22
www.singervalve.com 185 Models 106-A-Type 1 / 206-A-Type 1 Two-Way Flow Altitude Control Valve Level Control 2013.1 KEY FEATURES No overlows Superior repeatability Positive shut-off Easily serviceable at ground level Product Overview The 106-A-Type 1 and 206-A-Type 1 altitude control valves are based on the 106-PG or 206-PG main valve and are ideal for maintaining a preset maximum water level. The valve functions as a two position control valve, either fully open or fully closed. The Type 1 allows normal forward low to ill the reservoir to the maximum level and then closes drip-tight at the set-point. It opens to allow reverse low through the valve when the supply pressure drops a ixed amount below the reservoir head. When a higher supply pressure is restored, the Type 1 valve will then allow normal forward low to reill the tank to the maximum level. 206-A-Type 1 Globe

Two-Way Flow Altitude Control Valve - JNF - Fehlingerjnfsteam.com/wp-content/uploads/2016/02/Level-Control-Valves... · Two-Way Flow Altitude Control Valve Level Control 2013.1 KEY

  • Upload
    tranque

  • View
    233

  • Download
    2

Embed Size (px)

Citation preview

www.singervalve.com185

Models 106-A-Type 1 / 206-A-Type 1

Two-Way Flow Altitude Control Valve

Le

ve

l Co

ntro

l

2013.1

KEY FEATURES• No overlows• Superior repeatability

• Positive shut-off

• Easily serviceable at ground level

Product OverviewThe 106-A-Type 1 and 206-A-Type 1 altitude control valves are based on the 106-PG or 206-PG main valve and are ideal for maintaining a preset maximum water level.

The valve functions as a two position control valve, either fully open or fully closed. The Type 1 allows normal forward low to ill the reservoir to the maximum level and then closes drip-tight at the set-point. It opens to allow reverse low through the valve when the supply pressure drops a ixed amount below the reservoir head.

When a higher supply pressure is restored, the Type 1 valve will then allow normal forward low to reill the tank to the maximum level.

206-A-Type 1 Globe

186

Models 106-A-Type 1 / 206-A-Type 1

Two-Way Flow Altitude Control Valve

Le

ve

l Co

ntro

l

2013.1

1. Main Valve - 106-PG or 206-PG - with X107 position indicator

2. Isolation Valve

3. Strainer - 40 mesh stainless steel screen

4. Model 10 Check Valve

5. Closing Speed Control

6. Model 12 Check Valve

7. Model 301-4 Altitude Pilot

8. Altitude Gauge

9. Fixed Restriction - 1/8 in / 3.2 mm, 1/16 in / 1.58 mm

10. Union

11. Isolation Valve

12. Connection to Reservoir - complete in ield13. Model 12 Check Valve

14. Isolation Valve

Schematic Drawing

Typical Application

Reservoir tower

Higher supply pressure (e.g. from pumps) and distribution to users

Sensing connected to drain line or to the reservoir directly (completed by others).Sensing line minimum recommended size is 3/4 in / 20 mm. Slope to avoid air pockets.

Provides connection to drain for displaced water from bonnet

Drain

Singer 106-A-1, Two-Way Flow Altitude Control Valve

Schematic A-0412D

www.singervalve.com187

Models 106-A-Type 1 / 206-A-Type 1

Two-Way Flow Altitude Control Valve

Le

ve

l Co

ntro

l

2013.1

Standard MaterialsStandard materials for pilot system components are:

• Ductile Iron

• Stainless Steel

• Brass

• Copper

Speciications • The valve shall be a Singer Valve model 106-A-Type 1 / 206-A-Type 1, size “_____”, ANSI Class

150 (ANSI 300, ANSI langes drilled to ISO PN 10 / 16 / 25 or 40) pressure rating / lange standard, globe (angle), style valve. The Model 301-4 Altitude Pilot spring range (elevation) shall be “___ to ___” feet / meters, with set-point preset at Singer Valve to “___” feet / meters. Assembly shall be according to Schematic A-0412D.

• The valve allows normal forward low to ill the reservoir to the maximum level then closes drip-tight at the set-point. It opens to allow reverse low through the valve to distribute to users when the supply pressure drops a ixed amount below the reservoir head. When a higher supply pressure is restored the Type 1 will then allow normal forward low to reill the tank to the maximum level.

