BID CLARIFICATION #02 TO: CONTRACTORS PREPARING COST ESTIMATES RE: PLANS DATED JULY 17, 2016 DATE: AUGUST 2, 2016 SUBJECT: HOPE HARBOR OF OKLAHOMA CITY-54 UNIT BUILDING OKLAHOMA, OK ARCHITECT PROJECT #15-10980 PLEASE TAKE THIS BID CLARIFICATION INTO CONSIDERATION IN PREPARING YOUR CONSTRUCTION COST BREAKDOWN.
TYSON AND BILLY ARCHITECTS, P.C. _______________________________________ RONALD G. BILLY JR., AIA, LEED AP BD + C
THIS BID CLARIFICATION CONSISTS OF ANSWERS TO BIDDERS QUESTIONS AND ADDITIONAL DRAWINGS ORIGINALLY OMITTED FROM THE BID SET. DUE TO TIME CONSTRAINTS ADDITIONAL SPECIFICATION SECTIONS HAVE BEEN ADDED FROM A DIFFERENT PROJECTS IN WHICH THE HEADERS AND FOOTERS WILL BE REVISED AND INSERTED IN THE ISSUED FOR CONSTRUCTION SET. Bid Clarification #02 General Clarifications
1. Door frame elevations as referenced in the drawings to all have 2” frames and 2” heads
2. Vapor barrier to be deleted from face of exterior walls. Details on Sheet A311 to have the vapor barrier deleted
3. Concrete stops required at exterior door openings
4. Self-leveling underlayment to be gypsum system on second and third floors
5. Retaining walls will require railings as indicated on the drawings
6. Foundation WF2.0 is to be at a minimum depth of 2’-6”
7. Spec section 00 7300 – 2.10 states “Contractor shall obtain any and all construction permits required by the City of North Chicago, Illinois, with the Architect providing procedural assistance.” Remove “City of North Chicago, Illinois” and replace with “City of Oklahoma City, Oklahoma.”
8. Floor joist shall be TJI’s as indicated on the architectural drawings and corresponding fire rated assembly
2
9. There will not be a gazebo in this project and delete all references to one.
10. Door types will be as follows
a. F: Flush
b. DBL-F: Double Flush
c. HG: Half Glass
11. Unit Room Finish Schedule change Carpet 3 to Carpet 2. Carpets listed in the attached specification section.
12. Brick allowance for Monarch size will be $2,100/1000
Mechanical Clarifications
1. Radiation damper to be utilized at ceiling registers. Drawings to follow.
2. Apartment: Unit A (typical) will have a supply duct size 12x10 for 600 CFM max and Apartment B (typical) will have supply duct size 12x12 for 750 CFM max.
3. Condenser unit can be mounted on prefabricated pads
Electrical Clarifications
1. Electrical meters to be located at the exterior of the building.
2. All apartment distribution is to be single phase
3. The use of 150 Amp panels acceptable in each apartment
4. Fire alarm system to be an Addressable system – Simplex or approved equal
5. Electrician responsible for installing CATV lines and receptacles and phone/data lines and receptacles
6. This is an independent living facility and a nurse call system is not required
Plumbing Clarifications
1. Pex piping is acceptable if the pex-a chanel is utilized and is approved by the local jurisdiction
2. Section 33 1116 Site Water Distribution: PVC piping is acceptable
3
HVAC Clarifications
1. Delete Sheet H310, Sheet H330, and Sheet H340. Delete references to Sheet H310, Sheet H330 and Sheet H340 from the Sheet Index. The project will use an entirely electric building and the abovementioned Sheets are not included.
Specification Attachments
1. Section 04 2000 Masonry
2. Section 09 3000 Tile
3. Section 09 6800 Carpeting (Delete in its entirety from the original document and add the attached section)
Drawing Attachments
1. Sheet E100 (Delete in its entirety from the original document and add the attached section)
2. Sheet E210 (Delete in its entirety from the original document and add the attached section)
3. Sheet E310 (Delete in its entirety from the original document and add the attached
section)
4. Sheet E500 (Delete in its entirety from the original document and add the attached section)
5. Sheet E601 (Delete in its entirety from the original document and add the attached
section)
6. Sheet E602 (Delete in its entirety from the original document and add the attached section)
7. Sheet E700 (Delete in its entirety from the original document and add the attached
section)
8. Sheet H210 (Delete in its entirety from the original document and add the attached section)
9. Sheet H600 (Delete in its entirety from the original document and add the attached
section)
10. Sheet H601 (Delete in its entirety from the original document and add the attached section)
11. Sheet P600 (Delete in its entirety from the original document and add the attached
section)
4
END BID CLARIFICATION #02
SECTION 04816
MASONRY VENEER
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Clay Facing Brick.
B. Mortar.
C. Reinforcement and Anchorage.
D. Installation of Lintels.
E. Accessories.
1.02 RELATED SECTIONS
A. Section 05500 - Metal Fabrications: Loose steel lintels.
B. Section 06100 - Rough Carpentry: Wood stud backup for masonry veneer.
C. Section 07620 - Sheet Metal Flashing and Trim
D. Section 07650 - Flexible Flashing
E. Section 07900 - Joint Sealers: Backing rod and sealant at control and expansion joints.
1.03 ALLOWANCES
A. See Section 01210 - Allowances, for cash allowances affecting this section.
B. This allowance includes purchase and delivery of bricks. Installation is not included in the allowance but is specified in this section and is part of the Contract Sum/Price.
1.04 REFERENCES
A. ACI 530/ASCE 5/TMS 402 - Building Code Requirements for Masonry Structures; American Concrete Institute International.
B. ACI 530.1/ASCE 6/TMS 602 - Specification For Masonry Structures; American Concrete Institute International.
C. ASTM A 82 - Standard Specification for Steel Wire, Plain, for Concrete Reinforcement.
D. ASTM A 153/A 153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.
E. ASTM A 615/A 615M - Standard Specification for Deformed and Plain Billet-Steel Bars for Concrete Reinforcement.
F. ASTM C 91 - Standard Specification for Masonry Cement.
G. ASTM C 216 - Standard Specification for Facing Brick (Solid Masonry Units Made From Clay or Shale).
H. ASTM C 270 - Standard Specification for Mortar for Unit Masonry.
I. ASTM D 226 - Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing.
J. IMIAWC (CW) - Recommended Practices & Guide Specifications for Cold Weather Masonry Construction; International Masonry Industry All-Weather Council.
Spring Ridge Senior Living 04-6690
04816 MASONRY VENEER
04816 - 1
Owner: __________ Architect: __________ Contractor: __________ Bonding:__________
K. IMIAWC (HW) - Recommended Practices & Guide Specifications for Hot Weather Masonry Construction; International Masonry Industry All-Weather Council.
L. UL (FRD) - Fire Resistance Directory; Underwriters Laboratories Inc..
1.05 SUBMITTALS
A. See Section 01300 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide data for masonry units, mortar, and masonry accessories.
C. Samples: Submit four samples of facing brick units to illustrate color, texture, and extremes of color range.
D. Manufacturer's Certificate: Certify that masonry units meet or exceed specified requirements.
1.06 QUALITY ASSURANCE
A. Comply with provisions of ACI 530/ASCE 5/TMS 402 and ACI 530.1/ASCE 6/TMS 602, except where exceeded by requirements of the contract documents.
1.07 REGULATORY REQUIREMENTS
A. Conform to applicable code for standard requirements for fire rated masonry construction.
1.08 DELIVERY, STORAGE, AND HANDLING
A. Deliver, handle, and store masonry units by means that will prevent damage and contamination by other materials. Follow manufacturers recommendations.
B. Deliver all materials in sufficient quantity and time to maintain approved construction schedule. Deliver all packaged materials in manufacturer's original containers, with all labels and markings intact and legible. Remove damaged materials and containers immediately from site.
C. Store all products in a secure, dry location, out of way of construction operations. Store materials on pallets, a minimum of 4" off of the ground. Prevent intermixing of granular materials.
1.09 ENVIRONMENTAL REQUIREMENTS
A. Maintain materials and surrounding air temperature to minimum 40 degrees F prior to, during, and 48 hours after completion of masonry work.
B. Cold Weather Requirements: Comply with recommendations of IMIAWC (CW).
C. Maintain materials and surrounding air temperature to maximum 90 degrees F prior to, during, and 48 hours after completion of masonry work.
D. Hot Weather Requirements: Comply with IMIAWC (HW).
1.10 EXTRA MATERIALS
A. See Section 01600 - Product Requirements, for additional provisions.
B. Provide 50 of each size, color, and type of masonry units for Owner's use in maintenance of project.
PART 2 PRODUCTS
2.01 BRICK UNITS
A. Facing Brick: ASTM C 216, Type FBS, Grade SW.1. Color and texture as selected by Architect.2. Actual size: 3-5/8" x 3-5/8" x 15-5/8".
04816 MASONRY VENEER
Spring Ridge Senior Living 04-6690
04816 - 2
Owner: __________ Architect: __________ Contractor: __________ Bonding:__________
3. Special shapes: Molded units as required by conditions indicated, unless standard units can be sawn to produce equivalent effect.
B. Cast Stone Medallions as manufactured by Pineapple Grove Designs: www.pineapplegrove.com Product number 24SM-027 - 24"x24" square medallion Quadrant Design. Color to be selected by Architect from manufactures complete line of standard colors.
C. Trenwyth Prairie stone architectural concrete masonry units for use in all areas called out as cast stone on the contract drawings, including but not limited to banding, sills, and stone caps. Color to be selected by the Architect from manufacturer's standard. Installed according to manufacturer's printed instructions.
D. Cast Stone Veneer at Fireplace in first floor lounge. Coronado Honey Ledge as manufacturered by Coronado Products: www.coronado.com. Color to be selected by the Architect from manufacturer's standard. Install according to manufacturer's printed instructions.
2.02 MORTAR MATERIALS
A. Masonry Cement: ASTM C 91 Type S. One part portland cement, one half part lime. No more than four and one half parts sand, measured damp and loose. Compressive strength of 1800 psi at 28 days; Type M, high strength mortar with 2500psi compressive strength below grade, other types as required by application.1. Colored mortar: Premixed cement as required to match Architect's color sample.
B. Water: Clean and potable.
C. Accelerating Admixture: Nonchloride type for use in cold weather.
D. Moisture-Resistant Admixture: Water repellent compound designed to reduce capillarity.
2.03 REINFORCEMENT AND ANCHORAGE
A. Reinforcing Steel: ASTM A 615/A 615M, grade 60 (420) yield grade, deformed billet bars; galvanized.
B. Joint Reinforcement: Truss type; ASTM A 82 steel wire, hot dip galvanized after fabrication to ASTM A 153/A 153M, Class B; 0.1483 inch deformed side rods with 0.1483 inch cross rods; width as required to provide not more than 1 inch and not less than 1/2 inch of mortar coverage on each exposure.1. Manufacturers:
a. Dur-O-Wal: www.dur-o-wal.com.b. Hohmann & Barnard, Inc: www.h-b.com.c. Masonry Reinforcing Corporation of America: www.wirebond.com.d. Substitutions: See Section 01600 - Product Requirements.
C. Masonry Veneer Anchors: 2-piece anchors that permit differential movement between masonry veneer and structural backup, hot dip galvanized to ASTM A 153/A 153M, Class B.1. Anchor plates: Not less than 0.105 inch thick, designed for fastening to structural backup
through sheathing by two fasteners; provide design with legs that penetrate sheathing and insulation to provide positive anchorage.
2. Wire ties: Triangular shape, 0.1875 inch thick.3. Vertical adjustment: Not less than 5-1/2 inches.4. Seismic Feature: Provide lip, hook, or clip on end of wire ties to engage or enclose not less
than one continuous horizontal joint reinforcement wire of 0.1483 inch diameter.
2.04 FLASHINGS
A. Flashing Materials:As specified in Section 07620 and/or Section 07650.
2.05 ACCESSORIES
Spring Ridge Senior Living 04-6690
04816 MASONRY VENEER
04816 - 3
Owner: __________ Architect: __________ Contractor: __________ Bonding:__________
A. Preformed Control Joints: Extruded Neoprene Rubber, closed cell virgin material. Provide with corner and tee accessories, fused joints.1. Manufacturers:
a. Dur-O-Wal: www.dur-o-wal.com.b. Heckmann Building Products, Inc: www.heckmannbuildingprods.com.c. Hohmann & Barnard, Inc: www.h-b.com.d. Substitutions: See Section 01600 - Product Requirements.
B. Joint Filler: Closed cell polyethylene; oversized 50 percent to joint width; self expanding with backer rod. 1. Manufacturers:
a. Dur-O-Wal: www.dur-o-wal.com.b. Heckmann Building Products, Inc: www.heckmannbuildingprods.com.c. Hohmann & Barnard, Inc: www.h-b.com.d. Substitutions: See Section 01600 - Product Requirements.
C. Building Paper: ASTM D 226, Type I ("No. 15") asphalt felt.
D. Weeps: Open head joints or rope wicks as indicated. 3/8" 100% cotton sash rope.
E. Cavity Mortar Diverter: Semi-rigid polyethylene or nylon mesh blocks, sized to fill bottom of wall cavity and suspend mortar droppings above weep/cavity vents to allow cavity drainage. Provide system manufactured by Masonry Reinforcing Corporation of America, www.wirebond.com.1. "Mortar Net" Weep Vent 1" thick x 10" height x 5'-0" length trapezoidal configuration
designed to allow moisture to flow downward in the cavity or collar joint to masonry flashing and weeps and hence to the exterior.
F. Cleaning Solution: Non-acidic, not harmful to masonry work or adjacent materials.
2.06 MORTAR MIXES
A. Mortar for Unit Masonry: ASTM C 270, Proportion Specification.1. Masonry below grade and in contact with earth: Type M.2. Exterior, non-loadbearing masonry: Type S.3. Interior, non-loadbearing masonry: Type N.
