Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
TYM-VS2Slide Gate Operator
Installation & Owner’s Manual
Tymetal Corp.Greenwich, NY • Pearland, TX
Phone (800) 328-GATE
Fax (518)692-9404
Email [email protected]
www.tymetal.com
JDE Item # 41274 Revision 0, 072012Document PN 620-101409 REV X12 09/01/2016
TYM-VS2 Slide Gate Operator Installation Guide Revision 0, 072012
Table of ContentsPre-installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Before You Begin... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Always Check the Gate’s Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Approved Obstruction Detection Devices . . . . . . . . . . . . . . . . . . . . . 1
Safety Information and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Regulatory Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2AC Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2DC Control and Accessory Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Mounting Pad Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3Gate Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operator Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Vent Plug Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Gate Bracket and Chain Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Chain Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operator Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Controller Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Manual Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5AC Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Earth Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Open and Close Limit Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . .6Limit Nuts Rough Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Limit Nuts Fine Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Setting Speeds using LSO-2 & LSC-2 . . . . . . . . . . . . . . . . . . . . . . .6Torque Limiter Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Indicator Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Terminal Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Operator Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Basic Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Programming Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Entering Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Exiting Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Programming Keystrokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Left or Right Hand Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Dual Gate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Auto Close Timer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Run Alarm and Pre-start Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Maximum Open Direction Current Setting. . . . . . . . . . . . . . . . . . . .13Maximum Close Direction Current Setting . . . . . . . . . . . . . . . . . . .13
Advanced Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . .14Entering Advanced Programming Mode . . . . . . . . . . . . . . . . . . . . .14Maximum Run Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Single Button Input Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Stagger Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Stagger Delay Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Auxiliary Relay Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Reverse Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Brake Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Constant Pressure Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Shadow Loop Open Prevention . . . . . . . . . . . . . . . . . . . . . . . . . . .15Reset Cycle Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Maintenance Alert Trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Mid-travel Stop Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Anti-tailgate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Radio Enable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Antenna Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Radio Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Radio Transmitter Delete. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17MGT Obstacle Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . .17MGT Obstacle Transmitter Delete. . . . . . . . . . . . . . . . . . . . . . . . . .17Motor Type Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17Reset Controller to Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . .17
APeX v1.4 Gate Controller Quick Programming Guide . . . . . . . . . . .18
Loop Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Safety Edge Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Photoeye Installation Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Picket Gate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Dual Gate Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Optional In-Cabinet Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Gate Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Open Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Close Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Stop Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Single Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Fire Department Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Open Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Open Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Close Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Reverse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Open Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Reverse Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Shadow/Reset Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Operation Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Power-up Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Idle Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Last Gate Position/Condition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Pre-start Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Reverse Delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Run Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26Entrapment or Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26COMM LINK Connection Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . 26MGT Obstacle Transmitter Trouble . . . . . . . . . . . . . . . . . . . . . . . . .26Maximum Run Time Exceeded . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Contacting Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Operator fails to start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27Motor operates, but gate does not move. . . . . . . . . . . . . . . . . . . . .27Motor sounds like it is working harder than normal . . . . . . . . . . . . .27Limit switch getting out of time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Gate stopping part way open or closed. . . . . . . . . . . . . . . . . . . . . .27Gate staying open with automatic system. . . . . . . . . . . . . . . . . . . .27How to Order Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Model TYM-VS2 Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Controller Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316-Month Preventative Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . 31
FCC Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Variable Speed Drive Programming. . . . . . . . . . . . . . . . . . . . . . . . . . .32Programming the Hitachi Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Gate Operator Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . 34
TYM-VS2 Slide Gate Operator Installation Guide - 1 - Revision 0, 072012- 1 -
Before You Begin...
Before unpacking, inspect the carton for exterior damage.
claim. Inspect your package carefully. You can check your
accessory box parts with the enclosed packing slip for your
convenience. Claims for shortages will be honored for only
30 days from the date of shipment.
If you have any questions about the requirements for proper
installation of this gate operator contact technical support at
800-328-4283.
Always Check the Gate’s Action
It’s very important before installing the gate operator
to make sure the gate slide is free and level throughout
the entire opening distance. If the gate does not seem to
operate properly, it may affect the operator performance
or greatly shorten the life of the unit.
All gate operators can be divided into one of four different
this gate operator only when the operator is appropriate for
• Class I Residential Vehicular Gate Operator
A vehicular gate operator intended for use in a home or for one
to four single family dwellings with a common garage or parking
area associated with these dwellings.
• Class II Commercial / General Access Vehicular Gate Operator
A vehicular gate operator intended for use in a commercial
or more single family units, hotel, retail store or other building
servicing the general public.
• Class III Industrial / Limited Access Vehicular Gate Operator
A vehicular gate operator intended for use in an industrial
location or building such as a factory or loading dock area or
other location not intended to service the general public.
• Class IV Restricted Access Vehicular Gate Operator
A vehicular gate operator intended for use in a guarded industrial
location or building such as an airport security area or other
restricted access locations not servicing the general public,
in which unauthorized access is prevented via supervision by
security personnel.
