217
Transcritical Carbon Dioxide Heat Pumps for Simultaneous Cooling and Heating A Thesis Submitted in Partial Fulfillment of the Requirements for the Award of the degree of Doctor of Philosophy in Engineering By Jahar Sarkar Under the Supervision of Prof. Souvik Bhattacharyya & Dr. M. Ram Gopal Department of Mechanical Engineering Indian Institute of Technology Kharagpur 2005 A-PDF Merger DEMO : Purchase from www.A-PDF.com to remove the watermark

Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Embed Size (px)

DESCRIPTION

HEAT EXCHANGER

Citation preview

Page 1: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Transcritical Carbon Dioxide Heat Pumps for Simultaneous Cooling and Heating

A Thesis Submitted in Partial Fulfillment of the Requirements for the Award of the degree of

Doctor of Philosophy

in Engineering

By

Jahar Sarkar

Under the Supervision of

Prof. Souvik Bhattacharyya &

Dr. M. Ram Gopal

Department of Mechanical Engineering Indian Institute of Technology

Kharagpur 2005

A-PDF Merger DEMO : Purchase from www.A-PDF.com to remove the watermark

Page 2: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

INDIAN INSTITUTE OF TECHNOLOGY

KHARAGPUR-721302

DEPARTMENT OF MECHANICAL ENGINEERING

CERTIFICATE

The thesis entitled “Transcritical carbon dioxide heat pumps for simultaneous

cooling and heating” submitted by Mr. Jahar Sarkar, for the award of the degree of

Doctor of Philosophy in Engineering to the Indian Institute of Technology Kharagpur is a

record of bonafide research work carried out by him under our guidance and supervision.

The results presented in this thesis have not been submitted to any other

university or institution for the award of any other degree of diploma.

Dr. Souvik Bhattacharyya Professor

Deptt. of Mechanical Engineering Indian Institute of Technology Kharagpur

Dr. M. Ram Gopal Associate Professor

Deptt. of Mechanical Engineering Indian Institute of Technology Kharagpur

Page 3: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Acknowledgements

At the outset, I would like to express my deepest sense of appreciation and

gratitude to Prof. Souvik Bhattacharyya for initiating me into a subject that was

challenging as well as of my interest. His scientific acumen, analytical mind and

methodical supervision have enabled me to complete the work in its present shape. I

shall, forever, remember his encouragement and help towards me during the entire course

of work.

I shall also like to express my sincere gratitude to Prof. M. Ram Gopal for his

guidance, assistance and valuable suggestions in various phases of my work. I will

remember his encouragement and cooperation forever.

I like to acknowledge with deepest regard the valuable suggestions offered by

Prof. R. C. Arora, Prof. P. K. Das, Prof. M. Sarangi, T. K. Goswami and Prof. S.K. Som

through many stimulating discussions during the period of research.

I also like to express my sincere thanks to Prof. S. K. Som, Head, Department of

Mechanical Engineering and Prof. R. Bhattacharya, Ph.D coordinator, Department of

Mechanical Engineering for extending the necessary facilities to carry out the research

work.

Special thanks are due to my friends and fellow research scholars, N. Agrawal,

P. K. Satpathy, B. Tripathi, and S. Kumar for their help on innumerable occasions. I am

grateful to Ranen De, Pradip RoyChowdhury and Biswajit Majumdar, the staff members

of Refrigeration and Air-conditioning Laboratory for their help during my research work.

Page 4: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

I also like to express special thanks to material and component suppliers for their

cooperation during my experimental work. I will never forget the cooperation of Mr A.

Nandy and other workshop staff in the fabrication work.

I will remember the contributions of my hall mates and other fellow research

scholars for their strong mental support during my entire period of research in IIT

Kharagpur. I will ever remember my hall of residence, Dr. B. C. Roy Hall of Residence.

Last, but not the least by any means, in this auspicious moment, I shall forever

remember the contributions of my mother, brother, sister and my other family members

for their constant inspiration during the entire period of the work with great patience and

understanding.

Date

IIT Kharagpur Jahar Sarkar

Page 5: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

ABSTRACT

To safeguard the environment, it would be prudent to use technologies that are

eco-friendly and energy efficient. Ozone layer depletion and global warming phenomena

caused by synthetic refrigerants has brought about an increasing interest in technologies

based on ecologically safe natural refrigerants instead of continuing search for new

chemicals. Carbon dioxide is one such natural refrigerant that, although is old and was

abandoned earlier due to the invention and vigorous promotion of synthetic refrigerants,

has been revived recently as a potential candidate due to its environmental and personal

safety features. This has led to subsequent development of transcritical carbon dioxide

cycles where the condenser gets replaced by a gas cooler. Use of a gas cooler, with heat

rejection taking place over an unusually large temperature glide, offers several unique

possibilities such as simultaneous refrigeration and heating, heat pump drying, etc. Along

with eco-friendliness, CO2 based vapor compression systems have various advantages

over conventional systems such as, compatibility with normal lubricants and common

machine construction materials, non-flammability and non-toxicity, greatly reduced

compression ratio, easy availability, high volumetric refrigerant capacity, and excellent

heat transfer properties. Unique possibilities in simultaneous cooling and heating

applications along with various advantages are the main motivating factors behind the

present research work.

The main objective of this research work was to carry out theoretical and

experimental studies on CO2 heat pumps for simultaneous cooling and heating

applications. A high precision property code was developed initially based on recently

reported correlations. The transcritical CO2 cycle has been analyzed to optimize the

performance. Analyses of the optimum condition indicate that a system meant for low or

moderate temperature heating is more economical not only due to high COP but due to

lower optimum discharge pressure (low operating pressure ratio) as well. Expressions for

optimum cycle parameters have been developed and these correlations offer useful

guidelines for optimal system design. Effects of several cycle modifications such as

i

Page 6: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

internal heat exchange, multi-staging, use of expansion turbine and ejector-expander

device on optimum condition, have been studied. Results showed that multi-staging has

more significant effect than other modifications. The simulation code of CO2 heat pump

for simultaneous water cooling and heating applications including heat transfer and fluid

flow effects in each component has been developed and the energetic and exergetic

performances with different operating parameters at optimum discharge pressure have

been obtained. Gas cooler to evaporator heat transfer area ratio has been optimized as

well. A nomogram suitable for optimum design has been presented. Exergy flow diagram

has been presented and techniques to reduce the irreversibility for various components,

which yield improved system exergetic efficiency, have been suggested. The expansion

valve contributes a significant amount of exergy loss here whereas it is negligible for a

conventional system. Replacement of expansion valve with a turbine will increase the

COP as well as the exergetic efficiency significantly, but it will also raise issues related to

cost, design and dynamic balancing of the system. Detailed exergetic analyses of the gas

cooler and evaporator of CO2 heat pumps have been studied to obtain optimum sets of

diameter, length and tube passes for given operating conditions and capacity, to get

minimum total irreversibility associated with operational (thermal, pressure drop),

material and manufacturing stages. Although the effect of pressure drop on the

irreversibility can be neglected for higher diameter, it is quite significant for smaller

diameter tubes. Such exergetic optimization exercise is expected to help design the

optimal heat exchanger for a given capacity and the operating parameters.

The thermodynamic comparison of R744 with R134a and R22 has been carried

out for heat pump drying applications, which showed that R744 exhibits better

performance than R134a whereas it performs poorer compared to R22. Then a simulation

model of CO2 heat pump dryer including heat and mass transfer, and pressure drop in

each component has been developed and validated with experimental data available in the

literature and showed fairly good agreement. Finally, effects of different operating

parameters such as bypass air ratio (BAR), ambient temperature and relative humidity,

dryer efficiency (DE), recirculation air ratio (RAR) and air mass flow rate on COP, MER

and SMER have been investigated. Results show that unlike BAR and ambient relative

ii

Page 7: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

humidity, the effects of DE, RAR, ambient temperature and air mass flow rate are

significant on system behavior.

A fully instrumented prototype of CO2 heat pump for simultaneous water cooling

and heating has been developed and tested. The gas cooler pressure has been successfully

controlled by simultaneously controlling the total mass of the system and degree of

opening of expansion device. Uncertainty analyses show that the test data is fairly good.

Results of transient analysis and performance with different operating conditions (water

mass flow rates and inlet temperatures, pressures, valve opening, etc.) have been

presented. The valve opening has significant effect near the valve closing condition.

Effect of water mass flow rates is not significant for both evaporator and gas cooler,

whereas the effect of water inlet temperature to gas cooler on the system performance is

significant. Compressor performance results have been presented as well. Recently

available correlations for heat transfer and pressure drop, used in the theoretical analyses,

have been validated by test data obtained from the experiments and showed reasonable

agreement for both gas cooler and evaporator. Comparison between test results and

simulation model prediction has been presented as well and shows reasonable agreement

and the trends are fairly similar. Finally based on the theoretical and experimental work,

several conclusions have been drawn and recommendations have been made for future

studies.

iii

Page 8: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

iv

Page 9: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

TABLE OF CONTENTS Certificate

Acknowledgements

Abstract i

List of figures x

List of tables xiii

Nomenclatures xiv

1. Introduction 1

1.1 Motivation 1

1.2 Carbon dioxide as a refrigerant 2

1.2.1 Background 2

1.2.2 Comparison with other refrigerant 6

1.2.3 Present status of CO2 systems 8

1.3 Thesis objective and contribution 9

1.4 Structure of the thesis 11

2. Literature review 13

2.1 Introduction 13

2.2 Transcritical vapor compression cycle of CO2 13

2.3 CO2 cycle with modifications 17

2.3.1 Internal heat exchange cycle 17

2.3.2 Expansion with work recovery 17

2.3.3 Multistage cycle 18

2.3.4 Flash gas bypass 18

2.3.5 Ejector-expansion cycle 19

2.4 Refrigerant mixtures with CO2 19

2.5 Supercritical CO2 heat transfer and pressure drop 20

2.6 Two-phase heat transfer and fluid flow of CO2 22

2.7 High pressure related issues 25

v

Page 10: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.7.1 Issues related to component design 26

2.7.2 High pressure safety issues 27

2.8 Component design 28

2.8.1 Compressor 28

2.8.2 Gas cooler 30

2.8.3 Internal heat exchanger 32

2.8.4 Evaporator 33

2.8.5 Other components 34

2.9 Application areas 35

2.9.1 Automotive air-conditioning 36

2.9.2 Automotive heating 38

2.9.3 Residential cooling 39

2.9.4 Residential heating 39

2.9.5 Water heating 41

2.9.6 Environmental control unit 42

2.9.7 Refrigeration applications 43

2.9.8 Simultaneous cooling and heating 44

2.9.9 Heat pump dryers 45

2.10 Summary 45

3. Optimization of transcritical CO2 cycles 47

3.1 Introduction 47

3.2 Property code development 48

3.2.1 Some of the important features of CO2 property 49

3.3 Optimum compressor discharge pressure 51

3.4 Thermodynamic cycle optimization 53

3.4.1 Process analysis and simulation 53

3.4.2 Results and discussion 57

3.4.3 Correlations for optimum conditions 66

3.5 Effect of cycle modifications on optimum discharge pressure 68

3.5.1 Internal heat exchanger 68

3.5.2 Expansion with work recovery 68

3.5.3 Multi-staging 69

vi

Page 11: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3.5.4 Ejector-expansion device 70

3.6 Summary 71

4. Simulation of transcritical CO2 heat pump for simultaneous cooling and heating

4.1 Introduction 73

4.2 Mathematical modeling 75

4.2.1 Compressor 76

4.2.2 Gas cooler 76

4.2.3 Evaporator 78

4.2.4 Internal heat exchanger 80

4.2.5 Expansion device 81

4.2.6 Performance parameters 81

4.3 Numerical procedure and input parameters 83

4.4 Results of energy analysis 85

4.5 Results of exergy analysis 91

4.6 Improvement of exergetic efficiency 96

4.6.1 Compressor 97

4.6.2 Evaporator and gas cooler 97

4.6.3 Expansion device 98

4.7 Summary 98

5. Exergetic optimization of heat exchangers for transcritical CO2 heat pumps

5.1 Introduction 101

5.2 Total irreversibility analysis 102

5.3 Mathematical Modeling and Numerical Simulation 104

5.4 Heat transfer and pressure drop correlations 105

5.4.1 Gas cooler (refrigerant side) 105

5.4.2 Evaporator (refrigerant side) 106

5.4.3 Waterside heat transfer and pressure drop 107

5.5 Results and discussion 107

5.5.1 Exergetic optimization of gas cooler 108

5.5.2 Exergetic optimization of evaporator 112

5.6 Summary 115

vii

Page 12: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

6. Transcritical CO2 heat pump dryer 116

6.1 Introduction 116

6.2 Thermodynamic evaluation 117

6.2.1 Thermodynamic cycle and its modeling 117

6.2.2 Numerical procedure 120

6.2.3 Result and discussion 120

6.3 Transcritical CO2 heat pump dryer systems 123

6.4 Mathematical modelling 124

6.4.1 Compressor model 124

6.4.2 Gas cooler model 125

6.4.3 Evaporator model 127

6.4.4 Expansion device model 130

6.4.5 Dryer Model 130

6.4.6 Fan model 131

6.4.7 Air and CO2 properties 131

6.4.8 Performance criteria of heat pump dryers 132

6.5 Numerical simulation 132

6.6 Model validation with experimental data 134

6.7 Simulation results 137

6.7.1 Effect of bypass air ratio (BAR) 138

6.7.2 Effect of dryer efficiency (DE) 140

6.7.3 Effect of re-circulation air ratio (RAR) 141

6.7.4 Effect of ambient temperature 143

6.7.5 Effect of ambient relative humidity 144

6.7.6 Effect of air mass flow rate 146

6.8 Summary 147

7. Experimental study of a CO2 heat pump 149

7.1 Introduction 149

7.2 Component Design and description 149

7.2.1 Compressor 150

7.2.2 Expansion device 151

7.2.3 Evaporator 152

viii

Page 13: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

7.2.4 Gas cooler 153

7.2.5 Separator 154

7.2.6 Receiver 156

7.2.7 Condensing unit 156

7.2.8 Water re-circulation loop in evaporator 156

7.2.9 Tubing and fittings 157

7.3 Test facility and test procedure 157

7.4 Data reduction 159

7.5 Results and discussion 163

7.6 Validation of heat transfer and pressure drop correlations 169

7.7 Validation of system simulation 171

7.8 Summary 172

8. Conclusions and recommendation for future work 175

8.1 Conclusions 175

8.2 Recommendation for future work 178

Appendix A 180

Appendix B 182

References 183

ix

Page 14: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

List of Figures

Figure 1.1 Comparison in term of probable application ranges Figure 2.1 Pressure-enthalpy diagram of transcritical CO2 cycle Figure 3.1 Phase diagram of carbon dioxide Figure 3.2 Variation of isobaric heat capacity with temperature Figure 3.3 Prandtl number of CO2

Figure 3.4 System schematic diagram transcritical CO2 heat pump Figure 3.5 Heat pump cycle on the P-h plane for various gas cooler pressures

Figure 3.6 Transcritical CO2 heat pump cycle on T-s plane Figure 3.7 Variation of maximum system COP and optimum discharge pressure with

evaporator temperature Figure 3.8 Variation of maximum system COP and optimum discharge pressure with cooler

outlet temperature Figure 3.9 Maximum system-COP contour (0.5 increment of iso-lines) Figure 3.10 Optimum discharge pressure contour (in bar) Figure 3.11 Gas cooler inlet temperature (oC) at optimum discharge pressure contour (0.5

increment of iso-temperature lines) Figure 3.12 Variation of second law efficiency with discharge pressure for different

evaporator temperatures Figure 3.13 Variation of second law efficiency with discharge pressure for different gas

cooler exit temperatures Figure 3.14 Variation of percentages of irreversibility of different components with discharge

pressure Figure 3.15 Energy and exergy flow diagram Figure 3.16 Multi-staging with flash gas inter cooling Figure 3.17 Schematic diagram of CO2 cycle with ejector-expansion device Figure 3.18 P-h diagram of transcritical CO2 cycle with ejector-expansion device Figure 4.1 Schematic layout of a transcritical carbon dioxide system for simultaneous water

cooling and heating Figure 4.2 Corresponding T-s diagram of transcritical CO2 heat pumps Figure 4.3 A computational Segment of gas cooler Figure 4.4 Flow-chart for the simulation model Figure 4.5 Variation of refrigerant-side heat transfer properties with bulk temperature in gas

cooler Figure 4.6 Variation of performance with area ratio Figure 4.7 Variation of optimum discharge pressure and mass flow rate with area ratio

x

Page 15: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 4.8 Variation of system performance with area ratio and discharge pressure Figure 4.9 Variation of performance with compressor speed Figure 4.10 Variation of performance with water inlet temperature Figure 4.11 Variation of optimum pressure and mass flow rate with water inlet temperature Figure 4.12 Design nomogram for a carbon dioxide based heat pump Figure 4.13 System performances with varying heat exchanger area ratio Figure 4.14 Variation of component irreversibility with heat exchanger area ratio Figure 4.15 Influence of heat exchanger area ratio on irreversibility due to pressure drop Figure 4.16 System performance with varying water inlet temperature Figure 4.17 Variation of component irreversibility with water inlet temperature Figure 4.18 Effect of compressor speed on system performance Figure 4.19 Exergy flow (Grassmann) diagram at mean operating condition Figure 4.20 System performances with varying compressor isentropic efficiency Figure 4.21 System performances with varying total heat exchanger length Figure 5.1 Total irreversibility (in W) of a 2-pass gas cooler Figure 5.2 Total irreversibility ( in ) of a 5-pass gas cooler WFigure 5.3 Irreversibility ratios in a 5-pass gas cooler Figure 5.4 manI (in W) contours for a 5-pass gas cooler

Figure 5.5 Total irreversibility (in W) of 2-pass evaporator Figure 5.6 Total irreversibility (in W) of a 5-pass evaporator Figure 5.7 Irreversibility ratios in a 5-pass evaporator Figure 5.8 manI (in W) contours for a 5-pass evaporator

Figure 6.1 Thermodynamic cycle of air in closed HPD Figure 6.2 T-s diagram of R22 & R134a heat pump dryer cycle Figure 6.3 T-s diagram of R744 heat pump dryer cycle Figure 6.4 Schematic diagram of a CO2 based heat pump dryer system Figure 6.5 Transcritical CO2 heat pump cycle on P-h plane Figure 6.6 Air cycle on a psychrometric chart Figure 6.7 A computational segment of cross-flow gas cooler Figure 6.8 Different heat transfer zones in the evaporator Figure 6.9 A computational segment of the wet region in an evaporator Figure 6.10 Flowchart of the entire air and refrigerant loop simulation

Figure 6.11 Air cycle with the results obtained by Klocker et al. [100] Figure 6.12 Effect of BAR on system performance Figure 6.13 Effect of dryer efficiency on COP, MER and SMER

xi

Page 16: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 6.14 Effect of re-circulation air ratio on COP, MER and SMER; At RAR = 0, heating COP = 4.3, MER = 7.558 kg/h, SMER = 2.905 kg/kWh

Figure 6.15 Effect of RAR on air conditions at dryer inlet Figure 6.16 Effect of ambient temperature on MER and SMER Figure 6.17 Effect of ambient temperature on dryer inlet temperature and COP Figure 6.18 Effect of ambient relative humidity on MER and SMER Figure 6.19 Effect of ambient relative humidity on dryer inlet temperature and COP Figure 6.20 Effect of air mass flow rate on SMER and COP Figure 7.1 A fully instrumented CO2 heat pump test facility for simultaneous water cooling

and heating Figure 7.2 Swagelok Integral Bonnet Needle Valve (Courtesy: Swagelok) Figure 7.3 Design layout of evaporator Figure 7.4 Design layout gas cooler Figure 7.5 Insulated gas cooler Figure 7.6 (a) receiver, (b) separator Figure 7.7 Prototype of transcritical CO2 heat pump Figure 7.8 Experimental setup with full instrumentation Figure 7.9 Calculation of heat loss from connecting tube Figure 7.10 Repeatability analysis for Pev = 35 bar Figure 7.11 Repeatability and uncertainty data for Pev = 40 bar Figure 7.12 Transient behaviors at the starting of system Figure 7.13 Suction and discharge pressure and mass flow rate with varying expansion valve

opening Figure 7.14 Variation of cooling and heating output with discharge pressure for suction

pressure of 35 bar Figure 7.15 Variation of cooling and heating output with discharge pressure for suction

pressure of 40 bar Figure 7.16 Variation of compressor isentropic efficiency with pressure ratio Figure 7.17 Variation of system performance with water flow rate in gas cooler Figure 7.18 Variation of system performance with water flow rate in evaporator Figure 7.19 Variation of cooling COP with water inlet temperature in gas cooler Figure 7.20 Heat transfer coefficient of CO2 in gas cooler Figure 7.21 Predicted versus measured pressure drop of CO2 in gas cooler Figure 7.22 Boiling heat transfer coefficient of CO2 versus vapour quality Figure 7.23 Validation of numerical results against experimental data

xii

Page 17: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

List of Tables Table 1.1 Comparison with other refrigerants

Table 2.1 Recent transcritical heat transfer correlations for CO2 cooling

Table 2.2 Summary of experimental investigation on flow boiling of CO2

Table 6.1 Performance Comparison for R22, R134a and R744 HPD

Table 6.2 Component irreversibilities

Table 6.3 Comparison of numerical results with experimental data

Table 7.1 CO2 compressor specifications

Table 7.2 Test matrix

xiii

Page 18: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Nomenclatures A heat transfer area (m2)

pc isobaric specific heat (kJ/kgK)

C irreversibility in different stages of material processing (MJ/kg or MJ/m)

d inner tube diameter (m)

D outer tube diameter (m)

dw water film thickness (m)

E exergy (kW) *e specific exergy output (kJ/kg)

,f ξ friction factor

g gravitational acceleration (m/s2)

G mass flux or mass velocity (kg/m2s)

h specific enthalpy (kJ/kg)

hfg latent heat of vaporization (kJ/kg)

i specific irreversibility (kJ/kg)

I irreversibility (kW)

k thermal conductivity (kW/mK)

L heat exchanger tube length (m)

dcL depth of coil (m)

LMTD log mean temperature difference (K)

m mass flow rate (kg/s)

M material mass (kg), molecular mass (kg/kmol)

n number of pass

N compressor speed (rpm)

Nu Nusselt number

P pressure (bar)

Pr Prandtl number

q specific heat transfer (kJ/kg), heat flux (kW/m2)

Q heat transfer rate (kW)

R ideal gas constant (kJ/kgK)

xiv

Page 19: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Re Reynold number

RH relative humidity (%)

pr compressor pressure ratio

s specific entropy (kJ/kgK)

fs fin spacing (m)

St Stanton number

T,t temperature (K or oC)

0T reference temperature (K)

dT dew point temperature (K or oC)

ft fin thickness (m)

rst tube row spacing (m)

UA product of overall heat transfer coefficient and area (kW/K)

v specific volume (m3/kg)

cV volumetric capacity ( 3mkJ )

sV swept volume of compressor (m3)

w specific work (kJ/kg)

W work, power (W)

x vapour quality

Greek symbols

α heat transfer coefficient (kW/m2K)

mα mass transfer coefficient (kg/m2s)

ε heat exchanger effectiveness

ρ density (kg/m3)

µ dynamic viscosity (Ns/m2)

η efficiency

sη surface effectiveness

vη volumetric efficiency

xv

Page 20: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

isη isentropic efficiency

IIη second law (exergetic) efficiency

T∆ finite temperature difference (K)

P∆ pressure drop (bar)

ω specific humidity (kg/kg d.a.)

σ surface tension (N/m)

τ dimensionless temperature difference

θ angular portion (rad)

Subscripts

1… state points

1a-6a air state points

a air

ai air in one pass

am moist air

amb ambient

as asbestos

b bulk properties

c core

cr critical

comp compressor

d dew point, dryer

dis discharge

ef external fluid

exp expansion device

ev evaporator

evr refrigerant in evaporator

evw water in evaporator

f fin, foam

F fan

fab fabrication

gc gas cooler

xvi

Page 21: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

gcr refrigerant in gas cooler

gcw water in gas cooler

i inner, inlet

ihx internal or suction heat exchanger

ins insulation

l saturated liquid

m measured, mechanical

man related to manufacturing

nb nucleate boiling

o outer, outlet

oper operation

opt optimum

p primary material, outer tube wall

pc pseudocritical

Pr Prandtl number

r, ref refrigerant

ri refrigerant in one pass

rw refrigerant at wall temperature

suc suction

sys system (combine heating and cooling)

t tube

tp two-phase

v,g saturated vapour

w water, water surface

wi water inlet

wo water outlet

Subscripts

i computational segment

T∆ finite temperature difference

P∆ pressure drop

xvii

Page 22: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

xviii

Page 23: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 1

INTRODUCTION

1.1 Motivation

Refrigeration, heat pump and air conditioning systems play an important role in

modern civilization. Environmental control is one of the major requirements of a healthy

and non-pollutant living condition. Hence the prudent strategy would be to use advanced

technologies that are eco-friendly. Over the last few decades, refrigeration, air-

conditioning and heat pump industries have seen major changes caused by restrictions on

specific refrigerant use due to their detrimental effects on our climate. Two successive

international agreements; Montreal Protocol and Kyoto Protocol were introduced to

combat the twin menace of ozone layer depletion and global warming. The Montreal

Protocol (MP) on substances that deplete the ozone layer was adopted in September 1987

to phase-out the use of Ozone Depleting Substances (ODSs) within a fixed time period.

Ozone depleting Potential (ODP), a comparative measuring index, is fraction of the

ozone depleting potency of a substance compared to that of R11 or R12. Kyoto Protocol

(KP) was adopted at the third conference of parties to the United Nations Framework

Convention on Climate Change (UNFCCC) in December 1997, which has imposed

restrictions on refrigerants on the basis of GWP. Global warming Potential (GWP) is an

index that relates the potency of green house gas to the CO2 emission over a 100-year

period. The CFC refrigerants, although once considered to be the best refrigerants, were

abandoned due to high ODP. The chlorine free synthetic refrigerants based on HFCs,

which were taken as permanent replacement of CFCs, are also in the list of regulated

substances due to their considerably high GWP.

In this situation, industries are obviously looking for long-term solution for

refrigerant related problems. This has triggered a large number of innovative studies to

develop new technologies. Instead of continuing search for new chemicals, there is an

increasing interest in technologies based on ecologically safe natural refrigerants, i.e. air,

1

Page 24: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

water, noble gases, ammonia, carbon dioxide and hydrocarbons. In principle, it must be a

much better solution to use naturally occurring substances as refrigerants; these are

compounds already circulating in large quantity in the biosphere and which we know are

harmless. Because of non-toxicity and non-flammability, carbon dioxide offers both

environmental and personal safety.

Although carbon dioxide is an old refrigerant, it was abandoned earlier after the

discovery of synthetic refrigerants. Now due to harmful effects of the synthetic

refrigerants on the environment, it has been revived as a potential refrigerant by the

seminal work of Lorentzen [1-3] in 1994. This has inspired subsequent development of

transcritical carbon dioxide cycles where the condenser gets replaced by a gas cooler.

Due to the low critical temperature of CO2, the gas cooler is operated above the critical

pressure and the evaporator is operated below that; hence the cycle is called transcritical

cycle. These systems have strong potential in two sectors: i) automotive air-conditioning

and ii) heat pumps. It was found that the use of a gas cooler with heat rejection taking

place over an unusually large temperature glide offers several unique possibilities such as

simultaneous refrigeration and hot water heating/steam production, heat pump drying,

simpler control of capacity, etc. Along with eco-friendliness, CO2 based vapor

compression systems have various advantages over conventional systems such as,

compatibility with normal lubricants and common machine construction materials, non-

flammability and non-toxicity, greatly reduced compression ratio, easy availability, high

volumetric refrigerant capacity, and excellent heat transfer properties. Several unique

application possibilities along with various advantages motivated the huge research work

and industrial innovation recently in this area.

1.2 Carbon dioxide as a refrigerant

1.2.1 Background

This section outlines the invention, decline, and reinvention of carbon dioxide as a

refrigerant. The role of carbon dioxide in refrigeration systems goes back well over a

century and possibly had the largest impact on early food refrigeration and human

2

Page 25: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

occupied space air conditioning. Though the Evans-Perkins process, upon which modern

refrigerator and air conditioners are based, was developed in 1834, it was in 1866 when

Thaddeus S.C. Lowe first harnessed carbon dioxide for ice production in his British

Patent, although Alexander Twining first proposed CO2 as a refrigerant in his British

Patent [4] in 1850. Following a period of further development, Carl Linde build the first

CO2 machine in 1881 in Europe. W. Raydt first developed compression ice-making

system using carbon dioxide in 1884. The carbon dioxide compressor was built by

Windhausen of Germany in 1880 and was awarded a British patent. Other landmark uses

of carbon dioxide refrigeration was made by Britain company J & E Hall, who had

purchased the Patent right in 1887 and after further development of technology, they first

installed a carbon dioxide based marine plant in 1890 and the first continuous production

of carbon dioxide refrigerating equipment was started in USA in 1897. In the field of

marine applications, CO2 dominated as a refrigerant in the first half of 20th century. Not

only were carbon dioxide based machines were growing in numbers in the late 1800s, but

improvements were continually being made as well on the basic cycle. J & E Hall

demonstrated that the efficiency of the vapour compression process could be improved

through the use of two-stage compression and made the first two-stage CO2 machine in

1889. In 1905, Voorhees developed what is now known as the multiple effect cycle,

which involves a separation of liquid and vapour at an intermediate stage in the

expansion process.

The advent of refrigeration and air conditioning in the late 1800s had an

enormous impact on thousands of industries. In Europe CO2 machines were often the

only choice at that time. In United States, CO2 was used in refrigeration systems from

about 1890 and in comfort cooling from about 1900. Carbon dioxide was used with brine

distribution for most ship installations and also in many stationary ones. Until about

1940, along with carbon dioxide, ammonia was used for medium and large stationary

systems and also sometimes in ships, often with brine as a secondary refrigerant, but

increasingly with direct cooling. Sulphur dioxide was used as well for household

equipment and small commercial applications, but occasionally for capacities up to

several hundred kW. But use of ammonia and sulphur dioxide was being limited in

3

Page 26: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

industrial applications owing to their toxicity and/or flammability. No such hazard is

inherent in carbon dioxide and hence food-related industries, food markets, kitchens,

restaurants and places of human occupancy such as passenger ships, hospitals, theatres

and restaurants used carbon dioxide based refrigerator/ air conditioning systems almost

extensively. Most of these systems used calcium chloride solutions as a secondary

refrigerant. Compressors were slow running single or double acting cross head machines

with atmospheric crankcase pressure and expansion valves were usually manual-control

type. Condensers were often water-cooled double pipe units [4]. Though they used

technology ancient by current standards, carbon dioxide machinery functioned

satisfactorily.

Although, the safety compared to refrigerants like NH3 and SO2 gave a preference

on refrigeration and air conditioning applications, CO2 suffered from some

disadvantages. The commonly reported disadvantage of CO2 was loss of capacity and

low COP at high heat rejection temperatures, especially in warm climates. Refrigerant

containment at high pressure was difficult with the sealing technology available at that

time. Only one modification has been proposed that time to reduce the capacity and COP

loss by using various two-stage arrangements. However, these perceived demerits of CO2

influenced people to search for new refrigerants, which are safe, have high capacity and

COP at high discharge temperatures and can be operated at low pressures. This resulted

in the introduction of fluorocarbons in 1930s.

In the 1930s-1940s the fluorocarbon-based refrigerants were introduced with a massive advertisement campaign and quickly took over a large part of market. High pressure containment problems, capacity and efficiency loss at high discharge temperature, aggressive marketing of CFC products, low cost tube assembly in competing systems, and a failure of CO2 system manufacturers to improve and modernize the design of systems and machineries are the probable reasons behind the decline of CO2. Carbon dioxide was phased out by the 1950s. Only ammonia has remained the preferred refrigerant in the large industrial machines. While all other conventional fields became completely dominated by the various types of CFCs and HCFCs. The main argument put forward in the propaganda were their complete safety and environment friendliness. Both these claims have turned out to be wrong. Damage to stratospheric

4

Page 27: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

ozone layer has led to the Montreal Protocol and universal banning of most CFC and HCFC compounds. This has forced refrigeration engineers to search for new refrigerants such that there is no degradation of performance compared with that of proven CFC and HCFC technology. HFCs are presently used in newly produced refrigeration and air conditioning systems. HFCs are substances with zero ODP, and which exhibit thermal and transport properties similar to CFCs and HCFCs. Hence this new class of fluids may be used with machinery already designed for CFCs and HCFCs with minor modifications. R134a is one of the HFC refrigerants extensively used in automobile air conditioning. But R134a may be decomposed by sunlight in the troposphere resulting in formation of acid and poisonous substances. So similar predicaments have occurred from the release of many other new chemicals to the environment. In this situation it does not seem very sensible to replace the CFC/HCFCs with a new family of related hydrocarbons, equally foreign in nature, to be used in quantities of hundreds of thousands of tons every year, and hence the whole industry was searching for viable refrigerant alternatives.

In principle, it must be a much better solution to use naturally occurring substances as refrigerants; these are compounds already circulating in large quantities in the biosphere and which we know are harmless. Carbon dioxide is one such naturally available old refrigerant, which has been completely abandoned for more than 40 years, and is arguably the best future refrigerant both in air conditioning and heat pump applications due to its environmentally benign nature. In the early 1990s, Norwegian Professor Gustav Lorentzen proposed a transcritical carbon dioxide cycle where the high side pressure can be controlled by throttling valve. Main difference between this cycle and conventional cycle is that heat rejection occurs in supercritical regimes due to very low critical temperature (31.2 oC) and the condenser gets replaced by a gas cooler. Automobile air-conditioning, a sector that dominated the global CFC emissions, is one of the intended applications of this system, along with applications where non-toxic and non-flammable refrigerants are needed. The potential for more compact components due to high pressure was also another interesting feature. In 1993, Lorenten and Petersen published experimental data on a prototype CO2 system for automobile air-conditioning and comparison was made with a state of the art R12 system with equal heat exchanger dimensions and design point capacity [1]. They showed that the number of practical factors made the efficiencies of two systems nearly equal, although simple cycle calculation indicated lower COP for CO2 system. Based on their results the interest in

5

Page 28: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

CO2 as refrigerant increased considerably in nineties and number of developments and projects were initiated by research sector and industries in European countries and USA [5].

1.2.2 Comparison with other refrigerants

Table 1.1 shows the comparison of CO2 with other pure refrigerants. Although the

normal boiling point is low (– 78.4 oC), CO2 cannot be used down to that temperature due

to higher triple point temperature (– 56.6 oC). The main difference with other refrigerants

is the low critical temperature with comparatively higher critical pressure of CO2, which

is responsible for very high system pressure compared to others. However this gives an

advantage of very high volumetric capacity compared to others, which can lead to a

compact design. Due to a gliding temperature in the gas cooler, carbon dioxide can be

effectively used in heat pump applications. This offers very wide application ranges

compared to others as shown in Figure 1.1. Although the subcritical cycle of CO2 is

applicable to only low temperature applications, the transcritical CO2 cycle can cover

cooling up to – 50 oC and heating up to 120 oC approximately.

Table 1.1 Comparison with other refrigerants [2, 6, 7]

Refrigerants R22 R134a R717 R290 R600a R744 Chemical formula CHClF2 C2H2F4 NH3 C3H8 C4H10 CO2 Molecular. Weight 86.48 102.03 17.03 44.1 58.0 44.01 N.B.P., °C – 40.80 – 26.15 – 33.35 – 42.10 – 11.60 – 78.40 Triple point, °C – 160.0 – 96.6 – 77.7 – 187.1 – 159.6 – 56.6 Critical Pressure, bar 49.88 40.56 112.97 42.52 36.40 73.72 Critical Temp., °C 96.0 101.1 113.0 96.8 134.7 31.1 Sat. Pr. (0°C), bar 4.976 2.929 4.304 4.712 1.564 34.80 ODP 0.05 0.0 0.0 0.0 0.0 0.0 GWP* 100 years 20 years

1500 4100

1200 3100

0.0 0.0

0.0 0.0

0.0 0.0

1(0)** 1(0)

Flammable or Explosive? No No Yes Yes Yes No

Toxicity Yes Yes Yes No No No Vol ref. capacity at 0°C (kJ/m3) 4344 2860 4360 3870 1509 22600

6

Page 29: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

* Global warming potential in relation to CO2 with 20 and 100 years integration time (IPCC 1990, 1992) ** Abundant amounts of CO2 are recovered from waste gas. Thus the effective GWP of commercial carbon dioxide, for instant use as refrigerant is 0.

-60

-40

-20

0

20

40

60

80

100

120

140

Refrigerant

Tem

pera

ture

, o C

R22 R

134

Am

mon

ia

Prop

ane

Isob

utan

e

Car

bon

diox

ide

Figure 1.1 Comparison in terms of probable application ranges

Benefits of CO2 as a refrigerant are summarized below:

1. It has a background of successful use as a refrigerant.

2. It is compatible with normal lubricants and common machine construction

materials.

3. It is nonflammable and non-toxic. Maximum short- and long-term exposure limits

are comparable to, or better than, those of CFCs and their replacements.

4. Greatly reduced compression ratio compared with conventional refrigerant.

5. Carbon dioxide has easy availability everywhere and is independent of any supply

monopoly.

6. Simple operation and service, no ‘recycling’ required, very low price.

7. Weight and space requirement of the components of CO2 based system will be

reduced due to its high volumetric refrigerant capacity (Table 1.1).

7

Page 30: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

8. All properties and characteristics of carbon dioxide are well known and

thoroughly documented. Further toxicity testing is not required.

9. CO2 has zero ozone depletion potential (ODP) and zero effective GWP, the latter

because more than sufficient quantities of CO2 are recovered from industrial

waste gas, e.g., in oil refineries or ammonia production plants. As a natural

constituent of the biosphere, CO2 will not have any unexpected long-term effects

on health or the environment.

10. Applicable temperature ranges are wider than other pure refrigerants.

1.2.3 Present status of CO2 systems

Not only in transcritical cycle, attempts have also been made within the last

decade to use CO2 as a secondary fluid or as a bottoming (subcritical) cycle refrigerant in

cascade system with other natural refrigerants in food related applications due to its good

heat transfer properties. The cascade systems with carbon dioxide and propane as

refrigerants were recently implemented in a small supermarket in Denmark. Dutch people

also started use of CO2 based cascaded systems in restaurants and food freezing. In 2003,

Grenco B.V. of the Netherlands introduced NH3-CO2 based cascade system for freezing

applications. Jointly with Kansai Electric Power Co., Mayekawa Mfg. Co. of Japan has

also developed an ultra-low temperature cascade system and have satisfactorily

completed test run on an 80 kW demonstration unit employing CO2 in the LT side and

NH3 in the HT side. In 2002, Stellar Group of USA installed the largest CO2/NH3

cascade system in the world. Such systems have garnered renewed interest in the

perishable food industry for cold storage and freezing applications based on their cost

effectiveness and operating features.

