44
The Role of Buildings in Smart Grid Linda, Fu Xiao and Shengwei Wang Department of Building services Engineering Building Energy and Automation Research Laboratory Research Institute of Sustainable Urban Development The Hong Kong Polytechnic University [email protected] 5 th International conference on Energy – Sustainable Energy Policies and Technologies 15-17 October 2014, Hong Kong

The Role of Buildings in Smart Grid - Energy Inst Prof Shengwei... · 2015. 9. 7. · The Role of Buildings in Smart Grid Linda, Fu Xiao and Shengwei Wang . Department of Building

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • The Role of Buildings in Smart Grid

    Linda, Fu Xiao and Shengwei Wang Department of Building services Engineering

    Building Energy and Automation Research Laboratory Research Institute of Sustainable Urban Development

    The Hong Kong Polytechnic University [email protected]

    5th International conference on Energy – Sustainable Energy Policies and Technologies 15-17 October 2014, Hong Kong

    mailto:[email protected]

  • Outline of Presentation 1. Brief Introduction of Smart Grid 2. Building Demand Side Management (DSM) 2.1 Outline of DSM Methods for Buildings 2.2 Load Management in Buildings 2.3 Energy Efficiency Improvement – An Example 3. Interactions between Buildings and Smart Grid 4. Proactive “Building Cooling Supply Side” Management

  • 1.Brief Introduction of Smart Grid 2. Building Demand Side Management 3. Interaction between Buildings and Smart Grid 4. Proactive “Building Cooling Supply Side” Management

  • Peak load: affects grid safety

    and wastes extra energy and cost due to the essential generation capacity reserve.

    50.2

    50.0

    49.8

    Power imbalance: decreases power quality of grid and requires more frequency controlled reserve, especially when large amount of fluctuant renewable generations are used

    and integrated to grid today.

    1.1 Critical Issues in Power Grid load profile of end-users

    renewable energies

  • Framework of Smart Grid

    Smart grid is considered as a promising solution concerning its improvements and benefits in power reliability, energy efficiency, economics and sustainability.

    1.2 Development of Smart Grid

    Smart grid involves micro-grid, renewable energies, smart metering system, information and communication technologies, demand response, intelligent energy management system, etc.

    Smart grid is a type of electrical grid with prediction and intelligent response to the behaviors and actions of all power participants.

    China

  • Information and Communication Technologies (ICTs)

    [Source: NIST Framework and Roadmap for Smart Grid Interoperability Standards]

    Click Here: Smart Metering Projects Map

    Smart Metering System

    1.3 Available Technologies for Smart Grid

    http://maps.google.com/maps/ms?ie=UTF8&oe=UTF8&msa=0&msid=115519311058367534348.0000011362ac6d7d21187

  • 1. Brief Introduction of Smart Grid

    2. Building Demand Side Management 2.1 Outline of DSM Methods for Buildings 2.2 Load Management in Buildings 2.3 Energy Efficiency Improvement – An Example 3. Interaction between Buildings and Smart Grid 4. Proactive “Building Cooling Supply Side” Management

  • Power Supply – Power Demand

    Mismatching between Supply and Demand

    Demand Side Management Supply Side Management

    1. Reducing Energy consumption by Increasing Energy Efficiency

    2. Peak Demand limiting/Load shifting

  • The DSM methods in buildings basically consist of load management and energy efficiency improvement.

    2.1 Outline of DSM Methods for Buildings

  • Efficiency and

    Conservation (Daily) Peak Load

    Management (Daily) Demand Response

    (Dynamic Event Driven)

    Motivation

    Economic;

    Environmental protection;

    Resource availability;

    TOU savings;

    Peak demand charges;

    Reliability

    Emergency supply

    Operations Integrated system operations

    Demand limiting

    Demand shifting

    Demand shedding

    Demand shifting

    Demand limiting

    2.1 Outline of DSM Methods for Buildings

  • 11 Thermal Storage - 1

    Energy Storage Methods

    Mechanical energy storage

    Thermal energy storage

    Magneticstorage

    Biological storage

    Chemical energy storage

    Hydro-storage

    Fly-wheels

    Compressed air storage

    Electrochem-ical batteries

    Organic mol-ecular storage

    Sensibleheat storage

    Latent heat storage

    Energy storage is critically important to the success of any intermittent energy source in meeting demand.

