TECHNICAL catalogue Heating Trench Fan coil VKN 2016_01_USA

Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

TECHNICAL catalogueHeating Trench Fan coil VKN

2016_01_USA

Page 2: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

37

The future of any heating systems is laying among solutions that work well with low temperature renewable sour-ces of heating energy, also by achieving a high level of system energy efficiency.

A solid technical background for this pro-duct – Fan Assisted Trench Heater type Turbo VKN5 has been created during a long term R&D process conducted to-gether with Warsaw Technical Univer-sity, Cracow Technical University, Lublin Technical University and Polish Scientific Academy, whereas its brand new desi-gn through innovative construction has achieved better hydraulic and heating characteristic.

During the process of optimization R&D, a high level heating emitter has been achieved, whereas it would raise an energy efficiency of the heat distribution throughout the building but also incre-asing an effectiveness of low tempera-ture heating systems since it has been working along with them.

Fan Assisted Trench Heater TURBO VKN5 has been design bearing in mind being suitable for spacious interiors having many glazed façades. Using a modern fan motor that will use low energy con-sumption feature and producing very low noise level would not distract any room occupants whilst precise and sim-plified control panel would enable easy and exact adjustment of desired tempe-

rature. Using an economical fan resulted with designing heating emitter producing more output with shorter adjustment reaction time. Additionally low thermal inertia and using advanced electronic control resulted an optional savings on running costs up to 20% in a heat season. Trench Heater Turbo VKN5 may be a per-fect solution for low supply temperature heating systems or high condensation wet installations, also is available in high supply pressure versions. Relatively low depth of trench required for such a he-ating emitter would allow to put trench heater in floor/ceiling space of any sto-rey. Evenly distributed heat in a room is one of many significant benefits of using trench heating.

TURBO VKN5

Trench Heater with 24V Fan TURBO VKN5

Page 3: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

38

ENERGY SAVINGS

Big advantage of this type of trench heaters is their high wor-king dynamic, quick coping with any changes in room thermal conditions, even warm air distri-bution throughout a room and low running costs.

Fan assisted trench heater is a perfect match for low temperatu-re water installations and heating systems.

FUNCTIONALITY

Trench heating distributes he-ating in perfect and discrete man-ner inside spacious and elegant interiors that having usually large glass façades. The only visible ele-ment of trench heating is an ele-gant grille that is composed into the floor that covers trench and coil elements.

Easy access through taking off a grille would enable easy access for cleaning or maintenance of a trench heating.

COMFORT

Trench heating are the ones that among many types of heating emitters would react in the quic-kest way for any changes of any thermal requirements in a room. This quick adaptation capacity allows to avoid any room overhe-ating.

Trench heating that are placed along the outskirts of a building would create a natural air curtain that may separate warm and cold air and prevents ‘floating’ cold air at the low, floor base level.

Using trench heating allows to eliminate of the moisture conden-sation from the surface of glass façades.

DURABILITY

There are high quality materials being used for designing copper aluminum coil, that also warrants corrosion resistance but also pro-tection against low quality of wa-ter from the boiler.

Due to using a raw steel with hot dip zm coating our heating emit-ters are usually more corrosion resistant.

Benefits of fan assisted trench heatingTURBO VKN5

Fan Assisted Trench Heaters Tur-bo VKN5 have been equipped with noiseless and energy efficient fans. Such a solution ena-bled a design of exceptionally ef- fective heating emitter that may be suitable to use in every single room.

Low thermal inertia and using advanced electronic control re-sulted an optional savings on operating costs up to 20% in a heat season.

Page 4: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

39

ww

w.v

eran

ocon

vect

or.co

.uk

The equipment of Verano heater

Construction of Verano heater

STANDARD equipment:• trench (casing) made of hot-dip galvanized steel sheet with zinc magnesium coating, powder painted in black RAL 9005,• copper and aluminium heat exchanger with air vent,• 24 V DC fan with EC motor,• fan cover,• connection space cover,• water connection 2xIT 3/4˝, • fixing anchors,• leveling brackets,

ADDITIONAL equipment:• trench (casing) painted in any RAL colour,• frame around the heater casing, L or F type made of natural aluminum, powder coated in RAL, anodized or can be done as wood imitation• aesthetic grille made of aluminum (natural, anodized or powder painted in any RAL color), natural wood (oak, ash, beech, merbau, jatoba) or stainless steel• installation cover to protect against damage during transport and installation

Fan coverAirflow targeting sheet

Heat exchanger (copper-aluminium)

Fixing anchorSupply and return connection for central heating

Additional hole

Holes for the connection pipes

Fan

Air ventHeat exchanger fixing element

Connection space cover

Trench (casing)

Leveling bracket

Grille

TURBO VKN5

Page 5: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

40

DimensionsTURBO VKN5

Heaters are also available with a non standard/custom lenghts (NS)

Heaters height of 2.5 inch are only available with SS grille, other will increase heater high to 3 inch

4 .75

3.52.5

,3 (3.

