Upload
others
View
11
Download
0
Embed Size (px)
Citation preview
TEST REPORT
IEC 61730-2
PV Module Safety Qualification
Part 2: Requirements for testing
Report Reference No. .................... : SHES170400348203
Date of issue .................................... : Jan. 18, 2018
Total number of pages ...................... 34
Testing Laboratory ......................... : SGS-CSTC Standards Technical Services (Shanghai) Co., Ltd.
Address ............................................ : 588 West Jindu Road, Xinqiao, Songjiang, 201612 Shanghai, China
Applicant’s name............................ : Hangzhou Solar Photoelectricity Co., Ltd.
Address ............................................ : No.4 South Longxi Road, Jiulong Truck Road, Shouxiang Town, Fuyang City, Zhejiang Province, China
Test specification ........................... :
Standard ........................................... : IEC 61730-2:2004 modified + IEC 61730-2 AMD 1-2011-11
Test procedure ................................. : Testing
Non-standard test method................ : N/A
Test Report Form No. ................... : IEC61730_2A
Test Report Form Originator ............ : TÜV Rheinland Product Safety GmbH
Master TRF ...................................... : Dated 2007-11
Copyright © 2008 IEC System for Conformity Testing and Certification of Electrical Equipment (IECEE), Geneva, Switzerland. All
rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test
Certificate issued by an NCB in accordance with IECEE 02.
Test item description ..................... : Photovoltaic (PV) Modules
Trade Mark ....................................... :
Manufacturer .................................... : Same as applicant
Model/Type reference ...................... : With 6” poly c-Si cell
HZSxxxP-72 (xxx=285-320W, in steps of 5, 72 cells)
HZSxxxP-60 (xxx=235-280W, in steps of 5, 60 cells)
HZSxxxP-72 (xxx=180-220W, in steps of 5, 72 cut cells)
HZSxxxP-36 (xxx=005-150W, in steps of 5, 36 cut cells)
With 6” mono c-Si cell
HZSxxxM-60 (xxx=235-285W, in steps of 5, 60 cells)
HZSxxxM-72 (xxx=180-220W, in steps of 5, 72 cut cells)
HZSxxxM-36 (xxx=020-150W, in steps of 5, 36 cut cells)
Ratings ............................................. : Refer to page Annex 5
Page 2 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Testing procedure and testing location:
Testing Laboratory:
Testing location/ address ...................... : SGS-CSTC Standards Technical Services (Shanghai) Co., Ltd. 588 West Jindu Road, Xinqiao, Songjiang, 201612 Shanghai, China
Tested by (name + signature) ..... : Simon Shi
Approved by (+ signature) ........... : Erin Lin
Testing procedure: TMP
Tested by (name + signature) ..... :
Approved by (+ signature) ............ :
Testing location/ address ...................... :
Testing procedure: WMT
Tested by (name + signature) ..... :
Witnessed by (+ signature) .......... :
Approved by (+ signature) ........... :
Testing location/ address ...................... :
Testing procedure: SMT
Tested by (name + signature) ..... :
Approved by (+ signature) ............ :
Supervised by (+ signature) ........ :
Testing location/ address ................ :
Testing procedure: RMT
Tested by (name + signature) ..... :
Approved by (+ signature) ............ :
Supervised by (+ signature) ........ :
Testing location/ address ...................... :
Page 3 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Copy of marking plate / device under test
Module type: HZS310P-72
Marking plate
Front side view
Page 4 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Back side view
Serial number label
Page 5 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Detail view of cell Detail view of closed junction box
Detail view of open junction box Detail view of cable
Detail view of connectors Detail view of frame
Page 6 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Detail view of mounting hole Detail view of grounding hole
Page 7 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Module type: HZS260M-60
Marking plate
Front side view
Page 8 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Back side view
Serial number label
Detail view of cell Detail view of closed junction box
Page 9 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Detail view of open junction box Detail view of cable
Detail view of connectors Detail view of frame
Detail view of mounting hole Detail view of grounding hole
Page 10 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Summary of testing:
HZS310P-72 is selected as samples and tested according to full set of IEC 61730-2:2004 modified + IEC 61730-2 AMD 1-2011-11 / EN 61730-2:2007+A1:2012 tests. Retest guideline a) of DSH 770 is conducted on HZS260M-60 with mono-crystalline silicon modules.
All samples are found to comply with the above-mentioned standards’ requirements.