• Refer to Main Valve section, page 11, 106-PG (or 206-PG) and Main Valve Options section, Model X107 Position Indicator for detailed information pertaining to valve sizes and materials, selection criteria and speciications.

• Refer to Pilot and Accessories, page 266, section, Model 301-4 Altitude Pilot for detailed information pertaining to materials and speciications.

Selection Summary1. Generally select line size to minimize losses during normal forward low.2. Use the performance curves and sizing bulletin to determine the pressure drop across the valve.

3. Limit maximum continuous low velocity to 20 ft/s / 6 m/s for 106 and 16 ft/s / 5 m/s for 206. Consult Singer Valve if higher lows are expected.

4. The pilot system exhausts to atmosphere, ensuring the valve opens fully; requires that the displaced volume of water be taken to drain with each opening.

5. Select pilot spring range: 4 to 20 ft / 1 to 6 m; 10 to 60 ft / 3 to 18 m; 40 to 125 ft / 12 to 38 m; 60 to 220 ft / 18 to 67 m.

6. There is a non-adjustable differential required between the reservoir head and the supply pressure in order for the valve to open. It ranges from 2 ft / 0.6 m to 5 ft / 1.5 m for the pilot spring ranges listed.

188

Models 106-A-Type 1 / 206-A-Type 1

Two-Way Flow Altitude Control Valve

Le

ve

l Co

ntro

l

2013.1

Note: based on fully open valve

(Q=CV P )

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

Ordering InstructionsRefer to page 293 for the order form and ordering instructions.

Additionally, include the following information for this product:

1. Full port (106) and reduced port (206)

2. Pilot range

106-A-Type 1Flow Coeficient C

v

(See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

206-A-Type 1Flow Coeficient C

v

(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

106-A-Type 1Flow Coeficient C

v

(See 106-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv2 310 500 610 780 1210 1800 3875

206-A-Type 1Flow Coeficient C

v

(See 206-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv2 230 370 520 780 810 830 1210 1850 1850 1870 1900 4265

www.singervalve.com189

Models 106-A-Type 2 / 206-A-Type 2

One-Way Flow Altitude Control Valve

Le

ve

l Co

ntro

l

2013.1

Higher pressure supply

Distribution to users

Reservoir tank

Sensing connected to drain line or to thereservoir directly (completed by others).Sensing line minimum recommended size is3/4 in / 20 mm. Slope to avoid air pockets.

Non-adjustable drawdown

Singer 106-A-2, one-way low altitude control valve, with a manual by-pass

Provide connection to drain for displaced water from bonnet

Drain

Typical Application

Product OverviewThe 106-A-Type 2 and 206-A-Type 2 altitude control valves are based on the 106-PG or 206-PG main valve and are ideal for maintaining a preset maximum water level.

The valve functions as a two position control valve, either fully open or fully closed. The Type 2 valve allows normal forward low to ill the reservoir to the maximum level and then closes drip-tight at the set-point. It opens to reill the tank once the level drops a ixed distance below the high water level.

Note: This valve does not operate as a check valve to prevent reverse low.

KEY FEATURES• No overlows - high level shut-off

maintained to close tolerances

• Superior repeatability

• Positive shut-off

• Easily serviceable at ground level

206-A-Type 2 Globe

190

Models 106-A-Type 2 / 206-A-Type 2

One-Way Flow Altitude Control Valve

Le

ve

l Co

ntro

l

2013.1

1. Main Valve - 106-PG or 206-PG - with X107 position indicator

2. Strainer - 40 mesh stainless steel screen

3. Model 301-4 Altitude Pilot

4. Closing Speed Control

5. Altitude Gauge

6. Isolation Valve

7. Union

8. Isolation Valve

9. Sensing connection to reservoir (complete in ield by others)

10. Isolation Valve

Schematic Drawing

Schematic A-0413C

Standard MaterialsStandard materials for pilot system components are:

• Ductile Iron

• Stainless Steel

• Brass

• Copper

Selection Summary1. Generally select line size to minimize losses during normal forward low.2. Use the performance curves and sizing bulletin to determine the pressure drop across the valve.

