following units are used throughout this document

Ah Ampere-hour

VAC Voltage with alternative current in volts

VDC Voltage with continuous current in volts

mA Current in milliampere

W Power in watt

The installation and commissioning of U•H1 control unit must be performed by qualified personnel only.

This qualified personnel is trained and accredited by DALEMANS SA During installation, refer to the

standards in application.

Should the equipment be installed or used in a manner not specified by DALEMANS SA, the protection

provided by the equipment may be impaired.

Modification, disassembling and total or partial destruction of this equipment may invalidate the essential

safety requirements of the whole plant.

For commissioning, please contact DALEMANS SA to arrange an appointment.

Do not open the equipment without disconnecting mains power supply first

Page 7: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

7

www.dalemans.com |

1.3 ENVIRONMENT

The presence of the crossed-out wheelie bin logo on this product means that you are

required to respect the regulations in force concerning the collection and recycling of

electrical and electronic waste.

These provisions aim to preserve the natural resources used to produce this product

and to avoid the dispersal of substances which are potentially harmful to the

environment and human health.

Once this product reaches the end of its life, you MUST discard it by taking it to an approved collection

centre for the recycling of electrical and electronic equipment.

For more information on collection and recycling centres in your region, please contact your local or

regional administration.

1.4 U•H1 CONTROL UNIT

General information

The U•H1 control unit is a fixed automatic alarm management device linked to explosive gas

detection. The 3F+ detector is a fixed device that permanently transmits to the U•H1 control unit a signal

proportional to the gas concentration detected in the air.

Before the LEL1 for the gas observed is reached in the atmosphere, this electronic control unit can act

on safety equipment such as:

• the closure of a gas valve,

• the cut-off of the electrical current,

• the triggering of an alarm,

Two adjustable alarm thresholds are respectively associated with the actions on the relays. These are

relays controlling the safety equipment connected thereto.

A U•H1 control unit output specifically adapted for the connection of a sounder or a flash lamp is

automatically activated in case of alarm. At any time, it may be reset from the U•H1 control unit.

The U•H1 control unit also has internal fault management. Once detected, any abnormal operation of a

detector or the control unit is indicated by an action on the relay signalling the technical fault. This

function guarantees the reliability of the gas detection.

1 LEL: Lower explosive limit: the concentration from which an air/gas mix becomes dangerous.

Danger zone

Detector

Zone may be

dangerous

Valve

Gas stop

Siren Flashing light

Non-danger zone U•H1

control unit

3F+

! It is strongly

recommended to place

the control unit outside

the zone being protected !

Page 8: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

8

www.dalemans.com |

Finally, all or part of the alarms can be notified to an external piece of equipment, such as a central

technical management system, by an action on an additional alarm relay.

At any moment, the status of the control unit and the triggering of each of the functions presented may

be observed visually through the elements on its front:

• A display with a backlight that varies based on the status of the U•H1 control unit and

providing an explanation of this status.

• A set of colour LEDs providing more specific information on these functions.

• An audible buzzer, which can be reset, is activated in the event of an alarm or by error

function.

Display interface

LED

LED indicators

“Power” LED The control unit is supplied by the main power.

“Fault” LED Presence of a technical fault connected to the fault

relay or not.

“Inhibit” LED The control unit is in a particular operating mode:

The measurement of the gas concentrations and the

alarm management still takes place, but the status

of the alarm relay is unchanged. This mode

spontaneously stops after 15 minutes of

inactivity.

Keypad

LED Indicators

Display

Page 9: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

9

www.dalemans.com |

Display

The current status of the U•H1 control unit is indicated by information messages on the display and a coloured backlight.

When an alarm is present, only alarm messages are displayed. Any messages associated with a technical fault is no longer present.

Keypad

Allows movement within a menu or within a selection

Allows entry to a sub menu or to the action associated with the selected menu item

Allows exiting a sub menu and return to the parent menu

ENTER

Allows entry in configuration mode, confirmation of a parameter change or starting the

action associated with the selected menu item

ESC

Allows exiting the configuration menu completely or to abandon the current parameter

change and return to the parent menu

RESET 1 x

Allows turning the audible alarm and the transistor output off (potentially connected to

an alarm)

RESET 2 x

Allows:

- - resetting an alarm if the gas concentration returns below the threshold which

triggers it.

- - resetting the errors still indicated but no longer ongoing.

Backlighting Off Green Yellow Red

Mode Sleep No alarm Maintenance Alarm

Message Cyclical display:

• “No Alarm” to report the absence of an alarm.

• Maintenance date: “Next maintenance”

• Gas concentrations values (LEL percentage) observed by the detector.

