3
CAT.200.01.T.E For more information contact Cutler-Hammer: www.ch.cutler-hammer.com/catalog 9-111 January 2001 Transformers 9 Industrial Control Transformers Type AP Vol. 1, Ref. No. [0395] Product Selection Additional Product Selection information begins on Page 9-120. Table 9-135. Type AP 1 See Page 9-83 for Wiring Diagrams. Note: For additional information refer to Cutler-Hammer Industrial Control Transformer Binder B1228A. kVA Mounting Dimensions (Inches) Weight Lbs. Dimensions (mm) Weight Kg Frame Wiring Diagram 1 Catalog Number Price U.S. $ H W D H W D 240/480 Volts to 120/240 Volts, 60 Hz 3 5 7.5 10 Bottom Bottom Bottom Bottom 8-5/16 10-3/4 10-3/4 10-3/4 9-9/16 10-3/4 10-3/4 10-3/4 8-13/16 8 -11/16 10-3/16 11-3/8 65 104 129 148 227 273 273 273 243 273 273 273 224 221 259 289 29.5 47.2 58.6 67.2 133 99 100 101 5 5 5 5 C0003P7GB C0005P7GB C0007P7GB C0010P7GB 1,360. 1,695. 2,330. 2,905. 15 3 5 Bottom Side/Wall Side/Wall 12 9-3/4 11-5/8 13-3/16 8-13/16 8-11/16 10-7/16 9-9/16 10-3/4 197 65 104 305 248 295 335 224 221 265 243 273 89.4 29.5 47.2 134 292 256 5 5 5 C0015P7GB C0003P7GS C0005P7GS 3,940. 1,360. 1,695. 7.5 10 15 Side/Wall Side/Wall Side/Wall 11-5/8 11-5/8 12-7/8 10-13/16 11-3/8 10-7/16 10-3/4 10-3/4 13-3/16 129 148 197 295 295 327 275 289 265 273 273 335 58.6 67.2 89.4 257 258 259 5 5 5 C0007P7GS C0010P7GS C0015P7GS 2,330. 2,905. 3,940. For other ratings or styles not shown, or for special enclosure types (including stainless steel) refer to Cutler-Hammer. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

Transformers 9-111 Industrial Control Transformersdlelectricsupply.com/files/C0010P7HSES.pdf12 9-3/4 11-5/8 13-3/16 8-13/16 ... Industrial Control Transformers, CE Marked Control Transformers

Embed Size (px)

Citation preview

Page 1: Transformers 9-111 Industrial Control Transformersdlelectricsupply.com/files/C0010P7HSES.pdf12 9-3/4 11-5/8 13-3/16 8-13/16 ... Industrial Control Transformers, CE Marked Control Transformers

CAT.200.01.T.E For more information contact Cutler-Hammer: www.ch.cutler-hammer.com/catalog

9-111January 2001

Transformers

9

Industrial Control TransformersType AP

Vol. 1, Ref. No. [0395]

Product SelectionAdditional Product Selection information begins on Page 9-120.

Table 9-135. Type AP

1 See Page 9-83 for Wiring Diagrams.Note: For additional information refer to Cutler-Hammer Industrial Control Transformer Binder B1228A.

kVA Mounting Dimensions (Inches) WeightLbs.

Dimensions (mm) WeightKg

Frame WiringDiagram 1

CatalogNumber

PriceU.S. $H W D H W D

240/480 Volts to 120/240 Volts, 60 Hz357.510

BottomBottomBottomBottom

8-5/1610-3/410-3/410-3/4

9-9/1610-3/410-3/410-3/4

8-13/16 8 -11/1610-3/1611-3/8

65104129148

227273273273

243273273273

224221259289

29.547.258.667.2

13399100101

5555

C0003P7GBC0005P7GBC0007P7GBC0010P7GB

1,360.1,695.2,330.2,905.

1535

BottomSide/WallSide/Wall

129-3/411-5/8

13-3/16 8-13/16 8-11/16

10-7/16 9-9/1610-3/4

19765104

305248295

335224221

265243273

89.429.547.2

134292256

555

C0015P7GBC0003P7GSC0005P7GS

3,940.1,360.1,695.

7.51015

Side/WallSide/WallSide/Wall

11-5/811-5/812-7/8

10-13/1611-3/810-7/16

10-3/410-3/413-3/16

129148197

295295327

275289265

273273335

58.667.289.4

257258259

555

C0007P7GSC0010P7GSC0015P7GS

2,330.2,905.3,940.

For other ratings or styles not shown, or for special enclosure types (including stainless steel) refer to Cutler-Hammer. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

472_09.fm Page 111 Monday, November 20, 2000 9:37 AM

Page 2: Transformers 9-111 Industrial Control Transformersdlelectricsupply.com/files/C0010P7HSES.pdf12 9-3/4 11-5/8 13-3/16 8-13/16 ... Industrial Control Transformers, CE Marked Control Transformers

9-124

For more information contact Cutler-Hammer: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

January 2001

Transformers

9

Vol. 1, Ref. No. [0408]

Catalog Numbering SystemTable 9-154. Industrial Control Transformers, CE Marked Control Transformers — Example: CE0250G2FES

Note: For the Cutler-Hammer Dry Type Transformers Catalog Numbering System see Page 9-122 and 9-123.Note: Contact your local Cutler-Hammer sales office for voltage combinations not shown. Use table for catalog number breakdown only.

