  • 789 Dixboro Road, Ann Arbor, Michigan 48105-9723 USA1-800-NSF-MARK 734-769-8010

    www.nsf.org

    FI20080218111153 J-00054243

    NSF InternationalFebruary 18, 2008

    This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

    Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

    Page 1 of 5

    TEST REPORT

    Send To:GOSLYN LP2710 SYLVAN WAYMC KINNEY TX 75070Attn: MR. JOHN C. SOWERBY

    Thank you for having your product tested by NSF.

    The enclosed report details the result of the testing performed on your product. Your program representative will

    Reviewer:

    be contacting you in the near future if there are any remaining issues concerning the status of this product.

    Please do not hesitate to contact us if you have any immediate questions pertaining to your product.

    CC:

    Sal Aridi - Manager, Engineering Laboratory

    Status: Pass

    Sample Description:Test Type:

    GOS 80 Grease Interceptor - 25GPM (Type A)QQ - Qualification Testing

    Plant:Customer:SHANGHAI SOLIO STAINLESS STEELPRODUCTS3758 JIAHANG ROADHUA TING COUNTY, JIAN DING DISTRICTSHANGHAICHINA

    GOSLYN LP1536 LANTERN TRAILFRISCO TX 75034

    Attn: MS. SHIRLEY ZHANG

    Attn: MR. JOHN C. SOWERBY

    PA Project: 9020674

    3C870*M

    3C870 3C871

    0015 - Mechanical Plumbing Products (including Section 9 of Standard 61) Program:Jennifer SharpProgram Rep:03 - AsiaRegion:

  • FI20080218111153 J-00054243This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

    Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

    Page 2 of 5

    Testing Parameter Result Units Entered On

    Test DescriptionActual Cold Water TemperatureRequired PressureActual PressureRequired Test DurationActual Test DurationActual leakagePressure Tests for Waste Fitting

    Connection Size and TypeRequired Diameter

    Manufacturer's name or trademarkModel number on labelRated flows on labelFlow restrictor on labelInlet and Outlet on labelProduct type by rating on labelEfficiency at rated capacity on labelNominal inlet size on labelLabeling in ComplianceInstallation Instr. in ComplianceMaintenance Instr. in CompliancePhysical Evaluation

    600.05 psi0.05 psi

    1515

    NonePass

    Goslyn L.P.GOS 8025 gpm

    YesYesYesYesYesYesYesPass

    degrees F

    minutesminutes

    Hydrostatic Pressure Test - Waste Fittings

    Grease Interceptor Physical Evaluation

    Engineering Lab

    15 Minute Hydrostatic Pressure Test

    2" Female NPT threads+/- 1 turn from flush; Measured 0.75 turns from

    flush

    "Flow control required, part No FC2"

    General Information

    Standard: 0MP - MECHANICAL PLUMBING PRODUCTS PROGRAM

    Description: GOS 80 - Grease InterceptorSampled Date: 02/08/2008Received Date: 02/13/2008

    Model Number GOS 80

    Performance Standard CSA B481.1

    Performance Standard Year 2007

    Sample Id: S-0000498960

  • FI20080218111153 J-00054243This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

    Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

    Page 3 of 5

    Job Notes:

    Inlet and outlet plumbing connections comply with ASME B1.20.1-1983

    This is a retest of job J-00051864 which failed hydrostatic pressureand markings. The access panel has been resealed and the label updatedto comply with the standard.

    Refer to job J-00024518 for grease performance results.

  • FI20080218111153 J-00054243This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

    Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

    Page 4 of 5

    Sample Under Test

    Sample Under Pressure

    Job Attachments:

  • FI20080218111153 Final_Std

    J-00054243This report shall not be reproduced, except in its entirety, without the written approval of NSF. This report does not represent NSF

    Official NSF Listing, (www.nsf.org). The results relate only to those items tested. Certification or authorization to use the NSF Mark. Authorization to use the NSF Mark is limited to products appearing in the Company's

    *J-00054243* Page 5 of 5

    References to Testing Procedures:

    NSF Reference Parameter / Test Description---------------------------- --------------------------------------------------------------------------------------------------------------P1198P1205

    Hydrostatic Pressure Test - Waste FittingsGrease Interceptor Physical Evaluation

    Testing Laboratories:Id--------------

    Address----------------------------------------

    All work performed at: NSF INTERNATIONAL789 N. DIXBORO ROADANN ARBOR MI 48105

    NSF_AA

    Test descriptions proceeded by an asterisk * indicate that testing has been performed per NSF International requirements but isnot within its scope of accreditation.