    Thermal energy storage (TES) is an effective energy management technology that has attracted increasing interest by building professionals for load management.

    2.2 Load Management in Buildings

  • • Centralized Thermal Energy Storage Involving one/more major storage devices (e.g. tanks) which usually are of big volume, such as ice storage, etc. • Decentralized Thermal Energy Storage Opposite to centralized systems, cold/heat are stored in various small storage devices distributed in buildings. • Use of Building Thermal Mass and Building Structures (Integrated with Phase Change Materials) Building itself used as a thermal energy storage; PCM integrated with building structures to increase building thermal mass/performance.

    (2.2) Means of Thermal Storage in Buildings

  • Cooling Plant

    Evaporators

    Condensers

    Air

    Handling

    Unit

    Air

    Handling

    Unit

    Building

    Cooling Plant

    Evaporators

    Condensers

    Evaporators

    Condensers

    Evaporators

    Condensers

    Air

    Handling

    Unit

    Air

    Handling

    Unit

    Building PCM

    To enhance storage capability of buildings, phase change material (PCM) is being considered in recent years.

    Phase change materials have the ability to provide high energy storage density and can store thermal energy at a relatively constant temperature.

    H(k

    J/kg)

    T (°C )

    Heating Process(Solid)

    Phase changeprocess

    Heating Process(Liquid)

    Tm

    ε ε

    Pure substancesRealistic

    Ideal

    It is a promising method for the buildings since most buildings today are designed with light-weighted structures.

    (2.2) Load Management – Building Integrated with Phase Change Materials

  • A Case Study of using PCM in Building Structures for Load Management in Hong Kong

    Zone 1

    145m2Zone 2

    175m2Zone 3

    175m2Zone 4

    145m2

    Zone 5

    110m2Zone 7

    153m2Zone 8

    153m2Zone 6

    110m2

    North

    West East

    20

    22

    24

    26

    28

    0 12 24 36 48 60 72 84 96 108 120

    Time (h)

    Tem

    pera

    tute

    of z

    one

    4 (℃

    ) Reference SSPCM

    Brick wall

    PCM layer

    IndoorOutdoor

    Hong Kong Test Case (HKD)

    Reference building

    PCM building

    Cost saving

    Normal control 1083.5 1026 5.31%

    Demand Limiting Control

    1082.7 968.5 10.55%

    Overall cost saving

    0.07% 5.6% 10.61%

    Proper use of PCMs in buildings supported by optimal control strategies can reduce the overall electricity of buildings significantly with better thermal comfort.

    (2.2)

  • 490 m 118 F

    Six-star Hotel

    High-rank commercial office

    Commercial center and basement

    Floor Area:

    Hotel 70,000 (m2)

    Office 286,000 (m2)

    Commercial center 67,000(m2)

    Gross area 440,000 (m2)

    Experiences in A Super-high-rise Building -International Commerce Centre (ICC)

    2.3 Energy Efficiency Improvement – An Example

  • EVAPORATOR EVAPORATOR EVAPORATOR EVAPORATOREVAPORATOR

    COOLINGTOWER 2

    COOLINGTOWER 4

    COOLINGTOWER 3

    COOLINGTOWER 6

    COOLINGTOWER 5

    COOLINGTOWER 8

    COOLINGTOWER 7

    COOLINGTOWER 1

    COOLINGTOWER 11

    COOLINGTOWER 9

    COOLINGTOWER 10

    EVAPORAROR

    WCC-06a-01(2040 Ton)

    PCHWP-06-01

    FROM OFFICCE FLOORS(7-41)

    TO OFFICE FLOORS(7-41)

    HX HX HX HX HX HX HX

    PCHWP-06-02 PCHWP-06-03 PCHWP-06-04 PCHWP-06-05 PCHWP-06-06

    WCC-06a-02(2040 Ton)

    WCC-06a-04(2040 Ton)

    WCC-06a-03(2040 Ton)

    WCC-06a-05(2040 Ton)

    WCC-06a-06(2040 Ton)

    CDWP-06-01 CDWP-06-02 CDWP-06-04CDWP-06-03 CDWP-06-05 CDWP-06-06

    CT-06a-01 CT-06a-02 CT-06a-03 CT-06a-04 CT-06a-05 CT-06a-06 CTA-06a-01 CTA-06a-02 CTA-06a-03 CTA-06a-04 CTA-06a-05G

