TP48400B Installation Key Points

TP48400B (Indoor) Installation Key Points

I. Install power system cabinet.1) Fix it

II. Install cables1) Install grounding cables Connect to PGND screws on the cabinet and ground bus bar (outside the cabinet).

2) Install AC input cablesa. Install new MCB rectifier 3 pole 16 Ampere in ACPDB.b. Install power cable from MCB in ACPDB to MCB ac input in rectifier.

3) Install DC load cables 4) Install battery cables Install Battery Middle sensor to each group of battery. Must fasten the battery bolts.

5) Install the communication cablea. Connect RS485/RS232 port on the SMU to MON 0 port on BBU :

b. Connect RS485/RS232 port from EMUA to BBU on port MON 1 :

6) Install external alarm cables from DDF to EMUA board

7) Install Battery temperature sensorConnect signal cable of battery temperature sensor to port BTEMP on the UIM02C.

8) Powering On and Commissioning the TP48400B1) First, switch on rectifier MCB, check whether power system can run smoothly.2) Set SMU parameterIf need to enter password, input like this picture below :

Password: 000001

a. Battery capacity

Fill the battery capacity. Change to 170 Ah

b. Time and Date

1st Menu 2nd Menu 3rd Menu ValueSet time and date of installation, Time zone change to UTC +7. Follow the steps elow:

c. Battery charge current limit set to 0.10C10 or 10 %.

d. LLVD and BLVD settingSet LLVD value is 46 V and BLVD value 43.2 V. Follow the steps below:

1st Menu 2nd Menu 3rd Menu ValueLLVD setting ( 46 V ) :

BLVD setting ( 43.2 V ) :

1st Menu 2nd Menu 3rd Menu Value

e. Host communication address

III. Please find the SMU02B menu This menu can help us how to set SMU parameter step by step.

IV. Alarm Test Procedure

No.AlarmProcedure

1Main Power Switch off main MCB input rectifier

2Rectifier Module Plug off one PSU module

3TemperatureChange battery temp. protection to Reduce DC Voltage then heat the sensor

4PLVD DisconnectChange LLVD threshold from 46V up to Floating charge voltage. If already show alarm Warning LLVD disconnect, then directly set back to default threshold otherwise LLVD will disconnect the load.

5ArresterPlug off one pole of arrester fuse

6Rectifier Battery Switch off one of battery MCB

7Door OpenOpen and close the door cabinet

8Aviation LightSwitch off the MBC of aviation light

2015-3-78, 10

SMU02BMAIN MENU1st Menu2nd Menu3rd Menu4th Menu5th MenuValueActive alarm

Running InformationPower SystemBasic Information System VoltageTotal Load CurrentPhase L1 VoltagePhase L2 VoltagePhase L3 VoltagePhase L1 CurrentPhase L2 CurrnetPhase L3 CurrentAC Frequency

DO Control StatusALM1ALM2ALM3ALM4ALM5ALM6ALM7ALM8

RectifierRectifier GroupTotal Output CurrentTotal DC PowerLoad Usage

Rectifier 1Slot NoDC Output VoltageDC Output CurrentDC Output PowerAC Voltagereal-time Efficiencyrectifier temp.Run StatusHardware VersionSoftware VersionBarcode

Rectifier 2Slot NoDC Output VoltageDC Output CurrentDC Output PowerAC Voltagereal-time Efficiencyrectifier temp.Run StatusHardware VersionSoftware VersionBarcode

Rectifier 3Slot NoDC Output VoltageDC Output CurrentDC Output PowerAC Voltagereal-time Efficiencyrectifier temp.Run StatusHardware VersionSoftware VersionBarcode

BatteryBattery GroupBattery StatusTotal batt. CurrentRemain Cap. PercentCurrent Limit StatusTest StatusBattery Temp 1

Battery String 1Rated CapacityMiddle Voltage

Battery String 2Rated CapacityMiddle Voltage

Batt Test Records

Temp. Control InfoTemp. Control GroupIndoor Vent. Temp

Fan GroupFan 1 SpeedFan 2 SpeedFan 3 SpeedFan 4 Speed

Hystorical Alarm

Setting WizardBattery ParametersBattery 1 ConnectedYesBattery 2 ConnectedYesRated Capacity170Ah(5-10000)

Date & TimeDate & TimeSet to actual timeTime ZoneUTC +08:00 SingaporeNTP EnableNo