Approved Obstruction Detection Devices
The following contact or non-contact obstruction detection
devices have been approved for use with this slide gate
operator as part of a UL325 compliant installation:
• Contact Edges
Miller Edge Models MGO20, MGR20, MGS20, ME120
• Photoeyes
MMTC Model IR-55 (165’ range - P/N 2520-441)
MMTC Model E3K (28’ range - P/N 2520-031)
Regulatory Warnings
Read the following before beginning to install this slide gate
operator:
THE FOLLOWING FORMATS ARE USED FOR SAFETY
NOTES IN THESE INSTRUCTIONS.
WARNINGThis type of warning note is used to indicate possible
mechanical hazards that may cause serious injuries or
death.
CAUTIONThis type of warning note is used to indicate the possibility
of damage to the gate or gate operator.
WARNINGThis type of warning note is used to indicate possible
electrical shock hazards that may cause serious injuries or
death.
WARNING
1. READAND FOLLOWALLINSTALLATION INSTRUCTIONS.2. Read the yellow “Safety Instructions” brochure enclosed
with the packet of information. If any pages are missing orare unreadable, or you do not have the safety instructions,please call Tymetal at 1-800-328-4283 to request additionalcopies.
3. ALL ELECTRICAL CONNECTIONS TO THE POWERSUPPLY MUST BE MADE BY A LICENSED ELECTRICIANAND MUST OBSERVE ALL NATIONAL AND LOCALELECTRICAL CODES.
4. A separate power-disconnect switch should be located nearthe operator so that primary power can be turned off whennecessary.
5. Install the enclosed warning signs on both sides of the gate.A minimum of two (2) WARNING SIGNS shall be installed,one on each side of the gate where easily visible.
6. Never reach between, through or around the fence tooperate the gate.
7. Never connect a button station within reach of the gate or onthe side of the gate operator.
8. Do not adjust the operator controller’s current sensingfeature too high. It should be adjusted high enough to keepthe gate from falsely triggering the sensing, but no higherthan necessary for the gate to operate. DO NOT DEFEATTHE PURPOSE OF THIS FUNCTION!
9. You must install all required safety equipment.10. UL325 Compliance requires the use of contact edges or
photoelectric controls on all automatic or remotely-controlledgate operators.
11. The operator is intended for installation only on gates usedfor vehicles. Pedestrians must be supplied with a separateaccess opening. The pedestrian access opening shall bedesigned to promote pedestrian usage. Locate the gate suchthat persons will not come into contact with the vehiculargate during the entire path of travel of the vehicular gate.
TYM-VS2 Slide Gate Operator Installation Guide - 2 - Revision 0, 072012-
Refer to the following steps for details on power and
accessory wiring for the operator.
AC Power Wiring
DO NOT EXCEED THE MAXIMUM
DISTANCE.
The green
ground wire must be properly connected.
7. LOCAL EARTH GROUND REQUIRED
DC Control and Accessory Wiring
Note:
The shield wire should be connected in both the
operators.
WARNINGALLACELECTRICALCONNECTIONSTO THEPOWER
SOURCE AND THE OPERATOR MUST BE MADE BYA
LICENSED ELECTRICIAN AND MUST OBSERVE ALL
NATIONALAND LOCAL ELECTRICAL CODES.
MODEL TYM-VS2 SINGLE PHASE POWER WIRING
VOLTS, HP &
AMPERAGE
MAXIMUM DISTANCE
(FEET)WIRE
GAUGESINGLE DUAL
MODEL TYM-VS2 THREE PHASE POWER WIRING
VOLTS, HP &
AMPERAGE
MAXIMUM DISTANCE
(FEET)WIRE
GAUGESINGLE DUAL
Figure 1. Earth Ground
TYM-VS2 Slide Gate Operator Installation Guide - 3 - Revision 0, 072012
The gate operator mounts to posts secured in concrete
footings. The posts support the operator and prevent it from
moving during operation, as shown in Figure 2.
Gate Preparation
Before installing, make sure the gate rolls or slides freely,
and that all exposed rollers are properly covered. The gate
must be covered with fabric with openings no larger than
2-1/4” in size, to a minimum height of 72” above ground
level. On picket-style gates, if pickets are spaced less than
2-1/4” apart, mesh is optional.
Use two 4” OD galvanized posts and secure with concrete
footings as shown, length to be determined by local codes,
frost line depth and soil conditions.
Attach the operator with the hardware provided.
To assemble the drive chain and chain support brackets,
refer to Pages 4 and 5. Make sure that the chain sag does
not exceed recommended dimensions and that the chain
does not come into contact with the moving parts of the gate
or ground.
WARNINGThe operator is intended for installation only on gates
used for vehicles. Pedestrians must be supplied with
a separate access opening. The pedestrian access
opening shall be designed to promote pedestrian
usage. Locate the gate such that persons will not
come into contact with the vehicular gate during the
entire path of travel of the vehicular gate.