Considering the results of the performed test according to standard IEC 61730-2:2004 modified + IEC 61730-2 AMD 1-2011-11 / EN 61730-2:2007+A1:2012, the items under test are IN COMPLIANCE with the requested specifications specified in the standard. The results of testing according to standard IEC 61730-1:2004 modified + IEC 61730-1 AMD 1-2011-11 / EN 61730-1:2007+A1:2012+A2:2013+A11:2014 and IEC 61215:2005(ed.2) /EN 61215:2005 available in Report Reference No. SHES170400348202 and SHES170400348201.
Tests performed (name of test and test clause):
Full tests of IEC 61730-2:2004 modified + IEC 61730-2 AMD 1-2011-11 conducted on HZS310P-72
Retest guideline a) of DSH 770 conducted on HZS260M-60
Testing location:
Wuxi Institute of Supervision and Testing on Product Quality (National Center of Supervision and Inspection on Solar Photovoltaic Products Quality)
Suite A-10F, Innovation & Creation Science Park, No.5 Xinhua Road, WND, Wuxi, Jiangsu, China
Summary of compliance with National Differences: European Group Differences
Page 11 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Test item particulars:
Accessories and detachable parts included in the evaluation ...................................................................:
N/A
Mounting system used ................................................: According to installation manual
Other options included ................................................: N/A
Possible test case verdicts:
- Test case does not apply to the test object ................ : N/A
- Test object does meet the requirement ...................... : P (Pass)
- Test object does not meet the requirement ................ : F (Fail)
Abbreviations used in the report:
CTI – Comparative Tracking Index PD – Partial Discharge
FF – Fill factor RTI – Relative Thermal Index
Ipm – Maximum power current STC – Standard Test Conditions
Isc – Short circuit current TC –Thermal Cycling
MST – Module Safety Test Voc – Open circuit voltage
Pmax – Maximum power Vpm – Maximum power voltage
Testing:
Date of receipt of test item ............................................ : 06/08/2017
Date (s) of performance of tests ................................... : 06/08/2017 to 09/12/2017
General remarks:
The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report, a comma is used as the decimal separator.
List of test equipment must be kept on file and available for review.
The original test report form (Test Report Form No: IEC 61730_2A, Test Report Form Originator: TÜV Rheinland Product Safety GmbH) does not include the European group deviation, so the relevant part of EN 61730-2:2007 standard was additionally added as Annex 2.
This document is issued by the company under its General Conditions of Service accessible at http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is advised that information contained hereon reflects the Company’s findings at the time of its intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law.
Page 12 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Unless otherwise stated: (a) the results shown in this document refer only to the sample(s) tested and (b) such sample(s) are retained for 30 days. This document cannot be reproduced except in full, without prior approval of the company.
Contents:
1) The main report contains the assessments according to IEC 61730-2:2004 (ed.1).
2) Annex 1 contains the product description sheet (manufacturer and type references) (3 pages).
3) Annex 2 contains summary of compliance with IEC 61730-2 A1:2011 differences (3 pages).
4) Annex 3 contains summary of compliance with EN 61730-2:2007+A1:2012 Differences (3 pages).
5) Annex 4 contains partial discharge report from TÜV Rheinland (Report no. 15042547 012, 6 pages).
6) Annex 5 contains Constructional Data Form (CDF) for Photovoltaic (PV) Modules
(CDF no.: SHES1704003482.01, 13 pages).
Page 13 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
General product information:
Product Electrical Ratings: Refer to Annex 5
Module type — — — — —
Voc [V] — — — — —
Vmp [V] — — — — —
Imp [Adc] — — — — —
Isc [Adc] — — — — —
Pmp [W] — — — — —
Maximum system
voltage [V] — — — — —
Series Fuse
Rating [A] — — — — —
Page 14 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Product Safety Ratings
Maximum systems operating voltage ............................................ : DC1000V
Maximum over-current protection rating ....................................... : 20A
Safety application class ................................................................. : Class A
Safety class in accordance with IEC 61140 .................................. : Class II
Fire safety class ............................................................................ : Class C
Recommended maximum series/parallel module configurations . : Refer to user manual
Scope of Module Safety Qualification Testing
Initial Module Safety Qualification
Extension of Module Safety Qualification
Original Test Report Ref. No ........................ :
Model differences and modification:
Change in cell technology Modification to junction box/el. termination
Modification to encapsulation system Change in cell interconnect materials/ technique
Modification to superstrate Change in el. circuit of an identical package
Increase in module size Higher or lower output by 10%
Modification to backsheet/substrate Removal of frame
Modification to frame/mounting structure
Note (1) Use the “General product information” field to give any information on model differences within a product type family covered by the test report.