Maintenance date if exceeded:

“Maintenance needed “.

Cyclical display of alarms:

• List of level-1 alarms if

no level 2 alarm

“Gas presence”

• List of level 2 alarms

“Gas alarm”

Technical fault

Cyclical display:

• List of errors and

technical fault

Note:

The display’s backlighting goes into sleep mode after 60 seconds. As soon as the keypad is used,

as soon as an alarm is detected or as soon as a technical fault appears, the U•H1 control unit goes

out after sleep mode.

Page 10: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

10

www.dalemans.com |

2. INSTALLATION OF THE CONTROL UNIT

2.1 PRECAUTIONS FOR USE

For your safety, before undertaking any action, always make sure that the equipment is disconnected

from mains power supply.

The U•H1 control unit’s enclosure can only be opened by qualified personnel.

The U•H1 control unit must be placed in a room without any explosive atmosphere and within easy

reach.

As the U•H1 control unit’s enclosure is reversible, it may be set up to receive electrical cables from the

top or bottom. To guarantee optimal sealing, cables should be received from the bottom.

The equipment must be placed in a dry and clean environment.

A set of holes are provided in the enclosure. To install the cable glands, it is necessary to remove the

machined parts from these holes using a flat-head screwdriver and a mallet.

Important note:

Never place the U•H1 control unit, the alarm and the cable for the detector in the vicinity of :

- a high-voltage cable or a power cable,

- coaxial cable or transmitter,

- welding station or frequency regulator.

2.2 PLACEMENT OF THE U• H1 CONTROL UNIT

The U•H1 control unit must be attached to a clean and damp-free wall. Two attachment systems, a

drilling diagram and a quick installation guide are provided with the equipment. You can opt for

attachment via the enclosure or via the 4 fixing feets provided.

Optionally, it is also possible to attach the U•H1 control unit to a DIN rail. Please contact your

DALEMANS SA representative for more information.

If the attachment method without feet is chosen, attach the enclosure using the 4 holes located in the

corners of the enclosure using a PZ2 screwdriver with a minimum length of 150 mm.

For the different stages, refer to the quick installation guide provided in the packaging.

Before drilling these holes using a tool, it is recommended to remove the

electronic part to avoid any accidental damage.

Page 11: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

11

www.dalemans.com |

2.3 CONNECTING THE CONTROL UNIT

The installation and the electrical connections must be carried out by qualified personnel in accordance

with the instructions set out in this manual and on the diagram shown on the back of the cover of the

U•H1 control unit.

It is recommended to place the circuit breaker in the vicinity of the equipment.

All installations must comply with locally-applicable standards and regulations, notably the cable type

and section of the wires to be used.

During electrical connection of the terminals, make sure the wires are attached to the connectors. Use

a maximum tightening torque of 0.60 Nm. In order to achieve electrical safety, wires going from the

enclosure’s cable glands to the board’s terminal blocks shall not be longer than 70 mm.

It is recommended to always use wires with a crimping end to avoid any risk of poor electrical contact.

Example of a connection diagram for the U•H1 control unit:

A circuit breaker (2-poles, 6A, 250V (AC)) must be placed on both live and

neutral. See the wiring example below.

Page 12: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

12

www.dalemans.com |

2.4 CONNECTING THE DETECTOR

In the majority of cases the design of the U•H1 control unit makes the use of a shielded cable

useless. However, if the cable is exposed to magnetic interference (transmitters, welding station,

switching relay, HF transmitter disturbance of the cable conduit, computer network, etc.), the use of a

shielded cable is recommended.

To connect the detector, use a flexible 3-conductors cable with a section between 0.75 and 1.5 mm2.

The distance between the detector and the control unit is limited to 300 m.

Connect the terminals from each detector in the U•H1 control unit be respecting the following order:

Detector terminal Central terminal

24V 24V

GND GND

OUT IN

Warnings:

- Never use two or more wires to increase the wire section. The cable must be a single length (without connection) and properly attached to suitable terminals. Use a maximum tightening torque of 0.60 Nm.

- Never place the cable of a detector in proximity to a coaxial cable or next to a power cable and certainly not in the same conduit or in the same wire path.

2.5 POWER CONNECTION

The U•H1 control unit must be able to be isolated electrically in case of intervention (protection by a

breaker or a 2-way switch).

The power for the U•H1 control unit and that for the gas valve(s) must be connected on the same circuit.

Make sure that the power conductors are always fixed together and separated from the low-voltage

conductors.

The power cables for the 230 V section must have a minimum section of 1.5 mm2.