WARNINGThe gate must be installed in a location so that enough
clearance is supplied between the gate and adjacent
structures when opening and closing to reduce the
risk of entrapment.
Vent Plug Installation
In order to keep gear oil from spilling out during shipping,
gear reducers used in gate operators have either a solid
plug, or a sealed vent plug, installed at the factory.
For operators with a solid plug, replace the solid plug with
the vent plug provided (see Figure 3).
With the vent plug installed, remove the vent plug’s breather
pin to allow the gear box to vent (see Figure 3)
Figure 3. Vent Plug Installation
Figure 2. Operator Elevations and Dimensions
TYM-VS2 Slide Gate Operator Installation Guide - 4 - Revision 0, 072012-
Figure 4a. Chain Path
Figure 4. Chain to Bracket Assembly
Figure 5. Standard
Figure 5a. Ornamental
Figure 3. Mounting Gate Bracket to Gate
5/16”-18 HEX LOCK NUT JDE# 3580
5/16”-18 x 3” HEX BOLTJDE# 3618
GATE FRAME
CHAIN MOUNTING BRACKETJDE# 3439
5/16” FLAT WASHERJDE# 3582
DRILL 11/32” THROUGHBOTH SIDES, 2 PLACES
NOTE: The item numbers shown in these illustrations
are for reference only. For the actual part numbers, refer
to the parts lists in the rear of this manual.
Your gate should be hung level and move freely by hand in
both directions before attaching the operator drive chain.
Slide the gate to the fully open position. Line up the slot
in the chain mounting bracket with the bottom of the idler
wheel on the operator. Mark the leading edge of the gate
frame using the chain mounting bracket as a template. Drill
Slide the gate to the fully closed position and mount the
other chain mounting bracket to the rear edge of the gate
frame in the same way.
Attach the chain to both chain mounting brackets as shown
5a. Brackets should support the chain but must not hit the
between the chain supports, as shown in Figure 6.
TYM-VS2 Slide Gate Operator Installation Guide - 5 - Revision 0, 072012
Figure 6. Operator Placement
Controller Access
The Controller is protected by a plastic dust cover. To
remove the dust cover, loosen the cover’s wing-screw and
lift the cover off (see Figure 7).
AC Power Connection
All Tymetal gate operators are supplied with a power
disconnect switch to turn on and off the power available
incoming power should be brought into the operator and
connected to the labeled pigtails from the disconnect box.
A wiring connections print can also be found on the label
inside the cover of the operator. See Figure 8.
Proper thermal protection is supplied with the operator. The
motor contains a thermal overload protector to guard from
overheating the motor due to overload or high-frequency
Figure 7. Controller Access
operation. This overload protector will reset automatically
after the motor cools down.
Earth Ground
Install a ground rod and connect it to the operator’s frame
in every gate operator installation. A good earth ground
is necessary to allow the Controller’s built-in surge and
lightning protection circuitry to work effectively. The physical
bolting of the operator to the mounting posts is not
for a good earth ground. See Figure 1.
NOTE:
Figure 8. Power Disconnect Box Wiring
TYM-VS2 Slide Gate Operator Installation Guide - 6 - Revision 0, 072012-
Open and Close Limit Adjustment
The limit nuts are NOT PRESET at the factory and must beadjusted for the gate in each installation. The limit switchesare activated by two threaded nylon rotary limit nuts whichare attached to a threaded limit shaft driven by a chainand sprockets from the main drive shaft. REMOVE THECARDBOARD FILLER BEFORE ADJUSTING THE LIMITNUTS.
The Controller is factory setup for right-hand installations.The OPEN limit switches are the ones closer to the frontof the operator. In left-hand installations, the CLOSE limitswitches are the ones closer to the front of the operator (seeFigures 10 & 11).
Limit Nuts Rough Adjustment
Before running the operator, set the limit nuts as follows:
OFF
OPENOPEN
CLOSECLOSE
CAUTIONIf the operator is installed in a left-hand installation.
Set the Controller to left-hand operation BEFORE
cams. Failure to do so will result in over-shooting the
limit switches, and may cause damage to the operator
and/or gate. Refer to programming on Page 12.
Manual Disconnect
The manual disconnect shifter lever and the locking lever is
illustrated in Figure 9. They can be found at the center and
to the left inside the operator cabinet. (The handle of each
To disconnect the unit for manual operation, grasp the
handle of the spring-loaded shifter lever and pull it directly
toward you until the spring-loaded locking lever snaps into
place behind it. This action disengages the pinned shifter
block from the drive mechanism and holds the block in the
disengaged position.
To re-engage the operator, move the locking lever to the
right, releasing the spring-loaded shifter lever to snap back
into the engaged position.
Manual Hand Crank
TYM-VS2 is equipped with a manual hand crank to operate
the gate as an emergency means when no utility power is
present.
