Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

  • Upload
    bldp03

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    1/40

    2014

    Jos Slotema (0832917) Wu8

    Mentor: Mr. van den Brink

    Project cordinator: Mr. H. de Klerk

    Company supervisor: Mr. S. de Leeuw

    Department: Mechanical Engineering

    Capelle aan den IJssel

    5/13/2014

    Thesis: Compression Cooling Vs.

    Absorption Cooling

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    2/40

    2

    Jos Slotema Graduation Internship at Technip-EPG

    Prefix

    This report was written as part of the graduation assignment, which is the conclusion of the Bachelor

    of mechanical engineering study at Hogeschool Rotterdam.

    The thesis is the result of a research to an existing compression cooling system with R134a refrigerant

    and an absorption cooling system with R717 (Ammonia) refrigerant. To understand this report some

    experience or knowledge of cooling systems is necessary.

    The thesis was developed in consultation with my dual study supervisor and the lead engineer from

    the mechanical department of Technip-EPG. The choice for the Energy Technologythesis fits well

    with my interest for the cooling industry.

    I want to thank Simon de Leeuw for giving me this opportunity, Johan van den Brink for the guidance,

    Ms. Molt for the English check and specially Hein de Klerk for his corrections, patience and hours of

    beer talk.

    Cheers,

    Jos Slotema

    Rotterdam, May 2014

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    3/40

    3

    Jos Slotema Graduation Internship at Technip-EPG

    Table Of Contents

    Prefix ..................................................................................................................................................2

    1. Abstract ......................................................................................................................................4

    2. Project backgrounds....................................................................................................................5

    2.1 Company .............................................................................................................................5

    2.2 Client ...................................................................................................................................6

    2.3 Situation ..............................................................................................................................6

    2.4 Project .................................................................................................................................6

    3 Existing cooling system................................................................................................................7

    3.1 What are Fluoro-polymers / carbons. ..................................................................................7

    3.2 Analysis of the existing cooling system including backup .....................................................7

    3.3 Brine system ........................................................................................................................8

    3.4 Connection between -30C and -45C system ......................................................................8

    4 Calculations existing -30C R134a system ...................................................................................9

    4.1 Log_P-h diagram R134a .......................................................................................................9

    4.2 Evaporator ........................................................................................................................ 10

    4.3 Compressor ....................................................................................................................... 11

    4.4 Condenser ......................................................................................................................... 13

    4.5 Hot Gas Bypass .................................................................................................................. 15

    4.6 Economizer........................................................................................................................ 15

    4.7 Energy balance .................................................................................................................. 16

    4.8 Check Brine pump capacity ................................................................................................ 17

    5 Explanation absorption cooling process..................................................................................... 18

    5.1 LogP-h R717 ...................................................................................................................... 19

    5.2 Calculations ....................................................................................................................... 20

    6 Comparison both systems ......................................................................................................... 26

    7 Conclusion ................................................................................................................................ 27

    8 Recommendations .................................................................................................................... 27

    9 References ................................................................................................................................ 28

    9.1 Text References ................................................................................................................. 28

    9.2 Figure References .............................................................................................................. 28

    10 Appendices ........................................................................................................................... 29

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    4/40

    4

    Jos Slotema Graduation Internship at Technip-EPG

    1.AbstractFor the production of Fluorocarbons a cooling system is necessary. The production plant at the

    Dordrecht site is using the cooling system for multiple products. This cooling system is split up in a

    primary and a secondary system. The primary system consist of a compression cooling system to cool

    the brine in the secondary system. This system is a circulation system connected to the different

    process users. The existing primary compression cooling system needs to be replaced due to aging

    and reliability.

    An economic comparison should be made for a new absorption cooler fed by waste heat versus a new

    compression cooling system with comparable specifications. Which system is preferable after all

    conditions are taken into consideration?

    The existing -30C R134a refrigeration system at the DuPont site in Dordrecht has been analyzed.

    Calculations have been made and compared with a new absorption cooling system equipped with R717

    or ammonia refrigerant. The result is that if there is enough waste heat to generate the needed amount

    of steam the absorption cooler is in operating conditions cheaper than the existing compression cooler.

    After the results of comparing both systems the energy level of waste heat, necessary to operate the

    absorption system, should be determined.

    In this report the lubrication and the purge unit are not taken in to account for the efficiency of the

    compression cooler. The lubrication for the rotating part is very important for especially the

    compressor. For future calculations this must be taken into account.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    5/40

    5

    Jos Slotema Graduation Internship at Technip-EPG

    2. Project backgrounds

    2.1 Company

    Technip is a world leader in design, engineering, supply and construction of facilities in the oil & gas

    and (petro) chemical industry. Technip-EPG is part of the umbrella organization Technip-Group which

    also includes Technip Benelux BV in Zoetermeer. Technip Group is represented in 48 countries across

    five continents and employs more than 30,000 people. The main business segments in which the

    Technip-Group is active are: Subsea, Offshore and Onshore. Technip boasts a fleet of 34 vessels of

    which five are now being built (1).

    Technip-EPG

    Technip-EPG was acquired by Technip-Group in July 2008 to strengthen Technip Benelux. At that time

    the company EPG (Engineering Project Group) had 35 years of experience in designing plant

    modifications such as modernization and capacity expansion. EPG has 2 locations: Capelle aan den

    IJssel and s-Hertogenbosch. This multidisciplinary engineering company has 150 employees who work

    on fixed or temporary contracts (2).

