Types SSVT and SSMV oil-filled stationservice voltage transformersAuxiliary power from high voltagetransmission lines
ABB product bulletin | Type s SSVT and S SMV oil-f illed sta tion se rvice voltage transformers 3
ABB has been producing instrument transformers formore than 60 years. Thousands of our products per formvital functions in electric power networks around theworld – day after day, all year round. Their main applicationsinclude revenue metering, control, indication and relayprotection.
All instrument transformers supplied by ABB are tailormadeto meet the needs of our customers. An instrumenttransformer must be capable of withstanding very highstresses in all climatic conditions. We design andmanufacture our products for a service life of at least 30years. Actually, most last even longer.
ABB’s family of Station Service Voltage Transformer (SSVT)products combine the characteristics of voltage transformerswith the power rating capability of distribution transformers.This results in fully-insulated products, up to 362 kV, withpower performance up to 333 kVA.
Station Service Voltage Transformer (SSVT)The SSVT is a line-to-ground connected single-phasetransformer that can be used either as an individual unit forsupplying single-phase loads, or in a three-phase bank tosupport larger kVA three-phase loads. The high voltagewinding with graded insulation is applied line-to-ground ongrounded WYE systems, and is coupled to secondarywindings through silicon steel cores.
This unique combination allows for a reliable, directconnection to the high voltage transmission line in aconvenient, economical installation using the pedestalmounted transformer. The power transformation is takendirectly from the high voltage primary to the low voltageoutput that supplies 125/250 VAC power, 277 VAC, 480 VAC,or any output up to 600 VAC to supply lighting loads, pumpand motor loads, instrumentation and rural electrificationpower needs.
Station Service Voltage Transformer for Medium Voltage(SSMV)This variation of the SSVT transforms power directly from thehigh voltage transmission line connetion and steps it down toa medium voltage output capable of transferring a reasonableamount of power over immediate d istances (up to 8-10 kM).This allows loads that are removed from the transmission r ightof way, to be powered with a cost effective transformer forremote/rural locations The design consists of the sameconstruction as the original SSVT, but with medium voltagebushings in the low side compartment to provide clearance for theincreased voltage level.
Standards - ElectricalThe SSVT transformers can meet the applicable sections(latest version) of the following standards respectively:
– IEEE C57.13 regarding Instrument transformers– IEEE C57.12.00 regarding Distribution/voltage transformers– CAN/CSA C60044-2 regarding Inductive voltage transformers– IEC 60044 regarding Instrument, voltage and current transformers– IEC 60076 regarding Distribution/power transformers
Standards - Quality– ISO 9001: 2000
Standards - Environmental– ISO 13001: 2004
Standards - Occupational Health & Safety– OHSAS 18001
4 Types SSVT and SSMV oil-filled station service vo ltage transformers | ABB product bu lletin
Applications
Switching station applicationMany utilities maintain switching stations for interconnectionof transmission lines. Frequently, these substations do nothave low voltage control power available from equipmentinside the station, rather they rely on distribution feeders fromoutside the substation (which may be owned by another utilitycompany). SSVT’s are mounted onto a pedestal, with theprimary tied to the incoming transmission line with the outputsecondary control wiring connected to the station powerpanel.
Benefits:- Eliminates the need for obtaining long-term power from an outside supplier- Reliable power for the substation with connection directly to the transmission line- Control power source self-contained within substation boundary
Rural electrification applicationIn developing countries where transmission systems arein place but a wide-spread distribution infrastructure islacking, SSVT’s can be used as a compact transformer togreatly reduce the electrification costs for small villages orcompounds. SSVT’s can either be used with its low voltageoutput to directly supply needed power for in-close loads nearthe transmission right of way, or simply step up the SSVT lowvoltage output through distribution transformers for a localdistr ibution network.
Small substations can be sited specific to the loadrequirements without a large distribution network. Tappingthe high voltage transmission line and connecting SSVT’s witha small footpr int substation will provide affordable, readily-available electricity to mill ions of people presently withoutpower.
Benefits:- Cost of electrification can be greatly reduced for developing countries with limited size load requirements and small substations- Output can be tailored to each specific voltage and load requirement using the flexible SSVT capability- Modular substations using the SSVT as the main transformer can be pre-packed, shipped in containers, and quickly erected on site to reduce time and costs
Remote cell tower site applicationGiven the rapid expansion of the cellular telephone industry,it is vital that all possible points be reached with clearcommunication signals. Given the limited distances thatcellular signals can be transmitted, it is often necessary to sitecell towers in remote locations to enable repetition of phonetransmissions. When a selected cell tower site lacks nearbyelectrical secondary feeders, locating the cell tower adjacentto the high voltage transmission line is now an economicaloption. A tap can be taken from the transmission line to anSSVT placed in a fenced-in area (a miniature substation) toenergize the cell tower. Where permitted, the cell transceivercan be located directly on the transmission tower.
