 RASHMI METALIKS LTD TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD FOR 350 CUM MBF AT KHARAGPUR BID DOCUMENT FOR  33 kV SWITCHBOARD PACKAGE VOLUME I OF I ENQUIRY NO.: RML/SPEC-33-SB/TS-05  

Ts of 33 Kv in Door Switch Board-i

Embed Size (px)

DESCRIPTION

ts

Citation preview

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    BID DOCUMENT

    FOR

    33 kV SWITCHBOARD PACKAGE

    VOLUME I OF I

    ENQUIRY NO.: RML/SPEC-33-SB/TS-05

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    VOLUME-I OF I

    TECHNICAL SPECIFICATION OF 33 kV SWITCHBOARD

    C O N T E N T S

    S.NO. DESCRIPTION PAGE NO.

    1. INTENT OF SPECIFICATION 2

    2. TECHNICAL SPECIFICATION FOR 33 kV SWITCHBOARD 3

    2.1 Introduction 3

    2.2 Specific Requirements: 3

    2.3 Standards 4

    2.4 General Requirements 5

    2.5 Busbars 7

    2.6 Circuit Breakers 8

    2.7 Earthing Trolleys 10

    2.8 Current Transformers 10

    2.9 Potential Transformer 11

    2.10 Integrating Meters 11

    2.11 Indicating Lamps 12

    2.12 Relays 13

    2.13 Control Switches and Push Buttons 13

    2.14 Internal Wiring 14

    2.15 Terminal Blocks 14

    2.16 Cable Termination 14

    2.17 Labels 15

    2.18 Painting 15

    2.19 Tests 15

    2.20 List of Documents / Drawings to be Submitted 16

    2.21 List of Operational Spares 18

    2.22 Make of Components 19

    3.0 CLEANING AND PACKING,SPARES:

    4.0 DATA SHEETS AND SCHEDULES 20

    5.0 TENDER DRAWING 29

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    1. INTENT OF SPECIFICATION

    1.1 This specification is intended to cover the design, engineering,

    manufacture, shop fabrication, assembly, pre-assembly, tests and

    inspection at manufacturers work, packing, shipment, supervision of

    erection at site of Rashmi Metaliks Ltd. at khadagpur.

    1.2 The equipment and services furnished shall meet all the requirement of

    this specification, data sheets etc., In case of any conflict / contradiction

    among various part of the specification, data sheets the same shall be

    referred to the engineer for clarification whose decision shall be final and

    binding.

    1.3 It is not the Intent to specify completely herein all aspects of design and

    construction of equipment. Nevertheless, the equipment shall conform in

    all respects to high standards of engineering, design and workmanship and

    shall be capable of performing in continuous commercial operation in a

    manner acceptable to the PURCHASER who will interpret the meaning

    of the specification, drawings and shall have right to reject or accept any

    work or material which in his assessment is not complete to meet the

    requirements of this specification and / or applicable national and / or

    international standards mentioned elsewhere in the specification.

    1.4 Whenever material or item is specified or described by the name of a

    particular brand, manufacturer or trade mark, the specific item shall be

    understood as establishing type, function and quality desired. Other

    manufacturer's products may also be considered provided sufficient

    information is furnished so as to enable the PURCHASER to determine

    that the products are equivalent to those named.

    1.5 GENERAL INFORMATION ON ELECTRICAL & CONTROL VOLTAGES:

    1.5.1 Auxiliary electrical equipment shall be suitable for operation on the following supply

    system:

    Spring charging motor, Closing & Tripping : 110 volts D.C. supply

    Auxiliary supply : 240 volts, 1 phase 50 HZ A.C supply.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    1.5.2 The above voltage may vary as follows. All devices shall be suitable for continuous

    operation over the entire range of voltages.

    A.C. Supply variation:

    i) Voltage variation : 10%

    ii) Frequency variation : 5%

    iii) Combined voltage and

    iv) Frequency variation : 10%

    D.C. Supply voltage variation :-

    i) Closing device : - 15% to + 10%

    ii) Tripping device : - 30% to + 10%

    1.5.3 Two sources of each of the above supplies i.e. 240 volts AC, 110 volts DC will be made

    available by the purchaser at one terminal point. The vendor shall include adequately

    rated control transformers for any other voltage levels are required. Vendor's scope shall

    include distribution beyond the points of supply including interconnecting cables,

    terminal blocks etc.

    1.5.4 Reference temperature for design of electrical equipment / devices:

    50 Deg C for tropical regions, all marine conditions and polluted industrial atmosphere

    with 100 percent humidity. However, the maximum temperature and humidity shall be

    assumed not occurring simultaneously.

    1.5.5 SCOPE OF WORK:

    This specification covers design, manufacturing, fabrication, assembly, cleaning, painting,

    testing, packing and supply of 33 KV MRSS HT Switch Board as per the enclosed

    Technical Specification & Single Line Diagram.

    1.5.6 SCOPE OF SUPPLY:

    Any item not specifically mentioned above but is essentially required for proper and

    successful operation of the systems shall be included in the scope of the bidder.