    The market segments in which Technip-EPG is active:

    1. Oil and Gas

    2. (Petro) Chemicals

    3. Energy and Water

    4. Industry

    5. Utility

    To manage the projects, the project team is divided into the disciplines mentioned below, each withtheir own specialties.

    Project

    HVAC (Heating Ventilation Air Conditioning)

    Electrical & Instrument

    Civil

    Structural

    Pipe stress

    Process

    Piping

    Mechanical

    Document Control

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    6/40

    6

    Jos Slotema Graduation Internship at Technip-EPG

    2.2 Client

    Du Pont de Nemours (Nederland) B.V. is part of the global E. I. Du Pont de Nemours and Company.

    DuPont is a science-based products and services company. Founded in 1802, DuPont puts science to

    work by creating sustainable solutions essential to a better, safer, healthier life for people everywhere.Operating in more than 70 countries, DuPont offers a wide range of innovative products and services

    for markets including agriculture and food; building and construction; communications; and

    transportation.

    The DuPont sites in the Netherlands are situated in Dordrecht, Breda and Landgraaf. DuPont

    Netherlands employs approximately 950 people.

    Dordrecht is one of the largest production sites of DuPont in Europe and it is the companys eldest site

    in the Netherlands. The site is home to nine manufacturing plants where the synthetic resins Delrin

    and Surlyn are made, the refrigerants Isceon and Suva and the Fluorocarbons Teflon and Viton.

    The Teodur Powder Coatings sales organization and the DuPont Crop Protection marketing

    organization are located in Dordrecht as well. The sales organization of Standox automotive

    refinishing paints is located in Breda. The Landgraaf site manufactures filaments for the toothbrush

    industry.

    All production sites of DuPont in the Netherlands are certified according to ISO-9001 (quality) and ISO

    14001 (environment).

    2.3 Situation

    The graduate student is working for the mechanical department of Technip-EPG Capelle aan den IJssel

    as draftsman. During the project the student works solitary. Guidance is provided if necessary. The

    mentor who is guiding this project works for the same department and keeps track of the planning and

    the progress of the project.

    2.4 Project

    For the production of Fluorocarbons a cooling system is necessary. The production plant at the

    Dordrecht site is using the cooling system for multiple products. This cooling system is split up in a

    primary and a secondary system. The primary system consist of a compression cooling system to cool

    the brine in the secondary system. This system is a circulation system connected to the differentprocess users. The existing primary compression cooling system needs to be replaced due to aging

    and reliability. An economic comparison should be made for a new absorption cooler fed by waste

    heat versus a new compression cooling system with comparable specifications. The following must be

    taken into account:

    Safety

    Environment

    Operational costs

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    7/40

    7

    Jos Slotema Graduation Internship at Technip-EPG

    3 Existing cooling system

    3.1 What are Fluoro-polymers / carbons.

    Fluorocarbons are the result of the chemical connection between fluorine and carbon particles. This

    gas is commonly used in Fluoropolymers, refrigerants, solvents and anesthetics.1) A mixture of

    fluorspar, hydrofluoric acid and chloroform (TFE tetrafluorethylene) is heated between 600 and 900C.

    To remove any impurities the gas needs to be distilled. During the distillation process the gas is heated

    and in a special distillation vessel which guide the heated gas thru a pipe system cooled by brine. The

    purified gas condensates and is collected in storage vessels. To store this gas it needs to be at very low

    temperature and pressure to maintain the liquid state of the material. TFE is colorless, odorless and

    extremely flammable (4).

    Fluoropolymers are the result of polymerized TFE. The polymerization process makes long strings of

    the molecules in TFE. To initiate the polymerization process the TFE is guided to special drums

    containing purified water and a small amount of initiators. When the TFE comes in contact with the

    initiator the process is started. The strings of material are formed to grains of PTFE. The grains are

    suspended in the water/initiator solution and will float on the surface. To increase the productivity the

    drum is shaken to mix the water mixture with un-used TFE gas to the mixture. The chemical process is

    producing heat that must be cooled by the brine system that flows thru the jacket of the drum. The

    grains can be sold as bulk or molded into billets (5).

    3.2 Analysis of the existing cooling system including backup

    The cooling system used for the production of fluoro -polymers and carbons is divided into a primary

    and a secondary system as shown in the Process Flow Diagram in figure 1.

    Figure 1: PFD R134a -30C

    The heat produced by the chemical polymerization processes needs to be absorbed and controlled by

    the secondary cooling system (9). The different end users pump their heated cooling medium to a heat

    exchanger which transfers the heat to the brine in the secondary cooling system (1). Because the

    temperature of the brine is lower than the processed cooling medium the cooled brine extracts the

    heat from the cooling medium which can be re-used by the end users.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    8/40

    8

    Jos Slotema Graduation Internship at Technip-EPG

    The brine solution, is pumped (2) to the evaporator (34) to exchange the absorbed heat to the R134a

    gas and is recirculated thru the secondary system. The R134a gas in the primary system is overheated

    due to the low pressure and temperature difference of the R134a. The overheated gas is compressed

    by a 4 stage compressor driven by an E-motor (5). To prevent an unnecessary stop of the compressor,

    the compressed vapor can be redirected to the evaporator by the hot gas by-pass. The high pressure

    Freon gas flows to the condenser (6) where the cooling water from the cooling tower rapidly cools

    down the Freon gas. Condensation of the R134a is realized by the heat exchange in the condenser by

    the cooling water from the cooling tower. The high pressure R134a liquid flows thru a pressure control

    valve (7) where the flow remains equal but the pressure drops to a level where the Freon almost

    evaporates and is transported into the evaporator where the cycle repeats.