3)

47.5

)35.

2.53,

3(3.

Order code VKN5-H/W/L - fin type - in mm

Trench height (H) 2-1/2 to 4-3/4 inch

Trench width (W) 9-27/32 to 13-3/4 inch

Trench lenght (L) 29-1/2 to 139-3/4 inch

10.79-27/32

14.713-3/4

10.79-27/32

10.79-27/32

14.713-3/4

14.713-3/4

Page 6: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

41

TURBO VKN5

Any empty space in a ceiling/floor void may result louder work of fan motors of trench heating units. In order to avoid any lon-gitudinal deflection (deflection of trench casing borders) during concrete coating you should use some elements that will expand a trench casing. Inside Turbo VKN5 trench heating units there are leveling and mount brackets, that will also enable fitting trench casing into a floor.

Holders that would keep the coil tight during the transport, are secured by screws to the trench casing. Before any fitting work you should unscrew screws that hold heat exchanger frame and implicitly take off the fan from a trench. When trench casing is fitted you need to tighten screws.

In a trench casing there are four holes – two of them are put at the same height as mounting brackets of a heat exchanger, third hole is as a spare one (i.e. for any fit-ting in any connections or capillary etc.).

It is forbidden to lead any water connec-tions along the coil inside the trench ca-sing, as it may harm temperature float by limiting an air exchange inside a trench. Connections of coil have internal thread of

Installation manual

Concrete slab

Fixing anchor

Hard polystyrene

ConcreteFlooring

PE foil

Low expansion foam

GrilleDilatation e.g. cork

Frame e.g. type L

Leveling bracket

Leveling-fixing anchor

24V Fan Coil trench heating is assembled to keep coil room side and to keep fan motor on a window side. In order to avoid causing any heat loss through the floor space, trench casing should be thermo insulated from outside of the trench casing. When assembling fan assisted trench heating unit you should remember to provide proper acoustic insulation in a spa-ce created by a trench void and through all layers of a floor.

¾˝. It could be connected by straight or angled thermostatic valves. There should be free space remained (for any connections, valves etc.) for c.a. 7 inch. It is not possible to turn around the coil heat exchanger for 180° according to its instal- lation. As an alternative it is possible to manufacture, according to any demand a trench heater having right side (R) or left side (L) valve connection. The side of valve connection to the water installation sho-uld be specified once the specific trench heating is being ordered.

An example of assembly a fan assisted trench heater L≥76-3/4 inch (side view)

Page 7: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

42

TURBO VKN5 The control options of Verano trench heater fan assisted type VKN5

Thermostatic valve must be installed on the supply pipe, and the return valve on the return pipe. The electric-thermal servo-motor is installed directly on the thermostatic valve. Servo-motor must be con-nected to the room controller via a two-wire cable. Room controller allows you to open and close the valve and control the fan speed.

matically turns on and off the fan when the room temperature drops below or goes up the set tempe-rature on the thermostat. The controller with a buil-t-in sensor measures the temperature in the room and maintains its value at the set-point by control-ling the 2-position servo-motor.

Type TURBO VKN5

VKN5-7,8/25/L-12VKN5-7,8/35/L-14VKN5-9/25/L-12VKN5-9/35/L-14

Number of fan 1 2 3 4 5 6 7 8

Number of fan motors 1 1 1 2 2 2 3 3

Fan voltage [VDC] 24 24 24 24 24 24 24 24

Maximum current [A] 0,35 0,45 0,60 0,90 1,05 1,20 1,55 1,65

Maximum power consumption of EC

fan [W]8,4 10,8 14,4 21,6 25,2 28,8 37,2 39,6

VKN5-12/25/L-12VKN5-12/35/L-14

Number of fan 1 2 3 4 5 6 7 8

Number of fan motors 1 1 1 2 2 2 3 3

Fan voltage [VDC] 24 24 24 24 24 24 24 24

Maximum current [A] 0,45 1,00 1,10 2,00 2,10 2,20 2,65 3,20

Maximum power consumption of EC

fan [W]10,8 24,0 26,4 48,0 50,4 52,8 63,6 76,8

Trench length [inch]