Page 13: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

13

www.dalemans.com |

U•H1 Control Unit is a class I equipment. It must always be connected to ground using the protective

ground terminal in accordance with the instructions in this manual.

First connect protective ground wire using terminal 3. Then connect the 230V mains voltage to

terminals 1 and 2; see diagram below.

2.6 CONNECTING THE SIREN

The siren’s connection cables must meet the same requirements as those of the detector (see §

connecting the detector).

Connect the terminals + (terminal 21) and – (terminal 22) from the sounder device to the U•H1 control

unit. Respect the polarity to avoid damaging the sounder device.

To connect and adjust the tone of the alarm, refer to the sounder's instruction manual.

2.7 CONNECTING THE RELAYS

The U•H1 control unit has a technical fault relay and 3 relays addressable by the alarms. It is possible

to connect different types of servo controls thereto such as a sounder device, a valve, a flash lamp, etc.

Page 14: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

14

www.dalemans.com |

3. INSTALLATION CONTROL

Wiring check

Check that each wire is positioned correctly and that the terminals are tightened properly.

Voltage verification

To power your U•H1 control unit on, make sure that the terminals are tightened properly and that the

supply voltage is within the accepted operating voltage range accepted by the U•H1 control unit.

4. INSTALLATION CONFIGURATION

The configuration mode for the U•H1 control unit comprises a set of menus allowing the consultation or

modification of the system’s parameters. These menus are accessible regardless of the status of the

U•H1 control unit by pressing “Enter” on the keypad (if the display is in sleep mode, this mode must be

exited first by pressing any button). Once in this mode, the colour of the display’s backlight changes

to blue.

The U•H1 control unit automatically exits from the configuration mode after a period of inactivity of 1

minute (no action on the keypad) and returns to the suitable mode (normal mode if no errors or alarms;

error mode if an error is present without an alarm; alarm mode if an alarm is present).

4.1 FACTORY CONFIGURATION

The U•H1 control unit comprises a factory configuration which can be adapted based on the installation in question.

By default, the U•H1 control unit is configured as follows:

• 1 detector,

• relays addressed as is:

o 1 first relay (terminals 7 - 9 on the diagram) associated with alarm of level 1,

o 2 finals relays (terminals 10 - 15 of the diagram) functioning simultaneously and associated with alarm of level 2,

• relay not in failsafe mode, i.e. not powered at rest and powered in case of alarm,

• gas concentration thresholds set at 20% LEL for alarm level 1 and 40% LEL for level 2,

• the input for an external alarm is disabled,

For commissioning, please contact DALEMANS SA to arrange an appointment !

Page 15: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

15

www.dalemans.com |

As standard, the channel is deactivated. Hence it is necessary to initialize the detector to activate the

channel to which it is connected (see § "Initialization of the detector").

4.2 GENERAL MENU

Service Menu

Service mode

Info Menu

System information

Status Menu

Status of the system’s elements

Tests Menu

System tests

Navigation in the menus is via the directional buttons on the keypad and the selection using “Enter”

(see the § “Keypad” paragraph).

System information

The information menu provides information concerning all the control unit’s elements. With the exception

of the date, all these elements are accessible as read-only.

View history

Consultation of the control unit’s history

Calibration age

Consultation of the age of the calibration parameters for

the detector

AREA

Alarm Level 1 20%LEL

Relay 1

Alarm Level 2 40%LEL

Relay 3 Relay 2

Channel 1

Page 16: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

16

www.dalemans.com |

Firmware version

Vx.yy Firmware version of the control unit

Date & time

dd/mm/yyyy hh:mm Control unit date and time

Configuration info

Sub menu providing control unit configuration information

History

All events occurring in the control unit are saved in a permanent memory of the U•H1 control unit.

The “Up” and “Down” buttons allow chronological navigation within these events.

The “Esc” button can be used to abandon the modification and return to the information menu.

Age of the calibration parameters

The calibration parameters for a 3F+ detector need to be verified after a period which can be set in the

U•H1 control unit. Once this period has passed, a maintenance alert is indicated.

The number of days since the last calibration is displayed.

Example of display of the age of the calibration parameters:

Heater

154 days

The “Esc” button can be used to abandon the consultation and return to the information menu.

Date and time

The date and time of the U•H1 control unit are stored in a volatile memory. They are only refreshed

when the control unit is powered.

If the date or time of the U•H1 control unit are incorrect, using the “Enter” button on the keypad accesses

editing mode:

• “Date & Time setting” is displayed

• The cursor flashes on the field value of the date or time to be modified.