PART 3 EXECUTION
3.01 WEATHER PROTECTION
A. Cold weather: Heat mortar water and sand, enclose walls and provide temporary heat as recommended by BIA Tech Notes 1, 1A, 1B, and 1C.
B. Hot Weather: Use Mortar within 1-1/2 hour after mixing for ambient 80 degree F or above.
3.02 EXAMINATION
A. Verify that field conditions are acceptable and are ready to receive masonry.
B. Verify that related items provided under other sections are properly sized and located.
C. Verify that built-in items are in proper location, and ready for roughing into masonry work.
D. Beginning of installation means installer accepts existing conditions.
3.03 FIRE RATING
A. Where rating are indicated, provide assemblies identical to tested assemblies and accepted by authorities having jurisdiction.
3.04 PREPERATION
04816 MASONRY VENEER
Spring Ridge Senior Living 04-6690
04816 - 4
Owner: __________ Architect: __________ Contractor: __________ Bonding:__________
A. Direct and coordinate placement of metal anchors supplied to other sections.
B. Provide temporary bracing during installation of masonry work. Maintain in place until building structure provides permanent bracing.
3.05 COURSING
A. Establish lines, levels, and coursing indicated. Protect from displacement.
B. Maintain masonry courses to uniform dimension. Form vertical and horizontal joints of uniform thickness.
C. Brick Units:1. Bond: Running. Except where areas of special coursing , patterns, and bonding are
indicated on drawings.2. Coursing: Two units and two mortar joints to equal 12 inches.3. Mortar Joints: Uniform 3/8", Tooled Concave.
D. Provide full bed, head and collar joints except at weepholes.
E. Keep cavity clean of mortar droppings and other materials during construction. Strike joints facing cavity flush.
3.06 PLACING AND BONDING
A. Lay masonry units in full bed of mortar, with full head and collar joints, except at weepholes, uniformly jointed with other work.
B. Lay hollow masonry units with face shell bedding on head and bed joints.
C. Buttering corners of joints or excessive furrowing of mortar joints is not permitted.
D. Remove excess mortar as work progresses. Keep cavity clean of mortar dropping and other material during construction. Strike joints facing cavity flush.
E. Interlock intersections and external corners.
F. Do not shift or tap masonry units after mortar has achieved initial set. Where adjustment must be made, remove mortar and replace.
G. Perform job site cutting of masonry units with proper tools to provide straight, clean, unchipped edges. Prevent broken masonry unit corners or edges.
H. Isolate top joint of masonry veneer from horizontal and vertical structural framing members or support angles with compressible joint filler.
3.07 WEEPS/CAVITY VENTS
A. Install weeps in veneer walls at 24 inches on center horizontally above through-wall flashing, above shelf angles and lintels, at bottom of walls, and ledges.
B. Install cavity mortar diverter at base of cavity as recommended by manufacturer to prevent mortar droppings from blocking weep/cavity vents. Drainage system to be continuous at the base of the wall.
C. Do not permit mortar to drop or accumulate into cavity air space or to plug weep/cavity vents.
3.08 REINFORCEMENT AND ANCHORAGE - MASONRY VENEER
A. Install horizontal joint reinforcement 16 inches on center.
Spring Ridge Senior Living 04-6690
04816 MASONRY VENEER
04816 - 5
Owner: __________ Architect: __________ Contractor: __________ Bonding:__________
B. Stud back-Up: Secure veneer anchors to stud framed back-up and embed into masonry veneer at maximum 2.0 sq ft of wall surface per anchor. Place additional anchors at perimeter of openings and ends of panels, so maximum spacing of anchors is 8 on center.
C. Seismic Reinforcement: Connect veneer anchors with continuous horizontal wire reinforcement before embedding anchors in mortar.
3.09 MASONRY FLASHINGS
A. Whether or not specifically indicated, install masonry flashing to divert water to exterior at all locations where downward flow of water will be interrupted.1. Extend flashings full width at such interruptions and at least 4 inches into adjacent masonry
or turn up at least 4 inches to form watertight pan at non-masonry construction.2. Remove or cover protrusions or sharp edges that could puncture flashings.3. Seal lapped ends and penetrations of flashing before covering with mortar.
B. Prepare masonry surfaces smooth and bed flashing in mortar.
C. Extend metal flashings through exterior face of masonry and turn down to form drip.
D. Lap end joints of flashings at least 4 inches and seal watertight with mastic or elastic sealant.
3.10 LINTELS
A. Install loose steel lintels over openings.
B. Maintain minimum 8 inch bearing on each side of opening.
3.11 CONTROL AND EXPANSION JOINTS
A. Do not continue horizontal joint reinforcement through control and expansion joints.
B. Provide expansion joint as detailed and at spacing no greater than 30 feet O.C. at locations approved by architect.
C. Install preformed control joint device in continuous lengths. Seal butt and corner joints in accordance with manufacturer's instructions.
D. Size control joint in accordance with Section 07900 for sealant performance.
E. Provide expansion joints as detailed and at spacing no greater than 30'-0" o.c.at locations approved by Architect.
3.12 BUILT-IN WORK
A. As work progresses, build-in hollow metal frames, window frames, steel angle, lintels, wood nailing strips, anchor bolts, plates, and other items supplied by other sections.
B. Build-in items plumb and true.
C. Bed anchors of hollow metal frames in mortar joints. Fill frame voids solid with mortar. Fill masonry cores with grout minimum 12 inches from framed openings.
D. Do not build-in organic materials which will be subject to rot or deterioration.
3.13 TOLERANCES
A. Maximum Variation From Unit to Adjacent Unit: 1/16 inch.
B. Maximum Variation from Plane of Wall: 1/8 inch in 20 ft.
C. Maximum Variation from Plumb: 1/8 inch in 20 ft.
D. Maximum Variation from Level Coursing: 1/8 inch in 20 ft.
04816 MASONRY VENEER
Spring Ridge Senior Living 04-6690
04816 - 6
Owner: __________ Architect: __________ Contractor: __________ Bonding:__________
E. Maximum Variation of Joint Thickness: 1/8 inch in 3 ft.
3.14 DAMAGED UNITS
A. Remove and replace damaged units
B. Enlarge holes in mortar.
C. Prepare joints to receive sealant.
3.15 CUTTING AND FITTING
A. Cut and fit for sleeves, pipes, conduit, and grounds. Coordinate with other sections of work to provide correct size, shape, and location.
B. Obtain approval from Architect/Engineer prior to cutting or fitting masonry work not indicated on drawings or where appearance or strength of masonry work may be impaired.
3.16 CLEANING
A. Remove excess mortar and mortar smears as work progresses.
B. Replace defective mortar. Match adjacent work.
C. Clean brick using bucket and brush method in compliance with BIA Tech Note 20.
D. Use non-metallic tools in cleaning operations.
3.17 PROTECTION OF FINISHED WORK
A. Without damaging completed work, provide protective boards at exposed external corners that are subject to damage by construction activities.
END OF SECTION
Spring Ridge Senior Living 04-6690
04816 MASONRY VENEER
04816 - 7
Owner: __________ Architect: __________ Contractor: __________ Bonding:__________
Legacy Manor of Mason City II 09 300014-10590 TILE
July 2014 09 3000 - 1
SECTION 09 3000 - TILEPART 1 GENERAL1.01 SECTION INCLUDES
A. Ceramic tile for floor applications.B. Ceramic accessories.
1.02 RELATED REQUIREMENTSA. Section 03 5400 - Cast Underlayment.B. Section 09 6800 - Carpeting: Transition strip at edge of tile.
1.03 REFERENCE STANDARDSA. TCNA (HB) - Handbook for Ceramic, Glass, and Stone Tile Installation - Version; 2013.1.
1.04 SUBMITTALSA. See Section 01 3000 - Administrative Requirements, for submittal procedures.B. Product Data: Provide manufacturers' data sheets on tile, mortar, grout, and accessories.
Include instructions for using grouts and adhesives.C. Selection samples: Sample of actual tile and grout for selection.D. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.E. Maintenance Data: Include recommended cleaning methods, cleaning materials, stain removal
methods, and polishes and waxes.1.05 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the types of productsspecified in this section, with minimum 5 years of documented experience.
B. Installer Qualifications: Company specializing in performing tile installation, with minimum of 5years of documented experience.
1.06 DELIVERY, STORAGE, AND HANDLINGA. Protect adhesives from freezing or overheating in accordance with manufacturer's instructions.
1.07 FIELD CONDITIONSA. Do not install solvent-based products in an unventilated environment.B. Maintain ambient and substrate temperature of 50 degrees F during installation of mortar
materials.PART 2 PRODUCTS2.01 TILE
A. Manufacturers: All products by the same manufacturer.1. Dal-Tile Corporation: www.daltile.com.2. Substitutions: See Section 01 6000 - Product Requirements.
B. Glazed Porcelain Floor Tile: For Unit Bathrooms1. Product: Exquisite2. Pattern: Brickwork Square (Running Bond)3. Moisture Absorption: Less than 0.5%4. Size and Shape: 12 inch square5. Thickness: 5/16 inch6. Edges: Square7. Dynamic Coefficient of Friction: Greater than or equal to .42 (wet) per A137.1-2012
section 9.68. Breaking Strength: Greater than 275 lbs9. Abrasion Resistance: 4
Legacy Manor of Mason City II 09 300014-10590 TILE
July 2014 09 3000 - 2
10. Surface Finish: Glazed11. Colors: To be selected by Architect from manufacturer's standard range
C. Glazed Porcelain Floor Tile: For Common Areas1. Product: Vivaldi Glazed Porcelain Tile by Lea USA2. Pattern: Staggered and varied to create wood floor look3. Moisture Absorption: Less than 0.5%4. Size and Shape: 6x245. Thickness: min 5/16 inch6. Edges: Square7. Static Coefficient of Friction: Greater than or equal to .6 (wet) per ASTM c10288. Breaking Strength: Greater than 250 lbs9. Abrasion Resistance: 410. Surface Finish: Glazed11. Colors: To be selected by Architect from manufacturer's standard range
2.02 TRIM AND ACCESSORIESA. Ceramic Accessories: Glazed finish, same color and finish as adjacent field tile; same
manufacturer as tile.2.03 SETTING MATERIALS
A. Provide setting materials made by the same manufacturer as grout.B. Polymer fortified thin set mortar: complying with ANSI A118.4 and ANSI A118.11.
1. Products:a. LATICRETE International, Inc; LATICRETE 254 Platinum: www.laticrete.com.b. Substitutions: See Section 01 6000 - Product Requirements.
2.04 GROUTSA. Manufacturers:
1. LATICRETE International, Inc; LATICRETE SpectraLOCK PRO Grout:www.laticrete.com.
2. Substitutions: See Section 01 6000 - Product Requirements.B. Epoxy Grout: ANSI A118.3 chemical resistant and water-cleanable epoxy grout.
1. Applications: Where indicated.2. Color(s): As selected by Architect from manufacturer's full line.3. Products:
a. LATICRETE International, Inc; LATICRETE SPECTRALOCK PRO Premium Grout:www.laticrete.com.
b. Substitutions: See Section 01 6000 - Product Requirements.C. Colors: To be selected by Architect from manufacturer's standard range.
2.05 THIN-SET ACCESSORY MATERIALSA. Tile contractor to supply and install one of the following at unit bathrooms located on the 2nd
and third floor below tile per manufactures instructions.1. Waterproofing Membrane at 2nd and 3rd floor unit bathrooms : Specifically designed for
bonding to cementitious substrate under thick mortar bed or thin-set tile; complying withANSI A118.10 and ANSI A118.12a. Type: Fluid-applied.b. Thickness: 25 mils, minimum, dry film thickness.
2. Waterproofing Membrane: Fluid applied neoprene complying with ANSI A118.10.3. Sheet Applied, pliable, bonded waterproof membrane made of Polyehtylene; adhered to
substrate with appropriate mortar.4. Other waterproofing systems designed for tile/thin set applications for architects review.
Legacy Manor of Mason City II 09 300014-10590 TILE
July 2014 09 3000 - 3
PART 3 EXECUTION3.01 EXAMINATION
A. Verify that sub-floor surfaces are smooth and flat within the tolerances specified for that type ofwork and are ready to receive tile.
B. Verify that sub-floor surfaces are dust-free and free of substances that could impair bonding ofsetting materials to sub-floor surfaces.
C. Verify that concrete sub-floor surfaces are ready for tile installation by testing for moistureemission rate and alkalinity; obtain instructions if test results are not within limits recommendedby tile manufacturer and setting materials manufacturer.
3.02 PREPARATIONA. Protect surrounding work from damage.B. Vacuum clean surfaces and damp clean.C. Seal substrate surface cracks with filler. Level existing substrate surfaces to acceptable
flatness tolerances.3.03 INSTALLATION - GENERAL
A. Install tile and grout in accordance with applicable requirements of ANSI A108.1A throughA108.13, manufacturer's instructions, and TCNA (HB) recommendations.
B. Pattern: All joints aligned or as indicated in part 2. products; no edge tile less than half size.C. Place tile joints uniform in width, subject to variance in tolerance allowed in tile size. Make
grout joints without voids, cracks, excess mortar or excess grout, or too little grout.D. Install ceramic accessories rigidly in prepared openings.E. Sound tile after setting. Replace hollow sounding units.F. Prior to grouting, allow installation to completely cure; minimum of 48 hours or as
recommended by the manufacturer.G. Grout tile joints.
