7/30/2019 tManager Performance Considerations
1/19
anager er ormance ons era ons
2013 Online Development Inc. All Rights Reserved. 1 J une 27, 2013
7/30/2019 tManager Performance Considerations
2/19
Topics
Performance overview
Rockwell Automation reference manuals
RA Logix Design recommendations
RA EtherNet/IP recommendations
OLDI tManager performance optimization recommendations
tManager EtherNet/IP Communication options
Database communication
2013 Online Development Inc. All Rights Reserved. 2 J une 27, 2013
7/30/2019 tManager Performance Considerations
3/19
Typical Performance Landscape
There are many factors that affect overall throughput of yourtManager system ..
ControllerNetwork or
ControlLogixBackplane
tManagerBusinessEthernet Database
Controller ModelControlLogix L63
vs L75, etc.
Rockwell DesignTi s
Backplane vsFront Ethernetport
Type of EthernetBridge
Trigger ScanTimes
OLDI Best
PracticesTri ers/End oints
NetworkConfigurationTransaction rates
FirewallsNetwork Loadin
DatabaseMaintenance &Design
Table Design --contains
Time Slice Continuous,
Periodic & Event-based tasks
DINTS
ENBT vs EN2TvsEN3T
EtherNet/IPDesignGuidelines
/MapsUse of Transaction
LogsUse of Store &
Forward
#of hopsetc
n ex eys on eappropriatecolumns
Stored Proceduredesign -- considerimpact of locks on
Single DimensionArrays
System Log
configurationHandshaking
eav y usetables, views, etc.
2013 Online Development Inc. All Rights Reserved. 3 J une 27, 2013
7/30/2019 tManager Performance Considerations
4/19
Rockwell Automation Design Documents
Referenced While Preparing this PPT
ControlLogix and CompactLogix Design Documents. . .
ExpandPerformance and Capacity Guidelines Chapter 2 of theLogix5000 Controllers Design Considerations manual has information concerning task
scheduling and time slice setup for optimum performance. Pub. 1756-RM094F-EN-P
Chapter 3 of theLogix5000 Controllers Design Considerations manual contains guidelines for usingvarious Logix data types
http://www.rockwellautomation.com/solutions/integratedarchitecture/resources4.html#top50
EtherNet/IP Performance Guidehttp://literature.rockwellautomation.com/idc/groups/literature/documents/ap/enet-ap001_-en-p.pdf
2013 Online Development Inc. All Rights Reserved. 4 J une 27, 2013
7/30/2019 tManager Performance Considerations
5/19
Logix Optimization: Logix Time Slice
If you have a continuous task, RSLogix 5000 & Studio 5000 allow you to allocate a SystemOverhead Time Slice (SOTS), which is a percentage of the CPUs time reserved forbackground CPU functions such as:
Communicating with programming & HMI devices Responding to messages Serial port message & instruction processing Alarm instruction processing
e anager uses ass unconnece messagng, processe n e me s ce
The SOTS only affects messaging performance if a continuous task exists
The default value is 20%
Raising the SOTS increases the scan time of the continuous task, but should increase thenumber of messages per second that are sent between the tManager and Logix processor
The recommended SOTS setting for a data concentrator is 50% or greater. Suggest starting with
2013 Online Development Inc. All Rights Reserved. 5 J une 27, 2013
50%. If everything is working well, you can see if raising it higher improves performance further
7/30/2019 tManager Performance Considerations
6/19
Logix Optimization : Task Configuration
When Motion, Periodic, and Event Based tasks are used, configure them
Eliminate task overlaps Allow enough time for the communications task - SOTS
Each task will task switch with the others, executing in 1 msecintervals until all
are complete
For more information on how Logix processors handle different types of tasks,and to see graphical examples of the effects of changing the SOTS and othertask arameters, reference Cha ter 2 in the RALo ix 5000 Controllers Desi n
Considerations manual
The information on this slide is from the Rockwell Automation O timi in Control S stem Per ormance resentation resented at various
2013 Online Development Inc. All Rights Reserved. 6 J une 27, 2013
,
Automation Fairs. The information is also contained in theLogix5000 Controllers Design Considerationsmanual.
