2-port / 3-port ValvesFemale Threaded,PN16/PN25
TL..-..BC-S.12 Series
Valve body material: stainless steel
DN15...DN80 (chilled/hot water) DN15...DN50(steam)
Kvs:1.9...66m3/h
Standard of female threaded connection: ISO 7/1
Can be fitted with electric actuators: TC/TR...-D..-.12 ,TC/TR...-X..-.12
1
This kind of valve body is suitable for HVAC system, air conditioning, and refrigeration system.
Chilled water
Anti-freeze water
Refrigerant
(R12、R22、R134a、R202)
Glycol
Hydrazine
Phosphate
Low temperature hot water
High temperature hot water
Saturated steam(≤150℃ or ≤0.1MPa)
Saturated steam(≤0.69MPa)
Overheated steam(≤180℃)
Note: when medium temperature in valve is below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should
be protected by electric heating cover(Type: THOT-1) to avoid frosting and icing.
-25℃~150℃
(Chilled/hot water valve)
2℃~180℃
(Steam valve)
Application
Datasheet No.:
TL-01
Type2-port
Type 3-port
Caliber(in.)
DN(mm)
Kvs(m3/h)
Stroke(mm)
ActuatorRecommended
2-port △pmax (Mpa)
3-port △pmax (Mpa)
TL15-2VBC-S.12 TL15-3VBC-S.12 1/2" 15 1.9 10 500N ≤1.60 ≤0.50TL20-2VBC-S.12 TL20-3VBC-S.12 3/4" 20 4.4 10 500N ≤1.10 ≤0.50TL25-2VBC-S.12 TL25-3VBC-S.12 1" 25 8 15 500N ≤0.70 ≤0.40TL32-2VBC-S.12 TL32-3VBC-S.12 1-1/4" 32 10 20 500N ≤0.40 ≤0.35TL40-2VBC-S.12 TL40-3VBC-S.12 1-1/2" 40 20 20 500N ≤0.25 ≤0.30TL50-2VBC-S.12 TL50-3VBC-S.12 2" 50 32 20 1000N ≤0.30 ≤0.30TL65-2VBC-S.12 TL65-3VBC-S.12 2-1/2" 65 50 20 1000N ≤1.60 ≤0.25TL80-2VBC-S.12 TL80-3VBC-S.12 3" 80 66 20 1000N ≤1.60 ≤0.25Note:(3-port female threaded stainless valve)DN15~DN80 3-port valve are all mixing , if you need diverting ones, please exchange A and AB according to plate on the valve.
Type Summary
Chilled/hotwater valves
(-25...+150℃)
Steam valves
(2...+180℃)
Actuator Overview
Valve Flow Characteristic
Type
2-portCaliber
(in.)DN
(mm)Kvs
(m3/h)Stroke(mm)
ActuatorRecommended
△pmax (Mpa)
TL15-2SBC-S.12 1/2" 15 1.9 10 500N ≤1.60TL20-2SBC-S.12 3/4" 20 4.4 10 500N ≤1.10TL25-2SBC-S.12 1" 25 8 15 1000N ≤1.20TL32-2SBC-S.12 1-1/4" 32 10 20 1000N ≤0.80TL40-2SBC-S.12 1-1/2" 40 20 20 1800N ≤1.20TL50-2SBC-S.12 2" 50 32 20 1800N ≤0.75
Notes: DN= Nominal diameterKvs= Nominal flow coefficient, which refer to the flow when medium (Density=1g/cm3) go through the full open control valve, whose differential pressure at two ends of valve is 0.1Mpa.Type instruction:e.g.TL**-2VBC-S.121. L: Female threaded2. **: Caliber3. Medium: V: water -25℃~150℃; S: steam 2~180℃4. Valve Body: B: stainless steel5. Pressure: C: PN16 D: PN256. .12: Tiger Controls' standard interface
Type Rating Force
Actual ForceOperatingVoltage
Control Signal Manual Running speed
TC500-X24-S.12 500N 500N~700N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.85s/mm (50Hz)TC500-D24-S.12 500N 500N~700N 24VAC 3-position Yes 3.85s/mm (50Hz)TC1000-X24-S.12 1000N 1000N~1200N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.85s/mm (50Hz)TC1000-D24-S.12 1000N 1000N~1200N 24VAC 3-position Yes 3.85s/mm (50Hz)TR1800-X24-S.12 1800N 1800N~2000N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.13s/mm (50Hz)TR1800-D24-S.12 1800N 1800N~2000N 24VAC 3-position Yes 3.13s/mm (50Hz)TR3000-X24-S.12 3000N 3000N~3500N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.13s/mm (50Hz)TR3000-D24-S.12 3000N 3000N~3500N 24VAC 3-position Yes 3.13s/mm (50Hz)Notes: 1. Operating voltage is available for 220V/24VAC, which must be noted when ordering, the type should be changed from "24" to "220". For example, change "TC500-X24-S.12" to "TC500-X220-S.12". 2. 10K feedback function can be selected when actuator is 3-position type, which must be noted when ordering, the type should be changed from"S" to "SF10K". For example, change "TC500-X24-S.12" to "TC500-X24-SF10K.12". 3. SPDT feedback function also can be selected when actuator is 3-position type, which must be noted when ordering, the type should be changed from"S" to "SF2". For example, change "TC500-X24-S.12" to "TC500-X24-SF2.12". 4. S means manual function.5. The actual running time depends on the actual valve stroke.
2Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
medium flow100%
control signal 100%
equal-linear curve
medium flow100%
control signal 100%
equal-percentage curve
The valve and actuator can be easily assembled without special tool and adjustment. See specification for installation details.
3
Machanical DesignFlow direction of medium
Medium flow relationship
Mounting with actuator
Mounting with pipe
Plate on the valve
Flow direction:valve stem retracts:valve stem extends:
A to ABflow increasesflow decreases
A,B to ABflow of A increases, B decreasesflow of A decreases, B increases
AB to A,Bflow of A increases, B decreasesflow of A decreases, B increases
2-port 3-port mixing 3-port diverting DN15~DN80 DN15~DN80 DN15~DN80
2-port 3-port mixing 3-port diverting DN15~DN80 DN15~DN80 DN15~DN80
2. Valve can be installed in the water supply pipe or return water pipe (priority selection). Besides, filter and check valve are recommended to be installed. When the medium is steam, install draw off valve in the pipe can remove the condensed water, or it will effect the life of valve.
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
Kvs
△P: Differential pressure when control valve is full open (unit: kPa)
V: Rating flow at the △P (unit: m3/h)
Kvs = Nominal flow coefficient, which refer to the flow when medium (Density=1g/cm3) go through the full open
control valve, whose differential pressure at two ends of valve is 0.1Mpa.
Relationship between Differential Pressure and Flow
1.valve should be installed according to marked direction.
2-port 3-port diverting valve 3-port diverting valve DN15~DN80 DN15~DN80 DN15~DN80
Note: The 2-port valve closes when the stem extends.
MountingOrientation
Commissioning
Maintenance
Technical Data
Operating Data
Material
4
Commission the valve only if the actuator has been mounted correctly.
Permissible Pressure
Standard of female threaded
connection
Leakage rate
Permissible media
Water valve
(-25℃~150℃)
Steam valve
(2℃~+180℃)
Permissible pressure
Stroke
Valve body
Valve core
Stem
Seal ring
Sealing structure
PN16
ISO 7/1
0.02% Kvs
Chilled water, Anti-freeze water, Refrigerant(R12、R22、R134a、
R202),Glycol, Hydrazine, Phosphate, Low and high temperature hot
water, Saturated steam(≤150℃ or ≤0.1MPa)
Saturated steam(≤0.69MPa), Overheated steam(≤180℃)
1.6Mpa(1600Kpa, 16bar)
10mm(DN15-DN20),15mm(DN25),20mm(DN32-DN80)
Stainless steel
Stainless steel
Stainless steel
Teflon
V model sealing gland + stainless steel spring auto-compensation
Medium is chilled/hot water Medium is steam
Downward installation is forbidden Any installation position is OK
When doing service work on the valve / actuator:
1. Close the pump and turn off the power supply.
2. Close the shut-off valve, exhaust water in the pipe to reduce the pressure inside pipes. Make water
pipe(hot water) cool down naturally.
3. Dismantle electric wires from wiring terminals.
Notice:When we do the pipe pressure testing and flshing,the valve body should be in a state of full open.
This operation can not only protect the internal parts of valve body, but also prevent pipe from blocking.
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
refer to <Dimensions>
refer to <Dimensions>
Dimension
Weight
Dimension/Weight
Dimension Figure
2-port
3-port
Type 2-port
Type 3-port DN L1
mm2-port L3
mm3-port L3’
mm H1mm
H2mm
Hmm
(500N/1000N)
2-port weight
Kg
3-port weight
Kg
TL15-2VBC-S.12 TL15-3VBC-S.12 15 80 38 49 18 95 248 1 0.8
TL20-2VBC-S.12 TL20-3VBC-S.12 20 80 40 51 21 98 251 1.1 1.1
TL25-2VBC-S.12 TL25-3VBC-S.12 25 100 44 55 24 101 254 1.5 1.6
TL32-2VBC-S.12 TL32-3VBC-S.12 32 103 47 62 30 107 260 1.8 1.8
TL40-2VBC-S.12 TL40-3VBC-S.12 40 122 52 71 36 113 266 2.3 2.3
TL50-2VBC-S.12 TL50-3VBC-S.12 50 138 65 85 41 118 271 3.4 3.3
TL65-2VBC-S.12 TL65-3VBC-S.12 65 160 77 100 51 128 281 5.2 6.0
TL80-2VBC-S.12 TL80-3VBC-S.12 80 180 87 115 58 135 288 6.8 7.1
Remark:1.The weight of the steam valve is the same as the water valve.
5Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
6
BAS valve bodySeries TC500... TC1000... TR1800...
Nominal stroke 22mm 22mm 44mm
Nominal output force 500N 1000N 1800N
Basic application Type
● HVAC TC500.../ TC1000...
TR1800.../ TR3000...
3-position, 24VAC 3-position TC500-D24-S.12 TC1000-D24-S.12 TR1800-D24-S.12
proportional, 24VAC 0(2)...10VDC , 0(4)...20mA TC500-X24-S.12 TC1000-X24-S.12 TR1800-X24-S.12
3-position, 220VAC 3-position TC500-D220-S.12 TC1000-D220-S.12 TR1800-D220-S.12
proportional, 220VAC 0(2)...10V,DC 0(4)...20mA
TC500-X220-S.12 TC1000-X220-S.12 TR1800-X220-S.12
3-position,10K resistance(24VAC / 220VAC) 3-position TC500-D24-SF10K.12/
TC500-D220-SF10K.12TC1000-D24-SF10K.12/TC1000-D220-SF10K.12
TR1800-D24-SF10K.12/TR1800-D220-SF10K.12
3 position,2 SPDT feedback(24VAC /220VAC) 3-position TC500-D24-SF2.12/
TC500-D220-SF2.12TC1000-D24-SF2.12/TC1000-D220-SF2.12
TR1800-D24-SF2.12/TR1800-D220-SF2.12
Valve body Type DN StrokeFlow
paremeter Kvs
△Ps △Ps △Ps
[mm] [mm] [m3/h] [MPa] [MPa] [MPa]
PN
16, medium
temperature -25 ℃
~ 150℃
Female threaded water
valve
TL15-2VBC-S.12 DN15 10 1.9 1.60
TL20-2VBC-S.12 DN20 10 4.4 1.10
TL25-2VBC-S.12 DN25 15 8 0.70
TL32-2VBC-S.12 DN32 20 10 0.40
TL40-2VBC-S.12 DN40 20 20 0.25
TL50-2VBC-S.12 DN50 20 32 0.30 0.60
TL65-2VBC-S.12 DN65 20 50 1.60 1.60
TL80-2VBC-S.12 DN80 20 66 1.60 1.60
2 ℃ ~ 180
℃
Female threaded steam
valve
TL15-2SBC-S.12 DN15 10 1.9 1.60
TL20-2SBC-S.12 DN20 10 4.4 1.10
TL25-2SBC-S.12 DN25 15 8 1.20
TL32-2SBC-S.12 DN32 20 10 0.80
TL40-2SBC-S.12 DN40 20 20 1.20
TL50-2SBC-S.12 DN50 20 32 0.75
PN
16,medium
temperature,-25
℃ ~ 150
℃
Female threaded water
valve
TL15-3VBC-S.12 DN15 10 1.9 0.50
TL20-3VBC-S.12 DN20 10 4.4 0.50
TL25-3VBC-S.12 DN25 15 8 0.40
TL32-3VBC-S.12 DN32 20 10 0.35
TL40-3VBC-S.12 DN40 20 20 0.30
TL50-3VBC-S.12 DN50 20 32 0.30 0.60
TL65-3VBC-S.12 DN65 20 50 0.25 0.50
TL80-3VBC-S.12 DN80 20 66 0.25 0.50
Notes:1.Kvs calculating software: log in website---www.tiger-control.com for online version. Download versions for Android and Apple users are available.2.PN25 is avaliable, please change the type from "C" to "D" when you place an order. eg: TF150-2VGD-S.12.3.Please choose accessory: THOT-1 heating cover to protect the valve stem from freezing if the meduim is glycol or other low-temperature medium.4.If the steam valves need Fail-safe function, please add accessory---TUPS-24 (Uninterruptible Power Supply). TUPS-24 will provide the control signal to shut off the valve when power fails in the system. For more information, please refer to the technical literature on website www.tiger-control.com or ask local agents for help.
