Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
IV.1 TRANSINT HOUSE BUILDING
I INTERNAL ELECTRIFICATION
1 135 Primary Light points PT
Supply and Wiring for PrimaryLight pointwith FRLS 1.5sq.mm,
1.1KV grade, ISI marked, PVC insulated single core, FRLS
stranded copper conductor cable conforming to IS:694 (withlatest amendments) in 20 mm dia 2mm thick electrical
grade,PVC conduit concealed in ceiling, or wall, or column, or
floor including supply and fixing of 1No 6Amp Modular(plate)
control switch fixed in a suitable size metal sheet flush boxes
suitable for modular switches and covered with modularswitch
plates and all necessary components, and earthing with
1.5Sq.mm PVC insulated copper wire run continuously inside
the conduit including supply of all fixing materials, accessories
and interconnections complete as required.
Notes:
1. Rates for all the point wiring items are inclusive of necessary
circuit mains with 3Runs of 2.5sqmm FRLS PVC insulatedCopper conductor wires from the distribution board to the first
switchboardand also sub circuits from one switchboard to the
subsequent switch boards in the same circuit.
2. The secondary point in case of point wiring shall include
necessary wiring looped from the primary light point as
indicated in the electrical layout drawings.
3. Rates for the power point wiring items are inclusive of
necessary power circuit from the DB to the power socket.
4. All 16A power Switch Sockets shall be with Built in LED
indication
2 71 Secondary Poin PTSupply and wiring generally same as item 1 above but without
control switch.
3 43 Ceiling Fan Point PT
Supply and Wiring for ceiling fan point with FRLS 1.5sq.mm,
1.1KV grade, ISI marked,PVC insulated single core, stranded
copper conductor cable conforming to IS:694 (with latest
amendments) in 20 mm dia,2mm thick electrical grade,PVC
conduit concealed in ceiling, or wall, or column, or floor
including supply and fixing of 1No 5Ampmodular(plate)control
switch & 100W step type electronic regulator fixed in suitable
size metal sheet Box suitable for modular switches and
regulator and covered with modular switch plates and earthing
with 1.5Sq.mm PVC insulated copper wire run continuously
along the conduit including supply of all fixing materials,accessories like fan hook box, termial box , interconnections
complete as required.
Page 1 of 11
7/29/2019 Transit House
2/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
4 25 Exhaust Fan Point PTSupply and wiring generally same as item 1 above but for
exhaust fan with 6 Amp modular SPMCB for control.
5 20 Two way poin PTSupply and wiring generally same as item 1 above, but for
Twoway light point with 2nos 2 way, 6 Amps. Modular
switches.(for Staircase-4 & For Rooms-16)
6 10 5 Amp 3 Pin Socket outlet poin PTSupply and wiring generally similar to item 1 above but for
modular5A, 3pin combined switch socket outlet point including
supply and fixing of 5A 3 pin combinedswitch socket outlet in a
suitable size metal sheet Box and covered with modular plate
complete as required.
7 38 5A 3pin socket outlet in lighting switch boar PTSupply and fixing of modular 5A 3pin combined switch socket
outlet in the metal sheet Box of lighting control switch board
including interconnections complete as required.
8 38 16A Combined Switch socket outlet PT
Supply and Wiring with FRLS 2runsX 2.5sq.mm, 1.1KV grade,
ISI marked, PVC insulated single core, stranded copper
conductorcableconforming to IS:694 (with latestamendments)
in 20 mm dia, 2mm thick electrical grade,PVC conduit
concealedin ceiling, or wall,or column, or floor including supply
and fixing of modular 16Amp/5Amp modular universal switch
socket outlet with LED indication fixed in a suitable size metal
sheet box suitable for switches and sockets and covered with
modular switch plate and earthing with 2.5SQmm insulated
copper wire run continuously alongthe conduit includingsupply
of fixing materials, interconnections complete as required.
9 16 AC OUTLET PTSupply and Wiring with FRLS 2runsX 4sq.mm, 1.1KV grade,
ISI marked, PVC insulated single core, stranded copper
conductor cable confirming to IS:694 (with latest amendments)
in 20 mm dia, 2mm thick electrical grade,PVC conduit
concealedin ceiling, or wall,or column, or floor including supply
and fixing of modular32Amp 2ploe ELMCB 100mA Sensitivity
in metal sheet box suitable for ELMCB,size and covered with
modular switch plate and earthing with 2.5sqmm insulated
copper wire run inside the conduit power supply shall be
trappedfrom DB,and 20mmdia 2mm thick electricalgradePVC
pipe shall be laied in wall with fish wire from ELCB board
(which is fixed at 1.2m from FFL) to the height of indoorAC unit
and teriminateina suitable MS box concealed in wall includingcover for interconnecting to AC unit complete as required.