    To prevent a shutdown of the plant the cooling system is provided with a backup installation to

    guaranty a continuous flow of cooling. This -45C system is fully separated from the main cooling

    system except for the cooling water produced by the cooling tower Instead of R134a, as used in the -

    30C system. Freon 22is used in the -45C refrigeration system. The connection between both systems

    is further explained in chapter 3.4 of this document.

    3.3 Brine system

    The secondary system is filled with a brine solution.Brine is a commonly used fluid used as a secondary

    refrigerant in large refrigeration installations for thetransport ofthermal energy from one place to

    another. This fluid is easily transported over longer distances and therefore suitable for the use of

    cooling multiple process units. The used type of brine for this installation is Methylene Chloride. For

    properties see figure 2 below.

    Because of the low temperature of -30C a normally used calcium chloride, natrium chloride or

    water/glycol solution is not applicable due to freezing of the fluid. Methylene chloride should not be

    used with aluminium or zinc and it will attack most rubber compounds and plastics. To make sure a

    minimum of temperature is lost during transport the entire system is insulated to maintain the lowtemperature.

    3.4 Connection between -30C and -45C system

    There are 5 different cooling systems present for the production facilities to cool all the necessary

    operations. The -30C and -45C are both connected to the same brine system as previously described.

    Both brine systems are connected with valves en piping spools. Both systems run simultaneously but

    when one needs to shut down the other takes over to maintain a continuous brine flow. Both systems

    have an electrical driven pump which acts as a backup pump for the other system. The complete

    diagram with all the connections is found in appendix 1 of this document.

    Property

    Boiling point 40 C

    Freezing point -97 C

    Vapor pressure at 25C 57 kPa

    Viscosity 0.70 mPa-sec

    Specific heat 1.13 kJ/kg.K

    Thermal conductivity 0.19 W/m.K

    Density 1400 Kg/mFigure 2: Properties Methylene Chloride

    http://en.wikipedia.org/wiki/Brinehttp://en.wikipedia.org/wiki/Refrigeranthttp://en.wikipedia.org/wiki/Transporthttp://en.wikipedia.org/wiki/Thermal_energyhttp://en.wikipedia.org/wiki/Calcium_chloridehttp://en.wikipedia.org/wiki/Natrium_chloridehttp://en.wikipedia.org/wiki/Natrium_chloridehttp://en.wikipedia.org/wiki/Calcium_chloridehttp://en.wikipedia.org/wiki/Thermal_energyhttp://en.wikipedia.org/wiki/Transporthttp://en.wikipedia.org/wiki/Refrigeranthttp://en.wikipedia.org/wiki/Brine
  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    9/40

    9

    Jos Slotema Graduation Internship at Technip-EPG

    4 Calculations existing -30C R134a systemIn this chapter a closer look will be taken at the specific components of the -30C cooling system. For

    further details of the components see appendix 2. The brine should be cooled from -30C to -23,5C.

    To be able to analyze the system a Log_P-h diagram should be made.

    4.1 Log_P-h diagram R134a

    See figure 3 and appendix 3 for completed log_P-h diagram.

    Figure 3: Log_P-h diagram -30C system

    Step 1 2: Evaporator.

    The heated brine evaporates the R134a till an overheated gas is realized. To make sure all the

    refrigerant is evaporated the hot gas bypass from the end of the compressor feeds hot vapor at the

    inlet of the evaporator. The high temperature will overheat the gas when necessary. When fluid enters

    the compressor the rotors will be heavily damaged and the lubrication isnt effective enough to handle

    the high speeds of the rotating parts. The enthalpy of the R134a at the inlet of the evaporator is 182

    kJ/kg. The evaporation temperature is by pressure drops reduced to -33C so it is able to absorb lots

    of heat from the secondary brine system. The pressure of the refrigerant at the outlet of the

    evaporator is equal to the suction pressure at the inlet of the compressor. The enthalpy at this point is

    385 kJ/kg. The temperature of the refrigerant is overheated by 10C to -23C by absorbing heat from

    the brine system. This fully overheated gas is ready to enter the compressor.

    Step 2 3: Compressor

    The compressor compresses the overheated gas from the evaporator from 0,65 bar at the inlet to 7,3

    bar in 4 different stages. The second and third stage are connected with the respectively High and Low

    stage of the economizer. The gas produced due to pressure drops in the economizer is entering the

    compressor at stage 2 and 3. This gas cools the gas from the previous stages of the compressor. This

    helps the compressor increase his efficiency and also prevents the refrigerant from reaching the critical

    temperature of 100.95C (3)from which the refrigerant is not able to condensate/recover any more.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    10/40

    10

    Jos Slotema Graduation Internship at Technip-EPG

    Step 3 4: Condenser

    The gas heated by compression leaves the compressor at 72C and enters the condenser. The cooling

    water from the cooling towers which are pumped thru the tubes of the heat exchanger, absorbs the

    heat from the gas flowing thru the shell side. To make sure all the gas is condensed the R134a is 3C

    sub cooled.