Denso of Japan first used transcritical cycle of CO2 and developed heat-pump hot-

water supply unit ‘EcoCute’. Shecco Technology, a core technology for ‘EcoCute’

owned by Norsk Hydro, is responsible for promoting this technology worldwide,

focusing also on the commercialization of the technology in car air-conditioning

equipment and vending machine in Japan, USA and Europe. Since 1995, SINTEF and

Denso had been developing this technology together, and then Denso managed to

8

Page 31: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

commercialize it. Coca Cola and Kirin is in testing phase of CO2 based vending machine,

and planning commercial rollout in selected countries. Denso has developed first CO2 air

conditioning system. Visteon of Europe developed car air-conditioning system using CO2

as refrigerant. Nissan Motor Co., Ltd. is willing to launch the fuel cell vehicles (FCVs)

equipped with an CO2 air-conditioning system, jointly developed by Nissan and Calsonic

Kansei Corp. Danfoss A/S and Hydro Alunova have established a joint venture to

develop a new generation of aluminium tubes for use in automotive air conditioning

systems. Denso and DaimlerChrysler AG are working together to develop a carbon

dioxide air conditioning system for a Mercedes vehicle. Sanyo and Danfoss are main

suppliers of CO2 hermetic compressors. Tecumseh, USA has also developed its own CO2

compressor. Mitsubishi Heavy Industries Ltd developed CO2 scroll compressors for air

conditioning application. Dorin of Italy has been manufacturing semi-hermetic CO2

compressors lately [8].

1.3 Thesis objective and contribution

Besides mobile air conditioning and heat pump water heating, the transcritical

CO2 cycle offers several application possibilities such as simultaneous heating and

cooling, drying and high temperature heating. Simultaneous heating and cooling is

applicable in food processing, other process heat applications or domestic applications

with various heating and cooling combinations. Even though there has been considerable

prior research done in the area of cycle analysis, component design, application areas and

control scheme development for transcritical CO2 system, there appears to be some

uncharted areas in thermodynamic analysis, system simulation, exergy analysis of

components and application fields. The present research work is concentrated on

optimization of cycle and components, and detailed theoretical and experiments studies

on simultaneous cooling and heating applications.

9

Page 32: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

The major contributions of the present work are:

• Accurate thermophysical and transport property code development for CO2

• Transcritical CO2 cycle optimization and studies on effect of various cycle

modifications

• Simulation and optimization of CO2 heat pump for simultaneous heating and cooling

application, and system irreversibility analysis

• Exergetic optimization of heat exchangers for CO2 heat pumps

• CO2 heat pump dryer simulation, validation with experimental data and optimization

• Experimental validation of heat transfer and pressure drop correlations

• Experimental study on CO2 heat pumps and validation of simulation model

The main objective of this research is theoretical end experimental study of CO2

heat pumps for simultaneous cooling and heating. For theoretical analysis, a complete

property code has been developed for thermophysical and transport properties of CO2.

The detailed thermodynamic optimization of transcritical CO2 cycle has been carried out

and effect of cycle modifications on it has been studied. The CO2 heat pumps with

internal heat exchanger have been simulated to study its performance for simultaneous

water heating and cooling applications Energetic and exergeric optimization of such

systems have been done as well. A prototype heat pump including a well instrumented

test loop has been developed; performance tests have been conducted and the results from

mathematical models have been validated with these experimental results. Experimental

validation of available heat transfer and pressure drop correlations in both gas cooler and

evaporator have been carried out.

The exergetic optimization of evaporator and gas cooler is another aspect of this

research work. One of objectives is to model a CO2 heat pump dryer system, followed by

experimental validation and the study of performance characteristics. Since the

transcritical CO2 cycle is different from other refrigerant-based cycles, it is quite

interesting how the CO2 heat pump dryer behaves. Two process applications:

simultaneous water cooling and heating, and heat pump drying, are the areas where such

a research study could be beneficial to agro-based industries.

10

Page 33: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

1.4 Structure of the thesis

After motivation, brief introduction on carbon dioxide as a refrigerant is presented

in the preceding sections. The section ‘carbon dioxide as a refrigerant’ includes history of

CO2 as a refrigerant, benefits and comparison with other refrigerants, and current use of

CO2 as a refrigerant in commercial applications.

The literature review is presented in chapter 2. The literature review chapter

thoroughly reviews the research efforts made on basic transcritical cycle with

modifications, heat transfer, pressure drop issues, component design and system design

issues, and application oriented progress after reinvention of CO2 as a refrigerant.

Chapter 3 first describes the complete property code development for both

thermo-physical and transport properties of CO2 and then cycle simulation model is

presented to study performance of CO2 transcritical cycle based on both energetic and

exergetic points of view. The compressor discharge pressure has been optimized and

correlations have been developed for optimum conditions. Finally the effect of cycle

modifications on the cycle performance and optimum discharge pressure has been

studied.

One application-oriented simulation is demonstrated in chapter 4. The simulation

model of CO2 heat pumps for simultaneous cooling and heating specially required for

dairy application has been developed to study the energetic and exergetic performance of

the system. Effects of various operating parameters on the system performance have been

studied. Inventory control between evaporator and gas cooler has been studied and the

compressor discharge pressure has been optimized based on simulation results. Finally

irreversibilities of various components and methods to reduce those are discussed.

Chapter 5 deals with the exergetic analysis for evaporator and gas cooler of CO2

heat pumps. The heat exchanger dimensions (tube diameters, length and pass) for both

evaporator and gas cooler have been optimized based on the life cycle irreversibilities.

11

Page 34: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Another application-oriented demonstration is given in chapter 6. After

thermodynamic comparison with other working fluids in heat pump dryer application, a

simulation model of CO2 heat pump dryer has been developed to study performance in

drying application. The simulation model has been validated with the experimental data

presented in the open literature. The simulation results have been presented to study the

effect of various operating parameters on both heat pump and dryer performances.

The detailed experimental study is presented in chapter 7. Tests on the CO2 heat

pump system for simultaneous cooling and heating have been performed to study the

system performance and component characteristics. The components have been designed

based on the simulation results presented in chapter 4. The experimental study includes

component fabrication, experimental setup, calibration, experimental procedure, data

reduction and error analysis. Comparison and validation of various correlations available

for heat transfer and pressure drop in gas cooler has been demonstrated. Similar analysis

has also been done for heat transfer and pressure drop in the evaporator. The

experimental results for the system have been presented to study the system performance

and effect of various operating parameters. Finally, simulation results presented in

chapter 4 are validated with the experimental results.

Chapter 8 summarizes the most important results and findings, the major

conclusions and recommendations the future work.

12

Page 35: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 2

LITERATURE REVIEW

2.1 Introduction

This chapter presents a survey of past transcritical CO2 cycle based refrigeration,

air-conditioning and heat pump investigations. Although CO2 was used as a refrigerant

in the early 1900s and some research activities such as modification of basic cycle and

compressors to improve the performance also were carried out; those technologies appear

rather ancient now. During several decades in the past, ground breaking changes have

been made on test facilities, instrumentation, manufacturing technique, etc. So after the

revival of CO2 as a refrigerant in transcritical cycle, researchers have started thinking

from the basics and even some old concepts and information have been employed. Hence

in this chapter, the detailed research developments of CO2 as a refrigerant with respect to

thermodynamic cycle, heat transfer, designs and application related issues will be

reviewed.

2.2 Transcritical vapor compression cycle of CO2

Compared to other refrigerants, the most remarkable property of CO2 is its low

critical temperature (31.1 oC). So a CO2 vapour compression system with normal

refrigeration, heat pump and air-conditioning temperatures will work close to and even

partly above the critical pressure (73.8 bar). Evaporation takes place at sub-critical

pressure similar to other refrigerants and heat rejection takes place at supercritical

pressure. Hence the modified vapour compression cycle for CO2 is called a transcritical

cycle, which is partly subcritical (low pressure side) and partly supercritical (high

pressure side). As the fluid above the critical temperature is treated as gas and the

temperature of CO2 in the heat rejection process is mostly above the critical temperature

due to high heat sink temperatures, the heat rejection takes place by cooling of

compressed CO2 gas at supercritical high side pressures. The heat exchanger in which

13

Page 36: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

cooling of CO2 gas takes place is called a gas cooler, which replaces the condenser of

conventional systems.

20

30

40

50

60

70

80

90

100

specific enthalpy (kJ/kg)

Pres

sure

(bar

)

cqCOPw

=

q w

Isotherm

32

14

Figure 2.1 Pressure-enthalpy diagram of transcritical CO2 cycle

In normal vapour compression systems, condensing temperature is chosen based on

coolant temperature in the condenser and corresponding saturated pressure is taken as the

condensing pressure. However, in supercritical heat rejection no saturation point exists,

so the gas cooler pressure is independent of the refrigerant temperature at gas cooler exit

(state 3 in Figure 2.1). The gas cooler pressure has marked influence on the specific

enthalpy due to the s-shape of the isotherm in supercritical region. Since the throttling

valve inlet condition determines the specific refrigeration effect, it is necessary to control

the high side pressure. Although, for conventional systems, COP decreases with increase

in pressure, the behavior is quite different in transcritical cycles [9]. In these systems, as

the pressure increases the COP increases initially and then the added capacity no longer

compensates for the additional work of compression and hence COP decreases. The

differentiation of cooling COP [= ( ) ( )1 3 2 1/h h h h− −

/ 0cCOP P

] with respect to the high side

pressure yields a maximum COP for ∂ ∂ = at pressure (P) defined by [10]:

14

Page 37: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3 2c

sT

h hCOPP

∂ ∂ = − ∂ P∂

(2.1)

This is the optimum pressure where marginal increase in capacity equals marginal

increase of work. Since this method is time consuming for actual cycles, Petersen et al.

[9] used simulation technique to optimize the high side pressure. Kauf [11] considered

component performance data and optimized the high side pressure in terms of ambient

temperature. Subsequently, Liao et al. [12] showed that the optimum pressure mainly

depends on outlet temperature of gas cooler, evaporation temperature and compressor

performance and they obtained a correlation for optimum heat rejection pressure in terms

of appropriate parameters for specific conditions, based on cycle simulation. Vaisman

[13] applied the modified cryogenic approach and showed that the maximum potential

COP is achieved when the it is equal to the product of three fundamental parameters,

density, Joule-Thomson coefficient and isobaric heat capacity determined at the

discharge pressure and ambient temperature, which is basically similar to the result

obtained from fundamental approach stated before. Srinivasan et al. [14] obtained

correlations for maximum COP and exergetic efficiency based on cycle analysis.

High-side pressure regulation can be applied to maintain the maximum COP and/or

to regulate the heating or cooling capacity. For the supercritical operation, high side

pressure is determined by the relationship between refrigerant charge (mass), inside

volume and temperature [5],

( ) (,P P v T P V m T= = ), (2.2)

As a result there are three fundamental ways to control pressure:

• Varying the refrigerant charge (m) in the high pressure side of the circuit,

• Varying the inside volume (V) of the high pressure side

• Allowing refrigerant temperature (T) to control the pressure.

The first technique is comparatively easy and common and can be achieved by

controlling the expansion valve opening. To avoid flooding or dry out of evaporator, a

different buffer system can be used for this case [5]. The inside volume of high pressure

side is varied by using a pressure vessel or cylinder of adjustable volume. The last

method is actually a passive scheme where refrigerant charge/volume conditions are

15

Page 38: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

adopted to change the pressure when temperature varies. Casson et al. [15] proposed

another innovative throttling system, which consists of a differential valve, separator and

thermostatic expansion valve to control the high side pressure optimally as well as to

control the superheat. The proposed system showed an intrinsic self-adjusting capability

that led to COP values quite close to the maximum level when a fixed suitable value of

the differential pressure is chosen, even if the temperature of the secondary fluid varies to

a large extent.

It has been shown [2,5] that the thermodynamic loss in heat rejection is higher

compared to other refrigerant based cycles due to the gliding temperature heat rejection.

This loss will reduce in water heating (or coolant with single phase heat transfer) by

proper design of the counterflow heat exchanger. This feature can be utilized in heat

pumps for tap water heating or hydronic heating systems. In applications where the

rejected heat is not of interest, the gliding temperature is not an advantage since the

average temperature of heat rejection becomes higher than necessary. For heat pump

applications, the influence of evaporator temperature on the heating capacity and heating

COP is smaller compared to that of other refrigerants, which enables the CO2 system to

maintain a high heating capacity at low ambient temperature [16]. By raising the pressure

above optimum value, increase in capacity can be obtained further. However in actual

operation this depends on factors like maximum allowable pressure, maximum motor

load and compressor temperature limitations. Where rejected heat is not needed, the

thermodynamic losses due to heat transfer can be reduced by maintaining approach

temperature as low as possible; proper heat exchanger design can give temperature

approach of a few degrees. Owing to large throttling losses in CO2 system, the cooling

COP is more sensitive to gas cooler exit temperature compared to condenser exit

temperature in case of other refrigerants [16]. The close temperature approach, obtained

in CO2 gas coolers, therefore contributes significantly to practical COP improvement.

16

Page 39: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.3 CO2 cycle with modifications

There are several reasons for modifying the basic single-stage transcritical cycle,

including improvement of COP, capacity enhancement for a given system and component

size, adaptation of the heat rejection temperature profile to given requirements and

keeping the pressure ratio and discharge temperature of the compressor within limit. In

principle, a large number of possible modifications are possible, including staging of

compression and expansion, splitting of flows, use of internal heat exchange, and work-

generating expansion instead of throttling. Lorentzen [2] outlined several modified cycles

including two-stage internal ‘subcooling’ and expander options. Research progress of

several modified CO2 cycles are presented here.

2.3.1 Internal heat exchange cycle

Due to the conflict between the increase in cooling or heating capacity and

compressor work with use of internal heat exchange in the system, the influence of the

internal heat exchange on the system overall efficiency depends on the working fluids

and operating conditions. The effect of internal heat exchange on CO2 transcritical cycle

is found to be marginal. The internal heat exchange can increase the COP by a maximum

of 7% [17]. In case of high lift application, where internal heat exchange may produce

compressor discharge temperature high enough to damage the lubricant, the internal heat

exchanger may employ a parallel-flow configuration. Boewe et al. [18] showed that the

enhancement on cycle efficiency can be a substantial 25%, because of the relatively high

irreversibility at the expansion device in the standard transcritical cycle. The internal heat

exchanger brings lower and higher side pressures close together at optimal condition,

creating opportunities for using less precise and simpler control system and strategies [5].

2.3.2 Expansion with work recovery

Another option to reduce the expansion losses is the use of a work producing

device (expander), which has potential for COP improvement. Work recovery turbine

with isentropic efficiency of 60%, may reduce contribution to total irreversibility by

17

Page 40: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

about 35% and cause an average increase of COP by 25% [17]. Heyl and Quack [19]

discussed various cycles with expanders and showed the design and results of a free-

piston expander concept. Kim et al. [5] have discussed many subsequent developments

on expander devices. Huff et al. [20] analyzed three types of expanders and carried out a

comparative study with a baseline R22 system, Due to the high pressure difference, the

effect of expander efficiency on the system COP is very significant for a CO2 system

whereas it is negligible for the R22 system. Quack et al. [21] proposed the integration of

three-stage expander in CO2 refrigeration system with two-stage compression with inter-

cooling. They installed a liquid-vapor separator between second and third stage of

expansion to get optimum performance.

2.3.3 Multistage cycle

Performance of the CO2 transcritical cycle can be improved by using multistage

compression with inter-cooling. Voorhees first introduced dual-effect CO2 compressor

[4]. By using ‘subcooling’, the COP of CO2 cycle could be improved while the capacity

increased and the necessary high pressure reduced [2]. Kim et al. [5] have pointed out

several developments on multistage cycle after 1994. These subsequent theoretical and

experimental investigations on the multistage transcritical CO2 cycles for

refrigeration/heat pump and air conditioning showed the significant performance

improvement over the basic single stage cycle.

2.3.4 Flash gas bypass

Most prototypes of CO2 systems employed small diameters with flat multi-pass

tubes in evaporator to handle high pressure without adding weight or bulk. But the

challenging problem is how to distribute the two-phase refrigerant uniformly after

expansion device into the many tube passes through the header. Under normal condition

the void fraction at the evaporator inlet exceeds 0.8 [5] and uniform distribution of liquid

and vapor is very difficult due to combined effect of surface and gravitational forces. One

option to deal with this problem is bypassing the vapor around the evaporator and

allowing only liquid to enter the multi-pass evaporator. An experimental comparison to a

18

Page 41: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

conventional direct expansion system revealed that using the flash gas bypass, the

cooling capacity and the COP improves by up to 9 and 7% respectively [22]. At the same

time, the refrigerant side heat transfer coefficient improves and the refrigerant side

pressure drop reduces significantly.

2.3.5 Ejector-expansion cycle

In transcritical CO2 cycle, regenerating expansion energy and increasing refrigerant

pressure by means of an ejector is an effective way to improving the COP. In addition,

the ejector simplifies the process of controlling the gas cooling pressure in the CO2 cycle.

The gas cooling pressure of the CO2 cycle could be controlled by changing the throat area

of ejector nozzle. Experiment showed that the COP of the car air-conditioner using the

ejector cycle was increased by 20% over the conventional cycle [23]. Li and Groll [24]

recently proposed new ejector-expansion CO2 refrigeration cycle and through theoretical

analysis showed the COP improvement to be more than 16%.

2.4 Refrigerant mixtures with CO2

One of the major operating problems of carbon dioxide as a refrigerant – high

operating pressure, can be avoided by using mixture of CO2 with other refrigerants. Groll

[25] introduced a mixture of CO2/acetone and showed that the pair can be a viable

alternative to ammonia/water in absorption compression cycle. Kim et al. [26]

numerically and experimentally investigated the autocascade refrigeration system using

zeotropic refrigerant mixtures of R744/134a and R744/290, and showed that the cooling

capacity increases whereas COP decreases with increase of CO2 mass fraction in mixture.

Mozurkewich et al. [27] studied the performance potential of CO2-cofluid refrigeration

cycle with wet compression and optimized the discharge pressures. Co-fluids (nonvolatile

absorbing liquid) considered were NMP, NPGDA, GBL and acetone. Theoretical COP

was maximized by minimization of overall entropy generation in the cycle.

19

Page 42: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.5 Supercritical CO2 heat transfer and pressure drop

Heat transfer in gas cooler tubes occurs at supercritical pressures where the thermo-

physical properties of carbon dioxide change drastically. The large variations in thermo-

physical properties cause the heat transfer coefficient to be greatly dependent on both the

local temperature and the heat flux. The variation occurs along and perpendicular to the

fluid flow direction. Since the reinvention of CO2 as a refrigerant, several investigations

have been carried out to study the heat transfer characteristics of supercritical CO2 in-

tube fluid flow. Pitla et al. [28] reviewed the supercritical heat transfer and pressure drop

characteristics of carbon dioxide in-tube flow primarily including effects of physical

factors on supercritical heat transfer and friction factor correlations. Results indicated that

there was an improvement in heat transfer when wall temperature was less than critical

temperature and bulk temperature was greater than critical temperature.

Olson [29] measured heat transfer coefficient for cooled supercritical in-tube CO2

flow in a 10.9 mm inner diameter tube and found that Gnielinski [30] correlation

overpredicted the measured coefficients, and more so when using wall-based property

data rather than bulk-based. Pettersen et al. [31] measured and correlated heat transfer of

cooled supercritical CO2 flow in 0.8 mm microchannel tubes. Standard single-phase

correlations, namely Dittus–Boelter and Gnielinski correlations, showed good

correspondence between measured and calculated heat transfer coefficient. Pitla et al.

[32,33] carried out numerical analysis and experimental validation of turbulent

supercritical CO2 in-tube cooling. Heat transfer coefficient and pressure drop were

measured for a 6.35 mm OD tube and it was concluded that a combination of extremely

high heat transfer coefficient along with low pressure drop make CO2 more attractive

than conventional refrigerants such as R22. Fang et al. [34] surveyed the in-tube heat

transfer and friction factor correlations and commented on the applicability of them to a

gas cooler. Wang et al. [35] developed a numerical model of gas cooler for comparison of

various single-phase heat transfer correlations and showed that the effective temperature

difference (ETD) expression can successfully predict the heat transfer process of

supercritical carbon dioxide rather than the conventional LMTD and ε-NTU techniques.

20

Page 43: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Liao et al. [36] experimentally investigated heat transfer from supercritical CO2

flowing in horizontal mini/micro circular tubes cooled at constant temperature and

showed that the effect of buoyancy force on supercritical CO2 cooling became significant

as the tube diameter decreased. Experimental results also indicated that the previous

correlations for large tubes deviated significantly. Based on the experimental data authors

developed a correlation for the axially average Nusselt number for forced convection of

supercritical carbon dioxide cooled at constant temperature. Jiang et al. [37] also

observed significant influence of buoyancy on convective heat transfer of carbon dioxide

at supercritical pressures in vertical mini-tubes and in porous media.

Based on numerical and experimental study (counter-flow, CO2 inside tubes, water

in the outer annulus; stainless steel tube with OD of 6.35 mm and thickness of 0.815

mm), Pitla et al. [38] presented a new correlation based on ‘mean Nusselt number’, where

Nu at constant thermophysical property was evaluated from Gnielinski correlation.

Presence of lubricant reduced heat transfer and increased the pressure drop. Scalabrin et

al. [39] developed a neural network model to estimate the heat transfer coefficient of CO2

in supercritical cooling based on data available in the literature and showed that the

model very accurately predicts the heat transfer coefficient data presented by Olson

whereas the Pitla correlation under-predicts the data.

Yoon et al. [40] presented the experimental data for heat transfer and pressure drop

characteristics during supercritical cooling of CO2 in horizontal copper tubes with ID of

7.73 mm and with an inlet pressure range of 75 – 88 bar. Conventional single-phase

pressure drop correlation with friction factor calculated from Blasius equation accurately

predicted the measured pressure drop for CO2 cooling. However, the authors showed that

most of the existing correlations for supercritical heat transfer coefficient under-predicted

the measured data and hence a new empirical correlation was proposed for the near

critical heat transfer coefficients. Zhao et al. [41] experimentally investigated the heat

transfer characteristics of supercritical CO2 cooling in a microchannel heat exchanger

(tube inner diameter of approximately 1 mm). Authors showed that refrigerant mass flow

rate, pressure and temperature highly dominated the heat transfer characteristics.

21

Page 44: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Recently, Dang et al. [42] experimentally investigated the heat transfer coefficient

and pressure drop for supercritical carbon dioxide cooled in four horizontal circular tubes

with different inner diameters ranging from 1 to 6 mm and showed the effect of mass

flux, pressure, heat flux and tube diameter. Based on the test data, authors established the

modified Gnielinski correlation of heat transfer coefficient using the reference

temperature method for supercritical carbon dioxide cooling in horizontal tubes. Authors

also compared the heat transfer coefficients obtained from numerical simulation applying

four different turbulent models and showed that the JL model (low Reynolds number

k ε− model by Jones and Launder) showed the best agreement with the experimental

data [43]. Table 2.1 shows some of the correlations presented in recent times for

estimating heat transfer coefficients in a gas cooler.

Table 2.1 Recent transcritical heat transfer correlations for CO2 cooling

Authors (Year) Tube material

Diameter, mm

Flow rate, kg/min

Pressure range, bar

Fang (1999) NA NA NA NA

Pettersen et al. (2000) NA 0.8 NA NA

Liao et al. (2002) SS 0.5 – 2.21 0.02 – 0.20 74 – 120

Pitla et al. (2002) SS 6.35 OD 1.20 – 2.35 94 – 134

Yoon et al. (2003) Cu 7.73 ID 0.63 – 1.27 75 –88

Dang et al. (2004) Cu 1 – 6 0.04 – 0.68 80-100

* NA = Not available

2.6 Two-phase heat transfer and fluid flow of CO2

High pressure, very low viscosity and surface tension, and near critical operation

make the flow boiling heat transfer and pressure drop phenomenon of carbon dioxide

distinct from conventional refrigerants. Distinct film break down and dry-out phenomena

make most of the general correlations unusable. Bredesen et al. [44] investigated heat

transfer and pressure drop of CO2 flow boiling in a horizontal 7 mm ID smooth aluminum

tube and found that CO2 has much higher heat transfer coefficient and much lower

pressure drop than that experienced with halocarbons. The heat transfer test data

22

Page 45: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

indicated regimes of convective boiling at high mass flux and low evaporative

temperature, and nucleate boiling regimes at low mass flux and higher evaporating

temperature. At most conditions, the heat transfer coefficient increased up to vapor

quality of 0.9, but the behaviour is quite different above evaporating temperature of 5 oC,

with decreasing heat transfer coefficient at increasing vapor quality. Zhao et al. [45]

conducted tests on flow boiling of CO2 in microchannel (stainless steel tube) for mass

fluxes of 250-700 kg/m2s and heat fluxes of 8-25 kW/m2 and results indicated that under

identical testing conditions, the heat transfer coefficient of CO2 is found to be much

higher than that of R134a with much lower pressure drop. Zhao et al. [46] studied flow

boiling of CO2 with miscible oil in microchannels (0.86 mm diameter tube) and results

indicated that larger oil concentration degrades the heat transfer coefficient significantly,

while smaller oil concentrations (< 3%) at low vapor quality (x < 0.45) moderately

enhanced the heat transfer coefficient.

Yun et al. [47] experimentally investigated the boiling heat transfer and dry-out

phenomenon of CO2 in horizontal smooth tube (ID=6 mm) for saturation temperature of

5 to 10 oC and mass fluxes of 170 to 320 kg/m2s. They found that the heat transfer

coefficient of CO2 decreases with an increase of quality due to a lower dryout quality and

dominance of nucleate boiling compared to the conventional refrigerants. Authors

showed that Gungor and Winterton correlation [48] exhibits poor prediction at low mass

flux whereas good agreement at higher mass flux. Yun et al. [49] experimentally showed

that the dry-out phenomena of CO2 are similar to water in many respects while the effect

of mass flux on dry-out showed dissimilar behaviour.

Pettersen [50] conducted experiments on flow vaporization heat transfer coefficient

and pressure drop of carbon dioxide in extruded microchannel tubes with 25 flow-

channels (ID=0.8 mm). Flow pattern maps were presented at an evaporation temperature

of 20 oC and the heat transfer coefficients were correlated using asymptotic models for

combinations of nucleate boiling, and convection evaporation, dryout inception and post

dryout heat transfer. Flow visualization showed the dominance of intermittent and

annular regimes, although the latter one became more significant at high mass flux.

Pettersen [51] separately visualized the flow pattern of CO2 flow boiling in microchanel

23

Page 46: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

tube of 0.98 mm OD using a high-speed camera at temperatures 20oC and 0oC and for

mass flux ranging from 100 to 580 kg/m2s. The intermittent (slug) flow dominated at low

quality whereas the wavy annular flow with entrainment of droplets dominated at higher

quality. The aggravated dry-out problem reported from heat transfer experiments at high

mass flux could be explained by increased entrainment. The flow pattern observations did

not fit generalized maps or transition lines reported in the literature.

Yoon et al. [52] conducted experiments on evaporative heat transfer and pressure

drop of CO2 in a seamless SS tube with an inner diameter of 7.53 mm and length of 5 m,

for saturation temperatures of –4 to 20 oC, mass flues of 200 to 530 kg/m2s and heat

fluxes of 12 to 20 kW/m2. They showed that at low quality region, heat transfer

coefficient has a tendency to increase slightly as quality increases, with the increase in

saturated temperature heat transfer coefficient increases up to about 5 oC, after that heat

transfer coefficient decreases in low vapor quality region. A new correlation was

proposed to predict critical quality where liquid film breaks down and the heat transfer

coefficient for CO2, and also developed a correlation for frictional two-phase multiplier

for pressure drop calculation. Thome et al. [53] generalized the flow pattern map for flow

boiling of CO2 and developed a general correlation as an asymptotic model including

both nucleate and forced convection terms for flow boiling heat transfer coefficient for

CO2 based on data covering five tube diameters from 0.79 to 10.6 mm, mass velocities

from 85 to 1440 kg/m2, heat fluxes from 5 to 36 kW/m2 and saturation temperature from

–25 oC to 25 oC.

Huai et al. [54] experimentally studied boiling heat transfer and pressure drop of

CO2 flowing in a multi-port extruded aluminum test section having 10 circular channels,

each with an inner diameter of 1.311 mm for the evaporation pressure ranging from 39.9

to 53.8 bar, inlet temperature of CO2 from –3.08 to 16.96 oC, heat flux from 10.1 to 20.1

kW/m2, mass velocities from 131.4 to 399 kg/m2s and vapour quality from 0.0 to 1.0.

Results showed that two-phase CO2 flow exhibited a higher heat transfer coefficient than

that of single-phase liquid or vapor flow and once the dry-out occurred the wall

temperature increased and the heat transfer decreased rapidly. Results also showed that

the mass velocity and the applied mass flux have significant effect on the flow boiling

24

Page 47: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

characteristics. The measured heat transfer coefficients were found to deviate from those

obtained from correlations reported in the literature significantly. Table 2.2 shows a

summary of studies carried out recently on flow boiling aspect of CO2.

Table 2.2 Summary of experimental investigation on flow boiling of CO2

Investigator Tube Specifications

Mass flux (kg/m2s)

Heat flux (kW/m2)

Sat. temp. (oC)

Studies

Bredesen et al., 1997

Aluminum, 7 mm ID

200 - 400 3 - 9 -25 to 5 Local heat transfer

Zhao et al., 2000

Stainless Steel, 0.86 mm dia.

250 - 700 8 - 25 5 to 15 Heat transfer, pressure drop

Zhao et al., 2001

Stainless Steel, 0.86 mm dia.

250-700 8 - 25 5 to 15 Heat transfer

Yun et al., 2003

Stainless Steel, 6.0 mm dia.

170 - 320 10 - 20 5 to 10 Heat transfer

Yun et al, 2003

Stainless Steel, 1.6, 3.2 mm OD

500 - 3000 7.2 - 48.1 0 to 10 Dry-out

Pettersen, 2004

Aluminum, 0.8 mm dia.

190 - 570 5 - 20 0 to 25 Heat transfer, pressure drop

Yoon et al., 2004

Stainless Steel, 7.53 mm dia.

200 - 530 12 - 20 -4 to 20 Heat transfer, pressure drop

Huai et al., 2004

Aluminum, 1.311 mm ID

131.4 -399 10.1 - 20.1 -3 to 17 Heat transfer, pressure drop

2.7 High pressure related issues

Pressure in transcritical CO2 systems are typically 5-10 times higher than that of

conventional refrigerants and this gives rise to several issues that influence component

design and their performance such as compression process, compressor design, heart

transfer and pressure drop, and heat exchanger design. These issues are also related to

personnel safety during system operation.

25

Page 48: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.7.1 Issues related to component design

The compressor in a CO2 system is required to be operated at high pressure, with a

large pressure difference, but at modarate pressure ratio. Pettersen [16] showed that the

displacement of R134a machine is 6.5 times higher, and pressure ratio of CO2 is nearly

40% lower than R134a for equal cooling capacity at 0 oC. Re-expansion losses are much

smaller in CO2 system. Although a thicker wall is required due to high pressure, due to

the higher volumetric capacity, CO2 compressor will be smaller compared to

conventional refrigerant compressor for the same capacity [5]. Recent investigations

showed that internal leakage losses and the piston blow-by losses are much less (about

1%), which indicated that by proper design of the lubricated compressor the influence of

leakage can be neglected [5].

As the pressure level increases, allowable pressure drop becomes higher and this

gives rise to a possibility of improving heat transfer because of higher flow velocity

resulting in higher Reynolds number in heat exchanger. Both high pressure and proximity

to the critical point give considerable improvement of convective heat transfer.

Evaporator pressure drop leads to reduced temperature difference due to corresponding

drop in saturation temperature. Slope of saturation curve is very different for CO2

compared to the conventional refrigerants because of high pressure. Nucleate boiling heat

transfer is also affected to a large extent by pressure. The higher tolerable limit of

pressure drop leads to optimum design of compact heat exchanger with small diameter

tube and in many cases extruded multiport tubing with parallel flow of refrigerant in

several tubes and flow channels. Pettersen et al. [55] showed some compact heat

exchanger concepts for CO2 air conditioning systems having internal diameter of 2 mm.

Low side refrigerant line diameter are typically reduced to 60 – 70% compared to HFC

system due to higher density and flow velocity [5]. Higher side piping dimensions can

also be reduced. Assuming wall thickness that more or less same as in HFC piping of

equal capacity, pressure capability will be sufficient for CO2 due to reduced diameter.

Hence, the components size and weight reductions are possible due to reduced refrigerant

side volume and cross section.

26

Page 49: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.7.2 High pressure safety issues

Hazards in vapor compression systems are usually caused by flammability,

inhalation safety and explosion and rupture of pressurized components or vessels.

Although CO2 is usually regarded as non-flammable and non-toxic, there are

physiological effects from breathing air with a CO2 concentration above a few percent. In

general, maximum allowable concentration of 5% by volume seems to be a reasonable

limit and this is used for CO2 system design as maximum allowable limit [5]. The

explosion or rupture may include blast effect and shocks as well as flying fragments.

Such incidents may be caused by a number of factors such as manufacturing of safety

device, overheating, overcharging, incorrect operation, construction weakness/corrosion,

mechanical impact, etc. High pressure is not a safety issue itself, since the equipment will

be designed for this. In case of component rupture, however, the explosion energy (stored

energy) may characterize the extent of potential damage. The explosion energy can be

estimated to be released by expansion of the refrigerant contained in a component or

system. The explosion energies of baseline R22 system and CO2 system have been

calculated and compared [56]. The data are based on the ductless split residential air

conditioning systems of equal size and capacity (7 kW). Results showed that the

explosion energy of CO2 system is higher than that of R22 system at room temperature

(about 30 oC) and equal at a temperature around 60 oC, whereas explosion energy of the

R22 system become higher than that of CO2 system at higher temperature. The ratio of

explosion energies (CO2/R22) is 2 at room temperature and 0.7 at 100 oC. The difference

of energies are significant above 120-130 oC, and in an extreme situation such as a fire,

the energy release from a R-22 system is likely to be much higher than that from a CO2

system. Comparison with baseline R134a system also showed similar results; explosion

energy of baseline system is smaller at normal temperature but becomes higher at

elevated temperature [5]. Reductions in internal volume and refrigerant charge in CO2

system make the explosion energies comparable.

Vapor explosion of boiling liquid may create a more severe blast effect than by an

ordinary refrigerant explosion due to possible explosive vaporization in shorter duration.

These phenomena may occur when a vessel containing a pressurized liquid or

27

Page 50: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

supercritical fluid is rapidly depressurized, e.g. due to an initial crack or rupture. The

sudden depressurization gives a superheated liquid phase that is suddenly vaporized in an

explosive manner. This may give a transient overpressure peak inside the vessel, which

again may lead to a powerful burst of the whole vessel. However it has been observed

that maximum overpressure spike is not so high (about 7 % of initial) [5]. Thermal shock

effects on the pressure sensors were significant. In real systems the presence of

compressor lubricant, particles and contaminants, as well as unstable

pressure/temperature, would make homogeneous nucleation even less likely. Some rules

regarding pressure relief for safety standard for CO2 mobile air conditioning and heat

pump have been proposed [5].

2.8 Component design

2.8.1 Compressor

The vapor pressure inlet to the compressor for transcritical CO2 system is much

higher compared to that of conventional refrigerants. High pressure gives special

requirement regarding design of suitable components especially compressors for CO2

systems. As the compressor is one of the major components of air-conditioning and

refrigeration systems and has an important effect on the system performance, compressor

technology for the CO2 transcritical systems has reached an advanced level after years of

research and development. It has been shown that CO2 compressor can become compact

compared to R134a compressor due to higher density [5]. The relationship between

compressor mass and displacement rate will depend on specific design tradeoffs

involving piston diameter and stroke and number of cylinders, rpm, materials, etc. First

experimental study on hermetic compressor showed that the isentropic efficiencies for

compressor were 9–15% lower than the R22 unit, while volumetric efficiency was lower

by less than 5% [5] These results were considered promising considering the early stage

of development. Süss and Kruse [57] reported that high compressor performance could

be achieved due to the lower pressure ratio of the transcritical compression process with

CO2. Leakage may have strong influence on the CO2 compressor performance since the

pressure difference is extremely high, but the effect of leakage on the compressor

28

Page 51: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

performance can be reduced to a reasonable amount with an appropriate design of the

machine. On the other hand, the pressure losses inside a compressor have a small

influence on the energetic and volumetric efficiency of the compression process.

Measurements on a two-stage version of the compressor [58] showed a potential

for 20% COP improvement. This machine was intended for lower-temperature

applications, e.g. in commercial refrigeration at freezing temperatures. Two-stage

compression may also be of interest in relation to energy saving in air conditioning and

heat pump processes. Fukuta et al. [59] analyzed the potential for sliding vane machines

in CO2 compression and expansion. They showed that the leakage flows were the

dominant source of losses in the machine, and clearances had to be reduced compared to

conventional machines in order to get acceptable efficiency. Vane contact forces and

resulting friction losses were high, but could be reduced by pressure equalization on the

vane sides. Hubacher and Groll [60] measured the performance of two carbon dioxide

prototype compressors using a compressor load stand and developed compressor

performance maps based on the experimental data. The measured compressors were a

semi-hermetic, two-piston, single-stage, reciprocating compressor with an estimated

cooling capacity of 10.6 kW and a hermetic, two-stage, rotary compressor with an

estimated cooling capacity of 2.8 kW. Results showed volumetric efficiencies between

0.8 and 0.5 and overall isentropic efficiencies of up to 0.55 for pressure ratios between

1.5 and 6.5 for the single-stage, semi-hermetic compressor. The two-stage, hermetic

compressor showed calculated volumetric efficiencies of 0.9 to 0.78 and calculated

overall isentropic efficiencies up to 0.7, for pressure ratios between 1.5 and 5, based on

measurements performed with an oil separator. The effect of superheat on the efficiency

was found to be not very significant. Kim et al. [61] numerically compared the scroll,

two-stage twin rotary and two cylinder reciprocating compressors for heat pump water

heating applications. Results showed that clearance volume ratio of reciprocating

compressor needed is about 5% or less to have comparable volumetric efficiency with

scroll compressor with tip clearance of 5 µm. Isentropic efficiency of twin rotary

compressor was calculated to be lowest among them and the most severe drawback of

29

Page 52: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

scroll compressor was the increase of mechanical loss at the thrust surface supporting the

orbiting scroll number, while it showed very smooth torque load variation.

Several manufacturers, mostly in Japan and Europe, have started manufacturing

CO2 compressors. Denso Corporation has developed a single stage semi-hermetic scroll

compressor [5]. Dorin developed the first high-pressure semi-hermetic CO2 compressor

series in the range of 1.7–10.7 m3/h swept volume [8]. The series comprises single- and

two-stage compressors with two cylinders, running at nominal speeds of 1450 and 900

rpm (50 Hz). Kim et al. [5] listed various CO2 compressor manufacturers in Japan. Some

important manufactures have been listed in chapter 1.

2.8.2 Gas cooler

Maximum research efforts have been spared on the cross-flow extended surface

gas cooler, where air is the secondary fluid, applicable to air conditioning and room/space

heating. The high working pressure and favourable heat transfer properties of CO2 enable

reduced tube diameters and small refrigerant-side surface areas. Since these reductions

may give room for more airside surface per unit core volume, the compactness can be

increased. Pettersen et al. [55] initially reported microchannel heat exchangers (both gas

cooler and evaporator) could be used for air-conditioning systems.