Benefits:- Cost savings compared to installing a dedicated distribution feeder over long distances (Evaluation shows break-even point to be approximately ½ to 1 mile of distribution line.)- User advantage of economical power purchases at transmission level (with SSVT ownership)- Avoid costs of tower permits when installing on existing towers
ABB product bulletin | Type s SSVT and S SMV oil-f illed sta tion se rvice voltage transformers 5
Applications (cont‘d)
Substation aux iliary power application without using powertransformer tertiaryIn normal transmission substation installations, powertransformers are typically equipped with tertiary windingsin order to supply distribution transformers with 15 or 25kV primary voltages for substation load. The distributiontransformers supply control power for the substation location.In substations where the power transformers do not havetertiary windings, control power must be supplied by alternatemeans. SSVT’s can be mounted on the bus, as both a buspotential transformer with measuring winding, and a controlpower source.
Benefits:- Control power is supplied from within the substation directly from the transmission bus, improving reliability- Power transformer tertiary can remain buried, which prevents connection abuse and improves power quality control- Power from transmission line is less susceptible to weather- related outages- Dual functions incorporated, with SSVT’s acting as a power source and voltage control winding
Transmission line lighting applicationTransmission towers which span a body of water requireoverhead lighting be supplied for safety and securitypurposes. ABB has designed a 46 kV, 5 kVA power ratingtransformer with hanger brackets for pole-mounting, andfusing in the control cabinet for mounting atop a transmissionpole adjacent to the transmission line. This arrangementeliminated the need to maintain control wiring at near groundlevel from distribution transformers high up the transmissiontower. SSVT’s safely provide lighting power directly on thetower.
Benefits:- Small footprint allowing restricted installation in a compact space near transmission line- Short distance control wiring to reduce losses- Self-contained fusing and mounting format for quicker installation and reduced costs
Transmission switch automation applicationTo improve the service of a substation which feeds a 69 kVradial tap line, switches can be automated to sectionalizethe line in the event of a fault. A distribution feeder may notalways be available in order to power the SCADA RTU, radio,and motor-operated switches, so by supplying a 69 kV SSVTwith 10 kVA power rating and a measuring winding, utilitiescan achieve both control power and tap voltage indication formonitoring circuits. If necessary, additional standard voltagetransformers can be supplied on the loop line to monitorvoltages on both sides of the switches.
Benefits:- Savings from reduced space and installation times on compact switch structure arrangement- Self-contained power from transmission line, reliability assured by transmission connection- Could be used as part of a measuring circuit if primary measuring where needed
6 Types SSVT and SSMV oil-filled station service vo ltage transformers | ABB product bu lletin
Features and benefits
The SSVT and SSMV feature rugged transformer designsincorporating high creepage insulators and high over-voltagecapability with impedance protection to limit fault currents.
Features and benefits of the transformer designs include:
Incorporated inductive voltage transformer insulation andmagnetic performance.- Readily accommodates high momentary and maximum continuous operation voltage relative to power transformers.- Fully-rated impulse levels provide improved withstand to HV transients.
Low profile, compact overall size and weight relative to powertransformers.- Units do not require expensive concrete pad, simply a support stand and small foundation.- Minimal substation footprint.
Low cost alternative to distribution feeder construction.- Self-contained power source within substation fence, not subject to weather related outages.- Simplest power source for reliable station power.
Power ratings up to 333 kVA per phase (1 MVA bank),available with isolated measuring winding option.- Ample single-phase power ratings for any station power need, as well as for limited power applications.- Line voltage information and control power needs from one source.
Reliable transmission voltage access for substation power.- Very reliable control power access available directly from the transmission lines.- Eliminates need to bring in outside distribution voltage.- Not typically subject to line outages.
Special designs easily accommodate for different low voltagesand outputs.- Quick transformer availability with customer-specified design to meet site needs.
Isolated windings for flexibility in making various requiredsecondary connections.- Access to the full kVA regardless of voltage is needed.- Standard design can be used for both single phase installation, as well as three-phase needs.
High seismic withstand capability.- Most designs are rated for high seismic withstand per IEEE 693 via dynamic analysis.- Mechanically robust to withstand transportation and handling.
Short lead-time Station Service Voltage Transformer.- Produced using lean manufacturing techniques to provide short lead times and to prevent project delays.
ABB product bulletin | Type s SSVT and S SMV oil-f illed sta tion se rvice voltage transformers 7
Product details
The ABB Station Service Voltage Transformer (SSVT)incorporates an integral inner condenser bushing connectedto a layer wound coil (except 50 and 100 kVA 230 kV unitwhich is a disk wound design).