3. Maximum continuous low - 106 is 20 ft/s / 6 m/s, 206 is 16 ft/s / 5 m/s. Consult Singer Valve if higher lows are expected.

4. The pilot system exhausts to atmosphere ensuring the valve opens fully; requires that the displaced volume of water be taken to drain with each opening.

5. Select pilot spring range. Standard (301-4) is 10 to 60 ft / 3 to 18 m. Specify for 301-4 ranges 4 to 20 ft / 1 to 6 m, 40 to 125 ft / 12 to 38 m, 60 to 220 ft / 18 to 67 m.

6. Level drop required to open: 1 ft to 3 ft / 0.3 m to 0.91 m approximate.

7 If the ill line discharges below the reservoir surface, an internal drop check or separate check valve is suggested. This prevents return low on loss of supply pressure.

www.singervalve.com191

Models 106-A-Type 2 / 206-A-Type 2

One-Way Flow Altitude Control Valve

Le

ve

l Co

ntro

l

2013.1

Speciications• The valve shall be a Singer Valve model 106-A-Type 2 / 206-A-Type 2, size “_____”, ANSI Class

150 (ANSI 300, ANSI langes drilled to ISO PN 10 / 16 / 25 or 40) pressure rating / lange standard, globe (angle), style valve. The Model 301-4 Altitude Pilot spring range (elevation) shall be “___ to ___” feet / meters, with set-point preset at Singer Valve to “___” feet / meters. Assembly shall be according to Schematic A-0413C.

• The valve allows normal forward low to ill the reservoir to the maximum level then closes drip-tight at the set-point. It opens to reill the tank once the level drops a ixed distance below the high water level.

• Refer to Main Valve section, page 11, 106-PG (or 206-PG) and Main Valve Options section, Model X107 Position Indicator for detailed information pertaining to valve sizes and materials, selection criteria and speciications.

• Refer to Pilot and Accessories section, page 266, Model 301-4 Altitude Pilot for detailed information pertaining to materials and speciications.

Ordering InstructionsRefer to page 293 for the order form and ordering instructions.

Additionally, include the following information for this product:

1. Full port (106) and reduced port (206)

2. Pilot range

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop Note: based on fully open valve

(Q=CV P )

106-A-Type2 Flow Coeficient Cv (See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

206-A-Type 2 Flow Coeficient CV (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

106-A-Type2 Flow Coeficient Cv (See 106-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv2 310 500 610 780 1210 1800 3875

206-A-Type 2 Flow Coeficient Cv (See 206-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv2 230 370 520 780 810 830 1210 1850 1850 1870 1900 4265

192

Models 106-A-Type 3 / 206-A-Type 3

Two-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

KEY FEATURES• No overlows• Superior repeatability while operating

within close limits

• Positive shut-off

Product OverviewThe 106-A-Type 3 and 206-A-Type 3 altitude control valves are based on the 106-PG or 206-PG main valve, and are ideal for maintaining preset maximum level.

The Type 3 allows normal forward low to ill the reservoir to the maximum level, then closes drip-tight at the set-point. The valve opens to permit reverse low through the valve when the supply pressure drops an adjustable amount below the reservoir head.

The Type 3 will then allow normal forward low to reill the tank to the maximum level, when a higher supply pressure is restored.

Reservoir tank / tower

Higher pressure supply (e.g. from pumps) and distribution to users

Sensing connected to drain line or to the reservoir directly (completed by others).Sensing line minimum recommended size is 3/4 in / 20 mm. Slope to avoid air pockets.

Singer 106-A-3, Two-Way Flow Altitude Valve,with differential control, installed with a manual by-pass

Provides connection to drain for displaced water from bonnet

Drain

106-A-Type 3 Globe

Typical Application

www.singervalve.com193

Models 106-A-Type 3 / 206-A-Type 3

Two-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

1. Main Valve - 106-PG or 206-PG - with X107 position indicator

2. Isolation Valve

3. Strainer - 40 mesh stainless steel screen

4. Model 10 Check Valve

5. Closing Speed Control

6. Model 625-RPD Differential Relief Pilot

7. Altitude Gauge

8. Isolation Valve

9. Sensing connection to reservoir - complete in ield10. Union

11. Fixed Restriction - 1/8 in / 3.2 mm

12. Model 301-4 Altitude Pilot;

13. Isolation Valve

Schematic Drawing

Schematic A-0414D

Standard MaterialsStandard materials for pilot system components are:

• Ductile Iron

• Stainless Steel

Speciications• The valve shall be a Singer Valve model 106-A-Type 3 / 206-A-Type 3, size “_____”, ANSI Class

150 (ANSI 300, ANSI langes drilled to ISO PN 10 / 16/ 25 or 40) pressure rating / lange standard, globe (angle), style valve. The Model 301-4 Altitude Pilot spring range (elevation) shall be “___ to ___” feet / meters, with set-point preset at Singer Valve to “___” feet / meters. The Model 625-RPD differential (delayed opening) range shall be “___” to “___” feet / meters, with set-point preset at Singer Valve to “___” feet / meters. Assembly shall be according to Schematic A-0414D.

• The valve allows normal forward low to ill the reservoir to the maximum level then closes drip-tight at the set-point It opens to allow reverse low through the valve to distribute to users when the supply pressure drops an adjustable amount below the reservoir head. When a higher supply pressure is restored the A-Type 3 will then allow normal forward low to reill the tank to the maximum level.

• Refer to Main Valve section, see page 11, 106-PG (or 206-PG) and “Main Valve Options” section, Model X107 Position Indicator for detailed information pertaining to valve sizes and materials, selection criteria and speciications.

194

Models 106-A-Type 3 / 206-A-Type 3

Two-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

• Refer to Pilot and Accessories section, see page 266, Model 301-4 Altitude Pilot for detailed information pertaining to materials and speciications. Model 625-RPD Pilot speciication information, is available from Singer Valve only at this time.

Selection Summary1. Generally select line size to minimize losses during normal forward low.2. Use the performance curves to determine the pressure drop across the valve.

3. Limit maximum continuous low velocity to less than 20 ft/s / 6 m/s for 106 and less than 16 ft/s / 5 m/s for 206.

4. The pilot system exhausts to atmosphere ensuring the valve opens fully; requires that the displaced volume of water be taken to drain with each opening - refer to section 106-PG or 206-PG, page 11, for displaced volume

5. Select pilot spring range. Standard (301-4) is 10 to 60 ft / 3 to 18 m. Specify for 301-4 ranges 4 to 20 ft / 1 to 6 m, 40 to 125 ft / 12 to 38 m, 60 to 220 ft / 18 to 67 m.

6. Select the adjustable differential pilot spring range. Standard is 5 to 15 ft / 2 to 5 m. Specify for 12 to 30 ft / 3.7 to 9.1 m or 25 to 50 / 8 to 15 m. The total differential includes the non-adjustable differential of the altitude pilot.

Ordering InstructionsRefer to page 293 for the order form and ordering instructions.

Additionally, include the following information for this product:

1. Full port (106) and reduced port (206)

2. Pilot ranges

www.singervalve.com195

Models 106-A-Type 3 / 206-A-Type 3

Two-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

Note: based on fully open valve (Q=CV P )

106-A-Type3Flow Coeficient C

v

(See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

206-A-Type 3Flow Coeficient C

v

(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

106-A-Type3Flow Coeficient C

v

(See 106-PG in Main Valve section for other valve data)

Size (in) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv2 310 500 610 780 1210 1800 3875

206-A-Type 3Flow Coeficient C

v

(See 206-PG in Main Valve section for other valve data)

Size (in) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv2 230 370 520 780 810 830 1210 1850 1850 1870 1900 4265

196

Models 106-A-Type 4 / 206-A-Type 4

One-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

KEY FEATURES• No overlows • Adjustable draw-down level

(differential) set-point

• Superior repeatability

• Positive shut-off

• Adjustable draw-down for improved water cycling

Product OverviewThe 106-A-Type 4 and 206-A-Type 4 altitude control valves are based on the 106-PG or 206-PG main valve, and are ideal for maintaining a preset maximum water level. The valve functions as a two position control valve, either fully open or fully closed.