To handle the high pressures, many CO2 systems employ heat exchangers with

flat multiport (microchannel) tubes. Compared to conventional flat-fin/round-tube

designs, this technology provides additional benefits such as increase in refrigerant-side

area by about a factor of three, far less airside pressure drop due to the streamlined profile

presented by the tubes and flat tubes enable higher face velocities that increase the airside

heat transfer coefficient. Because of high investment costs, microchannel heat exchangers

for fluorocarbon refrigerants have appeared first in high-volume applications where

compactness is valued such as automotive applications. Some of the early theoretical

analyses of CO2 system performance assumed that both indoor and outdoor heat

exchangers would be of conventional flat-fin/round- tube design [5]. One issue in

compact gas cooler design is internal conduction due to large temperature differences

across small lengths. As pointed out by Pettersen et al. [55] internal conduction in fins,

30

Page 53: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

tubes and manifolds may lead to performance reduction. Solutions to avoid these

problems include splitting of fins, use of several heat exchanger sections, and careful

design of manifold geometries.

Fang et al. [62] developed a simulation model of gas cooler for calculating heat

transfer and pressure drop at supercritical pressures in both transitional and fully

developed turbulent flow and verified with experimental data thereafter. Model

considered the louvered fin geometries of rectangular channels, triangular channels and

plate and tube types for airside heat transfer and pressure drop. Results showed that the

pass segmentation and uncertainty of pressure drop influenced the accuracy of capacity

calculation. Neglecting pressure drop had caused 10%± uncertainty in capacity

calculation. The capacity increased with increase in tube depth, whereas fin height had

negligible effect on the capacity. A finite element model for a supercritical cross-flow gas

cooler model was developed and validated with data obtained in more than 350

experiments [63]. They proposed a multi-slab gas cooler design and reported that a newly

designed cross-counter flow gas cooler could improve the system capacity and COP by 3-

4% and 5% respectively. Simulation of different arrangements of the gas cooler within

original packaged dimensions showed that the 3-pass gas cooler is the best single slab

design. However using multiple slabs seemed to be a more effective way to improve the

performance. In the transcritical CO2 cycle, system performance is very sensitive to gas

cooler design. A small change in refrigerant exit temperature can produce a large change

in gas cooler exit enthalpy (and evaporator inlet enthalpy) because specific heat becomes

infinite at the critical point and hence COP is very much sensitive to gas cooler exit

temperature [64]. A counterflow configuration is important for the gas cooler to exploit

the large refrigerant-side temperature glide. Moreover, the steep refrigerant temperature

glide allows for ideal cycle efficiency to be achieved at finite air flow rate, in contrast to

the infinite air flow required to achieve ideal efficiency in the subcritical cycle. Using a

multi-slab, counter-flow arrangement gas cooler design was proposed [64] and the

predicted approach temperature difference was reduced from 6.9 to 3.6 oC and the design

seemed to be very effective at lower airflow rate and high capacity conditions. The flat

tubes are vertical in this prototype, to facilitate condensate drainage and defrosting in

31

Page 54: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

heating mode. The proposed design could give 11% higher gas cooler capacity than the

commonly used multi-pass design.

Garimella [65] has modeled a novel near counter-flow serpentine flow for the

tube side gas cooler for air conditioning system. The model used heat exchanger

geometry and inlet conditions as the inputs to predict the overall duty as well as the

temperature profiles of refrigerant and air. Model predicted that a gas cooler load of 6.97

kW could be transfered in very small envelope. The approach temperature difference was

predicted as 5.33 oC. However the optimum design of gas cooler such as optimizing

geometry parameters (e.g. core depth, face area, number of tube, number of serpentine

tube side passes, port diameter as well as fin pitch and thickness and louver geometry)

and refrigerant flow through port could give lower approach temperature difference.

Numerical investigation with validation with experimental data in open literature has

been done to investigate the effect of wall thermal conductivity on overall performance of

cross flow microchannel gas cooler [66]. Results showed that the longitudinal conduction

in fins, the transverse and the longitudinal conduction in tubes give negligible effects on

the total heat flow and on the temperature field. Neksa et al. [67] experimentally and

theoretically investigated the fan less gas cooler in CO2 system for heating purpose.

Along with the elimination of fan noise and fan power consumption, this concept reduces

the air draft in the room. The concept was found to be feasible also for high efficiency

heat pumps, as CO2 is partly characterized by a gas cooler giving a low cold end

approach temperature difference. It was therefore expected to be very well suited as an

indoor heat exchanger for an air-to-air heat pump for which fan noise may be an

important market-limiting factor.

2.8.3 Internal heat exchanger

The benefits of an internal heat exchanger for transcritical automotive air-

conditioning systems have been documented through extensive experiments in CO2

prototype systems, and subsequent analyses using a validated simulation model. It has

been demonstrated [18] that internal heat exchange can increase cycle efficiency by up to

25% because of the relatively high irreversibility at the expansion device in the standard

transcritical cycle. Three coaxial internal heat exchangers of various lengths (1.0, 1.5 and

32

Page 55: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.0 m), having identical cross-sections, were used in the experiments in both parallel and

counter-flow configurations. The counter-flow arrangement of internal heat exchanger

was shown to be better than parallel arrangement. The longer internal heat exchanger

provides the greatest increase in COP and the greatest decrease in the corresponding

optimal discharge pressure. The experimental data were used to develop simulation

model, which was used to develop a optimal design for a COP maximizing of internal

heat exchanger. In automotive air-conditioning systems, internal heat exchange provides

the greatest capacity enhancement when it is needed most, that is during idling at high

ambient temperatures. Boewe et al. [68] showed how three microchannel tubes could be

stacked to provide many parallel ports to control pressure drop in the cold suction gas,

while forcing the supercritical fluid through smaller ports to maximize heat transfer

coefficients and areas upstream of the expansion device where larger pressure drop can

be tolerated. Compared to conventional concentric tube designs, the microchannel

configuration reduced material requirements by 50% while eliminating the need for long

suction and liquid lines, and increasing effectiveness by 10%.

2.8.4 Evaporator

Microchannel evaporators are currently the subject of research within the

automotive air-conditioning industry because of the potential performance improvements

obtainable from further increases in refrigerant-side area and higher face velocities. Size

of microchannel evaporator with louvered fins of CO2 system is less than that of R134a

system [5]. The enhanced performance is attributable to the fact that microchannel tubes

are thinner than the brazed plates, allowing the same air volume to pass with greater face

velocity through a deeper heat exchanger, without a pressure drop penalty. In both plate

evaporators and microchannel evaporators, the challenge is to distribute the two-phase

flow uniformly through the parallel circuits. The current strategy for dealing with this

problem is to find ways of eliminating it, such as flash gas bypass as described earlier

[22]. Kim and Bullard [69] developed a detailed finite volume model for a multislab

microchannel evaporator for a CO2 mobile air-conditioning system and validated the

model for a two-slab prototype evaporator. Several correlations for air- and refrigerant-

side heat transfer and friction loss were compared before selecting appropriate

33

Page 56: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

correlations for the model. They reported that their model predicted the experimental data

with reasonable accuracy, and could be used for the performance analysis and designing

of a microchannel evaporator. Currently, all simulation models of microchannel heat

exchangers assume perfect distribution on the refrigerant side [69]. Their main focus is

on capturing accurately the important air-side phenomena such as the effects of

condensate and inclination angle.

Although several experimental studies have been reported on flow boiling heat

transfer in microchannel tubes, few experimental studies have been reported to measure

the effects of condensate retention on the performance of microchannel evaporator as

reported by Kim et al. [5]. The heat transfer coefficients and pressure drops for wet

conditions revealed the important of role of condensate drainage.

2.8.5 Other components

A variety of lubricants can be used for transcritical CO2 applications. In certain

systems synthetic hydrocarbons such as polyalpha olefins (PAOs) and alkyl benzenes

(ABs) can be used even though they have poor solubility. The poor solubility of the

synthetic hydrocarbons is compensated by their excellent low temperature flow properties

and can be improved still further by blending with more miscible lubricants (e.g.

polyalkylene glycols (PAGs), esters, etc.). A range of individual and blends of synthetic

lubricants are therefore being evaluated to find the more cost effective solution for a

particular application. Quite often lubricant selection will be based on logistic factors, i.e.

a lubricant that can work with a variety of refrigerants. Various synthetic lubricants

including mineral oil, Polyalkylene glycol (PAG), polyolester (POE), polycarbonate (PC)

and polyvinyl ether (PVE) were experimentally tested for CO2 applications [5].

Ikeda et al. [70] evaluated the chemical and physical properties (lubricity, chemical

solubility, miscibility, mixture viscosity and other properties) of possible base oils:

polyalkylene glycol (PAG), polyvinyl ether (PVE), polyol ether (POE) and polycarbonate

(PC) for a CO2 applications. It was found that PAG was the best lubricant for a CO2 heat

pump system due to its suitable miscibility, higher chemical stability and better lubricity

under high pressure. Although PAG was less miscible than other tested oils, oil return

34

Page 57: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

problem was not occurred. POE showed poor lubricity and stability and PC was worse

than PAG and PVE in lubricity. Newly developed refrigeration lubricants using PAG

have been successfully introduced into the market for CO2 heat pump water heater

systems and CO2 automotive A/C systems.

Some issues are being studied with respect to elastomer materials for seals and hose

connections in CO2 systems Permeation rates are quite high, thus giving potential

problems regarding desired leakage rates in automobile air conditioning systems.

Explosive decompression may occur when CO2 systems or components are rapidly

depressurized, leading to fractured and ruptured sealing elements [71]. A fluorite

elastomer, FKM was regarded as promising due to its wide temperature range of

application and the negligible impact of explosive decompression. Other components,

including electronic expansion valves, accumulators, hoses, o-rings and fittings have

been developed for CO2 air-conditioning systems. Several manufacturers in Japan and

Europe are working on expansion valves and controls for CO2 systems [5].

2.9 Application areas

Transcritical CO2 system was first proposed for mobile air-conditioning applications

[1]. Since then during the last decade, various applications of transcritical CO2 systems

have been proposed. The affected industries and many government sponsored R&D

programs have funded various projects including basic research and application

prototypes. Industry-sponsored efforts generally proceed in two stages: proof of the

technology that work for a specified application, and then in stage two the state of the art

is advanced to enable the technology to compete in the market. Any new technology that

challenges an existing one must demonstrate that it is workable, usually on the old

technology’s terms. For most of the application areas proposed recently, CO2 technology

is now at the second stage where it must demonstrate competitiveness. Current research is

aimed at identifying the best way to utilize the unique characteristics of the new

technology. In the case of CO2 these characteristics include certain thermophysical

(thermodynamic and transport) properties, which increase heat transfer and boost

compressor efficiency. Its high heat rejection temperature, a disadvantage for air

35

Page 58: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

conditioning, is a potential advantage for heating by delivering instant high-temperature

heat quietly due to the need to move less air than existing heat pump technologies.

During this second stage of prototype development the main question is how closely the

ideal cycle can be approached at reasonable cost—a question that goes beyond simple

thermodynamic cycle comparisons. While questions related to cost are being explored on

a proprietary basis, papers in the open literature are suggesting ways of approaching ideal

cycle efficiency by exploiting the unique characteristics of CO2 such as the slope of its

vapor-pressure curve, boiling behavior near the critical point, high capacity at low

temperatures, and its supercritical temperature glide. Other papers suggest ways of

altering the transcritical cycle to increase the ideal efficiency, for example, through use of

expanders, ejector, internal heat exchangers and multistage compression.

2.9.1 Automotive air-conditioning

Mobile air conditioning applications were among the first to be considered for

application of the transcritical CO2 cycle due to various disadvantages with R22 and

R134a including high leakage rate through the flexible nylon or butyl rubber hoses

needed for vibration protection, and through the compressor shaft seal needed to avoid

the additional weight and conversion losses associated with the hermetic electric

compressors used in other applications as well as high GWP. In successive studies,

Lorentzen and Pettersen [1] and Pettersen [72] developed and tested a prototype of

transcritical CO2 automobile air conditioning system. They used, as a reference, a

commercially available R12 automotive air-conditioning system and built the prototype

of comparable cooling capacity. The CO2 system had a liquid line/suction line heat

exchanger to transfer heat between CO2 leaving the gas cooler and low pressure CO2

leaving the evaporator. To match the cooling capacity, the displacement volume and

speed of compressor were adjusted. The external dimensions of the air-to-refrigerant heat

exchangers were nearly identical for both systems; however the CO2 evaporator had 25%

larger airside surface than the R12 evaporator, and the CO2 gas cooler had 34% larger

airside surface than the R12 condenser. The authors demonstrated that the CO2 system

had comparable performance of the R12 system.

36

Page 59: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

The ideal cycle comparisons of R-134a and CO2 for automotive air conditioning

carried out by Bhatti [73], rested on assumptions that failed to account properly for the

unique thermodynamic and transport properties of CO2 even though experimental data

for a prototype CO2 system had already shown competitive performance to a state-of-the-

art R-12 system. Not surprisingly the theoretical studies concluded that the total global

warming impact of CO2 systems would exceed that of R-134a, considering both direct

(leakage) and indirect (fuel combustion) emissions of greenhouse gases. Through

improvements in system operation and control [9], compressor performance, and heat

exchanger performance [55], the CO2 technology was able to compete even with the

improved R-134a systems that were introduced in the mid-1990s. McEnaney et al. [74]

presented experimental results for both steady state and cyclic operation for prototype

CO2 system and a commercially available 134a automotive air-conditioner. Both the gas

cooler and evaporator were microchannel heat exchangers. The external volumes of

evaporator were identical for both systems with the CO2 evaporator having 20% larger

airside surface area. The CO2 gas cooler had 23% lower external volume and 28% lower

air side surface than the R134a condenser. The test results indicated that the prototype

CO2 system provided a comparable performance to the current production R134a system

for both steady state and cyclic operation. Control strategy using clutch cycling, variable

displacement and variable speed compressor can be applied to adjust optimum high side

pressure for CO2 automotive air conditioning [75].

Brown et al. [76] evaluated merits of CO2 and R134a air conditioners using

simulation model and considering current production configuration of a R134a system

and a CO2 system, which was additionally equipped with liquid-line/suction line heat

exchanger. Results showed CO2 having an inferior COP to R134a. The COP disparity

depends on compressor speed (system capacity) and ambient temperature; the higher the

COP and discharge temperature, the lower was the COP difference. At the same speed

and lower ambient temperature, the COP disparity was lower; however at higher speed

and ambient temperatures, it was greater. Hence, better transport properties and

compressor isentropic efficiency did not compensate for its thermodynamic disadvantage

compared to R134a when equivalent heat exchangers were used for both refrigerants,

37

Page 60: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

even if internal heat exchanger was used to reduce throttling irreversibilities. The entropy

generation calculation indicated that CO2 had somewhat better performance than R134a

in evaporator, however poorer performance in gas cooler than R134a in condenser.

Based on the results of an analysis of a large number of experiments and some

new concepts, next-generation prototype systems have been designed and are serving as

the focus for current research. Most are equipped with variable-displacement

compressors, and heat exchangers configured to exploit the unique transport and

thermodynamic properties of CO2 [5]. Liu et al. [77] evaluated the effect of CO2 mass

charge on the performance of an automotive R744 transcritical air conditioner operated

by manual expansion valve and showed that there was optimum mass charge, which

make the COP maximum; however no maximum cooling capacity was found to exist

with varying CO2 charge.

2.9.2 Automotive heating

Because of insufficient waste heat from efficient fuel-injection engines for heating

of the passenger compartment in the winter season and also unacceptable heating-up

period and slow defroster action in terms of both safety and comfort, supplementary

heating is necessary, and heat pump may be one of the attractive solutions. CO2 systems

have special benefits in heat pump mode, since high capacity and COP can be achieved

also at low ambient temperature and with high air supply temperature to the passenger

compartment. Giannavola et al. [78] first ran an auto air-conditioning prototype system in

reverse for automotive heating. However, the cross-counter-flow interior heat exchangers

were far from ideal. Results showed that the capacity is highest at startup, at least three

times higher than that of electric resistance or friction heater due to the high heat

pumping efficiency; and capacity and efficiency decline slowly at higher temperature lift

due to reduced volumetric and isentropic compressor efficiencies. These initial results

have proven quite valuable in guiding the design and development of improved

components for next-generation systems. Heat pumps are not currently employed in

automobile due to disadvantages of R134a as heat pump fluid. The technical problem is

accumulation of frost in heat exchanger and very little knowledge about the drainage

from ultra-compact microchannel heat exchangers. There is no such effective option to

38

Page 61: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

avoid it. However, the ability of heat pump to provide instant heat and capability of CO2

heat pump to deliver that heat at high temperature while moving less air may give

potential advantage to CO2 systems [5].

2.9.3 Residential cooling

The first assessment of transcritical CO2 systems for residential air conditioning

was done by simulating operation of an Asian-style ductless mini-split system, comparing

CO2 to a baseline R-22 system. Evaporator temperatures were higher in the CO2 system,

and very small approach temperatures were estimated for the CO2 gas cooler. The effects

of pressure drop, particularly in the evaporator and suction line of the R-22 system and

the superheat characteristics of the expansion valve, gave cooling COPs (summer

operation) that were similar in both systems, even at high ambient temperatures [5].

Another extensive set of experiments was conducted on a prototype North American-

style ducted split air conditioning system and compared with baseline R-410A system

and the CO2 prototype heat exchangers were designed to match as closely as possible to

its overall package dimensions. Detailed literature review on residential cooling is cited

in reference [5]. Cycle analysis of CO2 air conditioner showed that the effect of internal

superheating is very small whereas the effect of compressor efficiency is significant on

system COP. The design of recuperative heat exchangers in the system is crucial, since

the system COP may decrease when the recuperator is above certain size [79]. The R-22

system had a significantly better coefficient of performance (COP) than the CO2 system

when equivalent heat exchangers were used in the CO2 and R-22 systems, which

indicates that the better transport properties and compressor isentropic efficiency of CO2

did not compensate for the thermodynamic disadvantage of the transcritical cycle in

comfort cooling applications [80].

2.9.4 Residential heating

Transcritical CO2 cycle can deliver air at 60 oC to achieve the same level of

comfort offered by a gas based furnace while quietly moving substantially less air than

conventional heat pumps Similarly, CO2 can provide heat via a hydronic secondary loop

without the energy penalty that would be incurred in a heat pump operating on a sub-

39

Page 62: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

critical cycle. Several analytical studies of the global warming implications of alternative

heat pumping systems have concluded that the direct effect of refrigerant emissions is

relatively small, Hence, for almost all applications except automotive air-conditioning

and supermarket refrigeration, the highest R&D priority is to maximize the efficiency of

CO2 systems.

Initial theoretical study [81] on controlled ventilation air heating system with CO2

heat pump showed very promising results. The overall seasonal performance factor for a

Graz, Austria climate was calculated in the range of 6.15 – 6.5. Beaver et al. [82]

reported that the R-744 system operated with the same or slightly higher COP at lower

ambient temperatures (26/27 oC) and a slightly lower COP at higher ambient temperature

(26/35 oC indoor/outdoor) for tests performed at equal capacity. Although COP (cooling)

of CO2 system in cooling mode is lower than that of R22 system, it is slightly higher in

heating mode [83]. Experimental investigations of transcritical CO2 systems for

residential space heating were conducted on a prototype residential split system,

originally designed for cooling only, by simply reversing its operation to study heating

performance [84]. Since the original baseline system was obtained before the first R-

410A heat pump system became available, the package dimensions for the heating

comparisons were no longer equal: the baseline subcritical R-410A system had larger

heat exchangers. Nevertheless, system performance was compared for two

configurations: first when the CO2 prototype semi-hermetic compressor speed was set to

match heating capacity at 8.2 oC outdoors and 21.1 oC indoors; and second when the air

conditioning capacity was matched at 35 oC outdoors and 26.5 oC indoors. The CO2

system had comparable cycle COP in heating mode, but its higher capacity at lower

outdoor temperatures increased its heating performance factor by reducing the need for

supplemental heat, which illustrates the CO2 system’s ability to select a compressor

discharge pressure that gives it extra capacity or efficiency when needed. Another

experimental investigation showed that the prototype CO2 unit had performed almost

equal as the R410A baseline unit in AC mode at 27.8 oC and 35 oC ambient temperature

and in heat pump mode it had performed around 30 to 40% better at –5 to 5 oC ambient

temperature [85].

40

Page 63: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

For hydronic heating applications, CO2 heat pump systems showed favorable

seasonal performance compared to the system using R134a [5]. Theoretical study on CO2

heat pumps for retrofit in typical hydronic heating systems showed that the seasonal

performance was increased from 2.8 to 3.2. In addition, this system will be able to supply

hot tap water without any loss in energetic efficiency. Experimental results from two

prototype systems reported the same range of efficiency figures as those calculated [83].

2.9.5 Water heating

The first application of CO2 systems on the market is heat pump water heaters,

where the thermodynamic properties are very favorable. Due to gliding temperature in

gas cooler the temperature characteristics of the transcritical cycle matches the

temperature profiles of the heat source and heat sink, giving small heat transfer losses and

high efficiency. A pre-condition for high efficiency is a low water inlet temperature,

giving a low refrigerant inlet temperature to the throttling device. Thus, the design of the

hot water accumulating system for temperature stratification is essential in order to

achieve high heating COP. Experimental study on CO2 heat pump prototype showed very

promising performance in tap water heating [86]. A heating COP of 4.3 was achieved for

heating tap water from 9 oC to 60 oC at an evaporation temperature of 0 oC. The result led

to a seasonal performance of about 4 for an Oslo (Norway) climate using ambient air as a

heat source and the primary energy consumption could be reduced by more than 75%

compared to electrical or gas fired systems. Increasing the required hot water temperature

from 60 oC to 80 oC reduced the heating COP from 4.3 to 3.6 at an evaporation

temperature of 0 oC. A CO2 system can produce hot water with temperature of 90 oC

without operational difficulties, whereas conventional heat pump systems are often

restricted to hot water temperature lower than 55 oC.

Hwang and Radermacher [87,88] compared the water chilling and tap water

heating performance of CO2 system with R22 system through their theoretical and

experimental studies. Theoretical analysis showed that the reduction of heat exchanger

size and mass of CO2 is possible for tap water heating by appropriate design.

Experimental study showed that though the ideal cycle coefficient of performance (COP)

of CO2 is only 50% to 60% that of R22, the actual CO2 cycle performed similar to the

41

Page 64: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

R22 cycle within when the same outside volume of the heat exchanger was

applied for both refrigerants. This large deviation between ideal and actual cycles was

due to beneficial thermodynamic properties of CO

6%±

2.

Important application areas for commercial size systems are in hotels, apartment

houses, hospital and food industries. Another experimental study on heat pump water

heater showed a heating capacity of 115 kW and heating COP of 3.4 for evaporation

temperature of +0.3 oC and hot water temperature of 77.5 oC [89]. Simulation model

based on equipment performance data from experiment showed that the hot water

temperature could be increased from 65 to 120 oC with relatively small reduction of

heating capacity and heating COP of 33% and 22%, respectively. Several manufacturers

introduced CO2 heat pump water heaters in the market during 2001-02 [5]. Stene [90]

developed a CO2 heat pump system for combined space heating and water heating and

tested for evaporation temperature of –5 oC to obtain hot water up to 80 oC. The test

results proved that an integrated brine-to-water CO2 heat pump may achieve the same or

higher seasonal performance factor than the most energy efficient state-of-the–art brine

water heat pump systems.

2.9.6 Environmental control unit

Military needs for space conditioning systems for temporary shelters, command

modules, and vehicles have traditionally been met by procurement rather than R&D,

using custom-built units based on the same basic technology used for commercial

applications. The conventional Mil-Std (Military-Standard) ECU (Environmental Control

Unit) consists of a reciprocating compressor, copper tube and aluminum fin coils, swirl

cage fan assemblies, and a housing that has been hardened to meet the unique military

requirements. However, two recent developments have motivated the US military to

sponsor research on CO2 systems to meet its operational requirements for (1) lightweight

ultra-compact units for rapid deployment via air transport, and (2) a refrigerant that is

globally available and free of the diverse and extensive regulatory requirements and

logistical challenges associated with greenhouse gases. Although, one of the earliest

theoretical analyses [91] showed roughly equivalent performance under same conditions,

experimental study on microchannel based CO2 prototype showed that the CO2 based

42

Page 65: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

ECU did not perform as well as the R22 ECU in terms of capacity and COP. The addition

of internal heat exchanger improved the capacity and COP but still fell short of the R22

baseline. However, capacity and COP could be further improved by using an appropriate

compressor, and a change in fan type [92]. Recent experimental study [93] indicated that

the CO2 based ECU demonstrates a higher cooling COP and a higher cooling capacity

compared to the R22 units.

2.9.7 Refrigeration applications

Research interest in CO2 has also been renewed in the area of transport

refrigeration for two reasons. The first relates to the relatively high density and capacity

of CO2 at low temperatures, compared to alternatives such as hydrocarbons or ammonia;

the advent of lightweight compact microchannel heat exchangers presents new

opportunities for system optimization. Second, the worldwide availability of CO2 and

freedom from HFC-related regulatory uncertainties fits well with the global nature of the

transport refrigeration industry. Studies showed that the performance of CO2 system

matched with equal size systems using R502 and 507 and very similar COP values in

freezing mode with R134a over a full range of ambient temperatures [5]. One problem

with CO2 may be its very high compressor discharge pressure. However, in shipping

application, this can be reduced due to lower ambient temperature in sea atmosphere.

Commercial refrigeration systems for shops, supermarkets, large kitchens, etc.

have large refrigerant emissions, and the energy use is in many cases high. Thus, there is

a need for efficient, safe and environment friendly refrigeration systems. New concepts

based on CO2 have been demonstrated for centralized systems using CO2 as a secondary

heat transfer fluid or in a low-temperature cascade stage, and recently decentralized

concepts with heat recovery have been shown. Schiesaro and Kruse [94] developed a

two-stage CO2 supermarket system and carried out experiments to optimize the operation

and performance. Results showed lower COP than theoretical value due to the effect of

large amount of oil, additional mass flow through venturi, internal leakage and pressure

drop. However, good performance could be achieved by using components specially

designed for this refrigerant. Use of CO2 as secondary fluid or lower side refrigerant in

43

Page 66: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

cascade system was already discussed in chapter 1. Study on a decentralized supermarket

system using CO2 as the only refrigerant in a system with heat recovery showed reduction

of energy consumption for refrigeration and heating by 32% compared to the R22 system

[5]. Sasaki et al. [95] did not obtain good efficiency with CO2 refrigeration system

compared to other refrigerants; hence they proposed simultaneous industrial heating and

cooling applications. Girotto et al. [96] experimentally investigated the CO2 supermarket

refrigeration system to compare with a conventional direct expansion system using

R404A. Results showed about 10% higher total annual energy consumption of the

installed CO2 system compared to the direct expansion R404A solution. Authors stated

that further improvement of efficiency and approaching the efficiency of present R404A

systems could still be possible. Due to lack of mass production, CO2 systems were

estimated to be 20 % more expensive than R404A system.

2.9.8 Simultaneous cooling and heating

Due to gliding temperature heat rejection in the gas cooler, simultaneous heating

and cooling is one of the most promising applications of transcritical CO2 cycle. A CO2

heat pump was constructed to enable the simultaneous production of refrigeration at less

than 0 oC and water heating to 90 oC for the New Zealand food processing industry [97].

The optimum heating COP of the prototype was about 3 in most trials, but increased to

3.2 when operating the heat pump compressor at part-load with no oil in the system. The

addition of oil caused fouling and reduced performance in the evaporator but had

minimal effect on the performance of the gas cooler. The addition of oil had little effect

on compressor isentropic efficiency when operating at maximum compressor speed but

caused a significant reduction in isentropic efficiency when operating the compressor at

reduced speed. Another experimental study on simultaneous air-conditioning and water

heating showed promising result as an energy recovery system [98]. Results showed that

the combined system is more effective compared to an air conditioning system without

heat recovery.

44

Page 67: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.9.9 Heat pump dryers

Another interesting application of transcritical CO2 cycle is heat pump dryers.

Schmidt et al. [99] theoretically showed possibility of energy saving due to better

temperature adaptation in the heat exchangers compared to sub-critical process and also

possibility to achieve higher temperature without loss in efficiency, thus better moisture

extraction rate. Results also showed equivalent or even better COP than the comparative

R134a system. Experimental results from Klöcker et al. [100] reported heating COPs in

the range 5.5, and a 55% reduction in the energy consumption, including fan power,

compared to a traditional electrically heated dryer. The results were achieved after a first

optimization of the prototype system and it was hoped that further essential

improvements still could be reached.

2.10 Summary

This chapter outlined the recent developments in carbon dioxide as refrigerant in

transcritical cycle in various refrigeration, heat pump and air-conditioning applications. It

is observed that details of thermodynamic analysis and cycle optimization for a wide

temperature range are still insufficient. Although various methods have been suggested

to control the gas cooler pressure at optimum condition, still there is a need for some easy

method to control it. There is also need for rigorous theoretical and experimental

investigations on cycle modifications for optimum design, also in term of economics.

Because of high temperature lift (stated in chapter 1) for CO2, there is an opportunity for

investigation of multistage systems for heating or cooling at various temperatures. Also

investigations of heating or cooling systems with various mixtures of CO2 can be carried

out with a view to reduce the system pressure and take advantage of superior heat transfer

properties of CO2. Although various theoretical and experimental investigations on

supercritical heat transfer and pressure drop, boiling heat transfer and pressure drop, two-

phase flow have been reported, pseudocritical region of gas cooling is still one of the

interesting areas, where one can rigorously study heat transfer and fluid flow.

Relatively low isentropic efficiency of developed compressor showed that still there

is a need to improve the design to achieve higher performance. Research on CO2

45

Page 68: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

compressors is required not only for improvement of performance, but also to reduce the

weight and cost. Although various types of heat exchangers have been theoretically and

experimentally investigated, detailed economic analysis of heat exchanger is missing,

which is essential in commercial applications. In the last few years, most of the research

was concentrated on mobile air conditioning and heat pump water heating, even though

transcritical heat pumps also have great potential in industrial applications where

simultaneous heating and cooling is required. However, the literature survey shows that

detailed theoretical and experimental studies on transcritical CO2 systems for

simultaneous cooling and heating applications are scarce. Detailed studies on CO2 heat

pump dryers have also been not done extensively. Hence in the present work, the

following aspects are studied:

i) CO2 cycle optimization and effects of various cycle modifications

ii) Simulation and optimization of CO2 heat pump for simultaneous heating and

cooling applications, and system irreversibility analysis

iii) Exergetic optimization of heat exchangers for CO2 heat pumps

iv) CO2 heat pump dryer simulation, validation with experimental data and

optimisation

v) Experimental validation of heat transfer and pressure drop correlations

vi) Experimental study on CO2 heat pumps and validation of simulation model

46

Page 69: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 3

OPTIMIZATION OF TRANSCRITICAL CO2 CYCLES

3.1 Introduction

This chapter initially describes the development of a comprehensive property code

for both thermo-physical and transport properties of CO2. One of the special features of

CO2 is its low critical temperature (31.1 oC), normally very close to the ambient

temperature and hence the high pressure side operates in the supercritical region. Thus

the specialty of CO2 as a refrigerant is its heat transfer characteristics near or above the

critical point and how the available CO2 correlations estimate the CO2 properties

accurately. It has been seen that CO2 exhibits very interesting heat transfer properties

near the critical point. Hence this chapter also describes some of the interesting

properties, which enhance the performance of CO2 system. Although the NBP of CO2 is –

78.5 oC, its minimum operating temperature is only –55.6 oC, due to its higher triple point

as shown in Figure 3.1.

Figure 3.1 Phase diagram of carbon dioxide

47

Page 70: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

One of the interesting features of the transcritical CO2 cycle is that the refrigerant

outlet temperature and the pressure in the gas cooler can be adjusted independently to get

optimum performance. The details of the cycle analyses with both energetic and exergetic

perspectives and optimization of compressor discharge pressure for a wide range of

temperature applications is demonstrated. Finally, effects of different cycle modifications

on the optimum discharge pressure have been presented.

3.2 Property code development

Span and Wagner [101] have developed a new fundamental equation in the form

of Helmholtz energy based on a comprehensive study on experimental data for

thermodynamic properties of carbon dioxide. This empirical formulation is valid in the

fluid region up to a temperature of 1100 K and pressures up to 8000 bar. Based on this

seminal work a computer code ‘CO2PROP’ has been developed to estimate

thermodynamic properties of carbon dioxide in sub-critical and super-critical regions.

The code employs a technique based on the derivatives of Helmholtz free energy

function. Efficient iterative procedures have been used to predict assorted state

properties. A systematic comparison with published property tables [101] calculated from

the equation of state yields a maximum of 0.1% deviation. It may be mentioned that the

present code performs much better than some of the available commercial refrigerant

property software in the region around the critical point.

Property code for viscosity and thermal conductivity of CO2 has been developed

based on the seminal work of Vesovic et al. [102]. The complete correlations cover the

temperature range of 200 for viscosity and 200 for

thermal conductivity and pressures up to 1000 bar. Fenghour et al. [103] further modified

the viscosity correlations [102] based on two new sets of measurement in order to

improve their performance in liquid region. The code incorporated the new correlation

for viscosity of CO

1500K T K≤ < 1000K T K≤ ≤

2. The transport property correlations are also based on temperature

and density. So, transport property coding depends on thermophysical property coding to

predict the assorted state properties. A systematic comparison with the published

transport property tables [102,103] yields a maximum of 0.15% deviation for both

viscosity and thermal conductivity, although the deviation is slightly higher near the

48

Page 71: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

critical points. For surface tension of CO2, REFPROP [104] source code was partly

incorporated in ‘CO2PROP’.

3.2.1 Some of the important features of CO2 properties

Due to near critical operation of transcritical CO2 cycle, the CO2 properties have

some distinct effect on component design. Since the transcritical CO2 cycle operates at a

very high pressure, the vapor density is high yielding 3-10 times greater volumetric

capacity compared to other refrigerants. Steeper vapor pressure curve near the critical

point gives a smaller temperature change for a given pressure change. Thus, the

temperature change associated with pressure drop through evaporator will become

smaller.

0

5

10

15

20

25

30

35

40

45

50

10 30 50 70 90 110 130 150

Temperature (oC)

Isob

aric

hea

t cap

acity

(kJ/

kgK) P = 40 bar

P = 75 barP = 80 barP = 90 barP = 100 barP = 120 bar

Figure 3.2 Variation of isobaric heat capacity with temperature

One of the most important characteristics of supercritical fluids near the critical

point is that their properties change rapidly with temperature in an isobaric process,

especially near the pseudocritical points (the temperature at which the specific heat

becomes a maximum for a given pressure). Pressure influences the enthalpy and entropy

above the critical temperature, while the effect of pressure is small below the critical

49

Page 72: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

temperature hence the pressure drops may be allowed to be higher. Near critical pressure,

more abrupt change in specific heat is observed as shown in Figure 3.2. Such large

variations in thermo-physical properties cause the heat transfer coefficient to be greatly

dependent on both the local temperature and the heat flux, and conventional design

techniques such as ε-NTU or LMTD method yield large error in the design of a gas

cooler. The pseudocritical temperature, Tpc of CO2 was calculated using the following

algebraic equation [36]:

2 2.5122.6 6.124 0.1657 0.01773 0.0005608pcT P P P= − + − + − 3P (3.1)

for 75 , where temperature is in 140P≤ ≤ oC and pressure is in bar.

The high vapor density may have significant effects on two-phase flow patterns

where differences in phase density determine phase separation characteristics, and vapor

density influences the flow momentum of the vapor phase and shear force between vapor

and liquid phase. The low density ratio of CO2 may give more homogenous two-phase

flow than with other refrigerants and thus affects the heat transfer coefficient. Distinct

film break down and dry-out phenomena make most of the general correlations unusable.

A small surface tension for CO2 reduces the superheat required for nucleation and

growth of vapor bubbles, which may positively affect heat transfer. Wetting

characteristics of the liquid is affected by surface tension, thus influencing evaporation

heat transfer. Reduced liquid surface stability with small surface tension may affect heat

transfer negatively due to increased droplet formation and entrainment.

The thermal conductivities of saturated CO2 liquid and vapor are higher than

those of R-134a liquid and vapor, respectively, while the viscosity of CO2 liquid is lower

than R-134a liquid viscosity, and the vapor viscosities of the two fluids are comparable.

Viscosity can play an important role on fluid flow behavior, convection characteristics

and two-phase heat transfer and pressure drop.

Prandtl number is an important parameter for the heat transfer coefficient. Figure 3.3

shows a very abrupt change in Prandtl number of supercritical and liquid/vapor CO2. High

Prandtl number near the pseudocritical temperature is due basically to high isobaric heat

capacity, and the maximum value decreases with pressure. The effect of temperature on

Prandtl number depends on pressure. This results in a strongly varying local heat transfer

50

Page 73: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

coefficient depending on temperature and pressure. Thermo-physical and transport

properties of CO2 seem to be favorable in terms of heat transfer and pressure drop,

compared to other refrigerants.

0

2

4

6

8

10

12

0 20 40 60 80 100 120 140Temperature (oC)

PrP = 40 bar

P = 80 bar

P = 100 bar

P = 120 bar

Figure 3.3 Prandtl number of CO2

3.3 Optimum compressor discharge pressure

COP of the transcritical carbon dioxide system is significantly influenced by the

gas cooler pressure, and interestingly non-monotonically. Studies show that there exists

an optimum pressure where the system yields the best COP and the knowledge of the

optimum operating conditions corresponding to maximum COP is a very important factor

in the design of a transcritical carbon dioxide cycle. The gas cooler exit temperature is

dependent on external fluid inlet temperatures; so for any discharge pressure, cooler exit

temperature will be fixed for a certain fluid inlet condition. The existence of an optimum

pressure for fixed cooler exit temperatures can be supported by the following argument.

For cycle 1-2-3-4-5-6-1 (Figures 3.4-3.5), COP for the heating mode is given by:

−=

−2

2 1heating

h hCOP

h h3 (3.2)

51

Page 74: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 3.4 System schematic diagram transcritical CO2 heat pump

20

30

40

50

60

70

80

90

100

50 150 250 350 450Specific Enthalpy (kJ/kg)

Pres

sure

(bar

)

1

22'P2

P2't3

3

3h∆

2h∆4

5 6

Figure 3.5 Heat pump cycle on the P-h plane for various gas cooler pressures

With increase in discharge pressure from to 2P 2P′ for a constant cooler exit temperature

of , the heating COP gets modified as: 3t

52

Page 75: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

heatingCOP′ = 212

3232

)()(

hhhhhhh

∆+−∆+∆+−

(3.3)

Due to the unique behavioral pattern of carbon dioxide properties around the

critical point and beyond, the slope of the isotherms is quite modest for a specific

pressure range; at other pressures above and below this range, the isotherms are quite steep. As pressure increases, the quantity 3h∆ is large compared to , as is evident

from Figure 3.5, and this causes an increase in the modified COP value as can be

observed from Equation (3.3). At a particular pressure the COP attains a maximum value

and the corresponding pressure is termed the optimum pressure for the cycle. With further increase in pressure, does not produce the required gain over ∆ and thus the

COP begins to fall. The pressure range where the isotherms are fairly flat and where this

beneficial gain in COP occurs varies considerably with cooler outlet temperature. Hence

the gas cooler outlet temperature plays an influential role in determining the optimum

operating conditions for the cycle.

