Transit House

Embed Size (px)

Citation preview

  • 7/29/2019 Transit House

    1/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    IV.1 TRANSINT HOUSE BUILDING

    I INTERNAL ELECTRIFICATION

    1 135 Primary Light points PT

    Supply and Wiring for PrimaryLight pointwith FRLS 1.5sq.mm,

    1.1KV grade, ISI marked, PVC insulated single core, FRLS

    stranded copper conductor cable conforming to IS:694 (withlatest amendments) in 20 mm dia 2mm thick electrical

    grade,PVC conduit concealed in ceiling, or wall, or column, or

    floor including supply and fixing of 1No 6Amp Modular(plate)

    control switch fixed in a suitable size metal sheet flush boxes

    suitable for modular switches and covered with modularswitch

    plates and all necessary components, and earthing with

    1.5Sq.mm PVC insulated copper wire run continuously inside

    the conduit including supply of all fixing materials, accessories

    and interconnections complete as required.

    Notes:

    1. Rates for all the point wiring items are inclusive of necessary

    circuit mains with 3Runs of 2.5sqmm FRLS PVC insulatedCopper conductor wires from the distribution board to the first

    switchboardand also sub circuits from one switchboard to the

    subsequent switch boards in the same circuit.

    2. The secondary point in case of point wiring shall include

    necessary wiring looped from the primary light point as

    indicated in the electrical layout drawings.

    3. Rates for the power point wiring items are inclusive of

    necessary power circuit from the DB to the power socket.

    4. All 16A power Switch Sockets shall be with Built in LED

    indication

    2 71 Secondary Poin PTSupply and wiring generally same as item 1 above but without

    control switch.

    3 43 Ceiling Fan Point PT

    Supply and Wiring for ceiling fan point with FRLS 1.5sq.mm,

    1.1KV grade, ISI marked,PVC insulated single core, stranded

    copper conductor cable conforming to IS:694 (with latest

    amendments) in 20 mm dia,2mm thick electrical grade,PVC

    conduit concealed in ceiling, or wall, or column, or floor

    including supply and fixing of 1No 5Ampmodular(plate)control

    switch & 100W step type electronic regulator fixed in suitable

    size metal sheet Box suitable for modular switches and

    regulator and covered with modular switch plates and earthing

    with 1.5Sq.mm PVC insulated copper wire run continuously

    along the conduit including supply of all fixing materials,accessories like fan hook box, termial box , interconnections

    complete as required.

    Page 1 of 11

  • 7/29/2019 Transit House

    2/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    4 25 Exhaust Fan Point PTSupply and wiring generally same as item 1 above but for

    exhaust fan with 6 Amp modular SPMCB for control.

    5 20 Two way poin PTSupply and wiring generally same as item 1 above, but for

    Twoway light point with 2nos 2 way, 6 Amps. Modular

    switches.(for Staircase-4 & For Rooms-16)

    6 10 5 Amp 3 Pin Socket outlet poin PTSupply and wiring generally similar to item 1 above but for

    modular5A, 3pin combined switch socket outlet point including

    supply and fixing of 5A 3 pin combinedswitch socket outlet in a

    suitable size metal sheet Box and covered with modular plate

    complete as required.

    7 38 5A 3pin socket outlet in lighting switch boar PTSupply and fixing of modular 5A 3pin combined switch socket

    outlet in the metal sheet Box of lighting control switch board

    including interconnections complete as required.

    8 38 16A Combined Switch socket outlet PT

    Supply and Wiring with FRLS 2runsX 2.5sq.mm, 1.1KV grade,

    ISI marked, PVC insulated single core, stranded copper

    conductorcableconforming to IS:694 (with latestamendments)

    in 20 mm dia, 2mm thick electrical grade,PVC conduit

    concealedin ceiling, or wall,or column, or floor including supply

    and fixing of modular 16Amp/5Amp modular universal switch

    socket outlet with LED indication fixed in a suitable size metal

    sheet box suitable for switches and sockets and covered with

    modular switch plate and earthing with 2.5SQmm insulated

    copper wire run continuously alongthe conduit includingsupply

    of fixing materials, interconnections complete as required.

    9 16 AC OUTLET PTSupply and Wiring with FRLS 2runsX 4sq.mm, 1.1KV grade,

    ISI marked, PVC insulated single core, stranded copper

    conductor cable confirming to IS:694 (with latest amendments)

    in 20 mm dia, 2mm thick electrical grade,PVC conduit

    concealedin ceiling, or wall,or column, or floor including supply

    and fixing of modular32Amp 2ploe ELMCB 100mA Sensitivity

    in metal sheet box suitable for ELMCB,size and covered with

    modular switch plate and earthing with 2.5sqmm insulated

    copper wire run inside the conduit power supply shall be

    trappedfrom DB,and 20mmdia 2mm thick electricalgradePVC

    pipe shall be laied in wall with fish wire from ELCB board

    (which is fixed at 1.2m from FFL) to the height of indoorAC unit

    and teriminateina suitable MS box concealed in wall includingcover for interconnecting to AC unit complete as required.