    Cooling tower circuit

    A

    F

    D

    CA

    B

    E

    B

    D

    C

    EFG

    Secondary water circuit for Zone 1

    Secondary water circuit for Zone 2

    Secondary water circuit for Zone 3 and Zone 4

    Primary water circuit

    Chiller circuit

    Cooling water circuit

    (S-B

    )

    FROM PODIUM & BASEMENT

    TO PODIUM & BASEMENT

    HX HX (S

    -B)

    (S-B

    )

    (S-B

    )

    FROM OFFICE FLOORS (43-77)

    TO OFFICE FLOORS (43-77)

    (S-B

    )

    CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER

    HXHXHX

    TO OFFICE FLOORSS (79-98)

    FROM OFFICE FLOORS (79-98)

    (S-B

    )(S

    -B)

    SCHWP-42-01 to 03SCHWP-42-04 to 06

    SCHWP-78-01 to 03

    PCHWP-78-03PCHWP-78-01 PCHWP-78-02

    PCHWP-42-01 PCHWP-42-02 PCHWP-42-03 PCHWP-42-04 PCHWP-42-05 PCHWP-42-06 PCHWP-42-07

    SCHWP-06-06 to 09

    SCHWP-06-03 to 05

    SCHWP-06-01 to 02

    SCHWP-06-10 to 12

    CTA Towers (without heating coil) CTB Towers (with heating coil)

    Central Cooling System

    (2.3)

  • • Verifying/improving the system configuration and component selection including the chiller system, water system (primary/secondary system), heat rejection system (cooling towers), fresh air system etc.

    • Verifying and improving the metering system for proper local control, and the original proposed control logics at the design stage.

    • Proposal of additional metering system for implementing supervisory control and diagnosis strategies and related facilities for implementing these strategies.

    Design commissioning mainly concerns the future operation and control performance of HVAC systems, including:

    The typical energy-saving efforts from the design and the installation phases

    (2.3) Commissioning at Design Stage

  • HX-42 HX-42 HX-42 HX-42 HX-42 HX-42 HX-42

    (S-B

    )

    FROM OFFICE FLOORS (43-77)

    TO OFFICE FLOORS (43-77)

    (S-B

    )

    HX-78HX-78HX-78

    TO OFFICE FLOORSS (79-98)

    FROM OFFICE FLOORS (79-98)

    (S-B

    )(S

    -B)

    SCHWP-42-01 to 03SCHWP-42-04 to 06

    SCHWP-78-01 to 03

    SCHWP-06-06 to 09

    To Z

    one

    3&4

    From

    Zon

    e 3&

    4

    Flow meter

    Bypass valve

    EVAPORATOR EVAPORATOR EVAPORATOR EVAPORATOREVAPORATOREVAPORAROR

    WCC-06a-01(2040 Ton)

    PCHWP-06-01

    FROM OFFICCE FLOORS(7-41)

    TO OFFICE FLOORS(7-41)

    HX-42

    PCHWP-06-02 PCHWP-06-03 PCHWP-06-04 PCHWP-06-05 PCHWP-06-06

    WCC-06a-02(2040 Ton)

    WCC-06a-04(2040 Ton)

    WCC-06a-03(2040 Ton)

    WCC-06a-05(2040 Ton)

    WCC-06a-06(2040 Ton)

    CDWP-06-01 CDWP-06-02 CDWP-06-04CDWP-06-03 CDWP-06-05 CDWP-06-06

    A

    F

    D

    CA

    B

    E

    B

    D

    C

    EF

    Secondary water circuit for Zone 1

    Secondary water circuit for Zone 2

    Secondary water circuit for Zone 3 and Zone 4

    Primary water circuit

    Chiller circuit

    Cooling water circuit

    (S-B

    )

    FROM PODIUM & BASEMENT

    TO PODIUM & BASEMENT

    HX-06

    (S-B

    )(S

    -B)

    (S-B

    )

    FROM OFFICE FLOORS (43-77)

    TO OFFICE FLOORS (43-77)

    (S-B

    )

    CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER

    HX-78HX-78HX-78

    TO OFFICE FLOORSS (79-98)

    FROM OFFICE FLOORS (79-98)

    (S-B

    )(S

    -B)