1 NEMA 4-hole stainless steel 4”x4” (100 mm x100 mm) pad primary terminal2 Gas cushion (dry air or dry nitrogen cushion)3 Pressure relief valve to prevent pressure buildup4 Shrader gas valve for cushion application / fi llcap5 Magnetic oil level gauge6 Powder-coated polyester paint on mild steel dome7 Glazed porcelain with major-minor shed pattern for high creepage distance8 Condenser graded inner bushing9 Stainless and bronze corrosion-resistant hardware10 Powder-coated polyester paint on mild steel cover and tank11 High contrast aluminum schematic and nameplates (not shown)12 Power conduit box with 12” x 20” (305 mm x 508 mm) removable bottom plate13 Aluminum 2-hole lugs for standard low voltage terminals14 Measuring conduit box (if measuring winding is specified) with three (3) 1-1/2” (38 mm) NPT openings (not shown)15 Measuring low voltage ¼”-20 (6 mm) copper alloy terminals (not shown)16 High visibility ratio and kVA stencils17 5 kV rated isolated H0 bushing connected to dedicated tank ground18 ½” (13 mm) bronze drain ball valve with stainless steel pipe plug19 Two (2) NEMA 2-hole stainless steel ground pads20 Four (4) 2” (51 mm) and four (4) ¾” (19 mm) l ifting holes
Optional Accessories- One (1) or two (2) measur ing windings- Special low voltage lugs or connectors (NEMA 4-hole, stud or cable connectors, etc.)- Special low voltage output ratings (277 VAC, 347 VAC, 480 VAC, any voltage up to 600 VAC)- Special medium voltage output ratings (voltates up to 15 kV class output)- Extra strike and creep insulators- Polymer insulators in lieu of porcelain designs- Corrosion-resistant stainless steel housings- Secondary terminal box heaters- Sudden pressure relay- CTs to power secondary monitoring- Oil sampling valve
For needs or features not listed, contact the factory.
41
2
3
65
7
9
10
17
1415
19
20
13
12
1618
8
8 Types SSVT and SSMV oil-filled station service vo ltage transformers | ABB product bu lletin
High vol tage winding
Product winding optionsThe standard Station Service Voltage Transformer (power only)has two (2) isolated secondary power windings that can beeither series or parallel connected for different voltage output.Also, one (1) or two (2) additional tapped measuring windingscan be supplied for measurement and control applicationwith some isolation from the power coils to minimize voltagefluctuations.
High vol tage winding
Low vo ltage wind ings
Ô·²
»
ײ¬»®²¿´ ·̧»´¼
These extra windings supply rated accuracy and burdensupport only when the power winding is loaded at 10% orless of its power rating, otherwise these measuring windingswill become less accurate as the power winding is loadedabove 10% of rating.
Low vo ltage wind ings
Ô·²
»
ײ¬»®²¿´ ·̧»´¼
б©»® ï б©»® î
Series / Parallel
Y or Delta
б©»®
or
Measuring Sing le
Measuring Dual
Auxiliary
Series / Parallel
íðß
or
or
Power winding options Measurement winding options
SSVT technical data
SSVT product rating matrix
Type System MSV kV BIL Style10kVA(1)
25kVA(1)
50kVA(1)
100/125kVA(1)
160/167kVA(1)
200kVA (1)
250kVA(1)
315/333kVA(1)
SSVT-250 48 kV 250 kVPower windingsMeasuring windings(2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)
SSVT-350 72 kV 350 kVPower windingsMeasuring windings(2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)
SSVT-550 123 kV 550 kV
Power windings
Measuring windings (2) Cl 0.5(5) Cl 0.2(3) Cl 0.2(3) Cl 0.2(3)
SSVT-650 145 kV 650 kVPower windingsMeasuring windings (2) Cl 0.2(3) Cl 0.2(3)
SSVT-650 170 kV 650 kVPower windingsMeasuring windings (2) Cl 0.2(3) Cl 0.2(3)
SSVT-750 170 kV 750 kVPower windingsMeasuring windings (2) Cl 0.2(3) Cl 0.2(3)
SSVT-900 245 kV 900 kVPower windingsMeasuring windings (2) Cl 0.5(4)
SSVT-1050 245 kV 1050 kV
Power windings
Measuring windings (2) Cl 0.5(4)
SSVT-1300 362 kV 1300 kVPower windings
1. kVA ratings shown are based on a 30° C average ambient condition and a 65° C ris e.2. M easuring windings, where available, may be quantity of one or two w indings, ex cept as noted.3. Accuracy of 0.2% at 400 VA or 0.15% at 400 VA (ZZ) .
