TR7 TP133 Full Content Part1 مهم

Embed Size (px)

Citation preview

  • 7/21/2019 TR7 TP133 Full Content Part1

    1/100

    Modeling and Analysis ofSystem Transients Using

    Digital ProgramsPREPARED BY THEIEEE Working Group 15.08.09

    IEEE Power & Energy Society

    1998

    TECHNICAL REPORT

    PES-TR7Formerly TP133

    IEEE 2013 The Institute of Electr ical and Electronic Engineers, Inc.No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publis

  • 7/21/2019 TR7 TP133 Full Content Part1

    2/100

    THIS PAGE LEFT BLANK INTENTIONALLY

  • 7/21/2019 TR7 TP133 Full Content Part1

    3/100

    IEEE PES

    pecial ublication

    MODELING AND ANALYSIS

    OF

    SYSTEM

    TRANSIENTS

  • 7/21/2019 TR7 TP133 Full Content Part1

    4/100

    Prepared

    By

    IEEE

    Working

    Group

    15.08.09

    MODELING AND ANALYSIS OF SYSTEM TRANSIENTS USING

    DIGITAL PROGRAMS

    Working

    Group Chairman

    A. J. F. Keri American Electric Power

    Task

    Forces and Chairmen

    1 Power Electronics

    2 Slow Transients

    3 Switching Transients

    4 Fast Front Transients

    5 Very Fast Front Transients

    Siemens

    6 Protection and Controls

    7 Bibliography

    K. K. Sen Siemens , Le Tang ABB

    R. Iravani Univ. of Toronto

    A. M. Gole Univ. ofManitoba ,

    D. W. Durbak PTI

    A. F. Imece ABB

    J.A. Martinez-Velasco Univ. Politec.

    de Catalunya* , D. Povh

    A.K.S. Chaudhary Cooper Power

    System , R.E. Wilson WAPA

    T.E. Grebe Electrotek Concepts, Inc

    J.A. Martinez-Velasco *

    Editors:

    A. M. Gole, J. Martinez-Velasco, A. J. F. Keri

    Acknowledgments: The Working group was originated and technically

    supported by Dr. B. R. Shperling New York Power Authority . T.E. Grebe

    was also the Secretary

    of

    the Working Group. Dr. A. M. Gole had also the

    difficult job

    of

    organizing Task Force reports into this Special Publication.

    Tutorial On

    Modeling And Analysis or SystemTransients Using Digital Programs

    Abstracting is permitted with credit to the source. For other copying, reprint, or republication permission, write to the IEEE

    Copyright Manager, IEEE Service Center, 445 Hoes Lane, Piscataway, NJ 08855-1331. All rights reserved. Copyright 1998

    by The Institute of Electrical and Electronics Engineers, Inc.

    IEEE Catalog Number: 99TP133-0

    Additional copies of this publication are available from

    IEEE Operations Center

    P. O. Box 1331

    445 Hoes Lane

    Piscataway, NJ 08855-1331 USA

    1-800-678-IEEE IndividuaUMember Orders

    1-800-701-IEEE Institutional Orders

    1-732-981-0060

    1-732-981-9667 FAX

    email: [email protected]

  • 7/21/2019 TR7 TP133 Full Content Part1

    5/100

    TABLE OF

    CONTENTS

    Introduction

    i

    1. Background 1-1

    2.

    Power

    Electronics 2-1

    3. Slow

    Transients

    3-1

    4. Switching Transients 4-1

    5. Fast

    Front

    Transients 5 -1

    6.

    Very

    Fast Front

    Transients

    6-1

    7. Protection and Controls 7-1

    8. BibIi

    0grap

    hy ....................... ..... ....... .. .. .. 8-1

  • 7/21/2019 TR7 TP133 Full Content Part1

    6/100

    Modelingand Analysis ofSystem TransientsUsing

    Digital Programs

    Introduction

    IEEE PES Working Group 15.08.09

    A J F

    Keri Chairman ,

    A M

    Gole

    1. INTRODUCTION

    Thisdocumentis written in orderto provideguide-

    lines for the modelingof power systemapparatusfor use in

    time- domainsolutionof electromagnetic transientphenom-

    enon. This publication has been arrangedin the following

    eight 8 parts.

    Part

    :Background

    Part 2 :PowerElectronics

    Part 3:SlowTransients

    Part

    :Switching Transients

    Part 5 :FastFrontTransients

    Part 6

    Very

    Fast FrontTransients

    Part 7 :ProtectionAndControl

    Part 8 :Bibliography

    A

    generalstatementof each area is as

    follows

    BACKGROUND

    This sectionpresentsa comprehensive summary of

    thebackground andstateof theart for thetransientsolutions,

    representation of control systems, and modeling of power

    systemcomponents.

    2

    POWERELECTRONICS

    Theguideline presentsthe basicissuesthat arecriti-

    cal for successfullymodeling of power electronics devices

    andthe interfacebetweenpowerelectronics andtheutilityor

    industrial system. Modelingaspectsare presentedfor simu-

    lation of the semiconductorswitchingdevices, power elec-

    tronics system,snubbertreatment, and simulation errors and

    control . A number of simulation examples, including

    FACTS

    modeling, are presented.

    3SLOW TRANSIENTS

    Modeling guidelines are presented for investiga-

    tionsof smallsignaltorsional oscillations, large -signalshaft

    transientstresses, turbine-bladevibrations, fastbus transfer,

    controllerinteractions, harmonics interaction, and resonance

    phenomena. Sample test systemsand simulationresults are

    provided.

    i-I

    4

    SWITCHING TRANSIENTS

    The range of frequencies of primary interest in a

    switching transients studyvary fromthe fundamental power

    frequency up to

    10kHz.

    Switchingsurgemodelingguide-

    lines are presentedincluding modelingof the variouspower

    systemcomponents suchas transmission lines, cables,trans-

    formers, sourceequivalents, loads and circuit breakers. In

    addition, typicalcasestudiesare alsopresented.

    5FASTFRONTTRANSIENTS

    Modeling guidelines are presented for fast front

    transients i.e., frequency rangefrom

    10 kHz

    up to

    1 MHz ,

    withparticularemphasison lightningsurgeanalysisof over-

    head lines and substation. Modelingphilosophies, simpli-

    fiedmathematical relationships,typical data, and examples

    are given for various power system components. A case

    studyis presentedin order to illustrate the overallmodeling

    procedure.

    6V RYFASTFRONTTRANSIENTS

    Theobjective of this sectionis to providean expla-

    nation of the phenomena of very fast transients, in the fre-

    quencyrangeof

    100

    kHz to

    50 MHz.

    Thistypeof transients

    typically occur in the gas insulated substations GIS .

    Effects andmodelingguidelines forGIS are presented. An

    example of a GIScalculationwith detailedinput data is pro-

    vided. A simulation accuracyis verifiedwith fieldmeasure-

    ments

    7PROTECTIONAND ONTROL

    Generalguidelinesformodelingof protection sys-

    tems is presented. Because digital modeling

    of

    protection

    systemsin the electromagnetic transients programsis a rela-

    tivelynewprocedure, this section describes the advantages

    and limitations of theprotectionsystemmodeling. Model-

    ing of instrument transformers, relays - electromechanical,

    staticandmicroprocessor based are summarizedandmodels

    are presented.

    8BIBLIOGRAPHY

    A

    comprehensive list of references on the subject-

    are provided.

  • 7/21/2019 TR7 TP133 Full Content Part1

    7/100

    Digital Computation of Eelectromagnetic

    Transients in Power Systems:

    Current

    Status

    JuanA.Martinez-Velasco

    Departament d Enginyeria Electrica

    Universitat Politecnica deCatalunya, Spain

    Abstract-

    Thisdocumentpresentsan introductionto time-domain

    solution of electromagnetic transients in power systems using a

    digitalcomputerCurrently, themostwidely usedsimulation tools

    to

    solve

    electromagnetictransientsare basedonthe trapezoidalrule

    andthemethodofcharacteristics(Bergeron smethod). Onlyworks

    related to this solutionalgorithmare considered in this

    document

    whichcoverstwomaintopics: solution techniques and

    modeling

    of

    powercomponents.

    Keywords : Electromagnetic Transients, Time-domain

    Simulation, TrapezoidalRule, Numerical Oscillations, Control

    Systems, Modeling.

    1. INTRODUCTION

    Transient phenomena in power systems are caused by

    switching operations, faults, and other disturbances, such as

    lightning strokes. They involve a frequency range from DC to

    several MHz. A rough distinction is usually made between

    electromechanical transients, traditionally covered by transient

    stability studies, and electromagnetic transients. The latter type

    of transients can occur on a time scale that goes from

    microseconds to several cycles; they are a combination of

    travelling waves on lines, cables and buses, and ofoscillations

    in lumped-element circuitsofgenerators, transformers andother

    devices. Some electromechanical transients, such as

    subsynchronous resonance, for which detailed machine models

    are needed, are usually included in this class of transients.

    Several tools have been used over the years to analyze

    electromagnetic transients. At early stages, miniature power

    systemmodels, known as Transient Network Analyzers INA),

    were used. At present, the digital computer is the most popular

    tool, although INAs are still used; in addition, the new

    generation of real-time digital systems are probably the most

    adequate tool in some applications for which either a very

    high-speed or a real-time simulation is required.

    Many techniques have been developed to solve electromagnetic

    transients using a digital computer. They can be classified into

    two main groups : frequency-domain and time-domain

    1-1

    techniques. The subject of this document is the digital

    simulation ofelectromagnetic transients inpower systems, using

    time-domain techniques. Presently, the most widely used

    solution method is based on the application of

    the trapezoidal

    rule and the Bergeron s method, also known as method

    of

    characteristics [1] - [6].

    This document has been arranged as follows. Section 2 deals

    with the basic solution techniques either already implemented

    or proposed for implementation in electromagnetic transients

    programs (emtps). It covers not only the algorithms aimed at

    solving the transient solution, but procedures to reduce

    numerical oscillations produced by the trapezoidal rule,

    initialization methods, and procedures to solve the interface

    between power networks and control systems.