1. Turn off Power
2. Put operator in manual mode using the disconnect shiftlever.
3. Remove hand crank from safety switch/holder assemblylocated in the upper right corner of the operator cabinetand unfold handle. See Figure 9a.
4. Place hand crank over hex clutch disc.
5. Turn the handle in the desired direction for gatemovement.
6. Reverse these steps to return operator to normaloperation.
NOTE: Removal of the crank handle from the safetyswitch holder will disable the gate operator. The crankhandle must be properly placed in the safety switchholder to allow gate operator function.
Figure 9. Manual Disconnect Lever
WARNINGALLAC ELECTRICAL CONNECTIONS TO THE POWER
SOURCE AND THE OPERATOR MUST BE MADE BY A
LICENSED ELECTRICIAN AND MUST OBSERVE ALL
NATIONAL AND LOCAL ELECTRICAL CODES
Figure 9a. Manual Hand Crank
TYM-VS2 Slide Gate Operator Installation Guide - 7 - Revision 0, 072012
Limit Nuts Fine Adjustment
ON
OPEN
CLOSE
Setting Speeds using LSO-2 & LSC-2Limit switches LSO-2 and LSC-2 control when the operatoraccelerates to maximum speed and decelerates tominimum speed. It is recommended that LSO-2 and LSC-2
hitting LSO-1 or LSC-1 as these will apply the brake uponactivation.
Adjust LSO-2 and LSC-2 by slightly loosening the twoscrews which hold them in place and sliding toward or awayfrom the center of the limit box. Care must be taken not toadjust too close to the center as the limit nut may travel past
the switch and start accelerating at the end of the cycle.
Torque Limiter Adjustment
Before adjusting the torque limiter, make sure the gate is
in good working condition. With the gate operator in the
disconnected position, one person should be able to move
the gate by hand. Be certain the gate moves freely and
without binding throughout its travel.
Torque limiters are SET LIGHT AT THE FACTORY. They
must be adjusted during installation, preferably after limit
cams have been manually set. With the gate operator
engaged to the gate, adjust the torque limiter tight enough
to keep it from slipping during normal operation. The
inherent entrapment protection (current sensing) feature
must activate prior to any slipping of the torque limiter.
NOTE:
To adjust the torque limiter in a Model TYM-VS2:
TURN THE OPERATOR POWER DISCONNECT
SWITCHOFFBEFOREMAKINGANYADJUSTMENTS
Figure 12. Setting the Limits
Figure 10. Limit Box Assembly (Right-hand Installation)
Figure 11. Limit Box Assembly (Left-hand Installation)
Figure 13. Torque Limiter Adjustment
TYM-VS2 Slide Gate Operator Installation Guide - 8 - Revision 0, 072012-
Figure 14. Controller Features
TYM-VS2 Slide Gate Operator Installation Guide - 9 - Revision 0, 072012
INDICATOR DEFINITION INDICATION WHEN LIT
DURING NORMAL OPERATION
INDICATION WHEN LIT
DURING PROGRAMMINGOPERATION PROGRAMMING
TYM-VS2 Slide Gate Operator Installation Guide - 10 - Revision 0, 072012-
TERMINAL GROUP FUNCTION
-
+
-
+
+
-
+
-
TYM-VS2 Slide Gate Operator Installation Guide - 11 - Revision 0, 072012
Figure 15. Operator Accessory Connections
TYM-VS2 Slide Gate Operator Installation Guide - 12 - Revision 0, 072012-
Programming Overview
Entering Programming Mode
UP DOWN
PROGRAM
Exiting Programming Mode
UP DOWN
Programming Keystrokes
(Typical Programming Method)
UP DOWN
ENTER
When an option is displayed, the decimal
points are lit.
ENTER
UP DOWN
ENTER
ENTER UP
DOWN
Left or Right Hand Operation
Dual Gate Enable
COMM LINK
NOTE:
Auto Close Timer
TYM-VS2 Slide Gate Operator Installation Guide - 13 - Revision 0, 072012
Run Alarm and Pre-start Alarm
• Run Alarm Off and Pre-start Alarm Off
• Run Alarm On and Pre-start Alarm Off
• Run Alarm On and Pre-start Alarm On for 1-9
Seconds
Maximum Open Direction Current Setting
while this function
is being displayed, OPEN
Maximum Close Direction Current Setting
while this function
is being displayed, CLOSE
TYM-VS2 Slide Gate Operator Installation Guide - 14 - Revision 0, 072012-
Entering Advanced Programming Mode
After exiting programming, theAdvanced Programming
functions will be available on the programming display
during the next programming session unless the
operator has run 50 ormore cycles.After that,Advanced
Programming must be enabled again.
Maximum Run Time
Single Button Input Setup
SINGLE
SINGLE
Stagger Mode
This function is used in dual gate installations only.