    Step 4 1: Economizer/Choke Valve

    The high pressure R134a liquid is flowing in to the first high pressure stage of the economizer. The

    pressure drop will partially evaporate the R134a condensate. The pressure drops from 7,3 bar to 3 bar

    (Step 4 4). The evaporated R134a flows to the inlet of the third compressor stage. The Condensate

    is then guided to the second low pressure stage of the economizer by a level control valve. The

    pressure drops from 3 to 1,6 bar and the gas flows to the 2ndstage of the compressor (Step 4 4).

    The last stage is the choke valve where the pressure drops to 0,75 bar (Step 4 1). The temperature

    at this point of the cycle is -33C and enters the evaporator to repeat the entire process.

    4.2 Evaporator

    The chiller used in the -30C cooling system is a shell and tube heat exchanger fabricated by Johnson

    Hunt. During normal operation the evaporator absorbs 1880 kW heat from the brine system.

    Figure 4: Evaporator -30C cooling system.

    The absorbed energy from the brine system is 1880 kW (kJ/s).

    is 385-182= 203 kJ/kg. The formula used for calculating the mass-flow is: ( ) = (

    ) \

    = = =9.26 / = 33.34 ton/h

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    11/40

    11

    Jos Slotema Graduation Internship at Technip-EPG

    4.3 Compressor

    The compressor used in the closed circuit R134a refrigeration system is powered by an electric motor

    thru a gearbox. See figure 5 for layout. To prevent excessive wear of the compressor and its

    components the lubrication is closely monitored and controlled.

    Figure 5: Compressor, engine and gear box assembly -30C cooling system.

    The Compressor uses 4 stages to compress the overheated gas from the evaporator from 0,65 bar to

    7,3 bar. See appendix 3 for the Log_P-h diagram. Each vane as seen in figure 6 is specifically shaped

    to increase the pressure at each stage.

    Figure 6: Inside compressor rotor assembly.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    12/40

    12

    Jos Slotema Graduation Internship at Technip-EPG

    Figure 7: Connections of the compressor

    The first compressor stage is connected to the outlet of the evaporator and takes in the overheated

    gas at -23C. The calculated flow of the vapor is 9,26 kg/s as determined in chapter 4.2 of this

    document. The enthalpy is 392 kJ/kg at the end of this stage and the pressure 1,22 bar. At the end of

    the first stage is the released gas from the low pressure side of the economizer added to the gas

    from the first stage. This realizes a temperature drop of +/- 7C, see figure 3.

    Compression ratio for the first stage is:

    1.220.65 =1.877

    The second stage compresses the new gas mixture to 2,45 bar. At the end of the stage the vaporized

    refrigerant from the high pressure stage of the economizer is added to the mixture. The temperature

    drop of the total mixture is +/- 9C for this stage of the compression, see figure 3.

    Compression ratio for the second stage is:

    2.451.22 =2.008

    The third and fourth stages is straight forward with no additional input.

    Compression ratio for the third stage is:

    4.32.45 =1.755

    Compression ratio for the second stage is:

    7.34.3 =1.697

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    13/40

    13

    Jos Slotema Graduation Internship at Technip-EPG

    The power consumption of the compressor is calculated with the compressor specifications in

    Appendix 2.

    Following formula is used:

    = 3

    = 6600 = 114 .=0.893is used because a three phase power supply is used.= 6 6 0 0 1 1 4 0 .8 9 3 = 1160 The efficiency of the compressor is calculated by dividing the input by the output of the compressor.

    =

    Poutis 1120 kW according specifications in Appendix 2.

    = 11201160 =0.96

    4.4 CondenserThe condenser should be able to condensate all the compressed vapor which leaves the compressor.

    To make sure there is no vapor left the refrigerant is sub cooled 3C. the water from the cooling towers

    is led thru the tubes of the heat exchanger (Shell/Tube type). The gas is fed into the topside of the

    condenser in the center shell part. The condensed refrigerant falls to the bottom of the shell. The

    temperature difference of the cooling water between the inlet and the outlet of the condenser is 4.7C.

    Figure 8: Condensor -30C cooling system

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    14/40

    14

    Jos Slotema Graduation Internship at Technip-EPG

    To make the condenser more efficient a two passes system is used. This means that the cooling water

    in the tubes enters in the bottom half of the exchanger redirected thru top part of the condenser. See

    figure 9.

    Figure 9: Inside Condenser during maintenance.

    To calculate the mass-flow of refrigerant thru the condenser the needed capacity from the

    specifications is used, see Appendix 2. The enthalpy is derived from the Log_P-h diagram in appendix

    3.

    The formula used for calculating the mass-flow of the refrigerant is:

    ( ) = ( ) \

    = 3000

    = = 4 3 8 2 3 5 = 2 0 3 =

    = = 14.78 / = 53.2 ton/h

    Cooling water consumption

    =

    = 3 0 0 0 = 4 .1 8 Specific heat of water at 44C(6) = 7 Assumed temperature drop = 30004.187 =102

    102 3600 = 367.200 /

    Density of water at 44C= 990 kg/m (6)

    376.200/990 = 371 m/h

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    15/40

    15

    Jos Slotema Graduation Internship at Technip-EPG

    Figure 10: Cooling water towers used on the plantsite.

    4 5 Hot Gas Bypass

    If the process cooling demand is, for whatever reasons low, the compressed refrigerant from thecompressor is let thru the hot gas bypass. This controlled piping system feeds the refrigerant back

    to the evaporator to avoid shut down of the compressor. The maximum flow thru the hot gas

    bypass is as much as the flow during normal operation. By regulating the feed to the evaporator itis not necessary for the compressor to start and stop when the demand is low. It also makes sure

    the compressed R134a is overheated. = 14.78 / .