    Section 3 presents a summary ofmodeling works related to the

    most important power components taking into account their

    frequency-dependent behaviour.

    Due to difficulties for developing power component models

    accurate enough for a wide frequency range, much work has

    been done toprovidemodeling guidelines for digital simulation

    of every type of transient phenomenon. Section 4 summarizes

    the work done in this area and reports about works still in

    progress.

    Some topics, such as parallel computation or real-time emtp

    based simulation of electromagnetic transients, which are

    closely related to the main subjects of this document are not

    covered here.

    A selected bibliography related to topics

    of

    each part has been

    included at the end

    of

    this document.

    2. SOLUTION METHODS

    2.1 TRANSIENT SOLUTION

    The studies to solve travelling wave problems by means

    of

    a

  • 7/21/2019 TR7 TP133 Full Content Part1

    8/100

    Thetrapezoidal ruleisusedto convertthedifferential equations

    of thenetworkcomponents into algebraic

    equations

    involving

    voltages, currentsandpast

    values.

    Thesealgebraic equations are

    assembled usinga nodalapproach

    digital computer were started in the early

    1960

    s using two

    different techniques, the Bewley s lattice

    diagram

    [7] and the

    Bergeron

    s

    method

    [8]. Thesetechniqueswere

    applied

    tosolve

    small

    networks,

    withlinearandnonlinear lumped- parameter, as

    well as distributed-parameter

    elements.

    The extension to

    multinode networks was made by H.W. Dommel [1]. The

    Dommel s scheme combined

    the Bergeron s

    method

    and the

    trapezoidal rule intoan algorithm

    capable

    of

    solving

    transients

    insingle- andmulti-phase

    networks

    withlumped anddistributed

    parameters. This solution method was the origin of the

    ElectroMagnetic Transients Program (EMTP), whose

    development was supported by Bonneville Power

    Administration (BPA).

    Using

    compensation,

    nonlinear elements are represented as

    currentinjectionswhicharesuperimposed to thesolutionof the

    linear

    network

    afterthis solution hasbeen computed. Figure1

    shows the scheme of the compensation method for a single

    nonlinear

    element.

    proposed to cope with nonlinear and time-varying elements

    [11] . These modifications were based on a current source

    representation, a piecewise-linear representation or the

    compensation method. Someof theadvantages anddrawbacks

    shownby theseapproaches werediscussed in [5]and

    [11].

    r

    Nonlinear

    V

    km

    e q u a t i o

    -

    l

    ACS g)

    ref

    a

    Vb

    JOO

    Vc

    100

    100

    0

    0 10

    Fig. 20The BlockDiagramof a PLL

    ' 0

    lime

    mS

    60

    Fig.24DerivedFrequency Reference

    () 00

    Iime(mS)

    DO

    PLLO>TACS IH['AR T

    yp

    e 9)

    10

    - -

    i

    i

    I

    /

    / I / /

    /

    I

    +:

    f

    ...

    ....

    __

    ....

    Ii.

    I

    -+

    I

    :::

    f-

    -

    _

    ..._

    i

    /

    7f / /

    ]

    /

    J

    1/

    17

    I

    1

    1

    i

    /

    Iime (mS)

    10

    Fig. 21 Input three-phase Voltage Signal

    Fig. 25 Outputof VCO

    0.5 -1-- --- -- -- L-- - -i-.:---f- I----+--------,-j

    Fig. 22DQVoltage Components

    Fig. 26 Comparison ofInput andObtainedSyn. Signals

    The response of this control circuitry to a system

    disturbance is illustrated in Fig. 27. A balanced system fault

    is placed on and removed from the system, resulting a three

    cycle voltage sag.

    Three phase fault

    Rf=0.01 ohms

    Tin=0.025s

    Tcl=0.075s

    Kpro= 100

    Kint =8.3E-3

    100

    0

    0 60

    Time mS

    DO-PLLO >l

    ACS

    -DU MD13 lype g)

    10

    v ,

    :

    ,

    0.1000

    0.0500

    0 . O O

    -0.1000

    o

    -urseo

    Fig. 23DerivedPhaseError

    With above given control parameters, it takes the

    PLL

    about three cycles to be relocked into the system volt

    age.

    2-8

  • 7/21/2019 TR7 TP133 Full Content Part1

    34/100

    1

    40.0

    SNUBBC

    SNUBBR

    ATRMNL

    i

    GTRMNL

    SNUBBC \... i

    A model for a general, unidirectional conducting,

    three terminal, controllable

    power

    electronic device

    with

    snubber connections is shown in Fig. 29. An actual snubber

    configuration can be different

    from

    one application to

    another. However, if the purpose

    of

    a simulation is not to

    design the snubber, a sample snubber configuration shown in

    this figure can often provide satisfactory results.

    The fmite nature of the simulation time step that the

    EMTP type programs use also poses another problem for

    power electronic circuit simulation which necessitates the

    use

    of

    snubber circuits across fast acting power electronic

    switches. Note that in some situations the snubber Rand C

    values

    of

    the actual system

    mayor

    may

    not work in simula

    tions using some programs. In this case, the

    Rand

    C values

    of

    the snubbers needed for stable simulation is primarily

    dependent on the time step and secondarily on systemconfig

    uration (capacitors and inductors in the system) and the load

    current level. Programs using special features such as vari

    able time steps (very short time steps during switching) or

    interpolated switching [59] (simulate the switching very

    close to the required instant using linear interpolation

    between time steps) do not require fictitious snubber circuits.

    Therefore, one of the following measures or their combina

    tions can be taken to prevent numerical inaccuracies in the

    simulation:

    Select a smaller time step

    Use artificial snubber circuits

    Introduce a small smoothing reactor for DC links

    Introduce proper stray capacitances in the system model

    Provide a parallel damping for lumped system.

    oscillations in which case it

    is

    not a concern to the simulation

    engineer. Otherwise, some of the measures listed later in this

    section may have to be implemented to obtain correct results.

    Note that this example of PLL logic based on the

    three phase to DQ transformation is valid for three-phase bal

    anced application. Also, its performance characteristic is

    highly affected by the parameter settings.

    Fig. 28 The PLLCircuitry Responseto a SystemDisturbance

    Three phase fault

    Rf=O.OI

    ohms

    Tin=0.025s

    Tcl=0.075s

    With Modified:

    Kpro = 1000

    Kint = 8.3E-4

    If the circuit parameters are changed from the above

    given values to the values listed below, for the same system

    and fault, one can observe that the same PLL logic can be

    relocked into the system voltage within a half cycle period

    of

    the time as shown in Fig. 28.

    Fig. 27The PLLCircuitryResponseto a SystemDisturbance

    3.5. Snubber

    Treatment

    inEMTPtypePEModeling

    The simulation programs using trapezoidal integra

    tion method are inherently prone to spurious oscillations

    (also known as chatter) in capacitive and inductive circuits

    when subjected to sudden changes such as step change in

    voltage, current injection and switching. Some EMTP type

    programs take special measures to detect and remove these

    CTRMNL

    Fig. 29 A Sample Snubber Circuit

    2-9

  • 7/21/2019 TR7 TP133 Full Content Part1

    35/100

    3.6.Simulation ErrorsandControl

    DC Link

    rrors in a Power Electronics simulation can come

    through the following sources:

    1. switching device approximation and system reduction

    2. added circuit elements for numerical oscillation control

    3. control system simplification

    4. time step related truncation

    5. program structure and solution method introduced inter

    facing time delay

    6. incorrect system initial conditions

    AC Supply

    ~

    Six Pulse

    Diode Rectifier

    PWM

    Inverter

    Induct ion

    Motor

    For application simulations, some errors resulting

    from the system simplification and measures of numerical

    oscillation control are acceptable. The fourth and fifth items

    in the list can be controlled by reducing the time step size. A

    recommended time step size should not be greater than 1/5 to

    1/20

    of the

    period

    of

    the highest concerned

    frequency

    cycle. For an example, for an IGBT inverter simulation with

    5000Hz PWM switching, a selected time step could be 10

    ms. However, if the objective

    of

    the simulation is to see the

    detailed transient at the terminal of the induction motor

    which is fed by the inverter through a section of the cable

    with an 1.0 ms travel time, an adequate time step should be

    0.2 ms or smaller.

    Fig. 30. Electrical Circuit Configuration of an Adjustable Speed

    Drive

    The built-in diode models are used to construct the

    front end rectifier. The same switching devices with added

    open/close controls are used to represent output inverter

    IGBTs. The EMTP input data modules are use to build this

    example case. Both the output reference frequency and the

    PWM carrier frequency are made to be controllable. Model

    ing of a signal processing and firing pulse generation is illus

    trated in

    this example . The

    motor load of the

    drive

    is

    represented by its R+jX equivalent branch. The simulated

    AC input current, carrier and reference signal for the PWM

    control, AC output voltage and current are presented in Fig.

    31 through Fig. 33.

    PW

    vS

    I>T

    ACS - D

    JM

    C58 yoe9

  • 7/21/2019 TR7 TP133 Full Content Part1

    36/100

    Fig.33.Simulated ACOutputLine-to-line Voltage ofA PWM-VSI

    Adjustable SpeedDrive

    4.2.Simulation ofVoltage Notching Causedby

    Operation

    of

    Current Source Inverter

    CSI)

    ASD

    8:xJ

    PWVSI>NVRTA-

    INVRTB(Type

    8)

    i

    600,

    II

    II

    II

    00

    i :

    slOO

    I i

    rio

    1

    Ig

    -lOO

    t

    .

    I

    i

    I

    I

    .

    -

  • 7/21/2019 TR7 TP133 Full Content Part1

    37/100

    Vo ltoge 01

    4160

    Vo lt Surge Copocitor - Bose

    Cose

    -6000

    -8000

    --

    ----:. . .-------cc----------I

    tl

    nous condenser (SC) and half-and-half mix of the two

    (SVC+SC).