    1.5.7 SCOPE OF SERVICES:

    For Supervision of erection, testing and commissioning of the equipment of the equipment

    will be done by the supplier, if required.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2. TECHNICAL SPECIFICATION FOR 33 kV SWITCHBOARD

    2.1 Introduction

    2.1.1 This specification covers the design, manufacture, supply & supervision of

    erection, pre-commissioning & commissioning of 33 kV indoor type

    switchboard incorporating draw out vacuum circuit breakers.

    2.1.2 The 33 kV switchboard shall be capable of continuous and reliable

    operation at the full load rating specified where continuity of operation is

    of prime importance. Workmanship shall be the highest grade and the

    entire construction in accordance with the best modern practice. The HT

    switchboard shall be capable of withstanding the severest stresses likely to

    occur in actual service and of resisting rough handling during transport.

    2.1.3 The HT switchboards shall have incoming and outgoing feeders as

    specified elsewhere in the enclosed single line diagram.

    2.1.4 Circuit breaker shall be suitable to withstand inrush magnetising currents

    of transformers and capacitor bank ON and OFF. Also circuit breakers

    shall be used for synchronizing applications as specified.

    2.2 Specific Requirements: 2.2.1 HT Switchboard:

    Rated voltage

    :

    33 kV, 3 phase

    Rated frequency

    :

    50 Hz

    Fault level

    :

    31.5 kA for 3 sec

    Degree of Protection

    :

    IP4X

    Highest System Voltage

    :

    36 kV

    One minute Power Frequency Withstand voltage

    :

    70 kV(rms)

    1

    1.2/50 micro second impulse

    :

    170kV (peak)1

    Clearance in air

    :

    As per IS/IEC

    Busbar Material

    :

    High Conductivity Electrolytic

    grade Copper

    Busbar Rating under natural cooled

    condition

    :

    2000A

    1 The insulation level of the synchronization breakers shall be as recommended by IEC:61936-1:2002 and

    IEC:60694:2001

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    Design Ambient

    :

    45 C

    Maximum Busbar Temperature

    :

    As per IEC

    Cable Entry for Outgoing feeder

    :

    Bottom of the panel

    Cable Sizes

    :

    As specified in the SLD.

    Class & VA Burden rating for CT/ PT

    Shall be as specified in the

    SLD.

    Communication protocol for Relays

    :

    IEC61850

    Communication protocol for meters

    :

    PROFIBUS / IEC61850

    Earthing System

    :

    Resistance Earthed / Unearthed

    2.2.2 Breaker Requirements:

    Description

    Outgoing Feeder Circuit

    Breaker

    Design ambient

    :

    45 C

    Natural Cooling Condition

    :

    Shall not be less than 2000 A of in panel rating

    Forced Cooling Condition

    :

    Not applicable

    Rated Voltage

    :

    33 kV, 3 phase

    Rated frequency

    :

    50 Hz

    Fault level

    :

    31.5 kA for 3 sec

    Circuit Breaker Type

    :

    Vacuum

    Highest System Voltage

    :

    36 kV

    One minute Power Frequency

    Withstand voltage

    :

    70 kV (rms)

    2

    1.2/50 micro second impulse

    :

    170 kV (peak)2

    Clearance in air

    :

    As per IS/IEC

    Operating Duty

    :

    O-0.3s-CO-3 min-CO

    Rated short circuit breaking capacity

    :

    31.5 kA

    Dynamic Rating

    :

    78.75 kA

    Rated short circuit making capacity

    :

    78.75 kA

    DC current

    :

    14.25 kA (minimum)

    Rated Asymmetrical breaking capacity

    :

    34.57 kA

    Control Voltage

    :

    110 V DC, with single

    independent source

    2.3 Standards

    The design, manufacture and testing of various equipments covered by

    this specification shall comply with the latest issue of the following

    standards:

    2 The insulation level of the synchronization breakers shall be as recommended by IEC:61936-1:2002 and

    IEC:60694:2001

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    IS:375 -

    IS:694 -

    IS:722 -

    Marking and arrangement of switchgear busbars

    PVC insulated cable with copper conductor for

    voltages upto 1100 V

    Integrating meters

    IS:1248 - Electrical indicating instruments

    IS:13118 - General requirements of circuit breaker for

    voltages above 1000V.

    IS:2705 - Specifications for current transformers

    IS:3156 - Specifications for voltage transformers

    IS:3231 - Electrical relays for power system protection

    IS:3427 -

    IS:6865 -

    IEC 44 -

    IEC 255 -

    IEC 1036 -

    IEC 60044-1 -

    IEC 60041-2 -

    Metal enclosed switchgear and control gear (1 kV

    to 52 kV)

    Control switches and push buttons

    Instrument Transformers

    Electric Relays

    Static Meters

    Current Transformers

    Potential Transformers

    IEC 62271-200- Circuit Breakers

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.4 General Requirements

    2.4.1 Construction

    2.4.1.1 The switchgear shall be metal clad, free floor standing, totally enclosed, dust and vermin

    proof with draw out type circuit breakers. Vertical units shall be assembled to form a

    continuous line up of uniform height.

    2.4.1.2 The panel structure shall house the components contributing to the major weight of the

    equipment such as circuit breaker, main horizontal busbars and other of the components is adequately supported without deformation or loss of alignment during transit or during operation.