2h∆

h3h∆ 2

3.4 Thermodynamic cycle optimization

3.4.1 Process analysis and simulation

The temperature-entropy diagram of a transcritical CO2 cycle, shown in Figure

3.6, is generated employing the thermodynamic property code CO2PROP. As shown,

saturated vapor at state 6 is superheated to state 1 in the internal heat exchanger and then

compressed in the compressor to state 2. The supercritical carbon dioxide at state 2 is

cooled in the gas cooler to state 3 by rejecting heat to the external fluid (useful heating

effect). Unlike in a condenser, in the gas cooler the heat rejection takes place with a

gliding temperature. Carbon dioxide at high pressure is further cooled from 3 to 4 in the

internal heat exchanger. Following the heat exchanger, the carbon dioxide is expanded

through an expansion device to state 5, which is the inlet to the evaporator. The state of

the refrigerant changes from 5 to 6 as it evaporates by extracting heat from the external

fluid (useful cooling effect). In Figure 3.6, process 1-2s is an isentropic compression

process, while process 1-2 is the actual compression process. The dashed line below

53

Page 76: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

process 2-3 represents the single phase heating of external fluid and dashed line above

evaporating process represents the single phase cooling of external fluid.

The entire system has been modeled based on the energy balance of individual

components of the system. Steady flow energy equations based on first law of

thermodynamics have been employed in each case and specific energy quantities are

used. The following assumptions have been made in the thermodynamic analysis:

1. Heat transfer with the ambient is negligible.

2. Only single-phase heat transfer occurs for the external fluid.

3. Compression process is adiabatic but non-isentropic.

4. Evaporation and gas cooling processes are isobaric.

240

260

280

300

320

340

360

380

-2 -1.5 -1 -0.5

Specific entropy (kJ/kgK)

Tem

pera

ture

(K)

4

5 6

1

2

3

2s

Figure 3.6 Transcritical CO2 heat pump cycle on T-s plane

(i) Refrigerating effect of evaporator:

= −6evq h 5h (3.4)

(ii) Heating effect of gas cooler:

54

Page 77: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

= −2gcq h 3h

h

4

(3.5)

(iii) Work input to compressor:

2 1compw h= − (3.6)

(iv) Energy balance in the internal heat exchanger:

1 6 3h h h h− = − (3.7)

(v) Energy balance for the entire system:

ev comp gcw qq + = (3.8)

(vi) Energy balance for gas cooler with respect to external fluid being heated:

gcef ,m gcef r gcp gcef T m qc =∆ (3.9)

where is the average specific heat of external fluid being heated and ,p gcefc,p gcefT∆ is

its temperature rise across the gas cooler.

(vii) Energy balance in evaporator with respect to external fluid being cooled:

evef ,m evef r evp evef T m qc =∆ (3.10)

where is the average specific heat of external fluid being cooled in the evaporator and ∆ is its temperature drop across the evaporator. The COPs for

heating and cooling modes are given by:

,p evefc

evefT

gcheating

compCOP

qw

= and evcooling

compCOP q

w= (3.11)

Effectiveness of the internal heat exchanger is given by:

ε = 63

61

TTTT

−−

(3.12)

The isentropic efficiency of the compressor is given by:

η ,is comp = 12

12

hhhh s

−−

(3.13)

It may be noted that depends on the type of compressor, compressor design,

degree of superheat, etc. The isentropic efficiency of available CO

η ,is comp

,is comp

2 compressors varies in

wide range. Hence has been varied from 50 to 90% to observe its effect. η

55

Page 78: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Exergy analysis: An exergy analysis has been performed for each component of the

system employing the fundamental steady state equation:

Net exergy transfer from the component = Exergy transfer due to heat transfer

+ Exergy transfer due to work transfer + Change in flow exergy.

i) Compressor irreversibility,

2 1( )comp oT s si −= (3.14)

ii) Expansion process irreversibility,

5 4exp (oi T s s−= )

v

(3.15)

iii) Internal heat exchanger irreversibility,

1 46 3)[( ( )]oihxi T s s s s− −−= (3.16)

iv) Total specific exergy change of the refrigerant in the evaporator,

56e ( )v o ee T s s q−= − (3.17)

Neglecting irreversibility due to pressure drop, the evaporator irreversibility is given by:

56( )ev o evevefo

T

Ts s q−= −i T (3.18)

The exergy output of the evaporator,

= −* 1 oev ev

evef

Te qT

(3.19)

where evefT is the external fluid entropic average temperature, ( )

=−9 10

9 10ln /evef

T TT T

T

v) Total specific exergy change of the refrigerant in the gas cooler;

2 3( )gc gc oT s se q −= − (3.20)

Irreversibility due to heat transfer through a finite temperature difference,

2 3, (gc ogc Tgcef

oT TT

)s si q∆ − −= (3.21)

where, gcefT is the heating fluid entropic average temperature and is estimated the same

way as that for the evaporator.

Irreversibility due to pressure difference:

56

Page 79: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

,gc Pi ∆ = 2

ln 1 gco

PRT

P ∆ − −

(3.22)

Hence total irreversibility in the gas cooler is given by:

gci = ,gc Ti ∆ + ,gc P∆i (3.23)

Thus exergy output of the gas cooler, *

, ,( )gc gc gc T gc Pe e i i∆ ∆= − + (3.24)

vi) Finally combined exergy output of the system is, *syse = + *

eve *gce (3.25)

Second law (exergetic) efficiency for the system is given by the ratio of net exergy output

and the work input to the compressor: *

comp

sysII

ewη = (3.26)

Percentage irreversibility has also been introduced to represent the contribution of

each component to the total irreversibility in the system and is given by the ratio of the

irreversibility of the component to the total irreversibility of the system. Based on the

thermodynamic analysis presented above, a simulation code was developed. This code

was integrated with the thermodynamic property code CO2PROP to compute relevant

thermodynamic parameters.

3.4.2 Results and discussion

Important design and performance parameters for the carbon dioxide

based heating and cooling systems are COP, the exergetic efficiency, the various

temperatures and pressures of the working fluid at hot and cold ends, and individual

component irreversibility fractions. These parameters are suitably plotted to illustrate the

various performance trends and optimum operating points.

The performance of the carbon dioxide system being studied for simultaneous

heating and cooling applications is evaluated on the basis of heating and cooling COPs,

which have been estimated for various operating conditions with a 0.5 bar step increase

57

Page 80: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

in compressor discharge pressure. Results are presented in term of combined system

COP, which is simply the sum of the heating and cooling mode COPs.

The variation of maximum system COP with corresponding optimum discharge

pressure for various evaporator temperatures for a refrigerant temperature at cooler outlet

of 35 °C, isentropic efficiency of 85% and internal heat exchanger effectiveness of 60%

is shown in Figure 3.7. With an increase in evaporator temperature from –10 °C to 10 °C,

the system COP increases sharply recording an increase of over 75%. However optimum

pressure variation with evaporator temperature is much less significant. Although

experimental results show that with increase in evaporator temperature the optimum

pressure increases due to increase in cooler outlet temperature, here optimum discharge

pressure exhibits a different nature due to the constraint on cooler outlet temperature. As

mentioned earlier, due to divergent nature of the isotherms in the supercritical region, the

COP reaches a maximum at higher values of discharge pressure for lower evaporator

temperatures as shown in Figure 3.7.

5

6

7

8

9

10

-10 -5 0 5 10

Evaporator temperature (oC)

Max

imum

sys

tem

CO

P

85.5

86

86.5

87

87.5

88

Opt

imum

dis

char

ge p

ress

ure

(bar

)COPPressure

Figure 3.7 Variation of maximum system COP and optimum discharge pressure

with evaporator temperature

58

Page 81: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

As mentioned earlier, the variation in the cooler outlet temperature has a

significant impact on the optimal design conditions. The maximum system COP increases

sharply with a decrease in the cooler outlet temperature as is evident from Figure 3.8. For

an evaporator temperature of 0 oC and an internal heat exchanger effectiveness of 60%,

the system COP gets almost doubled with exit temperature falling from 50 oC to 30 oC

and the corresponding required optimum pressure decreases from 122 bar to 74 bar.

4

5

6

7

8

9

30 35 40 45 50

Cooler outlet temperature (oC)

Max

imum

sys

tem

CO

P

70

80

90

100

110

120

130

Opt

imum

dis

char

ge p

ress

ure

(bar

)

COP

Pressure

Figure 3.8 Variation of maximum system COP and optimum discharge pressure with

cooler outlet temperature

In the present study, it is observed that the influence of internal heat exchanger

effectiveness on system COP and optimum pressure is marginal. With changes in

effectiveness for a cooler outlet temperature of 35 °C and an evaporator temperature of 0 oC, negligible variations occur in maximum COP and optimum compressor discharge

pressure. So, the performance of internal heat exchanger has a minor influence on system

optimization at low and moderate gas cooler exit temperatures. However, isentropic

efficiency of compressor has strong influence on system performance and design. For

evaporation temperature of 0 oC, refrigerant temperature at gas cooler exit of 40 oC and

59

Page 82: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

internal heat exchanger effectiveness of 60 %, with increase in isentropic efficiency from

50 to 90%, the COP increases by 60% and the compressor discharge temperature

decreases by 25%; however the optimum compressor discharge pressure remains nearly

the same (98 bar). Hence the optimum compressor discharge pressure is usually not

dependent on the compressor performance.

Contours for maximum system COP are shown in Figure 3.9, where the evaporator

temperature varies between –10 oC and 10 oC, and the gas cooler exit temperature varies

from 30 oC to 50 oC. The maximum COP varies from 3.8 to 13.4. Iso-COP lines are fairly

parallel; COP values increase from maximum cooler exit temperature and minimum

evaporator temperature to minimum cooler exit temperature and maximum evaporator

temperature. So to improve COP, the system has to be designed for the lowest possible

cooler exit temperature and the highest possible evaporator temperature.

4 4.5

5

6

7

8

Figure 3.9. Maximum system-COP contour (0.5 increment of

60

10

is

12

o-lines)

Page 83: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 3

Optimum discharge p

have been shown in Figure

and gas cooler exit temper

73 bar to 123 bar and the coC. Both the iso-optimum

lines are nearly parallel

minimum evaporator temp

exit temperature and max

higher temperatures from t

pressure, which is corres

evaporator temperature, al

to restrict the system to l

minimum cooler exit tem

high COP. With increa

temperature, the optimum

temperature heating or low

120

95

.10 Optimum discharge pressure c

ressure and corresponding coole

s 3.10 and 3.11, respectively, for

atures. It may be noted that the o

orresponding cooler inlet tempera

pressure lines and corresponding

and vary the least at maximum

erature as opposed to a maximum

imum evaporator temperature. S

he system, it has to be designed f

ponding to maximum cooler exi

though the COP will be low und

ower optimum cycle pressures, i

perature and the maximum evap

se in cooler exit temperature

discharge pressure increases.

temperature cooling the system

61

115

110

105

o

r

th

p

tu

i

c

v

o

or

t

er

t

o

o

T

i

100

90

85 80

75

ntour (in bar)

inlet temperature contours

e same range of evaporator

timum pressure varies from

re varies from 73 oC to 151

so-cooler inlet temperature

ooler exit temperature and

ariation at minimum cooler

to obtain useful heating at

high compressor discharge

temperature and minimum

these conditions. However

has to be designed for the

rator temperature, yielding

r decrease in evaporator

his implies that for high

s not profitable in terms of

Page 84: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

system COP as well as cost as it necessitates a high optimum discharge pressure. Keeping

the smallest possible refrigerant temperature difference between evaporator and cooler

outlet (yielding high COP), a system can be designed for a low optimum discharge

pressure (yielding lower pressure ratio) to obtain heating output at high temperature only

through high superheat.

145 135

125

115

105

95

85

75

Figure 3.11 Gas cooler inlet temperature (oC) at optimum discharge pressure contour

(0.5 increment of iso-temperature lines)

Second law efficiency and percentages of irreversibility for different components

have been obtained for different operating conditions. For the gas cooler, mass flow rates

for both refrigerant and the fluid being heated are assumed to be the same (1 kg/s). In the

evaporator, the secondary fluid exit temperature is assumed to be 2 ˚C above the

evaporator temperature and its mass flow rate has been calculated per unit refrigerant

mass flow rate basis. Inlet conditions for both secondary fluids have been taken as 10 oC

lower than the cooler exit temperature. The total pressure drop in the gas cooler is taken

as 2 bar. The minimum temperature difference required at cooler outlet to avoid pinch

problem in the gas cooler increases as compressor discharge pressure decreases. This

62

Page 85: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

behaviour gets more complex in the neighbourhood of the critical point and the pinch

problem becomes quite significant due to the irregular constant pressure line in that zone.

To circumvent the pinch issue, we have taken an average temperature difference of 10 K

between CO2 gas and external fluid.

32

34

36

38

40

42

44

46

48

50

80 85 90 95 100 105 110 115 120

Compressor discharge pressure (bar)

Seco

nd la

w e

ffici

ency

(%)

tev=-10tev = –10 oC tev=-5tev = –5 oC tev=0tev = 0 oC tev=5tev = 5 oC tev=10tev = 10 oC

Figure 3.12 Variation of second law efficiency with discharge pressure for

different evaporator temperatures

Second law efficiency (combined) variations with compressor discharge pressure

for various evaporator temperatures at a cooler outlet temperature of 35 oC and internal

heat exchanger effectiveness of 60% are presented in Figure 3.12. Maximum values of

second law efficiency vary from 44.3 to 48.9% with corresponding discharge pressure

varying from 93 to 88 bar, respectively. Calculations show that unlike its effect on COP,

the heat exchanger effectiveness has some influence on the second law efficiency of the

system. With increase in heat exchanger effectiveness from 0.6 to 0.9, the maximum

value of second law efficiency increases by about 3%, although this effect is somewhat

more than that on the system COP (about 1%) due to assumptions made pertaining to the

temperature difference between refrigerant and secondary fluid in the heat exchanger.

63

Page 86: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Second law efficiency variation with compressor discharge pressure for different

gas cooler exit temperatures at an evaporator temperature of 0°C and internal heat

exchanger effectiveness 60% is presented in Figure 3.13. With variation in gas cooler exit

temperatures, maximum values of second law efficiency are found to vary widely from

53.8 to 30.8% with corresponding discharge pressure varying from 75 to 125 bar,

respectively.

5

10

15

20

25

30

35

40

45

50

55

75 85 95 105 115 125Compressor discharge pressure (bar)

Seco

nd la

w e

ffici

ency

(%)

30 oC 35 oC40 oC 45 oC50 oC 55 oC

Figure 3.13 Variation of second law efficiency with discharge pressure for

different gas cooler exit temperatures

Figure 3.14 represents the variation of percentages of total irreversibility of

different components with discharge pressure at a condition specified by an evaporator

temperature of 0°C, gas cooler inlet temperature of 35oC and internal heat exchanger

effectiveness of 60%. It is observed that the effect of heat exchanger effectiveness on

irreversibility is comparatively minor. It may be observed that the nature of the curves for

evaporator and gas cooler are different due to different assumptions for both. Near the

optimum discharge pressure, irreversibilities of compressor and evaporator are maximum

but the irreversibility of gas cooler is minimum. With increase in discharge pressure,

64

Page 87: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

irreversibility of gas cooler increases due to increase in effective temperature difference

in gas cooler heat exchanger and irreversibility of evaporator decreases due to increase in

evaporation capacity. Irreversibility of compressor basically depends on isentropic

efficiency of compressor, so proper design of compressor can reduce this irreversibility.

Fartaj et al. [105] also reported maximum irreversibility for compressor. To reduce

evaporation irreversibility, the evaporator is to be designed such that the temperature

difference between the fluids can be maintained as small as possible. It can be seen that

the percent irreversibility of expansion valve is highest among all the components. Due to

fast increase in gas cooler irreversibility, percentage irreversibility in expansion device

decreases even though its absolute value increases. Hence, an opportunity exists for

extracting work from the expansion process by employing a turbine in place of an

isenthalpic expansion valve (at least in large capacity systems).

5

10

15

20

25

30

35

40

45

80 85 90 95 100 105 110 115 120Compressor discharge pressure (bar)

Perc

enta

ge o

f irre

vers

ibilit

y

CompressorGas coolerEvaporatorExpansion deviceInternal HEX

Figure 3.14 Variation of percentages of irreversibility of different components with

discharge pressure

65

Page 88: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

The energy and exergy flow per unit work input (or 100%) for an evaporator

temperature of 280 K, cooler exit temperature of 310 K, internal heat exchanger

effectiveness of 80%, optimum discharge pressure of 90 bar, and ambient temperature of

300 K, are presented in Figure 3.15. Energy flow diagram implies that system COP is

8.08. As discussed earlier, exergy loss through expansion device is comparatively large

due to large pressure difference between the two sides and also due to the distinct

properties of CO2; near the critical point the entropy change as abruptly as other

properties (as pressure drops from supercritical to subcritical). Exergy loss in internal

heat exchanger is about 4%. For the conditions stated above, irreversibility of evaporator

is greater compared to that in the gas cooler because of larger average temperature

difference across the evaporator compared to that in the gas cooler.

Heating output Exergy input

Cooling output

354 %

Compressor input

100 % Trans- critical CO2 system

454 %

Net = 46.3%Evaporator output 12.3%

Gas cooler output, 34%

18.7 %

Internal HEX4.76%

Evaporator irreversibility, 13% Gas cooler irreversibility, 5.2%

Expansion device

Compressor 12.2%

100 %

Figure 3.15 Energy and exergy flow diagram

3.4.3 Correlations for optimum conditions

The system COP depends on evaporator temperature, compressor efficiency, gas

cooler outlet temperature, compressor discharge pressure and heat exchanger

effectiveness and given by,

66

Page 89: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

COP= (3.27) 23 ,( , , , ,ev is compf t t Pη )ε

The maximum system COP is given by, CO max 3 .( , , , )ev is compP f t t η ε= and the

corresponding optimum pressure is given by, . In the

present study, it is observed that for the given input temperatures the internal heat

exchanger has a negligible effect on the system performance. Moreover isentropic

efficiency of the compressor is exclusively dependent on compressor design. Hence

fixing these two (η and ε) parameters at 70% and 60% respectively, the optimum

condition dependence reduces to its functional form of:

2, 3 ,( , , ,opt ev is compP f t t= η )ε

,is comp

max 3( , )evCOP f t t= ; 2, 3( , )opt evp f t t= (3.28)

To establish a correlation for optimum conditions, a large database have been

generated by cycle simulation for internal heat exchanger effectiveness of 60% and

compressor isentropic efficiency of 70% for a range of evaporation temperatures from –

50 oC to 20 oC and a range of refrigerant temperatures at gas cooler exit from 30 oC to 60 oC. Performing a regression analysis on the data, the following relations have been

established to predict estimates of the optimum design parameters:

3 3 2,max 3 3 322.58 0.3575 0.6136 5.075 10 1.8 10 4.7 10sys ev ev evCOP t t t t t t− −= + − − × + × + × 3 2− (3.29)

3 22, 3 3 33.47 0.32 2.23 0.0134 3.7 10opt ev evp t t t t −= + + − + × t

2

(3.30)

2( , ) 10.65 3.78 1.44 0.0188 0.0092 2, 3 3t at P t t t topt ev ev= − + − − + (3.31)

It may be noted that in actual practice, the isentropic efficiency of a given compressor

decreases as the pressure ratio increases. However the correlation for optimum

compressor discharge pressure (Equation 3.30) can be widely used for any compressor

because of its near independence from isentropic efficiency.

67

Page 90: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3.5 Effect of cycle modifications on optimum discharge pressure

Although various modifications can be incorporated to improve the system

performance, heat transfer and fluid flow in the systems, the effect of four important

cycle modifications on the transcritical CO2 cycle performance has been investigated.

3.5.1 Internal heat exchanger

Simulation results show that effect of internal heat exchanger on system

performance and optimum discharge pressure is negligible at low and moderate

refrigerant temperature at the gas cooler exit; however it becomes more significant at

high refrigerant temperature at the gas cooler exit. At an evaporator temperature of 0 oC

and compressor isentropic efficiency of 70%, COP increases by 1% and optimum

discharge pressure decreases by 2% for a cooler exit temperature of 30 oC, whereas the

COP increases by 15% and optimum discharge pressure decreases by 13% for a cooler

exit temperature of 60 oC due to the use of a perfect internal heat exchanger. Influence of

internal heat exchanger effectiveness slightly increases at lower evaporator temperatures.

These results show that the use of internal heat exchanger may be profitable at higher

refrigerant temperature at the gas cooler exit.

3.5.2 Expansion with work recovery

Previous studies [17] show that the use of a work producing device (expander)

such as a turbine instead of an expansion valve can improve the COP for transcritical

CO2 systems. For the cycle with expander, system COP is evaluated by overall cooling

and heating output divided by net work input (compressor work – turbine work). A

evaporation temperature of 0 oC and the refrigerant temperature at gas cooler exit of 40 oC, internal heat exchanger effectiveness of 60% and compressor isentropic efficiency of

70 %, the system COP improves by about 18% when an expander of 80% isentropic

efficiency is used. However the optimum compressor discharge pressure decreases by

only 2.5%. Hence the use of work producing device has marginal effect on the optimum

discharge pressure, whereas it has significant effect on system performance.

68

Page 91: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3.5.3 Multi-staging

Several types of configurations such as flash gas removal, flash gas intercooling,

compression intercooling for a multistage transcritical CO2 cycle can be adopted to

improve the system performance depending on the requirement. Figure 3.16 shows the

CO2 cycle of multistage compression with inter-cooling. Simulation result shows that for

evaporation temperature of –40 oC, refrigerant temperature at gas cooler outlet of 40 oC

and isentropic efficiencies of 70% for both compressors, the cooling COP (evaporative

cooling output divided by work of both compressors) improves by about 12% and the

optimum compressor discharge pressure reduces by 30% compared to single stage for a

degree of inter-cooling of 30 oC. The intermediate pressure has been taken as the

geometric mean of higher and lower side pressures. Hence the compressor discharge

temperature corresponding to optimal condition will reduce for multistage cycle. It is

noteworthy that all the three cycle modifications will improve the system performance

and reduce the optimum discharge pressure, which can be advantageous in high pressure

side component design.

Specific entropy

Tem

pera

ture

intercooling

Figure 3.16 Multi-staging with flash gas inter cooling

69

Page 92: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3.5.4 Ejector-expansion device

Recent studies [23,24] show that the use of an ejector-expansion device instead of an

expansion valve can improve the COP for transcritical CO2 cycles. For the ejector-

expansion cycle as given in Figures 3.17 and 3.18, for a evaporation temperature of 0 oC

and the refrigerant temperature at gas cooler exit of 40 oC, and pressures after nozzle and

diffuser of 0.8 lower and 5 bar higher than evaporation pressure, respectively, the system

COP improves by about 18.2% when expander, diffuser and compressor isentropic

efficiencies of 80%, 90% and 70 %, respectively are used. However the optimum

compressor discharge pressure decreases by only 2.4%. Result shows very similar effect

of ejector-expander as the work-producing device on the optimum discharge pressure and

system performance. All the improvements discussed above shows similar trend of

optimum discharge pressure, as it is lower than that of basic cycle with expansion valve.

Figure 3.17 Schematic diagram of CO2 cycle with ejector-expansion device

70

Page 93: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

20

30

40

50

60

70

80

90

100

specific enthalpy (kJ/kg)

Pres

sure

(bar

)

Isotherm

3 2

1

104

56

78

9evP

gcP

Figure 3.18 P-h diagram of transcritical CO2 cycle with ejector-expansion device

3.6 Summary

A comprehensive property code for both thermophysical and transport property of

CO2 based on latest available correlations has been developed. A cycle model and

computer simulation of a transcritical carbon dioxide based simultaneous heating and

cooling system have been developed and the effect of various cycle modification

including internal heat exchanger, turbine and multi-staging have been studied. Based on

the results and optimization of the system, the following conclusions can be drawn.

1. Due to the near critical operation, CO2 exhibits some distinct properties (mostly

favourable to system design) such as high Prandtl number, homogeneous two-phase

flow compared to other conventional refrigerants.

2. The effects of evaporator temperature and gas cooler outlet temperature are more

predominant compared to internal heat exchanger effectiveness at optimized

conditions for the system. Although the internal heat exchanger effectiveness has

negligible effect on optimum condition for low and moderate gas cooler exit

71

Page 94: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

temperature, its effect is more significant at high gas cooler exit temperature and

lower evaporator temperatures.

3. Analyses of the optimum condition indicate that a system meant for low or moderate

temperature heating is more economical not only due to high system COP but also

due to lower optimum discharge pressure (low operating pressure ratio). Such a

system will yield good performance at lower external fluid inlet temperatures.

However it is possible to obtain high temperature heating at the expense of COP.

Even though COP is lower, a system designed for such application is worthwhile

because conventional refrigeration systems do not offer this high temperature heating.

So there is some trade off among high COP, high outlet temperature and cost of

superheating.

4. Design of all heat exchangers must endeavour to involve lower temperature

differences between the two fluids to yield higher second law efficiency, although

that will also cause the heat exchangers to be bulkier, resulting in higher weight, cost

and pressure loss.

5. Expressions for optimum cycle parameters have been developed and these

correlations offer useful guidelines for optimal system design and for selecting

appropriate operating conditions.

6. Multi-staging has more significant effect than an internal heat exchanger, work

producing turbine and ejector-expander device on the optimum compressor discharge

pressure.

72

Page 95: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 4

SIMULATION OF TRANSCRITICAL CO2 HEAT PUMP

FOR SIMULTANEOUS COOLING AND HEATING

4.1 Introduction

Due to its transcritical nature, the performance of transcritical carbon dioxide

system will not be similar to the conventional subcritical vapour compression

refrigeration or heat pump systems. Hence, simulation models developed for the

conventional systems cannot be employed for this new system. Thus there is a need for

theoretical system simulation studies as the experimental performance evaluation across a

broad test matrix is difficult, expensive and time consuming. Accurate computer

simulation of the system to predict its steady state performance and effects of various

design and operating parameters on the steady state performance will be very useful. This

chapter presents the simulation of transcritical CO2 heat pump for simultaneous heating

and cooling considering detailed heat transfer and pressure drop phenomena in each

component.

A steady-state simulation model has been developed to evaluate the system

performance of a transcritical carbon dioxide heat pump system for simultaneous heating

and cooling. Such a system is suitable, for example, in a dairy plant where simultaneous

cooling at 4oC and heating at 73oC are required. Effects of operating parameters such as,

temperature of heat exchanger fluid at the inlet, discharge pressure, compressor speed and

heat transfer area allocation between gas cooler and evaporator are presented. An

optimizing study for the best allocation of the fixed total heat exchanger inventory

between the evaporator and the gas cooler based on the heat exchanger area has been

carried out. A novel nomogram is prepared to show the steady state performance of the

optimized system under various operating conditions. This offers useful guidelines for

optimal system design and for selecting appropriate heat exchanger dimensions and

compressor speed for a specific application. Based on this simulation, component level

73

Page 96: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

exergy analysis has been done for the carbon dioxide based heat pump to cater for

heating and cooling services simultaneously. Irreversibilities of all components and the

second law efficiency of the system for different values of operating parameters have

been estimated. Finally, techniques to reduce the irreversibility for various components,

which leads to improved system exergetic efficiency, have been suggested.

Figure 4.1 Schematic layout of a transcritical carbon dioxide system for simultaneous water cooling and heating

A simplified sketch of a transcritical carbon dioxide based heating and cooling

system showing its main components is given in Figure 4.1. In this study, water is used as

the secondary fluid for both heating and cooling. The temperature of water at gas cooler

outlet is maintained at 73oC and it is 4oC at evaporator outlet as is typically required in

dairy plants. Both the gas cooler and evaporator are double-pipe counter flow type heat

exchangers, where refrigerant is in the inner side and water flows in outer annulus.

Internal heat exchanger is also counter flow type where hot refrigerant is in inner side and

cold refrigerant in outer side. The corresponding temperature-entropy diagram with water

flow lines is shown in Figure 4.2.

74

Page 97: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

4.2 Mathematical modelling

The entire system has been modelled based on energy and exergy balance of

individual components yielding conservation equations. To consider the highly variable

heat transfer characteristics (due to sharp variation of refrigerant properties near pseudo

critical region in the gas cooler), all the three heat exchangers have been discretised and

momentum and energy conservation equations have been applied to each segment.

Figure 4.2 T-s diagram of a transcritical CO2 heat pump processes

The following simplifying assumptions have been made in the analysis:

1. The system operates at steady state.

2. Only single-phase heat transfer occurs for water (external fluid).

3. Compression process is adiabatic but not isentropic.

4. Pressure drop in all the connecting pipes and heat transfer between the connecting

pipes and the ambient are negligibly small.

Applying the exergy balance and the energy conservation to each component of the

system, the following modular relations can be developed to yield the system model.

75

Page 98: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

4.2.1 Compressor

The refrigerant mass flow rate through the compressor is given by,

ref 1 sNm V60vρ η= (4.1)

For volumetric and isentropic efficiencies of compressor, correlations developed for

semi-hermetic compressors [106] have been used in this simulation.

The volumetric efficiency for the semi-hermetic compressor is given by:

(4.2) 20.9207 0.0756 0.0018 v prη = − + pr

The isentropic efficiency (defined as: ,is compη =12

12

hhhh s

−−

) of the semi-hermetic compressor is

estimated employing the following correlation:

2 3is,c = 0.26 + 0.7952 0.2803 + 0.0414 0.0022 4

p p pr r rη − − − pr (4.3)

with compressor pressure ratio pr ( ) varying between 1.5 and 6.5. /dis sucP P=

The exergy input (same as power input) to the compressor is given by,

2 1(in refE m h h= − )

1)

(4.4)

Irreversibility in the compressor is estimated from:

0 2(comp refI T m s s= − (4.5)

4.2.2 Gas cooler

One of the computational segments of gas cooler of length L∆ is shown in Figure

4.3. Employing LMTD expression, heat transfer in segment is given by, thi

1 1

1 1

( ) (( )

ln

i i i igcr gcw gcr gcwi i

gcr gc i igcr gcwi i

gcr gcw

T T T TQ UA

T TT T

+ +

+ +

− − −=

− −

) (4.6)

Additionally, energy balance in each section of gas cooler yield:

1refm ( )i i i i i

gcw gco gcrQ Q Q h h ++ = = − (4.7)

where igcoQ is heat loss to ambient. The heating effect, i

gcwQ is given by:

76

Page 99: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

1gcwm (i i

gcw pw gcw gcwQ c T T += − )i (4.8)

Summation of heat transfer in all segments gives total heat transfer in gas cooler. The

overall heat transfer coefficient for the segment of gas cooler has been calculated using

the fundamental equation for overall heat transfer coefficient yielding:

( )ln /1 1 12

o ii

gc r r t w

d dUA A Lk Aα π α

= + +∆ w

(4.9)

Water flow (Annular side)

1 1,i igcr gcrT P+ + ,i i

gcr gcrT P

L∆

igcwT1i

gcwT +

wαwk

,rb rbT P

,w wT P

igcQ

gcwm

refm

Refrigerant flow (Inner side)

di do Di

Figure 4.3 A computational segment of the gas cooler

The resulting irreversibility is expressed as:

gco P 00 gcw pw ref 2 3 gcr 0

gci

TT m c ln m (s s ) + 1

TP

gc gcw gcgcw

TI I IT

∆ ∆

= − − + +

Q

(4.10)

The irreversibility due to pressure drop is given by:

gcwP P ir igcr gcw gcr gcw

gcr gcw

mmI I Pρ ρ

∆ ∆+ = ∆ + ∆∑ ∑ P (4.11)

Heat transfer and pressure drop correlations: To estimate heat transfer rates,

Gnielinski equation is not suitable for normal tubes (although it is valid for micro-

channels) due to large variation of fluid properties in the radial direction. To alleviate this

deficiency, Pitla et al. [38] proposed a modification for supercritical in-tube carbon

77

Page 100: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

dioxide cooling, incorporating both bulk and wall properties. This correlation, used for

gas cooler model, is given by;

2rw rb rw

rrb

Nu Nu kNuk

+=

r

ri

Nu kd

α = rb (4.12)

Here, and are the Nusselt number at bulk and wall temperature respectively,

predicted by Gnielinski equation within the range 2300 < Re < 10 and 0.6 < Pr < 10 .

rbNu rwNu

6 5

1/ 2 2 /3

( / 8)(Re 1000) Pr1.07 12.7( / 8) (Pr 1)

fNuf

−=

+ − (4.13)

and Petukhov-Popov-Kirilov correlation for Re > 106

1/ 2 2 /3

( / 8) Re Pr1.07 12.7( / 8) (Pr 1)

fNuf

=+ −

(4.14)

where f is the friction factor given by: 2(0.79ln(Re) 1.64)f −= −

Neglecting inertia effect, the refrigerant-side pressure drop in each heat exchanger

segment is given by [64], 2

1 1.22i i gcr gc

gcr gcrrb i

G LP P dξρ+ ∆− = +

(4.15)

where modified friction factor ξ is given by Petrov and Popov equation,

( ) 21.82ln(Re ) 1.64s

rw rwrw

rb rb

ρ µξρ µ

− = −

(4.16)

where, the exponent s is given by, 0.42

0.023i

gcr

gcr

Qs

G= .

4.2.3 Evaporator

The evaporator also has been discretised lengthwise for computation similar to the

gas cooler. Employing LMTD expression, heat transfer in the segment is given by, thi

( ) ( )1 1

1 1( )

ln

i i ievw evr evw evri i

evr ev i ievw evr

i ievw evr

UAT T T T

QT T

T T

+ +

+ +

− − −=

− −

i

(4.17)

Additionally, energy balance in each section of gas cooler yield:

78

Page 101: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

++ = = −1

0 ref (i i i i

evw ev evrQ Q Q m h h )i

)i

(4.18)

where Q is the heat gain with ambient and the cooling effect, Q is given by: ievo

ievw

1

evwm (i i

evw pw evw evwQ c T T+= − (4.19)

Summation of heat transfer in all segments gives total heat transfer in evaporator. The

overall heat transfer coefficient for each segment of the evaporator has been calculated in

the same way as for the gas cooler.

The irreversibility or exergy loss in the evaporator is expressed as:

Pevi 00 ref 6 5 evw pw evr

evo

TT m (s s ) m c ln +I 1T

Pev evw evo

evw

TIT

∆ ∆ = − − + +

I Q

(4.20)

where the temperature related terms on the right-hand side are due to the temperature

difference and heat interaction with ambient respectively. The pressure related terms are

due to pressure drop in refrigerant and water side respectively and are given by,

refP P i evwevr evw evr evw

evr evw

m m iI I Pρ ρ

∆ ∆+ = ∆ + ∆∑ ∑ P (4.21)

Heat transfer and pressure drop correlations: The convective heat transfer coefficient

has been estimated using the Wattelet-Carlo correlation, which was originally developed

for R-12, R-134a and a mixture of R22/R124/R1542a and later validated by Rieberer [18]

for R-744 evaporation in tubes. This is the preferred correlation for two-phase flow in the

evaporator and is expressed as:

1.r Fα α= 0.8 0.41 0.023 Re Prl

l li

kd

α = (Dittus-Boelter correlation) (4.22)

where0.831 1.925 ttF X −= + ttX is the Lockhart-Martinelli parameter given by:

0.5 0.10.91 v l

ttl v

xXx

ρ µρ µ

− =

(4.23)

The refrigerant side pressure drop, evrP∆ , is given by (Lockhart and Martinelli equation):

21 4 (1 )

2i i ev evrr

evr evr li l

L GfP P xd

2 2φρ

+ ∆− = − (4.24)

where, friction factor 0.250.0791Rerf−= l

79

Page 102: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

The two-phase frictional pressure drop multiplier is evaluated from: 1/ 2

1.655

7.2421.376lttX

φ

= +

where ttX is the Lockhart-Martinelli factor.

Waterside heat transfer and pressure drop: wα is the waterside heat transfer

coefficient and has been evaluated by the conventional Dittus-Boelter equation for

annular flow in both evaporator and gas cooler. For water-side friction factor, the

classical Blasius correlation [107] is used: 0.250.0791Rewf

−= w

2wT

wT

o

(4.25)

All water properties are assumed to be temperature dependent only for which

polynomial expressions have been used. Viscosity (10−3 Ns/m2) and thermal conductivity

(W/mK) of water can be expressed as (Tw in K): 5 = 10.16 0.05 +6.3 10 w wTµ −− × (4.26)

0.08331 0.00174 wk = + (4.27)

4.2.4 Internal heat exchanger

Discretisation and energy balance in the internal heat exchanger have been carried

out the same way as that in the gas cooler and similar correlations have been employed as

well for estimating heat transfer coefficients and pressure drop. It may be noted that

Reynolds number for annular flow is based on hydraulic diameter, ( ) and

Nusselt number is based on equivalent diameter {=

iD d= −

( )2 2i oD d d− o }. Internal heat

exchanger effectiveness (ε) is expressed as:

1

3 6

h hh h

ε −=−

6

0

(4.28)

Heat balance in the internal heat exchanger yields:

1 6 3 4( ) ( )ref r ihxm h h m h h Q− = − + (4.29)

where, Q is the heat gain ( sign) or loss (0ihx + − sign) with the ambient.

The irreversibility in the internal heat exchanger is given by,

80

Page 103: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

00 1 6 3 4 0

,

[( ) ( )] 1Pihx ref ihx ihx

ihx r

TI T m s s s s I QT

∆ = − − − + +

− (4.30)

It may be noted that the last term on the right hand side of this equation is always positive

whether or ,ihx rT > 0T< , which indicates that exergy is always degrading whether heat

loss or gain with the component. Heat transfer with the ambient for all the components

has been estimated employing the conventional natural convection equations assuming

that no other heat transfer mode is existent.

4.2.5 Expansion device

The expansion process is considered to be isenthalpic, yielding:

4 5h h= (4.31)

The irreversibility during the expansion process is expressed as:

exp 0 5 4(ref )I T m s s= −

)

(4.32)

4.2.6 Performance parameters

The system performance measures are based on the system COP and the exergetic

efficiency. The system COP (combined heating and cooling) is given by,

( i isys evw gcw compCOP Q Q W= +∑ ∑ (4.33)

The exergetic efficiency is the percentage ratio of total exergy output to the

exergy input, where the output exergy can be found by subtracting the total system

irreversibility (summation of irreversibilities of all the components in the system) from

exergy input to the system and is given by:

100% 1 100%in Components ComponentsII

in in

E I IE E

η −

= × = −

∑ ∑ × (4.34)

81

Page 104: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

evit

gcit evwm evot gcw gcot

refm

6 1P −∆ 6 1T −∆ 4P ε 3 *t

6 1T −

3 3 *t=

ε

Yes

Yes

Yes

No

No

Update Pdis

Update P6

No Update P1, Superheat

Output: state points, , COPmax, Pdis,opt

Maximum COP

If: t

Superheat = ∆

Input internal heat exchanger model Output: , , , ,

Input evaporator model & find P5, x5, h4

Input gas cooler model & find P3, t3

Calculate: mass flow rate,

Guess: Superheat & P1=P6, Psuc=P1

Guess: evaporator outlet pressure (P6)

Initial guess: discharge pressure (Pdis/P2)

Input: Evaporator dimensions (di, do, Di, Lev), Gas cooler dimensions (di, do, Di, Lgc), Internal heat exchanger dimensions (di, do, Di, Lhx), Compressor data; Vs, N, Water: ,

, or , m or .

Figure 4.4 Flow-chart for the simulation model

82

Page 105: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

4.3 Numerical procedure and input parameters

A computer code has been developed to simulate the transcritical carbon dioxide

system for dairy applications at various operating conditions. The simulation code

incorporates the property subroutine ‘CO2PROP’ to estimate the thermodynamic and

transport properties of carbon dioxide. Property variation is very abrupt near the critical

region and this is encompassed by the gas cooler model. To consider this variation, the

entire length of the gas cooler has been divided equally into several discrete segments and

each segment has been treated as a counter flow heat exchanger. In each segment, heat

transfer coefficients for both refrigerant and water are calculated based on mean values.

