Page 1
HRU3
UG4
ICT 2150
CT1 CT2
F-R2
F-R1
F
E
G
I
H
ICT 2150
R6 R6
R7 R7
R8
R9
R8
R9
R10
R10
R11
R12
R11
R12
R14
R13
R15
R14
R13
R15
R16
R16
UG2
HRU4
UF3
UF2
UG3B
UG3A
HRU2
F G
F G
FD1
FD2
DA1
DA2
DA3
2 WAY
2 WAY
2 WAY
2 WAY
2 WAY
2 WAY
TYPICAL EXTERNAL WALL DUCT OR
FIRE DAMPER INSTALLATION
MEZZ FLANGE
FIBREGLASS MEMBRANE & RESIN
WATERPROOFING WHERE DUCTS
PENETRATE WALLS.
(ALL ROUND DUCT)
ADDITIONAL DUCT STIFFENERS
WHERE REQUIRED
SECTION OF DUCT TO BE INSTALLED,
SEALED & FLASHED OFF BEFORE THE
REST OF THE DUCTING IS ADDED.
SHEET-METAL WATERPROOFING
TO BE BOLTED TO WALL &
IN BETWEEN DUCT FLANGES c/w
FIBREGLASS MEMBRANE & RESIN
WATERPROOFING
ALL DUCT JOINTS TO BE SEALED
WITH FIBREGLASS MEMBRANE
& RESIN WATERPROOFING
(EXPOSED DUCTING TO BE PAINTED)
NOTE:-
DUCTING TO SLOPE
TOWARDS A/C UNIT.
(DUCTING TO BE LAGGED
WITH 50mm, F.R.K.
FOIL-FACED FIBREGLASS.)
DUCTING TO BE EXTERNALLY
LAGGED 50mm POLYSTYRENE &
FIBREGLASS MEMBRANE
10
6
5
11
7
PIPE SUPPORT DETAIL - 125Ø
8 OFF REQUIRED
PIPE SUPPORT DETAIL - 65Ø
4 OFF REQUIRED
PIPE SUPPORT DETAIL
1 OFF REQUIRED
PIPE SUPPORT DETAIL
1 OFF REQUIRED
PIPE SUPPORT DETAIL
1 OFF REQUIRED
PIPE SUPPORT DETAIL
3 OFF REQUIRED
PIPE SUPPORT DETAIL
1 OFF REQUIRED
PIPE SUPPORT DETAIL - 50Ø
3 OFF REQUIRED
PIPE SUPPORT DETAIL - 50Ø
5 OFF REQUIRED
F
T.O.C :145.000
F-R1
F
T.O.C :145.000
F-R2
AIR BLEED
SCALE 1:10
06 07 08 09 10 11
SECTION FF
SCALE 1:50
SECTION GG
SCALE 1:50
DUCT SPLITTERS
DUCTWORK NOTES:
3: CHILLED WATER VALVES:
1: GENERAL NOTES:
2: CHILLED WATER PIPING NOTES:
4: CHILLED WATER PIPE INSULATION:
NOTES
6: CONDENSER WATER ISOLATION VALVES:
5: CONDENSER WATER PIPING NOTES:
AutoCAD SHX Text
1600x650
AutoCAD SHX Text
750x750 R/A
AutoCAD SHX Text
550x750 EXT + R/A
AutoCAD SHX Text
850x750 R/A
AutoCAD SHX Text
500x500 TOILET EXTRACT
AutoCAD SHX Text
1600x600
AutoCAD SHX Text
1500x550
AutoCAD SHX Text
27 kw H/Bank
AutoCAD SHX Text
1143 / 1030 / 3R / 10F
AutoCAD SHX Text
R/H Coil(WAS)
AutoCAD SHX Text
HEAT RECOVERY WHEEL
AutoCAD SHX Text
HEAT RECOVERY WHEEL
AutoCAD SHX Text
27 kw H/Bank
AutoCAD SHX Text
1143 / 1030 / 3R / 10F
AutoCAD SHX Text
R/H Coil(WAS)
AutoCAD SHX Text
27 kw H/Bank
AutoCAD SHX Text
1143 / 1030 / 3R / 10F
AutoCAD SHX Text
R/H Coil(WAS)
AutoCAD SHX Text
HEAT RECOVERY WHEEL
AutoCAD SHX Text
27 kw H/Bank
AutoCAD SHX Text
1143 / 1030 / 3R / 10F
AutoCAD SHX Text
R/H Coil(WAS)
AutoCAD SHX Text
27 kw H/Bank
AutoCAD SHX Text
1143 / 1030 / 3R / 10F
AutoCAD SHX Text
R/H Coil(WAS)
AutoCAD SHX Text
27 kw H/Bank
AutoCAD SHX Text
1143 / 1030 / 3R / 10F
AutoCAD SHX Text
R/H Coil(WAS)
AutoCAD SHX Text