    4.6 EconomizerThe economizer used in this system is a horizontal vessel vertically divided in two separate parts. The

    total volume of the vessel is 7,8 m and is also used as storage for the refrigerant. The entire system

    contains 6200 kg R134a, according specs see appendix 2.

    Figure 11: Schematic drawing of the economizer with connections.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    16/40

    16

    Jos Slotema Graduation Internship at Technip-EPG

    The economizer used in the -30C system uses the earlier explained 2 stages to:

    Cool the condensed refrigerant from the condenser.

    Cool the compressed gas in the compressor. Increase the enthalpy of the evaporator.

    Large volume is a buffer for un-used refrigerant.

    The mass flow of refrigerant vapor fed to the compressor is:

    = . . =14.789.26 =5.52/The enthalpy gained by the use of the economizer:

    4 4" = 2 3 5 1 8 2 = 53 /

    4.7 Energy balance

    Energy balance IN OUT

    Evaporator 1880 kW -

    Compressor 1120 kW -

    Condenser - 3000 kW

    COP:

    To calculate the Coefficient Of Performance of the compression cooler the following formula is used:

    =

    =3.8

    Figure 12: Closeup Log_P-h diagram

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    17/40

    17

    Jos Slotema Graduation Internship at Technip-EPG

    4.8 Check Brine pump capacity

    The brine pump is situated before the evaporator of the refrigeration system. The following

    calculations are only applicable for the brine system connected to the -30C refrigeration system.

    To calculate the brine flow the following formula is used:

    = According process data is the temperature difference of the brine 6,5C between the inlet and the

    outlet of the evaporator of the refrigeration system.

    The specific heat and the density of the brine is derived from Figure 2 in chapter 3.3 of this document.

    =

    = 1 8 8 0

    = 1 .1 3 = 6.5 = 18801.136.5 =256

    Pump specifications are given in the unit m/h.

    256 3600 = 921600 /

    Divided by the density of 1400 kg/m gives:

    9216001400 =658 /

    According to pump specifications in appendix 4 the maximum capacity of the pump is 795 m/h.

    658 < 795

    The brine pump has enough capacity to circulate the brine through the system.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    18/40

    18

    Jos Slotema Graduation Internship at Technip-EPG

    5 Explanation absorption cooling processThe compression cooling system will be compared with a single stage absorption cooling system. The

    low pressure part of this system is almost identical with the compression type cooler. To compare both

    systems the absorption cooler will be able to extract the same amount of energy from the heated

    process brine flow. The calculations for the absorption cooler will be done with the refrigerant R717

    which is in fact ammonia (NH3). This refrigerant is at 1 bar (atmospheric pressure) liquid at a

    temperature of -33C. Therefore is no additional vacuum needed to reach the desired temperature to

    cool the brine-flow. During the process NH3 is mixed with water and will the different evaporation

    temperature and pressure used to separate the water and the refrigerant. The amount of NH3 vapor

    that can be absorbed by the water gets bigger by increased pressure and lowers by the increase of

    temperature.

    Figure 13: PFD Absorption cooler

    The heated process brine enters the evaporator where it evaporates the refrigerant. The refrigerant is

    at this stage fully saturated and flows to the absorber. In the absorber the gas is mixed with weak

    liquor from the generator. The mix is cooled down by the cooling water from the cooling towers and

    the refrigerant will condense. The mixture is now called strong liquor due to the higher concentrate of

    refrigerant. In the chapter absorber of this document will the mixing and the strong and weak values

    be explained. The strong liquor is then pumped thru a heat exchanger. The cold strong liquor is pre

    heated by the heated weak liquor from the generator. This pre heating makes sure that there is less

    energy from the steam powered generator needed to evaporate the refrigerant due to a smaller

    temperature difference. The pre heated strong liquor flows after this stage into the generator. The

    generator uses steam to heat the strong liquor till the biggest part of the refrigerant is evaporated. The

    rest of the refrigerant still mixed with water flows thru the previous described heat exchanger and to

    the absorber. The evaporated refrigerant is now entering the condenser. The condenser cools down

    the refrigerant till it is entirely condensed and at a liquid state but at high pressure. A part of the

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    19/40

    19

    Jos Slotema Graduation Internship at Technip-EPG

    condensate is then led into the generator again and is called reflux. This part will help the generator

    to create a constant flow of evaporated refrigerant delivering to the condenser. The rest of the

    condensate flows thru a choke valve where the pressure is dropped till atmospheric pressure and

    repeats the entire process again. See figure 13 and appendix 9 for the process flow diagram.

    5.1 LogP-h R717For support of the calculations with the absorption cooler a log_P-h diagram must be made. Because

    this system does not already exists a few realistic assumptions must be made. See figure 14 for

    details.

    Figure 14: Log_P-h R717 (ammonia, NH3) Refrigerant

    Step 1 2: Evaporator.

    In the evaporator the process brine heat is absorbed and evaporates the R717. A correction must be

    made at the start point of the evaporator the value is derived from figure 14. This correction is used

    with values below 0C. The difference in enthalpy between 0C and -40C is 180 kJ/kg (8). This difference

    must be subtracted from the value of the condensate after the condenser. This brings the start value

    for the evaporator to:

    1=11801=4081801 = 228 /The enthalpy when fully saturated =1417 kJ/kg at 1 bar and -33C.

