21
Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-1 The Management Mechanism for Energy Efficiency of Chiller Units in Taiwan January 14 ~ 15, 2010 Asia ESCO Conference 2010 Bing-Chwen Yang Senior Researcher Energy & Environment Research Laboratory, ITRI Bill, Huei-Jiunn Chen President Taiwan Association of Energy Service Companies

The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-1

The Management Mechanism forEnergy Efficiency of Chiller Units in

Taiwan

January 14 ~ 15, 2010

Asia ESCO Conference 2010

Bing-Chwen YangSenior Researcher

Energy & EnvironmentResearch Laboratory, ITRI

Bill, Huei-Jiunn ChenPresident

Taiwan Association of EnergyService Companies

Page 2: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-2

Contents

• Introduction

• Current Situation in Taiwan

• Proposal for the Mandatory Mechanism

• Conclusion and Discussion

Page 3: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-3

Energy Situation in Taiwan

More than 99% of energy was imported. In 2008, the final energy consumption for Industry sector is 52%, Residential

and Commercial sectors 24%; Transportation sector 13%. In 2008, the electricity consumption for Industry sector is 49%, Residential and

Commercial sector 37%.

52%

8%

13%

1%

12%

12%2%

Industry

Energy

Transportation

Agriculture

Commercial

Residential

Others

Overall energy consumption in 2008

11.77 millions KLOE

Overall electricity consumption in 2008

22.98 billions kW-h

48.7%

8.2%

1.1%

19.4%

0.5%

17.8%

4.4%

Industry

Energy

Agriculture

Commercial

Transportation

Residential

Others

Page 4: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-4

Electricity Consumption in Taiwan

A/C

48%

Lighting

30%

Elevator

6%

Water

5%Others

11%

Power Device

55%

Air Compressor

9%

A/C

16%

Heating

11%

Others

9%

Electricity Consumption in C&R Sector

Electricity Consumption in Industry Sector

Page 5: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-5

Background

• The Chiller Energy Efficiency Standard has beenenforced in 2003 and upgraded in Jan.1, 2005

• To effectively implement the control mechanism,Bureau of Energy of MOEA ask EEL of ITRI assistanceto promote and implement the control mechanism .

• To comply with the government energy conservationgoal, and provide assistance to domestic chiller makersto up-grade their technologies, EEL further authorizedTaiwan Refrigerating and Air-Conditioning EngineeringAssociation (TRACEA) to promote and implement thecontrol mechanism under voluntary base from 2003.

Page 6: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-6

Energy Efficiency Standards

2.792.402.792.40AllAir-cooled

6.105.255.554.77≧300 RT

5.554.775.554.77≧150 RT<300 RT

5.004.305.004.30<150 RT

Centrifugal

5.504.734.654.00≧500 RT

4.904.214.193.60≧150 RT<500 RT

4.453.834.073.50<150 RT

Volumetric

Water-cooled

COPW/W

EERkcal/hr-W

COPW/W

EERkcal/hr-W

CoolingCapacity

Type

2005.01.012003.01.01Date

2nd Stage1st StageStages

Standard:CNS 12575-2007

Page 7: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-7

• Introduction

• Current Situation in Taiwan

• Proposal for the Mandatory Mechanism

• Conclusion and Discussion

Page 8: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-8

Guideline for Implementation

• Accreditation to manufacturer’s testing facility,Authorization to their own testing report, and Assessmentafter receiving the testing report. (3A)

• Review the manufacturers test laboratory for their QA system,test methods and procedure, test personnel qualification,operation procedure, instruments calibration records.

• Authorize manufactures to test their chiller energy efficiencyby themselves.

• Submit the test report to TRACEA for control, themanufactures may label their chillers with certified tag anddeliver to it’s the clients.

• An experts team formed by TRACEA may draw the productsand send to a TAF (Taiwan Accreditation Foundation)certified laboratory for re-testing in random base.

Page 9: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-9

Implementation Process

Form the ExpertsTeam

Maker apply forcertification

Visit Test Sta.