3.04 CLEANINGA. Clean tile and grout surfaces.
3.05 PROTECTIONA. Do not permit traffic over finished floor surface for 4 days after installation. Special attention
required at ground floor where tile is to be installed at main entry and corridor.END OF SECTION
Legacy Manor of Mason City II 09 680014-10590 CARPETING
July 2014 09 6800 - 1
SECTION 09 6800 - CARPETINGPART 1 GENERAL1.01 SECTION INCLUDES
A. Broadloom carpet, direct-glued.B. Entry walk-off carpet, direct-glued.C. Accessories.
1.02 RELATED REQUIREMENTSA. Section 03 3000 - Cast-in-Place Concrete: Restrictions on curing compounds for concrete
slabs and floors to receive adhesive-applied carpet.B. Section 03 5405 - Self-Leveling Underlayment.C. Section 06 2000 - Finish Carpentry: Wood base at perimeter of carpeting.D. Section 09 6500 - Resiliet Flooring: Resilient base at perimeter of carpeting; carpet edge
transition strips.1.03 ADMINISTRATIVE REQUIREMENTS
A. Coordinate with underfloor utility subcontractors to assure that access plates for underfloorutilities are installed flush to top of concrete slabs.
1.04 SUBMITTALSA. See Section 01 3000 - Administrative Requirements, for submittal procedures.B. Shop Drawings: Indicate seaming plan, method of joining seams, direction of carpet pile and
pattern, location of edge moldings and edge bindings .C. Product Data: Provide data on specified products, describing physical and performance
characteristics; sizes, patterns, colors available, and method of installation.D. Samples: Submit two samples 12x12 inch in size illustrating color and pattern for each carpet
material specified.E. Submit two, 4 inch long samples of edge strip for each color specified.F. Submit data documenting VOC content of carpet, cushion, and adhesives; copy of current CRI
Approved Products Listing is acceptable.G. Copies of Warranties: Submit manufacturer warranty and ensure that forms have been
completed in Owner's name and registered with manufacturer.H. Manufacturer's Installation Instructions: Indicate special procedures and perimeter conditions
requiring special attention.I. Maintenance Data: Include maintenance procedures, recommended maintenance materials,
and suggested schedule for cleaning.1.05 QUALITY ASSURANCE
A. Environmental Emissions: Carpet and adhesives shall be labeled with or otherwisedocumented as meeting the Carpet and Rug Institute (CRI) Green Label Plus or Green Labeltesting criteria.
B. Manufacturer Qualifications: Company specializing in manufacturing specified carpet withminimum three years experience.
C. Installer Qualifications: Company specializing in installing carpet with minimum three yearsdocumented experience.
1.06 FIELD CONDITIONSA. Store materials in area of installation for minimum period of 24 hours prior to installation.B. Maintain minimum 70 degrees F ambient temperature 72 hours prior to, during and 24 hours
after installation.
Legacy Manor of Mason City II 09 680014-10590 CARPETING
July 2014 09 6800 - 2
C. Ventilate installation area during installation and for 72 hours after installation.1.07 EXTRA MATERIALS
A. See Section 01 6000 - Product Requirements, for additional requirements.B. Broadloom Carpet: Turn leftover useable carpet pieces to Owner, furnishing at least 20 sq ft of
carpet of each type, color, and pattern installed.1. No carpet piece shall be less than 3x4 feet.
C. Modular Carpet Tile: Turn over to Owner at least 12 carpet tiles matching the tiles installed.1.08 WARRANTY
A. See Section 01 7800 - Closeout Submittals, for additional warranty requirements.B. Provide 10 year manufacturer's replacement warranty against excessive wear.
PART 2 PRODUCTS2.01 MANUFACTURERS
A. Carpet:1. J & J Industries, Inc: www.jjindustries.com. (Contact Heidi Fenoglia:
[email protected])2.02 CARPET
A. Carpet Type 1: Palladian Broadloom 6540 with TitanBac Plus backing by J&J Commercial1. Critical Radiant Flux: Minimum of 0.45 watts/sq cm, when tested in accordance with
ASTM E648 or NFPA 253.2. VOC Content: CRI Green Label Plus certified.3. Dye Method: Solution/Yarn Dyed4. Color: as selected.5. Roll Width: 12 feet6. Max. Electrostatic Charge: 3.0 K.7. Pile Weight: Dialed up to 28 oz/sq yd.
B. Carpet Type 2 (Apt Units): Merge Broadloam 3520 with Endure Plus Cushion Backing by J& JCommercial, conforming to the following criteria:1. Critical Radiant Flux: Minimum of 0.45 watts/sq cm, when tested in accordance with
ASTM E648 or NFPA 253.2. VOC Content: CRI Green Label Plus certified.3. Dye Method: Solution Dyed4. Color: As selected from manufacturer's full range of colors.5. Roll Width: 12 ft.6. Max. Electrostatic Charge: 3.0 Kv at 20 percent R.H.7. Pile Weight: Dialed up to 26 oz/sq yd.
C. Entry Walk-Off Carpet: Coral® Brush Activ Entrance Flooring by Forbo Flooring, Inc. by ForboFlooring, Inc.; www.forbo-flooring.com.1. Description: 100% polyamide, triple-texture, cut-pile yarns providing capillary, scraping
and wiping actions.2. Dye Method: Pigment dyed.3. Width: 2 Meters (79")4. Length: 27.5 Meters (90.22 Feet)5. Gauge: 10mm (0.394”)6. Backing: Water impervious EVERFORT® vinyl.7. Pattern and Color: As selected by Architect from manufacturer's standard patterns and
colors.8. Adhesive: Forbo Flooring, Inc. FRS 885 Adhesive.
D. Contractor is responsible for including appropriate yardage for pattern matches.
Legacy Manor of Mason City II 09 680014-10590 CARPETING
July 2014 09 6800 - 3
2.03 ACCESSORIESA. Sub-Floor Filler: Type recommended by carpet manufacturer.B. Mounting: Direct glue down with waterproof, strippable adhesive.C. Termination strips and transition strips: Heavy duty vinyl or rubber, color as selected.D. Adhesives: Releasable type compatible with materials being adhered; maximum VOC content
of 50 g/L; CRI Green Label certified; in lieu of labeled product, independent test report showingcompliance is acceptable.
E. Seam Adhesive: Recommended by manufacturer.PART 3 EXECUTION3.01 EXAMINATION
A. Verify that sub-floor surfaces are smooth and flat within the tolerances specified for that type ofwork and are ready to receive carpet.
B. Verify that sub-floor surfaces are dust-free and free of substances that could impair bonding ofadhesives to sub floor surfaces.
C. Cementitious Sub-floor Surfaces: Verify that substrates are dry enough and ready for flooringinstallation by testing for moisture and pH.1. Test in accordance with ASTM F710.2. Obtain instructions if test results are not within limits recommended by flooring material
manufacturer and adhesive materials manufacturer.3.02 PREPARATION
A. Prepare floor substrates as recommended by flooring and adhesive manufacturers.B. Remove sub-floor ridges and bumps. Fill minor or local low spots, cracks, joints, holes, and
other defects with sub-floor filler.C. Apply, trowel, and float filler to achieve smooth, flat, hard surface. Prohibit traffic until filler is
cured.D. Clean substrate.
3.03 INSTALLATION - GENERALA. Starting installation constitutes acceptance of sub-floor conditions.B. Install carpet and cushion in accordance with manufacturer's instructions and CRI Carpet
Installation Standard.C. Install carpet in accordance with manufacturer's instructions for direct-glued application.D. Verify carpet match before cutting to ensure minimal variation between dye lots.E. Lay out carpet and locate seams in accordance with shop drawings:
1. Locate seams in area of least traffic, out of areas of pivoting traffic, and parallel to maintraffic.
2. Do not locate seams perpendicular through door openings.3. Align run of pile in same direction as anticipated traffic and in same direction on adjacent
pieces.4. Locate change of color or pattern between rooms under door centerline.5. Provide monolithic color, pattern, and texture match within any one area.6. Lay carpet in adjacent areas in the same direction
F. Install carpet tight and flat on subfloor, well fastened at edges, with a uniform appearance.G. Unsatisfactory Work: Work installed not in accord with manufacturer's instructions, or in a
manner unacceptable to the Architect, will be deemed unsatisfactory and may require removaland relaying at the contractor's expense.
Legacy Manor of Mason City II 09 680014-10590 CARPETING
July 2014 09 6800 - 4
H. No splices in areas less than 12 x 12 ft. One splice per 12 running feet in areas greater than 12x 12 ft.
I. Modular Tiles: Lay symmetrical to axis of room so as to minimize number of tiles less than halfsize. Make joints tight and straight all across room.
3.04 DIRECT-GLUED CARPETA. Double cut carpet seams, with accurate pattern match. Make cuts straight, true, and unfrayed.
Apply seam adhesive to cut edges of woven carpet immediately.B. Apply contact adhesive to floor uniformly at rate recommended by manufacturer. After
sufficient open time, press carpet into adhesive.C. Apply seam adhesive to the base of the edge glued down. Lay adjoining piece with seam
straight, not overlapped or peaked, and free of gaps. Apply seam glue so that it will be over oras high as primary backing.
D. Roll with appropriate roller, minimum 100 pounds, for complete contact of adhesive to carpetbacking.
E. Trim carpet neatly at walls and around interruptions.1. At plates for access to underfloor utilities, cover the plates with section of carpet cut to
match shape of access plate; use compass cutter for round plates.F. Complete installation of edge strips, concealing exposed edges.
3.05 INSTALLATION ON STAIRSA. Use one piece of carpet for each tread and the riser below. Apply seam adhesive to all cut
edges.B. Install carpet with pile direction in the length of the stair.C. Adhere carpet tight to stair treads and risers.
3.06 CLEANING AND PROTECTIONA. Remove excess adhesive from carpet, floor and wall surfaces without damage.B. Upon completion of carpet work, restrict all traffic in finished areas to normal foot traffic for a
minimum of two days.C. Provide and maintain proper protection. Vacuum clean all carpet prior to placing protection.
Place protection continuously with all seams lapped a minimum of 6 inches and taped.Maintain in good condition until directed
D. When directed by the Architect, completely remove all protection and tape, and legally disposeof off site.
E. Clean and vacuum carpet surfaces with an upright beater bar or upright stiff nylon brush typevacuum cleaner.
END OF SECTION
E
T
T
e
l
e
.
R
i
s
e
r
T
T
e
l
e
.
R
i
s
e
r
T
Tele.
Riser
T
Tele.
Riser
W
WM
W
WM
W
WM
W
WM
W
WM
E
ICV
T
Tele.
Riser
T
Tele.
Riser
T
Tele.
Riser
T
Tele.
Riser
T
Tele.
Riser
Electric
Box
Electric
Box
TU
G
T
U
G
T
U
G
T
U
G
TU
G
T
U
G
T
U
G
TU
G
T
U
G
TU
G
T
U
G
T
U
G
TU
G
TUG
TUG
TUG
TU
G
T
U
G
T
U
G
T
U
G
T
U
G
TU
G
TUG
TUG
TUGTUG
TUG
T
U
G
T
U
G
Electric
Box
Electric
Box
OH
OH
OH
OH
OH
O
H
O
H
O
H
O
H
O
H
T
T
e
l
e
.R
i
s
e
r
T
Tele.
Riser
SS
SS
SS
SS
SS
SS
SS SSSS
25' Existing Building Setback
10' Existing Utility Easement
15
' E
xistin
g U
tility E
ase
me
nt
2
5
' E
x
is
tin
g
B
u
ild
in
g
S
e
tb
a
c
k
L
Y
R
E
W
O
O
D
L
A
N
E
Fence Enchroaches
a max of 2.2'
W
W
W
W
W
W
C.O.
C.O.
SS
SS
WW
W
8"
6"
6"
WW
W
W
W
W
W
W
W
C.O.
C.O.
SS
SS
FF
FF
FF
FF
F
F
FF
FF
F FF
FF
WW
WW
W WW
WW
6"
6"
S3
S3
S3 S3
S2
S2
S2
S2
S2
S7
S6
S2
S2
S4
S4
S4
S1
S3
S5
3 #10, 1" C.3 #10, 1" C.3 #10, 1" C.
2 #8, #10, 1" C. 2 #8, #10, 1" C.
3 #10, 1" C. 3 #10, 1" C.
3 #10, 1" C.
2 #8, #10, 1" C.
2 #8, #10, 1" C.
2 #8, #10, 1" C.
2 #8, #10, 1" C.
2 #8, #10, 1" C. 3 #10, 1" C.
3 #10, 1" C.
2 #8, #10, 1" C.
3 #10, 1" C.
PC
2 #8, #10, 1" C.
LPA:23,25
S7
PTZ
6'-0"
TYP.
EXPIRES: 07-31-2016
28881
L
O
R
N
I
C
E
S
E
D
P
K
A
M
O
L
A
O
H
R
E
E
S
F
S I
O
L
A
N
E
NE
G
I
N
Robert A.
Boellner
Sheet No:
of sheets
E100
ELE
CT
RIC
AL S
IT
E P
LA
N
1/16" = 1'-0"
1
ELECTRICAL SITE PLAN
KEY NOTES
1
2
GENERAL NOTES
1. SEE SHEET E001 FOR ELECTRICAL SYMBOLS AND ABBREVIATIONS.
2. WIRING SHOWN ON PLANS INDICATES ONE POSSIBLE SOLUTION. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMINGVOLTAGE DROP CALCULATIONS FOR THE ACTUAL WIRING AND ROUTING INSTALLED.
COORDINATE ACTUAL LOCATION AND MOUNTING HEIGHT OF PHOTOCELL WITH ARCHITECT FOR OPTIMUM OPERATION.
PROVIDE POLE WITH DUAL TENON YOKE FOR POLE MOUNTED PAN/TITL/ZOOM CAMERA BY OTHERS.
1
2
HO
PE
H
AR
BO
R O
F O
KLA
HO
MA
C
IT
Y
54 IN
DIP
EN
DE
NT
LIV
IN
G A
PA
RT
ME
NT
S
P14-4800
07-13-2016
Author
Checker
Tyso
n a
nd
B
illy A
rch
ite
cts, P
.C
.