    2.4.1.3 Each unit of the switchgear shall have necessary internal sheet metal barrier to form separate compartments for buses, instruments, relays, cable connections etc.

    2.4.1.4 Adequate barriers shall permit personnel work safely within an empty compartment

    with the busbars energised. Checking and removal of components shall be possible without disturbing the feeder. All auxiliary equipment shall be easily accessible to facilitate their operation and maintenance. It shall be possible to set all relays and measuring instruments without de-energising the switchgear.

    2.4.1.5 All doors and openings shall be fitted with dust excluding neoprene gaskets with

    fasteners designed to ensure proper compression of the gaskets.

    2.4.1.6 When covers are provided in place of doors, generous overlap shall be assured b e t w e e n sheet steel surfaces with closely spaced fasteners to preclude the entry of dust.

    2.4.1.7 The panels shall have a rear cable chamber housing the cable and connections the design shall ensure generous availability of space for easy installation and maintenance. Cabling and adequate safety for working in one section without coming into accidental contact with live part in an adjacent section.

    2.4.1.8 HT switchboard shall be constructed only of materials capable of withstanding the

    mechanical, electrical and thermal stresses, as well as the effects of humidity, which are likely to be encountered in normal service. All insulating materials used in construction of the equipment shall be non-hydroscopic material, duly treated to withstand the effects of high humidity high temperature tropical ambient service conditions. Creepage distances shall comply to those specified in relevant standards.

    2.4.1.9 Each panel shall be provided with space heater to prevent condensation and the same

    shall be equipped with differential thermostat to automatically cut in and cut out the heater so as to maintain interior temperature of 5 Deg.C. above the ambient and should have manual disconnect switch.

    2.4.1.10 The height of the panel shall not be more than 2700 mm. The total depth of the panel

    shall be adequate to cater for proper cabling space.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.4.1.11

    2.4.1.12

    2.4.1.13

    2.4.1.14

    2.5

    2.5.1

    2.5.2

    2.5.3

    2.5.4 2.5.5

    Provision shall be made for permanently earthing the frames and other

    metal parts of the HT switchboard through a copper earth busbar running

    throughout the full length of the switchboard at the bottom. Drawout type

    switching units shall have sliding ground contact. It shall be possible to

    earth the switchboard at two independent points on either ends for

    connections to the external earthing network of the plant.

    The panel shall have provision to extend on either direction of the board at

    a future date (2 Feeders on LHS & 2 Feeders on RHS). The Ends of

    busbars shall be suitably drilled for this purpose.

    Suitable eye bolt for lifting of panel shall be provided. On removing the

    eye bolts no holes offering access to panel shall be provided.

    Circuit breaker closing, tripping, control and indication power will be

    connected from single sources of 110V DC supply.

    Busbars

    The busbars shall be epoxy moulded sleeved.

    The busbar chamber shall be totally maintenance free.

    The switchboard shall comprise 3 phase main busbars which shall extend

    through all units of the switchgear line up. The busbar mating surface

    shall be tinned. High tensile bolts and spring washers shall be provided at

    all busbar joints and busbar joints shall be silver plated. The busbar shall

    be of uniform section throughout and shall be sized to continuously carry

    the rated current without exceeding the maximum temperature rise, as

    recommended by IEC over the maximum ambient temperature as

    specified. Busbars shall be colour coded for easy identification of

    individual phases. The SUPPLIER shall submit temperature rise test

    report for the substantiating the selected size of busbars.

    Busbars shall be supported at regular intervals and both, busbars and

    supports shall be adequately sized and braced to withstand short circuit

    level without deformation. All bus supports shall be non-carbonizing

    material resistant to acid alkalies and shall have non-hydroscopic

    characteristics.

    For long busbars suitable expansion joints shall be provided. Thermal

    design of the busbars shall be based on the installation of the switchgear in

    poorly ventilated condition as per IS Thermal Design.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.5.6 Busbars shall be housed in a separate chamber which shall be accessible

    for inspection only with special tools.

    2.5.7 Insulated busbars for control supply of 110V DC & 220V AC through out

    the panel shall be provided.

    2.6 Circuit Breakers

    2.6.1 Circuit breakers shall be triple pole, vacuum circuit breaker, drawout type.

    2.6.2 The breakers shall have motor operated spring charged mechanism with

    anti-pumping contactor. The control circuit shall be suitable for local as

    well as remote control. Provision for manual operation shall also be

    available.

    2.6.3 The power supply voltage for the spring charge motor shall be 110V DC.

    2.6.4 The breaker sockets and plugs should be heavily silver plated. The

    breaker shall have adequate auxiliary contacts required by plant control

    schematics. Additional 30% spare contacts (Minimum 10NO + 10NC) for

    future use shall be provided and wired upto Terminal Boxes. Auxiliary

    relays should be used to multiply the contacts.

    2.6.5 All spare contacts of breakers shall be wired upto terminal blocks.

    2.6.6 The operating mechanism shall be robust design with a minimum number

    of linkages to ensure maximum reliability. The operating mechanism

    shall be such that the breaker is at all times free to open immediately the

    trip coil is energised. It is to be ensured that all the three poles open/close

    in unison to avoid any eventuality of single phase operation of the

    generator. All controls shall be suitable for 85 % to 110 % for closing of

    110VDC and 70% to 110 % for tripping of 110 V DC supply.