The Type 4 allows normal forward low to ill the reservoir to the maximum level, then closes drip- tight at the set-point. It opens to reill the tank once the level drops an adjustable amount below the high water level.

Distribution from the reservoir is through a separate pipeline.

Note: This valve does not operate as a check valve to prevent reverse low.

206-A-Type 4 Globe

www.singervalve.com197

Models 106-A-Type 4 / 206-A-Type 4

One-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

Typical Application

Schematic Drawing

Maximum (Closed)

Higher Pressure Supply e.g. from pumps

Sensing connected to drain line or to thereservoir directly (completed by others).Sensing line minimum recommended size is3/4 in / 20 mm. Slope to avoid air pockets.

Distributionto users

Reservoir Tank

Singer 106-A-4, One-Way Flow Altitude Valve,with Differential Control, installed with a manual by-pass

Provide connection to drain for displaced water from bonnet

Static Drain

Minimum (Open)

Adjustable Drawdown

Schematic A-0415C

1. Main Valve - 106-PG or 206-PG - with X107 position indicator

2. Isolation Valve

3. Strainer - 40 mesh stainless steel screen

4. Closing Speed Control

5. Model 301-4 Altitude Pilot

6. Model 106-RD Differential Pilot

7. Altitude Gauge - dual scale - feet and meter

8. Isolation Valve

9. Sensing connection to reservoir - complete in ield10. Model 10 Check Valve

11. Union

12. Isolation Valve

198

Models 106-A-Type 4 / 206-A-Type 4

One-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

Standard MaterialsStandard materials for pilot system components are:

• Ductile Iron

• Stainless Steel

• Brass

• Copper

Speciication• The valve shall be a Singer Valve model 106-A-Type 4 / 206-A-Type 4, size “_____”, ANSI Class

150 (ANSI 300, ANSI langes drilled to ISO PN 10 / 16/ 25 or 40) pressure rating / lange standard, globe (angle), style valve. The Model 301-4 Altitude Pilot spring range (elevation) shall be “___ to ___” feet / meters, with set-point preset at Singer Valve to “___” feet / meters. The Model 106-RD differential (delayed opening) range shall be “___” to “___” feet / meters, with set-point preset at Singer Valve to “___” feet / meters. Assembly shall be according to Schematic A-0415C.

• The valve allows normal forward low to ill the reservoir to the maximum level then closes drip-tight at the set-point. It opens to reill the tank once the level drops an adjustable distance below the high water level.

• Refer to Main Valve section, see page 11, 106-PG (or 206-PG) and “Main Valve Options” section, Model X107 Position Indicator for detailed information pertaining to valve sizes and materials, selection criteria and speciications.

• Refer to Pilot and Accessories section, see page 266, Model 301-4 Altitude Pilot for detailed information pertaining to materials and speciications. Model 106-RD Pilot speciication information, is available from Singer Valve only at this time.

Selection Summary1. Generally select line size to minimize losses during normal forward low.2. Use the performance curves to determine the pressure drop across the valve.

3. Limit maximum continuous low velocity to less than 20 ft/s / 6 m/s for 106 and less than 16 ft/s / 5 m/s for 206.

4. The pilot system exhausts to atmosphere ensuring the valve opens fully; requires that the displaced volume of water be taken to drain with each opening. Refer to section 106-PG or 206-PG, page 11, for the displaced volume.

5. Select pilot spring range. Standard (301-4) is 10 to 60 ft / 3 to 18 m. Specify for 301-4 ranges 4 to 20 ft / 1 to 6 m, 40 to 125 ft / 12 to 38 m), 60 to 220 ft / 18 to 67 m.

6. Select differential pilot spring range. Standard is 5 to 15 ft / 1.5 to 4.6 m and 10 to 50 ft / 3 to 15 m. Specify for 12 to 50 ft / 3.7 to 15 m. The total differential includes the non-adjustable differential of the altitude pilot.

7. If the ill line discharges below the reservoir surface, an internal drop check or separate check valve is suggested. This prevents return low on loss of supply pressure.

www.singervalve.com199

Models 106-A-Type 4 / 206-A-Type 4

One-Way Flow Altitude Control Valve

with Differential Control

Le

ve

l Co

ntro

l

2013.1

*CV = USGPM at 1 psi pressure drop

**KV = L / s at 1 bar pressure drop

Note: based on fully open valve (Q=CV P )

Ordering InstructionsRefer to page 293 for the order form and ordering instructions.