    Page 2 of 11

  • 7/29/2019 Transit House

    3/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    10 16A socket outlet for Geze16 Supply and Wiring with FRLS 2runsX4 sq.mm, 1.1KV grade,

    ISI marked, PVC insulated single core, stranded copper

    conductorcableconforming to IS:694 (with latestamendments)

    in 20 mm dia, 2mm thick electrical grade,PVC conduitconcealedin ceiling, or wall,or column, or floor including supply

    and fixing of modular 16Amp modular socket outlet fixed in a

    suitable size metal sheet box suitable for sockets and covered

    with modular switch plate and earthing with 4SQmm PVC

    insulated copper wire run continuously along the conduit

    including supply of fixing materials,the power supply shall be

    tapped from exsisting 32A ELMCB fixed at the door including

    interconnections complete as required.

    PT

    11 Control switch for Geyser

    16 Supply and Wiring with FRLS 2runsX 4 sq.mm, 1.1KV grade,ISI marked, PVC insulated single core, stranded copper

    conductorcableconforming to IS:694 (with latestamendments)in 20 mm dia, 2mm thick electrical grade,PVC conduit

    concealedin ceiling, or wall,or column, or floor including supply

    and fixing of modular32Amp 2pole ELMCB in metal sheet box

    sutable for modular ELMCB of suitable size and covered with

    modular switch plate and earthing with 4SQmm PVC insulated

    copper wire run continuously alongthe conduit includingsupply

    of fixing materials,thepowersupply is tappedfrom DB, & switch

    board shall be fixed at out side of the door including

    interconnections complete as required.

    PT

    12 Run of mains

    12.1 500 Supply and wiring with 4runs of 6sq.mm, 1.1 KV grade FRLSpvc insulated, single core stranded copper conductor cable

    confirming to IS:694 (with latest amendments) in 3 2mm dia

    2mm thick electrical grade PVC pipe insulated concealed in

    wall/ceiling,or floor and earthing with 2 run of 4sq.mm copper

    wire run continuously along the conduit including supply of all

    fixing materials and accessories, interconnections completeas

    required. (from Vertical Dbs to room wise Dbs )

    Mtr

    12.2 100 Supply and wiringwith 4runs of 10sq.mm,1.1 KV grade FRLSpvc insulated, single core stranded copper conductor cable

    confirming to IS:694 (with latest amendments) in 40mm dia

    2mm thick PVC electrical grade concealed in wall/ceiling,or

    floor and earthing with 2 run of 6sq.mm copper wire runcontinuously along the conduit including supply of all fixing

    materials and accessories, interconnections complete as

    required (from panel to Vertical Dbs )

    Mtr

    Page 3 of 11

  • 7/29/2019 Transit House

    4/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    12.3 50 Supply and wiring with 2runs of 4sq.mm, 1.1 KV grade FRLSpvc insulated, single core stranded copper conductor cable

    confirming to IS:694 (with latest amendments) in 25mm dia

    2mm thick PVC electrical grade concealed in wall/ceiling,or

    floor and earthing with 2 run of 2.5sq.mm copper wire run

    continuously along the conduit including supply of all fixingmaterials and accessories, interconnections complete as

    Mtr

    13 Distribution BoardSupply installation Testing and commissioning of TPN MCB

    Double Door Distributionboards dust and vermin protectedand

    rated for 440V Three phase 50hz AC supply operation,

    including of bus bar suitable capacity, neutral link with required

    outgoings, din bar, fully factory fabricated with powder coated

    incoming ELMCB as per specifications and required capacity

    and Earth terminal complete as required and installed in flush

    with wall including all fixing materials required. (All MCB's in

    UDBs shall be of'D' Curve & other MCB's shall be 'C' Curve.