Adjusting the heaters is done automatically by using the room controller The system auto-

29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

Page 8: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

43

TURBO VKN5

29-1/2

42-1/4

61

76-3/4

92-1/2

108-1/4

124

139-3/4

Page 9: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

44

TURBO VKN5

ON

1 2 3

Attention! Switch (from the opposite side of the controller) needs to be turned on position „1”

RDG 160 TG0

PE

G0G

G0 STP 63electro-thermal servo-motor

24V type VKN5+ red- blackwhite - stearing

M-01Fan

Fan

Room controller L

Q1

+24VGND

LNPE

L1

+24V REG GND REG GND +24V GND +24V GND+24V

L2 L3

FAN.REG.2

Z N GND +24V

Q2 Q3 Q4

Valve

24V type VKN5

VKN5 24V

M

Fan

Valve

M

M1~

GY

0-10V

G0

10A24VDC

max 1mAY50 Y10

max 1mAG

G

-

-

+

+

Electrical connection instruction

Wiring diagram for the RDG160T controller

Wiring diagram for the other controllers

Attention!

Electrical connections can be only done by appropriate licensed person and in compliance with electric standards.

Voltage can be turned on only after through checking of whole connection diagram.

It is prohibited to supply TURBO VKN5 directly from the main voltage of 120- 208V.

Page 10: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

Name Description Net price

Room temperature controller RF10BWireless digital temperature controller 4in1, white,

Room temperature controller RF10CWireless digital temperature controller 4in1, black,

Room temperature controller RF20BWireless digital temperature controller 4in1, white,

Thermostatic head SH Diamant White Cat. No. 600100001

Schlösser thermostatic heads with connection thread

M30x1.5 cooperate with all Schlösser valves

as well as withother valves with inserts

M30x1.5 and closing dimension

11,5 mm

Thermostatic head SH Diamant Plus White-Chrome Cat. No. 600100011

Thermostatic head SH Brillant White–Chrome Cat. No. 600200001

Thermostatic head SH Brillant White Cat. No. 600200002

Thermostatic head SH Brillant Chrome Cat. No. 600200003

Thermostatic head SH Brillant Satin Cat. No. 600200004

Thermostatic head SH Brillant Steel Cat. No. 600200005

Thermostatic head SH Brillant Gold Cat. No. 600200007

Control devices for trench VK 15, wall-mounted and floor-mounted - wireless system

Thermostatic heads for VERANO Floor-mounted and LST Wall-mounted Convectors

Central strip L08 Wireless central strip to control 8 heating zones

L04 module Expansion Module for wireless central strip L08, 4 zones

Thermostatic head GM10 Wireless thermostatic head M30x1,5, MINI version

Network Repeater RE 10 ZigBee Repeater Network

Network Coordinator C010 ZigBee Network Coordinator

B30 Internet Gateway Internet Gateway

Programmable TRV GP60 Fully programmable thermostatic head

flush-mounted, 120 V

flush-mounted, 120 V

wall-mounted, 120 V

Wireless digital temperature controller 4in1, black, Room temperature controller RF20C

wall-mounted, 120 V

Name Description

Page 11: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

Straight thermostatic valvetype Siemens VDN 215

Angular thermostatic valvetype Siemens VEN 215

Straight return valve type Siemens ADN15

Angular return valvetype Siemens AEN15

Straight thermostatic valvetype Schlösser 601200004

Angular thermostatic valvetype Schlösser 601200005

Straight return valvetype Schlösser 601300004

Angular return valvetype Schlösser 601300002

Thermal servo-motor type Siemens STA 73 or STA 73/00

Supply voltage 24 V AC/DC, 2-position control. STA73 with1 m connection cable, STA73/00 – need a separate cable

ASY23L…

Cable – type Siemens ASY23L…Connection cable for STA 73/00 control mode 0…10 V,

length of 2 m, 3 m and 5 m, 2-position control

Verano controller type VER-24B (White)The control mode 0 … 10V or ON / OFF (valve 24V).

Ability to work in heating or cooling mode.Operating modes: comfort, economical and security.

Verano controller type VER-24C (Black)The control mode 0 … 10V or ON / OFF (valve 24V).

Ability to work in heating or cooling mode.Operating modes: comfort, economical and security.