    2.6.7 Two (2) numbers of tripping coils shall be used for tripping the circuit

    breaker and shall be planned with 110V DC supply along with capacitor

    tripping unit for all breakers. The DC tripping circuit shall be provided

    with capacitive tripping device additionally to facilitate positive operation

    of the DC tripping coil in the event of failure of DC supply to the tripping

    circuit.

    2.6.8 Breaker shall be tripped through any of the trip coils available in the

    breaker through TNC switch / remote tripping impulse / master trip

    operated signal during normal operation.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.6.9 The breaker shall have the distinct positions indicating:

    `Service ' position: With main auxiliary contacts connected

    `Test' position : With power contacts fully disconnected and control

    circuit contacts connected

    `Isolated' position: With

    fully

    both power and control circuit contacts

    disconnected

    2.6.10 The trolleys of the circuit breaker shall be so inter-locked that,

    - It shall not be possible to isolate it from the inserted position or

    to insert it in from the isolated position with the breaker closed.

    - The circuit breaker can be closed only when it is in one of the three

    positions or when it is fully out of the panel.

    - It shall not be possible to open the breaker compartment door

    unless the breaker is drawn to the isolated position or test position.

    - Inadvertent 'pushing in' of the drawout circuit breaker in service

    position, with auxiliary circuit plug not in the position shall be

    prevented.

    2.6.11 The breaker shall be able to function even under condition of phase

    opposition that may arise due to totally out phase synchronisation as per

    relevant IS or IEC standard.

    2.6.12 The tips of the main contact shall be adequately silver plated to withstand

    arcing.

    2.6.13 The operating mechanism shall be electrically controlled spring operated.

    2.6.14 Mechanism shall have anti pumping and trip free circuitry.

    2.6.15 Local arrangement for operating the breakers both electrically and

    mechanically shall be provided.

    2.6.16 The breaker trolley shall remain inside the cubicle even in the draw out

    position.

    2.6.17 Automatic safety shutters shall be provided to ensure the inaccessibility of

    live parts after the breaker is drawn out.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.6.18 The circuit breaker trolley shall be provided with a heavy duty self

    aligning earth contact which shall make before and break after the main

    isolating contacts during insertion into and withdrawal from the service

    position of the breaker. Even in the isolated position positive earthing

    contact should exist.

    2.6.19 Circuit breakers of identical rating shall be inter-changeable.

    2.6.20 Circuit breaker shall have provision for manual re-charging.

    2.6.21 ON / OFF indicator and number of operation centre shall be provided.

    2.6.22 Mechanical lock along with cover shall be provided for closing lever /

    knob for the circuit breaker, which are identified for synchronising

    purpose.

    2.7 Earthing Trolleys

    2.7.1 Bus earthing and cable earthing trolleys (one number each per rating) shall

    be provided along with each switchboard. Necessary safety interlocking

    shall be incorporated in the bus earthing trolley to avoid insertion of

    trolley, when the bus is live. Similarly, suitable interlock shall be

    provided to avoid insertion of cable earthing trolley, when the cable side is

    live (i.e.) supply is extended from remote for incomer feeders. These

    interlocks shall be of electro-mechanical type. Closing of the source

    incomer breakers shall be inhibited when the Bus earthing trolley is in

    inserted position by providing a suitable mechanical key interlock.

    2.8 Current Transformers

    2.8.1 The current transformer shall be cast-resin insulated type of adequate

    capacity and proper characteristics on secondary as specified. The current

    density should not be more than 1000 amps/sq.inch.

    2.8.2 CTs shall withstand stresses originated from short circuit. They shall have

    ratios, output and accuracy as specified in the drawings. Single core type

    CTs shall be provided for 2000 Amps rating breaker feeders. CTs in other

    feeder shall be of multicore type.

    2.8.3 CTs shall be preferably of bar primary type, they shall be mounted on the

    switchboard stationary part and suitable approach for maintenance shall be

    provided.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.8.4 The secondary CT leads from all panels should be terminated on the front

    of the board on easily accessible shorting type terminal connectors so that

    operation and maintenance can be carried out when the panels are in

    service.

    2.8.5 CTs shall be suitable for continuous loading of 120% of rated current.

    2.8.6 CTs shall be subjected to heat run test, if the same has not been type tested

    in the last three years.

    2.8.7 Single CBCT shall be considered in at incoming / outgoing feeders

    covering all runs of cables as indicated in the single line diagram.

    2.8.8 The Burden indicated for the current transformers shall be at lowest

    tappings.

    2.9 Potential Transformer

    2.9.1 The potential transformer shall be cast-resin insulated type. It shall be

    draw out type and easily accessible so that the same can be attended to or

    replaced when the panels are in service condition.

    2.9.2 The potential transformers shall be protected

    primary side and MCBs on secondary side.

    outputs and accuracies specified.

    through HRC fuses on

    They shall have ratios,

    2.9.3 The draw out mechanism shall disconnect the primary connection before

    the PT or its primary fuses become accessible.

    2.9.4 All PTs shall be single phase type. The voltage factor shall be 1.2 times

    continuous and 1.9 times for 8 hours.