    Fig. 38 shows the typical results obtained from the

    simulation for a permanentDC block. The fixed compensator

    case does not control the overvoltage; however, all other

    optionsdo. The SVC option is the fastest to respond followed

    by the SVC+SCoption and lastly the SCoption. This simula

    tion setup can be used to conduct almost any type of perfor

    mance study including a thyristor miss-fire in HVDC valve

    group or in the SVC itself.

    0.6

    .5

    .2 0.3 0.4

    Time (s)

    0.1

    1-

    - - - - - ,- - - - - - - YG:- - - - - - - - - -

    1.6

    1.5

    , - . .

    1.4

    ;:3

    5

    Q)

    1 3

    eo

    S

    ~

    1.2

    / )

    ~

    1 1

    u

    1.0

    )

    t:

    Q)

    >

    s::

    0.9

    -

    0.8

    0.7

    0.0

    The third example is an illustration case for model

    ing of an HYDC system with shunt TscrrCR compensation

    at the inverter bus [54]. The simulation example is made

    using PSCAD/EMTDC. The schematic systemshown inFig.

    37 is a modified version of the GlGRE BenchmarkModel for

    HYDC Control Studies [55].

    Fig. 36.Simulated waveform

    at

    surge

    capacitor

    location (4.16

    kV

    bus

    ofcustomer on

    parallel feeder)

    The inverter short circuit ratio has been reduced

    from its original value of 2.5 to 1.5to make the study more

    interesting. The DC link is a 1000MW, 500kV, 12 pulse

    monopolar system. There are damped low and high pass fil

    ters at each converter terminal to reduce the distortionon the

    AC bus. The control scheme for the HYDC system consists

    of a rectifier current controller with the gamma controller.

    4.3. Simulation ofHVDC

    Terminal

    and Shunt TSCITCR

    Compensation

    The SVC system is a -200/+300 MVAr, 12 pulse,

    TCR and TSC (two stage) combination connected to the

    inverter bus through a step up

    transformer,

    The SVCcontrols

    are designed to coordinate the control of TCR and TSC in

    such a way that the combined susceptance of the SVC is con

    tinuous over its entire operating range. The basic control

    mode is voltage control and has as a voltage droop built into

    the controls. Several studies to evaluate the recovery to full

    power after a contingency were simulated [54]. The perfor

    mances of

    several compensation options were compared.

    These options included fixed capacitors (FC), SVC, synchro-

    Rectifier AC

    System

    1000MW

    500kV

    12 Pulse

    Fig. 37. Study

    System

    Inverte

    r AC

    System

    Fig.

    38

    Inverter

    AC

    Voltage

    Follo

    winga

    Permanent DC

    Block

    4.4. ModelingofRotatingMachines

    Two possible situations can be considered for mod

    eling a rotatingmachine when simulating a power electronic

    system

    1. The machine is a component of a larger system where

    one or several power electronic devices are operating,

    for instance a synchronousmachine connected to a

    transmissionnetworkwhere FACTSdevices are used to

    control power flows and improve transient stability.

    2. The machine is part of the power electronic system, for

    instance an adjustable speed drive.

    Similar modeling guidelines for representing rotat

    ing machine in both situations can be used, however some

    particular considerations can be taken into account in some

    cases andstudies.Modelingguidelines provided in this docu

    ment assume that power electronic systems operate at low

    frequencies, betweenDC and 3 kHz. Therefore only the rep

    resentation of rotating machines for this frequency range is

    discussed. Regardless of the application to be simulated a

    2-12

  • 7/21/2019 TR7 TP133 Full Content Part1

    38/100

    detailed modeling for the electrical and the mechanical parts

    is usually required, saturation effects should be included, and

    capacitance effects can be neglected. Frequency dependent

    of

    electrical parameters, mainly rotor parameters might also be

    considered. If frequencies of the transient case to be simu

    lated are higher than 3 kHz, the simulation time is no longer

    than a few milliseconds and the machine is not close to any

    power

    electronic system (Le. a synchronous machine con

    nected to a transmission system), the mechanical part can be

    usually neglected and

    the machine

    can

    be represented by

    means of an ideal source behind its subtransient reactance

    and a frequency-dependent resistor; capacitance effects

    become important , they can be represented by a parallel

    capacitance-to-ground [1].

    Other representations should be considered for spe

    cific applications

    A) An

    aggregated

    representation of several

    machines can be used to reduce complexity and simulation

    time. Ref. [2] resents an aggregated induction model to be

    used in power quality studies where short term interruptions

    (i.e. sags) are

    of

    concern.

    B) A very simplified representation for synchronous

    and induction machines

    can

    be

    used

    in harmonic studies

    when the machine is not directly connected to the harmonic

    source [3].

    An important aspect of the simulation of a rotating

    machine is the procedure to obtain machine parameters and

    the information where these parameters are derived. Electri

    cal

    parameters of

    synchronous machines

    may usually

    be

    obtained in one of the following forms: (1) data supplied

    from manufacturer (conventional stability format data, stand

    still frequency response), (2) data from field tests (on-line

    frequency response, load rejection test, other tests) and (3)

    computer calculation using the finite-element method [4]. A

    good discussion about methods to obtain electrical and also

    mechanical parameters can be found in [5]. Data from steady

    state and short circuit tests include reactances and time con

    stants, armature resistance as well as saturation effects. Sev

    eral procedures have been proposed to pass from these data

    to electrical parameters which are used in the transient solu

    tion of the machine [6-8]. Although these tests and the corre

    sponding procedures can also be used to obtain electrical

    parameters

    of

    an induction machine, data conversion proce

    dures for this type of machines are performed from different

    specifications [9-10].

    Frequency response tests have received much atten

    tion during the last 25 years. Several methods have beenpro

    posed to obtain parameters of d-

    and

    q-axis

    equivalent

    circuits; they are based on standstill frequency response

    (SSFR) [11-14], and on-line frequency response [15-16].

    Some techniques have also been developed to account for

    saturation effects [17].

    4.5. VoltageSource InverterBased FACTSDevices and their

    Modeling Techniques Using EMTP

    This section describes the fundamentals

    and

    the

    modeling techniques of VoltageSource Inverter-based Flexi

    ble lternating Current Transmission Systems

    (FACTS)

    devices, namely, STATic synchronous COMpensator (STAT

    COM),

    Static Synchronous Series Compensator

    (SSSC), and

    Unified Power Flow Controller (UPFC) using an EMTP sim

    ulation package. The FACTS model includes all the neces

    sary components - a voltage source inverter with a DC link

    capacitor, a magnetic circuit, and a realizable controller. The

    UPFC model consists of two solid-state

    voltage

    source

    inverters which are connected through a common DC link

    capacitor. Each inverter is coupled with a transformer at its

    output. The first voltage source inverter,

    known

    as STAT

    COM, injects an almost sinusoidal current, of variable mag

    nitude, at the point of connection. The second voltage source

    inverter, known as SSSC, injects an almost sinusoidal volt

    age, of variable magnitude, in series with the transmission

    line. When the STATCOM and the SSSC operate as stand

    alone devices, they exchange almost exclusively reactive

    power at their terminals. While operating both the inverters

    together as a UPFC, the injected voltage in series

    with

    the

    transmission line can be at any angle with respect to the line

    current. The exchanged real

    power

    at the terminals of one

    inverter

    with

    the line f lows to the terminals of the

    other

    inverter through the common DC link capacitor. The func

    tionalities of the models have been verified.

    4.5.1 VSI BasedFacts Devices

    Flexible Alternating Current Transmission Systems

    (FACTS) devices, namely STATic synchronous COMpensa

    tor

    (STATCOM),

    Static Synchronous Series Compensator

    (SSSC) and

    Unified Power Flow Controller

    (UPFC), are

    used to control the power flow through an electrical transmis

    sion line connecting various generators and loads at its send

    ing and receiving ends. Each of the STATCOM and the SSSC

    consists

    of

    a solid-state voltage source inverter with several

    Gate Tum

    Off

    (GTO) thyristor switch-based valves and a DC

    link capacitor, a magnetic circuit, and a controller. The num

    ber

    of

    valves and the various configurations

    of

    the magnetic

    circuit depend on the desired quality of AC waveforms gen

    erated by the FACTS devices. When the STATCOM and the

    SSSC operate as stand-alone devices, they exchange almost

    exclusively reactive power at their terminals. While operat

    ing

    both

    the inverters

    together

    as a UPFC, the

    exchanged

    powerat the terminals of each inverter can be reactive as well

    as real. The exchanged line flows to the terminals of the other

    inverter through the common DC link capacitor. The objec

    tive in this section is to describe each component, such as a

    voltage source inverter, a magnetic circuit, and a controller

    of

    FACTS devices and its modeling techniques using an EMTP

    simulation package. Since, the emphasis

    of

    modeling is

    purely on FACTS devices,

    the power

    system in

    which

    the

    FACTS devices are connected to has been modeled in a sim-

    2-13

  • 7/21/2019 TR7 TP133 Full Content Part1

    39/100

    Fig.40 A Static

    Synchronous

    SeriesCompensatorModelin EMTP

    sssc

    12=

    _

    ~ ~ i i

    v, i;

    - ES22

    E, -

    1DC2 ES2

    -

    VSI2

    t.Cl

    C 9 r t r : ' o l

    ~

    plistic way. A simple transmission line, shown in Fig. 39, has

    an inductive reactance, X

    s

    and a voltage source V

    s

    at the

    sending end and an inductive reactance, X,., and a voltage

    source.P, at the receiving end, respectively. The STATCOM

    is connected at BUS 1

    of

    the transmission line as shown in

    Fig. 39 . The STATCOM model in EMTP consists

    of

    a har

    monic neutralized voltage source inverter,

    VSIl,

    a magnetic

    circuit,

    MCI

    a coupling

    transformer

    ,

    TI

    a mechanical

    switch, MS I , current and voltage sensors, and a controller.

