The blue line DRINKING WATER PIPE SYSTEM Handbook 2014

The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Embed Size (px)

Citation preview

Page 1: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Theblue line

D R I N K I N G W A T E R P I P E S Y S T E M

Handbook 2014

Page 2: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Contents

4 Quality targets; the blue line 5 Technical standards 6–7 Ketrix®

8–9 Problems and solutions

10–11 Raw material data: PP-R, metals, insulation

12–13 Pipe types KE00, KE02, KE08; operating temperatures

14 ALU composite pipe KE06

15–17 SENSO-LX insulated pipes; heat losses; savings

18–19 Methods of joining; the safest pipe connection

20–21 Joining the pipes with the hand welding machine

22–23 Welding the LX pipes; welding the saddle fittings

24–25 Table welding machine

26–27 Butt welding machine

28–29 Overhead welding machine

30–31 Electrofusion socket welding

32–33 Plumber friendly solutions

34 Pipe sizing; flow velocity; fitting pressure losses; circulation pipes

35–36 Pipe sizing according to DIN 1988-300

37–39 Sizing charts for PN10, PN16 and PN20

40–43 Flow rate calculations according to DIN 1988-300

44–45 Expansion; compensation; force of expansion

46–47 Compensating expansion in practice; pipe supports

48–51 Pressure testing

52–53 Rinsing; noise prevention; heat insulation

54–55 General installation guidelines

56–85 Product range; dimensions

86–87 Agencies; addresses

Abbreviation Description Unit

A Cross-sectional area mm2

d Outside diameter of pipe mm di Inside diameter of pipe mm E Module of elasticity N/mm2

FP Fixing point Ft Force of heat expansion N IS Insulation thickness mm l Length of piping m MS Minimum length of expansion pipe mm N Force Newton P Pressure bar PN Pressure rating bar R Pressure loss caused by friction Pa/m s Wall thickness mm sec Time second SF Safety factor SP Supporting point t Temperature °C tm Temperature of medium °C tv Temperature at time of installation °C V Volume l/m V̇ Flow volume l/sec v Flow velocity m/sec VP Packing unit pc VR Total flow rate (DIN) l/sec VS Peak flow rate l/sec W Power Watt Z Flow resistance for type of fitting Pa z z-dimension mm α Coefficient of expansion mm/m°C ∆ l Specific linear expansion mm ∆p Total pressure loss Pa ∆ t Temperature difference∆ °C ζ Pressure loss coefficient λ Coefficient of heat conductivity W/m°C ρ Density kg/m3

∑ Sum δv Tensile stress Mpa

IndexThe following commonlyused abbreviations arefound in this catalogue.

32

Page 3: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

The blue line

Blue is KE KELIT´s company colour and conjures up the following associations:

The preciousness of blue water: Clean water is becoming ever more precious. The surface of metal pipes are being destro-yed by ever more aggressive ions.

The durability of blue sapphire: Symbolic of value, durability and eternity.

The reliability of blue chip: On the fast moving share markets a syno-nym for ”safe bet”, or ”market leader” or ”recommended purchase” or ”no risk”

Lines are associated with continuity, direction and connections.

The colours, design and marking of the products are regulated by various national standards. KE KELIT products are easily identified by the ”blue line” marking on the product.

The advantages of the ”blue line” range:

l A complete system from one supplier.

l All three pipe materials use the same joint technology, the same machines and the same tools.

l However, each system has been designed for its particular application.

l Every new innovation is integrated into the complete product range.

The Blue line is the new direction taken by the leading pipe system supplier KE KELIT.

KE KELIT’s Quality targets

1. Our quality targets are not confined to the product. They include all areas covered by ÖNORM EN ISO 9001:2000.

2. Suppliers and customers are integrated into the quality assurance system to ensure that mistakes are prevented.

3. Every employee is responsible for the quality of his own work and should be highly motivated to continually assess his work.

4. Customer satisfaction can only be achie-ved by responding to the requirements of the customer and the market.

5. A responsible attitude to the environment can only be achieved by manufacturing long-life products by environment-friendly processes.

Technical standards National and international test institutes test the conformity of our products to a range of different standards.*

DIN 8077/8078 EN ISO 15874 1– 5 EN ISO 15494

Dimensions, pressure ratings Material requirements

ÖNORM B5174 EN ISO 15494 DIN 8078-1 ASTM F1249-90

Dimensions, pressure ratings Material requirements, resistance to impactResistance to chemicalsDiffusion of water vapour

General:EN ISO 8795:2001BS 6920ÖNORM B5014-1ÖNORM B5018-1 + 2EN 12873-1DIN 2999DIN 16962DIN 50911ISO 6509DIN 17660

Suitability for drinking water

Migration

Metal threads

Stress corrosion crackingDezincification resistance Brass materials

*For information about specific national approvals please contact the headquarters in Linz or the regional offices.

Senator Karl Egger eh. Managing Director

54

Page 4: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Chilled water conditioning (PN10)

Pipe systems for chilled water cooling systems (down to +2°C)

Pipe systems for brine refrigeration systems (down to –30°C)

Advantagesl Range of sizes: d20 – 160l Resistant to impact at – 30°Cl Resistant to any concentration of

glycol brines l Resistant to corrosion even when

the temperature unintentionally drops below the dew point and at the aggressive temperature of 0°C.

Drinking water max.temp: 30°C PN10 max.temp: 40°C PN16

Advantagesl Highly secure welded joint (safety factor > 3)

l Tools, machines, and welding times similar to KELEN® pipe system

l Resistant to chemicals, water particles and pressure hammer, even at low temperatures

l Resistant to corrosion even in places where unwanted condensation has formed

The alternative pipe system

The polymer

KEtrix® is made of CRYOLEN®, a PP-based polyolefine blend.

Properties:Density 0,9 g/cm3

Tensile strength: 40 N/mm2

Elongation at tear: 800 %E-module (20°C): 1500 N/mm2

Heat conductivity: 0,23 W/m °CSpec. thermal expansion: 0,14 mm/m °CResistance to impact: – 30° C

Compressed air technology (PN16)Compressed air has become indispensable for the manufacturing sector and is used for the following tasks:

l Driving medium for toolsl Pneumatic control systemsl Driving medium for regulator fittingsl Air purification at the workplace

Advantagesl Range of sizes: d20 – 125l High chemical resistance to compressor oilsl No corrosion and therefore no variation in the quality of the compressed air

Operating conditions as specifiedby ÖNORM:PN10: 20°C/10 barFrom –30°C to +30°C/8 barSafety factor: Taking into account theproperties of the raw material ÖNORMB5174 includes a safety factor of(SF=1.25) in the operating conditionsgiven on the right.

Operating conditions as specifiedby ÖNORM:PN16: 20°C/16 barFrom –30°C to +40°C/10 barSafety factor: Taking into account theproperties of the raw material ÖNORMB5174 includes a safety factor of(SF=1.25) in the operating conditionsgiven on the right.

Operating conditions as specifiedby ÖNORM:PN16: 20°C/16 barFrom –30°C to +40°C/10 barSafety factor: As a result of thealuminium layer a PN 12.5 medium pipecan withstand the same operatingconditions as a standard PN16 pipe.

A separate catalogue is available for the KEtrix® pipe system!

Operating pressure in relation toservice life and temperature

Temperature Pressure Service life (°C) (bar) (years)

10 13,4 50 20 10,9 50 30 8,7 50

Temperature Pressure Service life (°C) (bar) (years)

10 21,2 50 20 17,2 50 30 13,8 50 40 10,9 50

Temperature Pressure Service life (°C) (bar) (years)

10 21,2 50 20 17,2 50 30 13,8 50 40 10,9 50

KETRIX pipe system

76

Page 5: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Drinking water problems

Corrosionl The concentration of ions in drinking

water is increasing and consequently the risk of using metal pipes:

Chlorides: attack stainless steel Sulphates: attack galvanised steel Nitrates: attack copperl Ever more problematic sources of water reserves have to be tapped

for the supply of drinking waterl Acid rain reduces the pH value of

surface and spring water to critical levels below 7 (=neutral).

External corrosion occurs as a result of new building and insulation materials and new installation methods.

l Disinfectants (chlorine, ozone) attack copper in particular. Poisonous

Cu ions are released into the water!

Incrustationl Hard water causes incrustation on the inside walls of metal materials.

The consequences:

l Higher pressure lossesl Reduced flowl Blockagesl Expensive repair workl Time-consuming renovationl Disruptions in the water supply

A secure supply of drinking water is an essential factor for a high quality of life

Internal corrosion - Cu

External corrosion - Steel

Calcite deposits

Operating conditions

PN20 = 20°C/20 bar; 70°C/8 bar

PN16 = 20°C/16 bar; 60°C/8 bar

PN10 = 20°C/10 bar;

The solution

KELEN drinking water pipe system

Plastics are not ”replacement materials”. When chosen and applied correctly they often provide the better solution for a defined problem.

Sometimes even the only one

The Result

The KELEN pipe system has many advantages. Ideal for hot andcold water installations for both new projects and renovation.

l Pressure ratings: PN10, PN16 and PN20

l Cold water: d20 – d160 mm Hot water: d20 – d110 mm

l Resistant to internal and external corrosion caused by ions in the water or chemicals on the site

l No crystallisation points for lime deposits

l Secure joint technology which requires no additional materials.

l Conforms to hygiene regulations and approved for transporting foodstuff

l Low pressure losses as a result of smooth bore

l Low noise levell Resistant to high temperatures

and pressurel Low thermal conductivity comparison of λ-values: KELEN 0,24 W/m°C Copper 320,00 W/m°C Cast iron/steel 42,00 W/m°Cl Stringent testing and monitoring of quality to international standardsl Secure long-term performancel Pipes are insulated at the factory

and can be located behind the walll Can be combined with KELOX-multi-

layer flexible pipe system

”No more corrosion in the 3rd millennium”

98

Page 6: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

The raw materials

The long-life plasticThe raw material is a polypropylene copolymer (PP.R) with its typical quality characteristics (DIN 8077, DIN 8078).

Every material is subject to ageing. PP-R is no exception to this rule of nature. The ”long-term creep curves”, which are determined by temperature and stress, are proof of the long service life (see page 13 for operating conditions).

Density: 0,91 g/cm3

Melting Point: ~ 140° CTensile strength: 40 N/mm2

Elongation at tear: 800 %E-module (20°C): 900 N/mm2

Spec. heat 2 kJ/kg °CHeat conductivity: 0,24 W/m °CSpec. themal expansion: 0,15 mm/m °C

l KELIT technology has made KELEN pipes particularly resistant to impact at –5°C.

l Pipes and fittings are made of the same raw material.

The expected servicelife can be read off thegraph.

The following formulais used to calculate thetensile stress:

δvT

ensi

le s

tren

gth

in M

Pa

Time in h >

Long-term creep curve DIN 8078

10

Metal adaptor fittings

Special care has been taken over the choice and quality control of the metal threads.