4. Two m easuring w indings are standard w ith accuracy c lass 0.5% at 400 VA or 0.3% at 400 VA (ZZ).5. One or two measuring windings are ava ilable w ith accuracy class 0.5% at 400 VA or 0.3% at 400 VA (ZZ) .
ABB product bulletin | Type s SSVT and S SMV oil-f illed sta tion se rvice voltage transformers 9
Power conduit box internal v iew(750 kV BIL rating and lower)
Power conduit box
Typical nameplate layoutThe supplied nameplates are laser-etched aluminumand contain product technical details, as well as windingschematics. A power winding nameplate is affixednear the power conduit box and, where applicable, aseparate nameplate for measuring windings is providednear the measuring terminals. The example shown is forillustration purposes; actual nameplates will reflect thespecification for each site application.
ÓßÈò ÌÑ ÌßÔ ï ðð Õ Êß
ïîí Ê
îîë éççíð ðï
ÐßÎßÔ ÔÛÔ ÝÑÒÒÛÝÌ×ÑÒ
ïðð ÕÊß
ÝÑ ÑÔ×Ò ÙóÑÒßÒ
ïîí ñîìê ÈïóÈì
ïðð ÕÊß
Ú×ÔÔÛÜ É×Ì Ø ÒÑÒóÐ ÝÞ Ó×Ò ÛÎßÔ Ñ×Ô ÉØÛÒ ÓßÒËÚßÝÌËÎÛÜ øÔÛÍÍ Ì ØßÒ ï Ð ÐÓ÷ØÛÎÓÛ Ì×ÝßÔÔÇ ÍÛßÔÛÜæ Ü Ñ ÒÑÌ Ì×ÔÌ ÑÊ ÛÎ î ëp ÚÎÑ Ó ÊÛÎ Ì×ÝßÔò
ïîí
ÍÛÝ ÊÑ ÔÌÍ
ÎßÌÛÜ
êëpÝ Î ×ÍÛêð ØÆ
ÌÇÐÛ ÍÍÊÌóêë ðóïðð ÊÑÔÌßÙÛ ÌÎßÒÍÚÑÎÓÛÎ
ÐñÒ æ
ÓßÜÛ ×Ò ËòÍò ßò
ÐÎ ×ÓßÎÇ
ÊÑ ÔÌÍÝÑ ÒÒÛÝÌ×Ñ Ò
èðë ðð
ÌØÛÎ ÓßÔ
ÕÊ
ÒÍÊ æ
ÕÊ
Þ×Ôæ
Ñ×Ô Ê ÑÔæ
ÙßÔ
ÔÞ
ÌÑÌò É Ìò
ïíè
êëð
ÈïóÈî ×× ÈíóÈì
ÎßÌ×ÒÙ
íðé ë
èë
çòð û
çòð û
Èî Èí
û
ïîíñîìê ÊÍÛ Î×Û Í ÝÑ ÒÒÛÝÌ×Ñ Ò
Èì
Øï
Èï
Øð
ÍËÞÌÎßÝÌ×ÊÛ ÐÑÔßÎ×ÌÇ
ÍÛÎ×ßÔ
ÒËÓÞÛÎæ
ÍÛÛ ÕËØÔÓßÒ ×ÒÍÌÎËÝÌ×ÑÒ ÓßÒËßÔ ÞÛÚÑ ÎÛ Û ÒÛÎÙ× Æ×Ò Ùò
×ÓÐ ÛÜßÒÝÛÎßÌ×Ñ
íîè
êëê
ÈìÈî
Èï Èí
ÈìÈî
Èï Èí
ÝßÌßÔÑÙ ÒÑò
ÍÌßÌ×ÝÍØ×Û ÔÜ
ÌßÒÕ
ÇÛßÎ
Ó×ÍÍ×ÍÍ×ÐÐ×
ÝÎÇÍÌßÔ ÍÐÎ×ÒÙÍ
ßÞÞ ÕËØÔÓßÒ
ÔççÒê ëêïðð Ý
Measuring condu it box internal v iew(750 kV BIL rating and lower)
Measuring conduit box
Conduit box internal view(900 kV BIL rating and h igher)
10 Types SSVT and SSMV o il-f illed station service voltage transformers | ABB product bu lletin
Dielectric ratingsIn general, the SSVT (low voltage output only) is producedaccording to IEEE C57.13 relative to the dielectric ratings andfor 60 hertz performance.
The information shown below reflects the IEEE specification.
