12
Nov 2015, Rev. 2 TOVUS DN 15-50, Pressure Independed CV High accuracy High authority Easy commissioning • Dimension: DN 15-50 • Temperature: 0°C till +120°C • Pressure class: PN 25

TOVUS DN 15-50, Pressure Independed CV · TOVUS DN 15-50, Pressure Independed CV • High accuracy ... Description TOVUS DN 15-50 ... 2221 0,617 9,78 2405 0,668 10,59

Embed Size (px)

Citation preview

Nov

201

5, R

ev. 2

TOVUS DN 15-50, Pressure Independed CV

• High accuracy

• High authority

• Easy commissioning

• Dimension: DN 15-50

• Temperature: 0°C till +120°C

• Pressure class: PN 25

Nov 2015, Rev. 2

Description TOVUS DN 15-50

ApplicationThe pressure independent control valve TOVUS is used in secondary cooling and heating systems. Suitable applications include air heaters , chilled beams, FCU’s and control valve in one -pipe systems . TOVUS can be controlled with electrical actuators, and in some applications with thermostatic heads

DescriptionThe control valve TOVUS holds three functions ; presetting , differential pressure control and fl ow management . The functions are combined allowing TOVUS independently of available pressure limits the set fl ow rate . Along with a modulating actuator TOVUS ensures controllability over the entire stroke. TOVUS is equipped with test points for checking the fl ow and the ability to optimize the pump. TOVUS compact design and unique construction provides a space-saving valve that requires low differential pressure for full modulating control . TOVUS is equipped with blue protective cap for and protection of spindle and presetting

Nov

201

5, R

ev. 2

Description TOVUS DN 15-50

SizingSizing of TOVUS is based on the design fl ow . For full function the available pressure needs to be ensured.

Example: The design fl ow is 800 l / h to a FCU.

When the flow of 800 l/h is the differential pressure across the valve TOVUS ~ 15,7 kPa and the presetting 3

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

16.0

Kv (m 3/h)0.3 0.7 1.0 1.4 1.7 2.0 2.3 2.6

min. Δp kPa1100

Flow l/hFlow l/s

15.7

15.1

14.5

1000

900

800

700

600

500

400

300

200

100

0

0.306

0.278

0.250

0.222

0.194

0.167

0.139

0.111

0.083

0.056

0.028

0

TOVUS DN 20 5,0

3

15,7

Nov 2015, Rev. 2

Description TOVUS DN 15-50

SettingThe pressure independent control valve TOVUS is set via the top of the valve. The setting is made after the specifi ed scale .

MeasurementThe lids removed the valves test points . Then the differential pressure can be measured via the valve testpoints

MountingTOVUS has fl ow direction marked on the valve body . Note also that the valve is turned the right for the selected actuator and IP class.