Room temperature controllertype Siemens RDG160T

Power supply 24 V AC control output 0…10 V DC, for fan with ECM (electronically commutated motor). Automatic or ma-

nual heating /cooling. Fan speed is activated

Rail Power Supply Z030-24VDC Input voltage 100-240V AC, Input frequency

50-60Hz, Output voltage 24V DC, Max output current 1,25A

Rail Power Supply Z060-24VDCInput voltage 100-240V AC, Input frequency

50-60Hz, Output voltage 24V DC, Max output current 2,5A

Rail Power Supply Z100-24VDC Input voltage 100-240V AC, Input frequency

50-60Hz, Output voltage 24V DC, Max output current 3,8A

Rail Power Supply Z120-24VDCInput voltage 100-240V AC, Input frequency

50-60Hz, Output voltage 24V DC, Max output current 5A

Rail Power Supply Z240-24VDCInput voltage 100-240V AC, Input frequency

50-60Hz, Output voltage 24V DC, Max output current 10A

Rail Power Supply Z480-24VDCInput voltage 100-240V AC, Input frequency

50-60Hz, Output voltage 24V DC, Max output current 20A

Control devices for VERANO Trench Heaters Fan Assisted type TURBO VKN5 and Climaconvectors type CVK2/CVKS and CVK4

Valve diameter 15 DN

Valve diameter 15 DN

Valve diameter 15 DN

Valve diameter 15 DN

Valve diameter 15 DN

Valve diameter 15 DN

Valve diameter 15 DN

Valve diameter 15 DN

Name Description

Page 12: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

46

CONNECTIONS TYPE

Side connection to be choosen

Standard Right – P, optional Left – L

Fan from the window side standard

ACCESORIES TYPEroll-up/linear/modular

Aluminium frame type L or F

Assembly cover on request

VKN5-7.8/25/L-12

CONNECTIONS TYPE

Connection threads IT 3/4˝ one-sided

Side connection to be choosen

Standard Right – P, optional Left – L

Fan from the window side standard

ACCESORIES TYPEroll-up/linear/modular

Aluminium frame type L or F

Assembly cover on request

TURBO VKN5

Please remember:

Order code for heaters type TURBO VKN5:VKN5-H/W/L - fin type

where:H - Trench height [mm]W - Trench width [mm]L - Trench length [mm]

Please remember:

Order code for heaters type TURBO VKN5:VKN5-H/W/L - fin type

where:H - Trench height [mm]W - Trench width [mm]L - Trench length [mm]

Trench lenght (L)Lenght of the heat exchanger ribbed part (Lhe)

Lk

Trench lenght (L)Lenght of the heat exchanger ribbed part (Lhe)Lk

2.5 to 3 inch height

Heaters height of 2.5 inch are only available with a SS grille, other will increase heater height to 3 inch

1/2

2-1/

23 (

) 0.7

42

10.79.8

10.7

9.8

2

Grille H=3/4 inch

1/2

2-1/

23 (

) 0.7

L [inch]29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4Ts/Tr °F

The standard heat output does not include 15% for piping pick-up, according to DIN EN 442-2: 2013 for room air temperature Ti = 65°F 1° corresponds to the control voltage of 4,5V, 2° corresponds to the control volt 7V, 3° corresponds to the control voltage 10V.

The standard heat output does not include 15% for piping pick-up, according to DIN EN 442-2: 2013 for room air temperature Ti = 65°F 1° corresponds to the control voltage of 4,5V, 2° corresponds to the control volt 7V, 3° corresponds to the control voltage 10V.

CONSULT SOFTWARE AND MDL FOR OTHER CONDITIONS

1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3°180/160 2223 3427 4832 4146 6830 9002 6148 9462 13346 8293 12763 18004 10196 15686 22130 12296 18922 26693 14328 22048 31105 16241 24991 35252170/150160/140140/120110/90 719 1108 1565 1344 2066 2915 1991 3066 4324 2687 4133 5831 3301 5081 7168 3983 6128 8648 4641 7140 10076 5261 8095 11420

7-7/85-7/8

14-3/413-3/4

14-3

/413

-3/4

9

5-7/

8

Grille H=3/4 inch

L [inch]Ts/Tr °F 29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

DIMENSIONS UNIT [inch]

Trench height (H) 2-1/2 (3)

Trench width (W) 9.8

Grille width (Wg) 10-3/4

Trench length (L) 29-1/2 ÷ 139-3/4

Fin type 12

VKN5-7.8/35/L-14 DIMENSIONS UNIT [inch]