Note (2) Use the “General product information” field to describe the range of electrical and safety ratings, if the TRF covers a type family of modules.
Note (3) Use Annex 1 to list the used materials and components of the module (manufacturer/supplier and type reference)
Page 15 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
TEST SEQUENCES FOR MODULE SAFETY TESTING UNDER IEC 61730-2
Page 16 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
3 APPLICATION CLASSES
The module has been evaluated for the following Application Class (Class A, B, C) ............................. :
Class A P
REQUIRED TESTS DEPENDING ON THE APPLICATION CLASS
Application Class Module Safety Test
A B C
X
X
X
X
X
X
X
X
X
X
X
X
Preconditioning tests:
MST 51 Thermal cycling (TC50 or TC200)
MST 52 Humidity freeze
MST 53 Damp heat
MST 54 UV resistance
X
X
X
General inspection test:
MST 01 Visual Inspection
X
X
X
X
X
X
X
X
X
X*
X*
X
-
-
X
-
-
-
Electrical shock hazard tests:
MST 11 Accessibility test
MST 12 Cut Susceptibility test
MST 13 Ground Continuity test
MST 14 Impulse Voltage test
MST 16 Dielectric Withstand test
MST 17 Wet Leakage Current test
X X X MST 42 Robustness of terminations
X
X
X**
X
X
X
-
X
X
X
-
-
Fire Hazard tests:
MST 21 Temperature test
MST 22 Hot spot test
MST 23 Fire test
MST 26 Reverse current overload test
X
X
X
-
X
X
Mechanical stress tests:
MST 32 Module breakage test
MST 34 Mechanical load test
X
X
X
-
X
X
-
-
X
Component tests:
MST 15 Partial discharge test
MST 33 Conduit bending
MST 44 Terminal box knockout test
Legend:
X Test required
- Test not required
* Different test levels for Application class A and B
** Minimum Fire Resistance Class C is necessary for building roof-mounted modules.
Page 17 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
6 SAMPLING
The modules tested (modules and laminate) were taken at random from a production batch and subjected to manufacturer’s normal quality control and inspection for safety testing
N/A
The modules tested (modules and laminate) were prototypes of a new design and not taken from a production batch.
P
Preconditioning of test samples was performed within IEC 61215 or IEC 61646 performance testing
N/A
Preconditioning of test samples was performed separately from IEC 61215 or IEC 61646 performance testing
P
List of test samples
Sample No. Type/model Remark
P01
HZS310P-72
320170500195609920010
P02 320170500195609920012
P03 320170500195609920046
P05 320170500195609920043
P07 320170500195609920007
P09 320170500195609920008
P10 320170500195609920045
P11 320170500195609920049
P12 320170500195609920028
M01
HZS260M-60
26017031716409920173
M02 26017031716409920214
M03 26017031716409920181
M06 26017031716409920162
M07 26017031716409920144
Supplementary information: /
Page 18 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
9 PASS CRITERIA
The module under evaluation was judged to have passed all safety qualification test. The test samples met all of the criteria of each individual safety test.
See appended Tables P
Supplementary information: /
10 TEST PROCEDURES
Safety qualification testing included the following Module Safety Tests (MST) of IEC 61730-2:
10.1 MST 01 Visual inspection .................................. : See appended Table 10.1 P
10.2 MST 11 Accessibility test................................... : See appended Table 10.2 P
10.3 MST 12 Cut susceptibility test ........................... : See appended Table 10.3 P
10.4 MST 13 Ground continuity test .......................... : See appended Table 10.4 P
10.5 MST 14 Impulse voltage test See appended Table 10.5 P
10.6 MST 16 Dielectric withstand test ....................... : See appended Table 10.6 P
10.7 MST 21 Temperature test ................................. : See appended Table 10.7 P
10.8 MST 23 Fire test ................................................ : See appended Table 10.8 P
10.9 MST 26 Reverse current overload Test ............ : See appended Table 10.9 P
10.10 MST 32 Module breakage test .......................... : See appended Table 10.10 P
Component Tests
11.1 MST 15 Partial discharge test ........................... : See appended Table 11.1 P
11.2 MST 33 Conduit bending test ............................ : See appended Table 11.2 N/A
11.3 MST 44 Terminal box knockout test.................. : See appended Table 11.3 N/A
Supplementary information: /
Page 19 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
Overview of MST items for each test sample
MST item Sample No.