    2.9.5 The Line PTs will be mounted on the top of the respective panel and

    separate cubicle will be provided for bus PT.

    2.10 Integrating Meters

    2.10.1 Integrating meters of the Trivector or equivalent types capable of

    indicating all phase instantaneous parameters and recording kWH,

    kVARH and kVAH directly shall be provided.

    2.10.2 These shall be suitable for 3 phase, 4 wire 50 Hz circuits with unbalanced

    loading and with two sets of elements connected to current and potential

    transformers of specified ratio.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.10.3 The trivectormeter shall be of digital type, class 0.2 or better with

    communication port, RS485 interface with the protocol as specified in

    the specific requirement of the switchboard, for hooking up to PC /

    DCS.

    2.10.4 The Trivector meters available all the incoming and outgoing feeders shall

    have import/export facility.

    2.11 Indicating Lamps

    2.11.1 Indicating lamps shall be of cluster LED type low watt consumption,

    provided with series resistor where necessary and with translucent lamp

    covers. Bulbs and lenses shall be easily replaceable from the front.

    2.11.2 Following indicators are required on the panel having lens colours as

    follows:

    Breaker ON : RED

    Breaker OFF : GREEN

    Auto trip : AMBER

    Trip Circuit healthy : WHITE

    Spring Charged : BLUE

    Breaker in Test position : WHITE

    Breaker in Service Position : RED

    2.11.3 Potential Free contacts for the following function shall be provided in the

    synchronising breaker panels for hooking up to synchronisation panel:

    a) Breaker ON

    b) Breaker OFF

    c) Spring Charged

    d) Auto Trip

    2.11.4 Live line indications with proven design shall be provided at incoming

    and outgoing sides of all the feeders and bus bars. No PT supply shall be

    used for the above purpose.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.12 Relays

    2.12.1 All protective relays shall be back connected, draw out type, suitable for

    flush mounting and fitted with dust tight covers. All relays shall be

    mounted on the front of the panel and shall be specified as per

    requirement. The current and the voltage coils shall be rated as specified.

    2.12.2 All relays shall have built-in flag / indicator to indicate operation. All

    tripping relays shall be suitable to operate on the specified DC voltage.

    2.12.3 Feeder & transformer protection relays shall be of numeric /

    microprocessor type with self diagnostic facility, RS 485 communication

    port with protocol as specified for interfacing with PC / DCS, software for

    data downloading & configuration. Feeder / transformer protection relays

    shall have IDMT / highset overcurrent & earth fault elements. Alpha

    numeric display shall be available for the relays and all fault data

    shall be displayed in natural language, without needing to refer codes

    / manuals.

    2.12.4 Separate sensitive earth fault relay shall be provided for the feeders as

    called for in the single line diagram. Any case this relay can not be

    combined with the main protection of the feeders.

    2.12.5 Master trip relay, trip circuit supervision relays and auxiliary relays shall

    be provided, wherever specified. All the auxiliary relays shall be

    electromagnetic type.

    2.12.6 All spare contacts of relays shall be wired up to Terminal Blocks.

    2.13 Control Switches and Push Buttons

    2.13.1 Control switches shall be of the heavy duty rotary type with name plates

    clearly marked to show the operation. They shall be semi-flushed

    mounting with only the front plate and operating handle projecting.

    2.13.2 Circuit breaker control switches shall be of the spring return to neutral

    type, while local / remote selector switches and instrument selector

    switches shall be of the stay-put type.

    2.13.3 Emergency push button shall be provided for each circuit Breaker in the

    panel

    2.13.4 Mush-room type emergency push button shall be provided.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.14 Internal Wiring

    2.14.1 Internal wiring and inter-panel wiring for all circuits shall be carried out

    with 1100/660 V grade, single core, multi strand, PVC insulated copper

    conductor wire of minimum 2.5 Sq.mm for other control circuit.

    2.14.2 The wiring shall be neatly bunched adequately supported and properly

    routed and terminated in the respective terminals with suitable lugs. There

    shall not be more than two wires connected at a terminal.

    2.14.3 Wires shall be identified by numbered ferrules at each end. The ferrules

    shall be of ring type and non deteriorating material.

    2.14.4 All control circuits shall have MCBs mounted in front of the panel and

    shall be easily accessible.

    2.15 Terminal Blocks

    2.15.1 Terminal blocks for the LT connections shall be of 660V grade of stud

    type and of adequate current rating with minimum 2.5Sq.mm.

    2.15.2 The insulating barriers shall be provided between adjacent terminals.

    Provision shall be made for label inscription on terminal block. Cables

    should never be terminated directly on components. Provision shall be

    made for CT terminals shorting links, remote ON/OFF pushbutton, remote

    ON/OFF indication and remote ammeter. 30% spare terminals shall be

    provided on each terminal block.

    2.16 Cable Termination

    2.16.1 The HT switchboard shall be designed to facilitate outgoing power

    connection through XLPE insulated armoured cables with bottom entry.

    2.16.2 Ample space for connection of these cables shall be provided at the rear of

    the switchboard. The cable termination arrangement shall be of adequate

    size and design to receive the required number of cables as specified.

    Proper cable clamping arrangement shall be provided. Minimum height

    of 700mm shall be maintained between gland plate and the terminals

    for the HV cables.