This way, the gas cooler is made equivalent to a number of counter flow heat exchangers

arranged in series and the combined heat transfer of all the segments is the total heat

transfer of the gas cooler. Therefore, fast changing properties of CO2 have been modelled

accurately in the gas cooler. For the evaporator and internal heat exchanger, similar

discretisation has been carried out as well to obtain good accuracy.

At first the system was simulated based on the momentum and energy balance for

each component by Newton-Raphson iterative method, employing the property

subroutine code CO2PROP and the heat transfer calculations to evaluate the state points

with all the necessary thermodynamic and transport properties, to get maximum

accuracy. As shown in the flow chart (Figure 4.4), outlet temperatures or mass flow rates

of water may be the inputs and the code solves for the state points and performance

parameters such as cooling and heating output, compressor work, maximum COP and

corresponding optimum pressure, and internal heat exchanger effectiveness. Then the

irreversibility of each of the components, exergetic output and efficiency get evaluated

using the exergy balance equations presented in the previous section.

The performance of the system being studied for simultaneous heating and cooling

applications is evaluated on the basis of system COP, component irreversibility and

system exergetic efficiency, which have been estimated for various water inlet

temperatures for the heat exchangers, compressor speed and heat exchanger dimensions

of the heat pump envisaged to cater for heating at 73 oC and cooling at 4 oC

simultaneously. The gas cooler model is validated with the experimental results of Pitla et

83

Page 106: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

al. [38]. Figure 4.5 shows the variation of refrigerant side heat transfer coefficient and

mean values of Nusselt number in the gas cooler with bulk temperature for mass flow

rate of 0.029 kg/s, inlet pressure of 108 bar and water inlet and outlet temperatures of 30 oC and 73 oC respectively. It is observed that the heat transfer variation is predominant

particularly near critical region due to abrupt change in refrigerant properties; heat

transfer coefficient experiences a threefold change and Nusselt number varies from 720 at

gas cooler inlet to 550 at gas cooler exit with a peak value of 1180. This trend can be

attributed to the fact that, for certain tube diameter, though the Reynolds number of

refrigerant flow slightly decreases in the downstream direction due to increase in both

density and viscosity, the Prandtl number increases very significantly from 0.9 to 3.2 with

a peak value of 4.2 near the critical region due to sudden rise in isobaric heat capacity.

Similar theoretical and experimental results can be found in the literature [34,38] as well.

Absolute values of Nusselt number and heat transfer coefficients differ from

experimental values of Pitla et al. [38] due to different waterside temperatures resulting in

different tube wall temperatures. An inner diameter of 4.72 mm, used to plot Figure 4.5,

results in a total pressure drop of 1.2 bar; as expected, for an inner diameter of 7.875 mm

pressure drop becomes lower but the corresponding heat transfer coefficient gets halved.

The cooling COP as well as pressure loss increase with increase in heat exchanger length.

Here, results are presented for standard stainless steel inner tubes of 3/8 inch OD (9.525

mm, thickness of 0.815 mm, suitable to withstand high pressures) and outer tube of 5/8

inch OD (14.097 ID and 15.875 mm OD with 0.815 mm thickness) for evaporator,

internal heat exchanger and gas cooler. Internal heat exchanger length has been taken as 4

m, which yields an effectiveness of about 60 – 70%. A Dorin brand compressor (model

TCS113) with a rated speed of 2900 rpm and a swept volume of 11.7 cm3 has been

chosen [10]. Ambient temperature is assumed to be 30 oC (average in the Indian sub-

continent) for the analysis.

Presented results show the effects of varying area ratio and operating conditions

for the same combined length (25 m) of evaporator and gas cooler. The parameters varied

are: compressor speed from 1500 to 3500 rpm, water inlet temperature from 20oC to 40oC

and gas cooler to evaporator heat transfer area ratio from 1.0 to 3.0 (same as the length

84

Page 107: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

ratio of gas cooler and evaporator in this case because of equal diameters). Unless

otherwise specified, the mean values of these parameters are: compressor speed of 2900

rpm, water inlet temperature of 30oC and an area ratio of 1.8. One of the three

parameters is varied within the specified range stated above while the other two are kept

constant at the mean value to generate data for the plots. The compressor discharge

pressure has been optimized based on the maximum system COP using steady state

simulation and both energetic and exergetic results are presented corresponding to the

optimum value.

5

7

9

11

13

15

300 320 340 360 380 400Refrigerant bulk temperature (K)

Hea

t tra

nsfe

r coe

ffici

ent

500

600

700

800

900

1000

1100

1200

Mea

n N

usse

lt N

umbe

r .

2( / )r kW m Kα

rNudi = 4.72 mm do = 6.35 mm Lgc = 15 m T2 = 398 K

Figure 4.5 Variation of refrigerant-side heat transfer properties with bulk

temperature in gas cooler

4.4 Results of energy analysis

The variation of cooling load, compressor work and system COP with area ratio

for water inlet temperature of 30oC and rated speed of 2900 rpm are shown in Figure 4.6,

and corresponding optimum pressure and refrigerant mass flow rate variations are shown

in Figure 4.7. It may be observed that with increase in area ratio and at optimum

discharge pressure, cooling output and compressor work reduce due to decrease in

85

Page 108: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

refrigerant flow rate. The decrease in mass flow rate is due to decrease in optimum

discharge pressure as decrease in suction density (Figure 4.7). Hence, the system COP

first increases and then decreases with a peak value of 3.95 at a gas cooler-to-evaporator

area ratio of 1.8 (Figure 4.6). Whereas the corresponding optimum gas cooler to

evaporator conductance (UA) ratio is 1.15 (close to equal allocation). This optimum area

ratio shifts to higher values with decrease in compressor discharge pressure as evident

from Figure 4.8. The maximum cooling COPs also decrease with decrease in discharge

pressure. It may be noted that the optimum value of heat exchanger area ratio also

depends on other factors, such as water inlet temperature, heat exchanger dimensions and

compressor specifications.

2.8

3.3

3.8

4.3

4.8

1 1.5 2 2.5 3Area ratio (Agc/Aev)

(kW

)

3.8

3.84

3.88

3.92

3.96

4

Syst

em C

OP

Compressor workCooling outputSystem COP

Figure 4.6 Variation of system performance with area ratio

The effect of compressor speed on system performance at a heat exchanger area

ratio of 1.8 and a water inlet temperature of 30oC are presented in Figure 4.9. It is

observed that the system COP at optimum discharge pressure decreases as both

compressor work and cooling output increase with compressor speed. This is due to an

increase in mass flow rate of refrigerant with compressor speed. The optimum discharge

86

Page 109: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

pressure was found to remain almost constant varying between 107 and 109 bar as the

speed was modulated between 1500 and 3500 rpm.

0.022

0.024

0.026

0.028

1 1.5 2 2.5 3Heat exchanger area ratio

Ref

riger

ant m

ass

flow

rate

(kg/

s)

100

102

104

106

108

110

Pdis

,opt

(bar

)

mass flow rate

optimum pressure

Figure 4.7 Variation of optimum discharge pressure and mass flow rate with area ratio

3

3.2

3.4

3.6

3.8

4

1 1.5 2 2.5 3Heat exchanger area ratio

Syst

em C

OP

90 bar100 bar110 bar

Figure 4.8 Variation of system performance with area ratio and discharge pressure

87

Page 110: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

1.5

2

2.5

3

3.5

4

4.5

5

5.5

1500 2000 2500 3000 3500Compressor speed (rpm)

(kW

)

3.9

3.95

4

4.05

4.1

4.15

4.2

Syst

em C

OP

Compressor workCooling outputSystem COP

Figure 4.9 Variation of performance with compressor speed

2.8

3.4

4

4.6

5.2

20 25 30 35 40

Water inlet temperature (oC)

(kW

)

3.4

3.6

3.8

4

4.2

4.4

Syst

em C

OP

Compressor workCooling outputSystem COP

Figure 4.10 Variation of performance with water inlet temperature

88

Page 111: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

100

105

110

115

120

20 25 30 35 40

Water inlet temperature (oC)

Pdis

,opt

(bar

)

0.024

0.0242

0.0244

0.0246

0.0248

0.025

Ref

riger

ant m

ass

flow

rate

(kg/

s)optimum pressuremass flow rate

Figure 4.11 Variation of optimum pressure and mass flow rate with water inlet

temperature

The effect of water inlet temperature at a compressor speed of 2900 rpm and area

ratio of 1.8 is shown in Figures 4.10 and 4.11. As the water inlet temperature increases,

the cooling COP decreases due to the combined effect of shifting of cooler exit

refrigerant temperature to higher value that cause the degradation of heat transfer

properties in gas cooler and decrease in refrigeration effect. Water inlet temperature has a

negligible effect on refrigerant mass flow rate as shown in Figure 4.11. However, the

optimum discharge pressure increases rapidly with increase in water inlet temperature

due to rapid change of refrigerant outlet temperature in the gas cooler.

A nomogram has been developed based on the results of steady state simulation

model (Figure 4.12). This graphical aide to system design has been developed to obtain a

design through optimal area ratio, discharge pressure for achieving maximum cooling

COP. The parameters varied are compressor speed, water inlet temperature and area ratio.

Such a nomogram helps the design engineer to ascertain expected output parameters once

the input design and operating parameters are fixed. For example, when the water inlet

temperature is 30°C, compressor speed is 2500 rpm, and consequently to attain maximum

89

Page 112: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

system COP of 4.01, optimum area ratio and discharge pressure have to be 1.76 and 107

respectively as is illustrated in the nomogram, and the system is expected to yield a

cooling output of 4 kW.

Figure 4.12 Design nomogram for a transcritical carbon dioxide heat pump

The optimization of a carbon dioxide based cooling-heating system is quite

complex as it depends on several parameters such as compressor speed and efficiency,

water inlet temperature and flow rates, heat exchanger dimensions, etc. However,

constraining some of the parameters such as required cooling/heating output, specific

90

Page 113: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

compressor, area ratio, etc. based either on the requirements or other limitations makes

the task somewhat simpler. For the system studied here, the output cooling capacity and

water outlet temperatures are fixed by the application; in addition a standard Dorin

compressor with fixed displacement volume and speed is selected and the area ratio is

taken as 1.8. Under these conditions, the maximum COP (at optimum discharge pressure)

and the optimum discharge pressure itself become a function of the water inlet

temperature only. For the above input conditions, the following equations can be

regressed from the generated data with correlation coefficients (R2 values) of 0.999 and

0.995 respectively:

= −,max 5.12 0.039sys wiCOP t and (4.35) , 85.45 0.774dis opt wiP t= +

where water inlet temperature (twi) ranges between 20 and 40°C. is the system

COP at optimum discharge pressure.

,maxsysCOP

4.5 Results of exergy analysis

Both system COP and exergetic efficiency increase initially with area ratio (ratio

of gas cooler surface area to that of evaporator, here simply the length ratio as both have

the same diameter) and beyond a certain value, decrease as is evident from Figure 4.13.

Although the system COP attains a maximum at an area ratio of about 1.8, the exergetic

efficiency reaches the maximum at an area ratio of about 1.85. The irreversibility of the

evaporator increases and that of the gas cooler decreases with increase in area ratio

(Figure 4.14). This is attributed to the fact that effective temperature difference in the

evaporator rises while that for the gas cooler drops with increase in area ratio. The

irreversibility of the internal heat exchanger decreases for larger area ratio values since

the pressure for both the fluids drops. However, as shown, the influence of the internal

heat exchanger on system performance is marginal. Due to a decrease in entropy

generation rate at lower pressure drop in the expansion valve, irreversibility decreases as

area ratio increases. Although the irreversibility due to frictional pressure loss is

negligible compared to the total exergy loss (Figure 4.15), that for the evaporator is

significantly more than that yielded by internal heat exchanger and gas cooler. This could

91

Page 114: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

be attributed to pressure drop in evaporator being more than that in gas cooler and

internal heat exchanger due to both frictional and momentum effects.

3.65

3.7

3.75

3.8

3.85

3.9

3.95

1 1.5 2 2.5

Heat exchanger area ratio

Syst

em C

OP

20

20.5

21

21.5

22

22.5

23

23.5

24

Exer

getic

effi

cien

cy (%

)

Exergetic efficiency

System COP

Figure 4.13 System performances with varying heat exchanger area ratio

0

5

10

15

20

25

30

35

1 1.5 2 2.5

Heat exchanger area ratio

Com

pone

nt ir

reve

rsib

ility

(%)

Compressor

Internal HEX

Exp. valve

Evaporator

Gas cooler

Figure 4.14 Variation of component irreversibility with heat exchanger area ratio

92

Page 115: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

0.05

0.15

0.25

0.35

0.45

0.55

0.65

0.75

1 1.5 2 2.5

Heat exchanger area ratio

Irrev

ersi

bilit

y du

e to

pre

ssur

e dr

op (%

)

Evaporator

Internal HEX

Gas cooler

Figure 4.15 Influence of heat exchanger area ratio on irreversibility due to pressure drop

3

3.5

4

4.5

5

20 25 30 35 40

Water inlet temperature (oC)

Syst

em C

OP

18

19

20

21

22

23

24

25

Exer

getic

effi

cien

cy

System COP

Exergetic efficiency

Figure 4.16 System performances with varying water inlet temperature

The effect of water inlet temperature at a compressor speed of 2900 rpm, ambient

temperature of 30oC and area ratio of 1.8 is shown in Figures 4.16 and 4.17. As the water

inlet temperature increases, the system COP decreases due to an increase in compressor

93

Page 116: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

work and also due to decrease in cooling output. Water inlet temperature has a negligible

effect on refrigerant mass flow rate. However, the optimum discharge pressure increases

rapidly with increase in water inlet temperature due to rapid change of refrigerant outlet

temperature in the gas cooler. Hence the exergetic efficiency of the system deteriorates

with rise in water inlet temperature as the exergy losses in the evaporator and in the

internal heat exchanger increase rapidly due to the increase in heat exchanger temperature

differences. Although the irreversibility in gas cooler remains fairly constant with

changes in water inlet temperature, the exergy loss in the expansion valve increases.

The effect of compressor speed on system performance at a heat exchanger area

ratio of 1.8 and a water inlet temperature of 30oC is presented in Figure 4.18. It is

observed that the system COP at optimum discharge pressure decreases as both

compressor work and cooling output increase with compressor speed. Maximum

increment of irreversibility occurred in the gas cooler. This may be attributed to an

increase in temperature difference in the gas cooler as well as the increase in pressure

loss due to rapid increase in flow velocity. Thus increase in compressor speed yields

higher capacity and higher irreversibility as well due to higher mass flow rate and higher

frictional pressure loss.

0

5

10

15

20

25

30

35

20 25 30 35 40

Water inlet temperature (oC)

Com

pone

nt ir

reve

rsib

ility

(%) CompressorInternal HEXExp. deviceEvaporatorGas cooler

Figure 4.17 Variation of component irreversibility with water inlet temperature

94

Page 117: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3.8

3.9

4

4.1

2000 2500 3000 3500

Compressor speed (rpm)

Syst

em C

OP

20

21

22

23

24

25

Exer

getic

effi

cien

cy (%

)

System COP

Exergetic efficiency

Figure 4.18 Effect of compressor speed on system performance

Comp-ressor input, 100%

Output 23.1 %

Gas cooler, 17.0 %

Evaporator, 13.1 %

Expansion device, 10.6 %

Internal HEX, 2.7 %

Compressor, 33.5 %

Figure 4.19 Exergy flow (Grassmann) diagram at mean operating condition

The exergy loss in different components (Grassmann diagram) is shown in Figure

4.19. Similar to the behaviour reported for systems based on conventional refrigerants

such as R22, R12, R502 [108,109], exergy loss is maximum in compressor followed by

that in gas cooler, evaporator and expansion device, while exergy loss in the internal heat

95

Page 118: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

exchanger is negligible. Due to the high pressure drop occurring in the system being

studied, the expansion device contributes a much larger fraction of irreversibility

compared to conventional systems.

4.6 Improvement of exergetic efficiency

The exergy loss is relatively high in compressor, gas cooler, evaporator and

expansion valve while that in the internal heat exchanger is insignificant. Hence

contribution of the internal heat exchanger towards exergy destruction and its influence

on the system performance is not predominant; however, by increasing the effective heat

transfer area, we can modestly increase its effectiveness as well as the system COP and

exergetic efficiency. The primary challenge is to improve the system performance and

exergetic efficiency by improving the performance (by controlling exergy loss) of the

above stated four influential components. Some of the important improvement measures

are presented with associated betterment in system performance.

3.5

4

4.5

5

5.5

50 55 60 65 70 75 80Compressor isentropic efficiency (%)

Syst

em C

OP

2022242628303234363840

Exer

getic

effi

cien

cy (%

)System COP

Exergetic efficiency

Figure 4.20 System performances with varying compressor isentropic efficiency

96

Page 119: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.8

3.2

3.6

4

4.4

4.8

15 20 25 30 35

Total length (m)

Syst

em C

OP

16171819202122232425262728

Exer

getic

effi

cien

cy (%

)

System COP

Exergetic efficiency

Figure 4.21 System performances with varying total heat exchanger length

4.6.1 Compressor

Process irreversibility (due to mixing, throttling, internal convection, etc.),

pressure loss due to friction in inlet and outlet valves, and heat loss to the environment

are the basic reasons for the exergy loss in the compressor. The system COP and the

exergetic efficiency increase linearly with the isentropic efficiency as shown in Figure

4.20. Isentropic efficiency primarily depends on the compressor design and the working

pressure, so a superior compressor design will lead to higher isentropic efficiency

resulting in a reduction in process irreversibility, within certain limit. With a 10 %

increase in isentropic efficiency, system exergetic efficiency improves by almost 3%.

4.6.2 Evaporator and gas cooler

Irreversibilities in the evaporator and the gas cooler occur due to the temperature

difference existing between two heat exchanger fluids, pressure loss, flow imbalance and

heat transfer with the ambient. Results show that almost 90% of the irreversibility occurs

due to fluid temperature difference and 10% due to the rest. At the mean conditions, the

average fluid temperature differences in evaporator and gas cooler are about 22oC and

40oC respectively, whereas the pressure losses are 2.5 bar and 0.9 bar respectively. The

97

Page 120: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

effective fluid temperature difference can be reduced by increasing heat transfer area,

either by increasing the heat exchanger length or by incorporating fins; however, both

will result in higher pressure drop. System COP and exergetic efficiency of the system

increase, first rapidly and then slowly, because of increase in irreversibility due to

pressure loss (Figure 4.21). Heat transfer with the ambient is inconsequential for the

system performance; if better insulation reduces net outer wall conductivity from 20 to 1

W/mK, exergetic efficiency will increase by a mere 0.2 %.

4.6.3 Expansion device

Replacement of the expansion valve by a turbine is an option available to improve

the performance of the system and reduce the irreversibility of the expansion process. A

study [17] adopting such a technique reported that an expansion work recovery turbine

with isentropic efficiency of 60% would reduce the contribution of this process to total

cycle irreversibility by 35% in the thermodynamic cycle. In this system at the mean

condition stated above, using an expansion work recovery turbine of 85% isentropic

efficiency, both the system COP and the exergetic efficiency will improve by about 22%.

Hence, improvement in system performance through this technique is quite significant.

However such extensive hardware addition may not be economically feasible in many

practical applications, especially for small capacities.

4.7 Summary

The steady state performances for both energetic and exergetic points of view of a

carbon dioxide based transcritical heat pump to cater for heating and cooling

simultaneously have been presented in this chapter. The results are obtained for a system

that can be used, for example, in dairy applications of chilling and pasteurization of milk.

Unlike previous studies reported in literature, realistic heat transfer and fluid flow effects

have been included in this comprehensive analysis. The highly variable heat transfer

characteristics of the refrigerant in the gas cooler have been included in the analysis for

better accuracy. Spatial discretisation of all the heat exchangers has been carried out as

well to yield better precision where fluid properties change rapidly. A computer model

98

Page 121: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

has been developed to first simulate the system at steady state for different operating

conditions and then evaluate the system performance based on COP as well as exergetic

efficiency. Additionally, component level irreversibility analyses have been performed.

Results are obtained by varying important operating and design parameters such as heat

exchanger area ratio, compressor speed and water inlet temperature over a given range.

An enumerated summary of the results is as follows:

1. Optimum heat exchanger area ratio ranges between 1.7 and 1.9 for maximum

system COP as well as maximum exergetic efficiency at optimum discharge

pressure, although optimum value for later is slightly more.

2. Favourable heat transfer properties of carbon dioxide in both two-phase and

supercritical region and an efficient compression process contribute significantly

toward high system COPs and exergetic efficiency values. Although, existing

carbon dioxide compressors have lower volumetric efficiency and isentropic

efficiency resulting in lower system COP, it is expected that with development of

compressors of higher volumetric and isentropic efficiency, the system performance

can be improved significantly in the near future.

3. A nomogram with compressor speed and water inlet temperature as independent

parameters and optimum discharge pressure, optimum area ratio and maximum

COP as output parameters has been presented. The nomogram thus shows the

balanced performance of the system at various operating conditions. Thus this

nomogram helps the system designer in carrying out the optimal system design.

4. The temperature difference in heat exchangers contributes more than 90% of the

irreversibility, whereas the rest occurs due to pressure drop and heat transfer with

surroundings in the heat exchangers.

5. It is more effective to maintain the secondary fluid inlet temperature as low as

possible to get higher COP and exergetic efficiency within the given range. This

may be attributed to the fact that at lower secondary fluid inlet temperature, the gas

cooler operates closer to the critical point, where heat transfer properties are

superior.

99

Page 122: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

6. The compressor, evaporator, gas cooler and expansion device contribute to system

irreversibility to a larger extent while the internal heat exchanger has negligible

effect. The expansion valve contributes a significant amount of exergy loss here

whereas it is negligible for a conventional system.

7. It is effective, in terms of improvement in COP and exergetic efficiency, to employ

large heat exchanger area by increasing length or by using fins, which will also

involve additional investment and higher pressure drop. Hence, there is an optimal

trade-off between the two.

8. Replacement of expansion valve with a turbine will increase the COP as well as the

exergetic efficiency significantly, but it will also raise issues related to cost, design

and dynamic balancing of the system. It is advisable to employ a turbine for large

systems, such as a large dairy plant or other large system where simultaneous

cooling and heating is useful.

100

Page 123: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 5

EXERGETIC OPTIMIZATION OF HEAT EXCHANGERS

FOR TRANSCRITICAL CO2 HEAT PUMPS

5.1 Introduction

For effective sizing of heat exchangers, detailed knowledge of total irreversibility

is essential. For example, for the same capacity, length can be reduced by decreasing

diameter, so that irreversibility due to material reduces, but the irreversibly due to

pressure drop will increase rapidly. To circumvent this problem, a multi-pass

arrangement can be used with very small tubes (microchannel heat exchanger), but this

will give rise to higher manufacturing irreversibility. So it is a fairly complex task to

choose an effective set of diameter, length and number of passes for heat exchangers.

Irreversibility occurs in fluid flow system through three mechanisms of entropy

generation: molecular thermal dissipation, viscous dissipation and chemical dissipation.

The first mechanism leads to irreversibility due to temperature difference and the second

one leads to irreversibility due to pressure drop, while the third one is not generally

experienced in vapour compression heat pumps due to chemical stability of the

refrigerant. Different approaches such as entropy generation minimization, life cycle

analysis, exergoeconomic or thermoeconomic analysis have been employed in recent

years for optimization of heat exchangers mostly with constant fluid properties. High

pressure, distinct dry out phenomenon and near critical operation in evaporator, and

supercritical operation and abrupt variation of thermophysical and transport properties of

CO2 in gas cooler make this type of analysis very interesting in transcritical CO2 heat

pump systems.

In this chapter, detailed irreversibility analysis of both the evaporator and gas

cooler is presented for a CO2 based heat pump system of 1 ton cooling capacity with

101

Page 124: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

water as the secondary fluid for both heat exchangers. This analysis includes both

operational and material irreversibility. The present study includes the numerical

optimization of multi-pass counter-flow double-tube evaporator and gas cooler. Effect of

three parameters: tube diameter, length and number of passes have been studied in detail.

Results reveal the right combination of optimum diameter and length, which depends on

number of passes, capacity and operating parameters.

5.2 Total irreversibility analysis

The methodology of total irreversibility analysis includes the effect of all phases

of production, use and recycling, on the environment. So the total irreversibility of a heat

exchanger includes:

1. Operational (thermal dissipation, viscous dissipation and cumulative losses in

power and heat generation) irreversibility.

2. Irreversibility associated with use of material.

Now, irreversibility associated with operation of heat exchanger can be written as:

Toper T P

PI k I k I∆= + ∆ (5.1)

where, TI ∆ and PI ∆ indicate the irreversibilities due to thermal and viscous dissipation

respectively. The parameters and Tk Pk depend on the nature of applications of thermal

system, i.e., whether the heat exchanger is used in a power plant, heat pump,

refrigeration, etc. and its working characteristics. The irreversibility associated with use

of material includes total life cycle of material and the effect on environment. However

neglecting recycling and the environmental effect, the irreversibility associated with use

of material can be simply written as:

, , , ,n

1 ( ) ( )man i p o p p i man o man man fab ins insI M M C M M C LC Mt

= + + + + + ∑ C (5.2)

where, the first term denotes irreversibility due to raw material for inner and outer tubes,

the second term denotes that for inner and outer tube manufacturing processes, the third

102

Page 125: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

and fourth terms for heat exchanger fabrication and insulation respectively and ‘t’

indicates the total cycle time. So the total irreversibility is given by,

tot oper manI I I= + (5.3)

For certain applications and working fluids, if we try to reduce the TI ∆ , manI and

PI ∆ will increase. Likewise, with the same diameters, we can reduce TI ∆ by increasing

length, but manI and PI ∆ will increase and hence the total irreversibility will be minimum

for a particular optimum length. Analytical formulation to obtain optimum length based

on minimum total irreversibility is impossible for a real heat exchanger due to

dimensional variation of properties. Bejan [110] has optimized the single tube aspect

ratio based on combined thermal and frictional irreversibility for a balanced heat

exchanger with an ideal fluid and derived the following equation for a simplified case of

constant Stanton number (constant Reynolds number):

( ) 1/ 24

/ opt p

LD G R c f St

τ =

(5.4)

where, . This optimization analysis can be extended by adding (Re,Pr)St f= manI . For a

single tube, equation (5.2) can be rewritten as manI L∝ or = CmanI L for constant

diameter. The total irreversibility can thus be written as:

2 3

0 2

4 2

ptot T P

C D DG f LI k T k CLLSt

τ πρ

= + + (5.5)

Hence optimum heat transfer length can be expressed as:

0

3 2

/ 4

/ 2τ

π ρ=

+

T popt

P

k T C D StL

C k DG f (5.6)

It is clear from equations (5.4) and (5.6) that the optimum length will reduce if the

irreversibility associated with use of material is included.

103

Page 126: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

The following performance evaluation parameters based on second law evaluation

criteria have been used to show the relative influence of thermal and viscous dissipation on heat exchanger irreversibility [111]:

Irreversibility distribution ratio, φ∆

∆=T

PII

and Bejan number, ∆

=TIBe

I (5.7)

Rational (second law) effectiveness = Exergy gained by the cold streamExergy denoted by the warm stream

(5.8)

5.3 Mathematical Modelling and Numerical Simulation

Both the evaporator and the gas cooler have been modelled based on momentum,

energy and exergy balance as discussed in chapter 4 and with the following additional

assumptions as well. Both the heat exchangers are of multi-pass double-pipe counter flow

type, where the refrigerant flows through the inner tube and water flows through the outer

annular space. Mass flow rate in all the passes are equal. Overall system has been

considered similar to the one presented in chapter 4. Only difference is in terms of

configuration of heat exchangers; they are of multi-pass type here instead of a single pass

one. Due to equal flow rate in each pass, each pass has been treated in a manner similar to

that as discussed in chapter 4 and then all the passes are added up to obtain overall

performance. To consider the highly variable heat transfer characteristics (due to sharp

variation of refrigerant properties near pseudo critical region in the gas cooler), each pass

of both the heat exchangers has been discretised (similar to Figure 4.3) and momentum

and energy conservation equations have been applied to each segment.

To find the state points of the transcritical CO2 vapour compression cycle, first a

steady state simulation has been performed. Since the internal heat exchanger is not the

point of interest, a fixed value of 0.6 has been assumed as the effectiveness. For thermo

physical and transport properties of CO2 an exclusive property code ‘CO2PROP’ has

been employed. The simulation code solves the system equations by Newton-Raphson

iterative method integrated with the property code and the heat transfer and pressure drop

calculations. The total heat pump system is simulated for 1 ton of cooling capacity. Then

104

Page 127: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

total irreversibility of evaporator and gas cooler has been evaluated by summing up the

irreversibility in each segment and pass.

Specifications of a Dorin compressor (Model TCS113) have been used in the

simulation and the following correlation have been used for volumetric and isentropic

efficiency respectively, based on regression of experimental data [112]:

2

2 3is,c

1.1636 0.2188 0.0163

= 0.61 0.0356 0.0257 0.0022 v p p

p p

r r

r r

η

η

= − +

+ − + pr (5.9)

The irreversibility due to thermal dissipation in the evaporator is expressed as:

evi0 6 5

evo

TT (s s ) lnT

Tev ref evw pw

passI m m c∆

= − −

)

(5.10)

and the irreversibility due to pressure drop is given by,

( ) (/ /Pev ref evr evr evw evw evw

pass segment segmentI m P m Pρ ρ∆

= ∆ + ∆

∑ ∑ ∑ (5.11)

Similarly, the irreversibility due to thermal dissipation in gas cooler is expressed as:

gcoTgc 0 gcw pw ref 2 3

gci

TT m c ln m (s s )

TpassI ∆

= −

∑ −

)/i

ρ

(5.12)

and the irreversibility due to pressure drop in the gas cooler is given by:

( ) (/Pgc ref gcr gcr gcw gcw gcwi

pass segment segmentI m P m Pρ∆

= ∆ + ∆

∑ ∑ ∑ (5.13)

Total irreversibility has been estimated employing Equations 5.1 – 5.3.

5.4 Heat transfer and pressure drop correlations

5.4.1 Gas cooler (refrigerant side): The heat transfer in gas cooler tubes occurs at

supercritical pressures where the thermo physical properties of carbon dioxide change

drastically. The great variations in the thermo physical properties cause the heat transfer

coefficient to be greatly dependent on both the local temperature and the heat flux. The

variation includes two aspects: changes along and perpendicular to the direction of fluid

105

Page 128: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

flow. Longitudinal discretisation accommodates the former effect. To account for the

variation in the perpendicular direction, Pitla et al. [38] correlation has been used in this

study (Equations 4.12-4.14). Pressure drop has been estimated following Equations 4.15-

4.16.

5.4.2 Evaporator (refrigerant side): High pressure, very low viscosity and surface

tension, and near critical operation make the flow boiling heat transfer and pressure drop

phenomenon of carbon dioxide distinct from conventional refrigerants. Distinct film

breakdown and dry-out phenomena make most of the general correlation unusable. In this

analysis, the recently developed Yoon et al. [52] correlation has been used for boiling

heat transfer coefficient. The following correlation was proposed to predict critical

quality:

( )1.642.12 4.738.27 Re 1000cr lx Bo Bd −= (5.14)

where, Bond number, 2( )l g iBd g d /ρ ρ= − σ , boiling number, / fgBo q Gh= .

Yoon et al. proposed the following correlation for the heat transfer coefficient of CO2:

For region crx x< ; (5.15) ( ) ( )1/ 22 2. .tp nb lh S h E h= +

Nucleate boiling term and parameters S and E are given as:

( ) ( )( ) 0.550.12 0.5 0.671055 / log /nb cr crh P P P P M q

− −= − (5.16)

16 0.69 1.111 1.62 10 RelS E−− = + × ,

0.11

31 9.36 10 Pr 1ll

g

E x ρρ

= + × −

(5.17)

For region crx x≥ ; (2 )

2dry g dry wet

tp

h hh

θ π θπ

+ −= (5.18)

weth is the heat transfer coefficient on the wetted portion of the tube, given by,

wet lh E= h , 0.410.75

0.861 3000 1.121

l

g

xE Box

ρρ

= + + − (5.19)

where, dryθ is angle of dry portion, which is closely related with the flow pattern, given

by:

106

Page 129: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.63.47 4.84 0.27 136.23Re

2dry

tt

Bo BdX

θπ

− =

(5.20)

lh and gh are the heat transfer coefficients corresponding to saturated liquid and vapour,

given by Dittus-Boelter equation.

Pressure drop has been calculated from modified Martinelli correlation 2

2

0

2 1 xfoTP TP

l

f G Lp dx

d xφ

ρ ∆ = ∆ ∫ , (5.21) 0.20.046 Refo lf −=

where, the two-phase multiplier is given by [113]:

(5.22) ( ) ( ) ( ) ( )1 2.87 / 1.68 1 /TP cr crx x P P x x P Pφ = − + + −2 1 0.25 1.642 0.8− −

)

5.4.3 Waterside heat transfer and pressure drop: Waterside heat transfer coefficient

has been evaluated by the conventional Dittus-Boelter equation for annular flow in both

evaporator and gas cooler.

0.80.023Re PrnwNu = (5.23)

where, n = 0.3 for evaporator and n = 0.4 for gas cooler.

For waterside friction factor, Blasius correlation [107] has been used (Equation 4.25).

Water properties are assumed to be temperature dependent only, and polynomial

expressions have been employed to estimate these (Equations 4.26-4.27).

5.5 Results and discussion

For certain capacity and operating conditions, the total irreversibility of the

double pipe counter-flow multi-pass heat exchanger (both evaporator and gas cooler)

depends on the outer and inner tube diameters, length and number of passes, i.e.

( , , ,totI f d D L n= (5.24)

To simplify the analysis, the area ratio between annulus and inner cross section is

assumed to be constant (=2.0). This is a more reasonable assumption than the case of

constant diameter ratio because of the fact that the relative mass velocity and Re will

107

Page 130: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

retain approximately proportional values as individual cross-sectional areas are varied.

This will subsequently result in approximately equal pressure drop ratio (between

refrigerant and secondary fluid) and heat transfer rate as well for certain operating

condition. So, results are presented here for the three independent geometric parameters:

, and . Thickness of all the tubes has been taken as 1 of the outer diameters.

Tube material for both evaporator and gas cooler is stainless steel. The information on the

exergy losses for the material uses is limited. The exergy loss in steel production depends

on the manufacturing processes and is found to vary from 4 to 18 MJ/kg [114,115]. Here,

an average value of 11 MJ/kg has been taken for exergy losses for primary steel. The

exergy losses due to tube manufacturing, fabrication and insulation (density: 30 kg/m

d L n /10th

3)

have been taken as 5.7 MJ/kg, 0.26 MJ per metre length and 71 MJ/kg respectively [114].

The following operating parameters have been assumed for both evaporator and

gas cooler. For evaporator, inlet and outlet temperatures of water are 30 oC and 4 oC

respectively, typically used for dairy application. For gas cooler, inlet temperature and

mass flow rate of water are taken as 30 oC and 2 kg/min respectively, which will yield an

outlet water temperature of about 70-80 oC, typically required in dairy applications. The

heating capacity and the corresponding outlet temperature may vary. The ambient

temperature has been taken as 30 oC. Calculations are based on 1 ton of cooling capacity;

compressor work (exergy input) and heating capacity may vary based on the simulation.

5.5.1 Exergetic optimization of gas cooler

The effect of a tube diameter and length of a 2-pass gas cooler on the total

irreversibility is shown in Figure 5.1. The minimum irreversibility is seen to lie in the

range of 6 mm diameter and 25 m length. Decreasing the diameter beyond about 4 mm

yields a rapid increase in irreversibility due to a rapid increase in pressure drop. This can

be avoided by increasing the number of passes. For a 5-pass unit, the optimum diameter

and length are found to be 4.5 mm and 22 m respectively as shown in Figure 5.2. For

larger diameter and smaller length, the irreversibility due to thermal dissipation is very

high because of lower heat transfer coefficients; increasing the length can reduce this

irreversibility, but that will also give rise to higher manI and PI ∆ . However, the effect of

108

Page 131: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

PI ∆ (< 0.1 %) and manI (< 4 %) at larger diameter is fairly small as shown in Figures 5.3

and 5.4. On the other hand, for a very small diameter, the fluid velocity rises (25 m/s for

d = 2mm and n = 5) leading to high Re (1.6 approx.) and a larger pressure drop as

shown in Figure 5.3, although the heat transfer coefficient will also increase in this case.

510×

Re

PI ∆

manI

For smaller diameter and long heat exchangers, two problems will arise: i) Due to

the increase in heat transfer coefficient the temperature approach becomes zero, which is

practically not feasible and hence there is no further decrease in thermal dissipative

irreversibility, ii) A very rapid increase in pressure drop related irreversibility occurs. If

we recall the pressure drop equation, for certain size and operating condition, G 1n−∼ ,

and thus the pressure drop is given by, 1n−∼ xP n−∆ ∼ . For water, and for

CO

1.75x =

2, . So, the irreversibility due to pressure drop 1.5x > 1P xI n∆ −∼ (according to

Equation 5.13). In the present case, for a 4 mm diameter and 30 m long heat exchanger,

= 21 W with n = 2 and PI ∆ = 10 W with n = 5, so the value of x will be

approximately 1.8. This small deviation is due to the change in other properties. manI will

increase approximate linearly with n. It is very clear from the above discussion that with

increase in n, PI ∆ will decrease and manI increases, so the optimum diameter and length

will both decrease, but it is not an easy task to find the relationship. With increase in

number of passes from 2 to 5, the optimum diameter decreases as a function of n

approximately, although the value 0.4 will reduce with increase in n due to increase in

0.4−

, which will give some rough idea about the minimum number of passes required in a

microchannel heat exchanger to attain minimum irreversibility. For a 5-pass system with

inner diameter of 4.5 mm, the Equation 5.6 predicts the optimum length of about 8 m, for

C = 0 that will be about 13 m. However, for the water side, Equation 5.6 estimates a very

large optimum length (about 40 m) due to negligible pressure drop. Since Equation 5.6 is

based on several assumptions such as balanced heat exchanger, constant properties and

Reynolds number, the deviation in the predicted results from the numerical results is

quite intuitive.

109

Page 132: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 5.1 Total irreversibility (in W) of a 2-pass gas cooler

Figure 5.2 Total irreversibility (in W) of a 5-pass gas cooler

110

Page 133: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 5.3 Irreversibility ratio in a 5-pass gas cooler

Figure 5.4: manI (in W) contours for a 5-pass gas cooler

111

Page 134: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

5.5.2 Exergetic optimization of evaporator

The effects of diameter and length of evaporator with 2 and 5 passes on the total

irreversibility are shown in Figures 5.5 and 5.6, respectively. Unlike the gas cooler, there

does not exist any optimum length for the evaporator, although some optimum diameter

exists having values of 7.5 mm and 6 mm for 2 and 5 passes respectively. Reducing the

diameters (below 4 mm for 2 passes and 3 mm for 5 passes approximately) leads to very

rapid increase in irreversibility due to a fast rise in pressure drop. This can be avoided by

increasing the number of passes. As can be observed in the figure, the portion of the

contour at lower diameter and higher length is incomplete. This can be attributed to the

simulation being not feasible due to temperature approach tending to zero because of

higher pressure drop. So, beyond certain value of length the temperature approach

becomes negative, which is an unacceptably trivial situation as the heat transfer direction

reverses. So, the minimum temperature difference approaches zero before attaining the

optimum length.