P01
P02
P03
P05
P06
P07
P09
P10
P11
P12
Control module X
MST 01 Visual inspection X X X X X X X X
MST 11 Accessibility test X X X
MST 12 Cut susceptibility test X X X
MST 13 Ground continuity test X X X
MST 14 Impulse voltage test X
MST 15 Partial discharge test
MST 16 Dielectric withstand test X X X
MST 17 Wet leakage current test X X X
MST 21 Temperature test X
MST 22 Hot-spot test X
MST 23 Fire test X X
MST 26 Reverse current overload test X
MST 32 Module breakage test X
MST 33 Conduit bending test
MST 34 Mechanical load test X
MST 44 Terminal box knock out test
MST 51a Thermal cycling test (TC200) X X
MST 51b Thermal cycling test (TC50) X
MST 52 Humidity freeze test X
MST 53 Damp heat test X
MST 54 UV preconditioning test X
Supplementary information: /
Page 20 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
Overview of MST items for each test sample
MST item Sample No.
M01
M02
M03
M06
M07
Control module X
MST 01 Visual inspection X X X X
MST 11 Accessibility test
MST 12 Cut susceptibility test
MST 13 Ground continuity test
MST 14 Impulse voltage test
MST 15 Partial discharge test
MST 16 Dielectric withstand test
MST 17 Wet leakage current test X X X X
MST 21 Temperature test X X
MST 22 Hot-spot test X
MST 23 Fire test
MST 26 Reverse current overload test X X
MST 32 Module breakage test
MST 33 Conduit bending test
MST 34 Mechanical load test X
MST 44 Terminal box knock out test
MST 51a Thermal cycling test (TC200) X
MST 51b Thermal cycling test (TC50)
MST 52 Humidity freeze test
MST 53 Damp heat test X
MST 54 UV preconditioning test
Supplementary information: /
Page 21 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
Table
10.1 MST 01 VISUAL INSPECTION P
Sample No. Position in test sequence:
P03 Initial examination No visual defects P
Preconditioning: MST 54, MST 51b, MST 52
MST 12, Cut susceptibility test No visual defects P
Final examination No visual defects P
P07 Initial examination No visual defects P
Preconditioning: MST 53, MST 34
MST 12, Cut susceptibility test No visual defects P
Final examination No visual defects P
P05 Initial examination No visual defects P
Preconditioning: MST 51a, MST14
MST 12, Cut susceptibility test
Final examination No visual defects P
P02, M02 Initial examination No visual defects P
MST22, Hot-spot test
MST 21, Temperature test
MST 26, Reverse current overload
Final examination No visual defects P
P09 Initial examination No visual defects P
Supplementary information: /
Page 22 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
Table
10.2 MST 11 ACCESSIBILITY TEST P
Sample No. Position in test sequence:
P03 Initial examination No access P
Preconditioning: MST 54, MST 51b, MST 52
MST 12, Cut susceptibility test
Final examination No access P
P07 Initial examination No access P
Preconditioning: MST 53, MST 34
MST 12, Cut susceptibility test
Final examination No access P
P05 Initial examination No access P
Preconditioning: MST 51a, MST14
MST 12, Cut susceptibility test
Final examination No access P
Supplementary information: /
Page 23 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
Table
10.3 MST 12 CUT SUSCEPTIBILITY TEST P
Applied force (N) .................................................. : 8.9
Sample No.