    13.1 2 6way VTPNMCCB DB with 100ATPN MCCB 35KA asincomer-1 and 32A TPMCBs as outgoings 6nos. sets

    13.2 1 4way VTPNMCCB DB with 63ATPN MCCB 35KA as incomer1 and 32A TPMCBs as outgoings 4nos.

    set

    13.3 1 6wayTPNMCBDB with63A,100mA leakagecurrent sensitivityFP ELMCB as incomer and 18nos 6A SPMCBs as

    outgoings.(LDBs)

    sets

    14 Customized DB16 TPNMCBDB with 32A FP ELMCB with,100mA leakage

    current sensitivity as incomer-1and 32A TP contactor with

    230V coil one number and 6A ,16A &20A SPMCBs 6 nos as

    outgoings.

    sets

    15 1 8way SPNMCB DB with 32A MCB as incomer-1 and 6ASPMCBs as outgoings 8nos.

    sets

    16 BUZZER POINT16 Supply and Wiring for buzzel/call bell point with 1.5 sq.mm

    1.1kV grade, ISI marked, PVC insulated ,FRLS single core ,

    stranded copper conductor cable conforming to IS:694 ( with

    latest amendments) in 20mm. Dia 2mm thick ele.gradePVC

    conduit concealed in ceiling or buzzer/call bell fixed in suitable

    size independent metal sheet boxes covered with modular

    switch plates sheet, and earthing with 1.5sq.mm insulated

    copper wire run inside the conduit including supply of fixing

    materials and interconnections complete as required.

    PT

    Page 4 of 11

  • 7/29/2019 Transit House

    5/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    II Supply & Installation of Light Fixtures & Fans

    1 Supply &Installation of Light FixtureSupply, installation, testing & commissioning of the following

    light fittings with electronic ballast and all other accessories

    including supply of lamps. Installation of light fittings complete

    with supply of all materials like balancing socket, conduit pipe,nipples, check nuts, bolts, nuts, metallic flexible hose,

    suspension rod/ Chain, clampsetc., requiredfor such installtion

    as per specifications for the following fittings including painting

    with aproved synthetic paint, necessary interconnections in an

    approved manner.

    a) 1X28W TL5 light fixture (CAT NO:-TCH 207 1X TLF 28HFsimilar to PHILIPS)

    15 Supply Each

    15 Installation Each

    b) 1X14W wall bracket light fixture (In bed rooms) (CAT NO:-TCH 207/1XTL5-14W similar to PHILIPS)

    52 Supply Each

    52 Installation Each

    c) 1X9W wall bracket light fixture (for dressing table) (CAT NO:-FMC 21/109 similar to PHILIPS)

    16 Supply Each

    16 Installation Each

    d 1X9W wallbracket light fixture (for mirror light) (CAT NO:-FMS200/111 similar to PHILIPS)

    16 Supply Each

    16 Installation Each

    e 2X18W Surface mountinglight fixture (CAT NO:-FCS 518/218similar to PHILIPS

    10 Supply Each

    10 Installation Each

    f 4X14W T5 recess mounted light fixture (CAT NO:-TBS869/414 D8 HF similar to PHILIPS

    33 Supply Each

    33 Installation Each

    Page 5 of 11

  • 7/29/2019 Transit House

    6/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    g 2X28W T5 mirror optic type fixture (surface mounted) (CATNO:-TCS 398/2 X28 MDGN HF similar to PHILIPS)

    28 Supply Each

    28 Installation Each

    h 2X28W FTL (T5)-WEF 83228 SGW AEROS-DP IndirectDirect pendent mounted luminary with lamp(WIPRO Make) -

    12 Supply Each

    12 Installation with using of a set of 2.Quick install suspensionsystem for areos-DP suitable for RCC Ceiling(WVX 821)

    Each

    i 4W WALL MOUNTED LED LIGHT FIXTURE (bedside) (CATNO:-BBG 410 K2-10/CW PSU 220-240V similar to PHILIPS)

    20 Supply Each

    20 Installation Each

    j 1X5W CFL-DF foot luminary with lamp (Similar to Comptongrieves CHL 218 LSB)

    16 Supply Each

    16 Installation Each

    2 Supply, installation, testing and commissioning of light duty,totally enclosed motor type exhaust fans suitable for operation

    on 230Volts, 50Hz singlephase AC supplycompletewith 3core

    flexible copper conductor cable, gravity louvers shutters rigidframe with rubber mountings and of flooring sizes confirmingto

    IS-2312 (with latest amendments)

    2.1 225mm sweep 1400RPM with double Ball Bearing (in rooms)

    20 Supply Each

    20 Installationof exhaust fan with gravity louvers on wall includinggrouting of bolts for installation supply of material as Dwg.

    CED/24/S/17

    Each

    3 300 mm sweep 900RPM with double Ball Bearina 5 Supply Each

    b 5Installationof exhaust fan with gravity louvers on wall including

    grouting of bolts for installation supply of material as Dwg.

