Upload
others
View
5
Download
0
Embed Size (px)
Citation preview
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
TYPE ‘MC-PCS’ Cable Fittings Compatibility
There is a new MC Cable configuration on the market called “MC-PCS”. This specialty cable
was introduced in late 2014, and was designed to reduce the amount of wiring involved with todays
new LED and Fluorescent, SMART dimming systems.
Since this is a new MC Cable construction, there have been many field questions as to what
kind of fittings should be specified for terminating the cable to boxes, enclosures, and lighting fix-
tures. Also, there has been some confusion if cable fittings need to be specially Listed for this new
cable construction. The cable construction differs slightly from a standard MC Cable, as it contains a
separately grouped and insulated, 16/2 control cable, bundled in parallel with the current carrying
conductors. This new cable construction has recently been designated by UL as type: “MC-PCS”.
The Metal Clad Cable specification UL1569 (PJAZ), is currently poised to be amended to include
this new “MC-PCS” designation.
However, within the current fittings specification of UL514B (PJOX), there is no separate “MC-
PCS” fittings category designation, and therefore no specific fittings requirements for “MC-PCS” type
cable. This will likely change in the coming year as UL harmonizes all affected specifications. In the
interim, there will be no separate “MC-PCS” Listing required for fittings specified to be used
with the new MC Cable. The only requirement is that appropriately sized fittings Listed for MC
Cable are used.
Per NEC Articles 330.40, 320.40 & 300.15, ALL cable fittings must be Listed. The Listing
evaluations are made with cable constructions and dimensions which were available at the time of
evaluation. Among other requirements, UL514B specifies that a cable fitting used with AC/MC/MCI-
A cable must have a cable armor stop, which shall prevent the passing of cable armor completely
through the throat of the fitting – while allowing the insulated conductors pass through without
damage. This cable armor stop may be plastic or metal, or circular or oval. However, no matter what
the configuration, the cable stop shall restrict the cable armor from passing through, and allow all of
the cable conductors to pass through without restriction.
Bridgeport Engineering has evaluated the various type MC-PCS cable construction variations,
and developed a list of compatible and Listed fittings. These fittings are selected to handle the maxi-
mum diameter of the armor, providing a suitable armor stop, while allowing the conductor bundle to
pass through. Attached is a table which indicates Bridgeport’s current MC-PCS cable fitting options.
Of course, if there are any concerns or questions about a particular installation or specification,
please contact the Engineering Department at Bridgeport Fittings.
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
Cable Manufacturer
Conductor AWG/No.
Ground Conductor
AWG
Conductor Type (Solid, Stranded)
Twisted/Jacketed Pair
AWG/No. (SOLID)
Nominal OD of Cable Armor
(in.)
Nominal OD of
Conductor Bundle
(in.)
Suitable Fittings (CODE)
12/2 12 SOLID 16/2 .626 .406 A-G, I, 3
12/3 12 SOLID 16/2 .653 .433 A-G, I, L,
3
10/2 10 SOLID 16/2 .670 .450 A-G, I-K,
3
12/2 12 STRANDED 16/2 .638 .421 A-K, 3
12/3 12 STRANDED 16/2 .666 .446 A-K, 3
AFC Cable Systems ® Logo is a Registered trademark of AFC Cable Systems, Inc (A division of Atkore International)
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
Cable Manufacturer
Conductor AWG/No.
Ground Conductor
AWG
Conductor Type (Solid, Stranded)
Twisted/Jacketed Pair
AWG/No. (SOLID)
Nominal OD of Cable Armor
(in.)
Nominal OD of
Conductor Bundle
(in.)
Suitable Fittings (CODE)
12/2 12 SOLID 16/2 .562 .382 E, I, L-Z,
1-3
12/3 12 SOLID 16/2 .592 .561 F,G, I, L,
X-Y
10/2 10 SOLID 16/2 .606 .450 B-E, G, I, L, W-Y, 3
12/2 12 STRANDED 16/2 .590 .420 B, C-E, G, I, L, W-Z,
3
Encore Wire ® Logo is a Registered trademark of Encore Wire Corp.
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
Cable Manufacturer
Conductor AWG/No.
Ground Conductor
AWG
Conductor Type (Solid, Stranded)
Twisted/Jacketed Pair
AWG/No. (SOLID)
Nominal OD of Cable Armor
(in.)
Nominal OD of
Conductor Bundle
(in.)
Suitable Fittings (CODE)
12/2 12 SOLID 16/2 .553 .343 E,
L-Z, 1-3
12/3 12 SOLID 16/2 .553 .343 E,
L-Z, 1-3
10/2 10 SOLID 16/2 .618 .408 B-E, G, I,
L, W, X, 3
12/2 12 STRANDED 16/2 .573 .363 E, G,
L-Z, 1-3
Southwire ® Logo is a ®Registered Trademark and ™Trademark of Southwire Company, LLC
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
Applicable MC Fittings to be used with Type MC-PCS Cables
SELECTION CODE
Cat. # KO Size
UL File Image Cable Dia. min-max**
Armor Stop ID
A 561-DC2 1/2 E20534 .625 - .870 0.620
B 561-DCI2 3/4 E20534
.610 - .870 0.510
C 571-DCI2 1/2 E20534 .600 - .855 0.555
D 571-SI 1/2 E20534
.600 - .855 0.555
E 682-DC2 3/4 E20534 .530 - .865 0.525
F AMC-5075 1/2 E20534 .620 - .920 0.565
G AMC-75 3/4 E20534 .566 - .810 0.560
H 653-DC2 1/2 E20534 .675 - .900 0.630
I BL-17I 1/2 E20534 .600 - .803 0.580
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
SELECTION CODE
Cat. # KO Size
UL File Image Cable Dia. min-max**
Armor Stop ID
J BL-17 1/2 E20534 .625 - .803 0.625
K 571-DC2 1/2 E20534 .628 - .855 0.625
L 403-I 1/2 ML
E20534 .375 - .630 0.550
M 560-DC2 1/2 E20534
.44-.61 0.400
N 501-DC2 1/2 E20534
.43-.61 0.400
O 545-DC2 1/2 E20534
.44-.61 0.406
P 845ASP 1/2 E20534
.43-.61 0.406
Q 840SP 1/2 E20534 .44-.61 0.406
R SG38ASP 1/2 E20534 .43-.61 0.406
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
SELECTION CODE
Cat. # KO Size
UL File Image Cable Dia. min-max**
Armor Stop ID
S 570-DC2 1/2 E20534 .38-.61 0.400
T 570-DCI2 1/2 E20534 .38-.61 0.406
U 570-GI 1/2 E20534 .38-.61 0.406
V 570-RI 1/2 E20534 .38-.61 0.406
W 801-DC2 1/2 E20534 .45-.625 0.562
X 801-DCI2 1/2 E20534 .45-.625 0.580
Y 802-DC2 1/2 E20534 .48-.58 .608-.610
Z 802SP 1/2 E20534
.48-.58 0.531
1 AMC-50 1/2 E20534 .40-62 0.406
Bridgeport Fittings, Inc. • 705 Lordship Blvd. • Stratford, CT 06615 • Phone: 203-381-3431 • Fax: 203-381-3488 • bptfittings.com
REVISED 5-18-15
SELECTION CODE
Cat. # KO Size
UL File Image Cable Dia. min-max**
Armor Stop ID
2 590-DCI2 1/2 E20534 .43-62 0.407
3 621-DC2 3/4 E20534 .440-.700 0.810