80%%C CHW S&R
AutoCAD SHX Text
80%%C CHW S&R
AutoCAD SHX Text
125%%C CHW S&R
AutoCAD SHX Text
125%%C CHW S&R
AutoCAD SHX Text
125%%C CHW S&R
AutoCAD SHX Text
125%%C CHW S&R
AutoCAD SHX Text
150%%C CHW S&R
AutoCAD SHX Text
150%%C CHW S&R
AutoCAD SHX Text
150%%C CDW S&R
AutoCAD SHX Text
150%%C CDW S&R
AutoCAD SHX Text
150%%C CDW S&R
AutoCAD SHX Text
150%%C CDW S&R
AutoCAD SHX Text
150%%C CDW S&R
AutoCAD SHX Text
OFFSETS OVER 450mm HIGH UPSTAND BEAMS
AutoCAD SHX Text
4 OFF 150 CONDENSERWATER PIPES FROM PLANTROOM IN BASEMENT BELOW
AutoCAD SHX Text
2 OFF 150 CHILLEDWATER PIPES FROM PLANTROOM IN BASEMENT BELOW
AutoCAD SHX Text
1150x450
AutoCAD SHX Text
BALANCING DAMPER
AutoCAD SHX Text
1350x550
AutoCAD SHX Text
1350x550
AutoCAD SHX Text
REFER TO AC-06 FIRST FLOOR DRAWING FOR CONTINUATION OF DUCTING
AutoCAD SHX Text
REFER TO AC-06 FIRST FLOOR DRAWING FOR CONTINUATION OF DUCTING
AutoCAD SHX Text
MAKE UP WATER SUPPLY BY OTHERS
AutoCAD SHX Text
SUPPLY & RETURN AIR DUCTING TO BE INTERNALLY LINED WITH 25mm SONIC & EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
EXTRACT / RETURN DUCTING TO HRU-3 EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
700x450 O/A
AutoCAD SHX Text
SUPPLY & RETURN AIR DUCTING TO BE INTERNALLY LINED WITH 25mm SONIC & EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
EXTRACT / RETURN DUCTING TO HRU-4 EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
1850x550
AutoCAD SHX Text
750x1400
AutoCAD SHX Text
1400x1500 WEATHER LOUVRE
AutoCAD SHX Text
550x1000
AutoCAD SHX Text
550x1000
AutoCAD SHX Text
600x1400
AutoCAD SHX Text
500x350 COMBI FIRE DAMPER
AutoCAD SHX Text
500x350 COMBI FIRE DAMPER
AutoCAD SHX Text
SUPPLY & RETURN AIR DUCTING TO BE INTERNALLY LINED WITH 25mm SONIC & EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
FRESH AIR DUCTING TO/EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
SUPPLY & RETURN AIR DUCTING TO BE INTERNALLY LINED WITH 25mm SONIC & EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
SUPPLY & RETURN AIR DUCTING TO BE INTERNALLY LINED WITH 25mm SONIC & EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
SUPPLY & RETURN AIR DUCTING TO BE INTERNALLY LINED WITH 25mm SONIC & EXTERNALLY INSULATED WITH 50mm POLYSTYRENE
AutoCAD SHX Text
50%%C CHW S&R
AutoCAD SHX Text
65%%C CHW S&R
AutoCAD SHX Text
50%%C CHW S&R
AutoCAD SHX Text
50%%C CHW S&R
AutoCAD SHX Text
50%%C CHW S&R
AutoCAD SHX Text
80%%C CHW S&R
AutoCAD SHX Text
65%%C CHW S&R
AutoCAD SHX Text
65%%C CHW S&R
AutoCAD SHX Text
50%%C CHW S&R
AutoCAD SHX Text
50%%C CHW S&R
AutoCAD SHX Text
DISCHARGE UN-INSULATED