Rating Product voltage levels
SSVT-250 SSVT-350 SSVT-550 SSVT-650 SSVT-650 SSVT-750 SSVT-900 SSVT-1050 SSVT-1300
NSV 46 kV 69 kV 115 kV 138 kV 161 kV 161 kV 230 kV 230 kV 345 kV
MSV 48 kV 72 kV 123 kV 145 kV 170 kV 170 kV 245 kV 245 kV 362 kV
BIL 250 kV 350 kV 550 kV 650 kV 650 kV 750 kV 900 kV 1050 kV 1300 kV
MCOV (power only) 115% 115% 115% 115% 115% 115% 110% 115% 115%
MCOV (power + measure) 140% 140% 140% 140% 140% 140% 106% N/A N/A
MMOV (power only) 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min 125% - 1 min
MMOV (power + measure) 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 173% - 1 min 120% - 1 min N/A N/A
PF Withstand - Dry - Wet
95 kV - 1 min95 kV - 10 sec
140 kV - 1 min140 kV - 10 sec
230 kV - 1 min230 kV - 10 sec
275 kV - 1 min275 kV - 10 sec
275 kV - 1 min275 kV - 10 sec
325 kV - 1 min315 kV - 10 sec
395 kV - 1 min350 kV - 10 sec
460 kV - 1 min445 kV - 10sec
575 kV - 1 min575 kV - 10sec
PD f ree @ 37 kV 54 kV 93 kV 109 kV 124 kV 124 kV 186 kV 186 kV 300 kV
H0 bushing 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV 5 kV
H0 BIL 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV 30 kV
Creep** in. (mm) 37 (940) 52 (1321) 130 (3302) 147 (3734) 147 (3734) 199 (5055) 267 (6782) 351 (8915) 391 (9931)
Strike** in. (mm) 17 (432) 23 (584) 42 (1067) 49 (1245) 49 (1245) 54 (1372) 72 (1829) 79 (2007) 98 (2489)
**E xtra creep and s trike insulators ava ilable , contact factory.
The unit can be configured for IEC dielectric ratings as well asfor 50 hertz systems.
ABB product bulletin | Type s SSVT and S SMV oil-f illed sta tion se rvice voltage transformers 11
ÒÛÓß ìóر´»Ð®·³¿®§ Ì»®³·²¿´
ÒÛÓß îóر´»Ù®±«²¼ п¼
ïòéëøìì÷
îòððøëï÷
íòëðøèç÷
ïñîóïí ÒÝøî÷ ØÑÔÛÍ
ðòëêøïì÷
øì÷ ØÑÔÛÍ
íòððøéê÷
ïòéëøìì÷
ïòéëøìì÷
íòëðøèç÷
ëð ³³ ¸±́» °¿½·²¹ ¿ª¿·́¿¾´»
Dimensions and weights
SSVT-250 SSVT-350 SSVT-550 SSVT-650 SSVT-650 SSVT-750 SSVT-900 SSVT-1050 SSVT-1300
MSV / BIL kV 48 / 250 72 / 350 123 / 550 145 / 650 170 / 650 170 / 750 245 / 900 245 / 1050 345 / 1300
A - Height in. (mm) 66.39 (1686) 75.00 (1905) 94.05 (2389) 101.73 (2584) 101.73 (2584) 124.29 (3157) 175.20 (4450) 177.56 (4510) 207.48 (5270)
B - Width in. (mm) 30.50 (775) 30.50 (775) 30.50 (775) 31.00 (787) 31.00 (787) 34.25 (870) 70.08 (1780) 70.08 (1780) 70.08 (1780)
C - Depth in. (mm) 44.82 (1138) 44.82 (1138) 44.82 (1138) 48.97 (1244) 48.97 (1244) 53.96 (1371) 68.30 (1735) 66.00 (1676) 75.00 (1905)
D - Highest Gnd Part in. (mm) 34.37 (873) 34.37 (873) 34.37 (873) 35.19 (894) 35.19 (894) 39.81 (1011) 61.42 (1560) 66.07 (1678) 69.53 (1766)
E - Insulator Length in. (mm)
13.88 (353) 22.21 (582) 40.65 (1032) 47.64 (1210) 47.64 (1210) 58.38 (1483) 75.79 (1925) 74.80 (1900) 98.80 (2510)
F - Lowest live part in. (mm)