Page 2 of 11
7/29/2019 Transit House
3/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
10 16A socket outlet for Geze16 Supply and Wiring with FRLS 2runsX4 sq.mm, 1.1KV grade,
ISI marked, PVC insulated single core, stranded copper
conductorcableconforming to IS:694 (with latestamendments)
in 20 mm dia, 2mm thick electrical grade,PVC conduitconcealedin ceiling, or wall,or column, or floor including supply
and fixing of modular 16Amp modular socket outlet fixed in a
suitable size metal sheet box suitable for sockets and covered
with modular switch plate and earthing with 4SQmm PVC
insulated copper wire run continuously along the conduit
including supply of fixing materials,the power supply shall be
tapped from exsisting 32A ELMCB fixed at the door including
interconnections complete as required.
PT
11 Control switch for Geyser
16 Supply and Wiring with FRLS 2runsX 4 sq.mm, 1.1KV grade,ISI marked, PVC insulated single core, stranded copper
conductorcableconforming to IS:694 (with latestamendments)in 20 mm dia, 2mm thick electrical grade,PVC conduit
concealedin ceiling, or wall,or column, or floor including supply
and fixing of modular32Amp 2pole ELMCB in metal sheet box
sutable for modular ELMCB of suitable size and covered with
modular switch plate and earthing with 4SQmm PVC insulated
copper wire run continuously alongthe conduit includingsupply
of fixing materials,thepowersupply is tappedfrom DB, & switch
board shall be fixed at out side of the door including
interconnections complete as required.
PT
12 Run of mains
12.1 500 Supply and wiring with 4runs of 6sq.mm, 1.1 KV grade FRLSpvc insulated, single core stranded copper conductor cable
confirming to IS:694 (with latest amendments) in 3 2mm dia
2mm thick electrical grade PVC pipe insulated concealed in
wall/ceiling,or floor and earthing with 2 run of 4sq.mm copper
wire run continuously along the conduit including supply of all
fixing materials and accessories, interconnections completeas
required. (from Vertical Dbs to room wise Dbs )
Mtr
12.2 100 Supply and wiringwith 4runs of 10sq.mm,1.1 KV grade FRLSpvc insulated, single core stranded copper conductor cable
confirming to IS:694 (with latest amendments) in 40mm dia
2mm thick PVC electrical grade concealed in wall/ceiling,or
floor and earthing with 2 run of 6sq.mm copper wire runcontinuously along the conduit including supply of all fixing
materials and accessories, interconnections complete as
required (from panel to Vertical Dbs )
Mtr
Page 3 of 11
7/29/2019 Transit House
4/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
12.3 50 Supply and wiring with 2runs of 4sq.mm, 1.1 KV grade FRLSpvc insulated, single core stranded copper conductor cable
confirming to IS:694 (with latest amendments) in 25mm dia
2mm thick PVC electrical grade concealed in wall/ceiling,or
floor and earthing with 2 run of 2.5sq.mm copper wire run
continuously along the conduit including supply of all fixingmaterials and accessories, interconnections complete as
Mtr
13 Distribution BoardSupply installation Testing and commissioning of TPN MCB
Double Door Distributionboards dust and vermin protectedand
rated for 440V Three phase 50hz AC supply operation,
including of bus bar suitable capacity, neutral link with required
outgoings, din bar, fully factory fabricated with powder coated
incoming ELMCB as per specifications and required capacity
and Earth terminal complete as required and installed in flush
with wall including all fixing materials required. (All MCB's in
UDBs shall be of'D' Curve & other MCB's shall be 'C' Curve.