Figure 5.5: Total irreversibility (in W) of 2-pass evaporator

112

Page 135: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 5.6: Total irreversibility (in W) of a 5-pass evaporator

Figure 5.7: Irreversibility ratio in a 5-pass evaporator

113

Page 136: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 5.8: manI (in W) contours for a 5-pass evaporator

The effect of PI ∆ (< 0.1 %) and manI (< 4 %) at higher diameter is very small as

shown in Figures 5.7 and 5.8 respectively, but the effect of PI ∆ (> 5 %) is high at smaller

diameter. However, the contribution of pressure drop effect on the total irreversibility of

evaporator is more (about 4 times) than that in case of the gas cooler due to the well-

known dual effect of frictional and momentum pressure drop. For both the evaporator and

gas cooler, the rational efficiencies vary between 75 to 95 % and exhibit opposite trend of

irreversibility.

The heat transfer correlations, used in present study, are based on normal tube

diameters (not microchannel). Studies show that the heat transfer and pressure drop

correlations have to be modified in case of microchannel heat exchangers as the physics

in these is different from microchannel heat exchangers.

114

Page 137: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

5.6 Summary

Exergetic analyses of both evaporator and gas cooler of a CO2 based heat pump

system have been presented in this chapter. Water has been employed as the secondary

fluid in both heat exchangers. Typical operating conditions, required in dairy plants, have

been chosen for the analysis. Results clearly show that higher heat transfer coefficient can

be achieved by decreasing the diameter only to a limited extent due to rapid increase in

pressure drop thereafter. With increase in length, thermal irreversibility decreases but

irreversibilities due to both pressure drop and material become larger. So, for certain

operating conditions and capacity of gas cooler, a set of optimum diameter and length is

possible for each set of passes and the optimum diameter and length will decrease with

increase in number of passes. For the evaporator, although an optimum diameter has been

obtained, optimum length could not be found since as temperature approach becomes

zero before attaining the optimal length. The effect of material use on the irreversibility is

negligible. Although the effect of pressure drop on the irreversibility can be neglected for

higher diameter, it is quite significant for smaller diameter tubes. The effect of pressure

drop depends on the number of passes and mass velocity of the fluid. Irreversibility due

to pressure drop is higher for the evaporator compared to that in the gas cooler.

Outcome of such exergetic optimization exercise is expected to help design the

optimal heat exchanger (in terms of diameter, length and number of passes) for a given

capacity and the operating parameters.

115

Page 138: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 6

TRANSCRITICAL CO2 HEAT PUMP DRYER

6.1 Introduction Drying is an energy intensive process and is very common in many chemical,

food and process industries such as milk powder production, wood processing kilns. In

the conventional dryer, the exhaust air from dryer is vented to atmosphere and the useful

part of its energy is lost resulting in lower performance and lower specific moisture

extraction rate, SMER (about 0.2-0.6 kg/kWh). Using a heat pump dryer (HPD), which is

a combination of heat pump and dryer unit, both the latent heat and sensible heat can be

recovered from exhaust air thus improving the overall thermal performance and yielding

effective control of air condition at the inlet to the dryer. Studies show that SMER of a

heat pump dryer is in the range of 1.0-4.0 kg/kWh. Another advantage of HPD is that it

can yield dry (very low humidity) air of low temperature, which is essential in some

applications, such as drying of medicines. After the first installation of HPDs mainly for

timber drying in 1960s, many synthetic refrigerants such as R114, R22, R134a have been

used in HPDs. However, due to the adverse environmental effect of synthetic

refrigerants, natural refrigerants are being promoted lately. Carbon dioxide (R744) is one

such natural refrigerant, which has high potential for this application because of available

effective heating in the gas cooler due to gliding refrigerant temperature. CO2 also offers

various advantages such as high volumetric capacity, superior environmental properties

and favorable heat transfer properties.

To fully examine the operating characteristics, computer simulation of HPDs has

received attention in recent years. The simulation results explicitly explain the HPD

characteristics with respect to various operating parameters and results also help to

establish a fundamental guideline for the HPD operation. However, experimental

validation of the simulation model is needed to warrant its usefulness.

116

Page 139: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

In the present work, a mathematical model and simulation code has been

developed to investigate the performance of a transcritical CO2 heat pump dryer. The

model takes into account the momentum, heat and mass transfer phenomena taking place

in all components in the system. To take care of the variable heat transfer properties, the

heat exchanger components were divided into several small segments to examine the

state, heat and mass balance and pressure drop for both refrigerant and air, and hence

accurate results are expected from the present study. The simulation model has been first

validated with experimental data available in open literature and then the model is used to

investigate effects of important operating parameters on the system performances such as

heating COP, moisture extraction rate and specific moisture extraction rate. Simulation

results show the effect of key operating parameters such as by-pass air ratio, re-

circulation air ratio, dryer efficiency, ambient condition (temperature and relative

humidity) and air mass flow rate. Anomalies in the behavioral trends of the transcritical

CO2 heat pump are explained through comparison with such data for other refrigerant

based systems reported in the literature.

6.2 Thermodynamic evaluation

6.2.1 Thermodynamic cycle and its modeling

Thermodynamic cycle of air in the closed heat pump dryer is shown in a

psychometric chart (Figure 6.1) exhibiting the following processes: (i) a1-a3: cooling

and dehumidifying in evaporator, (ii) a3-a4: sensible heating in condenser/gas cooler, (iii)

a4-a1: cooling and humidifying in dryer. Cycle diagrams of a heat pump dryer for R22 or

R134a and that for R744 on the T-s plane are shown in Figures 6.2 and 6.3 respectively.

Main difference between R744 cycle and the conventional cycle is the presence of a gas

cooler in place of a condenser where R744 gas is cooled at constant pressure.

The following assumptions have been made for the performance analysis:

1. Compression process is adiabatic but non-isentropic

2. Refrigerant at evaporator outlet is considered as saturated vapor

3. Refrigerant at condenser outlet is considered as saturated liquid

4. Evaporation and heat rejection (condensation/gas cooling) processes are isobaric

117

Page 140: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

5. Heat transfer with the ambient is negligible

6. Air at the evaporator outlet or the gas cooler inlet is considered as saturated

(relative humidity is 100 %)

7. Outlet air condition from the dryer is same as the inlet condition to the evaporator

8. Approach temperature difference (AT) for both the evaporator and the

condenser/gas cooler is taken as 5 oC

Figure 6.1: Thermodynamic cycle of air in closed HPD

From the energy balance in the evaporator, the cooling load for cooling and

dehumidification of air is given by:

( ) ( )( ) ( )1 4 3 1 3 1 31.005 1.88 2500ev r a a a a a aQ m h h m T Tω ω= − = + − + − ω (6.1)

and the heating load in sensible heating of air is given by:

( ) ( )( )2 3 3 4 31.005 1.88gc r a a a aQ m h h m T Tω= − = + − (6.2)

Compressor power is expressed as:

( 2 1 comp gc ev rW Q Q m h h= − = − ) (6.3)

Cooling coefficient of performance is given by:

( ) ( )1 4 2 1c ev compCOP Q W h h h h= = − − (6.4)

118

Page 141: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 6.2: T-s diagram of R22 & R134a heat pump dryer cycle

Figure 6.3: T-s diagram of R744 heat pump dryer cycle

Moisture extraction rate (MER) and specific moisture extraction rate (SMER) are the

important performance measures of heat pump dryer and are given by:

( 1 4a a aMER m ω ω= − ) (6.5)

compSMER MER W= (6.6)

119

Page 142: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

6.2.2 Numerical procedure A computer code was developed based on energy and exergy balance equations

incorporating the developed property codes ‘CO2PROP’ for R744 and REFPROP [104]

for R22 and R134a. Although the AT is attained at point 4 in the evaporator

(T T ), in the condenser the AT may be attained at saturated vapor point (− =3 4a AT 2′ ) or

state 2, so the temperature approach condition for R22/R134a HPD can be

mathematically represented as:

2 32 4 2 3 4 3

2 3min ( ), ( )a a a a

h ht t t t t t ATh h

′′

−− − + − =−

(6.7)

For CO2 systems, the entire temperature range is divided into elemental sub-ranges to

find the minimum temperature difference between refrigerant and air (AT), and the gas

cooler pressure is set as the optimum compressor discharge pressure (Equation 3.30).

With the given input parameters: ta1, 1aω , , , , other state points are

calculated by employing an effective iterative technique incorporating property data and

then performance parameters COP

4at RT am

c, MER, SMER and irreversibilities have been

estimated.

6.2.3 Result and discussion

Results are presented in Table 6.1 for unit mass flow rate of air (1 kg/s) and for

the following input parameters: t = 30 , , inlet moisture content of

evaporator

1aoC 4 80 o

at = C

1aω = 0.02 kg/kg of dry air and reference temperature of 30 oC. Evaporator

outlet saturated air temperatures are 11.5 oC, 13.0 oC and 12.4 oC for R22, R134a and

R744 respectively. Results clearly show that due to the high system pressure the

volumetric capacity of R744 is very large compared to others. Another advantage for

R744 is the smaller pressure ratio compared to others, although the high system pressure

can pose some difficulty in design of components. COP of R744 based heat pump dryer

is 10% higher than that of R134a units, whereas it is 7% lower than that of R22 units. In

terms of moisture extraction rate as well R22 yields the best performance. SMER of

R744 system is 11% higher than that of R134a and 4% lower than that of R22 systems.

120

Page 143: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

For optimum evaporator inlet moisture content of 0.0195 kg/kg, the system is found to

yield a maximum cooling COP. This type of behavior is attributed to the nature of

saturated line in psychometric chart.

Table 6.1 Performance Comparison for R22, R134a and R744 HPD

Refrigerant 1aω 4aω pr COPc Vc 3kJ m

MER kg/min

SMER kg/kWh

R22 0.02 0.0082 4.605 2.170 3090.6 0.708 1.840

R134a 0.02 0.0090 5.838 1.812 1775.6 0.660 1.599

R744 0.02 0.0087 2.523 2.020 23172.2 0.6765 1.7779

Table 6.2 Component irreversibilities

Refrigerant Icomp (%) Iex (%) Iev (%) Ic/gc (%) I∑

R22 10.96 10.45 15.67 10.88 47.96

R134a 12.55 12.47 12.94 13.35 51.06

R744 13.20 15.75 13.15 7.75 49.85

Irreversibility analysis of the components shows that due to the gliding

temperature in the gas cooler, irreversibility of the gas cooler for R744 heat pump dryer is

much smaller than that for R22 and R134a heat pump dryers. Due to the large pressure

drop and near critical operation, irreversibility of expansion device for R744 HPD is

much larger than that for R22 and R134a HPD. In the actual heat exchanger design,

temperature approach for R744 system can be lower compared to R22 and R134a due to

more favourable heat transfer properties [116].

121

Page 144: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 6.4 Schematic diagram of a CO2 based heat pump dryer system

Enthalpy, h

Pres

sure

, P

1

1c

2c

23

4

Figure 6.5 Transcritical CO2 heat pump cycle on P-h plane

122

Page 145: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

0 10 20 30 40 50 60 70 80

Dry bulb temperature (oC)

-0.005

0

0.005

0.01

0.015

0.02

0.025

0.03

0.035

0.04

Hum

idity

ratio

(kg/

kg d

.a.)

6a

1a

23a 4a 5a

s

2a'

Figure 6.6 Air cycle on a psychrometric chart

6.3 Transcritical CO2 heat pump dryer systems

A HPD consists of a heat pump (refrigerant circuit) and a dryer system (air

circuit). The size of heat pump is determined by moisture removal capacity of dryer and

air conditions. Although several configurations of heat pump dryers are typically used, a

simpler and more general configuration has been considered in this study; it consists of

six main components: compressor, evaporator, expansion device, gas cooler (condenser

for conventional refrigerant based system), fan and dryer as shown in Figure 6.4. As this

is a semi-closed system it can be used either as an open system or as a closed system. A

special feature of CO2 refrigerant circuit is single phase cooling of CO2 in gas cooler (2-

3); rest of the processes in the heat pump are similar to other conventional refrigerants as

shown in Figure 6.5. Processes 1-1c and 2c-2 represent pressure drop in inlet and outlet

valves of the compressor respectively. The air cycle on psychometric chart is shown in

Figure 6.6. A part of moist and hot air leaving the dryer (state 6a) is directed to re-

circulate and mix with fresh air. Part of this mixed air (state 1a) passes through (1a-2a)

and the rest bypasses the evaporator. In evaporator, cooling (1a-2a’) and simultaneous

123

Page 146: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

cooling and dehumidification (2a’-2a) takes place. After the evaporator, both air streams

are mixed and the resulting dry and cold air (state 3a) is then heated sensibly in the gas

cooler (3a-4a) and through the fan (4a-5a). Then it passes through the dryer (5a-6a) to dry

the product. The amount of fresh air introduced in the system is equal to the exhaust air

from dryer vented to the atmosphere. Hence by adjusting re-circulation and bypass,

condition of air at inlet to dryer can be controlled.

6.4 Mathematical modelling

A steady state heat pump model can be defined as a series of mathematical

relationships used to obtain operating characteristics for specific operating conditions.

The CO2 based heat pump dryer model includes the model of compressor, evaporator, gas

cooler, expansion device, fan and dryer. For given operating conditions, RAR, BAR and

component specifications, the model can predict the state points and performance of the

heat pump dryer system.

In the present study the following simplifying assumptions are made:

(a) The heat pump is operated at steady state

(b) The heat transfer with ambient for the components, dryer and connecting

tubes is negligible

(c) The ambient conditions remain constant

(d) The temperature and air velocity are uniformly distributed in transverse

direction of flow.

(e) Compression process is adiabatic but non-isentropic

(f) Mixing of air is adiabatic

6.4.1. Compressor model

The refrigerant mass flow rate through the compressor is given by,

ρ η= 1 sNV60r vm (6.8)

Detailed modeling of the compressor is quite complex. The volumetric and isentropic

efficiencies and pressure drop in inlet and outlet valves depend on the compressor design,

inlet conditions, wall temperature, properties of coolant and fluid flow. To avoid the

124

Page 147: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

complexity, the pressure drop in both inlet and outlet are taken as 0.1379 bar [117] and

specifications of a Dorin R744 compressor have been used for simulation and

correlations have been used for volumetric and isentropic efficiency, respectively, based

on regression of manufacturer’s performance data (Equation 5.9).

Compressor work is given by:

( 2 1comp rW m h h= − ) (6.9)

6.4.2. Gas cooler model

Gas cooler model is comparatively simpler due to absence of mass transfer. Gas

cooler considered here is a plate fin and tube cross-flow heat exchanger, consisting of

several rows and passes, It is assumed that both air and refrigerant mass flow is equally

divided in each pass. Considering the large property change of supercritical carbon

dioxide, the gas cooler is divided into number of sections to calculate the heat transfer

rate. Each section has been individually treated as a cross flow finned tube heat

exchanger and log mean temperature difference method is used in each section. The heat

transfer properties of both air and refrigerant are evaluated based on the mean

temperature and the pressure of respective section. The energy balance in each section is

given by (Figure 6.7):

( ) ( ) ( )1( ) i i i iri r r ai pam a aUA LMTD m h h m c T T+ += − = −1 (6.10)

For multi row plate fin and tube (without fouling), the overall heat transfer coefficient is

given by:

ln( / )1 1 12

o i

r i t a s o

d dUA A Lk Aα π α η

= + +∆

(6.11)

where the surface effectiveness is given by,

( )1 1 fs f

o

AA

η η= − − , ( )tanh / 2/ 2

of

o

m dm d

φη

φ= (6.12)

and m and φ are determined following McQuiston et al. [118]. Summing up of heat

transfer in all the sections yields the total heating capacity of gas cooler.

125

Page 148: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 6.7 A computational segment of cross-flow gas cooler

Heat transfer and pressure drop correlations for gas cooler

The heat transfer coefficient on the refrigerant side is calculated using Pitla et al.

[38] correlation based on ‘mean Nusselt number’ and is given in Chapter 4 (Equations

4.12-4.14). Pressure drop has been estimated in the same way as given in Equations 4.15-

4.16 in chapter 4.

The airside forced convection heat transfer coefficient for a finned coil is given by

Rich [119]: 2/3 0.350.195 Pr Rea a pam a aG cα − −= (6.13)

where, Re a rsa

a

G tµ

= , Pr a pama

a

ck

µ=

This correlation is suitable for fin pitch within the range: 118 787fN< < .

Air side pressure drop in each segment is given by:

21

1 12

a oa i i

a c a a

f AP GAρ ρ +

∆ = + −

ρ (6.14)

For the dry region, the friction factor is given by [120]:

126

Page 149: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

0.28

0.270.589 Reoad a

p

AfA

=

, ( )4Re a c dc o

aa

G A L Aµ

= (6.15)

6.4.3. Evaporator model

As the evaporator of a HPD is used for cooling and dehumidifying of air, it plays

a very important role in moisture removing capability of the dryer system. The model of

evaporator is very complex due to simultaneous occurrence of heat and mass transfer.

The evaporator considered in the present study is a plate fin and tube type cross

countercurrent flow heat exchanger. Usually the working fluid, which flows inside the

tube, enters as a two-phase mixture and evaporates and thereafter may get superheated.

Hence in the evaporator model, refrigerant side consists of two regions: two-phase and

superheat, whereas outside the tubes, air is first cooled to dew point temperature and then

dehumidified by removing the moisture (both sensible and latent heat transfers occur

simultaneously). Hence the airside also consists of both dry region and wet region as

shown in Figure 6.8. The boundary of these two regions is set by dew point of the moist

air. To take into account the property variation, the evaporator is analyzed by dividing it

into number of sections and the heat transfer properties in each section are based on mean

temperature, pressure and/or humidity ratio of corresponding section.

Figure 6.8. Different heat transfer zones in the evaporator

127

Page 150: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Dry region: The dry region is treated similar to the gas cooler as only sensible heat

transfer takes place in this region. So heat balance in each computational section is

written as:

( ) ( ) ( ) ( ) ( ) ( )1 1i i i iri r r p r a p ai pam a ai o

m h h UA T T UA T T m c T T+ +− = − = − = − (6.16)

where,

( )ln( / )1 12

o i

r i ti

d dUA A k Lα π

= +∆

, (6.17) ( ) a s ooUA Aα η=

Figure 6.9: A computational segment of the wet region in an evaporator

Wet region: In the wet region, mass transfer and heat transfer take place simultaneously.

Water film thickness on both tube and fin surface are assumed to be equally distributed.

and T are taken as mean surface temperatures of tube and water, respectively. So,

using the energy balance in each section (Figure 6.9), the following equations are

obtained:

pT w

( 1iri r rq m h h+= − )i

)−

(6.18)

( ) ( )1 1,

i i i iai pam a a fg wq m c T T hω ω+ += − + − (6.19)

( ) ( w riq UA T T= (6.20)

128

Page 151: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

( ) ( ) ( )1,

i ia w ai fgo

q UA T T m hω ω += − + − w (6.21)

The overall heat transfer coefficients are determined by:

( )ln( / )1 12

o i

r i t w oi

d d dwUA A k L k Aα π

= + +∆

, ( ) a s ooUA Aα η= (6.22)

Mass balance equation in each section is expressed as:

(ai m s o sm A )ω α η ω ω∆ = − (6.23)

where, sω is the saturated specific humidity of air corresponding to the water surface

temperature (T ). Lewis correlation is given by: w

m a pamcα α= (6.24)

Using the Lewis correlation and replacing the mean value ω , yields:

( ) (1 21 2

i i i )sai pam o

m c UAω ω+ = − −

+ω ω (6.25)

Simultaneously solving of equations (6.18-6.21) and (6.25), the air outlet temperature and

humidity, surface temperature, refrigerant outlet enthalpy and heat transfer rate can be

determined. Water film thickness is taken as uniform and equal to 0.1016 mm [121].

Determination of wet region

To distinguish the dry and wet region the air temperature at which condensation

first occurs should be determined. This occurs when the airside surface temperature

reaches dew point of air. The following correlation is employed:

( )r i d rad d

a s o

A T TT T

α η−

= + (6.26)

For dry region: T or T ; for wet region: Tp T> d ad da T> w T≤ or T Ta ad≤

Heat transfer equation

To estimate single-phase heat transfer for the refrigerant, the gas cooler equations

have been employed once more. The recently developed Yoon et al. [52] correlation has

been used for boiling heat transfer coefficient, as given in chapter 5 (Equations 5.14-

5.20). For airside heat transfer coefficient, same equations have been used as for the gas

cooler.

129

Page 152: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Pressure drop correlation

For refrigerant side, two-phase pressure drop has been calculated from the

modified Martinelli correlation, presented in chapter 5. For single-phase refrigerant side

and airside dry region pressure drop, the gas cooler correlations have been used.

The following correlation [120] for friction factor was employed to estimate the

airside pressure drop in wet region: 0.4

0.04 0.420.318 Refw d

f

sf f

t−

=

a

4

(6.27)

It may be noted that momentum effect reduces the overall pressure drop of air in the

evaporator as the second term of the pressure drop equation (6.14) is negative.

6.4.4. Expansion device model

The expansion process in CO2 heat pump dryer system is crucial as it is required

to control both the amount of superheat at the evaporator outlet and optimum compressor

discharge pressure to get maximum COP. There are various ways to control these as

discussed in chapter 2. In the present model, the expansion process is assumed to be

isenthalpic, i.e.

3h h= (6.28)

The capacity of expansion device is assumed to be large enough so that the refrigerant

mass flow passing through the expansion device is the same as that through the

compressor.

6.4.5. Dryer Model

The dryer heat transfer characteristics depend on type of dryer (batch or

continuous), the flow rate and flow direction of air and product (co-current, counter or

cross flow) and types of products being dried. The dynamic behaviour of drying depends

very much on properties of product. Such multiple dependences make the heat and mass

transfer in dryer complex and difficult to generalize. To avoid the dynamic behaviour of

falling rate drying, the simulation is limited to constant rate drying in this model. The

working air in the constant drying rate period follows the constant wet bulb temperature

130

Page 153: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

in the psychrometric chart. In this model, the dryer is treated as a black box; such an

approach was successfully used previously [117,122], where a contact factor (CF) or

dryer efficiency (DE) is introduced. Using the psychrometric relations, the outlet

condition of air in the dryer can be calculated by DE, which is defined as [117]:

5 6 6 5

5 5

a a a

a s s a

T TDET T

aω ωω ω

− −= =

− − (Figure 6.6) (6.29)

To avoid actual simulation of the dryer the pressure drop in the dryer is evaluated using

the following correlation [100]:

a

am

mP SRρ

∆ = C (6.30)

The system resistance constant (SRC) of the dryer depends on various parameters such as

flow condition and product. In this model SRC is taken as an input parameter.

3.4.6. Fan model

The fan is used in a heat pump dryer system to generate a pressure head sufficient

to maintain flow of air in the system. Neglecting pressure drop in the duct, total air

pressure drop in the heat pump dryer system is given by:

s ev gc dP P P∆ = ∆ + + ∆P (6.31)

The power input to the fan, which can produce pressure rise of sP∆ is given by

1 100aF s

F am

mW Pη ρ

= ∆ × (6.32)

The power input to the fan will get transferred as sensible heat to air and is expressed as:

( 5 4F a pam a aW m c T T= )− (6.33)

6.4.7. Air and CO2 properties

In the present model, only the temperature dependent air properties have been

used. The following polynomial correlations found by regression analysis based on

available data have been used for density, isobaric heat capacity, viscosity and thermal

conductivity of air: 3 6 21.2933 4.44 10 9.7 10 0.085am t tρ ω− −= − × + × + (6.34)

131

Page 154: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

5 7 21.0052 1.65 10 3.45 10 1.88pamc t t ω− −= + × + × + (6.35)

5 217.07 0.054 6.2 10a tµ −= + − × t

8 2t−

(6.36)

50.02418 7.5 10 3.34 10ak t−= + × − × (6.37)

where, temperature t is in oC. For the psychrometric properties of moist air, the

correlations given in ASHRAE Handbook [123] are used in this model. For

thermophysical and transport properties of CO2, the exclusive property subroutine

‘CO2PROP’, the development of which was presented in chapter 3, has been employed

in this model.

6.4.8 Performance criteria of heat pump dryers

Although the performance of a heat pump dryer is characterized by several

criteria, only COP (heating), MER and SMER are considered here and are defined as:

heat delivered in the heat pump gas coolerpower input to compressor

COP = (6.38)

Specific moisture extraction rate (SMER) is given by:

moisture removed from dryer per unit timetotal energy input per unit time comp F

MERSMERW W

= =+

(6.39)

where, W and W are the compressor power and fan power respectively. comp F

( ,a d o d iMER m ω ω= − ), (6.40)

where , am ,d iω and ,d oω are mass flow rate of air through the dryer, inlet and outlet

humidity ratios of air, respectively. The MER is vital for the drying process as it

indirectly indicates the dry product throughput rate. SMER is the most commonly used

performance criteria for heat pump dryers.

6.5 Numerical simulation The numerical simulation consists primarily of two major computational loops:

air circuit is simulated in the outer loop whereas refrigerant circuit is simulated in the

inner loop. To start the simulation of refrigerant circuit, outlet state of evaporator (P1, T1)

and amount of superheat (10oC) have been initially assumed. By initial assumption of

132

Page 155: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

discharge pressure and using compressor specifications, refrigerant mass flow rate,

compressor work and state point 2 (inlet to gas cooler) are calculated from the

compressor model. After that, evaporator outlet condition of air (sate 2a and 3a) and inlet

condition of refrigerant (P4, h4) are determined by the evaporator model, then outlet

condition of refrigerant in gas cooler (P3, h3) and outlet condition of air in gas cooler

(state 4a) are determined by the gas cooler model. In both the gas cooler and evaporator

model, capacity, other state points, pressure drop for both refrigerant and air side are

determined using the heat exchanger configurations, input state points, and mass flow

rate of refrigerant and air. Particular attention is given to each computational section,

where the heat and mass balance, heat transfer and pressure drop correlations are used

and the Newton-Raphson method is used for iteration. Point 1 is iterated using Equation

(6.28) unless enthalpy of state 3 agreed with that of state 4 within a specified tolerance,

iteration was continued. In each iteration step, the discharge pressure of compressor is

updated by the following optimum correlation (Chapter 3):

( ) ( ) 3 22 1 3 1 33.47 0.32 t 2.23 0.0134 t 3.7 10 P t t t t −= + − ∆ + − − ∆ + × 3t (6.41)

In the air circuit simulation, outlet condition of dryer (state 6a) was assumed to be the

same as ambient condition. Using RAR, state 1a is determined, then by refrigerant circuit

simulation, state 4a and heat pump performance is determined. Then by fan model, state

5a is obtained and by dryer model state 6a is determined. Unless the new condition of

state 6a agreed with the initially assumed state 6a within a specified tolerance, iteration

(fixed iteration) was continued using new values until convergence was obtained. The

flow chart of this simulation procedure is shown in Figure 6.10. Input parameters in the

simulation model are as follows:

1. Ambient condition ( t , RH) amb

2. Re-circulation air ratio (RAR)

3. Bypass air ratio in the evaporator (BAR)

4. Air mass flow rate ( ) am

5. Amount of superheat at evaporator outlet ( t∆ ).

6. Compressor specifications

7. Evaporator and gas cooler geometries

133

Page 156: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

8. Contact factor or dryer efficiency

Figure 6.10: Flowchart of the entire air and refrigerant loop simulation

6.6 Model validation with experimental data

The present simulation model has been validated by experimental data on a CO2

heat pump assisted laundry dryer presented by Klocker et al. [100]. In absence of some

134

Page 157: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

required information reported, a few approximations have been made while using the

available data. Heat exchanger specifications are as follows. Gas cooler: inner and outer

diameters of the refrigerant tube are 8 mm and 9.6 mm respectively, aluminum fin of 0.3

mm thickness, tube spacing is 22 mm 25.4 mm× and total air side surface area is 118 m2;

evaporator: same as gas cooler except that total air side surface area is 30.1 m2. Tube

array, pitch and length are not given; however, through visual inspection of the gas cooler

presented, an array of tubes have been taken and length and pitch have been

adjusted in a way that the air side heat transfer occurs over a surface area of 118 m

8 2× 02.

Similarly, for evaporator, 30.1 m2 has been attained by taking an array of 6 tubes.

However, the tube arrangement is found to have little influence compared to other

parameters. Because of the reported transient characteristics, system behavior at 50 min is

considered for validation of steady state. The compressor inlet and outlet pressures are 46

bar and 80 bar, respectively. Basic strategy of this validation exercise is that first input

parameters of the simulation model are calculated from state points given in the results

using energy balance for both refrigerant and air, and then validate the numerical results

obtained from simulation. Due to lack of information on compressor characteristics,

refrigerant mass flow rate is taken as input parameter. For a given heating capacity of 12

kW, mass flow rate is estimated as 0.0665 kg/s. Kiln mass transfer coefficient is given as

0.75, which is higher than DE. DE and air mass flow rate are obtained graphically

through the psychrometric chart using available temperature data (Figure 6.11). Point 4

on the saturated line represents the minimum refrigerant temperature in the evaporator

and 4-KM is the tangent of saturated curve at that point. Correlations of saturated curve

and the tangent of the curve are given by [124]:

10×

20.0038 0.0002 0.000018 s stω = + + st (6.42)

0.0002 0.000036 ss

s

d tdtω

= + (6.43)

Value of /s sdt dω at point 4 (11 oC) is 1677. Air temperature at cooler inlet (16 oC) lies

on the tangent and 3a to 5a (52 oC) is the constant humidity line. So, specific humidity in

gas cooler is 0.01113 kg/kg d.a. Energy balance on air in the gas cooler yields an air mass

135

Page 158: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

flow rate of 0.334 kg/s. By taking the constant wet bulb line for dryer, the dryer

efficiency (DE) is given by:

5

5

KM aKM

s a

DE ω ωφω ω

−= −

(6.44)

A kiln mass transfer effectiveness ( KMφ ) of 0.75 yields a dryer efficiency of

0.619. Specific humidity of point 6a (36.13 oC) is 0.01777 kg/kg d.a. Evaporator capacity

and degree of superheat are 10.2 kW and 12oC, respectively.

At first, gas cooler and evaporator models have been tested separately. For the

same configuration, mass flow rates and inlet conditions in the gas cooler, the outlet

temperatures for both refrigerant and air deviate within 0.5% and the heating capacity

differs by about 4% between the model prediction and measured data. So the heat transfer

correlations for both CO2 and air agree quite closely with the experiment. However, in

case of evaporator model, deviations are larger (temperatures deviate by 2% and cooling

capacity is predicted 20% higher by the model). This may be attributed to the fact that the

correlations used typically overpredict the heat transfer coefficient of refrigerant.

Mismatch of heat exchanger configuration may be another reason. The overall system

simulation (BAR and RAR are 100%) shows a deviation of temperature within 1 %, of

capacities within 15 % and of SMER within 20% (Table 6.3). Although use of a suitable

multiplier for the evaporation heat transfer coefficient (about 0.85) can minimize the

deviation, such a measure is avoided in the forgoing analysis, since deviation is not

extremely high.

Table 6.3 Comparison of numerical results with experimental data

Results Experi-

mental

Numerical Results Experi-

mental

Numerical

Cooling load, kW 10.15 11.56 COP 6.5 7.1

Heating load, kW 12 k 13.45 MER, kgw/hr 5 6.02

Work, kW 1.85 1.89 SMER, kgw/kWh 2.05 2.45

136

Page 159: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

5

10

15

20

25

30

35

40

45

50

55

0 0.01 0.02 0.03 0.04Specific humidity (kg/kg d.a.)

Dry

bul

b te

mpe

ratu

re (o C

)

Saturation line

Constant wet bulb line

s

5a

6a

KM

3a

4

1677dtdω

=

3a

Figure 6.11: Air cycle with the results obtained by Klocker et al. [100]

6.7 Simulation results The quantity of air exhausted from the system is assumed to be equal to that of the

fresh air introduced to the system. The gas cooler model shows that tubes smaller than

9.6 mm diameter yield significant improvement in heat transfer with a marginal increase

in pressure drop. Based on the availability of compressor, tube and fin specifications, the

following technical data have been used for heat pump dryer components. For the chosen

compressor (Dorin model TCS113), swept volume is 12.9 cm3 and nominal speed is 2900

rpm. Both gas cooler and evaporator are plate-fin coils with 0.3 mm thick aluminum fin.

For gas cooler, inner and outer diameters of stainless steel (SS) tube are 4.75 and 6.35

mm, respectively with an array of 7 20× and having a pitch of 600 fins/m. For the

evaporator, a 6 1 array of SS tubes is chosen having inner and outer diameters of 7.5

and 9.5 mm, respectively. Tubes are in in-line arrangement with longitudinal and

transverse spacing of 22 and 25.4 mm respectively for both the heat exchangers. The

airside heat transfer surface areas for gas cooler and evaporator are 93 m

2 and 31 m2,

respectively.

137

Page 160: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

It is assumed that water vapor condenses without freezing. The fan efficiency is

taken as 35%. The variation band of the following operating parameters is as follows:

RAR from 0 (open system) to 1 (closed system), BAR from 0 to 0.5, dryer efficiency

(DE) from 50% to 90%, ambient temperature from 20oC to 40oC, ambient relative

humidity from 30% to 70% and air mass flow rate from 0.2 to 0.5 kg/s. Unless otherwise

specified, the mean values of these parameters are: RAR of 0.5, BAR of 0.2, DE of 70%,

ambient temperature of 30oC, relative humidity of 50% and air mass flow rate of 0.25

kg/s. To generate plots, one of these parameters is varied within the specified range stated

above while the others are kept constant at the mean value.

6.7.1. Effect of bypass air ratio (BAR)

The effect of evaporator by-pass air ratio on the heat pump performance, MER

and SMER is shown in Figure 6.12. It is obvious that the cooling load on the evaporator

decreases and the heating load follows suit whereas the ratio of heating load to cooling

load increases with BAR. Due to bypassing of air, cooling and dehumidification rate of

evaporator will improve because of decrease in evaporation temperature and increase in

humidity ratio at the inlet to the evaporator; however, the temperature rise between

evaporator and gas cooler increases, and hence the compressor work increases due to the

increase in pressure ratio. Consequently the COP decreases (with increase of BAR by

0.5, 18% drop in COP occurs) with increase in BAR. However, on the other hand, the

influence of BAR on MER and SMER is not very significant. The increase in

dehumidification rate and decrease in COP points to the existence of an optimum BAR.

Although the MER increases continuously with BAR, the SMER attains a maximum

value, which depends on refrigerant properties and other operating parameters. With

increase in BAR by 0.5, MER increases by only 3.5%, and the maximum value of SMER

at BAR of 0.3 is only 4% more than that at BAR of 0. Prasertsen et al. [125] reported

similar effect of BAR (less than 2%) but did not get the optimal BAR for R134, whereas

Jia et al. [126] showed significant effect (20%) and dependency of optimum BAR on air

mass flow rate. These trends clearly indicate that bypassing of air is not a very effective

mode of system control.

138

Page 161: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3.5

4.5

5.5

6.5

7.5

8.5

0 0.1 0.2 0.3 0.4 0.5

By-pass air ratio (BAR)

Hea

ting

CO

P, M

ER (k

g/hr

)

2.92

2.94

2.96

2.98

3

3.02

SMER

(kg/

kWh)

Heating COPMERSMER

Figure 6.12 Effect of BAR on system performance

4

5

6

7

8

9

10

50 60 70 80 90

Dryer efficiency, DE (%)

Hea

ting

CO

P, M

ER (k

g/hr

)

2

2.4

2.8

3.2

3.6

4

SMER

(kg/

kWh)

COPMERSMER

Figure 6.13 Effect of dryer efficiency on COP, MER and SMER

139

Page 162: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

-10

-5

0

5

10

15

20

25

0 0.2 0.4 0.6 0.8 1

Re-circulation air ratio

Rel

ativ

e va

riatio

n (%

)

heating COPMERSMER

Figure 6.14 Effect of re-circulation air ratio on COP, MER and SMER;

At RAR = 0, heating COP = 4.3, MER = 7.558 kg/h, SMER = 2.905 kg/kWh

6.7.2. Effect of dryer efficiency (DE)

The influence of dryer efficiency (ranging from 50% to 90%) on heat pump COP,

MER and SMER is depicted in Figure 6.13 for an air mass flow rate of 0.25 kg/s. The

dryer efficiency represents the ratio of actual moisture extraction from the product to

maximum possible moisture extraction when drying takes place up to the saturation

condition. In the open system (RAR = 0), the heat pump COP is independent of DE and

the inlet condition of dryer is invariant with DE; hence MER and SMER are linear

functions of moisture extraction and vary linearly with dryer efficiency, whereas heating

COP is held constant. On the other hand, for RAR > 0 (Figure 6.13), the heat pump

performance is influenced by DE, although the effect is marginal. This influence is

dependent on the RAR and the relative condition of air at dryer exit and ambient. In this

simulation, the ambient condition is fixed. So, with increase in dryer efficiency, the

evaporator temperature should drop due to the decrease in air temperature at inlet to the

evaporator. Conversely, condensation in the evaporator increases due to increase in

140

Page 163: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

humidity ratio at evaporator inlet, and hence the evaporator temperature tends to increase.

Due to these two contrasting effects, the evaporator temperature barely decreases (1% as

DE rises from 50% to 90%). Due to the decrease in air temperature at evaporator outlet,

the optimum gas cooler pressure and temperature decrease with increase in DE. So, both

lower side and higher side temperatures decrease, whereas the difference decreases

slightly. It is observed that the heating COP increases by only 6.5% when DE varies from

50% to 90% and the optimum compressor discharge pressure drops from 82 bar to 75.5

bar. There is little change in air condition at inlet to the dryer, whereas the MER and

SMER increase by 80% and 75%, respectively, as DE varies from 50% to 90% and the

variation is nearly linear.

50

54

58

62

66

70

0 0.2 0.4 0.6 0.8 1Re-circulation air ratio

tem

pera

ture

(o C)

5

6

7

8

9

10

Rel

ativ

e hu

mid

ity (%

)

TemperatureRH

Figure 6.15 Effect of RAR on air conditions at dryer inlet

6.7.3. Effect of re-circulation air ratio (RAR)

Figure 6.14 shows the relative variation of heating COP, MER and SMER with

re-circulation air ratio compared to those for open system (RAR = 0). With increase in

RAR, less warm air is vented to the atmosphere and hence more energy gets accumulated

within the system, which increases the operating temperatures of both refrigerant and air.

Hence the inlet air to the dryer becomes warmer. As RAR rises from 0 to 1, air

141

Page 164: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

temperature at inlet to dryer rises from 54 to 69oC whereas relative humidity increases

from 6.5 to 8.5% as shown in Figure 5.15. This will increase the MER and SMER, but it

also increases the temperature difference between evaporator and the gas cooler as well

as the individual temperatures of both and hence COP of the heat pump will reduce.

Because the optimum discharge pressure is more dependent on the refrigerant outlet

temperature in gas cooler than evaporation temperature, the optimum compressor

discharge pressure increases sharply with RAR. As shown in Figure 6.14, with increase

in RAR from 0 (open system) to 1 (closed system), heating COP decreases by 10%,

whereas the MER and SMER increase by 20% and 12%, respectively. The optimum

discharge pressure is found to increase by 50%. Due to the increase in compressor work,

the increase of SMER is much less than MER. The results yield an optimum value of

RAR for maximum MER as well as maximum SMER similar to that for refrigerant R22

[125]. However, in actual systems many other operating parameters influence this

optimal behavior of RAR.