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
2-port / 3-port valvesFlanged,PN16/PN25/PN40
TF...-..GC-S.12 Series
Valve body material: ductile iron
DN15...DN400
Kvs:2...2200m3/h
Below DN80 of 3-port valve, the valve core only mixing type (reversal when diverting occasion)
Above DN80 of 3-port valve, the valve core have both mixing type and diverting type
Standard of flanged connection: ISO 7005-2
Can be fitted with electric actuators: TC/TR...-D.-.12, TC/TR...-X..-.12
7
This kind of valve body is suitable for HVAC system, air conditioning, and refrigeration system.
Chilled water
Anti-freeze water
Refrigerant
(R12、R22、R134a、R202)
Glycol
Hydrazine
Phosphate
Low temperature hot water
High temperature hot water
Saturated steam(≤150℃ or ≤0.1MPa)
Saturated steam(≤0.89MPa)
Overheated steam(≤180℃)
High-temperature steam(≤200℃)
Super-High-temperature steam(≤450℃)
Notes: when medium temperature in valve below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by electric heating cover(Type: THOT-1) to avoid frosting and icing.
-25℃~150℃
(Chilled/hot water
valve) 2℃~180℃
(Steam valve)
Application
Medium
Datasheet No.:
TF-01
2℃~220℃
(High-Temp.
Steam valve)
2℃~450℃
(Super-High-Temp.
Steam valve)
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
Type2-port
Type 3-port
Caliber(in.)
DN(mm)
Kvs(m3/h)
Stroke(mm)
ActuatorRecommended
2-port△pmax (Mpa)
3-port△pmax (Mpa)
TF15-2VGC-S.12 TF15-3VGC-S.12 1/2" 15 2 20 500N ≤1.60 ≤0.80TF20-2VGC-S.12 TF20-3VGC-S.12 3/4" 20 3 20 500N ≤1.10 ≤0.80TF25-2VGC-S.12 TF25-3VGC-S.12 1" 25 5 20 500N ≤0.70 ≤0.80TF32-2VGC-S.12 TF32-3VGC-S.12 1 1/4" 32 8 20 500N ≤0.40 ≤0.80TF40-2VGC-S.12 TF40-3VGC-S.12 1 1/2" 40 20 20 500N ≤0.25 ≤0.80TF50-2VGC-S.12 TF50-3VGC-S.12 2" 50 31 20 1000N ≤0.30 ≤0.30TF65-2VGC-S.12 TF65-3VGC-S.12 2 1/2" 65 50 20 1800N ≤0.45 ≤0.45
TF80-2VGC-S.12 TF80-3VGC-HS.12TF80-3VGC-FS.12 3" 80 80 20 1800N ≤0.30 ≤0.27
TF100-2VGC-S.12 TF100-3VGC-HS.12TF100-3VGC-FS.12 4" 100 125 40 3000N ≤0.28 ≤0.20
TF125-2VGC-S.12 TF125-3VGC-HS.12TF125-3VGC-FS.12 5" 125 200 40 3000N ≤1.60 ≤0.15
TF150-2VGC-S.12 TF150-3VGC-HS.12TF150-3VGC-FS.12 6" 150 300 40 3000N ≤1.60 ≤0.10
TF200-2VGC-S.12 TF200-3VGC-HS.12TF200-3VGC-FS.12 8" 200 520 40 5000N ≤1.60 ≤0.13
TF250-2VGC-S.12 TF250-3VGC-HS.12TF250-3VGC-FS.12 10" 250 750 40 5000N ≤1.60 ≤0.08
TF300-2VGC-Y.12 TF300-3VGC-HY.12TF300-3VGC-FY.12 12" 300 1200 100 16000N ≤1.60 ≤0.25
TF350-2VGC-Y.12 TF350-3VGC-HY.12TF350-3VGC-FY.12 14" 350 1800 100 16000N ≤1.60 ≤0.15
TF400-2VGC-Y.12 TF400-3VGC-HY.12TF400-3VGC-FY.12 16" 400 2200 100 16000N ≤1.60 ≤0.10
Notes: (3-port ductile iron flanged valve)
1. DN15~DN65 3-port valve are all mixing, if you need diverting ones, please exchange A and AB according to plate on the valve.2. DN80~DN400, the valve core have both mixing type and diverting type. Please note it when ordering, "HS" means mixing, "FS" means diverting.3. Attention: DN80~DN400 medium flow relationship are opposite between mixing and diverting valve.
Type Summary
Chilled/hotwater valves
(-25...+150℃)
Steam valves
(2...+180℃)
8
Type2-port
Caliber(in.)