    Step 2 3: Generator+ Absorber

    For this step the assumption is made that the temperature of the vapor must be at least 165C when

    it enters the condenser. The next assumption is that the temperature at the exit of the condenser is

    44C. The line derived with these values gives an enthalpy of 1829 kJ/kg at 17.3 bar.

    Step 3 4: Condenser

    At the exit of the condenser at the assumed temperature of 44C the enthalpy is 408 kJ/kg.

    Step 4 1: Choke valve and correction

    The pressure is relieved of the condensate.

    4

    1 1

    2

    3

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    20/40

    20

    Jos Slotema Graduation Internship at Technip-EPG

    5.2 Calculations

    All calculations in this chapter are according the book: Kents Mechanical Engineers Handbook,

    Power Volume by J. Kenneth Salisbury 12thedition. All Imperial units are converted into Metric units

    and used in the formulas (8).

    Evaporator

    The evaporator must be able to absorb 1880 kW heat from the brine system.

    Figure 15: Schematic drawing evaporator absorption cool system.

    To calculate the mass-flow of R717 refrigerant the following formula is used:

    ( ) = ( ) \

    =

    =

    =1417228 = 1189 /

    3 = =1.58 / = 5.69 ton/h

    Absorber

    The absorber mixes the weak liquor and the condensed refrigerant by condensing the refrigerant

    with cooling water. The amount of strong liquid is calculated in this chapter. The percentages are

    derived from the table in appendix 5.

    (S) Strong liquor = 26% NH3 dissolved in water (74%H2O)

    (W) Weak liquor = 15% NH3 dissolved in water (85% H2O)

    3 + = The formula for the mixing point is:

    S 0 .7 4 = W 0 .8 5S = 1 . 1 4 9 W

    Figure 16: Schematic drawing absorberabsorption cool system.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    21/40

    21

    Jos Slotema Graduation Internship at Technip-EPG

    3 + = 1.149 1.149 = 0.149=1.58

    = 1.580.149 = 10.6 /

    This result is filled in in the formula for the mixing point to calculate the flow of strong liquor.

    S 0 .7 4 = W 0 .8 5S0.74=10.60.85

    S = 9.010.74 = 12.18 /

    The capacity to condense the flow of vaporized refrigerant is calculated with the following formula:

    = = 1.58 / = =1490405=1085 /

    = 1.58 1085 = 1714

    To calculate the needed amount of cooling water to condensate the refrigerant, the following

    formula is used:

    = Rewritten for mass flow

    =

    = 1 7 1 4

    = 4 ,1 8

    Specific heat of water at 44

    C(6)

    = 7 Assumed temperature drop = 17144.187 =58,6

    58,6 3600 = 210.881 /

    Density of water at 44C= 990 kg/m (6)210.881/990 = 213 m/h

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    22/40

    22

    Jos Slotema Graduation Internship at Technip-EPG

    Pump

    To calculate the needed capacity of the pump the following formula is used:

    =

    = 17.3 = 1730000 /= estimated efficiency of 0,75= 2+3 3 = 681.9 /`at -33C (7)

    2 = 1000 /

    3 12.18 = 26% 3 = 12.18 0.26 = 3.17 = 0.00464

    2 12.18 = 74% 2 = 12.18 0.74 = 9.01 =0.009

    = 0.009 + 0.00464 = 0.0136

    = 0.013617300000.75

    = 31,37

    Figure 17: Absorption cooler pump

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    23/40

    23

    Jos Slotema Graduation Internship at Technip-EPG

    Generator

    The strong liquor is pre heated in the heat exchanger by the weak liquor. After evaporation is a part of

    the refrigerant sent back as reflux. So there are 2 inputs and 3 outputs with different temperatures.

    Figure 18: Schematic drawing generator absorption cool system.

    First the reflux must be determined. According to appendix 5 the minimum amount of reflux ratio is

    0,7. To make the value is not at the bare minimum an assumed safety factor of 1,2 is applied. This

    makes the reflux ratio 0,7*1.2= 0,84. This means that 84% of the high pressure condensate is

    redirected to the generator.

    The next step is to calculate the temperature of the strong liquor at the inlet of the compressor. The

    assumed temperature of 165C is still present in the weak liquor that flows into the heat exchanger

    point 1 on figure 18. The insert temperature of the weak liquor in the generator at point 2 is assumed

    45C. The entrance temperature of the strong liquor in the heat exchanger is assumed 35C at point 3.

    The temperature at point 4 is calculated as follows:

    =

    = = 10.6 /=16545=120C = 12.1 / = 35Filled in in the formula gives:

    10.6120=12.1 35

    1 2

    34

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    24/40

    24

    Jos Slotema Graduation Internship at Technip-EPG

    127212.1 + 3 5 =

    =140CCondenser

    To calculate the needed cooling capacity for the condenser the mass-flow of NH3 at the exit of the

    condenser must be determined.

    85% reflux is what enters the generator and 1,58 kg/s is what enters the evaporator. So 100% NH3 l

    at the exit of the condenser 3is :1,58*1.85 =2.92 kg/s.

    Figure 19: Schematic drawing Condenser absorption cool system.