7/30/2019 tManager Performance Considerations
7/19
Logix Optimization : Use DINTS
Use the DINT data type whenever possible. Logix is optimized for 32bit data types, and they are processed faster than other data types
SINT INT DINT REAL
Memory usage for a Tag 4 Bytes 4 Bytes 4 Bytes 4 Bytes
emory eserve or a a n a
UDT
(8 Bit aligned)
(16 Bit aligned)
(32 Bit aligned)
(32 Bit
aligned)
Memory used to access*
236 Bytes 260 Bytes 28 Bytes 44 Bytes
Execution Time for an ADD
instruction * L63 - 3.31 sec L63 - 3.49 sec L63 - 0.26 sec L63 - 1.45 sec
* Assumes all parameters are same data type
2013 Online Development Inc. All Rights Reserved. 7 J une 27, 2013
The information on this slide is from the Rockwell Automation Optimizing Control System Performancepresentation, presented at various
Automation Fairs. The information is also contained in Chapter 3 of theLogix5000 Controllers Design Considerationsmanual.
7/30/2019 tManager Performance Considerations
8/19
Logix Optimization : Data Structure
Guidelines
Utilize the following data structure guidelines whenever possible Use Single Dimensional Arrays and User Defined Structures when
designing your application
Create tag names that are as descriptive as possible while keeping thems or o mnmze e memory usage an e communca on pac e sze
Use single aliasing to prevent changes to documented logic on upload of
project Create packed UDTs to optimize memory and performance
Use DINT arrays for B3 File usage (avoid bool arrays)
Use the LINT data type (64-bit integer value) to store date and time values
2013 Online Development Inc. All Rights Reserved. 8 J une 27, 2013
The information on this slide is from the Rockwell Automation Optimizing Control System Performancepresentation, presented at various
Automation Fairs. The information is also contained in Chapter 3 of theLogix5000 Controllers Design Considerationsmanual.
7/30/2019 tManager Performance Considerations
9/19
Logix Optimization : Optimizing UDT
Memory Usage
16 bytes 12 bytes
DATATYPE Sample1BOOL Bit1;SINT Tiny_Value
DATATYPE Sample1BOOL Bit1;BOOL Bit2;SINT Tin Value
INT Small_ValueDINT Big_Value
REAL Float_ValueEND_TYPE
_INT Small_ValueDINT Big_ValueREAL Float_Value
END_TYPE
User defined structures allow you to combine multiple data types (atomic, predefinedor user defined) into a new data type
All elements in a structure are located on a byte (8 bit) boundary
.yields better performance
Group all bits adjacent to each other when creating a user defined structure Reduces the amount of memory used and reduces communications time
2013 Online Development Inc. All Rights Reserved. 9 J une 27, 2013
The information on this slide is from the Rockwell Automation Optimizing Control System Performancepresentation, presented at various
Automation Fairs. The information is also contained in Chapter 3 of theLogix5000 Controllers Design Considerationsmanual.
7/30/2019 tManager Performance Considerations
10/19
Queuing Applications Reasons Needed
You might need to queue data if you cannot afford to loose data if: there are brief durations of database/network delays
Beore data is written to the tore Forward queue there is a time-out period
that will pass. This method will result in no data loss while waiting fortransaction timeouts
With the method described on the next slide, you cannot sustain data changingfaster than the minimum scan time for long periods of time just short periods
2013 Online Development Inc. All Rights Reserved. 10 J une 27, 2013
7/30/2019 tManager Performance Considerations
11/19
Queuing Applications -- Implementation
1. Write the controller tags to a temporary queue (array), and thenmove them to the mapped tags when the tManager trigger is
Use the LINT output of a Logix GSV instruction when mapping the time to the database vsusing the tManagers Timestamp macro
your scan rate, and then double it (to compensate for the transaction time-out)
2. Configure a Status Tag for the message path (in the TriggerConfi uration screen of the associated tri er
3. Advance the data from the controller queue to the mapped tagsby monitoring the status tag for values >=20 and 100 = an error has occurred
2013 Online Development Inc. All Rights Reserved. 11 J une 27, 2013
tags
7/30/2019 tManager Performance Considerations
12/19
RA EtherNet/IP Switch Recommendations
When using Ethernet/IP for control, use an industrial grade switch
Required switch features:
Full-du lex ca abilit on all orts
Recommended switch features: VLAN
Auto-negotiation/manually configurable speed/duplex
The information on this slide is from Chapter 6 of theLogix5000
Controllers Design Considerations manual.