    2.16.3 Detachable gland plate of adequate thickness shall be provided for the

    cable entry into the panel. Sufficient space shall be provided to avoid

    sharp bending and easy connection. Gland plates to be made up of non-

    magnetic material, wherever single core cable are used.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.16.4 Suitable shrouds shall be provided to prevent accidental contact with live

    outgoing terminations of other feeders while carrying out maintenance on

    one feeder.

    2.17 Labels

    2.17.1 Name plates of approved design shall be provided to represent circuit

    designation for each feeder. Material for name plates shall be anodised

    aluminium. They shall be firmly secured with fasteners.

    2.18 Painting

    2.18.1 All metal surfaces shall be chemically cleaned, degreased and pickled in

    acid to produce a smooth clean surface, free of scale, grease and rust.

    2.18.2 After cleaning, phosphating and passivation treatment, the surface shall be

    given two coats of zinc rich epoxy primer and baking in the oven.

    2.18.3 After primer, it shall be given two coats of epoxy paint, shade RAL 7032,

    in semi matt finish. Sufficient quantity of touch up paint shall be

    furnished for application at site

    2.19 Tests

    2.19.1 The 33 kV switchboard shall be tested for routine tests as per the relevant

    IS / IEC.

    2.19.2 All the panels shall be tested in assembled condition

    2.19.3 The routine tests shall be carried out in the presence of PURCHASER /

    CONSULTANT.

    2.19.4 Type test certificates having conducted in the last three years shall be

    submitted for similar rating, type of the switch board and circuit

    breakers for review. In case the above is not available, the

    SUPPLIER shall have to conduct the type tests as per IEC/IS with out

    affecting delivery schedule of the switch board without cost to

    PURCHASER.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.20 2.20.1 2.20.1.1

    2.20.1.2

    2.20.1.2.1

    2.20.1.2.2

    2.20.1.2.3

    2.20.1.2.4

    2.20.1.2.5

    2.20.1.2.6

    2.20.1.2.7

    2.20.1.2.8

    2.20.2

    2.20.2.1

    2.20.2.2

    List of Documents / Drawings to be Submitted Drawings / Documents required along with the Bid The BIDDER shall submit in their Technical BID, drawings, diagrams

    and all such information which are necessary to fully understand the offer

    both technically and commercially.

    As a minimum requirement the following information shall be supplied

    with the technical bid in sufficient detail to fully describe the scope of

    work and the services offered:

    Filled in Bidder Credentials

    Filled-in data sheets and schedules.

    Feeder wise Dimensioned General Arrangement Drawings showing

    the physical location of all the components for HT Switchboard

    Bill of quantities with type references.

    Fish plate details.

    Quality Assurance Plan.

    Catalogues of all equipment.

    List of sub-suppliers.

    Drawings and information required from Supplier during Contract

    Stage

    The drawings and documents to be furnished by the SUPPLIER after the

    award of the contract shall include but not limited to the following. A

    drawing / document submission schedule clearly identifying the

    documents to be submitted and the purpose of the submission (for

    information, approval etc., as elaborated elsewhere in this document) shall

    be furnished after discussions and in consultation with the

    CONSULTANT / PURCHASER.

    Detailed time schedule in the form of network or bar chart for the design,

    manufacture, delivery, erection, testing and commissioning period with

    critical milestone activities and other important intermediate dates for

    uninterrupted progress of the project.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.21.2.1 The following drawings and documents shall be compiled in a single set

    and submitted for approval:

    Filled-in revised technical data sheets.

    Quality Assurance Plan.

    List of manufacturers and specification of all standard equipment.

    Catalogues of all equipment.

    Connection diagram for all units (like incomer, outgoing feeders,

    breaker wiring diagrams, etc.).

    Schematic diagram for the complete switchboard.

    Fish plate details for the busbar connections.

    Terminal connection diagram of the main terminal boards.

    Temperature Rise test certificates for similar ratings conducted at

    any recognised institute.

    Sketches of the overall dimensions of the board / busduct - plan,

    elevation and section views clearly showing the bus size.

    Typical internal arrangement drawings for all types of feeders, showing clearly the dimensions of components / devices and

    clearances.

    Plan and sectional layout with detailed bill of quantities for the

    busduct and its accessories.

    Brand names of all components incorporated in the boards, etc.

    Marshalling TB schedule as per the required format.

    Guaranteed technical particulars for the critical components.

    Certificates of tests giving the results of tests conducted as per the appropriate standards on similar switchboard and interior

    components.

    Shipping dimensions of the board / busduct and its weight - gross

    and net (without packing).

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    Test certificates and inspection reports of all equipment.

    Other drawings and documents as indicated in various sections of

    this document.

    2.21.2.2

    2.21.2.3

    2.21.2.4

    2.21.2.5

    Erection manuals and installation procedures for all equipment.

    Operation and maintenance manuals for all equipment and systems.

    'As-Built' drawings.