Special quality criteria:l Dezincification resistant brass (MS 63, CZ 132) for all parts

transporting water ensures high resistance against aggressive water.

l A pore-free, chemically applied metal plating prevents stress corrosion

cracking.l Metal parts which are not in contact

with the media are generally made of metal-plated MS 58 brass.

l Exceptional resistance to torsion force and suitable for on-site conditions

l Depth of the thread conforms to DIN 1692 for normal faucets

The insulation (LX) Foam:l Cross-linked PEl 100% closed porel Density: 30 kg/m3l Heat conductivity (λ) at: 40°: 0.038 W/m°C 60°: 0.039 W/m°Cl Water vapour permeability µ = 10,000 (an effective vapour barrier)l Environment-friendly l (CFC- free foam)l Bubble structure to insulate against noise transmissionl Strong enough to withstand site

conditionsl Concealed pipe can be located

electronicallyl Insulation can be pushed back to allow room for the welding

Protective coating:High quality 5-layer composite made of polyolefines and aluminium

SENS

O

1110

Page 7: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

PP-R pipe system

KEO2 KELEN pipe PN10 d x s Flow rate L/m 20 x 1,9 mm 0,21 25 x 2,3 mm 0,33 32 x 2,9 mm 0,54 40 x 3,7 mm 0,83 50 x 4,6 mm 1,31 63 x 5,8 mm 2,07 75 x 6,8 mm 2,96 90 x 8,2 mm 4,25 110 x 10,0 mm 6,36 125 x 11,4 mm 8,20 160 x 14,6 mm 13,52

KEO2 KELEN pipe PN16 d x s Flow rate L/m 20 x 2,8 mm 0,16 25 x 3,5 mm 0,25 32 x 4,4 mm 0,42 40 x 5,5 mm 0,66 50 x 6,9 mm 1,03 63 x 8,6 mm 1,65 75 x 10,3 mm 2,32 90 x 12,3 mm 3,36 110 x 15,1 mm 6,36

KEO2 KELEN pipe PN20 d x s Flow rate L/m 20 x 3,4 mm 0,14 25 x 4,2 mm 0,22 32 x 5,4 mm 0,35 40 x 6,7 mm 0,56 50 x 8,3 mm 0,88 63 x 10,5 mm 1,39 75 x 12,5 mm 1,96 90 x 15,0 mm 2,83 110 x 18,3 mm 4,23

Dimensions: as specified by DIN 8077 Colour: Grey. 3 co-extruded green lines (90° apart) help the plumber to align pipe and fitting. Standard length: 4 m, Other lengths can be produced on request subject to minimum order quantities!

Dimensions: as specified by DIN 8077 Colour: Grey. 3 co-extruded blue lines (90° apart) help the plumber to align pipe and fitting. Standard length: 4 m, Other lengths can be produced on request subject to minimum order quantities!

Dimensions: as specified by DIN 8077 Colour: Grey. 3 co-extruded red lines (90° apart) help the plumber to align pipe and fitting. Standard length: 4 m, Other lengths can be produced on request subject to minimum order quantities!

Application as specified: Cold water PN10: 20°/10 barSafety factor: The DIN standard takes account of raw material properties and calculates a safety factor of 50% (SF=1.5) when deriving the opera-ting conditions given on the right:

Application as specified: Hot and cold water PN16: 20°/16 bar 60°/8 barSafety factor: The DIN standard takes account of raw material properties and calculates a safety factor of 50% (SF=1.5) when deriving the opera-ting conditions given on the right:

Application as specified: Hot and cold water PN20: 20°/20 bar 70°/8 barSafety factor: The DIN standard takes account of raw material properties and calculates a safety factor of 25% (SF=1.5) when deriving the opera-ting conditions given on the right:

Operating pressure in relation to service life and operating temperature

Temperature Pressure Service life (*C) (bar) (years) 20 10 50 30 9 50 40 8 50

Temperature Pressure Service life (° C) (bar) (years) 20 16 50 40 12 50 60 8 50 70 6 25

Temperature Pressure Service life (° C) (bar) (years) 20 20 50 40 15 50 60 10 50 70 8 50 80 6 25

1312

Page 8: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KELIT ALU Composite pipe

KO6 KELIT ALU Composite pipe PN20

d x s Flow rate L/m

20 x 2,8 mm 0,16 25 x 3,5 mm 0,25 32 x 4,4 mm 0,42 40 x 5,5 mm 0,66 50 x 6,9 mm 1,03 63 x 8,6 mm 1,65 75 x 10,3 mm 2,32 90 x 12,3 mm 3,36

Operating pressure in relation to service life and temperature

Operating conditions as specified:Cold water 20°– 20 bar Hot water 70°– 8 bar

Safety factor: As a result of its higher resistance to temperature and pressure a PN16 ALU composite pipe can withstand the same operating conditions as a standard KELEN PN20 pipe.

Colour: The PP-R medium pipe is colourless. The outside layer is azure blue. Standard length: 4 m.

A perforated ALU layer is bonded to the medium pipe by a coupling agent. This bonding reduces the expansion considerably.

Temperature Pressure Service life (° C) (bar) (years) 20 20 50 40 15 50 60 10 50 70 8 50 80 6 25

KELEN-LX SENSO insulated pipe system

Pressure rating PN10Type KE02-LX4Insulation thickness 4 mmSize d 20 x 1,9 mm d 25 x 2,3 mm d 32 x 2,8 mm

Pressure rating PN16 PN20Type KE08-LX4/LX9 KE00-LX4/LX9Insulation thickness 4 mm und 9 mm 4 mm und 9 mmSize d 20 x 2,8 mm d 20 x 3,4 mm d 25 x 3,5 mm d 25 x 4,2 mm d 32 x 4,4 mm d 32 x 5,4 mm

Length of pipe: 4 m Insulation: Pipe is covered in PE foam on the extruder line

Insulation thickness: standard 4 mm and 9 mm

Protective covering: HDPE linen bound fabric and viscoplastic polymer alloy

Tracing the pipe: SENSO layer makes it possible to trace concealed pipe

Advantages

l Enormous time savingsl Cost savingsl As a result of its elasticity the

insulation can be pulled back from the welding areal The ends of the pipes are protected

from damage and dirtl Prevents noise transmission of concealed pipes

1514

Page 9: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

The effect

Drinking water pipes made of PP-R are winning an ever bigger share of the world market as the best possible alternative to metal pipes which are subject to corrosion. The appropriate institutions (DIN,CEN, ISO) lay down the minimum standards.

KE KELIT does more than merely meet the minimum standards. KE KELIT provides solutions to specific economic and technical problems such as the heat loss in piping systems.

There is a much lower heat loss through KELEN hot water pipes than through metal pipes as a result of the vastly different heat conductivity of the materials (PP-R λ = 0.24 W/m°C; Copper λ= 320 W/m°C; Steel λ= 42 W/m°C ). This fact alone is not sufficient for KE KELIT who have gone a step further.

The d20, d25 and d32 pipes are pre-insula-ted at the factory with either 4 mm or 9 mm of a special insulation (LEXEL=LX) against heat loss. The results are remarkable:

The potential savings

The difference between the heat loss through non-insulated and insulated KELEN pipes over the period of a year shows that there is a remarkable potential for savings.

Amortisation calculationThe heat loss calculated above must be com-pensated by the permanent supply of extra energy. Depending on the source of energy (electricity, oil, gas or geothermic energy) the costs will increase considerably.

Example1KWh of electricity: e 0.06 – 0.15 1KWh of oil/gas: e 0.04 – 0.08

If we assume that the average energy cost is e 0.075/KWh then the reduction in heat loss of 297 KWh by installing the insulated LX4 pipe will provide savings amounting to: e 22.28 /year.

Example

Comparison of a hotel room installation with and without LX 4 insulation:2.7 m Riser d32 (installed in shaft)6.0 m Distributor pipe (embedded in concrete)8.0 m Circulation pipe (embedded in mortar)Operating conditions:Hot water temperature: 60°CAverage room temperature: 25°CSystem in constant operation 365 days per year: t2Hot water requirement: 2 hours/day: t1Source of energy: Electricity

By comparing the costs you can make the following conclusions:

l The extra costs of the insulation is re-paid within WEEKS.

l The total cost of the piping and the insulation is re-paid within a few MONTHS

l This represents a rate of return which cannot be matched by any other form of investment or shares.

Blue line = blue chip = secure tip

Annual heat loss (W)

KELEN without LX … KELEN LX4 KELEN LX9Medium temp.°C 60° 70° 60° 70° 60° 70°Ambient temp.°C 20° 25° 20° 25° 20° 25° 20° 25° 20° 25° 20° 25°

d20 17,5 15,3 21,8 19,7 12,4 10,9 15,5 14,0 9,4 8,3 11,8 10,6

d25 21,3 18,6 26,6 23,9 14,6 12,8 18,3 16,5 10,9 9,6 13,7 12,3

d32 26,1 22,9 32,7 29,4 17,6 15,4 22,0 19,8 12,9 11,3 16,2 14,5

KELEN without LX … KELEN LX4 KELEN LX9Medium temp.°C 60° 70° 60° 70° 60° 70°Ambient temp.°C 20° 25° 20° 25° 20° 25° 20° 25° 20° 25° 20° 25°

d20 49,3 43,1 61,6 55,4 17,6 15,4 22,1 19,9 11,0 9,7 13,8 12,4

d25 51,7 45,3 64,7 58,2 20,3 17,7 25,3 22,8 12,7 11,1 15,9 14,3

d32 54,3 47,5 67,8 61,0 23,5 20,6 29,4 26,5 14,9 13,0 18,6 16,7

Heat loss QR (W/m)

Type of installation Riser pipes and exposed piping

Type of installation Embedded piping in concrete and mortar

The following formula is used to calculate the heat loss:

Pipes Calculation KELEN KELEN LX4d/lfm lfm · QR · t2 · t1 QR QR

20 8,0 8,0 · QR · 365 · 2 43,1 251 704 15,4 30 353 Potential

25 6,0 6,0 · QR · 365 · 2 45,3 198 414 17,7 77 526 energy

32 2,7 2,7 · QR · 365 · 2 22,9 45 136 15,4 30 353 savings

Sum 495 254 197 815 297 439 W = 297 KWh/a

Annual heat loss (W)

1716

Page 10: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

The six ways of joining the pipes

A wide range of safe and secure methods for joining the pipes is essential for a pipe system.

KE KELIT has a comprehensive range of fittings for each method of joining.

All KELEN polyfusion fittings from d20 to d110 are rated PN20. They can be used for welding to pipes of all pressure ratings.

1. Polyfusion welding

Principle: Fusion welding occurs when a large area of the outside of the pipe and the inside of the socket are welded together

A wide range of welding fittings is available

Sizes: d20 – d110

2. Butt welding

Principle: After the end of the pipe has been cut flat the face of the pipe and fitting are simultaneously heated to melting temperature. They are then pressed together under pressure until the material has cooled.

Advantages

l Pipe and fitting are made of the same material. No additional materials are required.

l Welded joints are not a weak point in the system.

l The weld does not cause a reduction in the flow at the joint

Sizes: d125–d160

Advantages

l Pipe and fitting are made of the same material. No additional materials are required.

l Welded joints are not a weak point in the system

l Pipe can only enter the fitting after they have been heated on the welding machine (important safety feature)

l The weld does not cause a reduction in the flow at the joint.

3. Threaded adaptor fittingsSizes: d20 x 1/2”– d75 x 2 1/2” The threads conform to DIN 2999 and are made of dezincification resistant brass (MS63-CZ 132). They are metal- plated to protect against stress corrosion cracking. Male and female threads are available as both straight and elbow fittings.

4. Flange connection

Sizes: d20–d160 The solution for flanged fittings Backing ring conforms to pipe sizes Fusion welding: d20 – d125 Butt welding: d160

5. Detachable union fittings

Sizes: d20 x 1/2”– d90 x 3”

3 types:

6. Electrofusion welding

Sizes: d20–d160 KELIT E-welding sockets may be considered for welding in confined areas.

KE55-PPR-male thread KE56-PPR-PPR KE57-PPR-male thread

Advantagesl Wide range of fittings

Female thread is a straight thread

l Male thread is tapered and roughened

l Thread is firmly anchored in the fitting

High resistance to twisting strain

Advantagesl Can be detached at any timel Elastic EPDM seall Dimensions conform to DIN 2501-PN16

Advantagesl Detachable fittingsl Elastic EPDM fittingsl KE57 fitting for

connecting to appliances

Advantagesl Repair socket for

confined areasl Welding machine

available at KE KELITl Each fitting is packaged

individually Instruction sheet and cleaning tissue are enclosed

1918

Page 11: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KELEN® polyfusion welding with the hand welding machine

1. The pipes and fittings are joined by polyfusion welding at 260°C. The welding machines and tools are self-regulating. Just connect to the electricity supply (230V) and wait: The red light indicates that the machine is connected to the electricity supply. When the green light goes out the welding temperature has been reached. Work can begin.

Measure the length of pipe required and cut the pipe with the appro-priate pipe cutter (up to d40 with the pipe shears; up to d110 with the wheel pipe cutter).