    The STATCOM injects an almost sinusoidal current at the

    point

    of connection .

    This injected

    current is

    almost

    in

    quadrature with the line voltage, thereby emulating an induc

    tive reactance or a capacitive reactance at the point of con

    nection. To achieve the basic function

    of

    a STATCOM, the

    inverter is operated by regulating the reactive current flow

    through it.

    BUS1

    ii,

    Fig. 39A StaticSynchronous Compensator Modelin

    EMTP

    The UPFC which is connected to the simple trans

    mission line is shown in Fig. 41. The UPFC model in EMTP

    consists of two harmonic neutralized voltage source invert

    ers, VSIl and VSI2, two magnetic circuits, MCI and MC2 ,

    two

    coupling transformers

    ,

    Tl

    and

    T2,

    four mechanical

    switches ,

    MSI

    MS2, MS3, andMS4, two electronic switches,

    ES2 and ES22, current and voltage sensors, and a controller.

    The voltage source inverters are connected through a com

    mon DC link capacitor.

    In

    a basic operation of a UPFC, the

    STATCOM is operated by regulating the reactive current

    flow through it and the SSSC is operated by injecting a volt

    age in series with the transmission line.

    Fig. 40 shows an SSSC connected in series with the

    simple transmission line between BUS 1 and BUS 2. The

    SSSC model in EMTP consists of a harmonic neutralized

    voltage source inverter, VSI2, a magnetic circuit, MC2, a

    coupling transformer, T2, a mechanical switch, MS2, two

    electronic switches,

    ES2

    and

    ES22,

    current and voltage sen

    sors, and a controller. The SSSC injects an almost sinusoidal

    voltage, of variable magnitude, in series with the transmis

    sion line. This injected voltage is almost in quadrature with

    the line current, thereby emulating an inductive reactance or

    a capacitive reactance in series with the transmission line.

    ii,

    UPFC

    12=

    _ ~ ~ i i

    v, i;

    - ES22

    E,. -

    . ES2

    'DC2

    MS3

    -

    P.C1

    VSl1 MS4\ISI2 t.Cl

    C Q n t r : Q I

    Fig. 41A UnifiedPowerFlowController Modelin EMTP

    4.5.2 DESCRIPTIONOF THE INVERTER

    Fig.

    42 shows a single phase

    inverter

    circuit,

    referred to as a 3-level pole, which consists of a positive

    valve, A+, a negat ive valve, A-, and an AC valve , AAC '

    When a pole is connected across a series of capacitors which

    are charged with a total DC voltage of vDC and the valves are

    closed and opened alternately, the pole output voltage, v

    AD,

    at the midpoint of the pole A with respect to the midpoint, 0,

    2-14

  • 7/21/2019 TR7 TP133 Full Content Part1

    40/100

    (1)

    N

    InverterOEF

    -300

    .

    3 0

    o

    E

    VE,1

    V0,1

    Vx

    x

    r---o:-

    Vy

    MAGNETIC

    y

    f c:>

    -

    ORCUIT

    r

    Vz

    B lJc

    zf--c:>-

    A l

    VC,1

    VA,1

    . 5 V a : : ~

    o

    O . 5 V a : : ~

    Fig. 44 shows two 6-pulse inverters (ABC and DEF)

    which are operated from the same DC link capacitor. On the

    AC side, they are connected to a 3-phase load (XYZ) through

    a magnetic circuit. The poles D, E, and F are operated in such

    a way t ha t th e pole voltage fundamental phasors

    VE,

    1,

    Ve,1

    and

    VF,1

    and are 120 apart and the funda

    mental voltage phasor set

    of

    the DEF inverter lags the funda

    mental voltage phasor set of the ABC inver ter by 30. The

    displacement angle between two consecutive 6-pulse invert

    ers in a multipulse inverter arrangement is 21t

    /6m,

    where

    m

    is

    the total number

    of

    6-pulse inverters used. The configuration

    of the magnetic circuit in Fig . 44 is

    such

    that if an inverter

    pole voltage is time shifted by an angle of -e, the fundamen

    tal and all the harmonic components of the pole voltage get a

    phase shift by an angle of +e in the positive direction, irre

    spective of their sequence.

    Fig.44 A 12-Pulse HarmonicNeutralized InverterConfiguration

    with3-Level poles

    VNO consists of only a fundamental component and odd har

    monic components

    n)

    given by the equation (1) where

    n

    =6k

    1 for k =1,2,3, etc.

    2

    fA

    n = n7/

    DC

    ccsn):

    where

    y

    is the

    dead

    period during which the AC

    valve operates in each quarter cycle and the pole output volt

    age is zero and n=2k

    +

    1 for k =0, 1, 2, 3, etc. For

    y

    =0, the

    fundamental as well as all the harmonic components have the

    highest possible amplitudes.

    Fig. 42 A 3-Level Inverter Pole and itsOutputVoltage

    The amplitude

    of any

    odd multiple

    of

    fundamental compo

    nent is

    At- c=a:cJ

    aT

    3 Levellnverter

    Pole I>r

    aT

    W

    A ,cNJ

    aT

    rav

    aT

    COl

    O . 5 v o c ~ At-

    o

    o 5 v < t : ~

    7 t

    , Vf (j 1t-l'y Y

    . 5 v o c

    I>r

    1

    VIC Oy

    1t - ( 1 t .

    ..{ .

    5v

  • 7/21/2019 TR7 TP133 Full Content Part1

    41/100

    ing

    output

    voltage exhibits a fundamental

    component

    and

    odd harmonic components n) given by

    the

    equation

    (1)

    where

    n

    = 12k

    1 for

    k =

    1, 2, 3, etc. Note tha t the output

    voltage of a 12-pulse inverter with 3-level poles is referred to

    as a 12-pulse

    waveform

    when

    the poles are operated

    with

    dead angle

    y

    =

    o.

    Fig. 45 shows a possible configuration of the mag

    netic circuit

    which can

    be

    used

    to generate a 12-pulse har

    monic neutralized voltage. The ABC 6-pulse inverter voltage

    is fed to a

    Y-Y

    transformer and

    the

    DEF

    6-pulse

    inverter

    voltage

    is fed to a

    Y

    transformer.

    The

    inverter

    s ide A

    winding and

    DE

    winding

    wil l have

    pe r tum

    fundamental

    component voltages which

    are of

    same magni tude and

    in

    phase and

    the fif th

    and

    the seventh harmonic components

    each of which are of same magnitude but in opposite phase.

    Therefore, if the l ine side of the transformer windings are

    connected in series, the phase-X voltage will exhibit only a

    fundamental component and 12-pulse harmonic components.

    Note that the inverter side ( winding has

    J

    times the turns

    as the inverter side

    Y

    winding has. This is needed in order to

    keep the same volts

    per

    turn in both windings. The line side

    inverter windings

    can

    have any turns ratio other than 0.5 to

    increase or decrease the output voltage.

    component and odd harmonic components n)where n

    =

    12k

    1 for

    k

    =1, 2, 3, etc. The presence of 12-pulse harmonic

    components in the inverter output voltage may not be accept

    able in many applications.

    Therefore,

    an inverter with a

    higher pulse output voltage should be considered [56-58].

    4.5.3 MODELING TECHNIQUE

    ig. 46 shows the block diagram

    of

    the

    EMTP

    simu

    lation

    program

    layout.

    Sample EMTP program

    files

    are

    given in [56-58]. First, some general constants are defined.

    Next, the control or the Transient Analysis of Control Sys

    tems (TACS) section receives its input signals from the sen

    sors or measuring switches. This section generates the gating

    signals for the pole valves on the fly. The ideal pole volt

    ages are mathematically combined to produce

    harmonic

    neu

    tralized

    inverter

    voltages, eI,

    which

    are fed to the

    source

    section. In an actual simulation case, the gating signals are

    used to operate the pole valves of an inverter structure such

    as the one shown in Fig. 42.

    IGeneral

    Qlnsta1Is

    I

    n

    timeshift

    phase

    final time shift phase

    final

    shift phase

    shift

    phase

    pole A

    angle

    poleD

    angle

    5

    -5*(0)

    0

    0

    -5*

    -1tI6

    +1t/6 1t

    7

    +7*(0)

    0

    0

    +7*-1tI6

    +1t/6 1t

    11

    -11*(0)

    0

    0

    -11*(

    -1tI6

    +1t/6

    0

    13

    +13*(0)

    0

    0

    +

    I3*(-1tI6) +1tI6

    0

    17

    -17*(0)

    0

    0

    -17*

    -1tI6

    +1tI6 1t

    19

    +19*(0)

    0

    0

    +19*(-1t/6 +1t/6

    1t

    23

    -23*(0) 0

    0

    -23*(

    -1t/6

    +1t/6

    0

    25

    +25*(0)

    0

    0

    +25* -1tI6) +1t/6

    0

    Table 1 PhaseAnglesof a 12-PulseInverter Phasors

    ConboI/TACS

    Brmch

    Transnission

    Li1e

    Tn ISformeI

    Solrnes

    T

    oobo ed

    .1CIepeI1dert

    Inverter

    Voltages

    Fig.45 A Magnetic Circuitfora

    12-Pulse Harmonic

    Neutralized In

    verter

    The 12-pulse inverter configuration, shown in Fig.

    45, presents a 3-phase voltage which contains a fundamental

    Fig. 46 EMTP Modeling Structure

    Each valve,

    located

    in the switch section, can be

    modeled with a number of

    GTO

    thyristors connected in

    series

    each

    having

    an

    antiparallel diode

    and appropriate

    snubber circuits. The pole output voltages are fed to a mag

    netic circuit, located in the branch section, which produces a

    3-phase vol tage set. In this way, the effects of a

    nonideal

    magnetic circuit, which includes leakage reactance, magnetic

    saturation, etc.

    can

    be studied. However , in this paper, the

    valves and the magnetic circuit are assumed to be ideal. The

    voltage, vDC across the DC link capacitor is maintained by

    the power balance equation at both

    AC

    and

    DC

    sides of

    the

    inverter. This modeling technique gives sufficient insight to

    the operation of the power circuit which produces a 3-phase

    voltage set. The source section has some independent volt

    age sources which establish the power flow in a transmission

    ri

    VF

    Ve

    Vx

    Vo

    Vy

    VA

    Vz

    VB

    Vc

    2-16

  • 7/21/2019 TR7 TP133 Full Content Part1

    42/100

    line. Next, the control led and the independent sources are

    fed to the branch section which contains the transmission line

    and

    the

    coupling transformer

    .