TRACEA Issues Certified Report &Maker sign the conformation letter

Efficiencycompliance

TestReport

YES NO

Audit Report

ExpertsReview

NOYES

PerformanceTest

Expertsmeeting

Test Report YES

NO ProductsReady for

MarketRandom Test

Productslisted

Announce

Page 10: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-10

Implementation Procedure

• Organizing the chiller energy efficiency control experts team.• Chiller manufactures apply to inspect and certify their test station.• Arrange the expert team for test station visiting and inspectation,

it will be a one day visit, include documents review & approval,shop inspect and chiller test witness.

• After the visit and review, the expert team will write the visitreport and comments; and decide if they need for second visit.Final review shall be either documents review or shop review.

• Expert team held meeting to approve test report.• Authorize the manufactures toy test theirs chiller energy

efficiency by themselves, then submit the test report to TRACEAfor control, the manufactures are award a certification to identifytheir qualification, the manufactures can label their testedproducts with certified tag and deliver to it’s the clients .

Page 11: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-11

Implementation Procedure(cont.)

• The products with certified tag means its energyefficiency meets the national standard and allowto sell. The TRACEA may periodically publishthe testing result.

• Afterward audit and random inspection:

1. Random draw inspection;

2. By application (Users or Hostile competitors)

• Random inspection may send to TAF certifiedlaboratory for test and comparison.

Page 12: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-12

Certification of Testing Facilities

Page 13: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-13

Certification of Energy Efficiency

經濟部能源局

經濟部能源局

能源與環境研究所

能源與環境研究所

Page 14: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-14

Current Status of Voluntary Mechanism

• 23 testing facilities in 13 local manufacturers havebeen awarded the certification. 15 testing facilities for5 foreign manufacturers were also passed theassessment and got the certification.

• These manufacturers can test their own chiller unitsand submit the testing reports to TRACEA for theirreview and got the passing stick to put on their chillerunits.

• There are more than 2000 units has been awarded thelabeling sticks by the end of last year (2009).

Page 15: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-15

• Introduction

• Current Situation in Taiwan

• Proposal for the Mandatory Mechanism

• Conclusion and Discussion

Page 16: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-16

Shifting from Voluntary to Mandatory

• The revised Energy Management Law wasreleased in June of 2009.

• ITRI has set up the testing facilities with testingcapacity 2000 RT for water-cooled and 200 RTfor air-cooled units.

• It means that we have set up the enoughcapability to test most of the local or importedchiller units.

Page 17: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-17

Proposal for Mandatory Mechanism

• Similar procedures as the voluntary mechanism(3A)– Accreditation to manufacturer’s testing facility

– Authorization to their own testing report

– Assessment after receiving the testing report

• Multi-level of energy efficiency

• Standard type – post on the website in advance.

• Non-standard type – post on the website afterget the testing report

Page 18: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-18

Proposed Schedule

2012~201120102003~2009

Adjustment Period MandatoryVoluntary

Encourage the up loading ofthe testing report

Mandatory up loading of testing reportand meet the efficiency requirement

Draw the mandatory regulation and publish

Mandatory report for the units installedin the government sector

Random inspection for each manufacturers

Mandatory report forall the units

Set up multi-level of energyefficiency standards

Publish thestandards

Enforcement formulti-level labeling

Set up and draw theIPLV standards

Publish thestandards

Enforcement forIPLV standards

Page 19: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-19

• Introduction

• Current Situation in Taiwan

• Proposal for the Mandatory Mechanism

• Conclusion and Discussion

Page 20: The Management Mechanism for Energy Efficiency …asiaesco.org/pdf/presentation/5-2.pdf• Organizing the chiller energy efficiency control experts team. • Chiller manufactures apply

Copyright 2010 ITRI工業技術研究院 Chiller for Asia ESCO-20

Conclusion Remarks

• The enforcement of the mandatory mechanism is oneof the strategies to meet the target for energyconservation. It also can upgrade the technology forlocal manufacturers and increase the capability ofglobal competition.

• Gradually shifting from voluntary to mandatory canreduce the impact for local manufacturers.

• Multi-level and IPLV are still under reviewingprocess. We will come out a suggestion forgovernment reference before the enforcement ofmandatory mechanism.