Date & time setting

dd/mm/yyyy hh:mm

Page 17: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

17

www.dalemans.com |

The “right” and “left” buttons change the field to be edited:

• the day

• the month

• the year

• the time

• the minutes

The “Up” and “Down” buttons change the value of the selected field.

Once the date and time are updated, the modification is confirmed using the “Enter” button.

The “Esc” button can be used to abandon the modification and return to the information menu.

Configuration of the U•H1 control unit

All the elements of the U•H1 control unit configuration can be consulted using the “Configuration

Info” sub menu:

Base configuration

Default config. Basic standard configuration

Alarm thresholds

Alarm thresholds

Failsafe config.

Relays failsafe mode configuration

Level 1 alarm mode

Latching Reset mode for level 1 alarms

Level 1 siren mode

Not in siren mode “Siren” mode for level 1 alarms

Ext. alarm config.

Disabled Behaviour of the external alarm

Error reset mode

Automatic

Errors configuration mode

• Basic standard configuration

This is the standard configuration that has been selected during commissioning of the U•H1 control unit.

However, special configuration parameters can be modified relative to this basic configuration.

For details of the standard configurations, contact a DALEMANS SA representative.

Page 18: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

18

www.dalemans.com |

• Alarm thresholds

The elements in this sub menu can be used to view the gas concentration value associated with the

threshold of the different alarm levels.

• Relay failsafe mode configuration

The safety mode of a relay defines its status when it is at rest:

- Not in failsafe mode: the relay is not powered at rest.

- Failsafe mode: the relay is powered at rest.

The failsafe mode of an alarm relay is unset by default. The failsafe mode of each alarm relay is

independently configurable.

• Reset mode for level 1 alarms

The reset mode for an alarm specifies the way in which it is reset:

- Latching mode: when the cause of the alarm has disappeared, the alarm remains activated until a manual action (“RESET”) is performed on the control unit.

- Non-latching mode: when the cause of the alarm has disappeared, the alarm is automatically

reset and disappears

Only the reset mode for the level 1 alarms can be configured. A level 2 alarm always needs to be

manually reset.

In manual reset mode, the U•H1 control unit can display an alarm message when the gas concentration

has already returned to under the alarm threshold.

Heater

Gas alarm 13%LEL

This configuration element applies to all level-1 alarms.

• “Siren” mode

The “Siren” mode designates a specific behaviour similar to that of the “Siren” output of the U•H1 control

unit or its audible indicator: while the alarm is still active (the gas concentration is still greater than the

alarm threshold), it is possible to reset the actions on the relays.

Note:

The “Technical Fault” relay is always in failsafe mode.

Activation of this configuration is to be performed by a technician approved by DALEMANS SA.

Note:

The “latching” mode of the relays is the default mode.

Page 19: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

19

www.dalemans.com |

This configuration element applies to all level-1 alarms.

• Behaviour of the external alarm

The reaction of the U•H1 control unit to a change of state on the “External Alarm” input can be

configured as follows:

- Disabled: a change of the input’s state will have no effect,

- Addresses the level 1 alarm ("Set alarm level 1"): a change of the input’s state activates the

level 1 alarm of the U•H1 control unit,

- Addresses the level 2 alarm ("Set alarm level 2"): a change of the input’s state activates the

level 2 alarm of the U•H1 control unit.

- Addresses both alarm levels ("Set alarm levels 1&2"): a change of the input’s state activates

the levels 1 and 2 of the alarm of the U•H1 control unit.

• Normal state of the external alarm

The external alarm, when it is active, is triggered by a change of state on the U•H1 control unit which is

dedicated to the external alarm’s connection. This configuration element specifies the state of this input

at rest and, as a result, the nature of the state change which triggers the alarm.

The possible states are as follows:

• “normally closed”: at rest, the circuit connected to the input is closed. The external alarm is

thus activated when the circuit is opened.

• “normally opened”: at rest, the circuit connected to the input is open. The external alarm is

activated when the circuit is closed.

• Errors reset mode

The U•H1 Control Unit has an internal fault management. Once detected, any abnormal operation of the

U•H1 Control Unit or D•TEX 3F+ detector is notified by an action on the relay signaling the technical

defect.

The mode to reset a technical fault specifies how it is reset:

- as standard, the U•H1 Control Unit is configured for automatic reset.

Error reset mode

Automatic

Note:

This mode does not apply to level-2 alarms.

Page 20: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

20

www.dalemans.com |

When the cause of the error restored, the message is automatically reset and disappears.

- Manual reset.

In the manual acknowledge mode, although the cause of the error has disappeared and the system is restored, the error remains notified until a manual action (“2x RESET”) is performed on the U•H1 control unit.