DN(mm)
Kvs(m3/h)
Stroke(mm)
ActuatorRecommended
2-port△Ps(Mpa)
TF15-2SGC-S.12 1/2" 15 2 20 1800N ≤1.60TF20-2SGC-S.12 3/4" 20 3 20 1800N ≤1.60TF25-2SGC-S.12 1" 25 5 20 1800N ≤1.60TF32-2SGC-S.12 1 1/4" 32 8 20 1800N ≤1.60TF40-2SGC-S.12 1 1/2" 40 20 20 1800N ≤1.60TF50-2SGC-S.12 2" 50 31 20 1800N ≤1.60TF65-2SGC-S.12 2 1/2" 65 50 20 1800N ≤1.60TF80-2SGC-S.12 3" 80 80 20 1800N ≤1.60TF100-2SGC-S.12 4' 100 125 40 3000N ≤1.60TF125-2SGC-S.12 5" 125 200 40 3000N ≤1.60TF150-2SGC-S.12 6" 150 300 40 3000N ≤1.60TF200-2SGC-S.12 8" 200 520 40 5000N ≤1.60TF250-2SGC-S.12 10" 250 750 40 5000N ≤1.60TF300-2SGC-Y.12 12" 300 1200 100 16000N ≤1.60TF350-2SGC-Y.12 14" 350 1800 100 16000N ≤1.60TF400-2SGC-Y.12 16" 400 2200 100 16000N ≤1.60
Note:1.If medium temperature is low,pls select accessory:THOT-1 electric heating cover to protect valve stem from freezing2. If power reset function is needed for steam valve, pls select TUPS-24, it can provide control signal for valve closing when the system is power off.3. PN25 valve is selectable, just change the type from C to D,e.g. TF150-2VGD-S.124. 450℃ super high temperature valve is selectable, caliber:DN15~DN400 e.g.:2 port DN150 super high temperature valve type: TF150-2PGC-S.12
Type Instruction: eg: TF**-2VGC-S.121. F: Flanged2. **: Caliber3. Medium: V: water -25℃~150℃ S: steam 2℃~180℃ A: high-temp. steam 2℃~220℃ P: super-high-temp. steam 2℃~450℃4. Valve Body: G: ductile iron5. Pressure: C: PN16; D: PN256. .12: Tiger Controls' standard interface
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
Kvs
△P: Differential pressure when control valve is full open (unit: kPa)
V: Rating flow at the △P (unit: m3/h)
Kvs = Nominal flow coefficient, which refer to the flow when medium (Density=1g/cm3) go through the full open control valve,
whose differential pressure at two ends of valve is 0.1Mpa.
9
medium flow100%
control signal 100%
equal-linear curve
medium flow100%
control signal 100%
equal-percentage curve
Valve Flow Characteristic
Type Rating Force
Actual ForceOperatingVoltage
Control Signal Manual Running speed
TC500-X24-S.12 500N 500N~700N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.85s/mm (50Hz)TC500-D24-S.12 500N 500N~700N 24VAC 3-position Yes 3.85s/mm (50Hz)TC1000-X24-S.12 1000N 1000N~1200N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.85s/mm (50Hz)TC1000-D24-S.12 1000N 1000N~1200N 24VAC 3-position Yes 3.85s/mm (50Hz)TR1800-X24-S.12 1800N 1800N~2000N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.13s/mm (50Hz)TR1800-D24-S.12 1800N 1800N~2000N 24VAC 3-position Yes 3.13s/mm (50Hz)TR3000-X24-S.12 3000N 3000N~3500N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.13s/mm (50Hz)TR3000-D24-S.12 3000N 3000N~3500N 24VAC 3-position Yes 3.13s/mm (50Hz)TR5000-X24-S.12 5000N 4500N~5500N 24VAC 0(2)~10V, 0(4)~20mA Yes 3.13s/mm (50Hz)TR5000-D24-S.12 5000N 4500N~5500N 24VAC 3-position Yes 3.13s/mm (50Hz)TR16000-XD220-S.12 16000N 16000N~16500N 220VAC 0(2)~10V, 0(4)~20mA Yes 1s/mm (50Hz)
Notes: 1. Operating voltage is available for 220V, which must be noted when ordering, the type should be changed from "24" to "220". For example, change "TC500-X24-S.12" to "TC500-X220-S.12". 2. 10K feedback function can be selected when actuator is 3-position type, which must be noted when ordering, the type should be changed from"S" to "SF10K". For example, change "TC500-X24-S.12" to "TC500-X24-SF10K.12". 3. SPDT feedback function also can be selected when actuator is 3-position type, which must be noted when ordering, the type should be changed from"S" to "SF2". For example, change "TC500-X24-S.12" to "TC500-X24-SF2.12". 4. S means manual function.5. The actual running time depends on the actual valve stroke.