40
00
M
orsa
y D
rive
Ro
ckfo
rd
, IL
6
11
07
(8
15
) 2
29
-8
22
2
FA
X: (8
15
) 2
29
-8
21
8
ww
w.tyso
na
nd
billy.co
m
Project N
um
ber
REVISION DATE
Date
Drn.
Appd.
BO
ND
IN
G C
O.
CO
NT
RA
CT
OR
OW
NE
RA
RC
HIT
EC
T
63
0 N
. C
HU
RC
H S
T. S
UIT
E 1
01
Ro
ckfo
rd
, IL
6
11
03
(8
15
) 5
40
-4
73
3
FA
X: (8
15
) 9
65
-2
49
1
AN
CH
OR
H
OU
SIN
G
DE
VE
LO
PM
EN
T, L
LC
PERMIT SET
1
OC OC
OCOC
OCOCOC
OCOCOC
OC OCOCOC
OC OC OC
OCOC
OC OC
OC
OC
OCOC OC OC
OC
OC
J
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1F1
F1 F1 F1F1
F1F1
F1F1 F1 F1 F1
F3
F3
F2 F2 F2 F2 F2
F1
F4F4
F4
F4
F4
F4
F7 F7 F7F7 F7
F7F7F7F7F7
F5
F4
F4
F4
X1X1 X1 X1 X1
X1
F6
F6
X1
X1
F6
F6
X1 X1
X1
F2
F2 F2
F2
F2
F4 F4
F4
F4 F4F4
F2
F2 F2
F2
F2
F2
F2F2 F2
F2
F2
F2
F2 F2
F2
F2
E1E1 E1 E1E1 E1 E1 E1 E1 E1 E1
E1
E1
E1
E2
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
1
1
2
2
1
3
3
3
33
3
3
3
3
4 4
44
4
4
4 4 4 4 4
55
5
5
5 5
6
6 6 6
66
6
6 6
66
6
6
77
7
7
7
8
8
8 8
8
8
8
8
8
8
8
8
8 8
8
8
8
33
3
9
9
9
9
9
9
99
9
9
9
9
99
9
9
1010
10
10 10
10
10 1010
10 10 10 10 10 1010 10 11
1111 11 11 11
11
11
11
11 1111
11 1111
11 1111
20
202020
2020
20
20
20
20
E1
E1
E2
F9
F9
F9
E1
X1
E1
E1
X1
3
3
E1
baE1
E1
X1
E1
X1
E1
X1 4 4
33
E1
E1
E1
X1
X1
44
a b
a
bX1
E1
PIRPIR
PIR
X1
X1
3 3ab
F10
F10
F10
F11F11
F11
a
b
20
PIR
20
20
20 20
20
20
20
20 20
20
3
3
3
9
4
5
5
F46
8
8
8
8
F9
E111
2
2
22 22
22 2222
22
21
21
21
21
a
a
b
bb
PIR
7
621
A
8 9
E
D
10 11 12 14
I
H
G
3
F
C
4
13
B
5
15
L
16 17
J
K
UNIT-A797 SF
OFFICE101 SF
VEST.101 SF
MECH/ELECTRICAL633 SF
LOBBY270 SF
CORRIDOR1953 SF
STAIR 1182 SF
UNIT-A798 SF UNIT-A
798 SF
UNIT-A798 SF
UNIT-D857 SF
UNIT-A799 SF
UNIT-A799 SF
COMMUNITYROOM
1267 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A797 SF
UNIT-D857 SF
STAIR 2191 SF
UNIT-A798 SF
PRIVATEDINNING388 SF
STORMSHELTERS
815 SF
MAIL49 SF
W.60 SF
M.61 SF
TRASH85 SF
OFFICE142 SF
MECHROOM100 SF
STORMSHELTERS
1120 SF
RUBBISH164 SF
ELEVATOR50 SF
20X1
3E2
8
8
8F7
F7
F7
F7
8E1
7 7 7
7
777
F3 F3
F3 F3 F3
F3
F3
F3 F3 F3
F3F3
F3 F3
F3F3F3
5 5 5
55
5 5
555
LPA- 23,25SITE
LIGHTING 1
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:1
7:16
PM
E210
1ST
FLO
OR
LIG
HTI
NG
PLA
NH
OPE
HAR
BOR
OF
OKL
AHO
MA
CIT
Y54
IND
IPEN
DEN
T LI
VIN
G A
PAR
TMEN
TS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
1/8" = 1'-0"1 1ST FLOOR LIGHTING PLAN
1 8/02/2016
UP
UP
J
J
+42"GFCI
GFCI+42"GFCI
GFCI
GFCI
GFCI+44"
+44"
+44"
+44"MICRO
GFCI+44"
GDGD
+18"+44"
GFCIWP
GFCI
GFCI GFCI GFCI GFCI GFCI
WP
WP WP WP WP WP
WPWPWPWPWPWPGFCI GFCI GFCI GFCI GFCI GFCI
GFCI
GFCI
GFCIWP
WP
WP
AHU-1
HWCP-1
CU-D
CU-A
CU-1
CU-A CU-A CU-A
EF-T
EF-K EF-K
EF-TEF-T
EF-KEF-K
EF-TEF-T
EF-K
AHU-2
EF-4
EF-3
EF-K
EF-T
EF-T
EF-K EF-K
EF-T EF-T
EF-K EF-K
EF-T EF-T
EF-K EF-K
EF-T EF-T
EF-T
EWH-3
EWH-2
EWH-1
CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-A CU-D CU-D CU-D
CU-ST-4CU-ST-5CU-ST-6CU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-ACU-A
CU-D
CU-D
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A CU-A
MAIN GROUND BUS.
CU-ST-3 CU-ST-2 CU-ST-1
MFCU-1
AC-ST-1
AC-ST-4
DWBP-1
EF-2
GFCI
GFCI
GFCI
GFCI
GFCIGFCIGFCI
GFCIGFCI
GFCIGFCIGFCI
GFCI GFCI
GFCIGFCI
GFCI
REF+42"
+44"GFCI
FIREPLACE+18"
PPA
PPBMDP
LPA
ELECTRICAL METERS AND MAINDEVICE. SEE ELECTRICAL RISERDIAGRAM ON SHEET E700
PPA- 1,3,5
PPA- 2
PPA- 9,11
PPA- 4,6,8
PPA- 13,15
2727
27
27
27
27
27
888888
8
8
8
2525
25
2525
25
25
17
17
17 17
9
9
9 9
9
9
1
1
PPA- 16,18
PPA- 17,19
PPA- 10,12,14
PPA- 21,23
PPA- 20,22PPA- 25,27
PPA- 32,34
PPA- 24,26PPA- 28,30
PPA- 29,31
1
11
11 11 11
11
11
11
4 4 4
444
12
3
23
20PPA- 37,39
PPA- 44
PPA- 44
PPA- 44
15
1515
15
55
5
5
5
14141414
GFCI
2424
24
24
2424
292929
29
29 29 29
10
1010
1010
10
10 10 10
PPA- 53,55 PPA- 50,52
M
M
MPPA- 7
PPA- 44
TELECOMGROUNDBUS (TGB)
FOUR 4" RIGID CONDUITS STUBBED OUTMINIMUM 5' FROM BUILDING FORTELECOMMUNICATION SERVICES ENTRANCES.TRANSITION TO SCHEDULE 80 PVC CONDUITAND EXTEND TO SITE UTILITY EASEMENT.COORDINATE WITH SERVING UTILITIES.
PPA- 61
TELEPHONETERMINAL
BOARD
MDP- 8,10,12
MDP- 13,15,17
MDP- 14,16,18
ACCU-AHU-1
7
621
A
8 9
E
D
10 11 12 14
I
H
G
3
F
C
4
13
B
5
15
L
16 17
J
K
UNIT-A797 SF
OFFICE101 SF
VEST.101 SF
MECH/ELECTRICAL633 SF
LOBBY270 SF
CORRIDOR1953 SF
STAIR 1182 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-D857 SF
UNIT-A799 SF
UNIT-A799 SF
COMMUNITYROOM
1267 SF
UNIT-A798 SF UNIT-A
798 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A797 SF
UNIT-D857 SF
STAIR 2191 SF
UNIT-A798 SF
PRIVATEDINNING388 SF
STORMSHELTERS
815 SF
MAIL49 SF
W.60 SF
M.61 SF
TRASH85 SF
OFFICE142 SF
MECHROOM100 SF
STORMSHELTERS
1120 SF
RUBBISH164 SF
ELEVATOR50 SF
EF-1
AC-ME-1M
PPA- 57,59
PPA- 62,64
FCU-1
ELECTRICAL METERS AND MAINDEVICE. SEE ELECTRICAL RISERDIAGRAM ON SHEET E700
PPA- 63PPA- 65PPA- 66
F200
F200
F200
17
ALL 120V GENERAL PURPOSE ANDEQUIPMENT RECEPTACLES INSTALLED INMECHANICAL/ELECTRICAL ROOM SHALL BEGFCI TYPE.
ACCU-AHU-1
ACCU-AHU-2
ACCU-AHU-3
ACCU-AHU-4
TYPICAL- CU-A & CU-D: PROVIDE SAFETYSWITCH CONNECTED ON PANEL OF UNITSERVED. SEE SHEET E500.
CU-ME-1
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:1
8:26
PM
E310
1ST
FLO
OR
PO
WER
PLA
NH
OPE
HAR
BOR
OF
OKL
AHO
MA
CIT
Y54
IND
IPEN
DEN
T LI
VIN
G A
PAR
TMEN
TS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
1/8" = 1'-0"1 1ST FLOOR POWER PLAN
1 8/02/2016
1
J
J
SD SD SD
E
V VH
V
OC
OC
OCOC OC
OC
TV
TV
E
E
OC
J
J
V
V
V
SD
SD
SD
H
OC
OC
OC
OC
E
TV
TV
TV
E
OC
OC
+42"REF
+18"DWGFCI
+18"GD
RANGE
+72"HOOD
HOOD +44"
GFCI+44"
GFCI+44"
GD+44"
+44"GFCI
GFCI+44"
GFCIWASHER DRYER
GFCI+42"
GFCI+44" 3
3
177cd 177cd
M
EF-T
PNLA
R4
11
1
R5
R1
R7
R7
R7
R7
R7
R7
R7
11
11
1
1
11
11
11
11
11
11
11
11
11
11
1111
2 4,6147
8,10
12
3
3 9
5
20
20
20
20
18
18
18
18
18
22
22
22
22
24
9
13
CU-A CU-A CU-A
R3
R3
19,21
33
33
11 11 11
R2R6
EF-K
15cd
15cd
AC-A
15,17
11 12
I
H
UNIT-A798 SF
+44"DW
R8 R8 R8
16
MICRO+44"
DRYER WASHERGFCI
+42"REF
GFCI
GFCIGFCI
+44"
+44"+44"
RANGE
GFCI
+18"DW
GD GD+18"
+44"
+72"HOOD
HOOD+44"
GFCI+42"
GFCI+44"
3
3
177cd
15cd
177cd
M
15cd
PNLD
R4
R6
R5
R1R2
R3
R3
R3
R7
R7R7
R7
11R7
11
11
11
11
11
1111
11
11
1111
9
3
24
9
9
1
111
4,6 2
20
20
20
20
22
22
22
22
18
18 18
18
18
5
8,1012
7
14
1113
CU-D CU-D CU-D
15,17
R81111
EF-T
EF-K
11
19,21
AC-D
12 14
I
H
G
F
13
UNIT-D858 SF
R8
DW+44"
R8
16MICRO
+44"
11
R7
GENERAL NOTESA. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES, SEE SHEET
E001.B. SEE LIGHTING FIXTURE SCHEDULE ON SHEET E600.C. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT PLACEMENT
OF LIGHTING FIXTURES.D. ALL RECEPTACLE SHALL BE MOUNTED AT +16" AFF UNLESS NOTED OTHERWISE.E. FIRE ALARM VENDOR TO PROVIDE COMPLETE SHOP DRAWINGS TO THE
AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL. FIRE ALARMVENDOR TO INCLUDE ANY ADDITIONAL DEVICES TO PROVIDE A FULLYFUNCTIONAL SYSTEM.
F. COORDINATE ALL DEVICE LOCATIONS WITH ARCHITECT PRIOR TO ROUGH IN.G. PROVIDE SINGLE GANG PLASTER RING FOR EMERGENCY CALL STATION DEVICE.
EMERGENCY CALL SYSTEM WORK IS LIMITED TO ROUGH IN ONLY. DEVICE,CABLE, TERMINATIONS AND ACTIVATION BY OTHERS.
H. PROVIDE SMOKE DETECTOR WITH SOUNDER BASE IN EACH ROOM ON THISSHEET. SMOKE DETECTOR SHALL ACTIVATE SOUNDER BASE AND STROBESWITHIN THE ROOM ONLY AND INDICATE A SUPERVISORY SIGNAL ON THE FACP.SOUNDER BASE AND STROBES WILL ACTIVATE THROUGHOUT THE RESIDENCEWHEN THE GENERAL ALARM IS ACTIVATED.
I. CIRCUIT NUMBERS ARE FOR COUNT ONLY. SEE PANEL SCHEDULES ON THE E600SERIES OF SHEETS FOR SPECIFIC ROOM CIRCUIT NUMBERS.
J. ALL RECEPTACLES IN RESIDENCE UNITS SHALL BE TAMPER RESISTANT.K. ALL SLEEPING ROOM RECEPTACLE OUTLETS SHALL BE AFCI PROTECTED.
PROVIDE COMBINATION TYPE AFCI RECEPTACLE AT FIRST OUTLET ON CIRCUITAND CONNECT FOR DOWNSTREAM PROTECTION OF ROOM OUTLETS. LABEL ALLAFCI PROTECTED OUTLETS.