52.51 (1334) 62.25 (1581) 81.82 (2078) 89.50 (2273) 89.50 (2273) 89.70 (2278) 137.21 (3485) 140.87 (3578) 168.30 (4275)
G - Conduit box height in. (mm)
11.50 (292) 11.50 (292) 11.50 (292) 12.25 (311) 12.25 (311) 16.63 (422) 31.10 (790) 31.10 (790) 27.96 (710)
H - Mtg Holes front- back in. (mm) 30.38 (772) 30.38 (772) 30.38 (772) 34.75 (883) 34.75 (883) 40.88 (1038) 48.00 (1219) 48.00 (1219) 48.00 (1219)
I - Mtg Holes left- right in. (mm) 28.75 (730)) 28.75 (730) 28.75 (730) 28.87 (733) 28.87 (733) 32.25 (819)
57.00 (1448)66.00 (1676)
57.00 (1448)66.00 (1676)
57.00 (1448)66.00 (1676)
Shipping Volume(l x w x h) in. (mm)
60x46x75(1524x1168x1905)
60x46x83(1524x1168x2108)
60x46x102(1524x1168x2591)
60x46x102(1524x1168x2591)
60x46x102(1524x1168x2591)
60x46x102(1524x1168x2591)
66x70x142(1676x1778x3595)
66x70x145(1676x1778x3683)
196.5x80x125(4991x2032x3175)
Unit Weight lb. (kg) 2255 (1009) 2470 (1120) 2550 (1156) 2960 (1343) 2960 (1343) 3500 (1588) 9500 (4318) 9910 (4505) 11084 ( 5038)
Shipping Weightlb. (kg)
2325 (1055) 2570 (1166) 2650 (1202) 3060 (1388) 3060 (1388) 3600 (1633) 11480 ( 5281) 11500 ( 5227) 14291 ( 6496)
Oil Volume gal. (l iter) 69 (261) 75 (284) 80 (303) 105 (397) 105 (397) 120 (453) 541 (2048) 550 (2082) 550 (2082)
Information s hown herein is for informationa l purpos es and is subject to change w ithout not ice.For construct ion purp os es , contact factory for updated information.
For SSVTs with 900 kV BIL and higher ratings,a single conduit box contains both the powerwindings as well as the mea sur ing windings(w hen supplied) and has a fixed 3” conduit open-ing for power outlet.
Ø ·¹ ̧ ª± ¬́ ¿¹ »òÝ ¿² ½ ¿ « » »ª »® » ·² ¶« ®§ô ¼ » ¿¬̧
± ® ¼ ¿ ³ ¿¹ » ¬® ¿² º ±® ³ »® ò
ÔÑ
ÒØï
Ô× ÏË× Ü ÔÛ ÊÛ Ô
ÈÈÈñÈÈÈæï
ÈÈ ÕÊ ß
ïîëðíêðððïÚ× ÔÔ ÛÜ ß Ì ÌØ Û
É ×Ì Ø Ò Ñ Òó ÐÝ ÞøÔ ÛÍ Í ÌØ ß Ò ï Ð ÐÓ ÷
Ó ßÒ ËÚß Ý ÌË ÎÛ
Ü ×ÛÔ ÛÝ ÌÎ ×Ý ÚÔ Ë ×Ü
Ì× ÓÛ Ñ Ú
ÙÝÑÒÜË×Ì
ÞÑÈ
ØÛ×ÙØÌ
ÞÉ×ÜÌØ
ÜØ×ÙØÛÍÌ
ÙÎÑË ÒÜ
ÐßÎÌ
ØÛ×ÙØÌ
Û×ÒÍËÔßÌÑÎ
ÍËÎÚßÝÛ
ßÑÊÛ ÎßÔÔ
ØÛ×ÙØÌ
ÚÔÑÉÛÍÌ
Ô×ÊÛ ÐßÎÌ
ØÛ×ÙØÌ
Ê×ÛÉ ÚÎÑÓ ÞÑÌÌÑÓ
×ÓÌÙ ØÑÔÛÍÔ»º¬ ¬± η¹¸¬
ØÓÌÙ
ØÑÔÛÍÚ®±²¬
¬± Þ¿½µ
ÝÑÊÛÎßÔÔ
ÜÛÐÌØ
òêî ̈ ïòîëøïëòç ̈ íïòè÷
ÓÑËÒÌ×ÒÙÍÔÑÌ
øì÷ ÐÔÝÍ
êòðð ̈ îðòðð
ÕÒÑÝÕÑËÌÚÑÎ ÝÑÒÜË×Ì
ÛÒÌÎÇ úéòîë ̈ îïòéë
ÎÛÓÑÊßÞÔÛ
ÐÔßÌÛ ßÔøÒÑÌ ÍØÑÉÒ÷ÒÑÒóÜÎ×ÔÔÛÜ
ÓÑËÒÌ×ÒÙ Ü×ßÙÎßÓ
12 Types SSVT and SSMV o il-f illed station service voltage transformers | ABB product bu lletin
SSMV product rating matrix
Type System MSV kV BIL Style Frequency100kVA(1)
125kVA(1)
167kVA(1)
200kVA(1)
SSVT-350 72 kV 350 kV Power windings60 Hz50 Hz
SSVT-550 123 kV 550 kV Power windings60 Hz50 Hz
SSVT-650 145 kV 650 kV Power windings60 Hz50 Hz
SSVT-650 170 kV 650 kV Power windings60 Hz50 Hz
1. kVA rat ings shown are based on a 30° C average ambient condition and a 65° C ris e.