COMM LINK
NOTE:
Stagger Delay Time
This function is used in dual gate installations only.
NOTE:
TYM-VS2 Slide Gate Operator Installation Guide - 15 - Revision 0, 072012
Auxiliary Relay Mode
• Maglock:
• Ticket Dispenser:
• Strobe:
• Alarm:
Reverse Delay Time
Brake Delay Time
Constant Pressure Mode
OPEN CLOSE
OPEN CLOSE
NOTE:
Shadow Loop Open Prevention
TYM-VS2 Slide Gate Operator Installation Guide - 16 - Revision 0, 072012-
Reset Cycle Count
ENTER
Maintenance Alert Trigger
MAINTALERT
Mid-travel Stop Position
still fully open
OPEN
NOTE:
Anti-tailgate Enable
Radio Enable
Antenna Installation
ANTENNA
TYM-VS2 Slide Gate Operator Installation Guide - 17 - Revision 0, 072012
Radio Transmitter Learn
NOTE:
Radio Transmitter Delete
NOTE:
MGT Obstacle Transmitter Learn
NOTE:
MGT Obstacle Transmitter Delete
NOTE:
Motor Type Selection
Reset Controller to Factory Defaults
ALL PROGRAMMED
DATA WILL BE LOST
TYM-VS2 Slide Gate Operator Installation Guide - 18 - Revision 0, 072012-
TYM-VS2 Slide Gate Operator Installation Guide - 19 - Revision 0, 072012
TYM-VS2 Slide Gate Operator Installation Guide - 20 - Revision 0, 072012-
TYM-VS2 Slide Gate Operator Installation Guide - 21 - Revision 0, 072012
TYM-VS2 Slide Gate Operator Installation Guide - 22 - Revision 0, 072012-
TYM-VS2 Slide Gate Operator Installation Guide - 23 - Revision 0, 072012
TYM-VS2 Slide Gate Operator Installation Guide - 24 - Revision 0, 072012-
COMMLINK
COMM LINK
NOTE:
• Dual Gate Enable
• Stagger Mode
• Stagger Delay Time
The operator can be ordered with an optional cold weather
package that includes an in-cabinet heater to keep the drive
train and electronics warm in cold environments.
In-cabinet heaters can also be ordered separately and
should be wired to the operator as shown in Figure 17.
Contact Technical Support for heater wiring information for
Figure 16. COMM LINK Wiring
Figure 17. In-cabinet Heater Wiring
TYM-VS2 Slide Gate Operator Installation Guide - 25 - Revision 0, 072012
Open ButtonOpens the gate. If the Controller is programmed to stopopening the gate at mid-travel, a constant press of theOPENbutton will override the Mid-travel Stop and completely openthe gate. If the Auto Close Timer is set, it will be suspended
until the OPEN button is released.
Close ButtonCloses the gate if the gate is open. Also closes the gate if
the gate is in the process of opening.
Stop ButtonStops the gate from opening or closing at any time. CancelsFire Dept. Hold Open command (requires additional
movement command to re-start operator).
Reset ButtonResets overload relay. Cancels Fire Dept. Hold Opencommand (requires additional movement command to re-start operator).
Single Input
Opens the gate if it’s closed and closes the gate if it’s open(open-close programming option). Activating the input whilethe gate is moving will reverse the gate.
Can be programmed to stop the gate while the gate is
moving (open-stop-close programming option).
Fire Department InputFully opens the gate when the input is activated. Overridesthe Mid-travel Stop and Auto Close Timer (if either isprogrammed for the gate). The gate will lockout in the openposition without sounding the alarm. Press the STOP buttonto release the lockout. Press open or close to restart gate
operator.
Open Input
Functions the same as the OPEN button.
Open ObstructionWhile the gate is opening, any open obstruction signal willcause the gate to stop, reverse a short distance, and thenstop again. The Auto Close Timer will be disabled, and arenewed input will be required to start the gate again. Shouldthe gate be restarted and the obstacle signal occur againprior to reaching a limit, the gate will stop again, lockout,
and sound the emergency alarm.
Close ObstructionWhile the gate is closing, any close obstruction signalwill cause the gate to stop, reverse, and travel to the fullopen position. Should a open obstruction input or an opendirection inherent entrapment condition occur prior to thegate reaching the open limit, the operator will lockout andsound the continuous tone alarm. Another close requestwill be required to start the operator again. If after restart,the overload or a close obstacle happens again before theclose limit is reached, the operator will lockout and soundthe alarm. If the auto close timer is set, when the closeobstruction input is cleared, the gate will close when the
auto close timer expires.
Reverse Input
If the reverse input is triggered while the gate is closing, the
gate will reverse to the full open position. If the Auto Close
Timer is set, when the reverse input is cleared, the gate will
close when the Auto Close Timer expires.
Open Loop
Functions the same as the OPEN button.
Reverse Loop
Functions the same as the reverse input.