1.1 Before welding the KELIT ALU composite pipe sufficient aluminium must be removed by the peeler to allow the pipe to be welded to the full depth of the socket. The colourless medium pipe is clearly distinctive from the protective covering.

Important: There should be no aluminium in the welding area. Make a visual check before welding!

The pipe can then be welded to the fittings in the same way as the standard KELEN pipe.

The welding procedure

2. Ensure that the surface of the pipes are clean and free of grease

2.1 Measure the depth of the socket and mark the insertion depth on the pipe accordingly.

2.1

1.11.1

2.2 The heating time (see table) begins when the full insertion depth of the pipe and the whole of the socket in the fitting have been pushed on to the welding tools.

2.3 The heating time varies according to the pipe size (see table). Once the heating time has elapsed push the pipe and fitting together smoothly and evenly without delay. The result is a homo-geneous and strong joint.

2.4 Three lines on the pipe (90° apart) act as a guide for making a straight joint.

2.5 The position of the fitting can be adjusted for a few seconds immediately after the pipe and fitting have been joined. A short time later (see table) the joint is capable of withstanding operating conditions.

3. The low weight and high flexibility of the material makes it possible to weld whole sections of the piping at the work bench. Take advantage of this and save a lot of time.

4. Make sure that any joints which still need to made in the wall are positioned so that they are accessible with the welding machine.

5. The distance between the draw-off points at the wall can be set (for all common installations) both horizontally and vertically using a template equipped with a spirit level.

6. The pipes should be insulated according to the relevant national standards.

Welding times

4.

5.

2120

Page 12: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

4. SENSO pipe detection

The SENSO properties of the LX insulation allows the system to be located up to a maximum depth of 80 mm in the wall.

4.1 Follow the instructions for the detector.

4.2 Locate where the pipe is running both horizontally and vertically within a radius of 50 cm from the place where the hole is going to be drilled.

Welding KELEN® saddle fittings

1. The surface of the pipes and saddle fittings should be free of grease, clean and dry.

2. A hole is drilled in the pipe using a 24 mm saddle drill.

3. The pipe wall and the saddle fitting are heated simultaneously with the specially designed welding tools for approx. 30 sec.

4. Once the heating time is over the saddle fitting is pushed into the pipe wall immedia-tely (do not twist!) and pressed for approx. 30 sec. The melting of both the pipe wall and the pipe surface ensures a strong homogenous joint. After approx. 10 min-utes the joint can be subjected to operating conditions.

The following guidelines apply forall pre-insulated KELEN-LX pipes.

Point 1. is identical to the instructions for non-insulated pipes on pages 20 and 21

2. Exposing the ends of the pipes

2.1 For short lengths of pipes the welding area can be exposed by simultaneously supporting the pipe on a bench and pushing back the insulation.

2.2 For longer lengths of pipes one hand holds the pipe while the other hand pushes back the insulation

2.3 For especially long lengths of pipe it may be easier if the hands are crossed over.

2.4 It is NOT necessary to cut the insulation.

3. The welding procedure and welding times are identical to point 2. of the instructions for the standard KELEN pipe.

Polyfusion welding of KELEN®-LX pipes with the hand welding machine

Important!The bubble structure and the goodgrip make it easy to pull back theinsulation.

Pressing the insulation to the pipecan prevent the insulation fromslipping back

2322

Page 13: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

The welding procedure:

1. Fix the fitting in the clamp and the fitting holder. Ensure that the face of the fitting is flat against the clamp.

1.1 Put the pipe in the pipe clamp. Do not tighten the clamp.

1.2 Hold down the spacing button and move the sliding blocks together using the hand wheel until the pipe is touching the fitting or the sliding blocks can no longer move

1.3 Release the spacing button. Only now fix the pipe in the clamp.

2. Move the sliding blocks apart and pull down the welding plate.

2.1 Move the sliding blocks together until they are stopped by the lock

2.2 When the heating time has elapsed move the sliding blocks apart briskly and quickly remove the welding plate.

3. Push the sliding blocks together briskly until the pipe diameter switch catches.

3.1 Never cool the welded joint abruptly. After a while loosen the clamp and the finished joint can be removed from the machine.

3.2 Once the cooling time has elapsed the joint can be subjected to operating conditions.

Table welding machine

1. Screw the required heatingelements to the welding plate.The length of the heating element variesaccording to the size of the pipe and thesection of pipe to be welded.

2. One side of the pipe clamps canbe used for small pipe sizes (d20 – d40).For larger sizes (d50 – d90) the clampsshould be turned around.

3. The same principle applies for thefittings clamps.

See pages 20 and 21 for instructionson preparing pipes and fittings forwelding.

4. Set the pipe diameter switch tothe required size. This switch regulatesthe length of the pipe that will be weldedinto the socket

5. Spacing button.Press the button to fix the distancebetween the two sliding blocks which willenable the appropriate section of pipeand the complete socket of the fitting tobe heated on the welding elements.

Note: The machine is available intwo sizes:Type 1: d20–90 mmType 2: d25–125 mm

Heating elementFitting clamp

Fitting holderWelding plate

Lock

Pipe clamp

Pipe diameter switch Hand wheel

Spacing button

2524

Page 14: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

1. Loosen the screws and fit the required reducers in the clamps

1.1 The end of the pipes should protrude from the clamps by no more than 30 mm.

2. Put the surface cutter between the pipe ends. Move the pipes together and remove the oxide layer on the welding surface by cutting away 0.2 mm of the surface. Ensure that the ends of the pipes are vertically parallel to each other (maximum deviation: 0.3 mm). The maximum deviation horizontally is 0.5 mm.

3. The welding procedure(see table on the left for welding criteria)

3.1 Before welding begins read off the manometer the pressure required to bring the pipes together. This pressure must be added to the joining pressure given in the table.

3.2 Insert the heating element (temp: approx. 210 °C). Press the pipe ends on the heating element and apply the pressure as defined in 3.1 until a bead forms around the complete circumference of the pipe. During the heating time the pressure must be reduced to the heating pressure. Once the heating time is over move the sliding blocks apart rapidly and remove the heating element.

3.3 The change-over time (time between removing the heating element and welding the pipes) should be as short as possible.

3.4 The welding pressure should be built up as smoothly as possible during the time given in the table (minimum: 0.15 N/mm2)

3.5 The welding pressure must be maintained during the cooling time.

IMPORTANT:The pipes ends cannot be touched andmust be welded immediately.If this is impossible and the welding hasto be done later then the welding surfacehas to be cleaned and any greaseremoved.

Never cool the joint abruptly.If the weld has been done correctly adouble bead should be visible around thewhole circumference of the pipe.

Butt welding machine for KELEN® PN10 pipes

The table below is valid for the KELIT buttwelding machine WZ115.

If you use other welding machinesthen follow the operating instructionsfor that machine.

Hydrauliccontrol unit;Plug connectionfor welding plateand surfacecutter

30 mm

d x s125 x11,4160 x14,6

SDR

serie

s

Join

ing

pres

sure

Heig

ht o

f bea

d

Heat

ing

pres

sure

Heat

ing

time

Max

. cha

nge-o

ver T

ime

Time t

o buil

d up p

ress

ure

Wel

ding

pre

ssur

e

Cool

ing

time

Pipe

bar1627

1111

mm1,01,0

bar23

sec237277

sec78

sec1113

bar1627

min1924

2726

Page 15: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

1. Fix the pipe clamps to a pipe that has already been installed. The machine will hang at the end of the pipe.

1.1 To provide extra support the pipe should be clamped close to a pipe bracket

1.2 A pole can be placed under the centre of gravity to support the machine if necessary.

1.3 The pipe should protrude far enough out of the pipe clamp to ensure that the pipe can be fully welded into the socket of the fitting but also allow enough space for the welding plate.

The space between the pipe and the fitting when the sliding block has been completely rolled back should be approx. 100 to 150 mm.

2. Put the fitting in the clamp and support the fitting with the fixing elbow. The fitting must have sufficient room to move sideways so that the whole of the socket can be welded.

3. Put the welding plate between the pipe and fitting. Turn the hand wheel to move the pipe and fitting on to the welding tools. Heat the pipe and fitting.

3.1 When the heating time is over remove the welding plate and push the pipe and fitting together briskly to weld the joint.

3.2 When the cooling time is over the joint can be subjected to operating conditions.

Overhead welding machine

It is recommended to use theoverhead welding machine forexposed piping in confined areas(d50–d110).

Adjustablepipe clamps

(d50–d110) aremounted onsiding blocks

Hand wheelfor fixingthe pipes

Hand wheelfor moving the

sliding block on the pipe side

Centre of gravityis marked below the

machine

Hand wheel forFixing the fitting

Elbow forsupportingthe fitting

Adjustablefitting clamps(d50–d110) are fixed tothe machine

2928

Page 16: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

2.

3.

4.

5. By cutting out the buffer in the middle of the socket the e-socket can be pushed com-pletely over the pipe.

Display

Main switch

Welding cable

Electricity supply

Menu

Start-OKStop

6.1 Check that the electricity supply is 230V +/- 10% and 50/60 Hz. Switch the main switch to position “1”6.2 Take the orange adapter cable for d20-110mm sockets and connect the socket to the welding cable, adapter cable and welding machine6.3 Using the arrow key confirm the correct socket type “KE KELIT” by pressing “OK”6.4 Using the arrow key select the required di-ameter size and confirm by pressing “OK” The display will show that the correct size has been selected6.5 Press “OK” to start the welding proce-dure. The welding machine automatically cal-culates the welding time. The voltage, welding time and ambient temperature will appear on the display. 6.6 There is a sound to indicate when the wel-ding time is over. Then press “STOP” to end the welding. Check whether the tracers are pro-truding from the socket.7. Ensure that the electrofusion socket is axi-al to the pipe and is not subjected to stress or strain during welding.7.1 If necessary use the E-UNI socket holder (WZ146)8. Ensure that no moisture is present inside or outside of the weld zone during weldingThe ambient temperature should be between –10°C and +45°C9. Ensure that the weld is not subject to stress, impact, moisture or any other strain during the cooling period (allow at least 10 minutes for cooling)10. Wait for at least one hour before pressure testing or subjecting to operating conditions.

11. The warning codes are as follows:

05: Electricity supply not OK 10: Frequency (50/60 Hz) not OK 20: Ambient temperature outside the

permitted range (–10 to +45°C) 30: Welding voltage outside the

permitted range 35: Machine overheated 45: Maximum welding voltage exceeded

new electrofusion socket required 50: Minimum welding current not attained

new electrofusion socket is required 55: Welding cycle interrupted by operator

new electrofusion socket required 60: Short circuit – new electrofusion

socket required 65: Interruption of electricity supply

new electrofusion socket required. 70–75: Hardware defect

Should one of these codes appear during welding follow the instructions in the manual.

If the symbol appears it is recommended to get the machine checked by the manufac-turer or an authorised service centre.

Press “STOP” if you temporarily wish to remove the symbol. The symbol will reap-pear the next time the machine is switched on.

KELIT® E-Uni welding socket

1. Cut the KELEN® pipe at right angles.

2. Scrape the surface of the KELEN® pipe with a suitable tool, e.g. a blade (DO NOT use sand-paper). A thin layer must be removed from the pipe. At the same time the diameter should not be reduced below its nominal value.

3. Alu peelers are available for removing the aluminium layer from the Alu pipes (please note that more aluminium has to be remo-ved for an electrofusion socket than for a stan-dard socket).

4. Remove any grease from the end of the pipes and the electrofusion sockets where the weld is going to be made. This should be done with the cleaning tissue (soaked in isopropyl alcohol) which is enclosed with the E-socket. No oil-based solvents (e.g. paint thinner) should be used to clean the socket.

1. 5.

5.1

5.1 In order to guarantee the central position of the weld, mark the welding depth of the socket on the pipe. For pipes which are being installed horizontally try to ensure that the tracers point upwards.