    CD containing all final drawings and documents.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.21.2.6 Each drawing / document shall have a title block consisting of the

    following:

    Project :

    Customer :

    Consultant :

    Title :

    Drg. No. :

    Rev.No. and Details :

    2.21 List of Operational Spares

    The scope of supply for this package shall include the items as mentioned

    below:

    a. Three (3) Numbers of 110V DC Tripping Coil for each type of

    breaker 1 Lot

    b. Two (2) number of spring charging Motor for each type of breaker

    1 Lot

    c. One Set of PT Fuses (3 nos) 1 Lot

    d. Five (5) Sets of Indication lamps for each colour 1 Lot

    e. Three (3) Sets of fixed contacts with shrouds in each rating of

    breaker 1 Lot

    f. Three (3) sets of main contacts with shrouds in each rating of

    breaker 1 Lot

    g. Two (2) sets per rating of Auxiliary contacts for breakers 1 Lot

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    2.22 Make of Components

    1. HT Breaker( VCB) BHEL/Siemens/ABB/Areva/Crompton

    2. Vacuum Contactor BHEL/Siemens/ABB/Areva/Crompton

    3. HRC Fuse. L & T /GE/ Siemens

    4. Timer L & T /GE/ BCH/ Schneider/EAPL

    5. Pushbutton L & T / Siemens/ BCH/ Vaishnu/ GE

    6. Indication Lamp Vaishnu/ L&T/ Siemens/ BCH/Emco

    7. Current Transformer AE / Kappa / PRAGATHI

    8. Indicating Meters Enercon/AE / Rishav (L&T) / IMP/ SCHNEIDER

    9. Selector Switch- Auto / Manual Kaycee / Salzer / Vaishnu

    10. Power Terminal Connectwell / ACDC/Elmex

    11. Control Terminal Elmex / Connectwell / ACDC

    12. Power & Control wire. Finolex / KDK

    13. Socket (Crimping type) Dowells / UML/ Clippon

    14. Transducer Enercon/AE /ABB

    15. Potential Transformer AE / Kappa

    16. T N C Switch. Alstom / Salzer

    17. MCB MDS / Siemens/ GE

    18. Hooter. Kheraj / Local

    19. Relay Alstom / ABB/L&T

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    3.0 CLEANING AND PACKING:

    3.1 CLEANING

    Surface of all parts shall be cleaned to remove scale, dirt, oil, water, grease and other foreign

    objects prior to final assembly of the equipment.

    3.2 PACKING

    The equipment after acceptance by inspecting agency, if any shall be shipped to site duly

    packed in wooden crate. The equipment shall be wrapped in polyethylene sheet before being

    placed in crate or wooden box. All crates shall have skid bottom for handling. All lose parts

    of the equipment shall be properly boxed. The consignee address to be clearly marked on the

    crate. The wooden crate or box shall be sturdy so that it is not damaged during transportation

    or handling.

    3.3 DELIVERY:

    Delivery period of the equipment including all its accessories specified in the specification

    shall be strictly follows as per order. Timely delivery of the equipment is the essence of

    contract.

    3.4 GUARANTEE:

    The supplier should be responsible for correctness of rating / workmanship and performance

    of the equipment. The supplier / bidder shall provide a guarantee covering rectification of all

    detects in the design, materials and workmanship of all items provided under the

    specification for a period of 12 months from the date of satisfactory commissioning and 18

    months from the date of delivery whichever period is later. During guarantee period any

    defects found with the parts or equipment will be free replacement or repairing of the

    defective item. The guarantees for performance shall cover individual items and the system

    as a whole.

    3.5 SPARES: 3.5.1 COMMISSIONING SPARES

    All spares required for commissioning of the 33KV H.T. Switch Board and for its efficient

    operation until provisional acceptance after demonstration of satisfactory performance in

    accordance with the guarantees are in the scope of supply.

    3.5.2 SPARES FOR TWO (2) YEARS OF NORMAL WORKING

    Bidder are to submit purchaser a list of recommended spares for two years of normal

    operation of 33 KV H.T. Switch Board.

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    3. DATA SHEETS AND SCHEDULES

    SL. DESCRIPTION

    3.1 BIDDER INFORMATION

    3.2 BIDDER CREDENTIAL

    (to be submitted along with the offer)

    3.3 33 kV SWITCHGEAR

    3.4 SCHEDULE OF DEVIATIONS

    PAGE NO.

    II.21

    II.22

    II.23

    II.26

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    Data Sheet No.

    3.1

    Sheet No.: 1 / 1

    Title :

    BIDDER INFORMATION

    S.No

    Description

    Unit

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    Bidder's complete Company Name and Postal Address

    Tender Reference and Date

    Proposal Validity (No. of Days)

    Whether particulars of past similar experiences

    furnished?

    Name and particulars of Collaborator, if applicable

    Equipment warranty period from the date of

    commissioning

    Whether furnished offer as per specification?

    Whether list of deviations / exclusions taken furnished?

    Whether all taxes & duties included in the price

    schedule?

    Whether offer for 2 years' operational spares included?

    Whether all commissioning spares included in base

    offer?

    Whether a project schedule with commissioning date

    is enclosed?

    Whether equipment guarantee schedule furnished?

    Whether the drawings required as per specification

    enclosed?

    Whether quality plan enclosed?

    Signature Of The Bidder :

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    Data Sheet No.