Connection threads IT 3/4˝ one-sided

width (Wg) 13-3/4

Trench length (L) 29-1/2 ÷ 139-3/4

Fin type 12

Trench height (H) 2-1/2 (3)

Trench width (W) 14-3/4

Grille

Heaters height of 2.5 inch are only available with a SS grille, other will increase heater height to 3 inch

CONSULT SOFTWARE AND MDL FOR OTHER CONDITIONS

1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3°180/160 2905 4286 6605 5412 7986 12310 8027 11846 18253 10826 15979 24619 13305 19638 30263 16054 23689 36506 18707 27603 42542 24140 31286 48213170/150160/140140/120110/90 941 1388 2138 1753 2588 3986 2598 3836 5913 3509 5176 7976 4310 6359 9803 5200 7672 11826 6059 8941 13776 6868 10134 15617

Page 13: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

47

CONNECTIONS TYPE

Connection threads IT 3/4˝ one-sided

Side connection to be choosen

Standard Right – P, optional Left – L

Fan from the window side standard

CONNECTIONS TYPE

Connection threads IT 3/4˝ one-sided

Side connection to be choosen

Standard Right – P, optional Left – L

Fan from the window side standard

ACCESORIES TYPE

Grille H=18 mm roll-up/linear/modular

Aluminium frame type L or F

Assembly cover on request

ACCESORIES TYPE

Grille H=18 mm roll-up/linear/modular

Aluminium frame type L or F

Assembly cover on request

VKN5-9/25/L-12

VKN5-9/35/L-14

TURBO VKN5

Trench lenght (L)Lenght of the heat exchanger ribbed part (Lhe)

Trench lenght (L)Lenght of the heat exchanger ribbed part (Lhe)Lk

Please remember:

Order code for heaters type TURBO VKN5:VKN5-H/W/L - fin type

where:H - Trench height [mm]W - Trench width [mm]L - Trench length [mm]

Please remember:

Order code for heaters type TURBO VKN5:VKN5-H/W/L - fin type

where:H - Trench height [mm]W - Trench width [mm]L - Trench length [mm]

10.79.8

3-1/2 inch height

3-1/

23/

4

1/2

42

DIMENSIONS UNIT [inch]Trench height (H) 3-1/2

Trench width (W) 9.8

Grille width (Wg) 10-3/4

Trench length (L) 29-1/2 ÷ 139-3/4

Fin type 12

Trench width (W) 14-3/4

Grille (Wg) 13-3/4

Trench length (L) 29-1/2 ÷ 139-3/4

Fin type 12

14-3/413-3/4

1/2

7-7/85-7/8

14-3

/413

-3/4

9

5-7/

8

10.7

9.8

Lk 9

2

Ts/Tr °F 29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

Ts/Tr °F 29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

L [inch]

L [inch]

The standard heat output does not include 15% for piping pick-up, according to DIN EN 442-2: 2013 for room air temperature Ti = 65°F 1° corresponds to the control voltage of 4,5V, 2° corresponds to the control volt 7V, 3° corresponds to the control voltage 10V.

The standard heat output does not include 15% for piping pick-up, according to DIN EN 442-2: 2013 for room air temperature Ti = 65°F 1° corresponds to the control voltage of 4,5V, 2° corresponds to the control volt 7V, 3° corresponds to the control voltage 10V.

3-1/

23/

4

Trench height (H) 3-1/2 DIMENSIONS UNIT [inch]

1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3°180/160 2424 3751 5272 4511 6987 9821 6694 10363 14560 9026 13977 19638 11096 17179 24139 13387 20725 29121 15600 24152 33935 16241 27371 38460170/150160/140140/120110/90 784 1214 1708 1463 2264 3181 2169 3355 4716 2922 4528 6359 3594 5565 7819 4337 6714 9432 5053 7822 10994 6261 8866 12456

CONSULT SOFTWARE AND MDL FOR OTHER CONDITIONS

1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3°180/160 3171 4695 7212 5909 8746 13432 8763 12971 19917 11819 17496 26860 14530 21503 33018 17523 25943 39831 20422 30232 4641623146 34263 52605170/150160/140140/120110/90 1026 1521 2336 1913 2834 4351 2837 4201 6452 3829 5667 8702 10693 6966 12900 5677 8402 15034 6615 9793 10076 7498 11099 17039