Status of the system’s elements

This menu is used to consult the status of the elements of the U•H1 control unit.

Sub menu Content

Channel setting

Gives, the status of the channel:

- “disabled“: channel inactive in the

eyes of the system

- display of measurements

Outputs

Gives the status of the outputs: - output inactive in the eyes of the

system (“disabled”)

- enabled

(« activated » / « not activated »)

Supply Mentions if the control unit is connected to the distribution network. Pressing the “Enter” button gives the supply voltage.

Temperature

Mentions the temperature of the U•H1 control unit. Pressing the "Enter" key gives the minimum, current and maximum temperature.

Error reset mode

Manual acknowledge

Note:

All events occurring in the U•H1 control unit are saved in a permanent control unit memory

(cf. § “View history”).

Activation of the “Manual acknowledge” is to be performed by a technician approved by

DALEMANS SA.

Outputs

Channel setting

Power supply

xxxx

Temperature

xx °C

Page 21: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

21

www.dalemans.com |

System tests

This test menu is used to verify the proper operation of the display or the LEDs on the front.

The gas detection operates normally during the execution of a test.

Led tests

Display tests

Sub menu Content

LED tests

Starts a sequence with the LEDs

flashing one after another.

Display tests

Starts a sequence which displays a

character in each position of the

display while varying the colour of the

backlight.

4.3 SERVICE MODE

Service mode is used to modify the parameters of the U•H1 control unit which requires no specific

knowledge of the gas detection field or, in case of error or omission, cannot lead to a gas detection-

related risk.

For a more in-depth analysis of your situation, please contact someone approved by DALEMANS SA.

The service menu is protected by the following password:

Access code : 110

Entering the password

When entering the service menu, the display enters the password editing mode:

Enter password

_

The “Up” and “Down” buttons allow modification of the value of the selected character. The “Right”

button is used to move to the next character. The “Left” button is used to return to the previous character.

The movement from one character to another is accompanied by the concealment of the character that

is not selected. This means that only the character being edited is legible.

Enter password

**0

Page 22: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

22

www.dalemans.com |

The “Enter” button confirms the entered password. If it has been encrypted correctly, the service menu

is active and the tests sub menu item (“Tests Menu”) is displayed.

If the password entered is incorrect, the general menu remains active and the service sub menu item

(“Service Menu”) is displayed again.

Service menus

Tests Menu

Advanced system tests

Channel setting

Configuration of the channel of the U•H1 control unit

External alarm Menu

Configuration of the external alarm

Maintenance Menu

Maintenance management

Initialize sensor

Initialisation of the detector

Advanced system tests

• Output tests

Testing an output from the U•H1 control unit consists of activating it and, as a result, activating the servo

controls connected thereto (a gas valve, a sounder, etc). This test doesn’t allow an output already

activated to be deactivated. Once the output test option is selected, it is necessary to choose the output

to be tested using the “Up” and “Down” buttons.

The status of the output selected is shown each time.

Fault relay

Not activated Technical fault relay

Alarm relay 1

Not activated Alarm relay 1

Alarm relay 2

Not activated Alarm relay 2

Page 23: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

23

www.dalemans.com |

Alarm relay 3

Not activated Alarm relay 3

Siren output

Not activated

Transistor output dedicated to the sounder device

The selection is validated using the “Enter” button. A confirmation is then requested before switching

the output.

Fault relay

Ready to activate?

The “Enter” button confirms the activation of the selected output. The latter is activated as well as the

equipment connected thereto.

Fault relay

Activated

The output remains activated as long as the test function remains active.

This ends:

• either by a manual action (pressing “Esc”).

• or because the maximum manual activation time of the output (15 minutes) has expired.

At any point, the “output test” function may be interrupted and abandoned by pressing “Esc”. The test

sub menu is then activated again and displays the output test function.

• Detector simulation

It is possible, without disconnecting the detector connected to the measurement channel of the U•H1

control unit, to simulate the gas detection.

Once the function has been selected, the simulation begins:

- the initial value of the simulation is the gas concentration currently measured on the detector,

- the cursor flashes on the figure which can be modified (the tens or the units).

The value of simulated gas concentration is modified using the “Up” and “Down” buttons.

The “right” and “left” buttons move from one figure to another of the gas concentration value with the

first figure allowing modification by tens and the second by unit.

Page 24: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

24

www.dalemans.com |

Pressing the “Esc” button ends the simulation.

Configuration of the measurement channel

Once a measurement channel is selected, this sub menu can be used:

• to assign a location to the detector

• to put the detector out of service

• Location of the detector

In the U•H1 control unit, the location can be used to identify the connected detector. Changing the

parameters for locating the detector can be found in the sub-menu « Channel location » on the U•H1

control unit.