    The

    l ine voltage set,

    vb

    at

    BUS 1, the inverters' current sets, i

    l

    and i

    2

    , and the line cur

    rent,

    i,

    are measured by the measuring switches. Finally, the

    output section is defmed.

    In

    reality, the magnetic circuit can

    also serve as the coupling transformer. Therefore, there is no

    need for an additional coupling transformer.

    The

    modeling

    may

    be done at various levels.

    For

    example, to study the functionality of a FACTS device on an

    elaborated

    power system

    network, a FACTS device with a

    simplified model consisting of sinusoidal voltage sources and

    detailed control

    and

    protection

    schemes may

    be adequate.

    For magnetic circuit and valve designers, the primary focus

    should be on the modeling of the detailed power circuit. The

    modeling techniques described in this section are useful tools

    to the FACTS designers.

    The

    various control techniques

    of

    FACTS devices

    and simulation results are described in the next section. In

    each case, an instantaneous 3-phase set

    ofline

    voltages,

    vI>

    at

    BUS 1 is

    used

    to calculate the reference angle, e

    which

    is

    phase-locked to the phase

    a

    of the line voltage, Via'

    A. STATCOM

    The controller of a STATCOM is used to operate the

    inverter

    in

    such

    a

    way tha t

    the phase angle

    between the

    inverter voltage and the line voltage is dynamically adjusted

    so that the STATCOM generates or absorbs desired VAR at

    the point of connection [56]. Fig. 47 shows the control block

    diagram of the STATCOM. An instantaneous 3-phase

    calculated by

    adding

    the

    relative

    angle, 0. , of the

    inverter

    voltage

    and

    the

    phase-lock-loop

    angle

    ,

    e. The

    reference

    quadrature component,

    h

    q

    .,

    of the inverter current is defined

    to be either positive i f the STATCOM is emulating an induc

    tive reactance or negative

    i f

    it is emulating a capacitive reac

    tance. The DC

    link

    capacitor voltage, VDC, is dynamically

    adjusted in relationship with the inverter voltage.

    The

    con

    trol scheme used in this section shows the implementation of

    the inner current control loop

    which

    regulates the reactive

    current flow through the inverter regardless

    of

    the line volt

    age. However, if one is interested in regulating the line volt

    age, an outer voltage control loop must be implemented. The

    outer voltage control loop will automatically determine the

    reference reactive current for the inner current control loop

    which, in turn, will regulate the line voltage.

    Fig. 48 shows the digital simulation results from the

    reactive current control operation of

    a STATCOM. Between

    o

    and 50 ms, the mechanical switch,

    MSJ,

    stays open, discon

    necting the STATCOM from the transmission line .

    The

    DC

    link capacitor is precharged. The inverter output 12-pulse

    voltage

    of

    phase a, el

    a,

    and the line voltage

    of

    phase a,

    Via,

    are in phase. At 50 ms, MSJ closes and the quadrature cur-

    rent

    demand, h

    q

    , of the invert er is set to zero. Since the

    inverter current is zero, the inverter voltage of phase a, el

    a

    ,

    and the line voltage of phase a, Via, have equal amplitudes.

    At 125

    ms, the

    quadrature

    current demand

    , Il q

    ,

    of the

    inver ter is set to one per

    unit

    capacitive, which

    means

    the

    STATCOM

    should see

    the

    system

    as an

    inductive

    reac

    tance and the inverter current of

    phase a,

    i la , lags the l ine

    voltage

    of

    phase

    a,

    Via, by almost 90

    0

    .

    Gale

    PatIem

    1...cJge

    V,A

    (PU)

    1

    -1

    1

    I

    I

    I

    I

    I

    V1 I

    I

    I I

    Fig. 47 Control BlockDiagram

    ofa

    Static Synchronous Compensa

    tor

    set of measured inverter currents,

    iJ,

    is decomposed

    into its real or direct component, hd, and reactive or quadra

    ture component,

    h

    q

    , respectively. The quadrature compo-

    nent is compared with the desired rference value,

    h

    q

    ,

    and

    the error is passed through an error amplifier which produces

    a relative angle, 0. , of the inverter voltage with respect to the

    line voltage. The phase angle, eJ, of the inverter voltage is

    -1-

    Fig. 48 Performance of a Static Synchronous Compensator witha

    12-Pulse

    Harmonic

    Neutralized InverterOperating inCapacitive and

    Inductive

    Modes

    2-17

  • 7/21/2019 TR7 TP133 Full Content Part1

    43/100

    B. SSSC

    Fig.49 Waveformsfroma StaticSynchronous Compensator witha

    12-PulseHarmonicNeutralizedInverterOperatinginCapacitiveand

    InductiveModes

    Fig.50 ControlBlockDiagramofa StaticSynchronousSeriesCom

    pensator

    I

    I

    I

    I

    I

    V1

    I

    I

    I I

    inverter in such a way that the injected alternating voltage in

    series with the transmission line is proportional to the line

    current with the

    emulated

    reactance

    being

    the

    constant

    of

    proportionality [57].

    When

    an SSSC injects an alternating

    voltage

    leading

    the l ine current , it

    emulates

    an

    inductive

    reactance in series

    with

    the

    transmission

    line

    causing

    the

    power flow as well as the line current to decrease as the level

    of compensation increases and the SSSC is considered to be

    operating in an inductive mode. When an SSSC injects an

    alternating voltage

    lagging

    the l ine current , it

    emulates

    a

    capacitive reactance in series with the transmission line caus

    ing the power flow as well as the line current to increase as

    the level

    of

    compensation increases and the SSSC is consid

    ered to be operating in a capacit ive mode. An SSSC control

    ler can also be used for stable reversal of

    power

    flow in the

    transmission line.

    Fig. 50 shows a control block diagram of an SSSC.

    An instantaneous 3-phase set

    of

    measured line currents, i, is

    first decomposed into its real or direct component,

    Id, and

    reactive or quadrature component,

    I

    q

    , and then the amplitude,

    I, and the relative angle, 0

    in

    of the line current with respect

    to the phase-lock-loop angle, E>, are calculated. The phase

    angle, E>;, of the line current is calculated

    by

    adding the rela-

    tive angle,

    E>ir of

    the line current and the phase-lock-loop

    angle, 0.

    The

    calculated amplitude,

    I,

    of the l ine

    current

    *

    multiplied by the compensating reactance demand,X

    q

    ,i s the

    *

    insertion voltage amplitude demand,

    V

    q

    . The phase angle,

    0 of this insertion voltage demand is either 0

    i

    +900 if the

    demanding compensating reactance is inductive or

    0;-90

    if

    the demanding compensating reactance is capacitive.

    The

    DC link capacitor voltage is dynamically regulated in rela

    t ionship with the insertion voltage amplitude demand. The

    *

    insertion voltage amplitude demand, V

    q

    ,and the DC link

    *

    capacitor voltage demand,

    V

    DC , are related by the inverter

    DC-to-fundamental AC amplitude gain factor

    K;nv = 2/n

    for

    a true harmonic netralized voltage source inverter). The DC

    250

    tine

    (ms)

    -1

    -1

    1-

    Fig. 49 shows the expanded view of two sections of

    Fig. 48. The inverter voltage and current show the presence

    of

    12-pulse harmonic components.

    The inverter voltage set,

    el ,

    is greater than the line

    voltage set,

    VI.

    At 175 ms, the quadrature current demand,

    *

    IIq

    , of the invert er is set to one

    per unit

    inductive,

    which

    means the STATCOM should

    see

    the system as a capaci

    tive reactance and the inverter current in phase

    a,

    i la, leads

    the line voltage at phase

    a, VIa,

    by almost

    90.

    The inverter

    voltage set,

    el ,

    is less than the line vol tage set, VI. At 250

    *

    IDS,

    the quadrature current demand,

    IIq ,

    of

    the inverter is set

    to one

    per

    unit capacit ive and the transit ion takes place in a

    subcycle time.

    The phase

    angle, a, between the

    inverter

    voltage and the line voltage is dynamically adjusted so that

    the inverter maintains proper DC link capacitorvoltage.

    V,A

    (pu)

    1-

    An SSSC controller uses a solid-state voltage source

    inverter to inject an

    almost

    sinusoidal voltage, of variable

    magnitude, in series with a transmission line. This injected

    voltage is almost in quadrature with the line current. A small

    part of

    the injected vol tage which is in phase with the l ine

    current provides

    the

    losses

    in

    the

    inverter.

    Most

    of

    the

    injected voltage which is in quadrature with the line current

    emulates an inductive or a capacitive reactance in series with

    the

    transmission

    line.

    This

    emulated variable

    reactance,

    insertedby the injected voltage source, influences the electric

    power flow in the transmission line.

    If

    an SSSC is operated

    with

    an

    energy

    storage system, the controller

    becomes

    an

    impedance compensation controller which can compensate

    for the transmission line resistance as well as reactance. The

    reactance

    compensation controller is used to

    operate

    the

    2-18

  • 7/21/2019 TR7 TP133 Full Content Part1

    44/100

    *

    link capacitor voltage demand,

    VDC ,

    and the measured DC

    voltage, VDC, are compared and the error is passed through an

    error amplifier which produces an angle, p. The phase angle,

    02, of the inverter voltage is calculated by adding the angle,

    p, of the DC voltage regulator and the phase angle, 0\1> of the

    insertion voltage demand. The compensating reactance

    *

    demand,

    X

    q

    , is either negative

    if

    the SSSC is emulating an

    inductive reactance or positive i f it is emulating a capacitive

    reactance. In

    another

    application, the insertion voltage

    *

    amplitude demand, V

    q

    may directly be specified and the

    SSSC will inject the desired voltage almost in quadrature

    with the line current.

    neous DC link capacitor voltage is proportional to the ampli

    tude of the inverter voltage.