    SCHWP-42-01 to 03SCHWP-42-04 to 06

    SCHWP-78-01 to 03

    PCHWP-78-03PCHWP-78-01 PCHWP-78-02

    PCHWP-42-01 PCHWP-42-02 PCHWP-42-03 PCHWP-42-04 PCHWP-42-05 PCHWP-42-06 PCHWP-42-07

    SCHWP-06-06 to 09

    SCHWP-06-03 to 05

    SCHWP-06-01 to 02

    SCHWP-06-10 to 12

    To cooling towersFrom cooling towers

    HX-42 HX-42 HX-42 HX-42 HX-42 HX-42

    HX-06

    Original System Revised System

    Secondary water loop systems of 3rd/4th zones

    Primary pumps are omitted

    (2.3) System Design Optimization

  • Comparison between Two systems

    0

    200

    400

    600

    800

    1000

    1200

    1400

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Time (h )

    Pum

    p po

    wer

    (kW

    )

    Original designAlternative design

    Typical sunny-summer day

    Annual Pump Energy Saving is 1M kWh

    (2.3)

  • Optimal control strategies for central air-conditioning systems Chiller sequence, optimal start-up Optimal chiller sequence - based on a more accurate cooling load

    prediction using data fusion method, and considering demand limiting.

    Adaptive online strategy for optimal start - based on simplified sub-system dynamic models.

    Ventilation strategy for multi-zone air-conditioning system Optimal ventilation control strategy - based on ventilation demands of

    individual zones and the energy benefits of fresh air intake.

    (2.3)

  • Chilled water system optimization

    Optimal pressure differential set point reset strategy;

    Optimal pump sequence logic;

    Optimal heat exchanger sequence logic;

    Optimal control strategy for pumps in the cold water side of heat exchangers;

    Optimal chilled water supply temperature set-point reset strategy.

    Cooling water system optimization

    Optimal condenser inlet water temperature set point reset strategy;

    Optimal cooling tower sequence.

    Optimal control strategies for central air-conditioning systems

    (2.3)

  • • 1,000,000 kWh (about 2.2% of energy consumption) saving due to the modification on the secondary water loops of Zone 3 & 4.

    • 2,360,000 kWh (about 5.1% of annual energy consumption of chillers and cooling towers of the cooling system) saving due to the change from single speed to variable speed using VFD.

    • 607,000 kWh (about 2.8% of annual energy consumption of chillers and cooling towers of the cooling system) saving by modifying the lowest frequency is limited at 37Hz.

    • 3, 500,000 kWh (about 7% of the total energy consumption of HVAC system) saving by using PolyU control strategies based on the original design.

    Summary of Energy Benefits in ICC

    Saving by Control Optimization – compared with the case when the HVAC system operates correctly as the original design intent.

    About 3.5M per year

    Saving by Commissioning (Improving the system configuration and selection) – compared with the original design.

    About 3.5 M per year The annual total energy saving

    is about 7.0M kWh !

    (2.3)

  • 1. Brief Introduction of Smart Grid 2. Building Demand Side Management

    3.Interactions between Buildings and Smart Grid

    4. Proactive “Building Cooling Supply Side” Management

  • 01 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    Pow

    er S

    uppl

    y an

    d D

    eman

    d (M

    W)

    Time (hours)

    Power Demand

    Power Supply

    Power Surplus

    Power Shortage Power Surplus

    Power Surplus

    3.1 Interactions between Buildings and Smart Grid

  • Power Supply Power Demand

    Power Stations Building Sectors

    Power Flow (transmission & distribution)

    Information Flow (monthly bill)

    “One-way” Operation of Conventional Power Grid (3.1)

    Online

    Offline

    “One-way” approach: Operation online but Communication with outdated information. Buildings cannot help relieve power imbalance timely using demand response.

  • Power Supply Power Demand

    Power Stations Building Sectors

    Power Flow (distributed generation)

    Information Flow (information & communication technologies)

    Renewable Generations

    “Two-way” Operation of Smart Grid (3.1)

    Online

    Online

    “Two-way” approach enable smart grid to achieve a better overall performance of all participants when integrated with distributed generation and storage.