Check the electricity supply before using the electrofusion welding machine for the first time. Turn on the main switch to position “1”Press the arrow key to choose the language and press “OK”. Use the arrow and OK keys to set the time and date and confirm by pressing “OK”. This information only needs to be entered when the machine is being used for the first time

3130

Page 17: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Special plumbing solutions

Polyfusion welding of the KELEN®pipe system is both secure and quick. A lot more time is spent fixing the pipes and joining to the faucets. The are some practical solutions which can make the job easier for the plumber.

Method of installation:

l Partition wall installation l Brick wall installation l Installation in front of the wall

K85 KELEN® Joining set

The set is used for fixing the outlets at the wall and consists of the following items:

l Metal plate (2.5 mm thick)l Wall brackets: KE83 d20 or d25 x 1/2” and double peg fittingl Sound insulation capsl Elastomer sound insulation padsl Plastic stoppersl Pegs and screwsl Connection to d50 siphon trap and d30 rubber nipple is optionall Set available for single outlet or

for double outlet (80–100 mm or 150 mm)

For special applications the metal plate is available separately (ref: K85A)

K85K sound insulation cap for KE83. The cap does not fix the fitting. A special solution is required for fixing the fitting and the cap.

K85H KELEN® Fixing plate for partition wallsA special system is required for installations in front of the wall and in partition walls.

By cutting the K85H plate to the required length it is possible to arrange the plate so that the fittings are fixed in the required positions.

The fitting is fixed to the double peg fitting K86D behind the plate.

K86 HA Faucet plateThe faucet connection fitting KE83HA has the following properties:

l No transmission of energy to the plaster board

l The holes are octagonal to prevent twisting of the fitting

l The torque force on both fittings is balanced by the fixing plate

l The octagonal holes mean that the fitting can be fixed in every position

l Sound insulating pad is completely covered with PE soft foam

3332

Page 18: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Maximum flow velocity according to DIN 1988-300Maximum design flow velocity for a given pipe run ≤ 15 min >15 min m/s m/s

Service pipes 2 2Supply mains:pipe runs with low head lossin-line valves (ζ < 2.5) 5 2In-line valves with greater loss factor 2,5 2

Pipe sizing Pressure losses in KELEN®pipesThe total pressure loss (∆p) in the KELEN®pipe system is calculated by multiplying the friction loss (R) by the length of the piping (l) plus the sum (∑) of the friction losses for the individual fittings (Z).

∆p = (I · R + ∑Z) in Pa

The choice of pipe size for the water supply is dependent on the following factors:l The available water pressurel Geodetic difference in heightl Pressure losses through system

componentsl Minimum flow pressure through faucetsl Pressure losses in the pipesl The individual pressure losses of the

fittings l Type, number and simultaneous use

of the draw-off pointsl Flow velocity

Note:For the purpose of pipe sizing it is assumed that that there will be no reduction in the internal diameter caused by incrustation since the surface structure of the pipe is amorphous and the surface roughness of the pipe is minimal (0,007).

Guidelines for circulating pipe systems (DIN 1988–300)

For hygienic reasons the circulating system should be designed so that the temperature at any point in the system is no lower than 5K below the operating temperature. The power of the pump and the regulati-on of the temperature are designed so that the temperature does not fall below 55°C at any point in the system. For economic rea-sons the flow velocity in circulating systems should be approx.. 0.2– 0.5 m/s and in exceptional circumstances up to a maximum of 1.0 l/s.

Guidelines for pipe sizing (DIN 1988-300)

1. Determining the calculated flow rate and minimum flow pressures of the outlet fittings

The calculated flow rate V̇R is an adopted out-let fitting flow value in the calculation rate. The guidance values of the calculated flow rates of common fixtures are included in the table. The calculated flow rate V̇R (as an average value) is obtained from the following equation:

V̇R = V̇min + V̇max 2

2. Determining total flows and allocating them to the sections

The calculated flow rates are to be added con-trary to the flow direction – always at the far-thest sampling point and ending at the supply line – the total flow rates achieved in this way are then to be allocated to the corresponding sections. The part route in question begins with the mold piece on which the cumulative flow or the diameter changes.

The total flow rates (cold and hot water) are to be added to the cold water line branch point which heads to the drinking water heater.

3. Application of the conversion curve from the total flow to the peak flowDuring calculation of the line systems, it is ab-solutely necessary that all sampling points be applied with their calculated flow rates.

An exception to this is when a second sink, a bathtub with a shower unit, a bidet, a urinal or nozzles in toilet facilities vestibules are inclu-ded in a usage unit (NE). These are not taken into account in the total flow.

4. Simultaneity depending on building type The calculation of the peak flow depends on the total flow; the simultaneity of the water outlet depends on how the building is used (e.g. flats, hotels etc.).

Generally it is not expected that all connected outlets will ever be fully open at once.

On Pages 40 and 41 you will find the conversi-on curves for the various building types.

5. Select pipe diameter Pipe diameters and pipe friction pressure gradi-ents and all corresponding calculated flow rates must be determined. (Pressure loss diagrams: Page 37 to 39).

6. Pressure loss compared with available pressure The total pressure loss for the determined pipe diameter should reach the existing pressure difference, but not exceed it.

Calculation of the pressure loss (Z)for the standard fittings

Z = ζ• v2 ρ

2

Fitting Symbol Coefficient ζ

Elbow 90° 1,3

Elbow 45° 0,4

Tee-straight flow 0,3

Tee-flow separation 0,3

Tee-reverse flow 1,5

Reducer 0,4

Stop valved20 10,0d25 8,5

Slanted seat valved20 3,5d25 2,5d32–63 2,0

S

G

3534

Page 19: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Pressure losses PN10

The method for calculating the pressure loss of the individual fittings is described on page 34.

The pressure losses are calculated according to the Nikuradse formula:

Surface roughness: 0,007 mm

Guidelines for pipe sizing (DIN 1988-300)

7. Minimum flow pressures and calculated flow rates (VR: l/s) of common drinking water extraction points

Important note:The valves manufacturers must specify the minimum flow pressure and the fittings flow rates calculations (VR). The manufacturer’s information absolutely must be consi-dered when measuring the pipe diameter – if it lies abo-ve the values listed in the table, then the drinking water installation must be sized according to the manufacturer’s instructions.

Notes:Equal-type outlets and devices not included in the table with flow rates or minimum flow pressures that are greater than those listed must also be taken into account according to the manufacturer’s instructions.

Min. flow- Drinking water pressure extraction type

bar Dimension V̇R: l/s

Outlet valves 0,5 Without aerator a DN 15 0,30 0,5 DN 20 0,50 0,5 DN 25 1,00 1,0 With aerator DN 10 0,15 1,0 DN 15 0,15 Mixing valves b,c for 1,0 Shower tubs DN 15 0,15 1,0 Bathtubs DN 15 0,15 1,0 Kitchen sinks DN 15 0,07 1,0 Washbasins DN 15 0,07 1,0 Bidets DN 15 0,07

Household machines 0,5 Dishwasher DN 15 0,07 0,5 Washing machine DN 15 0,15

WC basins and urinals 1,0 Urinal flush valve DN 15 0,30 manual or automatic 1,2 Flush valve for WC DN 20 1,00 0,5 Cistern according to EN 14124 DN 15 0,13 a) Without connected appliances (e.g. sprinklers) b) The indicated calculation flow is to be included in the cold and warm water calculationsc) Angle valves for e.g. basin taps and shower hose connections are to be regarded as individual resistors or recognised with the outlet fitting minimum flow pressure.

3736

Page 20: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Pressure losses PN16

The method for calculating the pressure loss of the individual fittings is described on page 34.

The pressure losses are calculated according to the Nikuradse formula:

Surface roughness: 0,007 mm

Pressure losses PN20

The method for calculating the pressure loss of the individual fittings is described on page 34.

The pressure losses are calculated according to the Nikuradse formula:

Surface roughness: 0,007 mm

3938

Page 21: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Building type Constants a b c Residential building 1,48 0,19 0,94

Assisted living facility, nursing home 1,48 0,19 0,94

Bed house in hospital 0,75 0,44 0,18

Hotel 0,70 0,48 0,13

School and administration building 0,91 0,31 0,38

Care home 1,40 0,14 0,92

0

1

2

3

4

5

0 10 20 30 40 50

Zusammenstellung

Pflegeheim Wohngebäude Seniorenheim Krankenhaus Hotel Schule/Verwaltung

Depending on the building type, the peak flow (V̇S) is calculated with the constants included in the table on Page 33 as follows:

V̇S: a (Σ V̇R)b – c

For the building types indicated in the table, the peak flow (V̇S) is calculated with the following scope:

Σ V̇R: 0,2 bis ≤ 500 l/s

Graphical solution for the calculation of the peak flow V̇S depending on the total flow V̇R for the range 0–600 l/s

Peak flow constants (a, b, c) for each building type

Graphical solution for the calculation of the peak flow V̇S depending on the total flow V̇R for the range 0–50 l/s

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0 50 100 150 200 250 300 350 400 450 500 550 600

Zusammenstellung

Pflegeheim Wohngebäude Seniorenheim Krankenhaus Hotel Schule/Verwaltung

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0 50 100 150 200 250 300 350 400 450 500 550 600

Zusammenstellung

Pflegeheim Wohngebäude Seniorenheim Krankenhaus Hotel Schule/Verwaltung

Hotel

Hospital

School, administration building

Residential building, nursing home

Care home

V̇R in l/s

V̇R in l/s

V̇ S in

l/s

V̇ S in

l/s

Exceptions with calculation of the peak flow V̇S

Usage units (NE)A room with outlets in residential buildings (e.g. bath, kitchen, utility room) or in non-resi-dential buildings (in the event that the recogni-sed use is similar to that of a flat).

Experience has shown that the flows of the flow direction up to the end of the strand cable and in the floor distribution of NE‘s are too high; this is because, normally, no more than two outlets are open at the same time e.g. in a bath.

Therefore, the peak flow in each leg of a NE is, at maximum, equal to the total flow of the two biggest outlets installed in the leg (also applies in cases within an NE where the calculation in-dicates a smaller flow). If a second NE is attached to a leg (e.g. in the riser), then the values of the peak rates of the two NEs shall be added (if the resulting peak flow is smaller than the value calculated accor-ding to the calculation). Otherwise, the peak flow must be determined according to the respective equation.

Permanent consumersThe flow of permanent consumers is added to the peak flow of the other outlets. Permanent consumers are defined as water outlets which last longer than 15 min e.g. garden blast valve.

Series equipmentThe total flow is the basis for the calculation. The simultaneity of the water outlet is to be defined with the operator. The multiple peak flow rates of the series system must to be added up if they could both occur at once.

Special buildings, commercial and industrial facilitiesWith special buildings (other than those indica-ted above), including industry buildings, agricu-lture buildings, gardening buildings, slaughter-houses, dairies, shops, laundries, large kitchens, public baths etc. the peak flow must be deter-mined from the total flow in co-operation with the facilities operator. The peak flows of the sub-zones of the drinking water installation must be added up if they coincide.

Excerpt from DIN 1988-300

0

1

2

3

4

5

0 10 20 30 40 50

Zusammenstellung

Pflegeheim Wohngebäude Seniorenheim Krankenhaus Hotel Schule/Verwaltung

Hotel

Hospital

School, administration building

Residential building, nursing home

Care home

4140

Page 22: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Expansion behaviour of KELEN® pipes

Linear heat expansion

Under heat conditions all materials increase in volume and/or length according to the following formula:

Calculation of the linear expansion:

∆ l = I · ∆ t · α

The linear expansion is determined by the length of the pipe, the increase in temperature and the coefficient of expansion. It is not determined by the diameter of the pipe

Comparison of materials

Coefficient of E-module 60° expansion α = mm/m°C N/mm2

Galv. steel 0,012 220000Stainless steel 0,015 200000Copper 0,016 130000KELIT Alu comp.* 0,035* 3500PVC 0,080 1100KELEN 0,150 300PEX 0,175 540

* αd63and above =0,050

This means that when heated KELEN® will expand more than metal materials if the expansion is unhindered.