Additionally, include the following information for this product:

1. Full port (106) and reduced port (206)

2. Pilot range

106-A-Type 4Flow Coeficient C

v

(See 106-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 110 200 460 800

Kv2 26 47 110 190

206-A-Type 4Flow Coeficient C

v

(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in

Size (mm) 80 mm 100 mm 150 mm 200 mm

Cv1 60 150 250 505

Kv2 14 36 60 120

106-A-Type 4Flow Coeficient C

v

(See 106-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Cv1 1300 2100 2575 3300 5100 7600 16340

Kv2 310 500 610 780 1210 1800 3875

206-A-Type 4Flow Coeficient C

v

(See 206-PG in Main Valve section for other valve data)

Size (inches) 10 in 12 in 16 in 18 in 20 in 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 250 mm 300 mm 400 mm 450 mm 500 mm 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Cv1 985 1550 2200 3300 3400 3500 5100 7800 7800 7900 8000 18000

Kv2 230.0 370.0 520.0 780.0 810.0 830.0 1210.0 1850.0 1850.0 1870.0 1900.0 4265

200

Models 106-F-Type 4 / 206-F-Type 4

Modulating Float Valve

Le

ve

l Co

ntro

l

2013.1

KEY FEATURES• Maintains relatively constant level

• Automatic compensation for level draw-down

• Standard integral damping reduces hunting

• Drip-tight at high level shut-off

• Low supply pressure options

Product OverviewThe Singer model 106-F-Type 4 and 206-F-Type 4 modulating loat valves are based on the 106-PG or 206-PG main valve. They are ideal for balancing the inlow and outlow demand into the reservoir and maintaining level at the designated maximum.

The valve closes drip-tight at the maximum level and modulates to maintain the tank level. The loat pilot is remotely installed at the high level in the reservoir tank. Pilot connections to the main valve are connected in the ield. As the reservoir level drops the main valve is opened proportionally to increase the illing rate. Movement of the main stem alters the size of the closing restriction, interrupting the tendency of the valve to hunt.

Typical Application

Tubing supplied by others.

Singer 106-F-Type 4

R400 pilot

206-F-Type 4 Globe

www.singervalve.com201

Models 106-F-Type 4 / 206-F-Type 4

Modulating Float Valve

Le

ve

l Co

ntro

l

2013.1

Schematic A-0608D

1. Main Valve - 106-PG or 206-PG, Internal Needle Stem Valve (INSV) built into stem

2. Isolation Valve

3. Strainer - 40 mesh stainless steel screen

4. Isolation Valve

5. R400 Float Pilot comes with plastic loat

Note: Schematic shown for 2.5 in / 65 mm and larger

Standard MaterialsStandard materials for pilot system components are:

• Stainless Steel

• Plastic loat• Brass, Copper, Iron

Note: The stilling well and the connections between the main valve and the R-400 pilot are provided by others.

Speciications• The valve shall be a Singer Valve model 106-F-Type 4 / 206-F-Type 4, size “_____”, ANSI Class

150 (ANSI 300, ANSI langes drilled to ISO PN 10 / 16/ 25 or 40) pressure rating / lange standard, globe (angle), style valve. The Model R-400 Modulating Float Valve shall be utilized with a ten inch brass loat rod and polypropylene loat (connection between main valve and Model R-400 Modulating Float Valve by others). Assembly shall be according to Schematic A-0608D.

• The valve allows low into the reservoir in order to maintain the level at the designated maximum. The valve closes drip-tight at the maximum level. As the reservoir drops, the main valve opens proportionally (modulates) to increase the illing rate in an effort to maintain the maximum reservoir level.

• Refer to Main Valve section, see page 11, 106-PG (or 206-PG) for detailed information pertaining to valve sizes and materials, selection criteria and speciications.

• Refer to Pilot and Accessories section, see page 267, Model R-400 Modulating Float Pilot for detailed information pertaining to materials and speciications.

Selection Summary1. Generally select line size to minimize losses during normal forward low.2. Use the performance curves and sizing bulletin to check the pressure drop across the valve at

normal low rate.

