Tutorial 3 - July 2010

Embed Size (px)

Citation preview

  • 8/10/2019 Tutorial 3 - July 2010

    1/9

    1. Three 15 MVA, 30 kV synchronous generators A, B, and C are connected via threereactors to a common bus bar, as shown in Figure 1. The neutrals of generators Aand B are solidly grounded, and the neutral of generator C is grounded through a

    reactor of 2.0 . The generator data and the reactance of the reactors are tabulatedbelow. A line-to-ground fault occurs on phase a of the common bus bar. Neglect

    prefault currents and assume generators are operating at their rated voltage.Determine the fault current in phasea.

    Figure 1

    The generator base impedance is

    == 6015

    (30)Z

    2

    B

    The reactor per-unit reactance, and the per-unit generator C neutral reactor are

    pu1.0==60

    6XR

    pu3333.0==602Xn

    The positive-sequence impedance network is shown in Figure (a), and the zerosequence impedance network is shown in Figure (b).

  • 8/10/2019 Tutorial 3 - July 2010

    2/9

    The positive-sequence impedance is

    3.0

    1

    3.0

    1

    35.0

    1++=

    1X

    1 pu105.0X1 =

    The negative-sequence impedance network is the same as the positive-sequenceimpedance network, except for the value of the generator negative-sequencereactance. Therefore, the negative-sequence impedance is

    255.0

    1

    255.0

    1

    255.0

    1++=

    2X

    1 pu085.0X 2 =

    The zero-sequence impedance is

    26.0

    1

    156.0

    1

    156.0

    1++=

    0X

    1 pu06.0X 0 =

    The line-to-ground fault current in phasea is

    pu12j)06.0085.0105.0(j

    3I3I )0(aa =

    ++==

    2. The reactance data for the power system shown in Figure 2 in per unit on a commonbase is as follows:

    X1 = 10 %

    X0 = 5 %

    X1 = 25 %

    X0 = 25 %

    X1 = 25 %

    X0 = 25 %

    XG1 = 10 %

    XG0 = 5 %

    X1 = 30 %

    X0 = 50 %

    Figure 2

    Obtain the Thevenin sequence impedances for the fault at bus 1 and compute thefault current in per unit for the following faults:(a) A bolted three-phase fault at bus 1.(b) A bolted single line-to-ground fault at bus 1.(c) A bolted line-to-line fault at bus 1.(d) A bolted double line-to-ground fault at bus 1.

  • 8/10/2019 Tutorial 3 - July 2010

    3/9

    The positive-sequence impedance network is shown below, and impedanceto the point of fault is

    pu2275.0j65.035.0

    )65.0)(35.0(jZ1 =

    +=

    Since negative-sequence reactances are the same as positive-sequence reactances,X2=X1= 0.2275.

    The zero-sequence impedance network is shown below, and impedance to the pointof fault is

    pu1875.0j75.025.0

    )75.0)(25.0(jZ0 =

    +=

    (a) For a bolted three-phase fault at bus 1, the fault current is

    pu3956.4j2275.0

    1jI f ==

    (b) For a bolted single-line to ground fault at bus 1, the fault current is

    pu669.4j)1875.02275.02275.0(j

    3I3I )0(af =

    ++==

    (c) For a bolted line-to-line fault at bus 1, the fault current in phase b is

    pu1978.2j)2275.02275.0(j

    1I )1(a =

    +=

    pu3jI f 3.8067-I(1)

    a ==

  • 8/10/2019 Tutorial 3 - July 2010

    4/9

    (d) For a bolted double line-to-line fault at bus 1, we have

    pu02767.3j

    )1875.02275.0(

    )1875.0)(2275.0(j2275.0j

    1I )1(a =

    ++

    =

    pu6597.1j02767.3jI )0(a =+

    =0.1875)(0.2275

    0.2275

    pu9792.4jI3I )0(af ==

    3. The zero-, positive-, and negative-sequence bus impedance matrices for athree-bus power system are

    jZ0 = pu

    0.300.080.12

    0.080.100.050.120.050.20

    1Z = jZ2 = pu

    0.250.120.15

    0.120.200.100.150.100.16

    Determine the per unit fault current and the bus voltages during fault for(a) A bolted three-phase fault at bus 2.(b) A bolted single line-to-ground fault at bus 2.(c) A bolted line-to-line fault at bus 2.(d) A bolted double line-to-ground fault at bus 2.