SSVT Medium Voltage (SSMV) winding rating designThis design has been developed to aid siting the productanywhere there is a transmission line to allow connection.The design will facilitate power tap off of transmission lines formining sites, rural electrification projects or remote loads ofany description.
A distribution class surge arrester is supplied on the side of thetank wall for direct protection of the low side winding. Take offoptions can be overhead directly from the medium voltagebushings (with protective box cover removed) or sub-surface viaconduit entrance at the bottom of the box.
Unit provided for medium voltage power output cannot be
Product winding schematic and protection arrangement
SSMV (secondary) dielectric ratings
Rating
Product voltage leve ls
SSVT-350 SSVT-550 SSVT-650
Frequency 60 Hz 60 Hz 60 Hz
Thermal rating range 100-200 100-200 100-200
Standard thermal ratings
NSV 69 kV 115 kV 138 kV
MSV 72 kV 123 kV 138 kV
BIL 350 kV 550 kV 650 kV
MCOV power only 115% 115% 115%
MMOV power only 125%, 1 min 125%, 1 min 125%, 1 min
Power f requency withstand
Dry 140 kV, 1 min 230 kV, 1 min 275 kV, 1 min
Wet 140 kV, 10 sec 230 kV, 10 sec 275 kV, 10 sec
PD free upto 54 kV 93 kV 109 kV
H0 bushing 25 kV 25 kV 25 kV
H0 bushing BIL 125 kV 125 kV 125 kV
Secondary voltage 7200 V 7200 V 7200 V
X1 - X2 bushing class 25 kV 25 kV 25 kV
X1 - X2 bushing BIL 125 kV 125 kV 125 kV
HV creep in. (mm) 52 (1321) 130 (3302) 147 (3734)
HV strike in. (mm) 23 (584) 40.9 (1040) 48 (1219)
Secondary arrester rating
Frequency 50 Hz 50 Hz 50 Hz
Thermal rating range 100-200 100-200 100-200
Standard thermal rat ings 25 kVA, 50 kVA, 100 kVA, 125 kVA, 167 kVA
Secondary voltage 6600 V 6600 V 6600 V
HV arrester 60 kV 102 kV 120 kV
MV arrester 60 kV 60 kV 60 kV
SSMV technical data
ABB product bulletin | Type s SSVT and S SMV oil-f illed sta tion se rvice voltage transformers 13
Dimensions and weights
SSVT-350 SSVT-550 SSVT-650
MSV / BIL kV 72 / 350 123 / 550 145 / 650
A - Height in. (mm) 75.05 (2261.87) 108.52 (2756) 116.33 (2955)
B - Width in. (mm) 33.75 (857) 33.75 (857) 34.25 (870)
C - Depth in. (mm) 66.18 (1681) 66.21 (1681) 70.56 (1792)
D - Highest Gnd Part in. (mm) 41.83 (1062) 42.91 (1090) 43.71 (1110)
E - Insulator Length in. (mm) 22.91 (582) 40.65 (1033) 47.64 (1210)
F - Lowest live part in. (mm) 64.93 (1649) 83.74 (2127) 91.55 (2325)
G - Conduit box height in. (mm) 11.50 (292) 11.50 (292) 12.25 (311)
H - Mtg Holes front- back in. (mm) 36.40 (925) 36.40 (925) 40.77 (1038)
I - Mtg Holes left- right in. (mm) 32.13 (816) 32.13 (816) 32.25 (819)
Shipping Volume (l x w x h) in. (mm)
2 crates
80x48x72(2032x1219x1829)
24x24x26(610x610x660)
80x48x92(2032x1219x2337)
24x24x26(610x610x660)
85x50x98(2159x1270x2489)
24x24x26(610x610x660)
Unit Weight lb. (kg) 3513 (1593) 3593 (1629) 4343 (1970)
Shipping Weight lb. (kg) 3620 (1642) 3700 (1678) 4450 (2023)
Oil Volume gal. (l iter) 150 (568) 75 (284) 180 (681)
Information shown herein is for informational purposes and is subject to change without notice.
For construction purposes, contact factory for updated information.