2.7

2.8

2.9

3

3.1

3.2

3.3

20 25 30 35 40

Ambient temperature (oC)

SMER

(kg/

kWh)

7

8

9

10

11

MER

(kg/

h)

SMERMER

Figure 6.16 Effect of ambient temperature on MER and SMER

142

Page 165: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Although the closed system (RAR = 1) is better in terms of MER and SMER, it is

required to ventilate some warm and moist air to the atmosphere (partially open: RAR <

1) to maintain the maximum refrigerant temperature and pressure within limit and also to

control the air condition at inlet to the dryer. In the end, the choice of open or closed

system is dependent on the user requirement and many operating parameters such as

ambient condition, dryer type and dryer efficiency as both the dryer exit and ambient

conditions affect the humidity of the air entering the evaporator. Clements et al. [127]

suggested that a heat pump dryer for the constant rate drying should be designed to

operate in two modes depending on the seasons (temperature). In winter, the dryer should

operate as a closed system and in summer the open system was suggested. Although in

summer, if relative humidity of ambient air is very high, then the open system may not be

desirable as it will increase the system load pulling the heat pump performance down.

6.7.4. Effect of ambient temperature The performance based on the SMER and MER, for an ambient temperature

variation of 20-40oC for a relative humidity of 50%, is illustrated in Figure 6.16. With

increase in ambient temperature, inlet air temperature for the evaporator increases and

hence the working fluid temperature at all the points increases, which gives warm air at

inlet to the dryer. On the other hand, the specific humidity also increases with the

ambient temperature. With increase in ambient temperature from 20 to 40oC, the air inlet

temperature to the dryer increases from 55 to 73oC (about 33%) as shown in Figure 6.17,

whereas the inlet relative humidity to the dryer increases slightly. As a result, both MER

and SMER increase. With increase in ambient temperature from 20 to 40oC, MER

increases by 40% and the SMER increases by 18%. The effect of ambient temperature on

optimum gas cooler pressure is predominant because of significant increase in air inlet

temperature to the gas cooler. As both the evaporator temperature and the gas cooler

temperature increase proportionately, the temperature difference remains approximately

the same and hence the compressor work remains same. So the MER and SMER show

similar trends. On the other hand, due to the deterioration of heat transfer properties of

CO2 in the gas cooler, heating output decreases and hence the heating COP decreases. At

ambient temperature lower than 25oC, the optimum gas cooler pressure falls below the

143

Page 166: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

critical pressure. Hence a constant gas cooler pressure of 74 bar has been considered in

the simulation, as a result COP is nearly the same for this region as shown in Figure 6.17.

Although Prasertsan et al. [125] showed that MER and SMER are not strong functions of

ambient temperature; the result obtained here shows that the ambient temperature

strongly influences both the CO2 heat pump and dryer performance.

3.8

3.9

4

4.1

4.2

4.3

4.4

20 25 30 35 40

Ambient temperature (oC)

heat

ing

CO

P

50

55

60

65

70

75

Dry

er in

let t

empe

ratu

re (o C

)

Heating COPDryer inlet temperature

Figure 6.17 Effect of ambient temperature on dryer inlet temperature and COP

6.7.5. Effect of ambient relative humidity The dryer performance, MER and SMER are not strong functions of ambient

relative humidity. In general, the MER and SMER are expected to decrease as ambient

relative humidity increases in the open system. But in the closed system, evaporator inlet

temperature increases due to the increase in dryer outlet temperature and hence the

operating temperature of both CO2 and air increase. The air inlet temperature to dryer

increases by 17% as ambient relative humidity increases from 30 to 70%. As a result, the

MER and SMER increase slightly. With increase in ambient relative humidity from 30 to

70 %, MER and SMER increase by 9% and 2% respectively (Figure 6.18). Because of

the increase in temperature difference between evaporator and gas cooler, the compressor

144

Page 167: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

work increases and on the other hand both cooling and heating outputs increase and

hence COP decreases slightly. As shown in Figure 6.19, with increase of ambient relative

humidity from 30 to 70 %, the heating COP decreases by 2.5%.

3

3.05

3.1

3.15

3.2

30 40 50 60 70

Ambient relative humidity (%)

SMER

(kg/

kWh)

7.5

8

8.5

9

9.5

MER

(kg/

h)

SMERMER

Figure 6.18 Effect of ambient relative humidity on MER and SMER

4.24

4.26

4.28

4.3

4.32

4.34

4.36

4.38

30 40 50 60 70Ambient relative humidity (%)

heat

ing

CO

P

54

56

58

60

62

64

66

68D

ryer

inle

t tem

pera

ture

(o C)

Heating COP

Dryer inlet temperature

Figure 6.19 Effect of ambient relative humidity on dryer inlet temperature and COP

145

Page 168: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

2.7

2.8

2.9

3

3.1

3.2

3.3

0.2 0.25 0.3 0.35 0.4 0.45 0.5

Air mass flow rate (kg/s)

SMER

(kg/

kWh)

3.3

3.5

3.7

3.9

4.1

4.3

4.5

4.7

4.9

heat

ing

CO

P

SMERCOP

Figure 6.20 Effect of air mass flow rate on SMER and COP

6.7.6. Effect of air mass flow rate

An increase in total mass flow rate of air causes the temperature difference

between the evaporator and the gas cooler to reduce, thus improving the heating COP and

SMER. On the other hand, the temperature at all points decreases and the refrigerant

mass flow rate increases due to increase in load. Influence of other parameters on

pressure drop is marginal (refrigerant side pressure drop in gas cooler and evaporator are

marginal at 0.5% and 2.5%, respectively) whereas mass flow rate influences pressure

drop significantly. Pressure drop for both CO2 and air increases with mass flow rate,

which in turn increases the compressor pressure ratio and hence the compressor work.

These two opposing effects combine to yield an optimum mass flow rate for maximum

COP and SMER, not necessarily at the same value. Although other operating parameters

have little influence on fan power (within 2–3% of compressor power), effect of mass

flow rate is quite significant. With an increase in air mass flow rate from 0.2 to 0.5 kg/s,

the fan power increases by 400% (4-5% of compressor power). Consequently, fan power

becomes significant at higher mass flow rates (8% of compressor power at 0.5 kg/s). This

causes the maximum SMER to occur earlier than maximum COP. As shown in Figure

146

Page 169: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

6.20, the maximum SMER occurs well before a mass flow rate of 0.5 kg/s, whereas the

maximum COP occurs beyond that, although this optimization is not very definite as fan

power is a small fraction of compressor power.

The simulation results reported here show that the effect of ambient conditions

(mainly temperature) and dryer efficiency are significant on the performance of the CO2

heat pump dryer. Degree of RAR (open, RAR = 0; close, RAR = 1; or partially close, 0 <

RAR < 1) can be decided based on the ambient conditions and dryer efficiency to obtain

optimum performance. Control of RAR is fairly vital for some applications, where the air

temperature at inlet to the dryer has to be controlled.

6.8 Conclusions

The thermodynamic comparison of R744 with two other conventional refrigerants

R22 and R134a for heat pump drying in terms of both 1st and 2nd laws showed that R744

yields better performance than R134a whereas its performance is poorer when compared

to R22. Irreversibility of expansion device for R744 is higher whereas that of gas cooler

is smaller as compared to R22 and R134a systems.

A mathematical model and simulation code of a CO2 heat pump dryer has been

developed. Particular attention has been given to developing a detailed evaporator model.

Highly variable heat transfer properties of CO2 were also carefully considered. The heat

exchanger components were divided into several small segments in which the state, heat

and mass balance and pressure drop for both refrigerant and air were calculated. By this

approach, accurate results are expected. The numerical model has been first validated

with experimental data available in the literature and then used to investigate effect of

different operating parameters on important performance parameters such as COP, MER

and SMER of dryer system.

Individual validation of evaporator and gas cooler models shows that the gas

cooler model accurately predicts the performance whereas the evaporator model

overpredicts the performance. The assumption of an adiabatic model for the compressor

and negligible heat interaction with the ambient could be the other reasons behind the

slight overprediction of overall system performance. The present simulation model is

147

Page 170: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

suitable for a continuous dryer where the dryer efficiency is constant and the operation is

fixed for a particular ambient condition. Results show that unlike BAR and ambient

relative humidity, the effects of DE, RAR, ambient temperature and air mass flow rate

are significant on system behavior. The performance of the dryer system increases

linearly with increase in DE. Although the SMER increases with ambient temperature,

COP deteriorates, whereas both decrease with ambient relative humidity. Both BAR and

RAR yield some optimum values for maximum SMER, but the COP decreases in both

cases. An optimization of air mass flow rate is possible to maximize both COP and

SMER although optimum values for maximum COP and SMER are not necessarily

identical.

148

Page 171: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 7

EXPERIMENTAL STUDY OF A CO2 HEAT PUMP

7.1 Introduction

This chapter is devoted to the experimental study of a CO2 heat pump system for

simultaneous water heating and cooling. An experimental facility was developed in the

Refrigeration Laboratory of the Department of Mechanical Engineering, IIT Kharagpur

and tested for different operating conditions. Several heat transfer and pressure drop

correlations, cited in the literature to be used for carbon dioxide based system and its

components, have been validated by the test results. Finally, the numerical model that

was developed for the CO2 heat pump having simultaneous water heating and cooling in

counter-flow tube-in-tube heat exchangers has been validated by the test data.

7.2 Component design and description

The transcritical CO2 heat pump system for simultaneous water cooling and

heating have been designed based on the numerical simulation presented in chapter 4.

The schematic diagram of designed CO2 heat pump system along with location of various

sensors is shown in Figure 7.1. The system was designed for an expected cooling

capacity of 1 ton ( 3.56 kW). Both evaporator and gas cooler are counter-flow tube-in-

tube heat exchangers. Since the numerical simulation showed that the optimum gas

cooler to evaporator heat transfer area ratio was above 1.5, the dimensions of heat

exchangers have been chosen to match heat transfer area ratio of approximately 1.5.

Stainless steel was chosen as the material for all system components to sustain the high

pressure. Due to the very high-pressure existing in the system and other special

characteristics of the working fluid and operating conditions, all system components were

designed carefully for smooth operation. Design details of all components are given

below:

149

Page 172: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 7.1: A fully instrumented CO2 heat pump test facility for simultaneous water

cooling and heating

7.2.1 Compressor

Table 7.1 CO2 compressor specifications

Model TCS 113

Bore/ stroke 22 mm/ 17 mm

Displacement 2.2 m3/h

Input voltage 3-phase, 380-420 V @ 50 Hz

Max Pressure 150 bar

Oil Dorin CL80

Capacity 2.5 kW @ 2900 rpm

A Dorin CO2 compressor (model TCS113) was chosen for the experimental

investigation. The compressor is a single stage two-cylinder model. The detailed

specifications for TCS113 are given in Table 7.1. The motor is provided with Thermik

150

Page 173: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

thermal protection. The inlet port of compressor was designed for a minimum suction

pressure of 10 bar. The compressor contains a safety valve for a maximum pressure 168

bar. Expected compression ratio was 2 to 4 and the mass flow rate range for the CO2 was

0.025-0.45 kg/s.

7.2.2 Expansion device

Numerical results in chapter 4 showed that the optimum discharge pressure varies

between 100 to 116 bar for the given range of water inlet and outlet temperatures. Hence

a maximum limit of 120 bar was considered to select the expansion device, although the

minimum discharge pressure was considered as 80 bar. Since it is recommended by the

compressor manufacturer to ensure a minimum evaporation temperature of –10 oC

(saturation pressure is about 26.3 bar), the minimum suction pressure limit was taken as

26 bar whereas 50 bar was set as the maximum limit. Hence the minimum and maximum

expansion ratios for the expansion valve should be 80/50 and 120/26 bar respectively. A

Swagelok integral bonnet needle valve (model SS-1RS4), shown in figure 7.2, was

chosen for this application. Detailed specifications are: stainless steel body, regulating

stem, 1/4" inch Swagelok tube fitting for both inlet and outlet, 0.37 Cv (flow coefficient),

pressure rating of 345 bar at 38 oC and temperature range of –54 oC to 232 oC.

Figure 7.2 Swagelok Integral Bonnet Needle Valve (Courtesy: Swagelok)

151

Page 174: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

7.2.3 Evaporator

Heat transfer and pressure drop analysis of the evaporator showed that a decrease

in tube diameter could improve the heat transfer although at the cost of pressure drop

increasing at a very faster rate (as discussed in chapter 5). For the present system design

condition, 3/8 inch (9.5 mm) OD tube will give rise to considerable pressure drop

(expected pressure drop will be up to 2.5 bar), whereas a lower standard diameter 1/4

inch (6.35 mm) OD will lead to very high pressure drop. Hence, 3/8 inch OD was chosen

for the evaporator. The tube thickness was taken as 1 mm (yielding an ID of 7.5 mm),

which is sufficient to sustain the expected refrigerant pressure. For water side (annulus),

standard stainless tube of 5/8 inch (16 mm approximately) OD with 1 mm thickness

(hence ID = 14 mm) was taken, although that was slightly higher than the design value.

Design mass flow rate of water was 1.2-3.2 L/min. The cross-sectional ratio of water to

refrigerant was 1.88. Total design length for the evaporator tubes was taken as 7.2 m.

Figure 7.3 shows a layout of the tube-in-tube counter-flow evaporator, which was

designed and developed for the test facility. Refrigerant flows through inner tube whereas

the water flows through the annulus. For the sake of simplicity of fabrication, only one

row was considered. The evaporator contains 9 parallel segments, each having 0.8 m

length (total 7.2 m), where the refrigerant tubes are connected by 180o circular bends

having the same diameter and the water tubes are connected by 90o straight tube of ½

inch OD. Sufficient gap between the two parallel segments was maintained in fabrication

for proper insulation and handling. The fabrication of the evaporator was done by brass

and silver brazing within the laboratory. Special care was taken during fabrication to

maintain uniform gap between the two tubes to obtain uniform peripheral heat transfer.

After the fabrication, the evaporator was tested up to a pressure of 75 bar for leak

detection and pressure sustainability. The fabricated evaporator has an effective length

0.825 m (total length is 7.4 m considering the 9 segments). The evaporator was properly

insulated using glassfibre insulation to reduce the heat transfer with the ambient.

Thermocouples were connected to each segment for detailed study of heat transfer

through the evaporator.

152

Page 175: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 7.3: Design layout of evaporator

7.2.4 Gas cooler

Due to single-phase flow in the gas cooler, pressure drop is very low compared to

that of evaporator for the same conditions and the same diameter (as discussed in chapter

5). For 1/4 inch OD, the maximum pressure drop is around 1 bar accompanied by

excellent heat transfer rate as is evident from the simulation. Hence for the present

system design condition, 1/4 inch (6.35 mm) OD was chosen for the gas cooler. The tube

thickness was taken as 0.8 mm (leading to 4.75 mm ID), which is sufficient to withstand

the expected refrigerant pressure in the gas cooler. For the water side (tube annulus),

standard stainless tube of 12 mm OD with 1 mm thickness (10 mm ID) was taken. Mass

flow rate of water was in the range of 1.2-3.2 L/min for design conditions. The cross-

sectional area ratio of water to refrigerant was 2.64. Total designed heat transfer length

for the gas cooler was taken as 14 m. Figure 7.4 shows the layout of tube-in-tube counter-

flow gas cooler, which was designed for the experiment. Refrigerant flows through inner

tube whereas the water flows through the annulus. For the sake of simplicity of

fabrication, only two rows were considered. Gas cooler contains 14 parallel segments in

153

Page 176: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

two rows, each 1 m long, where the refrigerant tubes are connected by 180o circular

bends having the same diameter and the water tubes are connected by 90o straight tubes

of 9.5 mm OD. Sufficient gap between the two parallel segments was maintained in

fabrication for proper insulation and handling. The gas cooler fabrication closely

followed that of the evaporator and similar practices were implemented in both the

fabrication processes. After the fabrication, the gas cooler was tested up to a pressure of

120 bar for leak detection and pressure sustainability. The fabricated gas cooler, as shown

in Figure 7.5, has an effective total heat transfer length of about 13.6 m. The gas cooler

was properly insulated by glassfibre insulation to reduce the heat transfer with the

ambient. The thermocouples were connected to each segment for detailed study of heat

transfer through the gas cooler.

Figure 7.4: Design layout gas cooler

7.2.5 Separator

The separator was designed for a total refrigerant capacity of 8 L. Figure 7.6

shows the separator, which was fabricated by rolling of stainless steel sheet metal

followed by tungsten inert gas welding. Mean diameter and height of separator are 175

mm and 350 mm, respectively. A wall thickness of 6 mm was taken for both side-wall

154

Page 177: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

and upper and lower plates. Sufficient insulation was added to reduce the heat transfer

with the ambient. The separator has two ports; the inlet port is at the lower end and the

outlet port is at the upper end. Due to atomization of liquid refrigerant, it is possible that

carry-over of some liquid occurs which along with the vapor goes to the compressor. To

prevent this, two parallel horizontal thin plates covering 2/3 area, were installed inside

the cylinder for separation of the liquid fraction.

Figure 7.5 Insulated gas cooler

Figure 7.6: (a) receiver, (b) separator

155

Page 178: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

7.2.6 Receiver

It was expected that the receiver would contain mostly liquid (high density).

Hence, it was designed for a total refrigerant capacity of 2 L (lower than that of

separator). Figure 7.6 shows the receiver, which was fabricated similar to the separator.

Inner diameter and height of receiver are 90 mm and 300 mm, respectively. A thickness

of 6 mm was taken for both side-wall and upper and lower plates. Receiver was properly

insulated as well. Among the two ports, inlet port is at the higher side and the outlet port

is at the lower side. A pressure gauge was fitted on the upper side.

7.2.7 Condensing unit

As the maximum design heating capacity was estimated to be 6 kW, the

condensing unit was designed for this load. The hot water from the gas cooler was re-

circulated through the air-cooled condensing coil of 6 kW capacity to cool down to its

initial temperature at the inlet to the gas cooler. To control the water outlet temperature

from coil (or cooling effect), a variable speed fan was used with the coil. An insulated

tank with storage capacity of 25 L was used after the coil. A centrifugal pump was used

to supply the water to gas cooler. The pumping power was calculated by estimating the

total pressure drop in the water circuit including all bends, reducers and expanders. The

condensing unit contains flow control valve to control the mass flow rate and the flow

meter to measure the water flow rate.

7.2.8 Water re-circulation loop in evaporator

An arrangement similar to the gas cooler was incorporated with the evaporator to

supply water at constant temperature and flow rate. Water re-circulation loop for

evaporator contains heater, insulated tank, centrifugal pump, flow control valve and mass

flow meter. Heating arrangement comprises number of immersion heaters of total

capacity 3.5 kW. By on-off control of each heater, the input heater load (equal to cooling

load of CO2 heat pump) was controlled. The pumping power was calculated following

the procedure of the condensing unit. By attenuating the heater and the valve, inlet

temperature and flow rate to the evaporator was controlled.

156

Page 179: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

7.2.9 Tubing and fittings

All the connections for the refrigerant circuit was made by SS-316 tube of 1/4

inch OD (6.35 mm) of thickness 0.8 mm (ID = 4.75 mm). Tubing was designed for

maximum pressure of 150 bar. Total tube length was estimated as 8 m. All the tube

connections were made by SS-316 ferrule adaptors. All the tubes were insulated by

asbestos rope covered by foam.

Figure 7.7 Prototype of transcritical CO2 heat pump

7.3 Test facility and test procedure

Figure 7.7 shows a photograph of the test facility for the prototype of a transcritical

CO2 heat pump for simultaneous water heating and cooling with accessories and

instrumentation. Saturated or superheated vapour from separator (item 11) is compressed

to high pressure through compressor (item 4) and the compressed hot CO2 gas is cooled

as it flows through gas cooler (item 6). Then the cooled CO2 fluid is expanded to

evaporation pressure through expansion device (item 9) and the resulting two-phase CO2

passes through evaporator (item 10) to give the cooling effect. Two-phase, saturated

vapour or superheated vapour of CO2 exit from the evaporator and it enters the separator.

A receiver (item 7) is used between gas cooler and expansion device to store the CO2

157

Page 180: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

liquid or control the pressures. A Coriolis mass flow meter (item 3) is installed between

the separator and the compressor to measure the mass flow rate and temperature of CO2

vapour entering the compressor. Two Swagelok safety valves (item 2) are used in both

low and high pressure sides to control the higher limit of pressure. Four pressure gauges

(item 5) have been used in different locations. One differential pressure gauge (item 8)

has been used to measure the refrigerant side pressure drop in the gas cooler. CO2

cylinder (item 1) is used for external charging of CO2. A W-bend is provided before

compressor to provide superheating of CO2 vapour, if required. A temperature-controlled

bath is used in which W-bend is immersed. Although this was never used, because the

outlet of evaporator was already sufficiently superheated at operating conditions.

However, this provision for heating the refrigerant could be requisitioned during cooler

water inlet ambient temperatures in winter. A separate air-cooled condensing unit has

been used to supply water at required temperature and flow rate to the gas cooler. For

water inlet to evaporator at required flow rate and temperature, a separate heating unit

was used (not shown in figure). Thermocouples were fitted in different sections to

measure various temperatures; the sensors are subsequently connected to the data

acquisition system (DAS), which is interfaced with a computer as shown in figure 7.8.

Before test run, the system was purged by nitrogen gas and then evacuated by a

vacuum pump. Then CO2 gas was charged from the cylinder. Before setting, all the

measuring devices were calibrated properly (Appendix A). Reading of differential

pressure gauge and mass flow meters are set to zero. Then external heating and

condensing unit are started and set to certain inlet temperature and mass flow rate of

water. After recording initial reading and starting the data scan of the DAS, the

compressor was switched on. To measure the power input to the compressor, a 3-phase

energy meter was employed. Controlling the discharge pressure at a required level is

important for a transcritical CO2 system as it needs to operate at optimum discharge

pressure. This was achieved by simultaneous control of the total mass of the system and

degree of opening of the expansion device. The operating parameters were varied

following a test matrix as listed in Table 7.2.

158

Page 181: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Figure 7.8: Experimental setup with full instrumentation

Table 7.2: Test matrix

Parameters Ranges Parameters Ranges

Psuc 26-45 bar Tcwi 30-40 oC

Pdis 75-110 bar mew 1.0-2.5 kg/min

Tewi 25-35 oC mcw 0.7-1.5 kg/min

7.4 Data reduction Before evaluation of performance, all the readings (temperature, pressure and mass

flow rate) have been modified according to the calibrations. Temperatures have been

measured at the outer surface of tube wall. To find the bulk temperature of fluid, first heat

loss has to be determined.

Heat loss per unit length is given by (Figure 7.9):

159

Page 182: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

RTT

q ambml

−= where,

ofas

o

fDkDD

kdD

R2

121 12

)/ln(2

)/ln(πππ

++= (7.1)

D2

D1

di do

ql Foam

Asb-estosTube

wall

TmTb

Tamb

Figure 7.9: Calculation of heat loss from connecting tube

fo is outer surface heat transfer coefficient due to combined convection and radiation.

Value of fo has been taken as 25 W/m2K. Thermal conductivities of asbestos and foam

have been taken as 0.154 and 0.03 W/mK, respectively.

Now, the bulk temperature of fluid can be found by,

++=

iit

iolmb dk

ddqTT

αππ1

2)/ln(

(7.2)

iα has been found by Dittus-Bolter equation for water and Gnielinski correlation for

single phase refrigerant. For T ambm T< (evaporator side), heat transfer is from ambient

and same procedure has been used; with opposite sign. iα for two-phase refrigerant has

been found by Yoon et al. correlation.

Volumetric efficiency of compressor has been determined by,

NVm

s

rv

1ρη = , where, ( 111 ,TPf= )ρ (7.3)

Isentropic efficiency is determined following,

160

Page 183: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

12

12

hhhh s

is −−

=η where, , ( )111 ,TPfh = ( )222 ,TPfh = and ( )2112 ,, PTPfh s = (7.4)

Indicated power input to the compressor is given by,

( 12, hhmW rcompi −= ) (7.5)

Combined motor and mechanical efficiency of compressor is estimated from:

, / (measured by energy meter)m i comp compW Wη = (7.6)

Evaporating capacity and actual cooling effect of water are given by,

( ),evr r evr o evr iQ m h h= − , and ( ), ,evw evw pw evw i evw oQ m c T T= − (7.7)

Heat rejection of refrigerant and heat gain by water are given by,

( ), ,gcr r gcr i gcr oh h= −Q m and ( ), ,gcw gcw pw gcw o gcw iQ m c T T= − (7.8)

Cycle COP and actual COP are given by, respectively,

( )sys evr gcr icompCOP Q Q W= + & ( ) compgcwevwact WQQCOP += (7.9)

To find the heat transfer coefficient, gas cooler and evaporator was divided into 14

sections (1 m each) and 9 sections (0.85 m each), respectively. By measuring heat

transfer between COrq 2 refrigerant and water, and log mean temperature difference

(LMTD), UA can be calculated as: LMTDqrUA = (Note: , also heat gain/rejection by

CO

rq

2 = heat rejection/gain by water + heat gain/loss with ambient in one segment). Now

for segment of length , L∆

owt

io

ir ALkdd

AUA απα1

2)/ln(11

+∆

+= (7.10)

Hence, the heat transfer coefficient of CO2 is found by,

11

2)/ln(1

+∆

−=owt

io

rir ALk

ddq

LMTDA απ

α (7.11)

161

Page 184: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Water side heat transfer coefficient ( wα ) was estimated through Gnielinski correlation

[30].

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

75 80 85 90 95

Discharge pressure (bar)

Coo

ling

CO

P

test 1test 2

Figure 7.10 Repeatability analysis for Pev = 35 bar

0.8

1

1.2

1.4

1.6

1.8

2

72 82 92 102 112Discharge pressure (bar)

Coo

ling

CO

P

test 1test 2

Figure 7.11 Repeatability and uncertainty data for Pev = 40 bar

162

Page 185: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

15

25

35

45

55

65

75

85

0 2 4 6 8 10 12 14 16

Time (min)

Pre

ssur

e (b

ar)

20

40

60

80

100

120

Tem

pera

ture

(o C)Suction pressure

Discharge pressureDischarge temperature

,evw ot,gcw ot

Figure 7.12 Transient behaviors at the starting of system

7.5 Results and discussion

Repeatability tests were conducted for two sets of operating parameters: Psuc = 35

bar, tevw,i = 29 oC and tgcw,i = 33 oC, and Psuc = 40 bar, tevw,i = 29 oC and tgcw,i = 34 oC by

varying Pdis as shown in Figures 7.10 and 7.11 respectively. Most of the data points for

cooling COPs are within the uncertainty ranges ( ) in both cases. Due to lack of

precise control and measurement errors, few points lie beyond the uncertainty bar, but not

far apart. We conclude that the tests repeat reasonably well within the range of

uncertainty of the test loop measurements.

%6±

Figure 7.12 shows the transient behavior of suction and discharge pressures, and

discharge and gas cooler outlet refrigerant temperatures during start-up of the system.

Initial temperature, pressure and charge were 51 bar, 30 oC and 1.28 kg, respectively. The

inlet temperatures of water were maintained at 31 oC and 32 oC for evaporator and gas

cooler respectively. It can be observed that the system takes about 15 minutes to reach the

steady state.

163

Page 186: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

30

40

50

60

70

80

90

10 190 370 550 730

Expansion valve opening (degree)

Pres

sure

(bar

)

0.7

0.8

0.9

1

1.1

1.2

1.3

1.4

1.5

CO

2 mas

s flo

w ra

te (k

g/m

in)

Suction pressureDischarge pressureMass flow rate

Figure 7.13 Suction and discharge pressure and mass flow rate with varying

expansion valve opening

1.2

1.6

2

2.4

2.8

3.2

75 80 85 90 95Discharge pressure (bar)

Qev

w,Q

gcw (k

W)

CoolingHeating

Figure 7.14 Variation of cooling and heating output with discharge pressure for suction

pressure of 35 bar

164

Page 187: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

1

1.4

1.8

2.2

2.6

3

3.4

3.8

72 82 92 102 112Discharge pressure (bar)

Qev

w, Q

gcw

(kW

)

CoolingHeating

Figure 7.15 Variation of cooling and heating output with discharge pressure for suction

pressure of 40 bar

Variation of suction and discharge pressures, and refrigerant mass flow rate for

various valve openings (degree of opening measured from completely closed condition)

of the needle valve are shown in Figure 7.13. For this study, test was started by initial

opening of 720o and different angles of opening were maintained by gradual closing of

valve, measurements were recorded at steady-state for each position. When the valve is

gradually closed, pressure difference rises rapidly due to instant accumulation of mass in

gas cooler and reduction of mass in the evaporator, and then reduces gradually to steady

state. Valve opening exhibits a very significant effect near the full valve closing condition

as shown in figure.

Cooling and heating outputs of the system are plotted with discharge pressure in

Figures 7.14 and 7.15 for suction pressure of 35 and 40 bar, respectively. Both cooling

and heating outputs increase with discharge pressure due to increase in mass flow rate of

refrigerant. As the water mass flow rate in gas cooler and evaporator are kept constant at

1 kg/min and 1.5 kg/min, respectively, water outlet temperature increases in gas cooler

while it decreases in the evaporator with increase in discharge pressure due to increase in

both cooling and heating capacities.

165

Page 188: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

40

42

44

46

48

50

2 2.2 2.4 2.6 2.8Pressure ratio

Isen

tropi

c ef

ficie

ncy

(%)

Pev = 35 barPev = 40 bar

Figure 7.16 Variation of compressor isentropic efficiency with pressure ratio

The trend of how compressor isentropic efficiency varies with pressure ratio is

shown in Figure 7.16 for suction pressure of 35 bar and 40 bar as the degree of superheat

varies between 15 to 22 oC. Although the compressor performance is mostly dependent

on pressure ratio, other operating parameters also have minor effect for the same

compressor. Above a pressure ratio of 2.2, the trend matches with Dorin data [ref. 112],

although values are about 20% lower.

The fact that effect of water mass flow rate does not influence the system

performance strongly is evident in both evaporator and gas cooler. With increase in water

mass flow rate in gas cooler, heating output increases due to increase in water side heat

transfer coefficient, although the effect on system COP or cooling output are not so

significant as shown in Figure 7.17, at evaporator side water mass flow rate of 1.5

kg/min, and suction and discharge pressures of 40 and 90 bar respectively. For a similar

reason, cooling output increases with increase in water mass flow rate in the evaporator,

however system COP and heating output vary marginally as shown in Figure 7.18, at a

gas cooler side water mass flow rate of 1 kg/min.

166

Page 189: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

3.8

3.9

4

4.1

4.2

4.3

0.7 0.9 1.1 1.3 1.5

Water flow rate in gas cooler (kg/min)

Syst

em C

OP

1.5

2

2.5

3

3.5

4

Out

puts

(kW

)

System COPCooling outputHeating output

Figure 7.17 Variation of system performance with water flow rate in gas cooler

4.05

4.1

4.15

4.2

4.25

4.3

4.35

4.4

0.9 1.2 1.5 1.8 2.1 2.4 2.7

Water flow rate in evaporator (kg/min)

CO

Psys

0.5

1

1.5

2

2.5

3

3.5

4

Out

puts

(kW

)

System COPCooling outputHeating output

Figure 7.18: Variation of system performance with water flow rate in evaporator

Conversely, the effect of water temperature at inlet to gas cooler on the system

performance is fairly significant. Figure 7.19 exhibits the experimental data for a suction

pressure of 40 bar and a discharge pressure of 90 bar, mass flow rates of water in gas

167

Page 190: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

cooler and evaporator of 1 kg/min and 1.5 kg/min respectively, and water inlet

temperature to evaporator of 31 oC. With almost 10 oC increase in water inlet temperature

the system COP decreases by about 13% due to deterioration of heat transfer properties

of CO2 as discussed in chapter 4.

4.1

4.2

4.3

4.4

4.5

4.6

4.7

4.8

30 32 34 36 38 40

tgcw,i (oC)

Sys

tem

CO

P

, 31 oevw it C=

Figure 7.19: Variation of cooling COP with water inlet temperature in gas cooler

Effects of some important operating parameters on the system performance have

been discussed above. Maximum cooling and heating output from the system have been

recorded as 3 kW and 5 kW respectively. Maximum heat gain or loss from evaporator

and gas cooler were 20% and 30%, respectively. It can be noted that calculated system

COP is less than the ratio of (heating output + cooling output) and (heating output –

cooling output) due to heat gain or loss. Maximum volumetric and isentropic efficiencies

of compressor have been recorded as 60% and 50% respectively.

168

Page 191: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

7.6 Validation of heat transfer and pressure drop correlations

The heat transfer coefficient and pressure drop correlations have been validated for

refrigerant mass flow rate of 0.3-1.5 kg/min both for evaporator and gas cooler. The great

variation in thermo-physical properties (specially in the pseudo-critical region) cause the

heat transfer coefficient of carbon dioxide to be greatly dependent on both the local

temperature and the heat flux in gas cooler tubes. The recently developed Pitla et al.

correlations for CO2 cooling are based on a limited set of diameters and flow rates (about

3 to 4 sets). Hence, the correlations are required to be validated for other dimensions and

flow rates as we need a more general expression for the design of an entire heat

exchanger. Figure 7.20 shows the comparison of measured and predicted data of heat

transfer coefficient from Pitla correlation [38] with bulk temperature of CO2 in the gas

cooler for a mass flow rate of 0.91 kg/min and discharge pressure of 100 bar. The heat

transfer coefficient changes sharply near the critical temperature due to a large variation

in thermo-physical properties and shows the peak value at near pseudo-critical

temperature. The Pitla correlation for gas cooler heat transfer coefficient showed a close

match with the test results (within 5% difference) as is evident in Figure 7.20. The

comparison between the values of heat transfer coefficient of CO2 at different discharge

pressure show that at pressures near the critical point the variation in heat transfer

coefficient is greater than at higher pressures. Hence peak in the value of heat transfer

coefficient is more pronounced at pressures near the critical point, which is due to the fact

that the variation in thermo-physical properties and specific heat in particular is more

pronounced at pressures near the critical point. The peak value of heat transfer coefficient

is shifted towards higher temperature with increase in pressure. Figure 7.21 shows the

measured and predicted trend of pressure drop using correlation used for simulation in

previous chapters for different pressure and mass flow rates of CO2. Pressure drop due to

tube bending has also been considered for estimating the predicted data. Comparison

shows that the measured values are higher (up to 55% deviation) than predicted values.

One reason may be due to tube roughness, which was neglected for pressure drop

estimation for the predicted data.

169

Page 192: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

22.5

33.5

44.5

55.5

66.5

7

42 51 60 69 78 87 96 105

Bulk temperature (oC)

Hea

t tra

nsfe

r coe

ffici

ent (

kW/m

2 K)

Pitla et al.correlationExperimental

Figure 7.20 Heat transfer coefficient of CO2 in gas cooler

0.2

0.4

0.6

0.8

1

1.2

1.4

0.2 0.4 0.6 0.8 1 1.2 1.4Predicted pressure drop (bar)

Mea

sure

d pr

essu

re d

rop

(bar

)

(82,

(90,

(115, 0.83) (105,

(100, 0.91)

(Pressure in bar, mass flow rate in kg/min)

Figure 7.21 Predicted versus measured pressure drop of CO2 in gas cooler

For the evaporator, two different correlations were compared against the test data,

which were used in the analyses presented in previous chapters and varying degrees of

match were attained. The Yoon et al. [52] correlation showed very good comparison

with the test data following the trend throughout the range of tests carried out with a

maximum difference of 50% between them; however, the modified Wattlet correlation

170

Page 193: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

[18] exhibited a distinctly opposite trend against the test data towards higher vapour

quality with increasing difference from the measured data, although it matches very well

up to a vapour quality of 0.75 compared to Yoon et al. correlation as shown in Figure

7.22. Comparison of pressure drop data in evaporator predicted from correlation with

measured data showed that the used correlation underpredicted the measured data by a

maximum of 45%. This may be attributed to similar reasons as was cited for the gas

cooler. We may conclude that our test data has performed reasonably well against some

of the published correlations.

0

5

10

15

20

25

30

0.4 0.5 0.6 0.7 0.8 0.9 1

Vapour quality

Boi

ling

heat

tran

sfer

coe

ffici

ent (

kW/m

2 K)

Modified WatteletcorrelationYoon et al.correlationExperimental

Figure 7.22: Boiling heat transfer coefficient of CO2 versus vapour quality

7.7 Validation of system simulation The numerical simulation model of transcritical CO2 heat pump for simultaneous

water cooling and heating presented in chapter 4 has been validated by test data obtained

from experiments on the prototype. The experimental results clearly showed that

superheating takes place in the evaporator. Hence the model has been modified

accordingly: superheating zone has been added in evaporator model, internal heat

exchanger model has been eliminated and water mass flow rates are set as input

parameter instead of water outlet temperatures in both evaporator and gas cooler

171

Page 194: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

accordingly. One such comparison for water mass flow rates of 1.5 kg/min and 1 kg/min,

and water inlet temperatures of 30 oC and 30.5 oC in evaporator and gas cooler,

respectively and evaporator pressure of 40 bar is shown in Figure 7.23. Comparison

between the test results and the model prediction shows a modest agreement with a

maximum deviation of 20% and the trends are fairly similar. Comparison for other

operating parameters also shows fairly similar deviation between the test results and the

model prediction.

2.9

3.1

3.3

3.5

3.7

3.9

4.1

4.3

4.5

70 80 90 100 110

Discharge pressure (bar)

Sys

tem

CO

P

Experimentalnumerical

Figure 7.23 Validation of numerical results against experimental data

7.8 Summary This chapter described the experimental testing of a prototype CO2 heat pump

system for simultaneous water heating and cooling, and presented the experimental

results. An experimental facility was developed and detailed tests were carried out to

study the performance of system and components at different operating conditions.

Validation of heat transfer and pressure drop correlations for both gas cooler and

evaporator, and validation of system simulation model are also presented. The system has

been designed for a cooling capacity of 1 ton (3.56 kW). Due to the presence of very

high-pressure in the system and some of the special characteristics, special attention was

given in designing all the components. The gas cooler pressure was attenuated by

172

Page 195: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

simultaneously controlling the total mass of the system and degree of opening of

expansion device.

The system performance for various operating parameters was studied closely.

Uncertainty analyses show fairly acceptable results. Lack of precise control and presence

of measurement errors cause a few data points to lie beyond the uncertainty bar.

Transient study shows that the system takes about 15 minutes to attain steady state. Study

on the system behaviour with different expansion valve opening shows that the valve

opening has significant effect near the full valve closing condition. Performance study

with different compressor discharge pressures shows that both the cooling and heating

outputs increase with discharge pressure due to increase in mass flow rate of refrigerant.

Water outlet temperature increases in gas cooler whereas, it decreases in evaporator with

increase in discharge pressure. Effect of water mass flow rates is not so significant for

both evaporator and gas cooler, whereas the effect of water inlet temperature to gas

cooler on the system performance is significant. Maximum cooling and heating output

from the system have been recorded as 3 kW and 5 kW respectively. Maximum

percentage heat gain/loss in evaporator and gas cooler were 20% and 30% respectively.