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:5
4:49
PM
E500
ENLA
RG
ED E
LEC
TRIC
AL P
LAN
- U
NIT
A &
BH
OPE
HAR
BOR
OF
OKL
AHO
MA
CIT
Y54
IND
IPEN
DEN
T LI
VIN
G A
PAR
TMEN
TS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
1/4" = 1'-0"1 ENLARGED ELECTRICAL PLAN - UNIT A
1/4" = 1'-0"2 ENLARGED ELECTRICAL PLAN - UNIT B
1
11
1
2
2 33
PLAN NOTES1 ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL CEILING FAN BOX AS
REQUIRED FOR CEILING FAN INSTALLATION. ONE SWITCH SHALL CONTROLFAN BLADES AND ONE SWITCH SHALL CONTROL FAN LIGHT.
2 PROVIDE CONNECTIONS TO EXHAUST FAN BY MECHANICAL CONTRACTOR.3 PROVIDE DOUBLE SINGLE POLE SWITCH FOR LIGHTS AND SINGLE SWITCH FOR
EXHAUST FAN.
1 8/02/2016
11
1
1
1
1
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:1
8:40
PM
E601
ELEC
TRIC
AL S
CH
EDU
LES
SHEE
T-1
HO
PE H
ARBO
R O
F O
KLAH
OM
A C
ITY
54 IN
DIP
END
ENT
LIVI
NG
APA
RTM
ENTS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
Remarks:
Total Connected Load (Amps): 41.9 ATotal Connected Load (kVA): 15.1 kVA
Total Load: 5.9 kVA 5 kVA 4 kVA30
2928
2726
25 -- -- -- 225 VA24
23 Site Lighting 20 A 2 225 VA168 VA 1 20 A Lighting 22
21 Lighting 20 A 1 240 VA200 VA 1 20 A 1st Floor Exit Lights 20
19 Lighting 20 A 1 920 VA700 VA 1 20 A Lighting 18
17 Lighting 20 A 1 840 VA510 VA 1 20 A Lighting 16
15 Lighting 20 A 1 860 VA760 VA 1 20 A Lighting 14
13 Lighting 20 A 1 840 VA590 VA 1 20 A Lighting 12
11 Lighting 20 A 1 860 VA820 VA 1 20 A Lighting 10
9 Lighting 20 A 1 780 VA1605 VA 1 20 A Lighting 8
7 Lighting 20 A 1 430 VA350 VA 1 20 A Lighting 6
5 Lighting 20 A 1 660 VA980 VA 1 20 A Lighting 4
3 Lighting 20 A 1 580 VA480 VA 1 20 A Lighting 2
1 Lighting 20 A 1 460 VA
CircuitNumber Circuit Description Trip Poles
A B CPoles Trip Circuit Description
CircuitNumber
xxxxxGeneral Panel Comments:
Enclosure Type: Type 1 Ground: Standard Main Rating: 100 AMounting: Surface Wire: 4 Main Type: M.L.O
Supplied From: MDP Phase: 3 A.I.C. Rating: 65kAICLocation: MECH/ELECTRICAL 118 Voltage: 120/208 Wye Branch: Normal
Branch Panel: LPA
Remarks:
Total Connected Load (Amps): 893.2 ATotal Connected Load (kVA): 321.8 kVA
Total Load: 107.8 kVA 108 kVA 106 kVA30
2928
2726
2524
2322
2120
1920000 VA -- -- -- 18
17 -- -- -- 20000 VA20000 VA -- -- -- 16
15 -- -- -- 20000 VA20000 VA 3 200 A EWH-3 14
13 EWH-2 200 A 3 20000 VA20000 VA -- -- -- 12
11 -- -- -- 4214 VA20000 VA -- -- -- 10
9 -- -- -- 4927 VA20000 VA 3 200 A EWH-1 8
7 LPA 100 A 3 5900 VA10700 VA -- -- -- 6
5 -- -- -- 31282 VA10500 VA -- -- -- 4
3 -- -- -- 32284 VA10400 VA 3 225 A PPB 2
1 PPA 400 A 3 31538 VA
CircuitNumber Circuit Description Trip Poles
A B CPoles Trip Circuit Description
CircuitNumber
General Panel Comments:
Enclosure Type: Type 1 Ground: Main Rating: 1200 AMounting: Surface Wire: 4 Main Type:
Supplied From: Phase: 3 A.I.C. Rating:Location: MECH/ELECTRICAL 118 Voltage: 120/208 Wye Branch:
Branch Panel: MDP
1 8/02/2016
1
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:1
8:52
PM
E602
ELEC
TRIC
AL S
CH
EDU
LES
SHEE
T-2
HO
PE H
ARBO
R O
F O
KLAH
OM
A C
ITY
54 IN
DIP
END
ENT
LIVI
NG
APA
RTM
ENTS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
Remarks:
Total Connected Load (Amps): 264.0 ATotal Connected Load (kVA): 95.1 kVA
Total Load: 31.5 kVA 32 kVA 31 kVA0 VA -- -- Space 84
83 Space -- -- 0 VA0 VA -- -- Space 82
81 Space -- -- 0 VA0 VA -- -- Space 80
79 Space -- -- 0 VA0 VA -- -- Space 78
77 Space -- -- 0 VA0 VA -- -- Space 76
75 Space -- -- 0 VA0 VA -- -- Space 74
73 Space -- -- 0 VA0 VA 1 20 A Spare 72
71 Spare 20 A 1 0 VA0 VA 1 20 A Spare 70
69 Spare 20 A 1 0 VA0 VA 1 20 A Spare 68
67 Spare 20 A 1 0 VA400 VA 1 20 A TELEPHONE TERMINAL BOARD 66
65 TELEPHONE TERMINAL BOARD 20 A 1 400 VA840 VA -- -- -- 64
63 TELEPHONE TERMINAL BOARD 20 A 1 400 VA840 VA 2 15 A CU-ME-1 62
61 TELEPHONE TERMINAL BOARD 20 A 1 400 VA216 VA -- -- -- 60
59 -- -- -- 840 VA216 VA 2 15 A FCU-4 & 5 58
57 AC-ME-1 15 A 2 840 VA216 VA -- -- -- 56
55 -- -- -- 2247 VA216 VA 2 15 A FCU-2 & 3 54
53 CU-1 30 A 2 2247 VA108 VA -- -- -- 52
51 -- -- -- 2486 VA108 VA 2 20 A FCU-1 50
49 AHU-4 50 A 2 2486 VA1706 VA -- -- -- 48
47 EF-8 15 A 1 23 VA1706 VA 2 30 A AHU-3 46
45 EF-5 TO EF-7 15 A 1 59 VA141 VA 1 15 A EF-1 TO EF-4 44
43 -- -- -- 840 VA840 VA -- -- -- 42
41 AC-ST-6 15 A 2 840 VA840 VA 2 15 A AC-ST-5 40
39 -- -- -- 840 VA840 VA -- -- -- 38
37 AC-ST-4 15 A 2 840 VA840 VA 2 15 A AC-ST-3 36
35 -- -- -- 840 VA840 VA -- -- -- 34
33 AC-ST-2 15 A 2 840 VA840 VA 2 15 A AC-ST-1 32
31 -- -- -- 840 VA840 VA -- -- -- 30
29 CU-ST-5 15 A 2 840 VA840 VA 2 15 A CU-ST-6 28
27 -- -- -- 840 VA840 VA -- -- -- 26
25 CU-ST-3 15 A 2 840 VA840 VA 2 15 A CU-ST-4 24
23 -- -- -- 840 VA840 VA -- -- -- 22
21 CU-ST-1 15 A 2 840 VA840 VA 2 15 A CU-ST-2 20
19 -- -- -- 1321 VA1716 VA -- -- -- 18
17 ACCU-AHU-3 25 A 2 1321 VA1716 VA 2 35 A ACCU-AHU-4 16
15 -- -- -- 1716 VA4143 VA -- -- -- 14
13 ACCU-AHU-1 35 A 2 1716 VA4143 VA -- -- -- 12
11 -- -- -- 2486 VA4143 VA 3 70 A ACCU-AHU-2 10
9 AHU-1 60 A 2 2486 VA5812 VA -- -- -- 8
7 HWCP-1 20 A 1 1176 VA5812 VA -- -- -- 6
5 -- -- -- 3038 VA5812 VA 3 70 A AHU-2 4
3 -- -- -- 3038 VA1176 VA 1 20 A SP-1 2
1 DWBP-1 30 A 3 3038 VA
CircuitNumber Circuit Description Trip Poles
A B CPoles Trip Circuit Description
CircuitNumber
xxxxxxGeneral Panel Comments:
Enclosure Type: Type 1 Ground: Standard Main Rating: 400 AMounting: Surface Wire: 4 Main Type: M.L.O
Supplied From: MDP Phase: 3 A.I.C. Rating: 65kAICLocation: MECH/ELECTRICAL 118 Voltage: 120/208 Wye Branch: Normal
Branch Panel: PPA
Remarks:
Total Connected Load (Amps): 87.7 ATotal Connected Load (kVA): 31.6 kVA
Total Load: 10.4 kVA 11 kVA 11 kVA0 VA -- -- Space 42
41 Space -- -- 0 VA0 VA -- -- Space 40
39 Space -- -- 0 VA0 VA -- -- Space 38
37 Space -- -- 0 VA0 VA 1 20 A Spare 36
35 Spare 20 A 1 0 VA0 VA 1 20 A Spare 34
33 Spare 20 A 1 0 VA0 VA 1 20 A Spare 32
31 Spare 20 A 1 0 VA0 VA 1 20 A Spare 30
29 Storm Sheltors Receptacles 20 A 1 1400 VA0 VA 1 20 A Spare 28
27 Private Dining Receptacles 20 A 1 1400 VA0 VA 1 20 A Spare 26
25 External Receptacles 20 A 1 1400 VA1200 VA 1 20 A Storm Sheltors Receptacles 24
23 Community Room Microwave 20 A 1 1000 VA1200 VA 1 20 A Comp Lab, Mech / Storage Receptacles 22
21 3rd Floor Corridor Receptacles 20 A 1 1000 VA1200 VA 1 20 A Community Room Refrigerator 20
19 2nd Floor Corridor Receptacles 20 A 1 1000 VA800 VA 1 20 A 3rd Floor Corridor Receptacles 18
17 Mech and Electrical Room 20 A 1 1000 VA800 VA 1 20 A 2nd Floor Corridor Receptacles 16
15 Mech Room, Elevator Receptacles 20 A 1 800 VA800 VA 1 20 A 1st Floor Corridor Receptacles 14
13 Exercise Room Receptacles 20 A 1 800 VA1500 VA 1 20 A Community Room Fireplaces 12
11 Community Room Receptacles 20 A 1 1400 VA1800 VA 1 20 A Storm Sheltors Receptacles 10
9 Office Receptacles 20 A 1 1600 VA1800 VA 1 20 A External Receptacles 8
7 Comp Lab Receptacles 20 A 1 1600 VA1400 VA 1 20 A 2nd Floor Salon Receptacles 6
5 1st Floor Corridor Receptacles 20 A 1 1000 VA1200 VA 1 20 A Community Room Receptacles 4
3 Community Room Garbage Disposal 20 A 1 700 VA1200 VA 1 20 A 2nd Floor Arts and Craft, Meach Room... 2
1 Toilets and Water Fountaine Receptacles 20 A 1 600 VA
CircuitNumber Circuit Description Trip Poles
A B CPoles Trip Circuit Description
CircuitNumber
xxxxxGeneral Panel Comments:
Enclosure Type: Type 1 Ground: Standard Main Rating: 225 AMounting: Surface Wire: 4 Main Type: M.L.O
Supplied From: MDP Phase: 3 A.I.C. Rating: 65kAICLocation: MECH/ELECTRICAL 118 Voltage: 120/208 Wye Branch: Normal
Branch Panel: PPB
1 8/02/2016
1
EQUIPMENTGROUND
CONDUIT SIZE AND QUANTITY
2-1/2"
1/0
F2000 600
F900
F1600
F1200
F1000
350
500
350
500
500
2/0
2/0
3/0
4/0
F450 4/0
F800
F500
F600
F700
350
350
500
250
F250
F300
F350
F400
500
350
250
2
1
1/0
2
4
3
4
(3) 3"(3) 2-1/2"
(5) 4"
(4) 2-1/2"
(3) 2-1/2"
(5) 3"
(3) 3"
(5) 4"
(4) 3"
(5) 3"
(3) 3"
(3) 3"
(2) 2"
(2) 2-1/2"
(2) 3"
(2) 2"
2"
2"
3"
2-1/2"
2"
(2) 2-1/2"
(2) 3"
(2) 3"
(2) 2-1/2"
3"
2-1/2"
3"
1-1/4"
1-1/4"
1-1/4"
1-1/2"
1-1/4"
BRANCH FEEDER SCHEDULE - COPPER
F60 106
F150
F175
F225
F200 3/0
4/0
1/0
2/0
F125
F110
F90 & F100
F70 & F80
3
2
1
4
6
6
6
4
8
6
6
8
NEUTRALPHASE AND
CONDUCTOR PER CONDUIT
F30
F20
F40 & F50
10
8
12
FEEDER
10
10
12
OR
1"3/4" 3/4"
1-1/4"
2"
2"
1-1/2"
1-1/2"
1"
1"
3/4"
1"
1-1/4"
1"
1-1/2"
2-1/2"
2"
2"
1-1/2"
1-1/4"
1-1/4"
1-1/4"
2P, 1N, 1G1P, 1N, 1G
3/4"
3/4"
2P, 1G3/4"
3/4"
3/4"
3P, 1GOR
3/4"
3P, 1N, 1G
3/4"
3/4"
3/4"
(3) 3-1/2"
(5) 5"
(4) 3-1/2"
(3) 3-1/2"
(5) 4"
(3) 4"
(2) 3"
(2) 3"
(2) 3-1/2"
(2) 4"
3"
4"
3-1/2"
1"
2"
2"
2-1/2"
2-1/2"
2-1/2"
1-1/2"
1-1/2"
1-1/4"
3P, 3N, 1G
1"
3/4"
3/4"
2-1/2"500 3 3" 3" 4"
-
-
-
-
-
-
-
-
-
-
DESIGNATION
EQUIPMENTGROUND
CONDUIT SIZE AND QUANTITY
2-1/2"
F250A
F300A 500 AL
350 AL
2
2
(3) 3-1/2"(3) 3"
(6) 3"
(4) 3"
(3) 3"
(5) 3"
(3) 3"
(6) 4"
(4) 3-1/2"
(5) 3-1/2"
(3) 3-1/2"
(3) 3-1/2"
(2) 2"
(2) 2-1/2"
(2) 3"
(2) 2"
2"
2"
3"
2-1/2"
2"
(2) 2-1/2"
(2) 3"
(2) 3"
(2) 2-1/2"
3-1/2"
2-1/2"
3"
1-1/4"
1-1/4"
1-1/4"
1-1/2"
1-1/4"
BRANCH FEEDER SCHEDULE - ALUMINUM
F60A 84 AL
F150A
F175A
F225A
F200A 4/0 AL
350 AL
2/0 AL
3/0 AL
F125A
F110A
F90A & F100A
F70A & F80A
2 AL
1/0 AL
1/0 AL
3 AL
4
2
6
4
6
NEUTRALPHASE AND
CONDUCTOR PER CONDUIT
F30A
F20A
F40A & F50A
8 AL
6 AL
10 AL
FEEDER
8
8
10
OR
1"3/4" 3/4"
1-1/4"
2"
2"
1-1/2"
1-1/2"
1"
1"
3/4"
1"
1-1/4"
1"
1-1/2"
2-1/2"
2"
2"
1-1/2"
1-1/4"
1-1/4"
1-1/4"
2P, 1N, 1G1P, 1N, 1G
3/4"
3/4"
2P, 1G3/4"
3/4"
3/4"
3P, 1GOR
3/4"
3P, 1N, 1G
3/4"
3/4"
3/4"
(3) 4"
(6) 5"
(4) 4"
(3) 4
(5) 4"
(3) 4"
(2) 3-1/2"
(2) 3-1/2"
(2) 4"
(2) 4"
3"
4"
3-1/2"
1"
2"
2"
2-1/2"
2-1/2"
2-1/2"
1-1/2"
1-1/2"
1-1/4"
3P, 3N, 1G
1"
3/4"
3/4"
2-1/2" (2) 3" (2) 3" (2) 3-1/2
-
-
-
-
-
-
-
-
-
-
DESIGNATION
3/0 AL
F2000A 600 AL
F900A
F1600A
F1200A
F1000A
500 AL
600 AL
500 AL
600 AL
500 AL
4/0 AL
4/0 AL
250 AL
350 AL
F450A 350 AL
F800A
F500A
F600A
F700A
500 AL
500 AL
600 AL
350 AL
F350A
F400A
600 AL
1/0 AL
2/0 AL
3/0 AL
1/0 AL
1/0 AL
350 AL 1/0 AL
4
4
4
SCALE: NTS1 POWER RISER DIAGRAM - COMMON AREASCALE: NTS2 POWER RISER DIAGRAM - DWELLING UNITS
SCALE: NTSMAIN GROUND BUS CONNECTIONS DETAIL
SCALE: NTS3 POWER RISER DIAGRAM - UTILITY SERVICE
GROUND LEVEL
UTILITY TRANSFORMERPAD PROVIDED BY
ELECTRICALCONTRACTOR
TERMINATION CABINETPROVIDED BYELECTRICAL
CONTRACTOR
TWO 4" UNDERGROUND CONCRETEENCASED SCHEDULE 40 PVC CONDUIT
FOR EL. PRIMARY TO UTILITY.COORDINATE WITH UTILITY COMPANY.