Expansion arm for exposed pipingCompensation must be made for the expansion of KELEN pipes under heat conditions.Even if the rise in temperature is only for a short time sufficient compensation must be made for this temperature differenceCompensation is always made between two fixed points or between a fixed point and a change in direction of the piping (expansion arm). Calculation of the expansion arm:

MS = 20 · d · ∆ l

20 = Coefficient for KELEN MS = Minmum length of the expansion arm (mm) Length of pipe which branches off at 90° from the main pipe to the next fixed pointExample: d50 mm pipe runs over a length of 15 m ∆t = 35°C Question: How long does the expansion arm have to be to compensate for the expansion?

∆I = 15 · 35 · 0.15 ∆I = 79 mm expansionMS = 20 · 50 · 79 MS = 1256 mm expansion arm

Heat expansion chart (unhindered linear expansion) ∆l

Diffe

renc

e in

tem

pera

ture

∆t

Min

imum

leng

th o

f exp

ansio

n ar

m (m

m)

4342

Page 23: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Practical solutions for compensating expansion

The following methods can be used tocontrol the linear expansion and the forceof expansion:

l Piping that is embedded in the wall or the floor is prevented from expansion by frictional force. No extra measures are required.

l Compensation must be made for expansion of exposed piping

l Even if the rise in temperature is only for a short time sufficient compensation must be made for this temperature difference (see pages 42, 43, 44, 46 and 47)

l Every change in temperature will exert a force. > An expansion force will occur when the temperature rises. < A shrinking force will occur when the temperature falls.

The force of expansion can be calculated for every installation. However, in ge-neral the force is just a fraction of the force which occurs with metal materials.

Suppliers of pipe clamps and brackets know the properties of the materials and offer a range of solutions.

l Pipe channels may be used to increase the stability of the pipe. The expansion is reduced to the same value as steel pipes.

l The strength of the fixed points should be sufficient to compensate the expansion force.

l The specific expansion can be minimised by installing the KELIT ALU composite pipe (d20 – d90), especially on long pipelines.This pipe reduces the expansion by approx. 75%.

Force of heat expansionThe force of linear expansion is differentfor each material. The specific force of heat expansion is calculated according to the following formula:

The force of heat expansion isdependant on the dimension of thepipe and the change in temperaturebut not on the length of piping.

An important factor is the rigidity of thematerial (E-module)

Comparison of the materials:If unhindered KELEN® pipes willexpand more than metal materialsunder the influence of heat. Theforce of heat expansion, however,is much smaller!

The E-module of PP-R (like any otherplastic) is dependant on the temperature(see graph below)

> Temperature: < E-module< Temperature: > E-module

As the temperature increases the E-moduledecreases.

E-module of PP-R in relation to theoperating temperature tm

Example:Length of piping: l = 50 mTemperature during installation: tv = 20°CMedium temperature: tm = 60°CDifference in temperature: dl = 40°C

10

1000

900

800

700

600

500

400

300

200

180

020 30 40 50 60 70 80

Temperature tm in °C >

E-mod

ule (E

) in N

/mm2

Ft = E · A · α · Δt1000

4544

27,3 x 3,2 Galvanised steel 25 585 N

18 774 N

8 406 N

1 248 N

771 N

426 N

894 N

Dimension Linear expansion Force of expansion(Ft)

26,9 x 2,0 Stainless steel

28 x 1,2 Copper

25 x 3,5 KELIT Alu Composite

25 x 2,9 PVC

25 x 3,5 KELEN®

25 x 3,5 PEX/VPE

0 100 200 300 400 mm

Page 24: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

3. Exposed piping3.1 Preventing expansion bymechanical restraint d20–d50

For aesthetic reasons KELEN ALU pipesare often preferred for exposed pipesbelow d63. Greater stability can beobtained by installing the pipes in steelchannels.

3.2 Expansion loops d 63–110All changes in the direction of the pipecan be used to accommodate the linearexpansion. In some cases an expansionloop will be necessary.

In order to achieve this stability all of thepipes must be supported by pipe channelsand all of the brackets must be fastenedtightly to the pipe to make them fixedpoints. In addition the channels are fixedto the pipe (e.g. using cable ties) exceptfor the sizes d20, d25 and d32 as thechannels for these sizes are self-locking.This method reduces the linear expansionto the same amount as steel.

The fixed points are arranged so that thepiping is divided into sections and theexpansion force can be guided in thedesired direction. See pages 42 –45 forthe calculations of the length of theexpansion arm.

Installing KELEN®

1. Installing the pipes in the shaftIn practise the main risers can expand and contract laterally in the shaft between two floors if a fixed point is located next to the pipe that branches off from the main pipe. The distance between two fixed points should not exceed 3 m. Other methods can be used to accommodate expansion such as an expansion arm in the pipe branching off from the riser.

2. Embedding the pipePiping that is embedded in the wall, floor screed etc. … is prevented from linear expansion. The material can absorb the pressure and tensile stress without causing any damage. If the pipes are insulated then the insulation material provides further room for expansion.

Guidelines for distance between pipesupport pointsThe distances between the support points given below (in cm) prevent KELEN® pipes from sagging when they are filled with water and there are NO pipe channels.

d PN 1O PN 16 PN 20 ALU PN 20 mm 20°C 20°C 60°C 20°C 60°C 20°C 60°C 20 70 75 60 80 65 120 100 25 75 80 70 85 75 130 110 32 90 95 80 100 85 150 130 40 100 105 90 110 95 170 150 50 115 120 100 125 105 180 160 63 130 135 110 140 120 195 180 75 150 160 130 170 150 205 190 90 185 195 150 205 170 215 200 110 195 205 160 215 180 – – 125 205 – – – – – – 160 220 – – – – – –

minimum (mm)2 · Δ l + 150 mm

MS

4746

Page 25: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Pressure test – drinking water systems with drinking water according to ÖNORM EN 806-4 The pressure test with drinking water is a combined leakage / load test and it must be performed for all lines in accordance with the specifications of ÖNORM EN 806-4. Pipes and other piping components are designed for maximum operating pressure (MDP) in accordance with the ÖNORM EN 805 or ÖNORM EN 806 series. However, they must be designed to withstand at least a system operating pressure (MDP) / nominal pressure (PN) of 1000 kPa (10 bar). As the test pressure must be 1.1 x the maximum system operating pressure (in accordance with ÖNORM EN 806-4), the pressure test must be performed with at least 1100 kPa (11 bar) (recommended by KE KELIT 15 bar).

The accuracy of the pressure gauge (positioned at the lowest possible point wherever possible) is to the nearest 0.02 MPa (0.2 bar). Depending on the pipe materials and dimensions, 3 different procedures can be applied in the leakage and load test.

Test procedure A– test time 10 minutes For all metal and multi-layer composite systems For all plastics (e.g. PP, PE, PEX, PB etc.≤ DN 50/OD 63 For all combined systems (metal systems/multi-layer composite systems with plastics) ≤ DN 50/OD 63 The test pressure (1) must be achieved with pumping and maintained for up to 10 minutes; during this time the test pressure must remain constant, and there must be no drop in pressure.

Choice of test method B or C Test procedure B – test time 60 minutes For all plastics (e.g. PP, PE, PEX, PB etc.) > DN 50/OD 63

For all combined systems (metal systems/multi-layer composite systems with plastics) > DN 50/OD 63 The test pressure (1) must be achieved with pumping and maintained for 30 minutes by subsequent pum-ping, then the pressure must be reduced to 50% of the test pressure by draining it; then the drain valve must be closed. During the time of the additional 30 minutes the 50% test pressure must remain con-stant and there must be no drop in pressure. In addition, it is necessary to perform a visual inspec-tion of the connections.

Test procedure C – test time 180 minutes For all plastics (e.g. PP, PE, PEX, PB etc.) > DN 50/OD 63

For all combined systems (metal systems/multi-layer composite systems with plastics) > DN 50/OD 63 The test pressure (1) must be achieved with pumping and maintained for 30 minutes by subsequent pum-ping, then the test pressure must be checked, and after another 30 minutes the pressure must be che-cked again. If after this period the pressure has drop-ped to less than 0.06 MPa (0.6 bar) then the test pressure must be continued with no further pum-ping. The test period is an additional 120 minutes, during which the last recorded test pressure may not drop by more than 0.02 MPa (0.2 bar). In additi-on, it is necessary to perform a visual inspection of the connections.

MD

P

1

1

1,1

1,1

1,0

1,0

0,5

0,5

0

0

0

0 10 20 30 40 50 60

10

min

1

1,11,0

0,5

00 10 20 30 60 120

≤ 0,06 MPa

≤ 0,02 MPa

180

min

min

MD

PM

DP

MD

P

1

1

1,1

1,1

1,0

1,0

0,5

0,5

0

0

0

0 10 20 30 40 50 60

10

min

1

1,11,0

0,5

00 10 20 30 60 120

≤ 0,06 MPa

≤ 0,02 MPa

180

min

min

MD

PM

DP

MD

P

1

1

1,1

1,1

1,0

1,0

0,5

0,5

0

0

0

0 10 20 30 40 50 60

10

min

1

1,11,0

0,5

00 10 20 30 60 120

≤ 0,06 MPa

≤ 0,02 MPa

180

min

min

MD

PM

DP

Pressure testing protocol according to ÖNORM EN 806-4 for KELEN-Drinking water systems test medium: drinking water

Client: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Contractor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Subject: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test section: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pipe materials and dimensions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . System vents:

Temperature compensation: Visual inspection:

Maximum system operating pressure MDP: . . . . . . . . . . Test pressure 1.1 x MDP: . . . . . . . . . . .

Pipes: d 16 . . . . . . . . . . . . m Pipes: d 40 . . . . . . . . . . . . mPipes: d 20 . . . . . . . . . . . . m Pipes: d 50 . . . . . . . . . . . . m Pipes: d 25 . . . . . . . . . . . . . m Pipes: d 63 . . . . . . . . . . . . mPipes: d 32 . . . . . . . . . . . . . m Pipes: d 75 . . . . . . . . . . . . m

Test procedure A – test time 10 minutes

Metal and composite pipe systems – all sizesPlastic systems and combined systems with plastics ≤ DN 50/OD 63Choice of test method B or C

Test procedure B – test time 60 minutes Plastic systems and combined systems with plastics > DN 50/OD 63

Test procedure C – test time 180 minutes Plastic systems and combined systems with plastics > DN 50/OD 63

Notes:• Temperature fluctuations can affect the test pressure!• Each pressure test is a snapshot survey of the actual condition and it cannot guarantee

no installation faults.• Following a successful pressure test, we would recommend the creation of a confirmed test protocol.

Confirmation:

Clerk: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Date: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time: from: . . . . . . . . . . . . . . . . to: . . . . . . . . . . . . . . . . . .

Client: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4948

Page 26: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

A pressure test with air or inert gases takes place using a two-step procedure consisting of the leak test and the load test. For ≤ DN 50/ OD 63 pipes the leak test can be carried out in 2 ways.

The pressure test with light or inert gases can be carried out bit by bit, and may not replace the final pressure test with drinking water!

The pressure test must be performed with light or inert gases that is / are largely free of oil and dust, and it is suitable for all pipe materials. In buildings with higher hygiene demands (e.g. medical establishments) inert gas must be used for the pressure test.

Due to the compressibility of the medi-um, during a pressure test with light or inert gases no pressure test greater than 300 kPa (3 bar) may be applied, for safety reasons.

Higher test pressures comprise a large safety risk and they do include the test accuracy. The safety of people and goods must be considered during the test.

During a pressure test, division into small line sections ensures a higher test accuracy and the-refore a higher level of safety. A gradual incre-ase in pressure is useful as an additional secu-rity measure.

All pipe openings must be well sealed against the test pressure (with sufficient strength) with plugs or blind flanges.

During a pressure test with light or inert gases, the connection parts of the pipe elements must be accessible and visible. Bleed valves are provi-ded for the safe discharge of the test pressure.