13.1 2 6way VTPNMCCB DB with 100ATPN MCCB 35KA asincomer-1 and 32A TPMCBs as outgoings 6nos. sets
13.2 1 4way VTPNMCCB DB with 63ATPN MCCB 35KA as incomer1 and 32A TPMCBs as outgoings 4nos.
set
13.3 1 6wayTPNMCBDB with63A,100mA leakagecurrent sensitivityFP ELMCB as incomer and 18nos 6A SPMCBs as
outgoings.(LDBs)
sets
14 Customized DB16 TPNMCBDB with 32A FP ELMCB with,100mA leakage
current sensitivity as incomer-1and 32A TP contactor with
230V coil one number and 6A ,16A &20A SPMCBs 6 nos as
outgoings.
sets
15 1 8way SPNMCB DB with 32A MCB as incomer-1 and 6ASPMCBs as outgoings 8nos.
sets
16 BUZZER POINT16 Supply and Wiring for buzzel/call bell point with 1.5 sq.mm
1.1kV grade, ISI marked, PVC insulated ,FRLS single core ,
stranded copper conductor cable conforming to IS:694 ( with
latest amendments) in 20mm. Dia 2mm thick ele.gradePVC
conduit concealed in ceiling or buzzer/call bell fixed in suitable
size independent metal sheet boxes covered with modular
switch plates sheet, and earthing with 1.5sq.mm insulated
copper wire run inside the conduit including supply of fixing
materials and interconnections complete as required.
PT
Page 4 of 11
7/29/2019 Transit House
5/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
II Supply & Installation of Light Fixtures & Fans
1 Supply &Installation of Light FixtureSupply, installation, testing & commissioning of the following
light fittings with electronic ballast and all other accessories
including supply of lamps. Installation of light fittings complete
with supply of all materials like balancing socket, conduit pipe,nipples, check nuts, bolts, nuts, metallic flexible hose,
suspension rod/ Chain, clampsetc., requiredfor such installtion
as per specifications for the following fittings including painting
with aproved synthetic paint, necessary interconnections in an
approved manner.
a) 1X28W TL5 light fixture (CAT NO:-TCH 207 1X TLF 28HFsimilar to PHILIPS)
15 Supply Each
15 Installation Each
b) 1X14W wall bracket light fixture (In bed rooms) (CAT NO:-TCH 207/1XTL5-14W similar to PHILIPS)
52 Supply Each
52 Installation Each
c) 1X9W wall bracket light fixture (for dressing table) (CAT NO:-FMC 21/109 similar to PHILIPS)
16 Supply Each
16 Installation Each
d 1X9W wallbracket light fixture (for mirror light) (CAT NO:-FMS200/111 similar to PHILIPS)
16 Supply Each
16 Installation Each
e 2X18W Surface mountinglight fixture (CAT NO:-FCS 518/218similar to PHILIPS
10 Supply Each
10 Installation Each
f 4X14W T5 recess mounted light fixture (CAT NO:-TBS869/414 D8 HF similar to PHILIPS
33 Supply Each
33 Installation Each
Page 5 of 11
7/29/2019 Transit House
6/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
g 2X28W T5 mirror optic type fixture (surface mounted) (CATNO:-TCS 398/2 X28 MDGN HF similar to PHILIPS)
28 Supply Each
28 Installation Each
h 2X28W FTL (T5)-WEF 83228 SGW AEROS-DP IndirectDirect pendent mounted luminary with lamp(WIPRO Make) -
12 Supply Each
12 Installation with using of a set of 2.Quick install suspensionsystem for areos-DP suitable for RCC Ceiling(WVX 821)
Each
i 4W WALL MOUNTED LED LIGHT FIXTURE (bedside) (CATNO:-BBG 410 K2-10/CW PSU 220-240V similar to PHILIPS)
20 Supply Each
20 Installation Each
j 1X5W CFL-DF foot luminary with lamp (Similar to Comptongrieves CHL 218 LSB)
16 Supply Each
16 Installation Each
2 Supply, installation, testing and commissioning of light duty,totally enclosed motor type exhaust fans suitable for operation
on 230Volts, 50Hz singlephase AC supplycompletewith 3core
flexible copper conductor cable, gravity louvers shutters rigidframe with rubber mountings and of flooring sizes confirmingto
IS-2312 (with latest amendments)
2.1 225mm sweep 1400RPM with double Ball Bearing (in rooms)
20 Supply Each
20 Installationof exhaust fan with gravity louvers on wall includinggrouting of bolts for installation supply of material as Dwg.
CED/24/S/17
Each
3 300 mm sweep 900RPM with double Ball Bearina 5 Supply Each
b 5Installationof exhaust fan with gravity louvers on wall including
grouting of bolts for installation supply of material as Dwg.
