Testing Off-Grid Operations onDigester (Low Btu) Fuels

Page 2: Testing Off-Grid Operations on Digester (Low Btu) Fuels

PurposeThe main priority for the summer was qualifying theGT333S on low caloric value fuels (500-800 Btu/scf) bytesting four areas*:• Ignition• Off-Grid Load Following (topic of this presentation)• Fuel Following• Emissions

*Sensitive information was removed from the following presentation due to proprietary rights. 2

New key feature: Inlet guide vanes improve part‐load conditions

Page 3: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Presentation Overview• Concepts• Testing / Data Collection• Off-Grid Load Following• Test 1 – Triple Pump-Jack Operations• Test 2 – Simulating Abrupt Power Demands

• Conclusion

3

Page 4: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Concepts• Combustion

• Minimum ignition energy• Air – fuel ratio• Flame stability• Rate of fuel flow and fuel supply pressure

• Modeling power cycles• Energy analysis Conservation of Energy!

• Brayton cycle with regeneration

4

Steady State

Page 5: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Testing and Data CollectionTests conducted on R&D GT333S at FlexEnergy’sPortsmouth production facility.

FUEL: Mixed natural gas and CO2 to deliver desiredheating value to engine.

DATA: Unit’s monitoring system recorded engineparameters to an automated analysis log.

Criteria: Tests were considered successful if operatinglimits were within limits and no faults were tripped.

5

Page 6: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Test 1 – Triple Pump-Jack SimulationTwo minute cycles were applied to test the engine’sperformance throughout the Btu range of interest.

6

Page 7: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Test 1 – Triple Pump-Jack SimulationThe example below shows the load cycle denotedby kWe. Here you can see the engine was able tokeep the speed (NGEN1) relatively constant byadjusting the fuel input (Fuel Request).

7

Page 8: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Test 2 – Applied Load StepsThe following test ensured:1. Turbine generator can supply demanded power2. The generator braking resistor (GBR) is able to

absorb the power off loaded by the engine3. Minimum power setting for continuous engine

operation without triggering faults.

8

Page 9: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Test 2 – Fuel heating value of 600 Btu/scfNatural gas was diluted to 67% the mean heatingvalue for this test and the engine operated steadywith no faults.

9

X1 X2

Page 10: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Test 2 – Fuel heating value of 540 Btu/scfFurther fuel dilution, the engine was unable tooperate when the load demand was too low.

10

X1

Page 11: Testing Off-Grid Operations on Digester (Low Btu) Fuels

Test 2 – Fuel heating value of 540 Btu/scfThe test on 60% diluted natural gas providedvaluable results to improve the engine control andmonitoring system. At the conclusion of thefellowship, further testing was needed to verify therecommended minimum power settings.

11

Page 12: Testing Off-Grid Operations on Digester (Low Btu) Fuels

ConclusionTest 1GT333S can successfully handle three pump-jackloads in the desired Btu range. Important to note,the engine speed stayed relatively constant, varyingless than 1.5% from the design speed.

Test 2GT333S can provide the necessary loads for off-grid operations running on digester gas. Arecommended minimum power setting requiresfurther testing.

12

Page 13: Testing Off-Grid Operations on Digester (Low Btu) Fuels

AcknowledgementsI would like to thank the entire FlexEnergy team for their support andprofessionalism to create an exceptional workplace. The patiencedemonstrated by team members who were readily available to assist me wasnot overlooked. In particular I would like to thank Jeff Armstrong for his adviceand guidance throughout the fellowship. Tom Hackett, Dr. Chris Bolin, AdamMitchneck, and Dr. Mohammed Ebrahim for their assistance on testing andsharing their knowledge with me.