Actuator Overview
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
Relationship between Differential Pressure and Flow
Mechanical Design
Flow direction
Medium flow relationship
Mounting with actuator
Mounting with pipe
2. Valve can be installed in the water supply pipe or return water pipe (priority selection). Besides, filter
and check valve are recommended to be installed. When the medium is steam, install draw off valve in
the pipe can remove the condensed water, or it will effect the life of valve.
10
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
flow direction:valve retracts:valve extends:
flow direction:valve retracts:valve extends:
2-portDN15~DN400
3-port mixingDN15~DN65
3-port diverting DN15~DN65
A,B to ABflow increasesflow decreases
A,B to ABA port flow increases,B port decreasesA port flow decreases,B port increases
AB to A,BA port flow increases,B port decreasesA port flow decreases,B port increases
3-port mixing DN15~DN65
3-port diverting DN15~DN65
A,B to ABA port flow increases,B port decreasesA port flow decreases,B port increases
AB to A,BA port flow increases,B port decreasesA port flow decreases,B port increases
The valve and actuator can be easily assembled without special tool and adjustment. See specification for installation details.
3-port mixing connection/valve DN15~DN65 /DN80~DN400
3-port diverting connection/valve DN15~DN65 /DN80~DN400
1.valve should be installed according to marked direction.
2-port DN15~DN400
2-port 3-port mixing connecting 3-port diverting connecting 3-port diverting valve DN15~DN400 DN15~DN65 DN15~DN65 DN80~DN400 3-port mixing valve DN80~DN400
Note: The 2-port valve closes when the stem extends.
MountingOrientation
Commissioning
Maintenance
Technical data
Operating Data
Material
11
Commission the valve only if the actuator has been mounted correctly.
Permissible Pressure
Standard of flanged connection
Leakage rate
Permissible media
Water valve
(-25℃~150℃)
Steam valve
(2℃~+180℃)
High-temp. Steam valve
Super-high-temp. Steam valve
Permissible pressure
Stroke
Valve body
Valve core
Stem
Seal ring
Sealing structure
PN16, PN25, PN40 are optional
ISO 7005-2
0.02% Kvs
Chilled water
Refrigerant(R12、R22、R134a、R202)
Glycol,Hydrazine,Phosphate,low and high temperatur hot water
Saturated steam(≤150℃ or ≤0.1MPa)
Saturated steam(≤0.89MPa),Overheated steam(≤180℃)
High-temperature steam(≤220℃)
Super-High-temperature steam(≤450℃)
1.6Mpa, 2.5Mpa, 4.0Mpa
20mm(DN15~DN80), 40mm(DN100~DN250)
Ductile iron
stainless steel
Stainless steel
Teflon
V model sealing gland + stainless steel spring auto-compensation auto-compensation (≤220℃ valve)
V model sealing gland + stainless steel spring auto-compensation+metal exhaust bellows(≤450℃ valve)
When doing service work on the valve / actuator:
1. Close the pump and turn off the power supply.
2. Close the shut-off valve, exhaust water in the pipe to reduce the pressure inside pipes. Make water
pipe(hot water) cool down naturally.
3. Dismantle electric wires from wiring terminals.
Remark: Valve should be fully open when doing the pipe pressure test and pipe flushing.
Medium is chilled/hot water Medium is steam
Downwards installation is forbidden Random Orientation is suitable
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
Dimensions
12
2-port 3-port
DN Bmm
Dmm
D2mm
D4mm
Kmm
L1mm
L2mm
2-portL3mm
3-portL3'mm
H1 H22-portweight
Kg
3-portweight
Kg
H-1mm
H-2mm
H-3mm
H-4mm