    Therefore, when an SSSC emulates a reactance in

    series with the transmission line, the power flow in the trans

    mission line always decreases

    if

    the emulated reactance is

    inductive. Also, the power flow always increases if the emu

    lated reactance is capacitive.

    Fig. 52 shows the expanded view

    of

    the two sections

    of

    Fig.

    51. The inverter voltage show the presence

    of

    24-pulse har

    monic components.

    2-

    V,A,X,P

    1 - ~ ~ P

    PU)

    /i

    a

    1

    ~ ~ ~

    - q

    0

    P

    q

    1-

    -1

    *

    q

    X

    q

    tiTle

    -2-

    I

    (ms)

    200

    400

    600

    Fig. 51 Performance of a Static Synchronous Series Compensator

    with a 24-Pulse Harmonic Neutralized Inverter Operating in Induc

    tive and Capacitive Modes

    Fig. 51 shows the digital simulation results when an

    SSSC emulates a reactance in series with the transmission

    line. At the beginning

    of

    the operation, the mechanical

    switch,

    MS2,

    and the electronic switch,

    S22,

    are open and

    the electronic switch, S2, is closed. The inverter, VSI2,

    injects no voltage. The DC link capacitor voltage, VDC, is

    zero. At 50 ms, an inductive reactance compensation

    of

    0.15

    per unit is requested. The inverter output 24-pulse voltage,

    e2a,

    of phase a leads the line current, i

    a

    ,

    by almost 90

    0

    . At

    175 ms, the inductive reactance demand is increased to 0.3

    per unit. As the inductive reactance demand increases, the

    line current, i

    a

    , and the power flow, Pq and

    Qq,

    in the trans

    mission line decrease. At 300 ms, a capacitive reactance

    compensation

    of

    0.1 per unit is requested. The inverter volt-

    age,

    e2a,

    lags the line current,

    i

    a,

    by almost 90

    0

    .

    At 450 ms,

    the capacitive reactance demand is increased to 0.15 per unit.

    As the capacitive reactance demand increases, the line cur

    rent, i

    a

    , and the power flow, Pq and Qq, in the transmission

    line increase. In reality, the SSSC would encounter power

    losses in the valves and in the magnetic circuit. Therefore,

    there will always be a small part of real current component,

    lId, flowing into the inverter and the inverter voltage will be

    almost 90

    0

    out of phase with the line current. The instanta-

    Fig. 52 Waveforms from a Static Synchronous Series Compensator

    with a 24-Pulse Harmonic Neutralized Inverter Operating in Induc

    tive and Capacitive Modes

    C. UPFC

    The stand alone operations

    of

    the STATCOM and

    the SSSC, as just described,

    only allow

    the inverters to

    exchange almost exclusively reactive power at their termi

    nals. However, ifboth the inverters are operated from a com

    mon DC link capacitor, the injected voltage by the SSSC can

    be at any angle with respect to the line current. The real

    power exchanged at the terminals of the SSSC appears at the

    terminals

    of

    the STATCOM through the DC link capacitor.

    The STATCOMcan still be used to control the reactive cur

    rent flow through it independently [58]. The current injected

    by the STATCOM has two components. First, a real or direct

    component, which is in phase with the line voltage, absorbs

    or delivers the real power exchanged by the SSSC with the

    line. Second, a reactive or quadrature component, which is

    in quadrature with the line voltage, emulates an inductive or

    a capacitive reactance at the point

    of

    connection with the

    transmission line.

    The SSSC can be operated in many different modes,

    2-19

  • 7/21/2019 TR7 TP133 Full Content Part1

    45/100

    i

    a

    1

    -1-

    Fig. 55 shows the expanded view of two sections of

    Fig. 54. The inverter voltage and current show the presence

    of

    harmonic components.

    Fig. 54 Performance of a Unified PowerFlowControllerwith a 24

    PulseQuasi Harmonic Neutralized Inverterwith3-LevelPolesOp

    eratingin a VoltageInjectionMode

    At the beginning

    of

    the operation, the mechanical

    switch, MS2, and the electronic switch, ES22, are open and

    the electronic switch,

    ES2,

    is closed. The inverter,

    VSI2,

    injects no voltage. The voltage , VIZa, at the terminals of the

    coupling transformer, T2, is the voltage across its leakage

    reactance. The mechanical switch,MSI , is open, disconnect

    ing the STATCOM from the transmission line. The DC link

    capacitor is precharged. At 50 ms , MSI closes and the

    quadrature current demand, Il q

    ,

    of the inverter is set to zero.

    At 100 ms, a series voltage injection

    of

    0.2 per unit at an

    angle of 60

    0

    leading the reference phase-lock-loop angle is

    requested. The series inverter output voltage, ez

    a

    , of phase a

    leads the line current, i

    a

    , by an angle o. The real power

    absorbed by the series inverter appears at the BUS 1 through

    the STATCOM. The shunt inverter output voltage, el

    a

    ,

    of

    phase a is in phase with the current, ;I a, flowing through it.

    The power delivered at the receiving end decreases. At 175

    ms, the injected voltage request is increased to 0.4 per unit

    while maintaining the same angle. As the voltage injection

    demand increases, the line current, i

    a

    , and the power flow, P,

    and Q in the transmission line decrease. By injecting a volt

    age by the SSSC

    of

    any magnitude, within the rating

    of

    the

    inverter, and at any angle with respect to the line current, the

    real power,

    P,.,

    and the reactive power, Q at the receiving

    end of the transmission line can be increased, decreased or

    even reversed selectively.

    ime

    (ms)

    Va:

    P- t-

    - - - - - --,

    V,A

    ,P,Q

    (pu)

    1

    t - ~ : : - - - - - - - - - - . : . . . . A - - - - - ~

    1

    *

    Vd:I

    Fig. 53 ControlBlockDiagram

    ofa

    StaticSynchronous SeriesCom

    pensator

    Fig. 54 shows the digital simulation results from the

    voltage injection mode of operation

    of

    an SSSC while the

    STATCOMis operated to deliver no reactive current.

    vo:;

    t

    such as voltage injection, phase angle shifter emulation, line

    impedance emulation, automatic power flow control, etc. In

    each mode

    of

    operation, the final outcome is such that the

    SSSC injects a voltage in series with the transmission line

    [58]. In this section, the SSSC is operated in a voltage injec

    tion mode. The control block diagram for the SSSC is shown

    in Fig. 53.

    The desired peak fundamental voltage , Vdq*, at the

    output

    of

    the inverter and its relative angle,

    P,

    with respect to

    the reference phase-lock-loop angle are specified. The phase

    angle, 0z,

    of

    the inverter voltage is calculated by adding the

    relative angle, P, of the inverter voltage and the phase-lock

    loop angle ,

    0 .

    The dead angle

    of

    each pole is calculated in

    accordance with the operation of 24-pulse quasi harmonic

    neutralized inverter [58].

    -1-

    2-20

  • 7/21/2019 TR7 TP133 Full Content Part1

    46/100

  • 7/21/2019 TR7 TP133 Full Content Part1

    47/100

    13. A. Keyhani and H. Tsai, Identification

    of

    high-order

    synchronous generatormodels from SSFR test data , pre

    sented at the 1994 IEEE/PES Winter Meeting, Paper no.

    94 WM 022-4 EC, New York, January 30-February 3,

    1994.

    14. J. R. Willis, G. J. Brook and J. S. Edmonds, Derivation

    of induction motor models from standstill frequency re

    sponse , IEEE Trans. on Energy Conversion, vol. 4, no.

    4, pp. 608-615, December 1989.

    15. P. L. Dandeno, P. Kundur, A. T. Poray and H. M. Zein

    El-din, Adaptation and validation

    of

    turbogenerator

    model parameters through on-line frequency response

    measurements , IEEE Trans. on Power Apparatus and

    Systems, vol. 100, no. 4, pp. 1656-1645, April 1981.

    16. P.L. Dandeno, P.Kundur, A. T.Poray andM. E.Coultes,

    Validation of turbogenerator stability models by com

    parison with power system tests , IEEE Trans. on Power

    Apparatus and Systems, vol. 100, no. 4, pp. 1637-1645,

    April 1981.

    17. F. P. de Mello, L. N. Hannett, J. R. Willis, Determina

    tion

    of

    synchronous machine stator and field leakage in

    ductances standstill frequency response tests , IEEE

    Trans. on Power Systems, vol. 3, no. 4, pp. 1625-1632,

    November 1988.

    18. L. Dube, H.W. Dommel, Simulation

    of

    control system

    in an Electromagnetic Transient Program with TACS ,

    IEEE Trans. on Power Industry and Computer Applica

    tions, 1977

    rs, EMTP Rule Book, EPRIIDCG Version 1.0.

    20. D. Goldsworthy, 1. J. Vithayathil, EMTP model of an

    HVDC transmission system , Proceedings of the IEEE

    Montech '86 Conference onHVDC Power Transmission,

    September 26-0ctober 1, 1986, pp. 39-46

    21. L. X. Bui, S. Casoria, G. Morin, Modeling

    of

    digital

    controls with EMTP , CEA Meeting, March 25-29,

    1989, Montreal, Canada

    22. J. Reeve and S. P. Chen, Versatile interactive digital

    simulatorbased on EMTP for AC/DC power system tran

    sient studies , IEEE Trans. on Power Apparatus and Sys

    tems, Vol. 103,No. 12, December 1984, pp. 3625-3633

    23. K. G. Fehrle, R. H. Lasseter, Simulation

    of

    control sys

    tems and application to HVDC converters , IEEE Tuto

    rial Course 81 EHOI73-PWR on Digital Simulation

    of

    Electrical Transient Phenomena, 1981.