Network ParametersIP Address192.168.0.10Subnet Mask255.255.255.0Default Gateway192.168.0.1

Parameter SettingPower SystemBasic ParametersAC Type (ThreePhases)D.G. Function (None)LLVD1 EnableYes

LLVD ParametersLLVD1 Mode (Voltage Mode)LLVD1 Voltage (44.0V(35.0-56.0)46.0VLLVD1 Con. Volt (51.5V(37.0-58.0))LLVD Delay Time (60s(5-90))

AC&DC Volt. Para.AC OV Thres. (60-300)280VAC UV Thres. (60-300)180VDC OV Thres. (53.0-60.0)58.0VDC UV Thres. (45.0V(35.0-57.0))46.0VDC Ultra OV Thres. (59.0V(53.0-60.0))DC Ultra UV Thres. (44.0V(35.0-57.0))

Sensor Config. ParaDC SPDYesAC SPDYesDoor SensorNoWater SensorNoSmoke SensorNoAmbient Temp. SensorNoAmbient Humidity. SensorNoBatt. Temp. Sensor 1Yes

Temp&Humi Para.Amb. HT Thres.55degC(25-80)Amb. LT Thres."-20degC(-20-20))Amb. Ultra HT Thres."70degC(25-80))Amb. HH Thres.80%(0-100)Amb. LH Thres.10%(0-100)

Other ParametersBuzzer enableNoBuzzer Alm. Duration10Min(1-100)

RectifierHigh Rect. Capacity5%(0-150)Low Rect. Capacity75%(0-150)Max Limited Current121%(1-121)

Energy SavingHibernation EnableNo

BatteryBasic ParametersBattery1 ConnectedYesBattery2 ConnectedYesRated Capacity170Ah(5-10000)FC Voltage53.5V(42.0-58.3)EC Voltage56.4V(42.0-58.3)Charge Limit Coef.0.10C10(0.05-0.25)BLVD EnableYesHibernation EnableNo

Temp. Comp. Para.TC Coefficient80mV/degC(0-500)Nominal Temperature25degC(5-45)TC Upper Thres.45degC(40-45)TC Lower Thres.5degC(5-10)TC Coefficient80mV/degC(0-500)

BLVD ParametersBLVD ModeVoltage ModeBLVD Voltage43.2V(35.0-56.0)BLVD Con. Volt51.5V(37.0-58.0)BLVD Delay Time60s(50-90)

Temp. Control GroupIndoor Vent TsYesOutdoor Amb. TSNo

Fan Group

Alarm ParameterDI Dry contact para.DIN1 Alm. Cond.CloseDIN2 Alm. Cond.CloseDIN3 Alm. Cond.CloseDIN4 Alm. Cond.CloseDIN5 Alm. Cond.CloseDIN6 Alm. Cond.Close

DO Dry Contact Para.ALM1 Alarm ActionCloseALM2 Alarm ActionCloseALM3 Alarm ActionCloseALM4 Alarm ActionCloseALM5 Alarm ActionCloseALM6 Alarm ActionCloseALM7 Alarm ActionOpenALM8 Alarm ActionClose

Alarm ParameterPower SystemAC SPD FaultEnableDC SPD FaultEnableAC FailureEnableAC Ph L1 OVAC Ph L2 OVAC Ph L3 OVAC Ph L1 UVAC Ph L2 UVAC Ph L3 UVAC Ph L1 FailureAC Ph L2 FailureAC Ph L3 FailureDC Ultra OVDC OVDC Ultra UVDC UVLoad Fuse BreakEnableSMU faultInsuff. Alm. SpaceVery High Amb. Temp.Unknown System TypeDoor AlarmWater AlarmHigh AmbTempEnableLow Amb. TempHigh Amb. Humi.Low Amb. HumiAmb. TS MissingAmb. TS FaultAmb. HS MissingAmb. HS FaultLLVD WarningEnableLLVD1 DisconnectedEnableLong Main FailureDIN1DIN2DIN3DIN4DIN5DIN6Abn Sys. Volt CheckAbn Sys. Cur Check

Rectifier

Rectifier GroupRectifier MissingDisableInsuff. Rdnt. Rects.Rect. Fault (Rdnt)Rect. Faultf (Non-Rdnt)Multi-Rect FaultAll Rects Comm. FailRect Hiber ActivatedHigh. Rect. CapacityLow Rect. CapacityRect. Upgrade Fault