AutoCAD SHX Text
PLATFORM OVER CHILLED WATER PIPING BY OTHERS - TO AVOID DAMAGE
AutoCAD SHX Text
ACCESS ONTO ROOF
AutoCAD SHX Text
WATER TREATMENT PLANT
AutoCAD SHX Text
WALKWAY OVER DUCT AND PIPING BY BUILDER
AutoCAD SHX Text
AIR BLEED VALVES
AutoCAD SHX Text
AIR BLEED VALVES
AutoCAD SHX Text
ACCESS ONTO ROOF
AutoCAD SHX Text
ACCESS ONTO ROOF
AutoCAD SHX Text
45° DISCHARGECOWL + WMS
AutoCAD SHX Text
45° DISCHARGECOWL + WMS
AutoCAD SHX Text
DISCHARGE VENTURI COWL
AutoCAD SHX Text
BLACK WELDED
AutoCAD SHX Text
REFER TO GROUND FLOOR DRAWING AC-05A FOR SECTIONS F & G
AutoCAD SHX Text
1200mm HIGH MASONARY HOUSING AROUND OPENING c/w SLAB OVER BY OTHERS
AutoCAD SHX Text
650x600 BLACK WELDED KITCHEN EXTRACT DUCT FROM GROUND FLOOR
AutoCAD SHX Text
650x600 FRESH AIR MAKE UP DUCT TO GROUND FLOOR LEVEL
AutoCAD SHX Text
100%%C CHW S&R
AutoCAD SHX Text
100%%C CHW S&R
AutoCAD SHX Text
80%%C CHW S&R
AutoCAD SHX Text
80%%C CHW S&R
AutoCAD SHX Text
0.75Kw MOTOR 6 POLE
AutoCAD SHX Text
10.1 AMP DOL
AutoCAD SHX Text
0.2.2Kw MOTOR 4 POLE
AutoCAD SHX Text
32.2 AMP DOL
AutoCAD SHX Text
AIR BLEED VALVES
AutoCAD SHX Text
AIR BLEED VALVES
AutoCAD SHX Text
AIR BLEED VALVES
AutoCAD SHX Text
AIR BLEED VALVES
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
2 x 125%%C
AutoCAD SHX Text
CHW PIPES
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
2 x 65%%C
AutoCAD SHX Text
CHW PIPES
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
2 x 150%%C
AutoCAD SHX Text
CHW PIPES
AutoCAD SHX Text
4 x 150%%C
AutoCAD SHX Text
CDW PIPES
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
2 x 150%%C
AutoCAD SHX Text
CHW PIPES
AutoCAD SHX Text
4 x 150%%C
AutoCAD SHX Text
CDW PIPES
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
2 x 150%%C
AutoCAD SHX Text
CHW PIPES
AutoCAD SHX Text
4 x 150%%C
AutoCAD SHX Text
CDW PIPES
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
2 x 50%%C
AutoCAD SHX Text
CHW PIPES
AutoCAD SHX Text
100x50 CHANNEL
AutoCAD SHX Text
2 x 50%%C
AutoCAD SHX Text
CHW PIPES
AutoCAD SHX Text
45 INLET COWLc/w WMS
AutoCAD SHX Text
DISCHARGE VENTURI COWL
AutoCAD SHX Text
BLACK WELDED
AutoCAD SHX Text
15 AIR BLEEDVALVE
AutoCAD SHX Text
CHW PIPING INSULATION
AutoCAD SHX Text
20mm SOCKETS
AutoCAD SHX Text
FOR SENSORS
AutoCAD SHX Text
TYPICAL AIR
AutoCAD SHX Text
HANDLING UNIT
AutoCAD SHX Text
VALVE CLUSTER
AutoCAD SHX Text
JUBILEE CLAMPS AND STRAPPED WITH DUCT TAPE
AutoCAD SHX Text
ALL FLEXIBLE DUCTING TO BE FIXED TO SPIGOTS WITH
AutoCAD SHX Text
ALL DUCTWORK TO BE HUNG ON 30x50x1.6 G.S.M
AutoCAD SHX Text
ALL HANGERS AND BRACKETS TO BE GALVANISED.