    (a) The symmetrical components of fault current for a bolted balanced three-phasefault at bus 2 is given by

    (1)

    afI = (1)22

    f

    Z

    V=

    j0.20

    1= -j5 ; (2)afI = 0 ;

    (0)

    afI = 0

    The fault current

    fc

    fb

    fa

    I

    I

    I

    =

    2

    2

    aa1

    aa1

    111

    0

    j5-

    0

    =

    0

    0

    0

    305

    1505

    90-5

    For balanced fault we only have the positive-sequence component of voltage. Thus,bus voltages during fault for phasea are

    0.50.2

    0.11.0

    Z

    Z1.0V

    1

    22

    1

    12)F(1 === p.u.

  • 8/10/2019 Tutorial 3 - July 2010

    5/9

    00.2

    0

    Z

    ZV

    22

    F)F(2 === p.u.

    0.4

    0.2

    0.121.0

    Z

    Z1.0V

    1

    22

    1

    32)F(3 === p.u.

    (b) The symmetrical components of fault current for a single line-to-groundfault at bus 2 is given by

    (1)

    afI =(2)

    afI =(0)

    afI = (0)22

    (2)

    22

    (1)

    22

    f

    ZZZ

    V

    ++

    Let0

    f 01.0V =

    Then (1)afI =(2)

    afI =(0)

    afI =0.10)0.20(0.20j

    01.0 0

    ++

    = 2j

    The fault current (1)af(2)

    af(1)

    af(0)

    afaf I3IIII =++= = - j 6; bfI = cfI = 0

    The sequence components of voltage at bus 2 are calculated as

    0.20)j()0.10j(IZV(0)

    af

    (0)

    22

    (0)

    a2 === 2

    0.60)j2()0.20j(1.0IZVV (1)af(1)

    22f

    (1)

    a2 ===

    0.40)j2()j0.20(IZV (2)af(2)

    22

    (2)

    a2 ===

    Phase components of line to ground voltage of bus 2 are computed as

    c2

    b2

    a2

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.40

    0.60

    0.20

    =

    The sequence components of voltage at bus 1 are calculated as

    0.10)j()0.05j(IZV (0)af(0)

    12

    (0)

    a1 === 2

    0.80)j()0.10j(1.0IZVV (1)af(1)

    12f

    (1)

    a1 === 2

    0.20)j2()j0.10(IZV (2)af(2)12(2)a1 ===

    Phase components of line to ground voltage of bus 1 are computed as

    0

    0.91650

    109.11

    0.9165 0109.11

  • 8/10/2019 Tutorial 3 - July 2010

    6/9

    c1

    b1

    a1

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.20

    0.80

    0.10

    =

    The sequence components of voltage at bus 3 are calculated as

    0.16)j()0.08j(IZV (0)af(0)

    32

    (0)

    a3 === 2

    0.76)j()0.12j(1.0IZVV(1)

    af

    (1)

    32f

    (1)

    a3 === 2

    0.24)j2()j0.12(IZV (2)af(2)

    32

    (2)

    a3 ===

    Phase components of line to ground voltage of bus 1 are computed as

    c3

    b3

    a3

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.24

    0.76

    0.16

    =

    (c) The symmetrical components of fault current for line-to-line fault at bus 2 are

    (0)

    afI = 0

    (1)

    afI = -(2)

    afI = (2)22

    (1)

    22

    f

    ZZ

    V

    +=

    )0.20(0.20j

    01.00

    +

    = -j2.5

    The phase components of fault currents in the fault are

    0IIII (2)af(1)

    af

    (0)

    afaf =++=

    ==+= (1)af(2)

    af

    (1)

    af

    2

    bf I3jIaIaI -4.33

    == bfcf II 4.33

    The sequence components of voltage at bus 2 are calculated as

    0)()0.10j(IZV (0)af(0)

    22

    (0)

    a2 === 0

    0.50)j2.5()0.20j(1.0IZVV (1)af(1)22f(1)a2 ===

    0.50)j2.5()j0.20(IZV(2)

    af

    (2)

    22

    (2)

    a2 ===

    Phase components of line to ground voltage of bus 2 are computed as

    0.50 00

    0.95390

    114.79

    0.9539 0114.79

    0.36 00

    0.96250

    115.87

    0.9625 0115.87

  • 8/10/2019 Tutorial 3 - July 2010

    7/9

    c2

    b2

    a2

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.50

    0.50

    0

    =

    The sequence components of voltage at bus 1 are calculated as

    0)()0.05j(IZV (0)af(0)