    3.2

    Sheet No.: 1 / 1

    Title :

    BIDDER CREDENTIAL (to be submitted along with the offer)

    S.No

    Description

    Unit

    1

    2

    3

    4

    5

    6

    7

    8

    Manufacturing unit location

    No. of years in manufacture of MV / HV Switchboards

    Total No of MV / HV Switchboard supplied per year for last three

    Years a. 2007-08

    b.2008-09

    c.2009-10

    Turn-over of MV / HV Switchboard division for last three year

    in Rs. Crores a. 2007-08

    b.2008-09

    c.2009-10

    Whether Type Test Certificate Copies enclosed, conducted

    within the last three (3) years ?

    a. Temperature rise test certificates for 2000A rating

    b. Short time rating (31.5kA with Idc of min.30%) certificate

    In-panel rating for 2000A breaker at ambient of 45 Deg C?

    Confirm whether the submitted offer has any Deviations

    ( if Yes, kindly ensure that the schedule of deviations sheet

    is attached with the offer )

    Confirmation of circuit breakers for the intended application

    as specified in the clause no:2.2.2

    A

    Yes / No

    Yes / No

    Yes / No

    Yes/No

    Signature Of The Bidder :

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    Data Sheet No.

    3.3

    Sheet No.: 1 / 3

    Title :

    33 kV SWITCHGEAR

    S.No

    Description

    Unit

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    19.1

    19.2

    19.3

    Make

    Type of switchgear

    Voltage rating

    Rated Current

    Short time current

    Short time duration

    Max. temperature of busbar

    Continous current rating of busbars and busbar material

    Degree of protection

    Colour, finish and shade

    Busbar insulation

    1.2/50 micro sec.impulse

    1 min. power frequency

    Cable Entry

    o. of Incomer Feeders and Rating

    No. of Outgoings Feeders and Rating

    Whether Bus PT panel considered?

    Whether CTs, PTs, metering and protection provided as

    per drawing / specification?

    Breaker Details:

    Rated Voltage

    Rated short circuit breaking capacity

    Rated current

    kV

    A

    kA

    Sec.

    kV

    kV

    kV

    kA

    Amps

    kA

    19.4 Rated short circuit making capacity Signature Of The Bidder :

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    Data Sheet No.

    3.3

    Sheet No.: 2 / 3

    Title :

    33 kV SWITCHGEAR

    S.No

    Description

    Unit

    19.5

    19.6

    19.7

    19.8

    19.9

    19.10

    19.11

    19.12

    19.13

    19.14

    19.15

    19.16

    19.17

    19.17.1

    19.17.2

    19.17.3

    19.17.4

    19.17.5

    19.17.6

    19.17.7

    19.17.8

    Rated short circuit duration

    DC component of rated short circuit breaking current

    Rated assymetrical breaking capacity

    Rated lightning impulse withstand voltage

    Rated power frequency withstand voltage

    Drive

    Rated Operating Duty

    Rated Auto Reclosing Duty

    Rated No. of Operation at Rated Current

    Rated No. of Operation at Rated Short Circuit Current

    Mechanical life of Interrupter

    Mechanical life for Drive

    Operating Times

    Closing Time

    Spring Charging Time

    Opening Time / Contact parting time

    Arcing Time

    Break Time

    Dead Time

    Close-open Time

    Minimum command duration

    a. Opening

    b. Closing

    kA

    kV

    kV

    m sec

    Signature Of The Bidder :

  • RASHMI METALIKS LTD

    TECHNICAL SPECIFICATION OF 33KV IN DOOR SWITCH BOARD

    FOR 350 CUM MBF AT KHARAGPUR

    4

    .

    T

    E

    N

    D

    E

    R

    D

    R

    A

    W

    I

    N

    G

    Title :

    PRICE SCHEDULE

    Sl.No.

    Description

    Unit

    Total Price in Rs.

    I.

    1.

    a.

    b.

    c.

    d

    e

    f.

    2.

    3

    4

    5

    6

    7

    II

    1.

    2.

    3.

    III

    SWITCHBOARD

    Basic price of 33 kV Switchboard complete with CTs/PTs, etc.,

    as per enclosed drawings & Ex-works,including packing &

    forwarding charges

    33 kV Switchgear Panel as per Drg. Titled, "Single Line Diagram

    for 33 kV Switchboard", Drg. No: 2-27331-900-0468, Rev.0

    Supply of manufacturers recommended Commissioning Spares.

    Supply of manufacturers recommended Maintenance spares for two years Normal operation.

    Busbar Earthing Truck with necessary interlocks (2000A)

    Cable Earthing Truck with necessary interlocks (2000A)

    Cable Earthing Truck with necessary interlocks (1250A)

    Sub-Total (a to f)

    Excise Duty including education cess

    Sales Tax / CST / VAT

    Freight Charges upto Site

    Transit Insurance

    Total (2 to 6)

    Site Services

    Charges for switchboard commissioning and supervision of

    erection, Pre-commissioning and Commissioning

    (Minimum four (4) days & two (2) visits)

    Configuration & simulation of the numeric relay and training

    of plant engineers for operation & maintenance of the numeric

    relays (Minimum two (2) days & one (1) visit)

    Total (1 to 2)

    GRAND TOTAL (I.7 + II.3)

    1 Set

    1 Lot

    1 No.

    1 Lot

    1 No.

    1 No.

    Signature Of The Bidder :