    To calculate the needed cooling capacity the following formula is used:

    ( ) = (

    ) \ = 44C (See figure 20)

    = 1490.8405.7 = 1085.1 /=2.921085.1=2.921085.1 = 3,17

    Figure 20: Saturation table R717 at 44

    To calculate the needed amount of cooling water to condensate the refrigerant, the following

    formula is used:

    = Rewritten for mass flow

    =

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    25/40

    25

    Jos Slotema Graduation Internship at Technip-EPG

    = 3 1 7 0 = 4 .1 8 Specific heat of water at 44C(6) = 7 Assumed temperature drop

    = 31704.187 =108

    108 3600 = 390.020 /

    Density of water at 44C= 990 kg/m (6)390.020/990 = 394 m/h

    Steam consumption

    To calculate the steam consumption in the generator a separation is made between the capacities IN

    and OUT. The generator is in fact a kind of heat exchanger so the formula used is:

    = 35 45 3 44

    + = + 3 +The values for the weak and strong liquor are derived from appendix 5 in kJ/kg

    +5626.5= 7155+366+3170= 7155+366+31705626.5=5065 The amount of steam necessary for evaporating in the generator is calculated with the following

    formula:

    =

    To derive the enthalpy specific for steam at 165Cthe enthalpy for gas and liquid is derived from thetable in appendix 6. = 5065 = =2762697=2065 /

    = =50652065 = 2,45 /

    Total steam consumption = 8,8 ton/h

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    26/40

    26

    Jos Slotema Graduation Internship at Technip-EPG

    6 Comparison both systemsThe price of a full year of operation is calculated to compare both systems. The prices are estimated

    and the year counts 365 days. The values are in operating condition that means without startup

    Cost Unit

    Cooling water 1000 m 33

    E- Power kWh 0,17

    Steam ton 18

    Compression cooler

    Consumption hour year

    Cooling water 371 m/h 3249960 m 107.248

    E-Power 1160 kW 10,161.600 kWh 1.727.472

    Total 1.834.720

    Absorption cooler

    Consumption hour year

    Cooling water 607 m/h 5.317.320 175.471

    E-Power 31,37 kW 274.801 46.716

    Steam 8820 kg 77.263.200 1.390.737

    Total 1.612.924

    With a difference of 221.796 the absorption cooler is cheaper in operational costs.

    The environmental load of the absorption system is bigger due to toxic NH3 levels.

    Maintenance costs are much lower for the absorption cooler because there are fewer rotating parts

    that need close monitoring of wear tear and lubrication

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    27/40

    27

    Jos Slotema Graduation Internship at Technip-EPG

    7 ConclusionThe Absorption cool system is during a year of 365 days 221.769 cheaper in operational costs than

    the compression cooler. The price for the steam used by the generator is only acceptable if the steam

    can be derived from waste heat from the chemical process.

    8 RecommendationsIn this report the lubrication and the purge unit are not taken in to account for the efficiency of the

    compression cooler. The lubrication for the rotating part is very important for especially the

    compressor. For future calculations this must be taken into account.

    The available waste heat should be calculated.

    The prices used to calculate the operational costs are estimated. For more accurate results the actual

    prices need to be used. Unfortunately I did not had access to these prices.

    Other absorption refrigerants can be calculated for use in the cooling system.

    Multiple stage absorption coolers can be calculated.

    If the absorption cooler is installed proper steps should be taken to prevent the refrigerant to spill in

    the environment due to high toxic levels. The operators must be instructed properly for the use of the

    absorption system.

    Maintenance costs are a big factor in the total costs of the systems so they can be calculated to be

    more accurate.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    28/40

    28

    Jos Slotema Graduation Internship at Technip-EPG

    9 References

    9.1 Text References

    1) Site TP Group,http://www.technip.com/en/about-us/company-profile/technip-glance

    2)

    Site TPEPG,http://www.epg.nl/organisatie/index.php

    3)

    Site Dupont NL,

    http://www2.dupont.com/Dordrecht_Plant_Site/nl_NL/sites_products/ddt/dordrecht.html

    4)

    Fluorocarbons information site,http://en.wikipedia.org/wiki/Fluorocarbon

    5) Teflon information site,http://www.madehow.com/Volume-7/Teflon.html

    6) Water properties, Information site,http://www.engineeringtoolbox.com/water-thermal-

    properties-d_162.html

    7) Log_P-h diagram R717, Appendix 7

    8) Kents Mechanical Engineers Handbook, Power Volume by J. Kenneth Salisbury 12thedition

    chapter 11 Absorption refrigeration, John Wiley & Sons Inc.

    9.2 Figure References

    Figure 1: PFD R134a -30C, Screenshot appendix 8, By J.Slotema

    Figure 2: Properties Methylene Chloride,http://www.inchem.org/documents/pims/chemical

    /pim343.htm

    Figure 3: Log_P-h diagram -30C system, CoolPack program, Microsoft Word, by J.Slotema

    Figure 4: Evaporator -30C system, Picture site visit 3-4-2014

    Figure 5: Compressor, engine and gearbox assembly -30C system, picture site visit 3-4-2014

    Figure 6: Inside compressor rotor assembly, Picture Maintenance 23-9-2009

    Figure 7: Connections of the compressor, Appendix 10, Bentley MicroStation, by J.Slotema Figure 8: Condenser -30C system, Picture site visit 3-4-2014

    Figure 9: Inside Condenser during maintenance, Picture Maintenance 23-9-2009

    Figure 10: Cooling water towers used on the plantsite, picture site visit 3-4-2014

    Figure 11: Schematic drawing of the economizer with connections, Appendix 10, Bentley