Schematic Drawing

202

Models 106-F-Type 4 / 206-F-Type 4

Modulating Float Valve

Le

ve

l Co

ntro

l

2013.1

3. Check the maximum operating pressure against the maximum working pressure rating of the langes.

4. If the outlet pressure is less than 35% of the inlet pressure, check for cavitation.

5. If the inlet pressure is less than 10 psi / 0.7 bar higher than the maximum reservoir head, consult with Singer Valve.

6. Assisted opening may be required for full low. - for non-modulating (on-off) service, refer to model 106-F-Type 5 / 206-F-Type 5 loat valve

- for high tower reservoir, refer to models 106-A-Type 1 / 206-A-Type 1, or 2, or 3, or 4 Altitude Control valves.

Ordering InstructionsRefer to page 293 for the order form and ordering instructions.

Additionally, include the following information for this product:

• Full port (106) and reduced port (206)

106-F-Type 4 Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Pressure Drop (PSI) 20 20 20 15 15 20 15 16 15

Pressure Drop (Bar) 1.4 1.4 1.4 1.0 1.0 1.4 1 1.1 1.0

206-F-Type 4 Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Pressure Drop (PSI) 19 15 17 21 17 17 18 23 22

Pressure Drop (Bar) 1.3 1.0 1.2 1.4 1.2 1.2 1.2 1.6 1.5

106-F-Type 4 Flow Capacity (See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25000 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1577 3500

Pressure Drop (PSI) 15 15 15 16 11 17 8.6 9.6 8.6

Pressure Drop (Bar) 1.0 1.0 1.0 1.1 0.8 1.2 0.6 0.7 0.6

206-F-Type 4 Flow Capacity (See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 55470

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3500

Pressure Drop (PSI) 21 21 17 17 17 17 17

Pressure Drop (Bar) 1.4 1.4 1.2 1.2 1.2 1.2 1.2

www.singervalve.com203

Models 106-F-Type 5 / 206-F-Type 5

Non-Modulating Float Valve

Le

ve

l Co

ntro

l

2013.1

KEY FEATURES• No overlow, drip-tight close• Adjustable draw down

• Easily adjustable level settings

• Low supply pressure options

Product OverviewThe 106-F-Type 5 and 206-F-Type 5 non-modulating loat valves are based on the 106-PG or 206-PG main valve. It is ideal for allowing normal forward low to ill water reservoirs to a desired high level and where the pilot and valve of the reservoirs are easily accessible.

The valve functions as a two position valve, either open or closed. The valve remains closed when the reservoir level drops, until the loat reaches the pre-determined adjustable minimum reservoir level. The F-Type 5 valve then opens to reill the reservoir and closes tightly when high water level is achieved.

206-F-Type 5 Globe

204

Models 106-F-Type 5 / 206-F-Type 5

Non-Modulating Float Valve

Le

ve

l Co

ntro

l

2013.1

Singer model 106-F-Type 5 Non-Modulating Float Valve

Model 43 loatpilot with 4 ft / 1.2 mrod and copper loat

Note:Per illustration, Float Valves greater than 4 in / 100 mm cannot be positioned on its side.

1. Main Valve - 106-PG or 206-PG

2. Isolation Valve

3. Strainer - 40 mesh stainless steel screen

4. Opening / Closing Speed Control

5. Model 43 Float Pilot c/w copper loat, 4 ft / 1.2 m brass rod

Schematic A-0421C

Stilling Well

Schematic Drawing

Typical ApplicationNon-modulating loat valves are typically used in buildings with reservoir tanks or installations where the valve and pilot are readily accessible.

The on / off service ensures that the reservoir contents are cycled. It will also prevent over cycling of the supply pumps as the minimum quantity per cycle is adjustable.

www.singervalve.com205

Models 106-F-Type 5 / 206-F-Type 5

Non-Modulating Float Valve

Le

ve

l Co

ntro

l

2013.1

Standard MaterialsStandard materials for pilot system components are:

• ASTM B-62 bronze or ASTM B-16 brass

• Copper loat

Note: The stilling well and the connections between main valve and pilot completed by others.