  • WEATHER DATA

    INTERNAL GAIN

    HVAC SYSTEMS OPTIMAL CONTROL STRATEGIES

    BUILDING LOAD AGGREGATION

    BUILDINGS LOAD PREDICTION

    DYNAMIC PRICING

    OPTIMAL SETTING Smart Grids

    Illustration of the interactive Concept (3.1)

  • Supply Curve: electricity price Increases when demand increases

    Demand Curve: demand decreases when electricity price increases

    Price ($/KWh)

    Demand (KWh)

    Supply Curve Demand Curve

    Resulting Price

    Initial Demand

    Resulting Demand

    Final Demand

    Dynamic Pricing in a Certain Time Interval [Source: Fred C. Schweppe et al., 1988]

    Electricity pricing is the essential incentive to encourage demand responses

    3.2 Principle of Dynamic Pricing

  • Cap

    acity

    & L

    oad

    Pr

    ofile

    Time (24 hr.)

    smart grid power capacity

    smart grid optimal operation profile

    end-users load profile at price α , β

    Cap

    acity

    & L

    oad

    Pr

    ofile

    Time (24 hr.)

    end-users load profile at price α′ , β′

    adjust electricity price from α , β to α′ , β′

    smart grid power capacity

    smart grid optimal operation profile

    Illustration of load profile alteration under incentive prices Objective of the Interaction under Dynamic Pricing (3.2)

    Overall energy efficiency of smart grid can be improved by approaching overall balance of power supply and demand sides.

    Operation cost savings of end-users can also be achieved and benefit in the form of electricity prices.

  • The integration of smart metering system with BAS

    Possibility of Establishing Interaction Integrated with smart meters and grid information management and control centre, Building Automation Systems (BASs) can provide valuable information and communication (e.g. energy demand characteristics) for grid optimization.

    (3.1)

  • Grid Dynamic Pricing Setting

    Altered Building Power Demand

    Predictor

    Building Power Demand Predictor

    Building Power Demand Alteration

    Potential Characterization

    Pi: the reference power demand prediction of the ith building

    Indices Pi

    Pi′

    Pi′: the altered power demand prediction of the ith building

    r

    Building Optimal Power Demand Control

    r: the finalized electricity prices

    Smart Grid Information Management and Control Center

    Building Automation System

    Intelligent Field Devices

    (Offline Process)

    (Online Process)

    (Online Process)

    r′: the trial electricity prices

    r′

    Other Buildings

    Other Buildings

    Interactive Building Power Demand Management Strategy

    Building Power Alteration Estimation

    Building-Smart Grid Interaction

    Building Power Demand

    Management

    (3.1)

  • 1. Brief Introduction of Smart Grid 2. Building Demand Side Management 3. Interaction between Buildings and Smart Grid

    4.Proactive “Building Cooling Supply Side” Management

  • • HVAC systems count for nearly 50%-60% of the total electricity consumption of buildings.

    Power Grid HVAC Systems Electricity Cooling

    To maintain thermal comfort

    4.1 Building Cooling Load Management

    • Increase/decrease of building cooling demand can significantly change power consumption of the HVAC system, then the buildings.

    - Reduce building cooling demand in the case of grid power supply shortage.

    - Increase building cooling demand in the case of grid power supply surplus.

  • - Conventional Method

    HVAC Systems Cooling

    To maintain thermal comfort

    Cooling supply side Cooling demand side

    Conventional Method: cooling demand side management - Change the building indoor air temperature (Tindoor)

    Limitation: - Long time required to reduce the HVAC power demand due

    to the building thermal capacity.

    4.1 Building Cooling Load Management

  • Example of the Building Cooling Reduction

    • Indoor temperature set-point reset (1℃ increase)

    7

    9

    11

    13

    9 11 13 15 17

    HVA

    C P

    ower

    C

    onsu

    mpt

    ion

    (MW

    )

    Pnormal Plimit

    15

    20

    25

    30

    35

    9 11 13 15 17

    Prov

    ided

    Coo

    ling

    Load

    (M

    W)

    Qnormal Qlimit

    22

    23

    24

    25

    26

    27

    9 11 13 15 17

    Indo

    or

    Tem

    pera

    ture

    (℃) Tnormal Tlimit

    Reset period

    Indoor Temperature

    Building Cooling

    HVAC Power

    - Conventional Method (4.1)

    Time delay over 30 in minutes

    Indoor temperature increase: 1 ℃ Power peak reduction: 650kW (6%) Response time required: over 30minutes

  • Proactive “Building Cooling Supply Side” Management : - Chillers are the major cooling producer/power consumer in HVAC system. - Proactively reduce the power of chillers (e.g. reduce the chiller operating number) during grid power shortage.