CONSULT SOFTWARE AND MDL FOR OTHER CONDITIONS

Page 14: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

48

TURBO VKN5

CONNECTIONS TYPE

Connection threads IT 3/4˝ one-sided

Side connection to be choosen

Standard Right – P, optional Left – L

Fan from the window side standard

ACCESORIES TYPEroll-up/linear/modular

Aluminium frame type L or F

Assembly cover on request

VKN5-12/25/L-12

VKN5-12/35/L-14

CONNECTIONS TYPE

Connection threads IT 3/4˝ one-sided

Side connection to be choosen

Standard Right – P, optional Left – L

Fan from the window side standard

ACCESORIES TYPEroll-up/linear/modular

Aluminium frame type L or F

Assembly cover on request

10050

1812

0

12

Trench lenght (L)Lenght of the heat exchanger ribbed part (Lhe)Lk

Please remember:

Order code for heaters type TURBO VKN5:VKN5-H/W/L - fin type

where:H - Trench height [mm]W - Trench width [mm]L - Trench length [mm]

Please remember:

Order code for heaters type TURBO VKN5:VKN5-H/W/L - fin type

where:H - Trench height [mm]W - Trench width [mm]L - Trench length [mm]

DIMENSIONS UNIT [inch]Trench height (H) 4-3/4

Trench width (W) 9.8

Grille width (Wg) 10-3/4

Trench length (L) 29-1/2 ÷ 139-3/4

Fin type 12

4-3/4 inch height

10-3/49.8

4-3/

43/

4

1/2

Trench lenght (L)Lk Lenght of the heat exchanger ribbed part (Lhe) 9

2

Trench width (W) 14-3/4

Grille (Wg) 13-3/4

Trench length (L) 29-1/2 ÷ 139-3/4

Fin

Trench height (H) 4-3/4 DIMENSIONS UNIT [inch]

14-3/413-3/4

14-3

/4

13-3

/4

9

5-7/

8

7 - 7 / 85 - 7 / 8

L [inch]

Grille H=3/4 inch

Grille H=3/4 inch

L [inch]Ts/Tr °F 29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

Ts/Tr °F 29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

The standard heat output does not include 15% for piping pick-up, according to DIN EN 442-2: 2013 for room air temperature Ti = 65°F 1° corresponds to the control voltage of 4,5V, 2° corresponds to the control volt 7V, 3° corresponds to the control voltage 10V.

The standard heat output does not include 15% for piping pick-up, according to DIN EN 442-2: 2013 for room air temperature Ti = 65°F 1° corresponds to the control voltage of 4,5V, 2° corresponds to the control volt 7V, 3° corresponds to the control voltage 10V.

10.7

9.8

1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3°180/160 2660 4106 5749 4951 7652 10707 7338 11348 15880 9896 15307 21418 12167 18816 26328 14676 22700 31760 17104 26451 37008 19382 29976 41942170/150160/140140/120110/90 1773 1330 1862 3301 2479 3468 4893 3676 5146 6593 4958 6936 8109 6093 8528 9783 7352 10288 11403 8569 11986 12924 9708 13585

CONSULT SOFTWARE AND MDL FOR OTHER CONDITIONS

1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3° 1° 2° 3°180/160 3458 5146 7863 6441 9582 14649 9555 14209 21718 12886 19164 29294 15839 23559 36009 19106 28418 43442 22263 33117 50620 25233 37529 57372170/150160/140140/120110/90 1118 1667 2547 2087 3103 4743 3096 4603 7035 4174 6206 9490 5128 7631 11665 6189 9203 14073 7212 10728 16398 8174 12156 18585

Page 15: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

51

TURBO VKN5How to choose the most efficient heater?

Correction factors for Verano heaters type TURBO VKN5 taking into account the type of grille.

GRILLE TYPE AIR FLOW CORRECTION FACTOR

Aluminium grille closed profile 61,6% 1,00

Aluminium grille I-beam profile 57,6 % 0,99

Wooden grille 52% 0,97

Modular grille 60,8% 1,00

Linear grille 58% 0,99

Stainless steel grille 61,2% 1,00

Water capacity [dm3]

H = 78, 90, 120 mm

W [mm]L [mm]

750 1150 1550 1950 2350 2750 3150 3550

250 0,14 0,26 0,38 0,51 0,63 0,74 0,88 0,99

350 0,29 0,52 0,75 1,02 1,25 1,48 1,75 1,99

Page 16: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

52

TURBO VKN5 Pressure looses [Pa]