#3/0 AWG, 1" PVC CONDUITFROM "MDP" PANELGROUND BUS.
MAIN GROUND BUS (MGB);PROVIDE MINIMUM 12" L. x 4" W. x 1/4" T. GROUNDBUS WITH STAND-OFF, INSULATED MOUNTING.
TELECOMMUNICATIONS GROUND BUS (TGB) ATTELECOMMUNICATIONS TERMINAL BOARD TTB;PROVIDE MINIMUM 12" L. x 4" W. x 1/4" T.PRE-DRILLED TELECOMMUNICATIONS GROUNDBUS WITH STAND-OFF, INSULATED MOUNTING.COORDINATE WITH OWNER'S I.T. DEPARTMENT.
PROVIDE #6 IN 3/4"PVC CONDUIT TOMAIN GROUND BUSWITH CONNECTIONS.
#3/0 AWG, 1" PVC CONDUIT FROM WATER SERVICE.
#4 AWG, 1" PVC CONDUIT FROM FOUNDATION(UFER GROUND). PROVIDE MINIMUM TWENTYFEET OF #4 BARE COPPER GROUND CONDUCTORAT OR NEAR BOTTOM OF FOOTING(S).COORDINATE WITH GENERAL CONTRACTORPRIOR TO POURING OF CONCRETE.
#3/0 AWG, 1" PVC CONDUIT FROM FIRE MAIN.
NOTE: ELECTRICAL CONTRACTOR SHALL PROVIDEGROUNDING AND BONDING OF ALL BUILDINGSYSTEMS AND STRUCTURAL COMPONENTS PERTHE REQUIREMENTS OF N.E.C. ARTICLE 250.COORDINATE INSTALLATIONS WITH THE BUILDINGAND MECHANICAL TRADES.
M M
M M
M M
M M
M M
RESIDENTSERVICE 1
1600A,120/208V, 2P
MAINBREAKER
PER O.G. &E.
M M
M M
M M
M M
M
M M125/2
M M
M M
M M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
PROVIDE TERMINATION CABINETPER REQUIREMENTS OF UTILITY.
M
PROVIDE 1200A, 120/208V, 3PH,NEMA 3R, CT, METER BASE AND1200A, 3P CIRCUIT BREAKER PERREQUIREMENTS OF UTILITY.
1200A,120/208V,3PH MDP
225A,120/208V,
3PH 42SPACE
PPB
400A,120/208V,
3PH 84SPACE
PPA
100A,120/208V,
3PH 30SPACE
LPA
TVSS
TYPICAL- FEEDER F125TO 27 UNIT PANELS.
#3/0 AWG, 1" PVC CONDUITFROM BUILDING STEEL.
TYPICAL- FEEDER F125TO 27 UNIT PANELS.
TVSS
PROVIDE MAINGROUND BUS (MGB)PER DETAIL.
#3/0 CU.,1" C.
F1200A
F225AF100A F400A F1200A
#500 CU.,1" C.
F1200A
F1600A
F4000A
F3000 600 500 (8) 4" (8) 4" (8) 5"-
(9) 4" (9) 4" (9) 5"-F3000A 600 AL 750 AL
(12) 4" (12) 4" (12) 5"-F4000A 600 AL (2) 500 AL
F4000 600 750 (10) 4" (10) 4" (10) 5"-
125/2 125/2 125/2 125/2 125/2 125/2 125/2 125/2 125/2 125/2
125/2125/2125/2125/2125/2
125/2 125/2 125/2 125/2 125/2
125/2125/2125/2125/2125/2
125/2125/2125/2125/2125/2125/2
125/2 125/2 125/2 125/2 125/2 125/2
125/2125/2125/2125/2125/2125/2
125/2 125/2 125/2
125/2
125/2
125/2
125/2M
125/2M
125/2M
125/2
RESIDENTSERVICE 2
1600A,120/208V, 2P
MAINBREAKER
PER O.G. &E.
F1600A#500 CU.,1" C.
#3/0 AWG, 1" PVC CONDUIT FROM RESIDENT SERVICE 2.#3/0 AWG, 1" PVC CONDUITFROM RESIDENT SERVICE 1.
TVSS
NOTE: THE ELECTICAL DISTRIBUTION SYSTEM INDICATEDREPRESENTS ONE POSSIBLE SOLUTION AND IS SHOWN FORCLARITY OF INTENT. CONTRACTOR SHALL PROVIDE METHODSAND MATERIALS AS REQUIRED FOR A COMPLETE INSTALLATIONPER THE REQUIREMENTS OF THE SERVING UTILITY (O.G. & E.)AND THE NATIONAL ELECTRICAL CODE.
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:1
9:05
PM
E700
ELEC
TRIC
AL R
ISER
DIA
GR
AMH
OPE
HAR
BOR
OF
OKL
AHO
MA
CIT
Y54
IND
IPEN
DEN
T LI
VIN
G A
PAR
TMEN
TS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
1 8/02/2016
1
UP
REF.
W. D.MWDW
REF.
W.D.MW DW
REF.
W. D.MWDW
REF.
W. D.MWDW
REF.
W.D.MW DW
REF.
W. D.MWDW
REF.
W.D.MW DW
REF.
UP
REF.
W. D.MWDW
REF.
W.D.MW DW
REF.
W.
D.MW
DW
REF.
REF.
W.D.MW DW
REF.
W. D.MWDW W.D.
W.
D.
MW
REF.
MW
REF.
RD-12758"
X 8"
RD-1120
14" X 10"
12" X
10"
6"ø
8" X 8"
SD-475
SD-4105
RD-1110
RD-175
SD-2165
(2200 CFM)
(810 CFM)
(100 CFM)(250 CFM)
8" X
8"
RD-1165
8" X 8"
SD-4100
SD-4110
SD-4110
(70 CFM)
(70 CFM)
FD
FD
FD
CU-1
CU-D
CU-A
CU-A
CU-A CU-A
8" X
8"
SD-6125
AC-ST-1
CU-ST-1CU-ST-2
CU-ST-3
RD-1100
CU-D
CU-D
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A
CU-A CU-A
CU-A
CU-A CU-A
CU-A
CU-A CU-A
CU-A
CU-A CU-A
CU-A
CU-A CU-A
CU-D
CU-D CU-D
CU-A
CU-ACU-A
CU-A
CU-A CU-A
CU-A
CU-A CU-A
CU-A
CU-A CU-A
CU-A
CU-A CU-A
CU-A
CU-A
CU-ACU-A
CU-ST-4CU-ST-5
CU-ST-6
AC-ST-4
AC-D
AC-A
AC-A AC-A AC-A AC-A AC-A AC-A AC-D
AC-AAC-AAC-AAC-AAC-A
EF-T
EF-K
EF-T
EF-T
EF-K EF-K
EF-T EF-T
EF-K EF-K
EF-T EF-T
EF-K EF-K
EF-T EF-T
EF-T
EF-KEF-K
EF-TEF-T
EF-KEF-K
EF-TEF-T
EF-K
1 TYP
1 TYP
1TYP
1TYP
1TYP
1
TYP
1
TYP
1TYP
1
TYP
2
2
2
2
2
2 2 2
3
23
3 3 3
2 3 2 32 32 3
3
3
4 5 4 5
4 54 5
6
6
6 6 6
7
7
7 7 7 7 7 7
7 77777
3
3
EF-2
EF-3
EF-4
8" X 6"
AHU-1
SD
U/C
U/C
U/C
AHU-2
20" X 10" 16" X 10"10" X 10"
SD-2250
TYP OF 6
SD-6100
RD-11500
8" X 8"
SD-4125
SD-4105
SD-2150
89
TYP
89
TYP
89
TYP
ACCU-AHU-1
ACCU-AHU-2
ACCU-AHU-3
ACCU-AHU-4
J
I
RTT
G
F
UU
3 4 SS XX AAA 5 6 10 M N O P
B
SD-6100
8" X
8"
6"ø
SD-4100
UNIT-A797 SF
OFFICE101 SF
VEST.101 SF
MECH/ELECTRICAL633 SF
LOBBY270 SF
CORRIDOR1953 SF
STAIR 1182 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-D857 SF
UNIT-A799 SF
UNIT-A799 SF
COMMUNITYROOM
1267 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A798 SF
UNIT-A797 SF
UNIT-D857 SF
STAIR 2191 SF
UNIT-A798 SF
PRIVATEDINNING388 SF
STORMSHELTERS
815 SF
MAIL49 SF
W.60 SF
M.61 SF
TRASH85 SF
OFFICE142 SF
MECHROOM100 SF
STORMSHELTERS
1120 SF
RUBBISH164 SF
ELEVATOR50 SF
6"ø
8"ø
4"ø
6"ø
8"ø 6"ø 6"ø 8"ø 8"ø
4"ø 4"ø 4"ø
6"ø 6"ø
4"ø
8"ø 8"ø 6"ø
4"ø
4"ø
6"ø6"ø
4"ø4"ø
8"ø8"ø6"ø6"ø
4"ø
8"ø8"ø
4"ø
6"ø6"ø
4"ø
8"ø8"ø
4"ø
6"ø
EF-1
10
AC-ME-1
CU-ME-1
42"X12" OA LOUVER(855 CFM)
RG-1125
RG-2200
8" X 8" 8" X 8"
SD-4110
RD-1320
16" X 10"(685 CFM)
(125 CFM)
14" X 10"
22" X 10"
SD-4150
(1400 CFM)
EF-9
2 3
10" X 10"
(490 CFM)
12"X12" OA LOUVER125 CFM
L-2125
10
L-1855
8" X
6"
14" X
10"
6"ø
6"ø
8" X 8"
EF-K2 3
8"ø
EF-K
1
1
1
HVAC KEY NOTESCEILING REGISTERS. LOCATIONS TO BECOORDINATED WITH THE INTERIOR PLANS.
CONTRACTOR TO PAINT WALL EXHAUSTCAPS TO MATCH WITH ADJACENT SIDING.
CONTRACTOR TO PROVIDE A BACK DRAFTDAMPER FOR THE EXHAUST DUCT HOODAND WIRE MESH (BIRD) SCREEN AT THEEND OF THE DUCT HOOD.
PROVIDE CLEAN OUT FOR WASHER/DRYER.