If any leakage is detected, or a drop in pressu-re is noticed, then all connections must be tested for leaks using appropriate bubbling test equip-ment, and the pressure test must be repeated after the leaks have been eliminated.

Two-step pressure test for all pipes ≤ DN 50/OD 63

Consisting of leak test (variant 1 or 2) and load test

Leak test – variant 1 Pressure test 15 kPa (150 mbar) – test time 60 minutes. Display accuracy of the pressure gauge or standpipe to the nearest 0.1 kPa (1 mbar)

Leak test – variant 2 Test pressure 100 kPa (1 bar) – test time 60 minutes. Display accuracy of the pressure gauge to the nearest 5 kPa (50 mbar); in addition, all connection points in the system must be checked for leakage with appropriate bubbling test equipment.

Load testTest pressure 300 kPa (3 bar) – test time 10 minutes. Display accuracy of the pressure gauge to the nearest 10 kPa (100 mbar)

Two-level pressure test for all pipes > DN 50/OD 63

Consisting of leakage test and load test

Leakage testTest pressure 15 kPa (150 mbar) – test time 90 minutes. Display accuracy of the measuring gauge or standpipe to the nearest 0.1 kPa (1 mbar); in addition, all connection points in the system must be checked for leakage with appropriate bubbling test equipment.

Load testTest pressure 100 kPa (1 bar) – test time 10 minutes. Display accuracy of the pressure gauge to the nearest 10 kPa (100 mbar).

Pressure testing protocol according to ÖNORM B 2531 for KELEN-Drinking water systems test medium: air or inert gases

Client: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Contractor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Subject: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test section: . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pipe materials and dimensions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . Temperature compensation:

Maximum system operating pressure MDP: . . . . . Visual inspection:

Two-stage pressure test for all pipes ≤ DN 50/OD 63: consisting of leak test (variant 1 or 2) and load testLeakage test – variant 1 Test pressure 15 kPa (150 mbar) – test time 60 minutes

Leakage test – variant 2 Test pressure 100 kPa (1 bar) – test time 60 minutesIn addition, all component points in the system must be checked for leakage using appropriate bubbling test equipment.

Load test Test pressure 300 kPa (3 bar) – test time 10 minutes

Two-stage pressure test for all pipes > DN 50/OD 63: consisting of Leak test and load test

Leak test Test pressure 15 kPa (150 mbar) – test time 90 minutesIn addition, all component points in the system must be checked for leakage using appropriate bubbling test equipment.

Load test Test pressure 100 kPa (1 bar) – test time 10 minutes

Notes• Followingasuccessfulpressuretest,wewouldrecommendthecreationofa

confirmed test protocol.• InaccordancewithÖNORMEN806-4,apressuretestwithlightorinertgasescannotreplace

a pressure test; it must be performed immediately prior to the activation of the system.

Confirmation

Clerk: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Date: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time: from: . . . . . . . . . . . . . . . . . . . . . . . to: . . . . . . . . . . . . . .

Client. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure test – drinking water systems with air or inert gases according to ÖNORM B 2531

5150

Page 27: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

Heat insulation for potable water pipesDrinking water pipes (cold)Cold water pipes need to be insulatedagainst warming and condensation.It must be ensured that the water qualityis not reduced as a result of the waterwarming.

DIN 1988/2 specifies the minimuminsulation thickness for potable waterpipes when the medium temperature isassumed to be 10°C.

Type of Installation Thickness of insulation mm

Exposed pipework in an unheated room (e.g. cellar) 4 KELEN LX-4

Exposed pipework in an heated room 13 KELEN+Insulation

Pipework underground with no adjacent hot water pipes 4 KELEN LX-4

Pipework underground next to hot water pipes 13 KELEN+Insulation

Pipework in wall, riser 4 KELEN LX-4

Pipework on concrete ceiling 4 KELEN LX-4

Drinking water pipes (hot)We recommend that hot water pipes areinsulated in accordance with DIN 1988/2.If there is no requirement for hot waterin circulation it is usually possible to dowithout insulation for pipes up to 25 mm.

Even thin insulation reduces theheat loss considerably!See pages 16 and 17.

Technical rules for drinking waterAssuming that the design and installationhas been done professionally werecommend that the following guidelinesare followed.

RinsingAfter pressure testing the drinking waterpipes must be rinsed.Depending on the size of the installationand how the piping is run the systemshould be rinsed in sections from thebottom to the top.Each riser is rinsed in turn and the lengthof piping should not exceed 100 m.DIN 1988/2, table 10, specifies theminimum number of draw-off points thathave to be opened. Under normalcircumstances all draw-off points shouldbe opened. The rinsing time depends onthe length of piping and should not beless than 15 seconds for each metre ofpipe. The rinsing time at each draw-offpoint should be at least 2 minutes. Afterthe pipe has been rinsed for approx. 2minutes at the last draw-off point all thedraw-off points are closed in the reverseorder to which they were opened.

Sound controlDIN 4109 recommends the followingmeasures:l Use low-sound faucetsl Avoid direct contact between pipes

and other sound transmitting bodies when fixing the pipe.

l Avoid high pressures and high flow velocities

l Special measures should be taken for sound sensitive areas

l Cover with sound reducing insulationl KELEN LX pipes

(4 mm or 9 mm insulation) The bubble structure of the insulation provides excellent protection against sound transmission. The high strength of the insulation cover provides a long term barrier between the pipe and other sound transmitters.

DIN 1988/2

Largest nominal diameter of the distributing pipe DN 25 32 40 50 65 80 100

Minimum flow through the completely full distributing pipe I/min 15 25 38 59 100 151 236

Minimum number of draw-off points to be opened DN15 1 2 3 4 6 9 14

Minimum flow and minimum number of draw-off points to be opened for rinsing ata minimum velocity of 0,5 m/so

5352

Page 28: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

7.Avoid using heat tobend the pipes(it is possible to bendthe cold pipe to a

radius of 8 x d). If the pipe has to be heated then only use hot air. Never heatthe pipe with a naked flame!Maximum temperature for bendingthe pipe: 140°C

8.Try to make the jointsfor standard sectionsof piping at the workbench before they areinstalled. This saves time

and increases the security of the system.

9.Once the system hasbeen installed itshould be subjected topressure testing.

You can copy pages 48 and 49 of thecatalogue to make a test report.

10.•Atemperatureof90°C for short periodsof time is NO problemfor KELEN®. Highertemperatures over lon-

ger periods of time should be avoided. The pipe system is suited for thermal disinfection.•Thegradualorcontinual(max.6months)disinfection of the pipe system with chlorine dioxide, chlorine or ozone is only permitted for the cold water system and after consultati-on with KE KELIT.•Excessiveconcentrationsarenotonlythreatening to health they can also causepremature ageing of pipe systems.•Copperundcopperionshaveadestabi- lising effect and their presence in the system should be avoided.

11.The followingprecautions can bemade to ensure thatthe maximum

operating temperature is not exceeded:•Monitorandregulatesolarenergystorage.•Checktheelectricconnectionstothehotwater storage before the system isoperated.•Werecommendinstallinginthehotwater piping a mixer valve which isregulated by the boiler.

12.In order to qualify forguarantee cover eachinstallation must useKELEN® system partsonly.

13.In order to install theKELEN® systemcorrectly a minimalamount of

expenditure is required for tools For yourown security we recommend that you useand maintain the tried and trusted tools.

14.If you are in doubt donot hesitate to consultour technicians.There is not always a

perfect solution but we can always help.

Summary of the instruction guidelines

1.The KELEN® pipesystem is made ofplastic and needs to betreated carefully to

prevent shocks and impact on the pipeduring transportation, storage andinstallation.

2.Protect the pipes,fittings andcomponents fromlengthy exposure to

direct UV radiation from the sun.The usual time required for storage andinstallation will have no effect on thematerial as it is stabilised against UV raysbut the material is not resistant to long termUV exposure.

3.The welding machinesare regulated tooperate at 260° C.Welding times

are based on an ambient temperatureof 20°C.If the ambient temperature changes thetime required to push the pipe and fittingon to the heating elements (before theheating time begins) may alter slightly.

4.Any corrections to thealignment of pipe andfitting up to amaximum of 5 must

be made during the welding procedure(see pages 18 – 25 for the permissibletime for adjustments). Any later correctionswill damage the joint.

5.Do NOT screw anythreaded pipes or anycast iron fittings intothe female threads of

the metal moulded fittings.Only join to faucets and components withstraight threads. The threaded joint canbe sealed by the usual methods (hemp,paste, tape …).Do not over twist the threads.

6.The expansion ofKELEN® pipes isclearly defined andmust be accounted for

in the design and installation of the system.

Please refer to pages 42– 47 regardingthe methods of accommodating theexpansion of exposed piping

•KELITAlucompositepipe(page14)•Pipechannels(page47)•Expansionloops(pages42and43)

For longer sections of piping the fixedpoints can be located in such a way thatthe system is split into expansion zones.Suppliers of pipe clamps and bracketsoffer a wide range of solutions.

5554

Page 29: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

K06 KELIT-ALU composite pipe PN20

KE00 KELEN® pipe PN20

KE08 KELEN® pipe PN16

d s di L Weight Vmm mm mm m kg/m l/m20 2,8 14,4 4 0,21 0,1625 3,5 18,0 4 0,32 0,2532 4,4 23,2 4 0,47 0,4240 5,5 29,0 4 0,70 0,6650 6,9 36,2 4 1,03 1,0363 8,6 45,8 4 1,60 1,6575 10,3 54,4 4 2,22 2,3290 12,3 65,4 4 3,15 3,36

d s di L Weight Vmm mm mm m kg/m l/m20 3,4 13,2 4 0,17 0,1425 4,2 16,6 4 0,27 0,2232 5,4 21,2 4 0,43 0,3540 6,7 26,6 4 0,67 0,5650 8,3 33,4 4 1,04 0,8863 10,5 42,0 4 1,65 1,3975 12,5 50,0 4 2,34 1,9690 15,0 60,0 4 3,36 2,83110 18,3 73,4 4 5,01 4,23

d s di L Weight Vmm mm mm m kg/m l/m20 2,8 14,4 4 0,15 0,1625 3,5 18,0 4 0,23 0,2532 4,4 23,2 4 0,37 0,4240 5,5 29,0 4 0,58 0,6650 6,9 36,2 4 0,90 1,0363 8,6 45,8 4 1,41 1,6575 10,3 54,4 4 2,01 2,3290 12,3 65,4 4 2,87 3,36110 15,1 79,8 4 4,30 5,00

KE02 KELEN® pipe PN10

d s di L Weight Vmm mm mm m kg/m l/m20 1,9 16,2 4 0,11 0,2125 2,3 20,4 4 0,17 0,3332 2,9 26,2 4 0,27 0,5440 3,7 32,6 4 0,42 0,8350 4,6 40,8 4 0,66 1,3163 5,8 51,4 4 1,04 2,0775 6,8 61,4 4 1,41 2,9690 8,2 73,6 4 2,11 4,25110 10,0 90,0 4 3,01 6,36125 11,4 102,2 4 3,92 8,20160 14,6 130,8 4 6,35 13,52

Product rangeThe KELEN®pipe system is constantlybeing extended and updated to meet therequirements of the industry.Please refer to the current KELEN®pricelist for the complete product range.The abbreviated references, e.gKE00 (= PN20 pipe) orKE30 (= tee), simplify the administration.Please refer to the KE numbers when youplace your order.

On request and subject to minimumquantities and capacities we canmanufacture special types of fittings(e.g. 30° elbow).