Maximum volumetric and isentropic efficiencies of compressor have been recorded as

60% and 50% respectively. The Pitla correlation for gas cooler heat transfer coefficient

showed a reasonably close match with the test results (within 5% error), whereas the

validation of pressure correlation shows that the measured values are significantly higher

(up to 55% deviation) than the model predicted values. For the evaporator, the Yoon et al.

correlation showed good comparison with the test data following the trend throughout the

range of tests carried out with a maximum difference of 50% between them; however, the

modified Wattlet correlation exhibited a distinctly opposite trend against the test data

toward higher vapour quality with increasing difference in coefficient prediction from the

measured data. However, at lower vapour quality, the Wattlet correlation predicted the

test results even better than the Yoon et al. correlation. Comparison of pressure drop data

in the evaporator predicted from correlation with measured data showed that the

correlations underpredicted the measured data by a maximum of 45%. This is attributed

to pipe roughness which is not included in the estimation calculation. Comparison

173

Page 196: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

between the test results and the simulation model prediction shows reasonably good

agreement and the trends are fairly similar.

174

Page 197: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Chapter 8

CONCLUSIONS AND RECOMMENDATION FOR FUTURE

WORK

8.1 Conclusions

Detailed theoretical analyses on a transcritical CO2 vapour compression heat

pump system and system components for simultaneous cooling and heating applications

have been presented. Subsequently, a fully instrumented test loop was designed and

developed for testing the performance of the prototype CO2 heat pump. Experimental

studies on the transcritical CO2 heat pump for simultaneous water cooling and heating

have been carried out to monitor the system performance and validation of system

simulation model, heat transfer and pressure drop correlations used in the theoretical

analysis. Based on the theoretical and experimental studies, major conclusions are

summarized below.

Due to the near critical operation, CO2 exhibits some distinct properties (mostly

favorable to system design) compared to other conventional refrigerants. The effects of

evaporator temperature and gas cooler outlet temperature are more predominant

compared to internal heat exchanger effectiveness at optimized conditions for the cycle.

However, the effect of internal heat exchanger effectiveness is more significant at higher

gas cooler exit temperature and lower evaporator temperature. Analyses for the optimum

condition indicate that a system meant for low or moderate temperature heating is more

economical not only due to high system COP but also due to lower optimum discharge

pressure (low operating pressure ratio) as well. Expressions for optimum cycle

parameters have been developed and these correlations offer useful guidelines for optimal

system design and for selecting appropriate operating conditions. Multi-staging is found

to have more significant effect compared to the use of internal heat exchanger, expansion

turbine and ejector-expander device on the optimum condition.

175

Page 198: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

The simulation of CO2 heat pump for simultaneous water cooling and heating

applications shows that the optimum gas cooler to evaporator heat transfer area ratio

ranges between 1.7 and 1.9 for maximum system COP as well as maximum exergetic

efficiency at optimum discharge pressure, although optimum value for the latter is

slightly more. Favourable heat transfer properties of carbon dioxide in both two-phase

and supercritical region and an efficient compression process contribute significantly

toward high system COPs and exergetic efficiency values. A nomogram, applicable for

optimum design, with compressor speed and water inlet temperature as independent

parameters and optimum discharge pressure, optimum area ratio and maximum COP as

output parameters has been presented. This is expected to be of simple help to designers

of such systems. The temperature difference in heat exchangers is found to contribute

more irreversibility than pressure drop in the heat exchangers. The compressor,

evaporator, gas cooler and expansion device contribute to system irreversibility to a

larger extent, while the internal heat exchanger has negligible effect. The expansion valve

contributes a significant amount of exergy loss in case of CO2 systems whereas it is

negligible for a conventional system. Replacement of the expansion valve by an

expansion turbine will increase the COP as well as the exergetic efficiency significantly,

but it will also raise counter-issues related to cost, design and dynamic balancing of the

system.

Exergetic analysis of the gas cooler in a CO2 heat pump shows that for given

operating conditions and capacity, a set of optimum diameter and length is possible for

certain set of tube passes to get minimum total irreversibility associated with thermal,

pressure drop and material. The optimum diameter and length will decrease with increase

in number of passes. For the evaporator, although an optimum diameter has been

obtained, optimum length could not be found as the temperature approach becomes zero

before attaining the optimal length. The effect of material use on the irreversibility is

found to be negligible. Although the effect of pressure drop on the irreversibility can be

neglected for higher diameter, it is quite significant for smaller diameter tubes.

Irreversibility due to pressure drop is higher for the evaporator compared to that in the

gas cooler. Such exergetic optimization exercise is expected to help design the optimal

176

Page 199: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

heat exchanger (in terms of diameter, length and number of passes) for a given capacity

and the operating parameters.

The thermodynamic comparison showed that R744 yields better performance than

R134a whereas it performs poorly compared to R22 for a heat pump drying applications.

Experimental validation of CO2 heat pump dryer simulation model, to investigate effect

of different operating parameters on important performance parameters such as COP,

MER and SMER of dryer system, shows that the gas cooler model accurately predicts the

performance whereas the evaporator model overpredicts the performance. The

assumption of an adiabatic model for the compressor and negligible heat interaction with

the ambient could be the reasons behind the slight overprediction of overall system

performance. Simulation results show that unlike bypass air ratio and ambient relative

humidity, the effects of dryer efficiency, recirculation air ratio, ambient temperature and

air mass flow rate are significant on system behavior. The performance of the dryer

system increases linearly with increase in dryer efficiency. Although the SMER

increases with ambient temperature, COP deteriorates, whereas both decrease with

ambient relative humidity. Both bypass air ratio and recirculation air ratio yield some

optimum values for maximum SMER, but the COP decreases in both cases. An

optimization of air mass flow rate is possible to maximize both COP and SMER although

optimum values for maximum COP and SMER are not necessarily identical.

Experimental studies show that the gas cooler pressure can be successfully

controlled by simultaneously controlling the total mass of the system and degree of

opening of expansion device. Repeatability and uncertainty analyses have been presented

and they exhibit reasonably acceptable trends. Transient study shows that the system

takes about 15 minutes to attain steady state. Study on the system behavior with different

degree of expansion valve opening shows that it has very significant effect near the fully

closed condition. Performance study with different compressor discharge pressures shows

that both cooling and heating outputs increase with discharge pressure due to increase in

mass flow rate of refrigerant. Effect of water mass flow rates is not so significant for both

evaporator and gas cooler, whereas the effect of water inlet temperature to gas cooler on

the system performance is significant. Maximum cooling and heating output from the

177

Page 200: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

system have been recorded as 3 kW and 5 kW respectively. Maximum volumetric and

isentropic efficiencies of compressor have been recorded as 60% and 50%, respectively.

Validation of Pitla correlation for gas cooler heat transfer coefficient showed a

close agreement with the test results whereas the pressure drop correlation significantly

underpredicts the measured values. For evaporator, the Yoon et al. correlation showed

very good comparison with the test data following the trend throughout the range of

vapour quality while the Wattlet correlation exhibited close validation at low quality.

Pressure drop data in evaporator predicted from correlation are significantly lower than

measured data. Comparison between the test results and the simulation model prediction

shows reasonable agreement and the trends are fairly similar.

8.2 Recommendation for future work

Several unique applications along with various advantages of CO2 based systems

motivated the large volume of research work and industrial innovation reported in the

literature recently. Several studies related to cycle analyses, system component design

and applications can be recommended. Detailed multistage cycle analysis to optimize the

gas cooler pressure and intermediate pressures can be done from both first law and

second law points of view. Theoretical and experimental investigation of capillary tube

(both adiabatic and non-adiabatic) including suction line heat exchanger option can be of

interest. The life cycle analysis or economic analysis can be recommended for future

work, which will be required before commercialization of the products. Also

investigations on heating or cooling systems with various mixtures of CO2 can be done

with a view to reduce the system pressure and take advantage of superior heat transfer

properties of CO2. Although various theoretical and experimental investigations on

supercritical heat transfer and pressure drop, boiling heat transfer and pressure drop, two-

phase flow have been done, pseudocritical region of gas cooling is still one of the

interesting areas, where one can rigorously study heat transfer and fluid flow. Relatively

low isentropic efficiency of developed CO2 compressors show that still there is a need to

improve the design to get higher performance. Research on compressor is required not

178

Page 201: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

only for improvement of performance, but also to reduce the weight and cost.

Transcritical CO2 heat pump has great potential in process heat industries. Prototype

developments and experiment CO2 heat pump for dairy and drying applications in food

industry are some of the very promising applications that can be pursued.

179

Page 202: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Appendix A

Measuring Instrument Calibration

The measuring instruments used for the experiments are listed below:

(i) Dial pressure gauge

(ii) Differential pressure gauge

(iii) Mass flow meter

(iv) 3-phase energy meter

(v) Thermocouples (T-type: 30 numbers, K-type: 15 numbers)

For high side pressure measurement, pressure gauges made by Swagelok, have

been used, whose range is 0-160 bar with an accuracy of ± 1.5% of full scale reading;

i.e. a maximum error of 2.4 bar can occur. For low pressures, locally procured pressure

gauges were used, with a range of 0-70 bar with much less accuracy. A Coriolis mass

flow meter (Rheonik brand of Rockwin Flowmeter) was installed for refrigerant mass

flow measurement with a range of 0.2–10 kg/min with fairly high accuracy (0.2% of

span) i.e. a maximum error of 0.02 kg/min can occur. For water side mass flow meters,

due to budgetary restrictions inexpensive models were used having lower accuracy. For

all pressure gauges, mass flow meters and energy meter, calibration charts supplied by

manufactures have been used.

For calibration of thermocouple a temperature controlled thermostatic bath was

used. The correction factors have been evaluated for different temperatures between 0 to

100 oC and plotted as shown in Figures A1 and A2 for two types of thermocouples used

in experiment. Calibration chart shows that the variation of correction factor is not linear.

Temperatures can be evaluated by using calibration chart or correlation of correction

factor fitted by calibration data. It may be noted that temperatures above 100 oC have

been evaluated by extrapolating the curve. The corrected temperature is evaluated by:

corrected temperature measured temperature correction factor= +

180

Page 203: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

-2

-1.6

-1.2

-0.8

-0.4

0

0.4

0.8

1.2

1.6

2

0 10 20 30 40 50 60 70 80 90 100

Temperatre (oC)

Cor

rect

ion

fact

or (o C

)

Figure A1. Calibration chart for K-type thermocouple

-4

-3

-2

-1

0

1

2

3

4

5

6

0 10 20 30 40 50 60 70 80 90 100

Temperatre (oC)

Cor

rect

ion

fact

or (o C

)

Figure A2. Calibration chart for T-type thermocouple

181

Page 204: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

Appendix B

Uncertainty Analysis Functional form of the various performance parameters are given by

( )1 1, , v rf m P Tη =

( )1 2 1 2, , , is f P P T Tη =

( ), ,, , evw evw evw i evw oQ f m T T=

( ), ,, , gcw gcw gcw o gcw iQ f m T T=

( )1 1 2 2, , , , , .................sys rCOP f m P T P T=

and the heat transfer coefficient is given by,

( )1 1, , , , , , , i i i ir r w r r w wf m m T T T T d Dα + +=

where are the inlet and outlet temperatures or both water and

refrigerant in measured section.

1, , , i i i ir r w wT T T T+ 1+

Uncertainty analyses have been performed using the square root formula [128].

i.e. if , then ( )1 2 31 2 3, , ,..................n n ny f x x x=

22 2

31 21 2 3

1 2 3

...............xx xy n n ny x x x

∆∆ ∆∆= + + +

The multiplying factors (ni) have been taken as 1 for all measuring parameter except for diameter that is 2.

182

Page 205: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

REFERENCES

1. Lorentzen G, Pettersen J. A new, efficient and environmentally benign system for

car air conditioning, Int J Refrigeration, 1993; 16(1); 4-12.

2. Lorentzen G. Revival of Carbon dioxide as a refrigerant, Int J Refrigeration, 1994;

17(5); 292-300.

3. Lorentzen G. The use of natural Refrigerant: a complete solution to the CFC/HCFC

predicament, Int J Refrigeration 1995; 18(3); 190-197.

4. William S, Bodinus PE. The rise and fall of carbon dioxide systems, ASHRAE

Journal, 1999; 37-42.

5. Kim MH., Pettersen J, Bullard CW. Fundamental process and system design issues

in CO2 vapor compression systems, Prog Energy Comb Sc, 2004; 30(2); 119-174.

6. Riffat SB, Afonso CF, Aliveira AC, Reay DA. Natural refrigerants for refrigeration

and air conditioning systems, App Thermal Engg, 1997, 17(1); 33-42.

7. Pearson S. F. Natural refrigerants for heat pumps, IEA heat pump center newsletter

article, 22 (1/2004), 2004.

8. Casini D. CO2 compressors and equipment, use and availability, EURO cooling and

heating, Centro Studi Galileo; www.eurocooling.com.

9. Pettersen J, Skaugen G. Operation of transcritical CO2 vapour compression systems

in vehicle air conditioning. IIR International conference in New Applications of

Natural Working Fluids in Refrigeration and air-conditioning, 10-13 May, Hanover,

Germany, 1994; 495-505.

10. Inokuty H. Graphical method of finding compression pressure of CO2 refrigeration

machine for maximum coefficient of performance. The Fifth International Congress

of Refrigeration, Rome, 1928; 185—92.

11. Kauf F. Determination of the optimum high pressure for transcritical CO2

refrigeration cycles, Int J Thermal Science, 1999; 38(4); 325-330.

12. Liao SM, Zhao TS, Jakobsen A. A correlation of optimal heat rejection pressures in

transcritical carbon dioxide cycles, App Thermal Engg, 2000; 20(9); 831-841.

183

Page 206: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

13. Vaisman IB. COP analysis of carbon dioxide cycles, ASHRAE Trans, 2002; 108;

252-262.

14. Srinivasan K, Lim YK, Ho JC, Wijeysundera NE. Exergetic analysis of carbon

dioxide vapour compression refrigeration cycle using the new fundamental equation

of state, Energy Conv Mgmt, 2003; 44(20); 3267-3278.

15. Casson V, Cecchinato L, Corradi M, Fornasieri E, Girotto S, Minetto S, Zamboni L,

Gilio C. Optimisation of the throttling system in a CO2 refrigerating machine, Int J

Refrigeration, 2003; 26(8); 926-935.

16. Pettersen J. Experimental results of carbon dioxide in compression systems,

ASHRAE/NIST Conference Refrigerant for the 21st Century, Gaithersburg, MD;

1997; 27-37.

17. Robinson DM, Groll EA. Efficiencies of transcritical CO2 cycles with and without

an expansion turbine, Int J Refrigeration 1998; 21(7); 577-589.

18. Boewe DE, Bullard CW, Yin JM, Hrnjak PS. Contribution of internal heat

exchanger to transcritical R-744 cycle performance, ASHRAE Tran, 2001; 107;

189-199.

19. Heyl P, Quack H. Free piston expander-compressor for CO2 – design, applications

and results, 20th International Congress of Refrigeration, IIR/IIF, Sydney, 1999

(Paper 516).

20. Huff H-J, Radermacher R. CO2 compressor-expander analysis, ARTI final report

ARTI-21CR/611-10060-01, 2003.

21. Quack H, Kraus WE, Nickl J, Will G. Integration of a three-stage expander into a

CO2 refrigeration system, 6th IIR Gustav Lorentzen Natural Working Fluid

Conference, Glasgow UK, 2004, paper 4/A/12.20.

22. Elbel S, Hrnjak P. Flash gas bypass for improving the performance of transcritical

R744 systems that use microchannel evaporators, Int J Refrigeration, 2004; 27(7);

724-735.

184

Page 207: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

23. Ozaki Y, Takeuchi H, Hirata T. Regeneration of expansion energy by ejector in

CO2 cycle, 6th IIR Gustav Lorentzen Natural Working Fluid Conference, Glasgow

UK, 2004, paper 4/A/11.20.

24. Li D, Groll EA. Transcritical CO2 refrigeration cycle with ejector-expansion

device, Int J Refrigeration, 2005; 28(5); 766-773.

25. Groll EA Modeling of absorption/compression cycle using working pair carbon

dioxide/acetone, ASHRAE Trans, 1997; 103; 863-872.

26. Kim SG, Kim MS. Experiment and simulation on the performance of an

autocascade refrigeration system using carbon dioxide as a refrigerant, Int J

Refrigeration, 2002; 25(8); 1093-1101.

27. Mozurkewich G, Greenfield ML, Schneider WF, Zietlow DC, Meyer JJ. Simulated

performance and cofluid dependence of a CO2-cofluid refrigeration cycle with wet

compression, Int J Refrigeration, 2002; 25(8); 1123-1136.

28. Pitla SS, Robinson DM, Groll EA, Ramadhyani S. Heat transfer from supercritical

carbon dioxide in tube flow, a critical review, HVAC & R Research, 1998; 4(3);

281-301.

29. Olson D. Heat transfer of supercritical carbon dioxide flowing in a cooled

horizontal tube, The Fourth IIR-Gustav Lorentzen Conference on Natural Working

Fluids, West Lafayette, 2000; 251-258.

30. Gnielinski V. New equation for heat and mass transfer in turbulent pipe and channel

flow, Int Chem Engineering, 1976; 16(2); 359-368.

31. Pettersen J, Rieberer R, Leister A. Heat transfer and pressure drop characteristics of

supercritical carbon dioxide in microchannel tubes under cooling, The Fourth IIR-

Gustav Lorentzen Conference on Natural Working Fluids, West Lafayette, IN.

2000; 99–106.

32. Pitla SS, Groll EA, Ramadhyani S. Convective heat transfer from in-tube flow of

turbulent supercritical carbon dioxide Part 1 – Numerical analysis, HVAC & R

Research, 2001; 7(4); 345-366.

185

Page 208: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

33. Pitla SS, Groll EA, Ramadhyani S. Convective heat transfer from in-tube flow of

turbulent supercritical carbon dioxide Part 2 – Experimental data and numerical

prediction, HVAC & R Research, 2001; 7(4); 367-382.

34. Fang, X, Bullard, CW, Hrnjak BS. Heat Transfer and Pressure drop of gas coolers,

ASHRAE Trans, 2001; 107; 255-266.

35. Wang J, Hihara E. Study on carbon dioxide gas cooler heat transfer process under

supercritical pressures, Int J Energy Research, 2002; 26(14); 1237-1251.

36. Liao SM, Zhao TS. Measurement of heat transfer coefficients from supercritical

carbon dioxide flowing in horizontal mini/micro channels, ASME J Heat Transfer,

2002; 124(1); 413-420.

37. Jiang PX, Xu YJ, Lv J, Shi RF, He S, Jackson JD. Experimental investigation of

convective heat transfer of CO2 at super-critical pressures in vertical mini-tubes and

in porous media, App Thermal Engg, 2004; 24(8-9); 1255-1270.

38. Pitla SS, Groll EA, Ramadhyani S. New correlation to predict the heat transfer

coefficient during in-tube cooling of turbulent supercritical CO2; Int J Refrigeration,

2002; 25(7); 887-895.

39. Scalabrin G, Piazza L, Condosta M. Convective cooling of supercritical carbon

dioxide inside tubes: heat transfer analysis through neural networks, Int J Heat Mass

Transfer, 2003; 46(23); 4413-4425.

40. Yoon SH, Kim JH, Hwang YW, Kim MS, Min K, Kim Y. Heat transfer and

pressure drop characteristics during the in-tube cooling process of carbon dioxide in

the supercritical region, Int J Refrigeration, 2003; 26(8); 857-864.

41. Zhao Y, Ohadi MM. Experimental study of supercritical CO2 gas cooling in a

microchannel gas cooler, ASHRAE Trans, 2004; 110; 291-300.

42. Dang C, Hihara E. In-tube cooling heat transfer of supercritical carbon dioxide. Part

1. Experimental measurement, Int J Refrigeration, 2004; 27(7); 736-747.

43. Dang C, Hihara E. In-tube cooling heat transfer of supercritical carbon dioxide. Part

2. Comparison of numerical calculation with different turbulence models, Int J

Refrigeration, 2004; 27(7); 748-760.

186

Page 209: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

44. Bredesen AM, Hafner A, Pettersen J, Neksa P, Aflekt K. Heat transfer and pressure

drop for in-tube Evaporation of CO2, Proceedings International Conference on Heat

Transfer Issues in Natural Refrigerants, Nov. 6-7, 1997, College Park, pp. 1-15.

45. Zhao Y, Molki M, Ohadi MM, Dessiatoun SV. Flow boiling of CO2 in

microchannels, ASHRAE Trans, 2000; 106; 437-446.

46. Zhao Y, Molki M, Ohadi MM, Franca FHR, Radermacher R. Flow boiling of CO2

with miscible oil in microchannels, ASHRAE Trans, 2001; 107; 135-143.

47. Yun R, Kim Y, Kim MS, Choi Y. Boiling heat transfer and dryout phenomenon of

CO2 in a horizontal smooth tube, Int J Heat Mass Transfer, 2003; 46(13); 2353-

2361.

48. Gungor, KE, Winterton RHS. A general correlation for flow boiling in tubes and

annuli, Int J Heat Mass Transfer, 1986; 29(3); 351-358.

49. Yun R, Kim Y. Critical quality prediction for saturated flow boiling of CO2 in

horizontal small diameter tubes, Int J Heat Mass Transfer, 2003; 46(14); 2527-

2535.

50. Pettersen J. Flow vaporization of CO2 in microchannel tubes, Exp Thermal Fluid

Science, 2004; 28(2-3); 111-121.

51. Pettersen J. Two-Phase Flow Patterns in Microchannel Vaporization of CO2 at

Near-Critical Pressure, Heat Transfer Engg, 2004; 25(3); 52–60.

52. Yoon SH, Cho ES, Hwang YW, Kim MS, Min K, Kim Y. Characteristics of

evaporative heat transfer and pressure drop of carbon dioxide and correlation

development, Int J Refrigeration, 2004; 27(2); 111-119.

53. Thome JR, Hajal JE. Flow boiling heat transfer to carbon dioxide: general

prediction method, Int J Refrigeration, 2004; 27(3); 294-301.

54. Huai X, Koyama S, Zhao TS, Shinmura E, Hidehiko K, Masaki M. An

experimental study of flow boiling characteristics of carbon dioxide in multiport

mini channels, App Thermal Engg, 2004; 24(10); 1443-1463.

187

Page 210: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

55. Pettersen J, Hafner A, Skaugen G, Rekstad H. Development of compact heat

exchangers for CO2 air-conditioning systems, Int J Refrigeration, 1998; 21(3); 180-

193.

56. Pettersen J. Comparison of explosion energies in residential air-conditioning

systems based on HCFC-22 and CO2, 20th International Congress of Refrigeration,

IIR/IIF, Sydney, 1999, (paper 240).

57. Süss J, Kruse H. Efficiency of the indicated process of CO2-compressors, Int J

Refrigeration, 1998; 21(3); 194-201.

58. Neksa P, Dorin F, Rekstad H, Bredesen AE, Serbisse A. Development of semi-

hermetic CO2 compressors, 20th International Congress of Refrigeration IIR/IIF,

Sidney, 1999, (paper 424).

59. Fukuta M, Radermacher R, Lindsay D, Yanagisawa T. Performance of vane

compressor for CO2 cycle, The Fourth IIR-Gustav Lorentzen Conference on Natural

Working Fluids, West Lafayette, 2000; 339–346.

60. Hubacher B, Groll EA. Measurement of Performance of Carbon Dioxide

Compressors, ARTI Project #611-10070 Final Report, December 2002.

61. Kim HJ, An KJ, Ahn JM, Cho SO. Performance comparison of various types of

CO2 compressors for heat pump water heating application, 6th IIR G. Lorentzen

Natural Working Fluid Conference, Glasgow, 2004, paper 6/A/12.00.

62. Fang X, Bullard CW, Hrnjak PS. Modeling and analysis of gas coolers, ASHRAE

Trans, 2001; 107(1); 4-13.

63. Yin JM, Bullard CW, Hrnjak PS. R-744 gas cooler model development and

validation, Int J Refrigeration, 2001; 24(7); 692-701.

64. Bullard CW, Yin JM, Hrnjak PS. Compact counterflow gas cooler for R-744,

ASHRAE Trans, 2002; 108(1); 487-491.

65. Garimella S. Microchannel gas coolers for carbon dioxide air-conditioning system,

ASHRAE Trans, 2002; 108(1); 492-499.

188

Page 211: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

66. Asinari P, Cecchinato L, Fornasieri E. Effects of thermal conduction in

microchannel gas coolers for carbon dioxide, Int J Refrigeration, 2004; 27(6); 577-

586.

67. Neksa P, Hoggen RL, Aflekt K, Jakobsen A, Skaugen G. Fan-less heat exchanger

concept for CO2 heat pump system, 6th IIR Gustav Lorentzen Natural Working

Fluid Conference, Glasgow UK, 2004, paper 6/A/11.40.

68. Boewe D, Yin J, Park Y, Bullard C, Hrnjak P. The role of suction line heat

exchanger in transcritical R744 mobile A/C systems, SAE Paper No. 1999-01-0583;

1999.

69. Kim MH, Bullard CW. Development of microchannel evaporator model for a CO2

air-conditioning system, Energy, 2001; 26(10); 931-948.

70. Ikeda H, Yagi J, Kawaguchi Y. Evaluation of various compressor lubricants for a

carbon dioxide heat pump system, 6th IIR Gustav Lorentzen Natural Working Fluid

Conference, Glasgow UK; 2004.

71. Leisenheimer B, Fritz T. Interaction between CO2 and elastomers with respect to

permeation and explosive decompression, The Fourth IIR-Gustav Lorentzen

Conference on Natural Working Fluids, West Lafayette, IN. 2000; 201–208.

72. Pettersen J. An efficient new automobile air-conditioning system based on CO2

vapour compression, ASHRAE Trans, 1994; 100; 657-665.

73. Bhatti M. A critical look at R-744 and R-134a mobile air conditioning systems,

SAE paper No. 970527; 1997.

74. McEnaney R, Park Y, Yin J, Bullard C, Hrnjak P. Performance of the prototype of a

transcritical R744 mobile A/C system. SAE Paper No. 99PC-6-7; 1999.

75. McEnaney RP, Hrnjak PS. Control strategies for transcritical R744 systems, SAE,

Paper No. 2000-0-1272, 2000; 1711-1720.

76. Brown JS, Yana-Motta SF, Domanski PA. Comparative analysis of an automotive

air conditioning systems operating with CO2 and R134a, International Journal of

refrigeration, 2002; 25 (1); 19-32.

189

Page 212: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

77. Liu H, Chen J, Chen Z. Experimental evaluation of the optimal refrigerant mass

charge in a CO2 automotive air conditioner, 6th IIR Gustav Lorentzen Natural

Working Fluid Conference, Glasgow UK; 2004; paper 7/A/2.20.

78. Giannavola M, Murphy R, Yin J, Kim MH, Bullard C, Hrnjak P. Experimental

investigations of an automotive heat pump prototype for military, SUV and

compact cars, The Fourth IIR-Gustav Lorentzen Conference on Natural Working

Fluids, West Lafayette, IN. 2000; 115–122.

79. Rozhentsev A, Wang C-C. Some design features of a CO2 air conditioner, Applied

Thermal Engineering, 2001; 21(8); 871-880.

80. Brown JS, Kim Y, Domanski PA. Evaluation of carbon dioxide as R-22 substitute

for residential air-conditioning, ASHRAE Transactions, 2002; 108(2); 954-963.

81. Rieberer R, Halozan H. CO2 heat pumps in controlled ventilation systems.

Proceedings of the Third IIR-Gustav Lorentzen Conference on Natural Working

Fluids, Oslo, Norway; 1998; 212–222.

82. Beaver A, Yin J, Bullard CW, Hrnjak PS. Experimental and model study of the heat

pump/air conditioning systems based on transcritical cycle with R744, 20th

International Congress of Refrigeration, IIR/IIF, Sydney, 1999; Paper 434.

83. Nekså P. CO2 heat pump systems, Int J Refrigeration, 2002; 25(4); 421-427.

84. Richter MR, Song SM, Yin JM, Kim MH, Bullard CW, Hrnjak PS. Experimental

results of transcritical CO2 heat pump for residential application, Energy, 2003;

28(10); 1005-1019.

85. Jakobsen A, Skaugen G, Skiple TV, Neksa P, Andresen T. Development and

evaluation of a reversible CO2 residential air conditioning system compared to a

state-of-the art R410A unit, 6th IIR Gustav Lorentzen Natural Working Fluid

Conference, Glasgow UK; 2004; paper 5/A/10.10.

86. Neksa P, Rekstad H, Zakeri GR, Schiefloe PA. CO2 heat pump water heater:

characteristics, system design & experimental results, Int J Refrigeration, 1998;

21(3); 172-179.

190

Page 213: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

87. Hwang Y, Radermacher R. Theoritical evaluation of carbon dioxide refrigeration

cycle, HVAC & R Research, 1998; 4(3); 245-263.

88. Hwang Y, Radermacher R. Experimental investigation of the CO2 refrigeration

cycle, ASHRAE Trans, 1999; 105; 1219-1228.

89. White SD, Yarrall MG, Cleland DJ, Hedley RA. Modelling the performance of a

transcritical CO2 heat pump for high temperature heating, Int J Refrigeration, 2002;

25 (4); 479-486.

90. Stene J. Residential CO2 heat pump system for combined space heating and hot

water heating, 6th IIR Gustav Lorentzen Natural Working Fluid Conference,

Glasgow UK, 2004; paper 6/A/12.20

91. Robinson DM., Groll EA. Theoretical performance comparison of CO2 transcritical

cycle technology versus HCFC-22 technology for a military packaged air

conditioner application, HVAC & R Research, 2000; 6(4); 325-348.

92. Manzione J, Calkins F. Evaluation of transcritical CO2 using an automotive

compressor in a packaged-unitary military ECU. ASHRAE Trans, 2002; 108(2):

937–943.

93. Li D, Groll EA Theoretical performance evaluation of a carbon dioxide based

environmental control unit (ECU) with microchannel heat exchangers, 6th IIR G.

Lorentzen Natural Working Fluid Conference, Glasgow UK, 2004; 5/A/9.30.

94. Schiesaro P, Kruse H. Development of a two-stage CO2 super market system, IIF –

IIR – Commission D1/B1 –Urbana, IL, USA – 2002/07.

95. Sasaki M, Koyatsu M, Yoshikawa C, Fujima K, Mizuno T, Kawai S, Hashizume T.

The effectiveness of a refrigeration system using CO2 as a working fluid in Trans-

critical region, ASHRAE Trans, 2002; 108(1); 413-419.

96. Girotto S, Minetto S, Neksa P. Commercial refrigeration system using CO2 as the

refrigerant, Int J Refrigeration, 2004; 27(7); 717–723.

97. Yarral MG, White SD, Cleland DJ, Kallu RDS, Hedley RA. Performance of

transcritical CO2 heat pump for simultaneous refrigeration and water heating, 20th

International Congress of Refrigeration, IIR/IIF, Sydney, 1999; Paper 651.

191

Page 214: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

98. Adriansyah W. Combined air conditioning and tap water heating plant using CO2 as

refrigerant, Energy and Buildings, 2004; 36(7); 690-695.

99. Schmidt EL, Klöcker K, Flacke N, Steimle F. Applying the transcritical CO2

process to a drying heat pump, Int J Refrigeration, 1998; 21(3); 202-211.

100. Klöcker K, Schmidt EL, Steimle F. Carbon dioxide as a working fluid in drying

heat pumps: Int J Refrigeration, 2001; 24(1); 100-107.

101. Span R, Wagner W. A new equation of state for Carbon dioxide covering the fluid

region from triple point temperature to 1100 K at pressure up to 800 MPa, J. Phys.

Chem. Ref. Data 1996; 25; 1509-1596.

102. Vesovic V., Wakeham W.A., Olchowy G.A., Sengers J.V., Watson J.T.R, Millat J.

The transport properties of carbon dioxide, J. Phys. Chem. Ref. Data, 1990; 19;

763-808.

103. Fenghour A, Wakeham WA, Vesovic V. The viscosity of carbon dioxide, J. Phys.

Chem. Ref. Data, 1998; 27; 31-44.

104. NIST database ‘REFPROP’ version 6.0, Washington DC, USA, 1998.

105. Fartaj A, Ting DS-K, Yang WW. Second law analysis of the transcritical CO2

refrigeration cycle, Energy Conversion Management, 2004; 45(13-14); 2269-228.

106. Ortiz TM, Li D, Groll EA. Evaluation of the performance potential of CO2 as a

refrigerant in air-to-air air conditioners and heat pumps: system modelling and

analysis, ARTI final report, no. 21CR/610-10030, 2003.

107. Kakac S, Liu H. Heat Exchangers: Selection, rating and thermal design, CRC Press,

Landon; 2002.

108. Aprea C, de Rossi F, Greco A, Renno C. Refrigeration plant exergetic analysis

varying the compressor capacity. Int J Energy Research 2003; 27: 653-669.

109. Stegou-Sagia A, Paignigiannis N. Exergy losses in refrigeration systems. A study

for performance comparisons in compressor and condenser. Int J Energy Research

2003; 27: 1067-1078.

110. Bejan A. Entropy generation through heat and fluid flow, New York, Wiley, 1982.

192

Page 215: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

111. Yilmaz M, Sara ON, Karsli S. Performance evaluation criteria for heat exchanger

based on second law analysis, Exergy: Int Journal, 2001; 4; 278-294.

112. Personal communication with Mario Dorin, Dorin S.p.A., Italy.

113. Zhang, M, and RL Webb. Correlation of two-phase friction for refrigerant in small

diameter tubes, Exp Thermal Fluid Sc, 2001; 25; 131-139.

114. Cornelissen RL, Hirs GG. Thermodynamic optimisation of a heat exchanger, Int J

Heat Mass Transfer, 1999; 42; 951-959.

115. Costa MM, Schaeffer R, Worrel E. Exergy accounting on energy and material flows

in steel production systems, Energy, 2001; 26(4); 363-384.

116. Sarkar J, Bhattacharyya S, Ramgopal M. Transcritical carbon dioxide based heat

pumps: Process heat applications. Tenth International Refrigeration and Air

Conditioning Conference. July 12-15, 2004, Purdue, USA.

117. Prasertsan S, Saen-Saby P, Ngamsritrakul P, Prateepchaikul G. 1996. Heat pump

dryer Part 1: Simulation of the models. Int J Energy Research, 20: 1067-1079.

118. McQuiston FC, Parker JD, Spitler JD. 2001. Heating, ventilating, and air

conditioning: analysis and design. 5th Ed, Wiley, New York

119. Rich DG. 1973. The effect of fin spacing on the heat transfer and friction

performance of multi-row, smooth plate fin and tube heat exchangers. ASHRAE

Trans, 79(1); 137-145.

120. Turaga M, Lin S, Fazio PP. 1988. Correlation for heat transfer and pressure drop

factors for direct expansion air cooling and dehumidifying coils. ASHRAE Trans,

94(2): 616-629.

121. Adapa PK, Schoenau GJ, Sokhansanj S. 2002. Performance study of a heat pump

dryer system for specialty crops – Part 1: Development of simulation model. Int J

Energy Research, 26: 1001-1019.

122. Chou SK, Hawlader MNA, Ho JC, Wijeysundera NE, Rajasekar S. 1994.

Performance of a heat pump assisted dryer. Int J Energy Research, 18: 605-622.

123. ASHRAE. 1993. Fundamentals Handbook, ASHRAE. Chapter 6.

193

Page 216: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

124. Shiming D. A dynamic mathematical model of a direct expansion (DX) water-

cooled air-conditioning plant, Building & Environment, 2000, 35: 603-613.

125. Prasertsan S, Saen-Saby P, Ngamsritrakul P, Prateepchaikul G. Heat pump dryer

Part 2: Result of the simulation, Int J Energy Research, 1997; 21(1): 1-20.

126. Jia X., Jolly P, Claments S. Heat pump assisted continuous drying - Part 2:

Simulation results, Int J Energy Research, 1990; 14: 771-782.

127. Clements S, Jia X, Jolly P. Experimental verification of a heat pump assisted

continuous dryer simulation model, Int J Energy Research, 1993; 17: 19-28.

128. Beckwith TG, Buck NL, Marangoni RD. Mechanical measurement, 3rd Ed, Narosa

Publishing House, New Delhi, 1994.

194

Page 217: Transcritical Carbon Dioxide Based Heat Pumps for Simultaneous Cooling and Heating Applications

195

Author publications (Total = 60)

Journal Papers published from Thesis

1. Sarkar J, Bhattacharyya S, Ramgopal M. Optimization of a transcritical CO2 heat pump cycle for simultaneous

cooling and heating applications. International Journal of Refrigeration 2004; 27(8): 830-838.

2. Sarkar J, Bhattacharyya S, Ramgopal M. Transcritical CO2 heat pump systems: Exergy analysis including heat

transfer and fluid flow effects, Energy Conversion and Management, 2005; 46(13-14): 2053-2067.

3. Sarkar J, Bhattacharyya S, Ramgopal M. Simulation of a transcritical CO2 heat pump cycle for simultaneous cooling

and heating applications, International Journal of Refrigeration, 2006; 29(5): 735-743.

4. Sarkar J, Bhattacharyya S, Ramgopal M. CO2 heat pump dryer: Part 1. Mathematical model and simulation, Drying

Technology, 2006; 24(12): 1583-1591.

5. Sarkar J, Bhattacharyya S, Ramgopal M. CO2 heat pump dryer: Part 2. Validation and simulation results, Drying

Technology, 2006; 24(12): 1593-1600.

6. Sarkar J, Bhattacharyya S, Ramgopal M. Irreversibility minimization of heat exchangers for transcritical CO2 systems,

International Journal of Thermal Sciences, 2009; 48(1): 146-153.

7. Sarkar J, Bhattacharyya S, Ramgopal M. A transcritical CO2 heat pump for simultaneous water cooling and heating:

Test results and model validation, International Journal of Energy Research, 2009; 33(1): 100-109.

8. Sarkar J. Transcritical CO2 heat pump simulation model and validation for simultaneous cooling and heating,

International Journal of Mathematical, Physical and Engineering Sciences, 2009; 3(4): 199-204.

9. Sarkar J, Bhattacharyya S, Ramgopal M. Performance of a transcritical CO2 heat pump for simultaneous water

cooling and heating, International J Applied Science, Engineering and Technology, 2010; 6(1): 57-63.

10. Sarkar J, Bhattacharyya S, Ramgopal M. Experimental investigation of transcritical CO2 heat pump for simultaneous

water cooling and heating, Thermal Science, 2010; 14(1): 57-64.

Conference Papers published from Thesis

1. Sarkar J, Bhattacharyya S, Ram Gopal M. Carbon dioxide based heat pump dryers in food industry, Int conf Emerging

technologies in Agri food engg, IIT Kharagpur, Dec 14-17, 2004.

2. Sarkar J, Bhattacharyya S, Ramgopal M, Gautam S. Comparison and validation of heat transfer correlations for in-

tube cooling of supercritical CO2, 18th national & 7th ISHMT-ASME heat & mass transfer conf, IIT Guwahati, Jan 4-6,

2006.

3. Sarkar J, Bhattacharyya S, Ramgopal M. Transcritical CO2 heat pump prototype development for simultaneous water

cooling and heating, 22nd IIR Int Congress of Refrigeration, Beijing, China, 2007; ICR07-E2-548.

4. Sarkar J, Bhattacharyya S, Ramgopal M. Pressure drop for in-tube supercritical co2 cooling: comparison of

correlations and validation, 19th national & 8th ISHMT-ASME heat & mass transfer conf, JNTU India, Jan 3-5, 2008.

5. Sarkar J, Bhattacharyya S, Ramgopal M. Comparison and validation of in-tube CO2 boiling heat transfer correlations

(Paper 58), 20th national & 9th ISHMT-ASME heat & mass transfer conf, IIT Bombay, India, Jan 4-6, 2010.