A location can be assigned to the detector in 2 different ways:

• predefined location (“Preset preset”)

• customised location (“Custom location”)

These 2 methods can be combined by customising a location that has been chosen beforehand from

the list of predefined locations.

• Predefined locations

The U•H1 control unit offers a list of predefined locations. The latter exists in 3 languages (English,

Dutch and French). For details of the list, please refer to annex 4 - Predefined locations.

The selection of the location from the list takes place using the “Up” and “Down” buttons.

When the location names allow (display limited to 20 characters), an index from 1 to 9 may be added

using the “Right” and “Left” buttons.

The confirmation of the location choice takes place using the “Enter” button.

The choice of location may be interrupted and abandoned using the “Esc” button.

Note:

During a simulation, the alarms management works normally. Then, if the simulated gas

concentration exceeds an alarm threshold, this alarm is triggered, and the associated outputs are

activated as well as the servo controls connected thereto.

Page 25: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

25

www.dalemans.com |

• Customised location

The location of the detector can be customised or modified completely. During selection of the

“Customised location” function, the U•H1 control unit enters the location editing mode.

Location channel 1

Channel

The cursor flashes on the character being edited.

The “Up” and “Down” buttons can be used to modify the selected character (refer to annex

“Available characters list”).

The confirmation of the location choice takes place using the “Enter” button.

The “Esc” button interrupts and abandons the modification of the location.

• Putting the detector out of service

Putting the detector out of service may be useful when waiting for intervention from a qualified person.

When the “Put out of order” function is selected, the U•H1 control unit displays the current status of the

selected detector.

Out of order setting

Initialized

The detector can be put out of service using the “Enter” button. Confirmation is then requested.

Out of order setting

Put out of order ?

Pressing “Enter” confirms putting the detector out of service. The technical fault relay switches if it has

not yet.

Out of order setting

Out of order

At any point, putting the detector out of service may be interrupted and abandoned by pressing “Esc”.

The configuration menu of the selected detector becomes active again.

The return to service of a detector occurs in the same way.

Note:

A detector out of order is viewed as a technical fault and the fault relay switches !

Page 26: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

26

www.dalemans.com |

Configuration of the external alarm

This sub menu is used to configure the behaviour of the external alarm as well as the normal state of

the thereto dedicated input.

Extern. alarm Config.

Set alarm level 1 Behaviour of the external alarm

External alarm state

Normally closed

Normal state of the input dedicated to the external alarm

• Behaviour of the external alarm

For details of possible configurations, refer to “Behaviour of the external alarm” paragraph in the

information menus.

Selection of the configuration of the external alarm:

Select configuration

Disabled

Select configuration

Set alarm level 1

Select configuration

Set alarm level 2

Select configuration

Set alarm levels 1&2

Navigation within the external alarm configurations is via the “Up” and “Down” buttons.

The configuration is then selected using the “Enter” button. Confirmation of the configuration change is

requested.

Select configuration ?

Set alarm levels 1

Pressing “Enter” confirms the configuration change.

Page 27: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

27

www.dalemans.com |

At any point, the configuration of the external alarm may be interrupted and abandoned by pressing the

“Esc” button. The configuration menu of the external alarm becomes active again.

• Normal state of the external alarm

For details of possible statuses, refer to § “Normal state of the external alarm” paragraph in the

information menus.

Modification of the normal state currently defined is via the “Enter” button. The change to the opposite

normal state is then proposed:

External alarm state

Set normally opened ?

Pressing “Enter” confirms the change of the normal state of the input dedicated to the external alarm.

The “Esc” button can be used to abandon the modification and return to the information menu.

Maintenance management

The maintenance menu is used to configure the functions related to the management of the

maintenance alert:

• the maintenance interval,

• the renewal of the validity of the calibration of a detector.

• Maintenance interval

By default, the maintenance period for the detector is set at 13 months in the U•H1 control unit.

Under certain conditions (particular atmospheres, fixed or variable temperature and humidity conditions,

etc), it may be useful to adjust the maintenance period. It is possible to adjust it in an interval between

3 and 26 months.

Once the modification of the maintenance interval is selected, the period currently configured in the

U•H1 control unit is displayed and the cursor flashes on the first digit (the tens) of the value in months.

Maintenance interval

13 months

To guarantee optimal monitoring of the installation, annual maintenance

is recommended. Therefore, changing the value of this interval is not recommended.