9

7

5

4

3

2

2

3

4

5

7

910000

1000

100

1

10

2

3

4

5

2

3

4

5

7

9

1000

100009

7

5

4

3

2

5

7

9

700200 300 400 6001008060403010 20

7

9

9

7

5

4

3

2

2

3

4

5

7

910000

1000

100

1

10

2

3

4

5

2

3

4

5

7

9

1000

100009

7

5

4

3

2

5

7

9

700200 300 400 6001008060403010 20

7

9

L=3550

L=1950L=1550

L=1150

L=750

L=3150L=2750L=2350

L=3550

L=1950L=1550

L=1150

L=750

L=3150L=2750L=2350

Water flow in kg/h

Pres

sure

dro

p in

Pa

Pres

sure

dro

p in

Pa

Water flow in kg/h

Width: 9-27/32 inch Width: 13-3/4inch

Page 17: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

53

TURBO VKN5

Heater typeControl voltage

U[V]

Trench TURBO VKN5 lenght [mm]

VKN5-7,8/25/L-12VKN5-7,8/35/L-14VKN5-09/25/L-12VKN5-09/35/L-14

VKN5-12/25/L-12VKN5-12/35/L-14

2 - -- 22 22 22 23,8 23,8

4 25 25 25 28 28 28 29,8 29,8

6 32 31 31 34 34 34 36,1 35,8

8 38 38 38 41 41 41 42,8 42,8

10 44 44 44 47 47 47 48,8 48,8

Due to the low sound pressure levels compared to the background measurement - value <20 dB, which is out of the hearing values range, are not shown in the table.

Due to the low sound power levels compared to the background measurement - value <28dB, which is out of the he-aring values range, are not shown in the table.

Heater typeControl voltage

U[V]

Trench TURBO VKN5 lenght [mm]

VKN5-7,8/25/L-12VKN5-7,8/35/L-14VKN5-09/25/L-12VKN5-09/35/L-14

2 - - - - - - - -

4 29 - - 29 29 29 32 30,8

6 36 34 34 37 37 37 39,5 38,8

8 41 42 42 45 45 45 46,5 46,8

10 48 48 46 51 50,1 49 51,5 51,5

VKN5-12/25/L-12VKN5-12/35/L-14

2 - - - 30 30 30 31,8 31,8

4 33 33 33 36 36 36 37,8 37,8

6 40 39 39 42 42 42 44,1 43,8

8 46 46 46 49 49 49 50,8 50,8

10 52 52 52 55 55 55 56,8 56,8

Sound pressure level Lp (A) [dB]

Sound power level Lw (A) [dB]

29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

29-1/2 42-1/4 61 76-3/4 92-1/2 108-1/4 124 139-3/4

2 - - - - - - - -

4 21 - - 21 21 21 24 22,8

6 28 26 26 29 29 29 31,5 30,88 33 34 34 37 37 37 38,5 38,8

10 40 40 38 43 42,1 41 43,5 43.5

Page 18: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

54

TURBO VKN5

TURBO VKN5-7,8/25/L-12

0500

100015002000250030003500400045005000550060006500700075008000850090009500

100001050011000

2 3 4 5 6 7 8 9 10U [V]

Q [W]

0246810121416182022242628303234363840424446

Lp [dB]

Q dla 750 Q dla 1150 Q dla 1550 Q dla 1950 Q dla 2350 Q dla 2750 Q dla 3150 Q dla 3550Lp dla 750 Lp dla 1150 Lp dla 1550 Lp dla 1950 Lp dla 2350 Lp dla 2750 Lp dla 3150 Lp dla 3550

TURBO VKN5-7,8/35/L-14

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

11000

12000

13000

14000

2 3 4 5 6 7 8 9 10U[V]

Q[W]

0246810121416182022242628303234363840424446

Lp[dB]

Q dla 750 Q dla 1150 Q dla 1550 Q dla 1950 Q dla 2350 Q dla 2750 Q dla 3150 Q dla 3550Lp dla 750 Lp dla 1150 Lp dla 1550 Lp dla 1950 Lp dla 2350 Lp dla 2750 Lp dla 3150 Lp dla 3550

Heat output and sound pressure

Heat output and sound pressure for Verano heaters type Turbo VKN5 depending on the control voltage for Ts / TR / Ti = 75/65/20°C

The charts show the changes of the heater output Q [W] and the sound pressure level Lp [dB] as a function of control voltage U [V] for the individual heaters TURBO VKN5.