    24. L. X. Bui, G. Morin, J. Reeve, EMTP TACS-FOR

    TRAN interface development for digital controls model

    ing , 91 SM 417-6 PWRS

    25. G. Morin, L. X. Bui, S. Casoria, J. Reeve, Modeling of

    the Hydro-Quebec - New England HVDC system and

    digital controls with EMTP , IEEE Trans. on Power De

    livery, Vol. 8,No.2, April 1993, pp. 559-566.

    26. R. H. Lasseter and S. Y. Lee, Digital simulation

    of

    static

    var system transients , IEEE Trans. on Power Apparatus

    and Systems, Vol. PAS-I0l, No. 10, pp. 4171-4177, Oc

    tober 1982.

    27. A. M. Gole and V. K. Sood, A static compensator model

    for use with electromagnetic transients simulation pro

    grams , IEEE Trans. on Power Delivery, Vol. PWRS-5,

    No.3,

    pp. 1398-1407, July 1990

    28. A.N. Vasconcelos et. al. Detailedmodeling

    of

    an actual

    static Var compensator for electromagnetic transients

    studies , IEEE Trans. on Power Systems, Vol. PWRS-7,

    no. l,pp. 11-19, February 1992

    29. S.Y. Lee et aI., Detailedmodeling ofstatic Var compen

    sators using the Electromagnetic Transients Program

    (EMTP) , IEEE Trans. on Power Delivery, Vol. 7, no. 2,

    pp. 836-847, April 1992

    30. S. Lefebvre and L. Gerin-Lajoie, A static compensator

    model for the EMTP , IEEE PES Meeting, San Diego,

    July 28-August 1, 1991, Paper 91 SM 461-4 PWRS.

    31. L. Dube and I. Bonfanti, MODELS: A new simulation

    tool in the EMTP , European Transactions on Electrical

    Power Engineering, Vol. 2, no. 1, pp. 45-50, January/

    February 1992.

    32. Leuven EMTP Center (ed.),

    ATP Rule

    BOQk, 1990.

    33. J. A. Martinez, Simulation

    of

    a microprocessor-con

    trolled SVC , 21th European EMTP Meeting, June 5-7,

    1992, Crete (Greece).

    34. H.W. Dommel,

    EMTP Reference-Manual

    (EMIP

    Theo

    ry Book), BPA, 1986.

    35. J. A. Martinez, Simulation of power electronics using

    the EMTP, Part I: Power converters, A survey , UP

    EC'94, September 14-16, 1994, Galway.

    36. G. A. Capolino, H. Henao, ATP simulation for power

    electronics and AC drives , 15thEuropean EMTP Users

    Group Meeting, Paper 88R-027, October 17-18, 1988,

    Leuven.

    37. G. A. Capolino, H. Henao, Simulation

    of

    electrical ma

    chine drives with EMTP , 18th European EMTP Users

    Group Meeting, Paper M7, May 28-29, 1990, Marseille

    38. J. A. Martinez, G. A. Capolino, TACS and MODELS:

    Drive simulation languages

    in

    a general purpose pro

    gram , Proc. MCED'91, Marseille, July 1-2, 1991, pp.

    RI-RI3.

    39. G. A. Capolino, H. Henao, ATP advanced usage for

    electrical drives , EMTP Summer Course, July 5-8,

    1993,Leuven.

    40. H.Knudsen, ExtendedPark's transformation for 2 by 3

    phase synchronous machine and converter phasor model

    with representation

    of

    harmonics , IEEE PES Summer

    Meeting, Paper 94 SM 350-9 EC, July 24-28, 1994, San

    Francisco.

    41. M. Mazzucchelli, G. Sciutto, Digital simulation of AC

    electrical drives based on field-oriented control method

    using a general purpose program , Proceedings PCIM,

    pp.350-364, 1986, Munchen

    42. Z. Daboussi, N. Mohan, Digital simulation of field-ori

    ented control

    of

    induction motor drives using EMTP ,

    IEEE Trans. on Energy Conversion, Vol. 3, pp. 667-673,

    September 1988.

    43. L. Tang, M. McGranaghan, Modeling an active power

    line conditioner for compensation

    of

    switching tran

    sients , Proceedings of First International Conference on

    Power Systems Transients (IPST'95), Lisbon (Portugal),

    pp. 403-408.

    44. X. Z. Meng, J. G. J. Sloot, H. Rijanto, Modelling

    of

    semiconductor fuses in EMTP , Proceedings

    of

    First In

    ternational Conference on Power Systems Transients (IP

    ST'95), Lisbon (Portugal), pp. 481-486.

    45. J. A. Martinez-Velasco, R. Abdo, G.A. Capolino, Ad

    vanced representation

    of

    power semiconductors using the

    EMTP , Proceedings

    of

    First International Conference

    on Power Systems Transients (IPST'95), Lisbon (Portu

    gal), pp. 505-510.

    2-22

  • 7/21/2019 TR7 TP133 Full Content Part1

    48/100

  • 7/21/2019 TR7 TP133 Full Content Part1

    49/100

    Modeling Guidelines for Low Frequency Transients

    Report Prepared by the Low-Frequency Transients Task Force

    of the IEEE Modeling and Analysis of System Transients Working Group

    ContributingMembers: R. Iravani (Chair), A.K.S. Chandhury,

    I.D. Hassan, J.A. Martinez, A.S. Morched,

    B.A.Mork, M. Parniani, D. Shirmohammadi, R.A. Walling

    Abstract: The objective of this report is to provide guidelines

    for modeling and analyses of low-frequency (approximately 5 to

    1000

    Hz)

    transients of electric power systems, based on the use

    of digital time-domain simulation methods. For the ease of ref

    erence, the low-frequency transients are divided in seven dis

    tinct phenomena. This report (1) briefly describes the physical

    nature of each phenomenon, (2) identities those power system

    components/apparatus which either contribute to or ar e

    affected by the phenomenon, (3) provides guidelines for digital

    time-domain simulation and analyses of the phenomenon and

    (4) provides sample study-system and typical digital time

    domain simulation results corresponding to each phenomenon.

    A comprehensive list of reference is also included in this report

    to provide further in-depth information to the readers.

    Keywords: Low-Frequency Transients, Electromechanical

    Transients, Modeling, Time-Domain Analysis, Torsional

    Dynamics, Turbine Vibrations, Bus-Transfer, Controller

    Interactions, Harmonic Interactions, Ferroresonance

    1. INTRODUCTION

    An

    interconnected power system can experience undesirable

    oscillations and transients as a result

    of

    small-signal perturba

    tions, large-signal disturbances, and nonlinear characteristics

    of

    the system components. The oscillations cover a wide fre

    quency range approximately from 0.01 Hz to 50MHz. Oscil

    lations in the frequency range of 0.01 to 1000Hz are defmed

    in this report as low-frequency (slow) transients. We inter

    changeably use the terms slow transients , low frequen

    cy(LF) dynamics , and LF oscillations throughout this

    report. All the issues relevant to Iow-frequency inter-area

    electromechanical oscillations (approximately 0.1 to 1 Hz)

    and classical turbine-generator swing modes (approximately

    1 to 2.5 Hz) are discussed by other IEEE working groups, and

    are not discussed here. A general guideline for representation

    of network elements for electromagnetic transient studies

    have been previously published [1.1]. The mandate of the

    IEEE Low-Frequency Transients Task Force is to provide

    modelling guidelines for time-domain analysis ofLF oscilla

    tions within the frequency range

    of

    5 to 1000 Hz. Low fre

    quency dynamics are

    of

    concern with respect to power system

    stability issues and/or temporary overvoltages.

    phenomena of 60 Hz power systems in the LF range are di

    vided into the following categories:

    3-1

    l.Torsionaloscillations (5 to 120Hz)

    2.Transient torsional torques(5 to 120Hz)

    3.Turbine bladevibrations (90to 250Hz)

    4.Fastbustransfer(1 to 1000Hz)

    5.Controller interactions (10 to 30Hz)

    6.Harmonic interactions andresonances (60 to 600Hz)

    7.Ferroresonance

    (1

    to 1000

    Hz)

    For each of the above phenomenon this report provides (1) a

    brief explanation of the physical phenomenon, (2) modeling

    guidelines for time-domain simulation and analyses, and (3)

    typical sample systems and simulation results.

    This report is intended for practicing powersystem engineers

    who are involved in system analysis, system control, and sys

    tem planning. To use the report efficiently, adequate under

    standing

    of

    the physical phenomenon

    of

    interest and

    familiarity with the concepts and techniques

    of

    digital com

    puter simulation approaches are necessary.

    Section 2 of the report deals with low-frequency transients

    which involve both electrical and mechanical dynamics, i.e.,

    torsional oscillations, transient torsional torques, turbine

    blade vibrations and fast bus-transfer. Section 3 discusses

    low-frequency electrical dynamics, as a result

    of

    control sys

    tems interactions. Section 4 provides analysis guidelines for

    harmonic interactions and resonance phenomena. The phe

    nomenon

    of

    ferroresonance is discussed in Section 5.

    2. LOW-FREQUENCY ELECTROMECHANICAL

    DYNAMICS

    This section provides modeling and analysis guide

    lines for low-frequency dynamics which involve electrome

    chanical oscillations. The phenomena which are covered in

    this section are torsional oscillations, transient torques, tur-

  • 7/21/2019 TR7 TP133 Full Content Part1

    50/100

    bine-blade vibrations, and bus-transfer.

    2.1DEFINITIONS

    2.1.1 Torsional Oscillations [2.1, 2.2, 2.3, 2.4, 2.5J

    Shaft system

    of

    a steam turbine-generator experiences tor

    sional oscillations when one or more

    of

    its natural oscillatory

    modes, usually at subsynchronous frequencies, are excited.