14 Types SSVT and SSMV o il-f illed station service voltage transformers | ABB product bu lletin
ABB Station Service Voltag e Transformers Quote requests : [email protected] SSVT: Sing le Phase, Single Bushing
Customer / Project
Size / Load Rating kVA 10, 25, 50, 100, 167 or higher
Primary Voltage Volt Line-to-Neutral average, actua l, not nominal
MMOV Volt 30 seconds or 60 seconds maximum over voltage, L-N
MCOV Volt Continuous maximum over voltage, L-N
Primary Protection kV BIL 250 - 1300 kV
SEC. Pow er Voltages V nominal 110/220, 120/240, 240/480, 277, 347, other (600 V class)
or Limits NLV high / FLV low (V or ratio)
Ratios: PRI . L-N:SEC :1 for each Secondary Power Voltage at no load
Load Power Factor % at maximum power loading
Measuring Ou tputs None Single with tap Dual with tap Specia l
High accuracy is standard
Operating EnvironmentElev > 3000 f t. 24 hr. avg.
STANDARD FEATURES SPECIAL FEATURES
Primary Bushing ANSI 70 Gray Brown Increased / Reduced BIL rated
H-spade terminal standard
Type of Secondary Terminals2-hole lug
2-hole g spade 4-hole h spade
Tank Material Mild steel 304L SST or Other:
Dome Material Mild steel 304L SST or Other:
Finish Coating ANSI 70 Gray polyester powder Other:
Tank Ground Pads 1 on side 1 in T.B. Other:
Cable Connector Option Y/N Size Range
Primary Terminal MCM
Tank Ground MCM
Other options available - Oil sampling device
- 1 or 2 CTs in terminal box
- Heater in terminal box
- Export crating
- Temperature gauge
- Mounting riser stand
Comments: ___________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________
Inquiry and order information sheet
Copy form as needed.
ABB Statio n Service Voltag e TransformersType SSMV: Addit ional Informat ion
Frequency 60 Hz 50 Hz
Operating Environment 6 - 61 kV 72 kV 7 - 62 kV 7- 96 kV
Power Take-off Underground Overhead
ABB product bulletin | Type s SSVT and S SMV oil-f illed sta tion se rvice voltage transformers 15
J 99 N 328 050 C XXX
Dielectric Insulation Code (kV BIL)H = 250 kVJ = 350 kVK = 550 kVL = 650 kVM = 750 kV
Transformer TypeÚ¿½¬±®§ ¿·¹²»¼
Power / MeterM = Meter windingsN = No meter windingsD = Dual meter windings
Winding CodeFactory assignedHighest turns ratio
KVA102550100/125160/167200250
SeriesFactory assigned
Special Featuresß ®»¯«·®»¼
900 kV through 1300 kV BIL (230 kV - 345 kV Systems)
Typical SSVT Catalog Number:N91110N100-XXX
N 91 110 N 100 XXX
Dielectric Insulation Code (kV BIL)N = 900 kV or 1050 BILP = 1300 kV BIL
Power / MeterM = Meter windingsN = No meter windingsD = Dual meter windingsT = Taps power only
Winding CodeFactory assignedHighest turnsratio
KVA100167200250315/333
SeriesFactory assigned
Special FeaturesAs required
Low Voltage Output
250 kV through 750 kV BIL (46 kV - 161 kV Systems)
Typical SSVT Catalog Number:J99N328050C-XXX
J 99 N A 28 050 C XXX
Dielectric Insulation Code (kV BIL)J = 350 kVK = 550 kVL = 650 kVM = 750 kV
Transformer TypeÚ¿½¬±®§ ¿·¹²»¼
Power / MeterN = No meter windings
Winding CodeFactory assignedHighest turns ratio KVA
102550100/125160/167200
SeriesFactory assigned
Special Featuresß ®»¯«·®»¼
Medium Voltage Output
350 kV through 750 kV BIL (46 kV - 161 kV Systems)
Typical SSVT-MV Catalog Number:J99NA28050C-XXX
FrequencyA = 60 HzB = 50 Hz
Catalog number breakdown
16 Types SSVT and SSMV o il-f illed station service voltage transformers | ABB product bu lletin
Notes
Contact us
Do
cum
en
tN
um
be
rP
PH
VIT
SS
V1
110
BR
/A
ug
ust
20
12ABB, Inc.
High Voltage Instrument Transformers3101 Beaumont Centre CircleSuite 225Lexington, KY 40513Toll free: +1 800-950-6966Phone: +1 859-219-6040Fax: +1 859-223-2025
www.abb.com/highvoltage
Note:We reserve the r ight to make technical changes or
modify the contents of this document without pr iornotic e. With regard to pu rc hase orders, the agreedparticulars shall prevail. ABB does not accept anyresponsibility whatsoever for potential errors or possiblelack of in formation in this document. We reserve allrigh ts in this document and in the subject matter andillustrations contained therein. Any reproduction– inwhole or in parts –is forbidden without ABB’s priorwritten consen t.
May not be available in all markets.
Copyright® 2012 ABBAll rights reserved