DRYER EXHAUST HOOD TERMINATION TOBE A TYPE-A OUTLET AND SHOULD BEPAINTED.
LOUVERED DOOR TO TAKE THE RETURNAIR BACK TO THE ELECTRIC AIRCONDITIONERS.
CONTRACTOR TO PROVIDE ACCESS PANELFOR THE EXHAUST FAN.
CONTRACTOR TO PROVIDE CONDENSATEDRAIN TO THE NEAREST FLOOR DRAINFOR ALL THE EQUIPMENT. REFERPLUMBING DRAWINGS FOR THE FLOORDRAIN LOCATIONS.
CONTRACTOR TO PROVIDE REFRIGERANTPIPING FOR ALL THE EQUIPMENT AS PERTHE MANUFACTURER SPECIFICATIONSAND ONE HOUR FIRE DAMPER AT THECEILING PENETRATION.
TRANSFER 250 CFM OF SUPPLY AIR FROMTHE CORRIDOR TO THE RUBBISH AREA.
1
2
3
4
5
6
7
8
9
10
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:2
0:51
PM
H210
FIR
ST F
LOO
R H
VAC
PLA
NH
OPE
HAR
BOR
OF
OKL
AHO
MA
CIT
Y54
IND
IPEN
DEN
T LI
VIN
G A
PAR
TMEN
TS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
1/8" = 1'-0"1 FIRST FLOOR HVAC PLAN
1 8/02/2016
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:2
1:55
PM
H600
HVA
C S
CH
EDU
LES
HO
PE H
ARBO
R O
F O
KLAH
OM
A C
ITY
54 IN
DIP
END
ENT
LIVI
NG
APA
RTM
ENTS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
AIR HANDLING UNITS WITH ELECTRIC HEATING SCHEDULEEQUIPMENT TAG
REFERENCE PRODUCT(DAIKIN) AREA SERVED
CONDENSINGUNIT
TOTAL SUPPLY AIRFLOW(CFM)
OUTSIDE AIRFLOW(CFM) ESP (IN WG)
DX COOLING DATA DX HEATING DATA ELECTRIC HEATING DATA ELECTRICAL DATA
MANUFACTURER REMARKSTOTAL COOLING
CAPACITY (TONS)TOTAL COOLINGCAPACITY (MBH)
SENSIBLE COOLINGCAPACITY (MBH)
AMBIENT EAT LAT TOTAL HEATINGCAPACITY (MBH) EAT (ºF) LAT (ºF)
TOTAL HEATINGCAPACITY (MBH)
ENTERING AIRTEMP. (DB ºF)
LEAVING AIRTEMP. (DB ºF)
REQUIREDKW FLA MCA MOCP VOLTS PHASEDB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF)
AHU-1 DV30PTCC1/HKSC05CA FIRST FLOOR ACCU-AHU-1 1010 155 0.5 2.4 28.70 24.90 98.4 73.8 80.5 64.4 55.5 54.0 22.7 60.2 82.9 17.07 70 100 5.00 23.9 30 35 208 1 DAIKIN REFER TO NOTESAHU-2 DAT12043/AHKD15-3 FIRST FLOOR ACCU-AHU-2 2215 800 1.0 8.0 95.70 72.20 98.4 73.8 85.6 67.1 53.6 52.0 57.8 48.4 74.1 51.20 70 100 15.00 48.4 61 70 208 3 DAIKIN REFER TO NOTESAHU-3 DV24PTCC14/HSKC03CA SECOND FLOOR ACCU-AHU-3 365 135 0.5 1.4 17.10 11.90 98.4 73.8 85.7 68.4 53.6 52.2 7.6 48.0 68.6 10.24 70 100 3.00 16.4 21 30 208 1 DAIKIN REFER TO NOTESAHU-4 DV30PTCC1/HSKSC05CA THIRD FLOOR ACCU-AHU-4 570 255 0.5 2.3 28.20 18.70 98.4 73.8 87.4 69.9 54.2 52.9 16.6 42.2 71.6 17.07 70 100 5.00 23.9 30 35 208 1 DAIKIN REFER TO NOTES
NOTES1 FURNISH WITH SINGLE POINT WIRING KIT, ECM MOTOR, THERMOSTATIC EXPANSION VALVE, AND SEVEN DAY PROGRAMMABLE THERMOSTAT.2 REFRIGERANT LINES PIPE SIZES TO BE AS PER MANUFACTURER'S RECOMMENDATIONS.3 AIR CONDITIONERS WITH ELECTRIC HEATING SHOULD BE SELECTED WITH ENERGY STAR RATING.
AHU – AIR COOLED CONDENSING UNIT SCHEDULEDESIGNATION REFERENCE PRODUCT
(DAIKIN) SERVES OPERATINGWEIGHT (LBS)
REFRIGERANTTYPE
COOLING CAPACITY (MBH) CONDENSINGAIR TEMP. (ºF)
ELECTRICALREMARKSTOTAL SENSIBLE VOLTS / HERTZ /
PHASE FLA MCA MOCP
ACCU-AHU-1 DZ16TC0301 AHU–1 233 R – 410A 26.7 22.8 95.00 208 / 60 / 1 16.5 20.3 35 REFER TO NOTESACCU-AHU-2 DZ11S1203 AHU–2 383 R – 410A 95.7 72.2 95.00 208 / 60 / 3 34.5 43.2 70 REFER TO NOTESACCU-AHU-3 DZ16TC0241 AHU–3 190 R – 410A 17.1 11.9 95.00 208 / 60 / 1 12.7 15.8 25 REFER TO NOTESACCU-AHU-4 DZ16TC0301 AHU–4 233 R – 410A 28.2 18.7 95.00 208 / 60 / 1 16.5 20.3 35 REFER TO NOTES
NOTES.1 SEER RATING AT ACTUAL CONDITIONS, EER RATING AT ARI CONDITIONS. SELECTIONS SHOULD BE WITH ENERGY STAR RATING.2 FURNISH WITH HEAVY DUTY GRILLE.3 UNITS CONTROLS AND ACCESSORIES SHALL INCLUDE LOW AMBIENT PRESSURE SWITCH, START ASSIST CAPACITOR AND RELAY, ISOLATION RELAY, EVAPORATOR FREEZE THERMOSTAT, AND CRANKCASE HEATER.4 REFER TO SPECIFICATIONS FOR ADDITIONAL ACCESSORIES.
AIR CONDITIONERS WITH ELECTRIC HEATING SCHEDULEEQUIPMENT TAG
REFERENCE PRODUCT(DAIKIN)
AREASERVED
CONDENSINGUNIT
TOTAL SUPPLY AIRFLOW(CFM)
OUTSIDE AIRFLOW(CFM) ESP (IN WG)
DX COOLING DATA DX HEATING DATA ELECTRIC HEATING DATA ELECTRICAL DATA
MANUFACTURER REMARKSTOTAL COOLING
CAPACITY (TONS)TOTAL COOLINGCAPACITY (MBH)
SENSIBLE COOLINGCAPACITY (MBH)
AMBIENT EAT LAT TOTAL HEATINGCAPACITY (MBH) EAT (ºF) LAT (ºF)
TOTAL HEATINGCAPACITY (MBH)
ENTERING AIRTEMP. (DB ºF)
LEAVING AIRTEMP. (DB ºF)
REQUIREDKW FLA MCA MOCP VOLTS PHASEDB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF)
AC-A DV24PTCC14/HSKC05CA UNIT–A CU–A 563 45 0.35 1.0 15.20 13.40 98.4 73.8 78.2 63.3 55.2 53.8 11.4 68.9 88.6 17.07 70 100 5.00 23.9 30 35 208 1 DAIKIN REFER TO NOTESAC-D DV24PTCC14/HSKC05CA UNIT–D CU–D 708 45 0.35 1.5 17.80 16.10 98.4 73.8 77.9 63.2 55.7 54.3 15.2 69.0 89.9 17.07 70 100 5.00 23.9 30 35 208 1 DAIKIN REFER TO NOTES
AC–AIR COOLED CONDENSING UNIT SCHEDULEDESIGNATION REFERENCE PRODUCT
(DAIKIN) SERVES OPERATINGWEIGHT (LBS)
REFRIGERANTTYPE
COOLING CAPACITY (MBH) CONDENSING AIRTEMP. (ºF)
ELECTRICALREMARKSTOTAL SENSIBLE VOLTS / HERTZ /
PHASE FLA MCA MOCP
CU-A DZTC0241 AC-A 246 R – 410A 15.2 13.4 95.00 208 / 60 / 1 12.7 15.8 25 REFER TO NOTESCU-D DZTC0241 AC-D 246 R – 410A 17.8 16.1 95.00 208 / 60 / 1 12.7 15.8 25 REFER TO NOTES
NOTES1 FURNISH WITH SINGLE POINT WIRING KIT, ECM MOTOR, THERMOSTATIC EXPANSION VALVE, AND SEVEN DAY PROGRAMMABLE THERMOSTAT.2 REFRIGERANT LINES PIPE SIZES TO BE AS PER MANUFACTURER'S RECOMMENDATIONS.3 AIR CONDITIONERS WITH ELECTRIC HEATING SHOULD BE SELECTED WITH ENERGY STAR RATING.
NOTES.1 SEER RATING AT ACTUAL CONDITIONS, EER RATING AT ARI CONDITIONS. SELECTIONS SHOULD BE WITH ENERGY STAR RATING.2 FURNISH WITH HEAVY DUTY GRILLE.3 UNITS CONTROLS AND ACCESSORIES SHALL INCLUDE LOW AMBIENT PRESSURE SWITCH, START ASSIST CAPACITOR AND RELAY, ISOLATION RELAY, EVAPORATOR FREEZE THERMOSTAT, AND CRANKCASE HEATER.4 REFER TO SPECIFICATIONS FOR ADDITIONAL ACCESSORIES.
MINI–SPLIT HEAT PUMP INDOOR UNIT SCHEDULEEQUIPMENT
TAGREFERENCE PRODUCT
(DAIKIN) TYPECONDENSING
UNITAIRFLOW RATE
MAX (CFM)
DX COOLING DATA DX HEATING DATAREFRIGERANT
TYPE
ELECTRICAL DATA
MANUFACTURER REMARKSTOTAL COOLING
CAPACITY (TONS)TOTAL COOLING
CAPACITY (BTU/HR)SENSIBLE COOLINGCAPACITY (BTU/HR)
AMBIENT INDOOR AIR TEMP TOTAL HEATINGCAPACITY (BTU/HR)
AMBIENT INDOOR AIR TEMPFLA MCA MOCP VOLTS PHASEDB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF)
AC-ME-1 FTX09N WALL MOUNT CU–ME-1 400 0.75 10,200 8,010 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 8.08 10.10 15 208 1 DAIKIN REFER TO NOTESAC-ST-1 FTX09N WALL MOUNT CU–ST–1 400 0.75 10,200 8,010 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 8.08 10.10 15 208 1 DAIKIN REFER TO NOTESAC-ST-2 FTX09N WALL MOUNT CU–ST–2 400 0.75 10,200 8,010 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 8.08 10.10 15 208 1 DAIKIN REFER TO NOTESAC-ST-3 FTX09N WALL MOUNT CU–ST–3 400 0.75 10,200 8,010 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 8.08 10.10 15 208 1 DAIKIN REFER TO NOTESAC-ST-4 FTX09N WALL MOUNT CU–ST–4 400 0.75 10,200 8,010 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 8.08 10.10 15 208 1 DAIKIN REFER TO NOTESAC-ST-5 FTX09N WALL MOUNT CU–ST–5 400 0.75 10,200 8,010 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 8.08 10.10 15 208 1 DAIKIN REFER TO NOTESAC-ST-6 FTX09N WALL MOUNT CU–ST–6 400 0.75 10,200 8,010 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 8.08 10.10 15 208 1 DAIKIN REFER TO NOTES
NOTES - AC1 PROVIDE WITH PROGRAMMABLE THERMOSTAT, MICROPROCESSOR CONTROLS, BUILT-IN AUTOMATIC RESTART, SELF DIAGNOSTIC CAPABILITY AND ELECTRIC EXPANSION VALVE.2 REFER TO SPECIFICATIONS FOR ADDITIONAL ACCESSORIES.3 SELECTIONS SHOULD BE WITH ENERGY STAR RATING.
MINI–SPLIT AIR COOLED CONDENSING UNIT SCHEDULEDESIGNATION REFERENCE PRODUCT
(DAIKIN) SERVES OPERATINGWEIGHT (LBS)
REFRIGERANTTYPE
TOTAL COOLINGCAPACITY (BTU/HR) SEER CONDENSING AIR
TEMP. (ºF)
ELECTRICALREMARKSVOLTS / HERTZ /
PHASE FLA MCA MOCP
CU-ME-1 RX09N AC–ME–1 55 R410A 10,200 15.0 95.00 208/60/1 8.08 10.10 15 REFER TO NOTESCU-ST-1 RX09N AC–ST–1 55 R410A 10,200 15.0 95.00 208/60/1 8.08 10.10 15 REFER TO NOTESCU-ST-2 RX09N AC–ST–2 55 R410A 10,200 15.0 95.00 208/60/1 8.08 10.10 15 REFER TO NOTESCU-ST-3 RX09N AC–ST–3 55 R410A 10,200 15.0 95.00 208/60/1 8.08 10.10 15 REFER TO NOTESCU-ST-4 RX09N AC–ST–4 55 R410A 10,200 15.0 95.00 208/60/1 8.08 10.10 15 REFER TO NOTESCU-ST-5 RX09N AC–ST–5 55 R410A 10,200 15.0 95.00 208/60/1 8.08 10.10 15 REFER TO NOTESCU-ST-6 RX09N AC–ST–6 55 R410A 10,200 15.0 95.00 208/60/1 8.08 10.10 15 REFER TO NOTES
NOTES - CU1 OUTDOOR COMPONENT OF 09KLS71 SYSTEM (LOW AMBIENT), FURNISH WITH REFRIGERANT LINE SET.2 REFER TO SPECIFICATIONS FOR ADDITIONAL ACCESSORIES.3 FURNISH WITH ANCHOR BRACKET KITS.4 SELECTIONS SHOULD BE WITH ENERGY STAR RATING.