5756

Page 30: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE70 Elbow 45°

KE20 Elbow 90°

KE10 Socket

di z t AD VPmm mm mm mm Pcs20 12 15 29 1025 13 20 36 1032 15 22 46 1040 21 25 53 550 25 26 68 263 32 29 85 175 37 30 101 190 48 34 122 1

di z t AD VPmm mm mm mm Pcs20 11 15 29 1025 16 20 36 1032 20 22 46 1040 27 25 54 550 32 26 68 263 36 29 85 175 41 30 102 190 50 34 122 1110 58 37 145 1

di z t AD BL VPmm mm mm mm Pcs20 1,5 15 29 33 1025 1,5 20 36 43 1032 1,5 22 46 51 1040 2,5 25 54 57 550 2,5 26 68 60 263 2,5 29 85 62 175 2,5 30 101 65 190 3 34 121 74 1110 5,5 37 145 85 1

KE00-LX9 KELEN® LX-SENSO pipe PN20

KE00-LX4 KELEN® LX-SENSO pipe PN20

KE08-LX9 KELEN® LX-SENSO pipe PN16

KE08-LX4 KELEN® LX-SENSO pipe PN16

KE02-LX4 KELEN® LX-SENSO pipe PN10

d s di IS L Weight Vmm mm mm mm m kg/m l/m20 3,4 13,2 9 4 0,25 0,1425 4,2 16,6 9 4 0,34 0,2232 5,4 21,2 9 4 0,50 0,35

d s di IS L Weight Vmm mm mm mm m kg/m l/m20 3,4 13,2 4 4 0,21 0,1425 4,2 16,6 4 4 0,30 0,2232 5,4 21,2 4 4 0,46 0,35

d s di IS L Weight Vmm mm mm mm m kg/m l/m20 2,8 14,4 9 4 0,22 0,1625 3,5 18,0 9 4 0,30 0,2532 4,4 23,2 9 4 0,44 0,42

d s di IS L Weight Vmm mm mm mm m kg/m l/m20 2,8 14,4 4 4 0,18 0,1625 3,5 18,0 4 4 0,26 0,2532 4,4 23,2 4 4 0,40 0,42

d s di IS L Weight Vmm mm mm mm m kg/m l/m20 1,9 16,2 4 4 0,14 0,2125 2,3 20,4 4 4 0,20 0,3332 2,9 26,2 4 4 0,30 0,54

Diagram for all KELEN LX-SENSO pipes

5958

Page 31: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE35 Reducer tee

KE36 Reducer tee

di di1 z t z1 t1 AD BL VPmm mm mm mm mm mm mm mm Pcs25 20 16 20 16 15 36 68 1032 20 20 22 26 15 46 84 532 25 20 22 22 20 46 84 540 20 27 25 27 15 54 94 540 25 27 25 24 20 54 94 540 32 27 25 26 22 54 94 550 20 32 26 32 15 68 112 250 25 32 26 28 20 68 112 250 32 32 26 30 22 68 112 250 40 32 26 29 27 68 112 263 25 36 29 40 20 85 128 163 32 36 29 36 24 85 128 163 40 36 29 37 27 85 128 163 50 36 29 36 28 85 128 175 32 41 30 42 22 102 142 175 40 41 30 41 27 102 142 175 50 41 30 40 28 102 142 175 63 41 30 39 29 102 142 190 63 50 34 54 29 122 166 190 75 50 34 50 30 122 166 1110 63 58 37 70 29 145 195 1110 75 58 37 68 30 145 195 1110 90 58 37 65 34 145 195 1

di di1 di2 z t z1 t1 z2 t2 AD BL VPmm mm mm mm mm mm mm mm mm mm mm Pcs20 25 20 16 15 16 20 16 15 36 68 1025 20 20 16 20 18 15 18 15 36 68 1025 25 20 16 20 16 20 18 15 46 84 1032 20 25 20 22 26 15 22 20 46 84 532 25 20 20 22 22 20 26 15 46 84 532 25 25 20 22 22 20 22 20 46 84 532 32 20 20 22 20 22 26 15 46 84 532 32 25 20 22 20 22 22 20 46 84 5

KE26 Elbow 90° (male/female)

KE27 Elbow 45° (male/female)

KE30 Equal tee

d/di z t z1 t1 AD VPmm mm mm mm mm mm Pcs20 11 15 33 15 29 1025 16 20 42 20 36 10 32 20 22 42 22 43 5

d/di z t z1 t1 AD VPmm mm mm mm mm mm Pcs20 11 16 31 16 29 1025 18 20 33 20 36 10

di z t AD BL VPmm mm mm mm mm Pcs20 11 15 29 52 1025 16 20 36 68 1032 20 22 46 84 540 27 25 54 94 550 32 26 68 112 263 36 29 85 128 175 41 30 102 142 190 50 34 122 166 1110 58 37 145 195 1

6160

Page 32: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE47 Saddle Fitting

KE60 End cap

KE61 Manifold cap

KE90 Curved pipe

d di t AD BH VPmm mm mm mm mm Pcs40–63 20 15 36 29 575–125 20 20 36 29 540–63 25 20 36 29 575–125 25 20 36 29 5

di z t AD BL VPmm mm mm mm mm Pcs20 8 16 29 24 1025 9 21 36 30 1032 11 22 46 36 1040 13 25 53 38 550 17 26 67 43 563 19 30 84 49 575 21 31 100 52 190 26 36 120 62 1110 41 37 145 78 1

d t AD BL VPmm mm mm mm Pcs25 18 36 48 10

d z AD BL VPmm mm mm mm Pcs20 215 45 430 1025 215 48 430 1032 215 55 430 5

KE38 Manifold tee (male/female)

di/d di1 z t z1 t1 AD BL VPmm mm mm mm mm mm mm mm Pcs25 20 13 20 16 15 36 71 10

KE41 Reducer (male/female)

d di z t BL AD VPmm mm mm mm mm mm Pcs25 20 23 15 38 29 1032 20 27 15 42 29 1032 25 27 20 47 36 1040 20 29 15 44 29 540 25 28 20 48 36 540 32 36 22 60 45 550 32 65 20 85 45 250 40 56 24 80 53 263 40 61 24 85 53 163 50 61 24 85 68 175 50 68 26 94 68 175 63 65 29 94 84 190 63 66 29 95 84 190 75 66 29 95 101 1110 63 61 24 87 85 1110 75 61 29 90 101 1110 90 61 32 93 119 1

6362

Page 33: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE81LA LA Wall bracket 90° (male) 50 mm

KE11 Male adapter

K84 Fitting for partition wall connection

di AG z t t1 K BL VPmm Inch mm mm mm mm mm Pcs20 1/2" 13 15 50 43 98 10

di AG z t AD BL SW VPmm Inch mm mm mm mm mm Pcs20 1/2" 44 15 45 60 - 1020 3/4" 44 15 45 60 - 1025 1/2" 40 20 45 60 - 1025 3/4" 40 20 45 60 - 1032 3/4" 48 22 60 72 - 532 1" 59 22 60 83 39 540 1" 62 25 76 87 39 240 5/4" 65 25 76 90 46 250 6/4" 68 26 82 92 52 163 2" 80 29 97 107 64 175 21/2" 90 30 123 120 80 1

IG AG AG t BL SW VPInch Inch mm mm mm mm Pcs1/2" 1/2" M28x1,5 50 64 30 5

KE83 Wall bracket 90° (female)

KE83HA Partition wall fiitting 90°(female) 50 mm

KE83SP Flush box fitting 90°(female) 15 mm

di IG zi z1 t AD BL VPmm Inch mm mm mm mm mm Pcs20 1/2" 13 21 15 41,5 48,5 1020 3/4" 17 26 15 46 57 1025 1/2" 17 26 20 46 57 1025 3/4" 17 26 20 46 57 10

di IG AG z t t1 K BL SW VPmm Inch mm mm mm mm mm mm mm Pcs20 1/2" M28 x1,5 13 15 50 43 98 30 5

di IG AG z t t1 K BL SW VPmm Inch mm mm mm mm mm mm mm Pcs20 1/2" M28 x1,5 13 15 15 43 63 30 5

DO NOT join to any threaded pipes or cast iron fittings!

DO NOT join to any threaded pipes or cast iron fittings!

DO NOT join to any threaded pipes or cast iron fittings!

6564

Page 34: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE23 Elbow adapter 90° (female)

KE31LA LA Tee with male thread 50 mm

di IG z t zi AD SW VPmm Inch mm mm mm mm mm Pcs20 1/2" 13 15 21 42 - 1020 3/4" 13 15 21 42 - 1025 1/2" 17 20 21 46 - 1025 3/4" 17 20 21 46 - 1032 3/4" 20 24 21 46 - 532 1" 20 24 38 61 39 5

KE31 Tee with male thread

di AG z t zi AD BL SW VPmm Inch mm mm mm mm mm mm Pcs20 1/2" 13 15 49 29 54 - 1020 1/2"BF 13 15 49 29 54 - 1025 3/4" 17 20 60 36 66 - 1032 1" 20 24 78 46 86 39 5

di AG z t zi t1 AD BL VPmm Inch mm mm mm mm mm mm Pcs20 1/2"BF 13 15 85 50 29 54 10

DO NOT join to any threaded pipes or cast iron fittings!

KE13 Female adapter

KE43 Saddle fitting (female)

di IG z t AD BL SW VPmm Inch mm mm mm mm mm Pcs20 1/2" 18 15 45 45 - 1020 3/4" 18 15 45 45 - 1025 1/2" 16 20 45 45 - 1025 3/4" 16 20 45 45 - 1032 3/4" 25 22 60 68 - 532 1" 22 22 60 68 39 540 1" 27 25 76 70 39 240 5/4" 28 25 76 71 48 250 6/4" 30 26 82 71 56 163 2" 38 29 97 86 70 175 2 1/2" 44 30 123 96 88 1

KE21 Elbow adapter 90° (male)

di AG z t z1 AD SW VPmm Inch mm mm mm mm mm Pcs20 1/2" 13 15 49 42 - 1025 3/4" 17 20 52 46 - 1032 1" 20 22 61 61 39 5

d IG AD BH VPmm Inch mm mm Pcs40–63 1/2" 36 29 575–110 1/2" 36 29 5

DO NOT join to any threaded pipes or cast iron fittings!

DO NOT join to any threaded pipes or cast iron fittings!

6766

Page 35: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE50A Valve with stopper

KE50P Stop valve with stopper

KE50PF Valve with stem

di IG z t t1 AD BH VPmm Inch mm mm mm mm mm Pcs20 1/2" 21 15 80 30 127 520 1/2"BF 21 15 80 30 127 525 3/4" 23 20 80 37 132 5

di IG z t t1 AD BH VPmm Inch mm mm mm mm mm Pcs20 3/4" 23 15 80 37 132 125 3/4" 23 15 80 37 132 132 3/4" 21 20 80 43 132 1

di IG z t t1 AD BH VPmm Inch mm mm mm mm mm Pcs20 3/4" 23 15 46 37 93 125 3/4" 23 15 46 37 93 132 3/4" 21 20 46 43 93 1

KE33 Tee with female thread

KE50 Valve with stem

di IG z t zi AD BL SW VPmm Inch mm mm mm mm mm mm Pcs20 1/2" 13 15 23 30 56 - 1020 1/2"BF 13 15 23 30 56 - 1025 1/2" 17 20 32 37 66 - 1025 3/4" 17 20 32 37 66 - 1032 1" 20 22 42 46 84 39 5

di IG z t zi AD BH R VPmm Inch mm mm mm mm mm mm Pcs20 1/2" 21 15 80 30 127 70 125 3/4" 23 20 80 37 132 70 1

DO NOT join to any threaded pipes or cast iron fittings!

DO NOT join to any threaded pipes or cast iron fittings!