    Proactive “Building Cooling Supply Side” Management

    HVAC Systems Cooling

    To maintain indoor air temperature

    Cooling supply side Cooling demand side

    (4.1) - Proactive Method

  • Advantage: - Fast response by rapidly/immediately reducing power of HVAC in response to grid power shortage.

    Increase Tindoor

    Decrease Cooling supply

    to building

    Decrease Cooling supply

    by chillers

    Decrease Power consumption

    of chillers

    Proactive “Building Cooling Supply Side” Management (4.1)

    - Proactive Method

  • Comparison of Response Speed

    Indoor Air Temperature Set Point Reset (Conventional Method)

    Chiller Direct Load Control (Proactive Method) Time

    Chiller Power

    Demand

    Response time is over 30 minutes

    Chiller Power Reduction

    Temperature Reset Signal

    (4.1) - Conventional vs. Proactive Methods

    Time

    Chiller Power

    Demand

    Response in seconds and be stable in minutes

    Chiller Power Reduction

    Direct Load Control Signal

  • Item Avg. Power Decrease(kW)

    Limiting Time(hour)

    Avg. Power Increase(kW)

    Resuming Time(hour)

    Chiller Demand Limiting Strategy

    1015 2 1050 1

    -2000

    -1500

    -1000

    -500

    0

    500

    1000

    1500

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

    Power Alteration of Chillers and Pumps kW

    hours

    Chiller(s) Number Reduced

    Chiller(s) Resumed

    Power Alteration

    A Simulation Case of the Proactive Management (4.1)

  • 4.2 Proactive “Building Cooling Supply Side” Management

    - It is difficult to determine the reduced cooling to ensure an accepted indoor comfortable level;

    - Water distribution system could be out of balance;

    - Over-supplied water could be caused, resulting in deficit flow in decouple line;

    - Pump power could be highly increased.

    Some potential problems could be caused if just simply change the operating number of chillers

    - Potential Problems

  • AHU

    AHU

    CHIL

    LER

    CH

    ILLE

    R

    Bypass

    Secondary pump

    Primary pump

    Tsup Tsup

    AHU

    Tsup

    AHU

    Tsup

    • • •

    Close AHUs: sufficient Remote AHUs: insufficient

    Water distribution is not balanced

    Examples of Potential Problems (4.2)

    Water Imbalance Problem

  • Water Imbalance Problem

    • There is no existing solutions available. • Examples of solutions being considered in our current research:

    - Proactive control the water valve openings by resetting AHU supply air temperature set-point;

    - Proactive control of terminal demands by resetting the indoor temperature set-points;

    - Direct and scheduled control of valve openings of AHUs.

    (4.2) (4.2)

    Possible solutions

  • Conclusions • Buildings can play an important and effective role in addressing

    the critical issues in smart grid: peak load and power imbalance. • BAS, together with smart metering system, enable an bidirectional

    interactions between power supply and demand sides for grid-scale control and optimization.

    • Practice and regulations in BAS specifications need to be revised and updated for bidirectional interaction with grid.

    • Proactive “building cooling supply side” management can provide fast response to power shortage of smart grid. But proper proactive control strategies need to be developed further to solve the problems when using conventional strategies based on cooling supply responding to cooling demand

  • 44

    Slide Number 1Slide Number 2Slide Number 3Slide Number 4Slide Number 5Slide Number 6Slide Number 7Power Supply – Power Demand Slide Number 9Slide Number 10Slide Number 11Slide Number 12Slide Number 13Slide Number 14Slide Number 15Slide Number 16Slide Number 17Slide Number 18Slide Number 19Slide Number 20Slide Number 21Slide Number 22Slide Number 23Slide Number 24Slide Number 25Slide Number 26Slide Number 27Slide Number 28Slide Number 29Slide Number 30Slide Number 31Slide Number 32Slide Number 33Slide Number 34Slide Number 35Slide Number 36Slide Number 37Slide Number 38Slide Number 39Slide Number 40Slide Number 41Slide Number 42Slide Number 43Slide Number 44