    CED/24/S/17

    Each

    Page 6 of 11

  • 7/29/2019 Transit House

    7/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    4 Supply of 1200mm sweep ceiling fan capacitor type completewith 300mm down road suitable of 230V AC supply

    43 Supply Each

    43 Installation of ceiling fans of having standard down rod with allmaterials required for installation complete with necessaryinterconnections as per Dwg. CED/24/S/19

    Each

    5 15 Extra downrod with 20mm dia class C GI pipe including supplyof GI pipe,cutting threading and providing interconnectionpipe

    Mtr

    6 GeyserSupply & Installationof the following non -pressure type gezers

    with all required material, geysers conforming to IS 2082 (with

    latest amendments)and suitable for 230V 50HZ single phase

    AC supply complete with inlet and outlet manifolds and saftey

    devices like thermostat cutout with reset,LED indication

    lamp,3C flexible copper cable and plug top

    Storage type vertical fixing 15ltrs capacit

    6.1 16 Supply Each

    16 Installationon wall/coloumnwith necessary base plate bracketsmade out of MS angle iron/flat of suitable size including

    cutting,welding,groutingand supply of all Installation materials

    fixing of inlet/outlet water pipes interconnection complete as

    required.

    Each

    7 Supply and fixing of 10A Fab switch with Fab key andengraving the room number 230V 50HZ

    16 Supply & Installation (To control DB cont actor) Each

    8 1 Supply & fixing of 32 DP MCB in a sheet steel en closersuitable for wall concealed for outgoing of UPS

    Each

    9 OLYMPIA light poles with 4X18W CFL lamps, 3.6mts heightincluding fixing of junction box 16Aconnector and MCB

    Page 7 of 11

  • 7/29/2019 Transit House

    8/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    a 2 Supply and erection of 3.6Mts height garden light polefabricated out of 60mm dia MS Pipe OYMPIA LIGHT POLE

    with 4 arms core aluminumbracketwith end portionsuitable for

    4 numbers 18W CFL integralPost top lanthern typeDecorative

    light fitting, built in stainless steel control box etc. the pole shall

    be finished neatly with one coat of primer and two coats ofenamel paint of approved color. The scope of work includes

    necessary earth work upto a depth of 600mm with

    300X300X600mm 1:2:4 concretepedastal,necessary concrete

    coping 300X300X375mm, providing suitable ms junction box

    with fuse units, connectors suitable hole for termination of

    2.5Sq.mm cable with 25mm Pvc pipe and outgoing including

    interconnections with 1.5Sq.mm single core copper conductor

    cable and earthing with 1.5Sq.mm copper conductor complete

    as required. (OLYMPIA COLUMN 522 of Metal Coats)

    Each

    b 8 Supply, fixing and testing of Pre-wired decorative1X18W CFLintegral Post top lanthern of size 240mmX360mm with louvers

    clearglass completewith all accessories such as holder, lampsetc suitable for mounting on 60mm dia GI/ MS Pole complete

    with interconnections as specified and directed by the EIC.

    Each

    c 2 Supply and fixing of one way Metal enclosure for SPMCBindependentmounting suitable for terminationscable gland on

    MS conduit with 6A SPMCB concealed in wall interconnection

    earthing complete as required (For FL tube light) (similar

    Legrand no 60788)

    Each

    *** MV CABLES10 Supply of 1.1KV grade XLPE insulated, and overall sheathed,

    stranded aluminum/ Copper conductor, flat steel strip/wire

    armored / unarmored cables confirming to IS:7098/Part I (with

    latest amendments)and of followingsizes. The cable shall bear

    ISI certification mark.

    Note: The Actual Lengths of cables shall be verified at

    site before procurements

    10.1 2Core 2.5sq.mm Un- Armoured Flexible Cu. Cable (for Landsca e li htin

    a 30 Supply Mtr

    Laying of above cables in 25mm 2mm thick PVC pipe includin

    supply of PVC pipe and partly laying in wall/Concealedand in

    ground including excavationrefillingand providing baked bricks

    on top and side in depth 750mm belowground level complete

    including interconnections etc as required.

    b 20 Laying in Ground. Mtr

    c 10 Laying in wall (Concealed in wall) Mtr

    Page 8 of 11

  • 7/29/2019 Transit House

    9/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    11 2 Providing Spiral coil earthing with 8SWG GI wire includingspreading of salt and charcoal as per IS 3043/87 with latest

    amendments.

    Nos

    III INTERNAL COMMUNICATIONInternal Telephone/TV wiring & Networking Facility.