CED/24/S/17
Each
Page 6 of 11
7/29/2019 Transit House
7/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
4 Supply of 1200mm sweep ceiling fan capacitor type completewith 300mm down road suitable of 230V AC supply
43 Supply Each
43 Installation of ceiling fans of having standard down rod with allmaterials required for installation complete with necessaryinterconnections as per Dwg. CED/24/S/19
Each
5 15 Extra downrod with 20mm dia class C GI pipe including supplyof GI pipe,cutting threading and providing interconnectionpipe
Mtr
6 GeyserSupply & Installationof the following non -pressure type gezers
with all required material, geysers conforming to IS 2082 (with
latest amendments)and suitable for 230V 50HZ single phase
AC supply complete with inlet and outlet manifolds and saftey
devices like thermostat cutout with reset,LED indication
lamp,3C flexible copper cable and plug top
Storage type vertical fixing 15ltrs capacit
6.1 16 Supply Each
16 Installationon wall/coloumnwith necessary base plate bracketsmade out of MS angle iron/flat of suitable size including
cutting,welding,groutingand supply of all Installation materials
fixing of inlet/outlet water pipes interconnection complete as
required.
Each
7 Supply and fixing of 10A Fab switch with Fab key andengraving the room number 230V 50HZ
16 Supply & Installation (To control DB cont actor) Each
8 1 Supply & fixing of 32 DP MCB in a sheet steel en closersuitable for wall concealed for outgoing of UPS
Each
9 OLYMPIA light poles with 4X18W CFL lamps, 3.6mts heightincluding fixing of junction box 16Aconnector and MCB
Page 7 of 11
7/29/2019 Transit House
8/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
a 2 Supply and erection of 3.6Mts height garden light polefabricated out of 60mm dia MS Pipe OYMPIA LIGHT POLE
with 4 arms core aluminumbracketwith end portionsuitable for
4 numbers 18W CFL integralPost top lanthern typeDecorative
light fitting, built in stainless steel control box etc. the pole shall
be finished neatly with one coat of primer and two coats ofenamel paint of approved color. The scope of work includes
necessary earth work upto a depth of 600mm with
300X300X600mm 1:2:4 concretepedastal,necessary concrete
coping 300X300X375mm, providing suitable ms junction box
with fuse units, connectors suitable hole for termination of
2.5Sq.mm cable with 25mm Pvc pipe and outgoing including
interconnections with 1.5Sq.mm single core copper conductor
cable and earthing with 1.5Sq.mm copper conductor complete
as required. (OLYMPIA COLUMN 522 of Metal Coats)
Each
b 8 Supply, fixing and testing of Pre-wired decorative1X18W CFLintegral Post top lanthern of size 240mmX360mm with louvers
clearglass completewith all accessories such as holder, lampsetc suitable for mounting on 60mm dia GI/ MS Pole complete
with interconnections as specified and directed by the EIC.
Each
c 2 Supply and fixing of one way Metal enclosure for SPMCBindependentmounting suitable for terminationscable gland on
MS conduit with 6A SPMCB concealed in wall interconnection
earthing complete as required (For FL tube light) (similar
Legrand no 60788)
Each
*** MV CABLES10 Supply of 1.1KV grade XLPE insulated, and overall sheathed,
stranded aluminum/ Copper conductor, flat steel strip/wire
armored / unarmored cables confirming to IS:7098/Part I (with
latest amendments)and of followingsizes. The cable shall bear
ISI certification mark.
Note: The Actual Lengths of cables shall be verified at
site before procurements
10.1 2Core 2.5sq.mm Un- Armoured Flexible Cu. Cable (for Landsca e li htin
a 30 Supply Mtr
Laying of above cables in 25mm 2mm thick PVC pipe includin
supply of PVC pipe and partly laying in wall/Concealedand in
ground including excavationrefillingand providing baked bricks
on top and side in depth 750mm belowground level complete
including interconnections etc as required.
b 20 Laying in Ground. Mtr
c 10 Laying in wall (Concealed in wall) Mtr
Page 8 of 11
7/29/2019 Transit House
9/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
11 2 Providing Spiral coil earthing with 8SWG GI wire includingspreading of salt and charcoal as per IS 3043/87 with latest
amendments.
Nos
III INTERNAL COMMUNICATIONInternal Telephone/TV wiring & Networking Facility.