Shadow/Reset Loop
Holds the gate fully open or fully closed while triggered.
If open, the gate closes immediately when cleared if
Anti-tailgate is enabled.
During normal operation, the Controller’s displays will
indicate current operating conditions and status.
Power-up Display
When the Controller powers up, dashes will show on the
type (SL for slide and swing gates).
Exiting programming restarts the Controller. The power-up
display will show upon the restart.
Idle Condition
While the Controller is idling, waiting for a command, the
display will show circulating dashes.
Last Gate Position/Condition
When the gate moves or stops, the display will show the
status for up to one minute.
Pre-start Delay
During the pre-start delay, the display will countdown the
number of seconds remaining before the operator starts.
Reverse Delay
If the gate travel direction is reversed from a user activation
or reversing device, and a reverse delay is set, the display
will count down the delay time in seconds before the
operator restarts.
Run Timer
While the gate is opening or closing, the number of seconds
running time is displayed.
TYM-VS2 Slide Gate Operator Installation Guide - 26 - Revision 0, 072012-
During abnormal operation, the Controller’s displays and
beeper will indicate the error condition that has occurred.
Entrapment or Obstruction
If an entrapment condition occurs detected by two repeated
open or close obstruction triggers, the Controller will lock
the operator out. The beeper will sound constantly and the
gate will not operate. To reset the Controller press the STOP
button or press the RESET button on the operator’s cover.
COMM LINK Connection Failure
In dual gate installations, if there is a connection failure
between the two operators, the COMM LINK indicator will
blink once a second. During this condition the gate will not
operate, except if triggered by the FIRE DEPT input, which
functions normally.
MGT Obstacle Transmitter Trouble
If any MGT transmitters are used with the operator, their
supervision feature will alert the Controller if there is any
trouble with the transmitter. MGT transmitters send hourly
status reports and will send low battery reports when the
transmitter has a low battery. The MGT transmitters also
have a tamper detection switch that will trigger when their
case is opened.
When the Controller detects a low transmitter battery, a
tamper signal, or missing transmitter status reports, the
gate will still operate normally, but the beeper will change
as follows:
Correct the trouble (close case, replace battery, or replace
transmitter) to clear the obstacle transmitter trouble
indications.
Maximum Run Time Exceeded
If the Maximum Run Time is exceeded, the Controller
stops the operator the same as if a double obstacle has
occurred in an entrapment condition. The entrapment alarm
sounds constantly, and is cleared by pressing the STOP
button or the RESET button on the cover. After the STOP
or RESET button is pressed, because the Maximum Run
Time has been exceeded, the sounder will beep twice every
indication.
CONTROLLER ERROR CAUSES AND INDICATIONS
ERROR CAUSE ERROR INDICATION HOW TO CLEAR
En 00
En 01 MAX RUN
En 02 MAX RUN
En 03 COMM LINK
En 04
En 05
En 06
En 07
En 08
En 09
En 10
En 11
En 12
En 13
En 14
WARNINGThe Stop and/or Reset button must be located in the
line-of-sight of the gate. Activation of the reset control
shall not cause the operator to start.
TYM-VS2 Slide Gate Operator Installation Guide - 27 - Revision 0, 072012
Contacting Technical Support
1-800-328-4283 from 7 AM to 4:30 PM Eastern time
Operator fails to start
A. If the operator has been running a large number of
cycles, the motor may have become too hot and
tripped its thermal overload breaker. Allow the motor to
cool down and the thermal overload breaker will reset
automatically.
B. Make sure you have power at the master distribution
panel and that the power has not been turned off.
Motor operates, but gate does not move
A. In operators with torque limiters and friction pad clutches,
check for signs of slipping. You can mark the sprocket
and clutch with a yellow or white grease pen and watch
for the lines to move apart if slipping is taking place.
Adjust the torque limiter tighter if this is the problem.
B. Check for broken chain or worn belts.
C. Check all setscrews on pulleys and sprockets and
tighten them if necessary, and check for keys which may
have fallen loose from keyways.
Motor sounds like it is working harder than
normal
A. Make sure the gate is moving freely and without binding
throughout its entire travel.
B. Check the drive chain for obstructions (if the operator
has one).
C. If the operator has an internal brake mechanism, make
sure it is releasing.
Limit switch getting out of time
A. Check for proper tension on all limit chains to be sure
there is no jumping taking place. Mark one tooth and its
corresponding link and run the gate. If the marks have
moved, the chain is skipping.
B. Check the setscrews in limit sprockets for tightness. In
rotary limit boxes, check the rotary limit nut for sloppiness
or stripped threads. Replace if necessary.
Gate stopping part way open or closed
(but no visible obstruction)
A. The Controller may have received a false obstruction
input triggered by current sensing set too low. Make sure
the gate moves freely through its entire travel before
adjusting the current sensing.