The maintenance alert does not indicate a problem with the system but rather acts as a

reminder. However, renewing the validity of the calibration of the detector may have a

significant impact on the gas detection function and can lead to the malfunctioning of the

U•H1 control unit if the detector is no longer calibrated correctly.

Page 28: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

28

www.dalemans.com |

The value of the period is modified using the “Up” and “Down” buttons.

The buttons “Right” and “Left” move from one figure to another in the period value with the first figure

allowing modification by tens and the second by unit.

Pressing the “Enter” button selects the value chosen for the calibration period. A confirmation is requested.

Set interval ?

09 months

Pressing the “Enter” button confirms the modification of the calibration interval.

The “Esc” button can be used to abandon the modification and return to the information menu.

• Renewal of the validity of the calibration parameters

Ordinarily, the renewal of the validity of the detector’s calibration parameters takes place automatically

during its calibration by a technician approved by DALEMANS SA. The maintenance period for the

calibrated detector is then reset.

In certain cases, the detector may have been verified by an approved inspection body and the validity

of the calibration of the detector may then be extended.

The detector is displayed with the number of days since its last calibration and the value of the full gas

concentration scale that the detector can estimate.

heater

346 days 98%LEL

Pressing the “Enter” button confirms the detector selection. Confirmation of the renewal of the validity

of the calibration of the sensor selected is requested.

heater

Renew calibration ?

Pressing the “Enter” button confirms the renewal of the calibration validity for the detector. The date of

the next maintenance may then be modified. The “Esc” button can be used to abandon the modification

and return to the information menu.

Note:

This menu is only available if the renew calibration is activated. Enable or disable this configuration

is to be performed by a technician approved by DALEMANS SA.

Page 29: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

29

www.dalemans.com |

Initialization of the detector

When the U•H1 control unit leaves the factory, the detector channel is deactivated. An initialization of

the detector is necessary to activate the channel to which the detector is connected. Via this sub menu,

the U•H1 control unit starts the verification of the channel, performs an offset initialization of the

measurement and displays the situation visible thereto.

During the detection and calibration phase :

• a spinning symbol reports the initialization process

• a ‘-‘ symbol (dash) for a channel seen without the detector or with the detector that the offset

initialization failed for

• a ‘*’ symbol (star) for a channel seen with a connected and initialization detector

The initialized detector is displayed.

Detected sensor 1

*

The U•H1 control unit asks for a confirmation of the detected configuration.

Sensor initialized ?

*

Pressing the “Enter” button confirms the new configuration of the U•H1 control unit. The channel with

the connected detector is then enabled.

The “Esc” button can be used to abandon the modification and return to the information menu.

Initialization done

Page 30: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

30

www.dalemans.com |

5. SPARE PARTS AND OPTIONS

Please find below the list of spare parts available for sale:

Name Item reference

Cover U•H1 with display 000568

Flat cable for U•LINE display BASCAB00015

Enclosure for U•H1 control unit (base) 000406

Motherboard U•H1 000407

Fixing feet kit U•H1 BOI00000259

DIN rail fixing kit BOI00000260

Page 31: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

31

www.dalemans.com |

6. TECHNICAL CHARACTERISTICS

6.1 GENERAL REMARKS

The explosive power of a gas-air mixture depends on the gas concentration in the air. If this

concentration is too low, it is said that the mixture is too weak to explode. If, by increasing the gas

concentration, the mixture becomes rich enough to explode, we have reached the Lower Explosive

Level – L.E.L.

At the Upper Explosive Level - U.E.L., the mixture becomes too rich and cannot explode due to a lack

of oxygen and simply burns.

A DALEMANS SA gas detection control unit helps you to prevent any risk of explosion in an atmosphere

where the risk of a gas leak exists.

6.2 DETECTABLE GASES

The U•H1 control unit has been specially designed to be placed in a heater room environment where

there is a risk of leakage of the following gases:

Gas * Formula Density (air = 1) CAS N° Position

Cracked gas - 0,47 -

High Natural gas - 0,68 -

Methane CH4 0,55 74-82-8

Butane C4H10 2,05 74-98-6

Low

Propane C3H8 1,56 106-97-8

* List not exhaustive

COMBUSTION

Page 32: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

32

www.dalemans.com |

6.3 PRODUCT CHARACTERISTICS

This product has been designed and manufactured in Belgium according to the quality charter of DALEMANS SA.