KE33HA Tee with female thread for partition walls

di IG AG z t t1 AD BL SW VPmm Inch mm mm mm mm mm mm mm Pcs20 1/2"BF M28 x1,5 13 15 50 29 99 30 10

6968

Page 36: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE52 Slanted seat valve with KE57 union

KE55 Union (plastic – metal)

KE56 Union (plastic – plastic)

d DN AG z t BL BH SW VPmm Inch mm mm mm mm mm Pcs20 15 1" 84 17 168 110 36 125 20 5/4" 95 20 190 130 46 132 25 6/4" 107 26 214 155 52 140 32 2" 147 50 294 180 66 150 40 2 1/4" 155 50 310 190 70 163 50 2 3/4" 165 50 330 225 86 1

d AG z t z1 BL SW SW1 VPmm Inch Inch mm mm mm mm mm Pcs20 1/2" 42 17 33 75 36 23 525 3/4" 49 20 40 89 46 30 532 1" 55 26 44 99 52 37 340 5/4" 85 50 52 137 66 45 250 6/4" 85 50 58 143 70 55 163 2" 85 50 65 150 86 66 175 2 1/2" 90 50 68 158 108 80 190 3" 90 50 73 163 122 94 1

d z t BL SW VPmm mm mm mm mm Pcs20 42 17 84 36 525 49 20 98 46 532 55 26 110 52 340 85 50 170 66 250 85 50 170 70 163 85 50 170 86 175 90 50 180 108 190 90 50 180 122 1

includes drainage and replaceable EPDM seals!

includes drainage and replaceable EPDM seals!

includes drainage and replaceable EPDM seals!

K50F Stem for KE50A and KE50P

K50C Stem for KE 50A

K50S Extension to K50C

AG BL AD SW VPInch mm mm mm Pcs3/4" 46 50 17 1

AG BL R VPInch mm mm Pcs1/2" 80 70 13/4" 80 70 1

IG AD BL VP Inch mm mm Pcs 1/2"–3/4“ 26 150 1

7170

Page 37: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE18 Backing ring PP-R

di DN z t BL AD VPmm mm mm mm mm Pcs20 15 5 16 21 45 125 20 5 18 23 58 132 25 5 19 24 68 140 32 4 22 26 78 150 40 6 24 30 88 163 50 5 28 33 102 175 65 6 32 38 122 190 80 5 37 42 138 1110 100 5 42 47 158 1

KE19 PP flange with steel insert

d DN di LK d1 Holes BL AD VPmm Inch mm mm mm mm mm mm Pcs20 15 28 65 14 4 12 95 125 20 34 75 14 4 12 105 132 25 42 85 14 4 16 115 140 32 51 100 18 4 16 140 150 40 62 110 18 4 18 150 163 50 78 125 18 4 18 165 175 65 92 145 18 4 18 185 190 80 108 160 18 8 18 200 1110 100 135 180 18 8 18 220 1

Sizing according to DIN 2501 PN16

KE85 Joining set

Dimension Setting VP mm Pcs d20 x 1/2" Single outlet 1 d20 x 1/2" 80 – 100 1 d25 x 1/2" 80 – 100 1 d20 x 1/2" 150 1 d25 x 1/2" 150 1

Includes KE83 with sound insulation,stoppers, metal plate, pegs andscrews.

KE57 Union with female thread

d IG z t BL SW VPmm inch mm mm mm mm Pcs20 1" 44 17 53 36 525 5/4" 50 20 60 46 532 6/4" 56 26 67 52 340 2" 87 50 103 66 250 2 1/4" 87 50 103 70 163 2 3/4" 87 50 103 86 175 3 1/4" 93 50 114 108 190 3 3/4" 93 50 115 122 1

KE17 E-UNI Welding socket

di z t AD BL VPmm mm mm mm mm Pcs20 1,5 26 48 55 125 1,5 26 54 55 132 1,5 25 62 53 140 1,5 25 70 53 150 1,5 25 80 53 163 1,5 30 94 63 175 2 33 107 70 190 2 36 121 76 1110 2,5 41 143 87 1125 3 82 164 165 1160 3 89 200 177 1

KE85SB Joining set

Dimension Setting VP mm Pcs d20 x 1/2" 80 – 100 1 d25 x 1/2" 150 1

Includes KE83 with sound insulation, stoppers, metal plate, pegs and screws, siphon trap and d30 rubber nipple.

DO NOT join to any threadedpipes or cast iron fittings!

7372

Page 38: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

KE41ST Reducer PN10

KE18ST Welding neck PN10

KE19ST Flange PN10

d d1 BL VPmm mm mm Pcs125 90 190 1125 110 200 1 160 125 225 1

d AD BL VPmm mm mm Pcs125 158 173 1160 125 202 1

d DN di LK d1 Holes BL AD VP mm Inch mm mm mm mm mm mm Pcs 125 110 135 180 18 8 18 220 1 160 150 178 240 22 8 24 285 1

KE35ST Reducer tee PN10d d1z z1 z1 BL BH VP mm mm mm mm mm mm Pcs125 63 170 170 340 240 1 125 90 170 170 170 240 1 125 110 170 170 340 240 1 160 90 220 180 424 260 1160 110 220 200 424 280 1

KE20ST Elbow 90° PN10KE20ST Elbow 90° PN10

KE70ST Elbow 45° PN10

KE30ST Equal tee PN10

d z BL VPmm mm mm Pcs125 164 229 1160 220 300 1

d z VPmm mm Pcs125 133 1160 172 1

d z z1 BL BH VP mm mm mm mm mm Pcs125 175 175 355 240 1160 220 220 440 300 1

Butt welding fittings

Sizing according to DIN 2501 PN16

7574

Page 39: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

K84K Sound insulation cap

d di D AD BL VPmm mm mm mm mm Pcs20 41,5 53 75 52 1025 46 53 75 60 10

K86L Perforated plate

K86D Pegs for K86L

BL BH ST VPmm mm mm Pcs2000 60 3 1

VP Pcs 10

Sound insulation for KE83.Does NOT fix or secure the fitting.

Steel plate for securing fittingsin all positions.

Includes sound insulating discs and screws.

KE19A Flange seal set plastic - metal

KE19K Flange seal set plastic - plastic

KE99 Repair plug

d Holes VP mm Pcs Pcs 20 4 1 25 4 1 32 4 1 40 4 1 50 4 1 63 4 1 75 4 1 90 8 1 110 8 1 125 8 1 160 8 1

d Holes VP mm Pcs Pcs 20 4 1 25 4 1 32 4 1 40 4 1 50 4 1 63 4 1 75 4 1 90 8 1 110 8 1 125 8 1 160 8 1

d BL VP mm mm Pcs 7–11 120 10

1 set consisting of screws, bolts, washers and EPDM seal.

1 set consisting of screws, bolts, washers and EPDM seal.

K85A Rail

Setting A1 A2 AL BL BH BT ST R VPmm Inch mm mm mm mm mm mm mm PcsSingle - - - 228 60 45 3 - 180-100 80 100 210 456 60 45 3 - 1150 130 150 260 506 60 45 3 30 1i

K85H Rail for partition walls

BL BH BT ST VPmm mm mm mm Pcs350 60 45 3 1

Accessoires

7776

Page 40: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

WZ100 Welding set

WZ110 Pipe welding machine

WZ120 Overhead welding machine

WZ115 Butt welding machine

Pipe welding machine 230 Volt, 800 WattIncludes case, table clamp and floor rest Pipe cutters d16 – 40 mm.Heating elements: d20 – 32 mm

Heating elements: d20 – 40 mm

Pipe welding machine 230 Volt, 1000 WattIncludes case,heating elements d20 – 90 or d25 – 125,Pipe cutters d20 – 75, d50 – 140,special gloves and pipe rests.Packaged in transport crate.

Type 1 d20 – 90Type 2 d25 – 125

For making polyfusion joints in areas that cannotbe accessed with the table welding machine.Can be used for the pipe types KE00, KE02,KE06 and KE08. Includes hand weldingmachine (1200 Watt), d50 – 110 weldingtools, d16–75 and d50–140 pipe cutters,timer and special gloves. Packaged in transport crate.

Weight of machine: approx. 12 kilos

hydraulic butt welding machine 230 Volt,1000 WattIncludes plane cutter, welding plate,d40 –160 welding tools.Packaged in transport crate.

KELIT tools

K88 Pipe channel

di s L VPmm mm mm Pcs20 0,6 2000 2025 0,6 2000 2032 0,6 2000 2040 0,6 2000 1050 0,8 2000 1063 0,8 2000 1075 0,8 2000 1090 0,8 2000 10110 0,9 2000 10

Galvanised steel – d20, d25and d32 have clips to lock thepipe into the channel.

K95 Stopper

AG BL D IB VPinch mm mm mm Pcs1/2" 80 36 12 103/4" 80 42 12 10

K86HA Fixing plate

A1 A2 A3 BL BH R VPmm mm mm mm mm mm Pcs150 100 80 200 80 65 1

Octagonal holes to prevent twistingof KE83HA and K84 and elastomercovering for dry wall installations.

7978

Page 41: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

WZ128 Repair welding tool

WZ130 Pipe cutter

WZ130 Wheel pipe cutter

d VP mm Pcs 7 1 11 1

d VP mm Pcs 16–40 1 Replacement blade 1

d VP mm Pcs 16–75 1 50–140 1Replacement whee: small 1Replacement whee: large 1

Heating elements for weldingthe repair plugs

Size of drilled holesFor d7 = 6 mm holeFor d11 = 10 mm hole

WZ129 Timer

WZ122 Polyfusion welding tool

WZ125 Saddle drill

WZ124 Saddle welding tool

For setting and checking the welding timesof d20 – 110 pipes.

d VP mm Pcs 20 1 32 1 40 1 50 1 63 1 75 1 90 1 110 1

d VP mm Pcs 24 1

d VP mm Pcs 40–63x20/25 1 75–125x20/25 1

Heating elements

For welding the saddle fittings

For drilling the pipes before weldingthe saddle fitting.

8180

Page 42: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

WZ150 Alu peeler

WZ138 Bending tool for K86 L

WZ155 Setting gauge

d mm 20 25 32 40 50 63 75 90

Settings mm 75 100 120 150 200 240

For peeling KELIT ALU composite pipes K06before welding. Remove the screw to extend thepeeling area if the pipe is going to be welded toan E-UNI socket KE17.Peeler can be connected to a drill.

for bending the perforated plate K86L

WZ140 E-socket welding machine

WZ141 E-socket welding machine

WZ146 E-socket aligner

WZ145 Pipe scraper

For welding the E-UNI welding socketKE17 Hand scraper included.

For welding the E-UNI welding socketKE17 Hand scraper included.

For fixing the electrofusion socket

For setting the outlets adjustable depth

For scraping the surface of the pipe before electrofusion welding

Hand scraperPipe shaver d63– d160

d VP mm Pcs 20 – 110 1

d VP mm Pcs 20 – 450 1

d VP mm Pcs 20 – 63 1 63 – 160 1

8382

Page 43: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

8584

Page 44: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

The technical contents in this brochure are for your information and consultation. We are not liable for thecontents. The application and installation of the products should be adapted to the individual requirements of each project. KE KELIT is constantly improving its products a nd retains the right to make technical changes in the course of these improvements. We are not liable for printing and spelling errors.© by KE KELIT, KELEN Handbook 10/2014 engl.

8786

Please note that for technical printingreasons the numbers are written accordingto the common practice in the German speaking countries (i.e. the number and the decimals are separated by a comma).

Full technical back-up and support for the KELEN-pipe system is provided by KE KELIT-Austria/Europe.

The network of sales partners, subsidiariesand agents is constantly being expanded.Please ask at the Austrian headquartersfor the current status.

KE KELITKunststoffwerk GesmbH. Ignaz-Mayer-Straße 17A-4020 LinzAustria – Europe

Tel. +43 (0)5 07791 Fax +43 (0)5 0779 118

[email protected] www.kekelit.com

Page 45: The blue line - KE KELIT Innovative pipe systemskekelit.com/uploads/media/KELEN_Handbook_EN.pdf · The blue line DRINKING WATER PIPE SYSTEM Handbook 2014. ... ∆p Total pressure

��������

����������������������������

�������� �������������

Certified Quality Assurance System by ÖQS

ÖNORM EN ISO 9001:2000 Reg.Nr.366/0

Member of theAustrian Working Group

PLASTIC PIPERECYCLING

ARA-Lizenz Nr.9087

KE KELITKunststoffwerk GesmbH. Ignaz-Mayer-Straße 17A-4020 LinzAustria – Europe

Tel. +43 (0)5 0779 Fax +43 (0)5 0779 118

[email protected] www.kekelit.com