    PreDiCon Ltd.

    Work Request # 234Client Maintenance

    Area Customer

    System Electrical Distribution

    Location Substation #1

    Equipment Transformer #3

    Component Connection Box

    Priority No 1

    Priority Description Within 2 days

    Analyst Ron Frend

    Reports Date 20-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    While the body of the transfomer is no more than 35'C at any point, the top of the connection box is showing a high temperature at over 57'C. The most probable casue for this high temperature is a resistance connection inside the connection box.

    Recommendations Check the connection box internals as a matter of urgency and remake all electrical connections therein.

    Figure #1

    15.6C

    59.0C

    20

    30

    40

    50

    Conn Box Top: 57.3C

    Cable: 22.4C

    Transformer Body Top: 26.9C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 235Client Maintenance

    Area Customer

    System Electrical Distribution

    Location Boiler House

    Equipment EP713

    Component Top left fuse

    Priority No 3

    Priority Description When convenient

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    The left most fuse on the upper bank is considerably warmer than all others.

    Recommendations The circuit should be checked for load. Then replace the fuse, clean the fuse clips and check terminations for security.

    Figure #1

    23.6C

    32.2C

    24

    26

    28

    30

    32Fuse: 33.0C

    Background: 27.9C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 236Client Maintenance

    Area Customer

    System Conveyors

    Location Mill Room

    Equipment Elevator E4

    Component Gearbox

    Priority No 2

    Priority Description Within 1 month

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    The input shaft on this gearbox is hot at over 80'C. This is most likely indicative of a bad bearing or possibly bad gears.

    Recommendations The gearbox should be overhauled.

    Figure #1

    18.6C

    62.6C

    20

    30

    40

    50

    60

    Input Shaft: 80.1C

    Background: 19.0C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 237Client Maintenance

    Area Customer

    System Mash Tuns

    Location Underneath Mash Tuns 1/2/3

    Equipment Discharge Screw

    Component Gearbox

    Priority No 3

    Priority Description When convenient

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    Even though the discharge screw was lightly loaded at the time of measurement, the input shaft bearings were over 40'C. This is indicative of overloaded bearings or low oil level.

    Recommendations Check the gearbox oil level. If oil level is OK then overhaul the gearbox. On reassembly pay particular attention to the mounting arrangement for the motor to avoid misalignment.

    Figure #1

    22.5C

    40.5C

    25

    30

    35

    40Background: 26.2C

    Gbx Brgs: 40.5C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 238Client Maintenance

    Area Customer

    System Hot Liquor Ring Main

    Location Cellar #2

    Equipment Hot Liquor Ring Main Pump #1

    Component Motor

    Priority No 2

    Priority Description Within 1 month

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    The pump drive motor drive end bearing is relatively hot at over 50'C. This could be caused by over greasing, misalignment or bearing deterioration.

    Recommendations Monitor the bearing temperature in the short term. Arrange to change the motor bearings and carry out an alignment of the motor to the pump.

    Figure #1

    17.1C

    54.2C

    20

    30

    40

    50Drive End Bearing: 52.0C

    Background: 15.1C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 239Client Maintenance

    Area Customer

    System Electrical Distribution

    Location Switch Room G

    Equipment Panel EP301

    Component Fuse 18

    Priority No 3

    Priority Description When convenient

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    This fuse is warmer than all others on this panel. Cause may be load or a resistance connection or even a bad fuse.

    Recommendations Check the load. If the load is low then replace the fuse and remake all connections including cleaning the fuse clips.

    Figure #1

    14.1C

    27.4C

    16

    18

    20

    22

    24

    26Fuse 18: 29.4C

    Background: 15.3C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 240Client Maintenance

    Area Customer

    System Electrical Distribution

    Location Filtration Control Room

    Equipment Filter Room PLC Panel Power Section

    Component Transformer

    Priority No 2

    Priority Description Within 1 month

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    The bottom right connection on the front of the transformer is hot almost 70'C while the transformer is only 45'C. The pattern of heat distribution indicates a resistance joint in the connection block.