AutoCAD SHX Text
SPIGOTS TO BE EXTERNALLY INSULATED WITH 25 FOIL
AutoCAD SHX Text
ALL A.C DUCTING TO BE EXTERNALLY INSULATED WITH
AutoCAD SHX Text
ALL FLEXIBLE DUCTING TO BE FACTORY PRE-INSULATED.
AutoCAD SHX Text
ALL DUCT WORK TO BE MANUFACTURED TO S.A.N.S
AutoCAD SHX Text
FLEXIBLE CONNECTIONS TO BE FITTED TO ALL DUCTING
AutoCAD SHX Text
BETWEEN AIRHANDLING AND PACKAGE UNITS, FANS, ETC.
AutoCAD SHX Text
EXCEEDING 600 SEMI PERIMETER OR ONE SIDE EXCEEDS
AutoCAD SHX Text
1238/05 STANDARDS, WITH FLANGED JOINTS ON DUCTS
AutoCAD SHX Text
SPLITTER RADII
AutoCAD SHX Text
ALL VENTILATION DUCTING TO BE UNINSULATED.
AutoCAD SHX Text
25mm FOIL FACED FIBREGLASS INSULATION.
AutoCAD SHX Text
CHANNEL TRAPEZE HANGERS WITH 8%%C RODS.
AutoCAD SHX Text
FACED FIBREGLASS.
AutoCAD SHX Text
750 AND S&D JOINTS ON SMALLER DUCTS.
AutoCAD SHX Text
SUPPLY AIR ONLY
AutoCAD SHX Text
(W) IN MM
AutoCAD SHX Text
DUCT WIDTH
AutoCAD SHX Text
1201 TO 2400
AutoCAD SHX Text
300 TO 600
AutoCAD SHX Text
601 TO 900
AutoCAD SHX Text
901 TO 1200
AutoCAD SHX Text
1.1 THIS DRAWING FORMS PART OF THE SPECIFICATION AND MUST BE READ
AutoCAD SHX Text
THEREWITH AND INCONJUNCTION WITH THE DRAWINGS AS LISTED THEREIN.
AutoCAD SHX Text
2.3.1 %%C15 TO %%C50 : SCREWED MALLEABLE CAST IRON.
AutoCAD SHX Text
2.3.2 %%C65 UPWARDS : BUTT WELD TO ANSI B16.9
AutoCAD SHX Text
2.4 ALL CHILLED WATER PIPE FLANGES SHALL BE TABLE D SLIP ON.
AutoCAD SHX Text
2.5.2 FOR FLANGES USE RUBBER INSERTION.
AutoCAD SHX Text
3.1.1 %%C15 TO %%C50 : BALL VALVE ,SCREWED BSP ENDS.