B. The Maximum Run Timer may have counted down and
expired. This can be caused by having the timer set too
low, if a chain or belt is broken, or if a sprocket or pulley
is slipping. When the timer expires, the gate stops and
the beeper will sound.
C. An obstruction signal from an accessory wired to the
obstruction input may have triggered falsely. Check the
control board for lit indicators for any of the following
inputs: safety, shadow/reset, open obstruction, close
obstruction, stop, etc. If any are lit when the operator
should be running, remove all devices hooked to that
function and hook them up one at a time and try to run
the operator until the problem device is found. Refer to
Page 9 for details on the control board indicators.
Gate staying open with automatic system
A. If there are vehicle detectors used with the operator, one
of the loops or loop detectors may be sending a false
signal or needs to be reset. Observe the indicators on
the loop detector. Unplug the detector and try running
the operator.
B. An opening or reversing device may be stuck or
malfunctioning. Try disconnecting these devices and
hook them back up one at a time and try running the
operator until the malfunctioning device is found.
C. Make sure the close limit switch isn’t activated. If it is, the
operator will think the gate is already closed.
How to Order Replacement Parts
Use the part numbers listed on the following pages.
Contact Tymetal Corp. to order parts.
1. Supply the model number and serial number of your operator.
2. Specify the quantity of pieces needed and order by part number and name of part.
3. State whether to ship by freight, truck, parcel post, UPS or air express.
4. State whether transportation charges are to be prepaid or collect.
5. Specify name and address of person or company to whom parts are to be shipped.
6. Specify name and address of person or company to whom invoice is to be sent.
TYM-VS2 Slide Gate Operator Installation Guide - 28 - Revision 0, 072012-
Reference Part Number Description 1 49847 APeX II Controller
2
41494 3P AC Motor Drive Board Plug in for APeX (not shown)
40290 Reset Switch
3
4
42271
2110-741
APeX Alarm
Control Box
620-101243 Control Box Cover (clear, not shown)
5 2500-2288 Power Switch, 30A, 600V 3P
Select Motor Drive Based on Operator Voltage
6 Motor Drive with Keypad for 208/230V 1P TYM-VSA
Motor Drive with Keypad for 208/230V 3P TYM-VSA
Motor Drive with Keypad for 460V 3P TYM-VSA
Select Transformer Based on Operator Voltage
7 Transformer, 208/230V to 24V, 40VA
47842
47841 47843
35347 2500-214 Transformer, 460V to 24V, 40VA
8 620-101385 Heater Terminal
42266 Heater Kit, 208/230V 1P & 3P 49398 Heater Kit, 460V 3P
9 Complete Limit Box Assembly w/Cover, TYM-VSA 6 SWITCH
Limit & Ramp Switch (LSO-1, LSO-2, LSC-1, LSC-2)
AUX Switch Assembly (LSO-3 & LSC-3)
10 Complete Speed Reducer Assembly with Clutch & Crank Handle (40:1)
11
620-1014xx 51780 36498
35033
3201 Complete Crank Handle Assembly (replacement only)
12 190-111199 Control Box Support Bracket
13 Motor, 1HP, 230V/460V 3P, TEFC Motor Harness, TYM-VS A&C Series Control Box Motor Harness for 208/230V Operators Control Box Motor Harness for 460V Operators
14 Mounting Strap for VSA Enclosure
19397
620-101411 620-101413 620-101414
2100-2149
41015 Gate Warning Sign
- 29 -
TYM-VS2 Slide Gate Operator Installation Guide - 30 - Revision 0, 072012-
TYM-VS2 CONTROLLER MECHANICAL PARTS LIST
REF.
#PART # DESCRIPTION
Variable Speed Control Box Assemblies
Transformers
REF.
#PART # DESCRIPTION
Hitachi Controllers
APeX Parts
Wiring Harnesses
TYM-VS2 Slide Gate Operator Installation Guide - 31 - Revision 0, 072012
General
Tymetal gate operators are designed for many years of
trouble-free operation and, under recommended operating
conditions, will require only minimal maintenance. To ensure
that a unit is ready for operation at all times, and to preclude
serious damage or failure, inspect the unit systematically.
Proper adjustments and lubrication should be made as
recommended.
Lubrication
Bearings — For models which have pillow block style
year with a lithium complex based, petroleum oil NLGI 2
rated grease. Oilite and precision sealed bearings do not
require additional lubrication.
Motor — Motors have sealed ball bearings and do not
require further lubrication. If bearing noise develops
after several years of operation, bearings should be
replaced by a motor repair company, or the motor should
be replaced if necessary.
Drive Chain and Sprocket — The main drive chain and
sprockets should be inspected for wear, cleaned, and
wiped down with a lightly oiled rag every six months.
6-Month Preventative Maintenance
1. For operators which utilize torque limiting clutches,
check for proper tightness. If there appears to be dust
from wear on the pads, inspect the pads and replace
if necessary. If the clutch cannot be adjusted tightly
enough to move the gate without slipping, the pads must
be replaced.