U•H1 control unit

Manufacturer Design and fabrication DALEMANS SA

Power supply Mains 220 - 240 V(AC) ~ 50Hz

Power 15 W max

External circuits isolation

Primary-secondary isolation 3600Vrms

Relays isolation between contacts and coil 4000V(AC)

Enclosure Material Plastic PC UL94 V-0

Dimensions (excluding PE)* 264 x 233 x 72 mm*

Weight 1.2 kg

Protection Degree IP (IEC/EN 60529) IP65

Reversibility Rotation of 180°

Standard mounting 4 screws or mounting lugs

Optional mounting Mounting on DIN rail

Connection Cable inlets 2 x M20 and 4 x M16

Screwed terminals 1 x 2.5 mm² or 2 x 1.5 mm² per terminal

Inputs Detector 1

Type pf detector 3F+ (analog 3-wire)

Wiring length up to 300 m

Self-powered external alarm input 24vdc 1

Outputs Alarms: Addressable changeover relays Max. 230V / 3A 3

Fault: changeover relay Max. 230V / 3A 1

Transistor alarm 24 V(DC) - 200 mA max

Interface Display LCD backlighting of a variable colour

Voltage indicator Green LED

Technical fault indicator Yellow LED

Inhibition indicator Yellow LED

Navigation and configuration Using a membrane keypad

Main functions Configurable alarm levels 2

Access protection using password YES

Maintenance alert YES

Display of events and statuses YES

Customisable detector locations YES

Test and inhibition functions YES

Operating conditions

Temperature -10°C to +40°C

Humidity & Pressure 10 à 90% RH (non-condensing) 90-110kPa

Altitude Max. 2000 m

Certifications Electromagnetic compatibility (EMC) EN 50270 (type 1)

Low-voltage safety EN 61010-1

Marking CE, RoHS

* Refer to ANNEX 5

Page 33: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

33

www.dalemans.com |

7. ANNEXES

CONTENTS

ANNEX 1 – PREDEFINED LOCATIONS ............................................................... 34

ANNEX 2 – CHARACTERS AVAILABLE WHEN EDITING THE TEXT ................ 35

ANNEX 3 – INFORMATION MENUS ..................................................................... 36

ANNEX 4 – SERVICE MENUS .............................................................................. 37

ANNEX 5 – DIMENSIONS (EXCLUDING PE) ...................................................... 38

Page 34: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

34

www.dalemans.com |

ANNEX 1 – PREDEFINED LOCATIONS

ENGLISH TEXT TEXTE FRANÇAIS NEDERLANDSE TEKST

Heater room Chaufferie Stookplaats

Gas room Local gaz Gas lokaal

Boiler room Local boilère Boiler lokaal

Technical room Local technique Technische ruimte

Venting room Local ventilation Ventilatie lokaal

Technical duct Gaine technique Technische schacht

Technical floor Etage technique Technisch verdiep

Kitchen Cuisine Keuken

Laundry room Buanderie Wasserij

Corridor Couloir Gang

Cellar Cave Kelder

Heater Chaudière Ketel

Left heater Chaudière gauche Ketel links

Right heater Chaudière droite Ketel rechts

Middle heater Chaudière milieu Ketel midden

Venting Ventilation Ventilatie

Gas valve Vanne gaz Gasklep

Co-generation Co-génération WKK

Gas meter Compteur Gaz Gasteller

Venting duct Vide Ventilé Kruipkelder

Gas pipe Conduite Gaz Gasleiding

Gas boiler Boilère gaz Gasboiler

Oven Four Gasoven

Moistener Humidificateur Stoombevochtiger

Extractor hood Hotte Dampkap

Dryer Sèche-linge Droogkast

Cooker Cuisinière Gaskeuken

Page 35: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

35

www.dalemans.com |

ANNEX 2 – CHARACTERS AVAILABLE FOR EDITING THE TEXT

- The numbers 0 - 9

- The letters of the alphabet lowercase

- The letters of the alphabet in uppercase

- Vowels with accents and ç in lowercase

- The dash and the special character @

Page 36: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

36

www.dalemans.com |

ANNEX 3 – INFORMATION MENUS

Page 37: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

37

www.dalemans.com |

ANNEX 4 – SERVICE MENU

Page 38: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

38

www.dalemans.com |

ANNEX 5 – DIMENSIONS (EXCLUDING PE)

Page 39: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

39

www.dalemans.com |

Notes

Page 40: U•H1 INSTRUCTION MANUAL EN V1R0 · Revision V1R0 • 10/2020 Alarm Control unit for flammable gases INSTRUCTION MANUAL

40

www.dalemans.com |

Rue Jules Mélotte 27 • B-4350 Remicourt (Belgium)

Tel.: +32 (0)19 33 99 43 • [email protected]

www.dalemans.com

Alarm Control unit for flammable gases

INSTRUCTION MANUAL