15 14 95 4-14 46 65 130 65 70 106 31 107 3.7 5.5 371 526 586 /20 16 105 4-14 56 75 150 75 70 106 31 107 4.3 5.5 371 526 586 /25 16 115 4-14 65 85 160 80 75 111 36 112 5.4 6.5 376 531 591 /32 18 140 4-18 76 100 180 90 80 121 45 121 7.7 9.4 385 540 600 /40 18 150 4-18 84 110 200 100 82 122 50 126 9.2 11.0 390 545 605 /50 20 165 4-18 99 125 230 115 98 136 60 136 12.5 14.8 400 555 615 /65 20 185 4-18 118 145 290 145 112 156 90 166 18.5 22.5 430 585 645 /80 22 200 8-18 132 160 310 155 130 185 120 196 25.0 28.8 460 615 675 /
1002-port
23 220 8-18 156 180 350 175150 - 136 212
35.6 40.6 /631 691 /
3-port - 202 162 238 657 717
125 24 250 8-18 184 210 400 200 175 240 157 233 50.6 55.4 / 652 712 /150 25 285 8-22 211 240 480 240 200 270 171 247 71.5 76.3 / 666 726 /200 26 340 12-22 266 295 500 250 236 320 263 339 112.7 125.6 / 758 818 /250 31 405 12-26 319 355 600 300 290 400 315 391 202 230.0 / 810 870 /
300
2-port
28 460 12-26 370 410 700 350
330 - 357 485
/ / / / /
13393-portMixing - 457 347 475 1329
3-portDiverting - 457 410 538 1392
350 46 520 16-26 429 470 788 394 400 520 437 565 / / / / / 1419400 48 580 16-30 480 525 912 456 420 595 487 615 / / / / / 1469
Tiger Controls Equipment Co., Ltd
Tel: 0086-429-6879888 Fax: 0086-429-6796222 Http:// www.tiger-control.com Email: [email protected]
actu
ator
DN Bmm
Dmm
D2mm
D4mm
Kmm
L1mm
L2mm
2-portL3mm
3-portL3'mm
H1 H22-portweight
Kg
3-portweight
Kg
H-1mm
H-2mm
H-3mm
H-4mm
15 14 95 4-14 46 65 130 65 70 106 31 107 3.7 5.5 371 526 586 /20 16 105 4-14 56 75 150 75 70 106 31 107 4.3 5.5 371 526 586 /25 16 115 4-14 65 85 160 80 75 111 36 112 5.4 6.5 376 531 591 /32 18 140 4-18 76 100 180 90 80 121 45 121 7.7 9.4 385 540 600 /40 18 150 4-18 84 110 200 100 82 122 50 126 9.2 11.0 390 545 605 /50 20 165 4-18 99 125 230 115 98 136 60 136 12.5 14.8 400 555 615 /65 20 185 8-18 118 145 290 145 112 156 90 166 18.5 22.5 430 585 645 /80 22 200 8-18 132 160 310 155 130 185 120 196 25.0 28.8 460 615 675 /
1002-port
23 235 8-22 156 190 350 175150 - 136 212
35.6 40.6 /631 691 /
3-port - 202 162 238 657 717
125 24 270 8-26 184 220 400 200 175 240 157 233 50.6 55.4 / 652 712 /150 25 300 8-26 211 250 480 240 200 270 171 247 71.5 76.3 / 666 726 /200 26 360 12-26 274 310 500 250 236 320 263 339 112.7 125.6 / 758 818 /250 31 425 12-30 330 370 600 300 290 400 315 391 202 230.0 / 810 870 /
300
2-port
28 485 16-30 389 430 700 350
330 - 357 485
/ / / / /
13393-portMixing - 457 347 475 1329
3-portDiverting - 457 410 538 1392
350 46 555 16-33 448 490 788 394 400 520 437 565 / / / / / 1419400 48 620 16-36 503 550 912 456 422 595 487 615 / / / / / 1469
Note:B: thickness of flange D: excircle diameter of flange D2: quantity and diameter of bolt hole on flange D4: outer diameter of sealing surface K: bolt hole center line diameter L1: distance of left and right flange endL3: distance from 2-port flange center line to valve bottom L3': distance from 3-port flange center line to down flange end
H-1: distance from left and right flange center line to head of 500N, 1000N actuatorH-2: distance from left and right flange center line to head of 1800N, 3000N, 5000N actuator (without manual device)H-3: distance from left and right flange center line to head of 1800N, 3000N, 5000N actuator (with manual device)H-4: distance from left and right flange center line to head of 16000N actuator (with manual device)
BAS valve bodySeries TC500... TC1000... TR1800... TR3000... TR5000... TR16000...Nominal stroke 22mm 22mm 44mm 44mm 44mm 110mm
Nominal output force 500N 1000N 1800N 3000N 5000N 16000N
Basic application
● HVAC TC500.../ TC1000...
TR1800.../ TR3000...
TR5000...
TR16000...