    Recommendations Clean and retighten the connections.

    Figure #1

    28.4C

    65.7C

    30

    40

    50

    60

    Btm Right Conn: 69.8C

    Cable temp: 54.1C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 241Client Maintenance

    Area Customer

    System Electrical Distribution

    Location Filtration Control Room

    Equipment Filter Room PLC Panel Power Section

    Component Contactor CTR01

    Priority No 2

    Priority Description Within 1 month

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    Connection 59 (behind connection 90) is hot. This is caused by a bad connection with the consequent resistance causing an increase in temperature.

    Recommendations Remake connection 59. Clean and tighten.

    Figure #1

    25.8C

    55.3C

    30

    40

    50

    Conn 59: 58.3C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 242Client Maintenance

    Area Customer

    System Electrical Distribution

    Location DAIKIN 1/2/3 Chiller Room

    Equipment No.1 DAIKIN Compressor Control Panel

    Component Connection 152

    Priority No 2

    Priority Description Within 1 month

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    Connection 152 appears to have a resistance at the crimp causing a high temperature.

    Recommendations Remake the cable crimp on connection 152. Clean & retighten.

    Figure #1

    24.1C

    42.0C

    25

    30

    35

    40

    Connection 152: 42.5C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request # 243Client Maintenance

    Area Customer

    System Electrical Distribution

    Location DAIKIN 1/2/3 Chiller Room

    Equipment No.1 DAIKIN Compressor Panel

    Component Contactor CR017

    Priority No 2

    Priority Description Within 1 month

    Analyst Ron Frend

    Reports Date 21-Feb-02

    Inspection Date 20-Feb-02

    Analysis and Comments

    The overloads on this contactor are very hot at over 100'C. This indicates that the overloads are nearing the end of their life.

    Recommendations Change the overload elements.

    Figure #1

    20.2C

    91.8C

    40

    60

    80

    Overload: 100.9C

    Figure #2

    Comments on Completion

    Completion Date: Approved for Issue by:

    Predictive Maintenance Work Request Thermography

    Please complete this form and return to PreDiCon on completion of work on Fax (01253) 400552

    Print Name Above

    Sign Above

    Issue Date

  • PDCreionWilmar House23-25 Windermere Road,Blackpool FY4 2BXtel: (01253) 400541fax: (01253) 400552email: [email protected]

    PreDiCon Ltd.

    Work Request Summary Work Request Number Location Equipment Component Description

    Substation #1 Transformer #3 Connection Box Check the connection box internals as a matter of urgency and remake all electrical connections therein.234

    Boiler House EP713 Top left fuse The circuit should be checked for load. Then replace the fuse, clean the fuse clips and check terminations for security.235

    Mill Room Elevator E4 Gearbox The gearbox should be overhauled.236

    Underneath Mash Tuns 1/2/3

    Discharge Screw Gearbox Check the gearbox oil level. If oil level is OK then overhaul the gearbox. On reassembly pay particular attention to the mounting arrangement for the motor to avoid misalignment.

    237

    Cellar #2 Hot Liquor Ring Main Pump #1

    Motor Monitor the bearing temperature in the short term. Arrange to change the motor bearings and carry out an alignment of the motor to the pump.

    238

    Switch Room G

    Panel EP301 Fuse 18 Check the load. If the load is low then replace the fuse and remake all connections including cleaning the fuse clips.239

    Filtration Control Room

    Filter Room PLC Panel Power Section

    Transformer Clean and retighten the connections.240

    Filtration Control Room

    Filter Room PLC Panel Power Section

    Contactor CTR01 Remake connection 59. Clean and tighten.241

    DAIKIN 1/2/3 Chiller Room

    No.1 DAIKIN Compressor Control Panel

    Connection 152 Remake the cable crimp on connection 152. Clean & retighten.242

    DAIKIN 1/2/3 Chiller Room

    No.1 DAIKIN Compressor Panel

    Contactor CR017 Change the overload elements.243