Please note! Example of the calculation of the heater output and sound pressure (for TURBO VKN5 and CVK) for various values of the voltage is located on page 71

Page 19: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

55

TURBO VKN5

TURBO VKN5-09/25/L-12

0500

100015002000250030003500400045005000550060006500700075008000850090009500

1000010500110001150012000

1 2 3 4 5 6 7 8 9U[V]

Q[W]

0

5

10

15

20

25

30

35

40

45Lp[dB]

Q dla 750 Q dla 1150 Q dla 1550 Q dla 1950 Q dla 2350 Q dla 2750 Q dla 3150 Q dla 3550

Lp dla 750 Lp dla 1150 Lp dla 1550 Lp dla 1950 Lp dla 2350 Lp dla 2750 Lp dla 3150 Lp dla 3550

TURBO VKN5-09/35/L-14

0100020003000400050006000700080009000

100001100012000130001400015000

2 3 4 5 6 7 8 9 10U[V]

Q[W]

0

5

10

15

20

25

30

35

40

45Lp[dB]

Q dla 750 Q dla 1150 Q dla 1550 Q dla 1950 Q dla 2350 Q dla 2750 Q dla 3150 Q dla 3550

Lp dla 750 Lp dla 1150 Lp dla 1550 Lp dla 1950 Lp dla 2350 Lp dla 2750 Lp dla 3150 Lp dla 3550

Heat output and sound pressure

Page 20: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

56

TURBO VKN5 Heat output and sound pressure

TURBO VKN5-12/35/L-14

0100020003000400050006000700080009000

10000110001200013000140001500016000

2 3 4 5 6 7 8 9 10U[V]

Q[W]

0

5

10

15

20

25

30

35

40

45

50Lp[dB]

Q dla 750 Q dla 1150 Q dla 1550 Q dla 1950 Q dla 2350 Q dla 2750 Q dla 3150 Q dla 3550

Lp dla 750 Lp dla 1150 Lp dla 1550 Lp dla 1950 Lp dla 2350 Lp dla 2750 Lp dla 3150 Lp dla 3550

TURBO VKN5-12/25/L-12

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

11000

12000

2 3 4 5 6 7 8 9 10U[V]

Q[W]

0

5

10

15

20

25

30

35

40

45

50Lp[dB]

Q dla 750 Q dla 1150 Q dla 1550 Q dla 1950 Q dla 2350 Q dla 2750 Q dla 3150 Q dla 3550

Lp dla 750 Lp dla 1150 Lp dla 1550 Lp dla 1950 Lp dla 2350 Lp dla 2750 Lp dla 3150 Lp dla 3550

Page 21: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

57

Total lenght of the trench (Lt)

Lenght of the trench heater (L)

Tota

l len

ght o

f the

tren

ch (L

t)

Leng

ht o

f the

tren

ch h

eate

r (L)

Lenght of the trench heater (L)

Total lenght of the trench (Lt)Lenght of the trench heater (L)

Total lenght of the trench (Lt)Lenght of the trench heater (L)

Total lenght of the trench (Lt)Lenght of the trench heater (L)

Corner (empty trench)

Grille corner so. herringbone

Lenght of the trench heater (L)

Lenght of the trench heater (L)

The angle of 90˚

Custom angle

Curved

Bevels Indentation

ANGLED & CURVED

Internal radius (Ri)

External radius (Re)

The l

ength

of th

e exte

rnal

arc

B

H

W

VK 15 / TURBO VKN5

To heat the room of irregular shape, such as circle or semi-circle and at the same time not to disturb its aesthetics and harmony ideally product will be angled and curved heaters available with or without fan.

Page 22: Trench Fan coil VKN TECHNICAL catalogue · Trench Heater Turbo VKN5 may be a per - fect solution for low supply temperature heating systems or high condensation wet installations,

www.mdlsoln.com

By: MDL Solutions

2275 UPPER MIDDLE RD, EOAKVILLE, ONTARIO

CANADA L6H 203TEL: 289 799-3414;

EMAIL: [email protected]

MDL SOLUTIONSNATIONAL DISTRIBUTOR

CANADA/ USA

After completion the edition of the directory on the 21.01.2015, may have been some changes in the products listed in.The manufacturer reserves the right to make changes to the design, color and specification.

Illustrations may include optional accessories. Printing technology can affect the differences in the forward colors. Please contact MDL for the newest information of Verano products.

Technical catalogue 2016_01_USA