    12

    (0)

    a1 === 0

    0.75)j()0.10j(1.0IZVV(1)

    af

    (1)

    12f

    (1)

    a1 === 5.2

    0.25)j2.5()j0.10(IZV (2)af(2)

    12

    (2)

    a1 ===

    Phase components of line to ground voltage of bus 1 are computed as

    c1

    b1

    a1

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.25

    0.75

    0

    =

    The sequence components of voltage at bus 3 are calculated as

    0)()0.08j(IZV (0)af(0)

    32

    (0)

    a3 === 0

    0.70)j()0.12j(1.0IZVV(1)

    af

    (1)

    32f

    (1)

    a3 === 5.2

    0.30)j2.5()j0.12(IZV (2)af(2)

    32

    (2)

    a3 ===

    Phase components of line to ground voltage of bus 1 are computed as

    c3

    b3

    a3

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    =

    0.30

    0.70

    0

    (d) The symmetrical components of fault current for a double line-to-ground fault atbus 2 is given by

    .75j

    0.10j0.20j

    )0.10j()0.20j(0.20j

    1.0

    ZZ

    ZZZ

    VI

    (0)

    22

    (2)

    22

    (0)

    22

    (2)

    22(1)

    22

    f(1)

    af 3=

    ++

    =

    ++

    =

    1

    0

    0

    0.6614 0139.11

    0.6140130.11

    10

    0

    0.5 0180

    0.50

    180

    1 00

    0.60830

    145.285

    0.6083 0145.285

  • 8/10/2019 Tutorial 3 - July 2010

    8/9

    j1.25j0.10j0.20

    j0.10)j3.75(

    ZZ

    ZII

    (0)

    22

    (2)

    22

    (0)

    22(1)

    af

    (2)

    af =+

    =+

    =

    j2.5

    j0.10j0.20

    j0.20)j3.75(

    ZZ

    ZII

    (0)

    22

    (2)

    22

    (2)

    22(1)

    af

    (0)

    af =

    +

    =

    +

    =

    Phase components of current at the fault bus are

    =++= (2)af(1)

    af

    (0)

    afaf IIII 0

    00(2)

    af

    (1)

    af

    2(0)

    afbf 21025150j2.5IaIaII ++=++= .175.3

    = 5.7282 0139.11 0.175.3 302530j2.5IaIaII 0(2)af

    2(1)

    af

    (0)

    afcf ++=++=

    = 5.7282 0.8940

    Fault current =+= cfbff III 7.5090

    The sequence components of voltage at bus 2 are calculated as

    0.25)j()0.10j(IZV (0)af(0)

    22

    (0)

    a2 === 5.2

    0.25)j3.75()0.20j(1.0IZVV (1)af(1)

    22f

    (1)

    a2 ===

    0.25)j1.25()j0.20(IZV (2)af(2)

    22

    (2)

    a2 ===

    Phase components of line to ground voltage of bus 2 are computed as

    c2

    b2

    a2

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.25

    0.25

    0.25

    =

    The sequence components of voltage at bus 1 are calculated as

    0.125)j()0.05j(IZV (0)af(0)

    12

    (0)

    a1 === 5.2

    0.625)j3()0.10j(1.0IZVV (1)af(1)

    12f

    (1)

    a1 === 75.

    0.125)j1.25()j0.10(IZV (2)af(2)12

    (2)a1 ===

    Phase components of line to ground voltage of bus 1 are computed as

    0.750

    0 0

    0

  • 8/10/2019 Tutorial 3 - July 2010

    9/9

    c1

    b1

    a1

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.125

    0.625

    0.125

    =

    The sequence components of voltage at bus 3 are calculated as

    0.20)j()0.08j(IZV (0)af(0)

    32

    (0)

    a3 === 5.2

    0.55)j()0.12j(1.0IZVV (1)af(1)

    32f

    (1)

    a3 === 75.3

    0.15)j1.25()j0.12(IZV (2)af(2)

    32

    (2)

    a3 ===

    Phase components of line to ground voltage of bus 1 are computed as

    c3

    b3

    a3

    V

    V

    V

    =

    2

    2

    aa1

    aa1

    111

    0.15

    0.55

    0.20

    =

    0.87500

    0.500

    120

    0.50 0120

    0.90 00

    0.37750

    113.413

    0.3775 0113.413