3

Nov

201

5, R

ev. 2

Setting TOVUS DN 15-50

TOVUS DN15, Low Flow

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

16.0

Kv (m 3/h)0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6

min. Δp kPa700

600

500

400

300

200

100

0

Flow l/hFlow l/s

15.7

15.1

14.5

0.194

0.167

0.139

0.111

0.083

0.056

0.028

0

TOVUS DN15, High Flow

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

18.0

Kv (m 3/h)0.7 1.3 2.0 2.5 3.1 3.5 3.8 4.1

min. Δp kPa1800

Flow l/hFlow l/s

17.0

15.8

14.0

1600

1400

1200

1000

800

600

400

200

0

0.500

0.444

0.389

0.333

0.278

0.222

0.167

0.111

0.056

0

Nov 2015, Rev. 2

TOVUS DN20, Low Flow

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

16.0

Kv (m 3/h)0.3 0.7 1.0 1.4 1.7 2.0 2.3 2.6

min. Δp kPa1100

Flow l/hFlow l/s

15.7

15.1

14.5

1000

900

800

700

600

500

400

300

200

100

0

0.306

0.278

0.250

0.222

0.194

0.167

0.139

0.111

0.083

0.056

0.028

0

TOVUS DN20, High Flow

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

22.0

Kv (m 3/h)0.8 1.5 2.2 2.7 3.3 3.8 4.2

min. Δp kPa

2200

Flow l/hFlow l/s

20.2

18.0

14.0

2000

1800

1600

1400

4.3

1200

1000

800

600

400

200

0

0.611

0.556

0.500

0.444

0.389

0.333

0.278

0.222

0.167

0.111

0.056

0

Setting TOVUS DN 15-50

Nov

201

5, R

ev. 2

TOVUS DN25, Low Flow

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

16.0

Kv (m 3/h)0.6 1.3 2.0 2.6 3.2 3.7 4.1 4.3

min. Δp kPa1800

Flow l/hFlow l/s

15.5

14.8

14.0

1600

1400

1200

1000

800

600

400

200

0

0.500

0.444

0.389

0.333

0.278

0.222

0.167

0.111

0.056

0

TOVUS DN25, High Flow

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

22.0

Kv (m 3/h)0.8 1.5 2.2 2.7 3.3 3.8 4.2 4.3

min. Δp kPa

2200

Flow l/hFlow l/s

20.2

18.0

14.0

2000

1800

1600

1400

1200

1000

800

600

400

200

0

0.611

0.556

0.500

0.444

0.389

0.333

0.278

0.222

0.167

0.111

0.056

0

Setting TOVUS DN 15-50

Nov 2015, Rev. 2

TOVUS DN32

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

18.0

Kv (m 3/h)1.3 2.4 3.5 4.5 5.5 6.2 6.8 7.2

min. Δp kPa3250

Flow l/hFlow l/s

17.0

16.0

14.5

3000

2750

2500

2250

2000

1750

1500

1250

1000

750

500

250

0

0.903

0.833

0.764

0.694

0.625

0.556

0.486

0.417

0.347

0.278

0.208

0.139

0.069

0

TOVUS DN40

Pre-set0 0.5 1 1.5 2 2.5 3 3.5 4

20

22.5

2526

Kv (m 3/h)5.1 8.7 11.2 12.8 13.6 13.8 13.8 13.9

min. Δp kPa75002.083

Flow l/hFlow l/s

18

16.5

16

70001.994

65001.806

60001.667

55001.528

50001.389

45001.250

40001.111

35000.972

30000.833

25000.694

20000.556

15000.417

10000.278

5000.139

00

Setting TOVUS DN 15-50

Nov

201

5, R

ev. 2

TOVUS DN50

Pre-set0 0.5 1 1,5 2 2,5 3 3,5 4

3230

29

28

25

22

19

Kv (m 3/h)5,1 9,2 11,9 13,4 14,4 15,0 15,1 15,2

min. Δp kPa90002,500

Flow (l/h)Flow (l/s)

85002,361

2,222 8000

75001,994

70001,806

65001,667

60001,528

55001,389

50001,250

45001,111

40000,972

35000,833

30000,694

25000,556

20000,556

15000,417

10000,278

5000,139

00

Setting TOVUS DN 15-50

Flow l/h Flow l/s Flow gpm78 0,022 0,34117 0,033 0,52156 0,043 0,69195 0,054 0,86234 0,065 1,03274 0,076 1,20313 0,087 1,38352 0,098 1,55391 0,109 1,72430 0,119 1,89469 0,130 2,06508 0,141 2,24547 0,152 2,41586 0,163 2,58625 0,174 2,75

TOVUS DN 15 LowFlow l/h Flow l/s Flow gpm244 0,068 1,08372 0,103 1,64501 0,139 2,20630 0,175 2,77759 0,211 3,34886 0,246 3,901009 0,280 4,441128 0,313 4,971241 0,345 5,461347 0,374 5,931444 0,401 6,361532 0,426 6,741609 0,447 7,081673 0,465 7,371724 0,479 7,59

TOVUS DN 15 HighFlow l/h Flow l/s Flow gpm131 0,036 0,58197 0,055 0,87263 0,073 1,16328 0,091 1,44394 0,109 1,73459 0,128 2,02525 0,146 2,31591 0,164 2,60656 0,182 2,89722 0,201 3,18788 0,219 3,47853 0,237 3,76919 0,255 4,04984 0,273 4,331050 0,292 4,62

TOVUS DN 20 LowPre-set0,500,751,001,251,501,752,002,252,502,753,003,253,503,754,00