Speciications• The valve shall be a Singer Valve model 106-F-Type 5/ 206-F-Type 5, size “_____”, ANSI

Class 150 (ANSI 300, ANSI langes drilled to ISO PN 10 / 16 / 25 or 40) pressure rating / lange standard, globe (angle), style valve. The Model 43 Non-Modulating Float Pilot shall be utilized with a 4 ft / 1.2 m brass loat rod with adjustable stops and a copper loat (connection between main valve and Model 43 Non-Modulating Float Valve by others). Assembly shall be according to Schematic A-0421C.

• The valve allows low into the reservoir to the maximum high level where it closes drip-tight. The valve remains close when the reservoir level drops until the loat reaches the pre-determined minimum reservoir level at which time it opens to reill the reservoir.

• Refer to Main Valve section, page 11, 106-PG (or 206-PG) for detailed information pertaining to valve sizes and materials, selection criteria and speciications.

• Refer to Pilot and Accessories section, page 271, Model 43 Non-Modulating Float Pilot With Vertical Rod for detailed information pertaining to materials and speciications.

Selection Summary1. Generally select line size to minimize losses during normal forward low - see chart of maximum

continuous low below.2. Use the performance curves and sizing bulletin to determine the pressure drop across the valve at

normal low rate.3. Check the maximum operating pressure against the maximum working pressure rating

of the langes.4. If the outlet pressure is less than 35% of the inlet pressure, check for cavitation.

5. If the inlet pressure is less than 10 psi / 0.70 bar higher than the reservoir head, consult with Singer Valve. Assisted opening may be required for full low.

– To maintain a relatively steady tank level, refer to model 106-F-Type 4 / 206-F-Type 4: Modulating Float Valve, 194

– for SCADA or electronic level control, refer to model 106-2SC-PCO / 206-2SC-PCO Dual Solenoid Control Valve

206

Models 106-F-Type 5 / 206-F-Type 5

Non-Modulating Float Valve

Le

ve

l Co

ntro

l

2013.1

Ordering InstructionsRefer to page 293 for the order form and ordering instructions.

Additionally, include the following information for this product:

1. Full port (106) and reduced port (206)

2. Pilot range

106-F-Type 5Flow Capacity

(See 106-PG in Main Valve section for other valve data)

Size (inches) 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 4 in

Size (mm) 15 mm 19 mm 25 mm 32 mm 40 mm 50 mm 65 mm 80 mm 100 mm

Maximum Continuous (USGPM) 12 19 49 93 125 210 300 460 800

Maximum Continuous (L/s) 0.8 1 3 6 8 13 19 29 50

Pressure Drop (PSI) 20 20 20 15 15 20 15 16 15

Pressure Drop (Bar) 1.4 1.4 1.4 1.0 1.0 1.4 1 1.1 1.0

206-F-Type 5Flow Capacity

(See 206-PG in Main Valve section for other valve data)

Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in

Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm

Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500

Maximum Continuous (L/s) 19 37 65 145 260 404 582 1040 1040

Pressure Drop (PSI) 19 15 17 21 17 17 18 23 22

Pressure Drop (Bar) 1.3 1.0 1.2 1.4 1.2 1.2 1.2 1.6 1.5

106-F-Type 5Flow Capacity

(See 106-PG in Main Valve section for other valve data)

Size (inches) 6 in 8 in 10 in 12 in 14 in 16 in 20 in 24 in 36 in

Size (mm) 150 mm 200 mm 250 mm 300 mm 350 mm 400 mm 500 mm 600 mm 900 mm

Maximum Continuous (USGPM) 1800 3100 4900 7000 8500 11000 17500 25000 55470

Maximum Continuous (L/s) 114 196 309 442 536 694 1104 1577 3500

Pressure Drop (PSI) 15 15 15 16 11 17 8.6 9.6 8.6

Pressure Drop (Bar) 1.0 1.0 1.0 1.1 0.8 1.2 0.6 0.7 0.6

206-F-Type 5Flow Capacity

(See 206-PG in Main Valve section for other valve data)

Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in

Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm

Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 55470

Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3500

Pressure Drop (PSI) 21 21 17 17 17 17 17

Pressure Drop (Bar) 1.4 1.4 1.2 1.2 1.2 1.2 1.2