    MicroStation, by J.Slotema

    Figure 12: Close-up Log_P-h diagram, Appendix 3, by J.Slotema

    Figure 13: PFD Absorption cooler, Appendix 9, Bentley MicroStation, by J.Slotema

    Figure 14: Log_P-h R717 refrigerant, Appendix 7,CoolPack program, Microsoft Word, by

    J.Slotema

    Figure 15: Schematic drawing evaporator absorption cooling system, Appendix 9

    Figure 16: Schematic drawing absorber absorption cooling system, Appendix 9

    Figure 17: Schematic drawing pump absorption cooling system, Appendix 9

    Figure 18: Schematic drawing pump generator cooling system, Appendix 9

    Figure 19: Schematic drawing pump condenser cooling system, Appendix 9

    Figure 20: Saturation table R717 at 44C, screenshot CoolPack program

    http://www.technip.com/en/about-us/company-profile/technip-glancehttp://www.technip.com/en/about-us/company-profile/technip-glancehttp://www.technip.com/en/about-us/company-profile/technip-glancehttp://www.epg.nl/organisatie/index.phphttp://www.epg.nl/organisatie/index.phphttp://www.epg.nl/organisatie/index.phphttp://www2.dupont.com/Dordrecht_Plant_Site/nl_NL/sites_products/ddt/dordrecht.htmlhttp://www2.dupont.com/Dordrecht_Plant_Site/nl_NL/sites_products/ddt/dordrecht.htmlhttp://en.wikipedia.org/wiki/Fluorocarbonhttp://en.wikipedia.org/wiki/Fluorocarbonhttp://en.wikipedia.org/wiki/Fluorocarbonhttp://www.madehow.com/Volume-7/Teflon.htmlhttp://www.madehow.com/Volume-7/Teflon.htmlhttp://www.madehow.com/Volume-7/Teflon.htmlhttp://www.engineeringtoolbox.com/water-thermal-properties-d_162.htmlhttp://www.engineeringtoolbox.com/water-thermal-properties-d_162.htmlhttp://www.engineeringtoolbox.com/water-thermal-properties-d_162.htmlhttp://www.engineeringtoolbox.com/water-thermal-properties-d_162.htmlhttp://www.inchem.org/documents/pims/chemical%20%20/pim343.htmhttp://www.inchem.org/documents/pims/chemical%20%20/pim343.htmhttp://www.inchem.org/documents/pims/chemical%20%20/pim343.htmhttp://www.inchem.org/documents/pims/chemical%20%20/pim343.htmhttp://www.inchem.org/documents/pims/chemical%20%20/pim343.htmhttp://www.inchem.org/documents/pims/chemical%20%20/pim343.htmhttp://www.engineeringtoolbox.com/water-thermal-properties-d_162.htmlhttp://www.engineeringtoolbox.com/water-thermal-properties-d_162.htmlhttp://www.madehow.com/Volume-7/Teflon.htmlhttp://en.wikipedia.org/wiki/Fluorocarbonhttp://www2.dupont.com/Dordrecht_Plant_Site/nl_NL/sites_products/ddt/dordrecht.htmlhttp://www.epg.nl/organisatie/index.phphttp://www.technip.com/en/about-us/company-profile/technip-glance
  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    29/40

    29

    Jos Slotema Graduation Internship at Technip-EPG

    10Appendices

    Appendix 1: Routing diagram between cooling systems.................. 30

    Appendix 2: Component description -30C cooler.. 31-32

    Appendix 3: Log_P-h diagram -30C cooler

    .. 33

    Appendix 4: Brine circulation pump specifications.. 34

    Appendix 5: Aqua Ammonia chart .. 35

    Appendix 6: Steam Saturation table .. 36

    Appendix 7: Log_P-h R717................. 37

    Appendix 8: PFD Compression cooler... 38

    Appendix 9: PFD Absorption cooler.................39

    Appendix 10: PFD Compressor, Economizer.... 40

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    30/40

    30

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 1: Routing diagram between cooling systems.

    Information obtained from site visit 3-4-2014, Drawing DuPont.

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    31/40

    31

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 2: Component description -30C cooler.

    Information obtained from site visit 3-4-2014

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    32/40

    32

    Jos Slotema Graduation Internship at Technip-EPG

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    33/40

    33

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 3: Log_P-h diagram -30C cooler.

    CoolPack program, Microsoft Word and Excel

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    34/40

    34

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 4: Brine circulation pump specifications.

    Information obtained from site visit 3-4-2014

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    35/40

    35

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 5: Aqua Ammonia chart.

    Kents Mechanical Engineers Handbook, Power Volume by J. Kenneth Salisbury 12thedition, figure 19

    page 11-32

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    36/40

    36

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 6: Steam Saturation table

    http://www.stoommachine.info/tabel.html

    http://www.stoommachine.info/tabel.htmlhttp://www.stoommachine.info/tabel.htmlhttp://www.stoommachine.info/tabel.html
  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    37/40

    37

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 7: Log_P-h R717

    CoolPack program, Microsoft Word and Excel

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    38/40

    38

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 8: PFD Compression cooler

    Bentley MicroStation, By J.Slotema

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    39/40

    39

    Jos Slotema Graduation Internship at Technip-EPG

    Appendix 9: PFD Absorption cooler

    Bentley MicroStation, By J.Slotema

  • 8/9/2019 Thesis Compression cooling vs Absorption cooling (Jos Slotema Wu8 0832917).pdf

    40/40

    40

    Appendix 10: PFD Compressor, Economizer

    Bentley MicroStation, By J.Slotema