    Sustained or negatively damped torsional oscillations occur

    when a turbine-generator shaft system exchanges energy with

    an electrical system at the shaft oscil latory modes. This ex

    change of energy can exist if the electrical system is equipped

    with eitherseries capacitors orHVDC converterstations. The

    phenomenon of torsional oscillations can also exist as a result

    of

    interaction between the shaft system of a steam turbine

    generator and

    the generator excitation systems through either AVR or PSS

    control loops,

    electronically controlled governor system,

    voltage control loop of an electricallyclose staticV

    AR.

    compen

    sator (SVC)

    large electric arc furnaces.

    AlthoughAVR, PSS and governor systemcan excite torsional

    oscillations, the excitation is primarily due to inadequate con

    trol design considerations and can be avoided by introducing

    filters in the control circuitry. Thus, this report does not con

    sider the generator controls as the main contributors to the

    phenomenon of torsional oscillations (Table 1).

    The phenomenon

    of

    torsional oscillation is referred to as sub

    synchronous resonance

    (SSR)

    when it is a result

    of

    interaction

    between a shaft system and a series capacitor compensated

    transmission line. The problems associated with the phenom

    enon of small-signal torsional oscillations are:

    i ) Sustained or even negatively damped oscillations which

    are considered as small-signal instability problems, and

    ii )

    (loss

    of

    life

    of

    turbine-generator shaft segment(s) due to the

    fatigue induced in the shaft segment(s) as a result of each

    oscillatory cycle.

    2.1.2 Transient Torsional

    Torques

    [2.1, 2.2, 2.3, 2.4, 2.5]

    The shaft segments of turbine-generator units are exposed to

    large-amplitude, oscillatory, mechanical stresses as a result of

    electric network faults, and planned and unplanned switching

    incidents. Frequencies of the shaft mechanical stresses are

    the natural frequencies of the shaft torsional oscil latory

    modes. Usually, the oscillatory mode at the first torsional fre

    quency dominates the shaft transient oscillations. The major

    incidents which resultin severe shaft stresses are: line-to-line

    faults, three-phase faults, fault clearing, automatic reclosures,

    and out-of-phase synchronization. The amplitudes of the

    shaft transient stresses can be particularly large when the net

    work is equipped with series capacitors.

    High amplitude shaft mechanical stress can induce significant

    fatigue in the shaft segments and result in not iceable shaft

    life-time reduction during each oscillatory cycle. Such oscil

    lations may even result in catastrophic shaft failure. The pri

    mary purpose of time-domain investigation of turbine

    generator shaft mechanical stresses is to identify the peak

    torques imposed on the shaft segments, after system distur

    bances. Transient shaft mechanical stresses calculated based

    on time-domain simulation methods also can be used to esti

    mate shaft loss of life as a result of system disturbances.

    2.1.3 Turbine-Blade

    Vibrations

    [2.6]

    Frequencies of turbine-blade vibrational modes are

    usual ly within 90 to 250 Hz,

    and

    constitute supersynchro

    nous frequency modes. Identification of supersynchronous

    frequency modes and their corresponding frequencies is best

    carried out by solving elasticity equation of the shaft system

    as a continuum, based on the use of finite element methods.

    This approach is beyond the scope of this report and usually

    carried out by turbine manufacturers.

    In

    this report, the objective is to investigate the impact of

    large-signal disturbances on those supersynchronous frequen

    cy natural modes which are the reason for turbine-blade vibra

    tions. Thus the required model is tailored to represent

    particular supersynchronous modes and not all

    of

    them.

    The concern with turbine-blade vibrations is fracture

    and loss-of-life of the blades due to the fatigue induced in the

    blades

    by

    repetitive or sustained oscillations. Vibrations

    of

    tur

    bine-blades can be excited by large-signal electrical distur

    bances, e.g. faults, fault clearing, line switching, reclosure, and

    out-of-phase synchronization.

    2.1.4FastBus Transfer

    [2. 7,2.8,2.9]

    Motors and other loads in utility and heavy industrial applica

    tions are supplied during normal operation from a preferred

    power source. An alternate power source is normally provid

    ed to supply such motors and other loads during planned shut

    downs and upon loss of normal power from the preferred

    power source. The process of disconnecting the motors and

    other loads from one source and reconnecting to an alternate

    source is commonly defmed as bus transfer . Manual trans-

    3-2

  • 7/21/2019 TR7 TP133 Full Content Part1

    51/100

    fer means are normally provided to allow transferring the mo

    tors and other loads from one power source to the other.

    However, upon loss of the preferredpowersource, the motors

    and other loads are automatically transferred to the alternate

    power source. This automatic transfer is necessary to allow

    uninterrupted operation of the motors and other loads impor

    tant to personnel safety and process operation. This report

    does not address the concept

    of

    bus transferby means of semi

    conductor switches [2.23].

    The normal and alternate power source connections are al

    ways selected such that they are in phase. Therefore, manual

    transfers can be accomplished in a make-before-break, i.e.,

    the motors and loads are connected to the second power

    source before the first power source is disconnected.

    In

    this

    overlapping transfer, the power supply is not interrupted and

    the motors are not subjected to transients. However, during

    automatic transfers, the motors may be disconnected from

    both power sources for a short duration depending on the type

    of

    transfer and the associated circuit breakers operating times.

    The time duringwhich the motors are disconnected from both

    power sources is termedthe dead time . Dead time is usually

    between two cycles to 12cycles.

    If

    the relative angle between

    the motor residual voltage and the power source voltage be

    comes large enough at the time

    of

    reconnection with signifi

    cant residual voltage remaining, the resultant voltage

    between the power source and the motor will produce an in

    rush current. The inrush current may be significantly largely

    than the normal full voltage staging current. Such high inrush

    currents cause high winding stresses and transient shaft

    torques which can damage the motor and/or the driven equip

    ment.

    The most common bus transfer scheme is the fast bus transfer

    scheme. In this scheme, opening of the normal power source

    breaker initiates closing

    of

    the alternate power source breaker

    without intentional time delay. Fast bus transfer operations

    result in the motors being disconnected from both power

    sources for a duration of as short as two cycles to as long as

    12 or more cycles.

    Presently,

    there

    are no

    generic criteria

    to

    ensure

    acceptable fast bus transfer operations. Therefore, it is nec

    essary to analyze the transient behavior

    of

    motors during fast

    bus transfer operations. The analysis should be on a case by

    case basis to ensure that the motors will not be subjected to

    excessive inrush currents and/or shaft transient torques.

    2.2 MODELING GUIDELINES

    2.2.1 Study Zone

    In contrast to an inter-area, electromechanical, oscillatory

    mode which propagates almost through the entire

    of

    an inter

    connected electric network, the phenomena described in Sec

    tion 2.1 are experienced only within a limited part of the

    network. The section of the network which experiences the

    phenomenon

    of

    interest, and

    must

    be represented in adequate

    detail for the study

    of

    the phenomenon, is referred to as the

    StudyZone The rest of the network is referred to as the ex

    ternal system The external system is represented by an

    equivalent model. Identification

    of

    border nodes

    of

    the study

    zone for a meshed network requires significant familiari ty

    with the network, as well as engineering judgment. As of

    now, there is no straightforward and systematic approach to

    identify the border nodes. One approach involves multiple

    harmonic analyses

    of

    the sys tem under investigation as

    boundaries are extended to identify

    if

    new resonant frequen

    cies (at the frequency range of interest) with low dampings ex

    ist.

    Proper determination

    of

    the study zone can exert a major im

    pact on the investigations of torsional dynamics and transient

    torques. Comparatively, the impact

    of

    the study zone on the

    vibrations of turbine blades is less significant. Identification

    of the study zone for bus transfer studies is relatively straight

    forward.

    2.2.2 Component Model

    Table 1 identifies the study zone components and their equiv

    alent models for investigations of slow transient phenomena.

    Further explanation of the system components are given in the

    following sections.

    2 2 2 1 Synchronous Generator Electrical System [2 lOJ

    Figure 2.1 shows a second-order and a third-order

    models of a synchronous machine. Inclusion

    of

    the differen

    tialleakage

    inductance Lfld in the second-order model is

    recommended.

    The different ial leakage inductance has

    noticeable influence on the damping, and the range

    of

    insta

    bility of

    each torsional mode, (with respect to series compen

    sation

    level), particularly

    fo r

    a salient

    pole

    machine.

    However, Lfld does not influence the phenomenon

    of

    blade

    vibrations.

    Representation of machine electrical system based on

    the third-order model, Fig.

    2.1,

    is more accurate. Inclusion

    of

    the differential leakage inductance

    Lf 2d

    in the third-order

    model has the same impact as that

    of

    Lf l

    d

    for the second-order

    model. Magnetic saturation of a synchronous machine, both on

    d-axis and q-axis, does not have any significant impact on the

    phenomenon of small-signal torsional oscillations, but has pro-

    3-3

  • 7/21/2019 TR7 TP133 Full Content Part1

    52/100

    Component

    Torsional

    Transient

    Turbine-Blade

    Fast Bus

    Oscillations

    Torques

    Vibrations

    Transfer

    Synchronous

    Second-Order

    Third-Order

    Third-Order Model

    Not

    Genera tor's

    Model and

    Model (d-q-o

    (d-q-o Model)

    applicable

    Electrical System

    Preferably Third-

    Model)

    Including

    Order

    Model (d-q-o Including Saturation

    Model)

    Saturation

    Turbine-Generator

    Mass-Spring-

    Mass- Spring-

    Detail

    Not

    Shaft

    System Dashpot

    Model

    Dashpot Model Mass-Spring-

    Applicable

    Dashpot Model

    Power

    Conventional

    Conventional

    Conventional

    Conventional

    Transformer

    Low-Frequency

    Low-Frequency

    Low-Frequency

    Low-

    Model including

    Model including

    Model including Frequency

    Saturation

    Saturation

    Saturation Model

    Characteristic

    Characteristic

    Characteristic including

    Saturation

    Characteristic

    Transmiss ion Line

    Equivalent-a

    Equivalent-a Equivalent-a

    Not

    Model

    Model

    Mo