    1 500 Supply and embedmentof 20mmdia 2mm thick electricalgradePVC conduit concealed in wall floor/ ceiling including supply

    and drawingof 12SWG wire as fish wire including supply of all

    fixing materialsas requiredand as directed by EIC. (250Mtr for

    Telephone & 250Mtrs for Lan, )

    Mtr

    2 100 Supply and embedmentof 25mmdia 2mm thick electricalgradePVC conduit concealed in wall floor/ ceiling including supply

    and drawingof 12SWG wire as fish wire including supply of all

    fixing materialsas requiredand as directed by EIC. (200Mtr for

    Telephone & 100Mtrs for Lan,)

    Mtr

    3 300 Supply and laying of PVC insulated copper conductor 0.5mmdia 2 pair Telephone wire in already embedded conduits

    including interconnections complete as required.

    Mtr

    4 100 Supply and laying of PVC insulated copper conductor 0.5mmdia 5 pair Telephone unarmoured cable in already embedded

    conduits including interconnections complete as required.

    Mtr

    5 100 Supply and laying of PVC insulated copper conductor 0.5mmdia 10 pair Telephone unarmoured cable in already embedded

    conduits including interconnections complete as required.

    Mtr

    6 Supply and installation of the following Telephone krone in 2mthick CRCA sheet steel enclosure flush mounting type with a

    removable hinged top cover and duly painted, including

    providing of mounting bracket for Krone type connector and

    inter connections as required

    a) 1 10 Pair each

    b) 2 20 Pair each

    c) 1 50 Pair each

    7 Supply and laying the following 0.5mm dia copper conductorarmoured telephone cables on existing cable trays/trench

    including all fixing accessories & connections and completeas

    required.

    a) 100 10 Pair Mtr

    b) 122 20 Pair Mtr

    c) 100 50 Pair Mtr

    Page 9 of 11

  • 7/29/2019 Transit House

    10/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    ( Cable shall be laid in ground wherever required including

    excavation & back filling with sand & brick protection )

    8 6 Supply and fixing of 6 way TV Tap off in 2mm thick MS boxcovered with 3mm thick hylam sheet, including supply of all

    fixing materials as required

    Each

    9 400 Supply and laying of RG6 copper conductor Co -axial joint lessTV antenna cable in existing conduit including supply of all

    fixing materials as required

    Mtr

    10 30 Supply and fixing of Telephone jack with RJ11 modular typejack includingsupply and fixing of anodisedGI box and its front

    plate including interconnections as required.

    each

    11 24 Supply and fixing of LAN jack with RJ45 modular type jackincludingsupply and fixingof anodisedGI boxand its front plate

    including interconnections as required.

    each

    12 25 Supply and fixing of following TV Sockets outlets ( Modular typ) in anodized box concealed in wall. Including front plate &

    other accessories

    each

    IV Earthing & Lightning Protection

    1 7 Providing standard pipe earth to earth stations with 2.5m long,38mm dia GI pipe earth stations confirming to IS : 3043 with

    latest amendments and as per standard dwg., and including

    supply of all materials and providing chamber complete as per

    standard drawing as required. (2Nos for panel,4Nos for

    LP,1no for UPS body)

    each

    2 1 Providing standard 2.5m depth with copper plate earth forearth station with 600x600x3.15mm electrolytic copper plate,

    confirming to IS:3043 with latest amendments and as per

    standard dwg., including supply of all materials and providing

    chamber complete as required. ( for UPS-1no )

    each

    Note:

    1) Copper plate shall be tinned

    2) Rate of earth station includes the cost of suitable medium

    class GI pipe for watering

    3 Supply and laying of electrolytic copper/GI strip of followingsizes including supply and fixing using MS/Aluminium spacers,

    saddles welding with all fixing materials required and when laid

    inside the building and inclusive of excavation & refilling of

    earth when laid outside the building and tinning of all the joints

    & terminations interconnections interconnections with earth pit

    and equipment, terminations/ interconnections in an approved

    manner as per IS 3043 (with latest amendments) inclusive of

    supply of all hardwares complete as required.

    Note: Strips whenlaid on roof for lightningprotectionshall be as

    Page 10 of 11

  • 7/29/2019 Transit House

    11/11

    Package-II Part-IV Electrical Works- Transit House Building

    Sl.No QTY DESCRIPTION OF ITEM UNIT RATE (in

    Figures&

    Words)

    AMOUNT

    3.1 500 25 x 3mm GI strip with flat GI on surface of building at every1Mtr spacing (for Lightning Protection as roof conductor)

    Mtr

    3.2 200 32 x 6mm GI strip burried in ground (For Lightning Protectionas ground conductor)

    Mtr

    3.3 75 25 x 6mm GI strip ( For Panel, UPS- Body& Cable tray) Mtr

    TOTAL Rs

    Page 11 of 11