1 500 Supply and embedmentof 20mmdia 2mm thick electricalgradePVC conduit concealed in wall floor/ ceiling including supply
and drawingof 12SWG wire as fish wire including supply of all
fixing materialsas requiredand as directed by EIC. (250Mtr for
Telephone & 250Mtrs for Lan, )
Mtr
2 100 Supply and embedmentof 25mmdia 2mm thick electricalgradePVC conduit concealed in wall floor/ ceiling including supply
and drawingof 12SWG wire as fish wire including supply of all
fixing materialsas requiredand as directed by EIC. (200Mtr for
Telephone & 100Mtrs for Lan,)
Mtr
3 300 Supply and laying of PVC insulated copper conductor 0.5mmdia 2 pair Telephone wire in already embedded conduits
including interconnections complete as required.
Mtr
4 100 Supply and laying of PVC insulated copper conductor 0.5mmdia 5 pair Telephone unarmoured cable in already embedded
conduits including interconnections complete as required.
Mtr
5 100 Supply and laying of PVC insulated copper conductor 0.5mmdia 10 pair Telephone unarmoured cable in already embedded
conduits including interconnections complete as required.
Mtr
6 Supply and installation of the following Telephone krone in 2mthick CRCA sheet steel enclosure flush mounting type with a
removable hinged top cover and duly painted, including
providing of mounting bracket for Krone type connector and
inter connections as required
a) 1 10 Pair each
b) 2 20 Pair each
c) 1 50 Pair each
7 Supply and laying the following 0.5mm dia copper conductorarmoured telephone cables on existing cable trays/trench
including all fixing accessories & connections and completeas
required.
a) 100 10 Pair Mtr
b) 122 20 Pair Mtr
c) 100 50 Pair Mtr
Page 9 of 11
7/29/2019 Transit House
10/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
( Cable shall be laid in ground wherever required including
excavation & back filling with sand & brick protection )
8 6 Supply and fixing of 6 way TV Tap off in 2mm thick MS boxcovered with 3mm thick hylam sheet, including supply of all
fixing materials as required
Each
9 400 Supply and laying of RG6 copper conductor Co -axial joint lessTV antenna cable in existing conduit including supply of all
fixing materials as required
Mtr
10 30 Supply and fixing of Telephone jack with RJ11 modular typejack includingsupply and fixing of anodisedGI box and its front
plate including interconnections as required.
each
11 24 Supply and fixing of LAN jack with RJ45 modular type jackincludingsupply and fixingof anodisedGI boxand its front plate
including interconnections as required.
each
12 25 Supply and fixing of following TV Sockets outlets ( Modular typ) in anodized box concealed in wall. Including front plate &
other accessories
each
IV Earthing & Lightning Protection
1 7 Providing standard pipe earth to earth stations with 2.5m long,38mm dia GI pipe earth stations confirming to IS : 3043 with
latest amendments and as per standard dwg., and including
supply of all materials and providing chamber complete as per
standard drawing as required. (2Nos for panel,4Nos for
LP,1no for UPS body)
each
2 1 Providing standard 2.5m depth with copper plate earth forearth station with 600x600x3.15mm electrolytic copper plate,
confirming to IS:3043 with latest amendments and as per
standard dwg., including supply of all materials and providing
chamber complete as required. ( for UPS-1no )
each
Note:
1) Copper plate shall be tinned
2) Rate of earth station includes the cost of suitable medium
class GI pipe for watering
3 Supply and laying of electrolytic copper/GI strip of followingsizes including supply and fixing using MS/Aluminium spacers,
saddles welding with all fixing materials required and when laid
inside the building and inclusive of excavation & refilling of
earth when laid outside the building and tinning of all the joints
& terminations interconnections interconnections with earth pit
and equipment, terminations/ interconnections in an approved
manner as per IS 3043 (with latest amendments) inclusive of
supply of all hardwares complete as required.
Note: Strips whenlaid on roof for lightningprotectionshall be as
Page 10 of 11
7/29/2019 Transit House
11/11
Package-II Part-IV Electrical Works- Transit House Building
Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in
Figures&
Words)
AMOUNT
3.1 500 25 x 3mm GI strip with flat GI on surface of building at every1Mtr spacing (for Lightning Protection as roof conductor)
Mtr
3.2 200 32 x 6mm GI strip burried in ground (For Lightning Protectionas ground conductor)
Mtr
3.3 75 25 x 6mm GI strip ( For Panel, UPS- Body& Cable tray) Mtr
TOTAL Rs