Wire-speed switching fabric
SNMP
IGMP snooping constrains multicast traffic to ports associated with a particular IP multicast group
Port diagnostics
Port-mirroring (required for troubleshooting)
-
STP for loop prevention
QoS
For additional control network uidelines, reference the RALo ix 5000 Controllers
2013 Online Development Inc. All Rights Reserved. 12 J une 27, 2013
Design Considerations manual and the RAEtherNet/IP Performance Guide
7/30/2019 tManager Performance Considerations
13/19
tManager Optimization: System Log &
Status Tags
When you configure the System log, do not keep theLog detail level setting at-
Only enable the DEBUG mode for System logging if you are instructed to use it by OLDIsupport, and then remember to change the setting back to INFO or one of the other optionswhen you are done
Logging DEBUG messages will have a negative impact on tManager performance
Status Tags
Since the will add loadin on the controller and could affect erformance onl defineStatus Tags for the projects, triggers and endpoints where they are needed and will be usedby the controllers application program
2013 Online Development Inc. All Rights Reserved. 13 J une 27, 2013
7/30/2019 tManager Performance Considerations
14/19
tManager Optimization: Transaction
Logging & Overrun Timers
Only enable Trigger & Endpoint Transaction Logging as needed for regulatorypurposes, or during troubleshooting & start-up
can process If you have a large transaction, logging the entire
transaction has a reater detrimental effect than ustlogging a specific number of bytes
Trigger and Endpoint Overrun Timers
The overrun features should be enabled sparingly, mainly during troubleshooting, sincethey will slow down the overall throughput of all the triggers on the module. For moreinformation on Overrun Timers, reference the tManager Troubleshooting presentation.
The values entered for the trigger overrun timers need to be greater than the Scan. , ,
module throughput will decrease, and other important events and/or errors may bemissed
2013 Online Development Inc. All Rights Reserved. 14 J une 27, 2013
7/30/2019 tManager Performance Considerations
15/19
tManager Optimization: Store & Forward
If Store & Forward is enabled on an endpoint, once communications areinterrupted & data is sent to the S&F queuethe number of transactionsprocessed per second may decrease
There is an initial time-out period that depends on either the adapters configuredconnection or the transaction time-out values before writing to the S&F queue is
Writing data to the queue, which is stored on the tManagers compact flash, maytake more time than sending the information to its normal destination
,tManager performance while data from the S&F queue is sent to its intendeddestination
2013 Online Development Inc. All Rights Reserved. 15 J une 27, 2013
7/30/2019 tManager Performance Considerations
16/19
tManager Optimization: Separate Triggers &
Endpoints
Handshake mode selection effects when the next trigger firing occurs:
When combining transactions under one trigger, remember that the trigger cannotre agan un e compe on o a e messages a er eve o an s a ng.
Therefore, one slow message, or one message with a high level of Handshakingselected, would cause all messages to wait for its completion
For more information on Handshaking, reference the tManager Details and BestPractices presentation
Separate endpoints are recommended if you have a transaction message whichyou might expect to be more time-consuming (x-sec vs.
7/30/2019 tManager Performance Considerations
17/19
tManager Optimization: One
Controller.One Map
Although you can use tags from multiple controllers in a single map, it is notrecommended
If any of a maps input variables are not available when the trigger fires, the trigger ismarked as faulted and will not retry for 60-seconds
If multiple controllers are used in a map, loss of communications with any of theseconro ers w cause e rgger o s op rng un a o e conro ers are onceagain available
If ou need ta s from multi lecontrollers ma ed into a sin le database table atthe same time
Recommend mapping all the tags into a data concentrator controller
Ma ta s from the data collector PLC to the database table in a sin le ma
2013 Online Development Inc. All Rights Reserved. 17 J une 27, 2013
7/30/2019 tManager Performance Considerations
18/19
tManager EtherNet/IP Communications
EtherNet/IP communication over the ControlLogix backplane is usually fasterthan out one of the front Ethernet ports
Rockwell Automation designed the ControlLogix backplane for speed and ease ofcommunications, so backplane communication to the tManager is always as fast orfaster
er e ou e ron por s compara e o communca on over er e vaa 1756-ENBT
A 1756-EN2T/3T is twice a fast as a 1756-ENBT
Reference Rockwell Automation Knowledgebase document 40784 for acomparison of the different Logix EtherNet/IP Bridge modules
htt ://rockwellautomation.custhel .com/a /answers/detail/a id/4078_
2013 Online Development Inc. All Rights Reserved. 18 J une 27, 2013
7/30/2019 tManager Performance Considerations
19/19
Database Communication
Configuring several database adapters versus having everything go to/from the
The size of the transactions & speed of the databases response to the ,
and maintenance, do have an impact on throughput
2013 Online Development Inc. All Rights Reserved. 19 J une 27, 2013