EXHAUST FANS SCHEDULEDESIGNATION REFERENCE PRODUCT TYPE SERVES OPERATING
WEIGHT (LBS)AIRFLOW RATE
(CFM)TOTAL STATICPRESSURE (IN.
WATER)FAN ROTATION
(RPM) DRIVE SONES MOTOR SIZE(WATTS)
ELECTRICAL DATAREMARKSVOLTS PHASE FLA MCA MOCP
EF-1 GREENHECK SP–A410 CEILING MOUNTED RUBBISH 31.0 250 0.40 1000 DIRECT 4 121.0 115 1 1.74 2.18 15 REFER TO NOTESEF-2 GREENHECK SP–110–VG CEILING MOUNTED TRASH 12.0 100 0.34 940 DIRECT 0.3 8.0 115 1 0.2 0.25 15 REFER TO NOTESEF-3 GREENHECK SP–80–VG CEILING MOUNTED TOILET 12.0 70 0.38 935 DIRECT - 6.0 115 1 0.10 0.13 15 REFER TO NOTESEF-4 GREENHECK SP–80–VG CEILING MOUNTED TOILET 12.0 70 0.38 935 DIRECT - 6.0 115 1 0.1 0.13 15 REFER TO NOTESEF-6 GREENHECK SP–A190 CEILING MOUNTED SALON 17.0 120 0.36 1400 DIRECT 3.0 43.0 115 1 1.3 1.63 15 REFER TO NOTESEF-7 GREENHECK SP–110–VG CEILING MOUNTED ARTS 12.0 100 0.34 940 DIRECT 0.3 8.0 115 1 0.2 0.25 15 REFER TO NOTESEF-8 GREENHECK SP–110–VG CEILING MOUNTED TRASH 12.0 100 0.34 940 DIRECT 0.3 8.0 115 1 0.2 0.25 15 REFER TO NOTESEF-K GREENHECK SP–110–VG CEILING MOUNTED APARTMENT KITCHEN 12.0 100 0.34 940 DIRECT 0.3 8.0 115 1 0.2 0.25 15 REFER TO NOTESEF-T GREENHECK SP–80–VG CEILING MOUNTED APARTMENT TOILET 12.0 70 0.38 935 DIRECT - 6.0 115 1 0.1 0.13 15 REFER TO NOTES
NOTES - EF1 FURNISH CAPACITOR START EXPLOSION PROOF MOTOR WITH THERMAL OVERLOADS AND 1.15 SERVICE FACTOR, BEARINGS WITH GREASE FITTINGS HAVING AN L10 LIFE OF 100,000 HOURS AND EXTENDED LUBE LINES, GRIP NOTCH BELTS, ALUMINUM BIRD SCREEN, 300 SERIES STAINLESS STEEL FASTENERS, 115 VOLT MOTORIZED DAMPER SHIPPED
LOOSE FOR FIELD INSTALLATION, NEMA-1 TOGGLE SWITCH, JUNCTION BOX MOUNTED & WIRED.2 PROVIDE A BACK DRAFT AND ONE HOUR RADIATION DAMPER FOR THE EXHAUST FAN.3 SELECTIONS SHOULD BE WITH ENERGY STAR RATING. 1 8/02/2016
1
1
1
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/2/
2016
8:2
2:06
PM
H601
HVA
C S
CH
EDU
LES
HO
PE H
ARBO
R O
F O
KLAH
OM
A C
ITY
54 IN
DIP
END
ENT
LIVI
NG
APA
RTM
ENTS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
MULTI–SPLIT VRF FAN COIL INDOOR UNIT SCHEDULEEQUIPMENT TAG REFERENCE PRODUCT
(DAIKIN) TYPE CONDENSINGUNIT
AIRFLOW RATEMAX (CFM)
DX COOLING DATA DX HEATING DATAREFRIGERANT
TYPE
ELECTRICAL DATAMANUFACTURER REMARKSTOTAL COOLING
CAPACITY (TONS)TOTAL COOLING
CAPACITY (BTU/HR)SENSIBLE COOLINGCAPACITY (BTU/HR)
AMBIENT INDOOR AIR TEMP TOTAL HEATINGCAPACITY (BTU/HR)
AMBIENT INDOOR AIR TEMP FLA MCA MOCP VOLTS PHASEDB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF) DB (ºF) WB (ºF)FCU-4 FDXS12LVJU HORIZONTAL DUCTED (SLIM) CU-1 305 1.0 11,500 95 75 80 67 11,500 47.0 43.0 70 70 R-410A 15 208 1 DAIKIN REFER TO NOTESFCU-5 FDXS12LVJU HORIZONTAL DUCTED (SLIM) CU-1 305 1.0 11,500 95 75 80 67 11,500 47.0 43.0 70 70 R-410A 15 208 1 DAIKIN REFER TO NOTESFCU-6 0.2 0.25 15FCU-7 FDXS09LVJU HORIZONTAL DUCTED (SLIM) CU-1 305 0.75 8,500 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 15 208 1 DAIKIN REFER TO NOTESFCU-10 FDXS09LVJU HORIZONTAL DUCTED (SLIM) CU-1 305 0.75 8,500 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 15 208 1 DAIKIN REFER TO NOTESFCU-12 FDXS09LVJU HORIZONTAL DUCTED (SLIM) CU-1 305 0.75 8,500 95 75 80 67 10,000 47.0 43.0 70 70 R-410A 15 208 1 DAIKIN REFER TO NOTES
MULTI-SPLIT AIR COOLED CONDENSING UNIT SCHEDULEDESIGNATION REFERENCE PRODUCT
(DAIKIN) SERVES OPERATINGWEIGHT (LBS) REFRIGERANT TYPE TOTAL COOLING
CAPACITY (BTU/HR) SEER CONDENSING AIRTEMP. (ºF)
ELECTRICALREMARKSVOLTS / HERTZ /
PHASE FLA MCA MOCP
CU-1 RMXS48LVJU FCU 1–5 283 R410A 48,000 18.8 208/60/1 21.6 27 30 REFER TO NOTES
NOTES
1 FURNISH WITH SINGLE POINT WIRING KIT, ECM MOTOR, THERMOSTATIC EXPANSION VALVE, ELECTRIC HEATER AND SEVEN DAY PROGRAMMABLE THERMOSTAT.2 FILTERS SHALL BE 1" THICKNESS THROW AWAY3 COOLING CAPACITIES INDICATED ARE NET CAPACITIES.
AIR DISTRIBUTION DEVICES SCHEDULE
DESIGNATION REFERENCE PRODUCT TYPE TOTAL PRESSUREDROP (IN. WATER)
NECK SIZE(IN.)
PANEL SIZE(IN.)
ACTUAL NCLEVEL
CONSTRUCTION FINISH NOTES
SD-4 TITUS TMS-AA SUPPLY LAY - IN MOUNT 0.05 6" ROUND 12 X 12 25 ALUMINUM WHITE 1SD-1 TRUAIRE MODEL 102 SUPPLY LAY - IN MOUNT 0.04 12 X 6 13.5 X 7.5 - ALUMINUM WHITE 1
TITUS TMS-AA SUPPLY LAY - IN MOUNT 0.05 6" ROUND 12 X 12 25 ALUMINUM WHITE 1SD-2 TITUS TMS-AA SUPPLY LAY - IN MOUNT 0.05 8" ROUND 24 X 24 25 ALUMINUM WHITE 1SD-3 TITUS TMS-AA SUPPLY LAY - IN MOUNT 0.05 10" ROUND 24 X 24 25 ALUMINUM WHITE 1SD-6 TITUS MODEL 301 SIDE WALL 0.132 12 X 8 13.5 X 10 - ALUMINUM WHITERD-1RD-1 TITUS PAR-AA RETURN LAY IN MOUNT 0.19 - 24 X 24 25 ALUMINUM WHITE 1
1 8/02/2016
NOTES:1. PROVIDE ONE HOUR RADIATION DAMPER
1
EXPIRES: 07-31-2016
28881L
OR
NIC
ES E
D
P
K AMOL A OH
RE
ESF S I OLAN
ENE
GI
N
Robert A.Boellner
Tyso
n an
d B
illy
Arc
hite
cts,
P.C
.40
00 M
orsa
y D
rive
Roc
kfor
d, IL
611
07(8
15)
229-
8222
FAX
: (81
5) 2
29-8
218
Sheet No:
of sheets
ww
w.ty
sona
ndbi
lly.c
omP
roje
ct N
umbe
r
REVISION DATE
Dat
eD
rn.
App
d.BO
ND
ING
CO
.C
ON
TRA
CTO
R
OW
NER
ARC
HIT
ECT
630
N. C
HU
RC
H S
T. S
UIT
E 10
1R
ockf
ord,
IL
611
03(8
15)
540-
4733
FAX
: (81
5) 9
65-2
491
ANC
HO
R H
OU
SIN
GD
EVEL
OPM
ENT,
LLC
PERMIT SET8/1/
2016
5:1
2:03
PM
P600
PLU
MBI
NG
SC
HED
ULE
HO
PE H
ARBO
R O
F O
KLAH
OM
A C
ITY
54 IN
DIP
END
ENT
LIVI
NG
APA
RTM
ENTS
P14-
4800
07-1
3-20
16Au
thor
Che
cker
PLUMBING FIXTURE SCHEDULE
TAG DESCRIPTION LOCATION FIXTURE VALVE TRIM WHA TYPE ADAROUGH-IN SIZES ELECTRICAL
NOTESW V CW HW TYPE EMERG.EWC-1 ELECTRICAL WATER COOLER CORRIDOR WF-6 - TR-5 - Yes 2" 1-1/2" 1/2" - PLUG No -FD-1 FLOOR DRAIN GENERAL D-1 - - - No * * - - - No *REFER TO PLANS FOR SIZEFD-2 FLOOR DRAIN MECHANICAL ROOM D-2 - - - No * * - - - No *REFER TO PLANS FOR SIZEHB-1 HOSE BIBB MECHANICAL ROOM - - - - No - - 3/4" - - No -L-1 LAVATORY APARTMENT BATHROOMS L-3 F-3B TR-1 - No 2" 1-1/2" 1/2" 1/2" - No -L-2 LAVATORY PUBLIC BATHROOMS L-2 F-4A TR-1 A Yes 2" 1-1/2" 1/2" 1/2" BATTERY No -
RB-1 REFRIGIRATOR/ICE REFRIGIRATOR/ICE HB-1 - - - No - - 1/2" - - No -S-1 KITCHEN SINK APARTMENT S-2 F-7 TR-2 - Yes 2" 1-1/2" 1/2" 1/2" - No -S-2 GENERAL SINK COMMUNITY / DINING S-4 F-1B TR-2 - No 2" 1-1/2" 1/2" 1/2" - No FIXTURE BY FOOD SERVICE CONSULTANTS-3 SALON SINK SALON S-6 F-9 TR-6 - No 2" 1-1/2" 1/2" 1/2" - No -
SH-1 SHOWER APARTMENT BATHROOMS BU-9 BV-2 - - Yes 3" 1-1/2" 1/2" 1/2" - No SHOWER HEADS WITH A MAXIMUM OF 2.5GPM FLOW RATEWB-1 WASH BOX CLOTHES WASHERS HB-2 - - A No 3" 1-1/2" 1/2" 1/2" - No -WC-1 WATER CLOSET APARTMENT BATHROOMS T-5 FV-3I - A Yes 4" 2" 1/2" - BATTERY No -WC-2 WATER CLOSET PUBLIC BATHROOMS T-1 FV-3I - A Yes 4" 2" 1-1/2" - BATTERY No -WH-1 WALL HYDRANT BUILDING EXTERIOR H-1 - - A No - - 3/4" - - No -
PLUMBING EQUIPMENT SCHEDULE
TAG DESCRIPTION LOCATION CAPACITY AND PERFORMANCE CONNECTION SIZES ELECTRICAL REQUIREMENTS BAS MAKE & MODEL NOTESINLET OUTLET HP KW V PH KAIC RATING EMERG.BFP-1 BACKFLOW PREVENTER MECHANICAL ROOM 210 GPM @ 15 PSI LOSS 3" 3" - - - --- - No No ZURN: 375 -
DWBP-1 DOMESTIC WATER BOOSTER PUMP MECHANICAL ROOM 110 GPM @ 60FD TDH 4" 4" 7.5 - 208 3 - No No GROUNDFOS: MPC-E 3CR15 -EWH-1,2,3 ELETRICAL WATER HEATERS MECHANICAL ROOM (3) AT 60KW, 100GAL, 246GPH @ 100°F 1 1/2" 1 1/2" - 60 208 3 - No Yes A.O.SMITH: DSE-100 -
HWCP-1 HOT WATER CIRCULATION PUMP-110 MECHANICAL ROOM 15 GPM @ 40 Ft. TDH 1 1/4" 1 1/4" 1/2 - 120 1 - No Yes GRUNDFOS: MAGNA3 50-150 INTEGRAL VARIABLE SPEED DRIVE RESPONDING TO INTEGRALTEMPERATURE AND PRSSURE SENSORS
SP-1 SUMP PUMP ELEVATOR SUMP PITS 50 GPM @ 30 Ft. TDH 2" 2" 1/2 - 120 1 - No No STANCOR: SE-50 PROVISE WITH OIL DISCRIMINATING CONTROL SYSTEMTMV-1 THERMOSTATIC MIXING VALVE MECHANICAL ROOM 133GPM @ 10 PSI LOSS 3" 3" - - 120 1 - No Yes ARMSTRONG: DMC 80 -
1 8/02/2016
1