Setting and flow

Nov 2015, Rev. 2

Flow l/h Flow l/s Flow gpm292 0,081 1,28435 0,121 1,91577 0,160 2,54719 0,200 3,17863 0,240 3,801007 0,280 4,431152 0,320 5,071296 0,360 5,701437 0,399 6,331573 0,437 6,921700 0,472 7,481815 0,504 7,991913 0,531 8,421990 0,553 8,762039 0,566 8,98

TOVUS DN 20 HighFlow l/h Flow l/s Flow gpm231 0,064 1,02357 0,099 1,57486 0,135 2,14617 0,171 2,72749 0,208 3,30878 0,244 3,871005 0,279 4,431128 0,313 4,961244 0,346 5,481352 0,376 5,951452 0,403 6,391540 0,428 6,781615 0,449 7,111676 0,466 7,381722 0,478 7,58

TOVUS DN 25 LowFlow l/h Flow l/s Flow gpm292 0,081 1,28435 0,121 1,91577 0,160 2,54719 0,200 3,17863 0,240 3,801007 0,280 4,431152 0,320 5,071296 0,360 5,701437 0,399 6,331573 0,437 6,921700 0,472 7,481815 0,504 7,991913 0,531 8,421990 0,553 8,762039 0,566 8,98

TOVUS DN 25 High

Pre-set0,500,751,001,251,501,752,002,252,502,753,003,253,503,754,00

Flow l/h Flow l/s Flow gpm465 0,129 2,05692 0,192 3,05921 0,256 4,051150 0,319 5,061377 0,382 6,061600 0,444 7,041816 0,504 7,992024 0,562 8,912221 0,617 9,782405 0,668 10,592574 0,715 11,332726 0,757 12,002858 0,794 12,582969 0,825 13,073056 0,849 13,45

TOVUS DN 32Flow l/h Flow l/s Flow gpm2022 0,562 8,902825 0,785 12,443538 0,983 15,584179 1,161 18,404758 1,322 20,955279 1,466 23,245741 1,595 25,276139 1,705 27,036470 1,797 28,486729 1,869 29,626916 1,921 30,447033 1,954 30,967090 1,969 31,217105 1,974 31,287105 1,974 31,28

TOVUS DN 40Flow l/h Flow l/s Flow gpm2204 0,612 9,703325 0,924 14,644337 1,205 19,095218 1,449 22,975963 1,657 26,256577 1,827 28,957070 1,964 31,127459 2,072 32,847766 2,157 34,198009 2,225 35,258024 2,279 36,118362 2,323 36,818486 2,357 37,368568 2,380 37,728586 2,385 37,80

TOVUS DN 50

Pre-set0,500,751,001,251,501,752,002,252,502,753,003,253,503,754,00

Setting TOVUS DN 15-50

Setting and flow

Nov

201

5, R

ev. 2

Techinal data TOVUS DN 15-50

Pressure classPN 25Max temperature Min temperature120°C 0°CMaterial DZR BrassMax differential pressure400 kPa

Leakage max 0,01 % of set fl ow

Ordering codes

Article number Name Description Flow

TOVUS 15 LF DN 15 78-625 l/h

TOVUS 15 HF DN 15 244-1724 l/h

TOVUS 20 LF DN 20 131-1050 l/h

TOVUS 20 HF DN 20 292-2039 l/h

TOVUS 25 LF DN 25 231-1722 l/h

TOVUS 25 HF DN 25 292-2039 l/h

TOVUS 32 DN 32 465-3056 l/h

TOVUS 40 DN 40 2022-7105 l/h

TOVUS 50 DN 50 2204-8586 l/h

Nov 2015, Rev. 2

Product information TOVUS DN 15-50

Dimensions mm

We reserve the right to alter information without notice

Dim A B C Weight/kg

TOVUS 15 DN 15 88 65 145 0,90

TOVUS 20 DN 20 88 65 145 0,91

TOVUS 25 DN 25 92 66 145 1,00

TOVUS 32 DN 32 128 72 152 1,52

TOVUS 40 DN 40 144 87 219 2,55

TOVUS 50 DN 50 155 93 225 3,20

CB

A

DN15-DN32A

BC