AutoCAD SHX Text
3.1.2 %%C65 TO %%C150 : LONG STEM BUTTERFLY VALVES
AutoCAD SHX Text
2.3 ALL CHILLED WATER FITTINGS SHALL CONFORM WITH THE FOLLOWING:
AutoCAD SHX Text
2.5 CHILLED WATER PIPE GASKETS .
AutoCAD SHX Text
2.5.1 FOR SCREWED PIPING USE THREAD SEAL (PTFE)
AutoCAD SHX Text
3.1 ALL CHILLED WATER ISOLATING VALVES TO BE AS FOLLOWS:
AutoCAD SHX Text
1.3 ALL DIMENSIONS TO BE CHECKED ON SITE PRIOR TO MANUFACTURE.
AutoCAD SHX Text
2.1 ALL CHILLED WATER PIPE WORK AND FITTINGS SHALL BE INSTALLED AS PER THE
AutoCAD SHX Text
2.2 ALL CHILLED WATER PIPING SHALL BE S.A.B.S 62 & 719 MEDIUM BLACK PIPING.
AutoCAD SHX Text
2.2.1 PIPE SIZES %%C15 TO %%C50 - S.A.B.S 62 MED. BLACK SCREWED ENDS TO
AutoCAD SHX Text
SPECIFICATION
AutoCAD SHX Text
1.2 REFER TO THE SPECIFICATION FOR ALL EQUIPMENT DETAILS.
AutoCAD SHX Text
ISO-R7 (BS21) THREAD.
AutoCAD SHX Text
2.2.2 SIZE %%C65 TO %%C150 - S.A.B.S 62 MED. BLACK BUTT WELDED.
AutoCAD SHX Text
2.2.3 SIZE %%C200 UPWARD - S.A.B.S 719 MED. BLACK BUTT WELDED.
AutoCAD SHX Text
4.1 ALL CHILLED WATER PIPING TO BE INSULATED AND CLAD AS PER THE
AutoCAD SHX Text
ENGINEERS SPECIFICATION.
AutoCAD SHX Text
5.5.3 SIZE %%C200 UPWARD - S.A.B.S 719 MED. BLACK BUTT WELDED. HOT DIP
AutoCAD SHX Text
5.5.2 SIZE %%C65 TO %%C150 - S.A.B.S 62 MED. BLACK BUTT WELDED. HOT DIP
AutoCAD SHX Text
5.5.1 PIPE SIZES %%C15 TO %%C50 - S.A.B.S 62 MED. BLACK GALVANIZED TO
AutoCAD SHX Text
5.2 ALL CONDENSER WATER PIPING SHALL BE S.A.B.S 62 & 719 MEDIUM
AutoCAD SHX Text
5.1 ALL CONDENSER WATER PIPE WORK AND FITTINGS SHALL BE INSTALLED
AutoCAD SHX Text
5.3 ALL CONDENSER WATER FITTINGS SHALL CONFORM WITH THE FOLLOWING:
AutoCAD SHX Text
5.4 ALL CONDENSER WATER PIPE FLANGES SHALL BE TABLE D SLIP ON.
AutoCAD SHX Text
5.3.1 %%C15 TO %%C50 : SCREWED MALLEABLE CAST IRON GALVANIZED TO
AutoCAD SHX Text
GALVANIZED TO S.A.B.S 763 AFTER FABRICATION.
AutoCAD SHX Text
GALVANIZED TO S.A.B.S 763 AFTER FABRICATION.
AutoCAD SHX Text
6.1 ALL CHILLED WATER ISOLATING VALVES TO BE AS FOLLOWS:
AutoCAD SHX Text
5.5.1 FOR SCREWED PIPING USE THREAD SEAL (PTFE)
AutoCAD SHX Text
5.5 CONDENSER WATER PIPE GASKETS .
AutoCAD SHX Text
5.5.2 FOR FLANGES USE RUBBER INSERTION.
AutoCAD SHX Text
5.3.2 %%C65 UPWARDS : BUTT WELD TO ANSI B16.9
AutoCAD SHX Text
S.A.B.S SCREWED ENDS ISO-R7 (BS21) THREAD.
AutoCAD SHX Text
AS PER THE SPECIFICATION
AutoCAD SHX Text
BLACK PIPING.
AutoCAD SHX Text
S.A.B.S 763
AutoCAD SHX Text
BSP ENDS.
AutoCAD SHX Text
6.1.1 %%C15 TO %%C50 : BALL VALVE ,SCREWED
AutoCAD SHX Text
6.1.2 %%C65 TO %%C150 : SHORT STEM BUTTERFLY VALVES
AutoCAD SHX Text
4.2. INSULATION THICKNESSES
AutoCAD SHX Text
15mm - 50mm - 25mm THICK
AutoCAD SHX Text
65mm - 150mm - 40mm THICK
AutoCAD SHX Text
150mm - 300mm - 50mm THICK