3-position, 24VAC 3-position TC500-D24-S.12 TC1000-D24-S.12 TR1800-D24-S.12 TR3000-D24-S.12 TR5000-D24-S.12 -
proportional, 24VAC 0(2)...10VDC , 0(4)...20mA
TC500-X24-S.12 TC1000-X24-S.12 TR1800-X24-S.12 TR3000-X24-S.12 TR5000-X24-S.12 -
3-position, 220VAC 3-position TC500-D220-S.12 TC1000-D220-S.12 TR1800-D220-S.12 TR3000-D220-S.12 TR5000-D220-S.12 TR16000-XD220-S.12
proportional, 220VAC 0(2)...10VDC , 0(4)...20mA TC500-X220-S.12 TC1000-X220-S.12 TR1800-X220-S.12 TR3000-X220-S.12 TR5000-X220-S.12 TR16000-XD220-S.12
3-position,10K resistance(24VAC / 220VAC) 3-position TC500-D24-SF10K.12/
TC500-D220-SF10K.12TC1000-D24-SF10K.12/TC1000-D220-SF10K.12
TR1800-D24-SF10K.12/TR1800-D220-SF10K.12
TR3000-D24-SF10K.12/TR3000-D220-SF10K.12
TR5000-D24-SF10K.12/TR5000-D220-SF10K.12 -
3 position,2 SPDT feedback(24VAC /220VAC) 3-position TC500-D24-SF2.12/
TC500-D220-SF2.12TC1000-D24-SF2.12/TC1000-D220-SF2.12
TR1800-D24-SF2.12/TR1800-D220-SF2.12
TR3000-D24-SF2.12/TR3000-D220-SF2.12
TR5000-D24-SF2.12/TR5000-D220-SF2.12 -
Valve body Type DN StrokeFlow
parameterKvs
△Ps △Ps △Ps △Ps △Ps △Ps
[mm] [mm] [m3/h] [MPa] [MPa] [MPa] [MPa] [mPa] [MPa]
PN
16 , medium
temperature -25
℃ ~ 150
℃
Flanged water valve
(specilized valve for heating)
TF15-2VGC-S.12 DN15 20 2 1.60 1.60TF20-2VGC-S.12 DN20 20 3 1.10 1.60TF25-2VGC-S.12 DN25 20 5 0.70 1.60TF32-2VGC-S.12 DN32 20 8 0.40 1.60TF40-2VGC-S.12 DN40 20 20 0.25 1.60TF50-2VGC-S.12 DN50 20 31 0.30 0.60TF65-2VGC-S.12 DN65 20 50 0.18 0.45TF80-2VGC-S.12 DN80 20 80 0.30 0.45TF100-2VGC-S.12 DN100 40 125 0.28TF125-2VGC-S.12 DN125 40 200 1.60TF150-2VGC-S.12 DN150 40 300 1.60TF200-2VGC-S.12 DN200 40 520 1.60TF250-2VGC-S.12 DN250 40 750 1.60TF300-2VGC-Y.12 DN300 100 1200 1.60TF350-2VGC-Y.12 DN350 100 1800 1.60TF400-2VGC-Y.12 DN400 100 2200 1.60
PN
16 , medium
temperature 2 ℃
~ 180 ℃
Flanged steam valve
(universal valve for heating and
cooling)
TF15-2SGC-S.12 DN15 20 2 1.60 1.60TF20-2SGC-S.12 DN20 20 3 1.10 1.60TF25-2SGC-S.12 DN25 20 5 1.20 1.60TF32-2SGC-S.12 DN32 20 8 0.80 1.60TF40-2SGC-S.12 DN40 20 20 1.60TF50-2SGC-S.12 DN50 20 31 1.60TF65-2SGC-S.12 DN65 20 50 1.60TF80-2SGC-S.12 DN80 20 80 1.60TF100-2SGC-S.12 DN100 40 125 1.60TF125-2SGC-S.12 DN125 40 200 1.60TF150-2SGC-S.12 DN150 40 300 1.60TF200-2SGC-S.12 DN200 40 520 1.60TF250-2SGC-S.12 DN250 40 750 1.60TF300-2SGC-Y.12 DN300 100 1200 1.60TF350-2SGC-Y.12 DN350 100 1800 1.60TF400-2SGC-Y.12 DN400 100 2200 1.60
PN
16, medium
temperature -25 ℃
~ 150 ℃
+
3-way Flanged water valve
(universal valve for heating and
cooling)
TF15-3VGC-S.12 DN15 20 2 0.80 1.60TF20-3VGC-S.12 DN20 20 3 0.80 1.60TF25-3VGC-S.12 DN25 20 5 0.80 1.60TF32-3VGC-S.12 DN32 20 8 0.80 1.60TF40-3VGC-S.12 DN40 20 20 0.80 1.60TF50-3VGC-S.12 DN50 20 31 0.30 0.60TF65-3VGC-S.12 DN65 20 50 0.25 0.45TF80-3VGC-HS(FS).12 DN80 20 80 0.27 0.45TF100-3VGC-HS(FS).12 DN100 40 125 0.20TF125-3VGC-HS(FS).12 DN125 40 200 0.15TF150-3VGC-HS(FS).12 DN150 40 300 0.10TF200-3VGC-HS(FS).12 DN200 40 520 0.08 0.13TF250-3VGC-HS(FS).12 DN250 40 750 0.05 0.08TF300-3VGC-HY(FY).12 DN300 100 1200 0.25TF350-3VGC-HY(FY).12 DN350 100 1800 0.15TF400-3VGC-HY(FY).12 DN400 100 2200 0.10