2. For operators with V-belts, inspect for wear and replace
as necessary. Check for proper tension and adjust if
required. Check all pulley setscrews for tightness and
tighten if necessary.
3. For operators with internal chain drives, inspect chain
and sprockets for wear and replace if necessary. Check
for proper tension and alignment, and adjust if required.
Check all hub sprocket setscrews and tighten if required.
4. Check limit switches and limit actuators (cams, limit
nuts, etc.) for wear and replace as required. In rotary
limit switch assemblies, wipe the limit shaft clean and
apply a light coating of dry lubricant.
5. For operators with magnetic brakes, check for proper
adjustment. Brake disc must run free when the brake
is engaged. For brake assemblies other than C-face
style, the brake should be adjusted so that the solenoid
plunger throw is between 3/8” to 1/2”. Too much throw
will damage the solenoid. If the solenoid emits a loud
buzzing sound when the motor is run, the brake
must be adjusted.
6. In operators which have a disconnect handle, inspect
disconnect handle for proper function and lubricate if
necessary. Use a lithium based grease on all moving
parts.
7. Inspect all nuts and bolts for proper tightness and tighten
as necessary.
8. Check all reversing devices for proper function. Inspect
all contact edges for wear and replace if required. Check
photoeyes for proper alignment and function.
9. Check current sensing for proper adjustment when
10.Inspect the installation area. Are all the warning signs
intact and visible? If they are missing or need replaced,
contact Tymetal. Be sure there are no control stations
mounted within reach of the gate. Review safety
literature with the customer and advise them to remove
any such stations found.
This device complies with FCC Rules Part 15 and Industry
Canada Rules & Regulations. Operation is subject to the
following two conditions: (1) This device may not cause
harmful interference and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
WARNINGAlways disconnect power from operator before
servicing. Keep clear of gate during operation.
For all gate operators, you must
inspect thegate forproperoperation.
The gate should move easily without
binding through its entire travel. If
required. Failure to keep the gate in
good working condition will have
adverse effects on the operator.
TYM-VS2 Slide Gate Operator Installation Guide - 32 - Revision 0, 072012-
Programming the Hitachi Inverter
1. Apply power
2. Press FUNC
3. F_ _ (F002 for X200)
4. Press FUNC, arrows to change to 3.0 (3.00 for X200),
STR
5. Up arrow to advance to next parameter, (F03), FUNC
to view, arrows to change, STR to store and continue,
advance through listed parameters and store new
values.
6. FUNC
FUNC,
advance to desired parameter.
7. When all parameters have been changed, advance to
D01, press FUNC, then press STR. This will display the
operating speed in Hz. (0-95)
CAUTIONThis unit has been programmed at the factory. No
changes should be necessary for normal operation.
PLEASE CONSULT THE FACTORY BEFORE MAKING
ANY CHANGES!
MODEL X200
FUNCTION DESCRIPTIONRECOMMENDED
SETTING
Figure 18. Hitachi X200 Inverter
NOTE: NOTE:
01 AUTO VOLTAGE REGA081
TYM-VS2 Slide Gate Operator Installation Guide - 34 - Revision 0, 072012-
1. The gate has been checked to make sure it is level and moves freely in both directions.
2. Potential pinch areas have been guarded so as to be inaccessible OR have
contact and/or non-contact obstruction sensing devices installed.
3. The installer has installed one or more contact or non-contact obstruction sensing
devices, in compliance with UL325 requirements for this installation.
installed, a minimum of seven feet from the gate. The customer has been
informed that .
5. Warning signs have been installed on each side of the gate in highly visible locations.
The customer has been informed that these signs must remain at all times.
6. There are no controls installed on the gate operator, or within seven feet of the gate.
7. The installer has properly adjusted the obstruction sensing feature and has tested the gate
to make sure that the gate stops and reverses a short distance with minimal resistance
applied (40 lbs. on a swing gate at the end of the gate, 75 lbs. on a slide gate)
8. The installer has instructed the customer in the proper use of the gate operator and reviewed
all of the operational functions, obstruction sensing devices, warning beeper and reset, etc.
9. The installer has instructed the customer in the proper use of the operator’s
manual disconnect feature. The manual disconnect must never be used
while the gate is in motion. The power switch must be turned off before
using the manual disconnect and disengaging the operator.
10. The installer has reviewed all safety instructions with the customer, and has left
the safety instructions and owner’s information sheets for their reference.
11. The installer has answered any questions the customer has regarding the
operation of the gate operator and gate operator safety precautions.
12. The installer has explained to the customer that a regular maintenance
schedule for both the gate and the gate operator is recommended.
By signing this installation checklist, I/we hereby certify that each item listed and checked above has been covered by the
installer and is clearly understood by the customer.
INSTALLER CUSTOMER
Customer’s Signature
Installer’s Signature
Date
Date