Type

C = Industrial Control Transformer

CE= CE Marked Control Transformer

VA Rating

0025 = 250050 = 500075 = 750100 = 1000150 = 1500200 = 2000250 = 2500300 = 3000350 = 3500500 = 5000750 = 7501000 = 10001500 = 15002000 = 20003000 = 30005000 = 5000

Type AP Only:0003 = 30000005 = 50000007 = 75000010 = 100000015 = 15000

Transformer Design

A= MTAC = MTCE = MTEG= MTGK = MTKP = AP

Voltage

Primary Secondary

1B =2A =

2B =2C =2F =2G =2U =

2V =2W =3A =3B =3C =3D =4C =4D =4H =

4W =5E =

6U =

7G =(Type AP

Only)

120 x 240240 x 480,

230 x 460,220 x 440

240 x 480240 x 480230/460230/460220/380/440/550,

230/400/460/575,240/416/480/600

208/230/400/460/575208/230/400/460/575208/277115230/460/575208/380/416550/575/600380/400/415380/400/415550/575/600200/220/440,

208/230/460, 240/480

240/416/480/600,230/400/460/575,220/380/440/550,208/500

240 x 480

24120/115/110

24120 x 240115115/23023/110, 24/115,

25/120

24/115/230115/23012024115/95115/95110/115/120110 x 22022/23/2422/23/2423/110, 24/115,

25/120

99/120/130,95/115/125,91/110/120,85/100/110

120/240

Modifications

Type MTE/MTG/MTKFB = Factory mounted 2-pole primary fuse block for

rejection type fusesFBN = Factory mounted 2-pole primary fuse block for

non-rejection type fusesQ = Secondary fuse clips for 1/4 x 1-1/4 inch fusesXX = No Secondary fuse clipsRT = Ring type terminals for connection to fuseblockES = Electrostatic shieldFS = Factory mounted finger safe terminal shields

Type APB = Bottom mountedS = Side/wall mountedES = Electrostatic shieldCU = Copper windings

Type MTA/MTCFB = Factory mounted 3-pole fuseblock (2-pole

primary rejection type with 1-pole secondary non-rejection type)

ES = Electrostatic shieldL = Lead terminations

CE 0250 G 2F ES

472_09.fm Page 124 Monday, November 20, 2000 9:37 AM

Page 3: Transformers 9-111 Industrial Control Transformersdlelectricsupply.com/files/C0010P7HSES.pdf12 9-3/4 11-5/8 13-3/16 8-13/16 ... Industrial Control Transformers, CE Marked Control Transformers

9-110

For more information contact Cutler-Hammer: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

January 2001

Transformers

9

Industrial Control TransformersType AP

Vol. 1, Ref. No. [0394]

Type AP

Type AP Transformer

Product Description■ Resin-encapsulated designs

Application DescriptionTransformers provide stepped down voltages to machine tool control devices enabling control circuits to be isolated from all power and lighting circuits. This allows the use of grounded or ungrounded circuits that are independent of the power or light-ing grounds; greater safety is afforded the operator. The control transformer line is particularly adaptable on appli-cations where compact construction is demanded.

Features, Benefits and Functions■ UL recognized ■ Resin encapsulated■ 60 Hz operation■ 115°C winding rise■ Convenient screw-type terminal

board■ Bottom or side/wall mounting

designs■ Performance meets/exceeds

requirements of ANSI/NEMA ST-1■ Regulation exceeds ANSI/NEMA

requirements for all ratings

Standards and CertificationsIndustry StandardsAll Cutler-Hammer dry type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI, and IEEE Standards.

Product SpecificationsOverload CapabilityShort-term overload is designed into transformers as required by ANSI. Dry type distribution transformers will deliver 200% nameplate load for one-half hour; 150% load for one-hour; and 125% load for four-hours without being damaged provided that a con-stant 50% load precedes and follows the overload. See ANSI C57.96-01.250 for additional limitations.

Continuous overload capacity is not deliberately designed into a trans-former because the design objective is to be within the allowed winding tem-perature rise with nameplate loading.

Insulation System and Temperature RiseIndustry standards classify insulation systems and rise as shown below:

Table 9-133. Insulation System Classification

The design life of transformers having different insulation systems is the same — the lower temperature systems are designed for the same life as the higher temperature systems.

Sound LevelsAll Cutler-Hammer 600 volt class general purpose dry type distribution transformers are designed to meet NEMA ST-20 levels listed here.

Table 9-134. Sound Levels

1 Applies to general purpose transformers only.

Winding Terminations

Cutler-Hammer recommends external cables be rated 90ºC (sized at 75°C ampacity) for encapsulated designs.

Series-Multiple WindingsSeries-multiple windings consist of 2 similar coils in each winding which can be connected in series or parallel (multiple). Transformers with series-multiple windings are designated with an “X” or “/” between the voltage ratings, such as voltages of “120/240” or “240 X 480.” If the series-multiple winding is designated by an “X,” the winding can be connected only for a series or parallel. With the “/” designa-tion, a mid-point also becomes avail-able in addition to the series or parallel connection. As an example, a 120 X 240 winding can be connected for either 120 (parallel) or 240 (series), but a 120/240 winding can be connected for 120 (parallel), or 240 (series), or 240 with a 120 mid-point.

Technical Data and SpecificationsPlease refer to Page 9-114.

Ambient + WindingRise

+HotSpot

=Temp. Class

40°C40°C40°C40°C

55°C80°C115°C150°C

10°C30°C30°C30°C

105°C150°C185°C220°C

kVA NEMA Average 1

Sound Level in dB

0 – 910 – 5051 – 150151 – 300

40455055

301 – 500501 – 700701 – 10001001 – 1500

60626465

472_09.fm Page 110 Monday, November 20, 2000 9:37 AM