P03 No visual evidence that the superstrate or substrate have been cut
P
No exposure of active circuitry of the module
Requirement of MST 13, MST 16, MST 17 are met (see appended Tables 10.4, 10.6, MST17)
P05 No visual evidence that the superstrate or substrate have been cut
P
No exposure of active circuitry of the module
Requirement of MST 13, MST 16, MST 17 are met (see appended Tables 10.4, 10.6, MST17)
P07
No visual evidence that the superstrate or substrate have been cut No exposure of active circuitry of the module
P
Requirement of MST 13, MST 16, MST 17 are met (see appended Tables 10.4, 10.6, MST17)
Supplementary information: /
Table
10.4 MST 13 GROUND CONTINUITY TEST P
Maximum over-current protection rating (A) ......... : 20
Current applied (A) .............................................. : 50.0
Location of designated grounding point ............... : Grounding hole
Location of second contacting point ..................... : Farthest point on adjacent edge
Location of third contacting point .......................... : Middle point on the other long edge
Location of fourth contacting point ....................... : Middle point on the other short edge
Sample No. Position in test sequence: Resistance ()
P03 Initial examination 0.001 P
0.001 P
0.001 P
Preconditioning: MST 54, MST 51b, MST 52
MST 12, Cut susceptibility test 0.001 P
Page 24 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
Final examination 0.001 P
0.001 P
P07 Initial examination 0.001 P
0.001 P
0.001 P
Preconditioning: MST 53, MST 34
MST 12, Cut susceptibility test Final examination
0.001 P
0.001 P
0.001 P
P05 Initial examination 0.001 P
0.001 P
0.001 P
Preconditioning: MST 53, MST 34
MST 12, Cut susceptibility test Final examination
0.001 P
0.001 P
0.001 P
Supplementary information: /
Page 25 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
Table
10.5 MST 14 IMPULSE VOLTAGE TEST P
Maximum system voltage (V) ............................... : 1000
Impulse voltage (V) .............................................. : 8000
Thickness of conductive foil (mm) ....................... : 0.05
Sample No.
P06 No evidence of dielectric breakdown or surface tracking observed
P
No evidence of major visual defects (See appended table 10.1)
Supplementary information: /
TABLE
10.6 MST 16 DIELECTRIC WITHSTAND TEST P
Maximum system voltage (V d.c.) ....................... : 1000
Test voltage applied (V d.c.) ................................ : 3000
Minimum allowable insulation resistance (MΩ) ... : 20.7
Sample No. Position in test sequence: Dielectric breakdown
Insulation resistance
(MΩ)
P03 Initial test ......................................... : >1000 P
MST 54, MST 51b, MST 52 Preconditioning
Intermediate test ............................. : >1000 P
MST 12, Cut susceptibility test MST
Final test ......................................... : >1000 P
P07 Initial test >1000 P
MST 53, MST 34 Preconditioning
Intemediate test >1000 P
MST 12, Cut susceptibility test MST
Final test >1000 P
P05 Initial test >1000 P
MST 51a Preconditioning
Intemediate test >1000 P
MST 14, Impulse voltage test MST
Final test >1000 P
Supplementary information: Size of module (m²) 1.93
Page 26 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
TABLE
10.7 MST 21 TEMPERATURE TEST P
Sample No. .......................................................... : P09
Reference solar irradiance (W/m²) ...................... : 1000
Reference ambient temperature (°C) .................. : 40
Module open-circuited
Measuring location : Component temperature
TOBS (°C)
Normalised temperature
TCON (°C)
Component temperature
limit (°C)
Module superstrate above the centre cell 78.2 81.0 85 P
Module substrate below the centre cell 74.3 77.1 85 P
Terminal enclosure interior surface 66.8 69.6 90 P
Terminal enclosure interior air space 71.2 74 85 P
Field wiring terminals 68 70.8 220 P
Insulation of the field wiring leads 61.0 63.8 90 P
External connector bodies 54.9 57.7 85 P
Diode bodies 75.5 78.3 200 P
Ambient 37.2 40 20- 55 P
Module short-circuited
Measuring location : Component temperature
TOBS (°C)
Normalised temperature
TCON (°C)
Component temperature
limit (°C)
Module superstrate above the centre cell 80.0 83.8 85 P
Module substrate below the centre cell 72.8 76.6 85 P
Terminal enclosure interior surface 65.0 68.8 90 P
Terminal enclosure interior air space 69.3 73.1 85 P
Field wiring terminals 66.8 70.6 220 P
Insulation of the field wiring leads 59.4 63.2 90 P
External connector bodies 54.3 58.1 85 P
Diode bodies 73.2 77.0 200 P
Ambient 36.2 40.0 20- 55 P
Supplementary information: TCON = TOBS + (40°C – TAMB) Temperature limits are given in Table 9 of IEC 61730-2.
Page 27 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
TABLE
10.7 MST 21 TEMPERATURE TEST P
Sample No. .......................................................... : M07 P
Reference solar irradiance (W/m²) ...................... : 1000
Reference ambient temperature (°C) .................. : 40
Module open-circuited
Measuring location : Component temperature
TOBS (°C)
Normalised temperature
TCON (°C)
Component temperature
limit (°C)
Module superstrate above the centre cell 73.8 77.8 85 P
Module substrate below the centre cell 75.9 80.4 85 P
Terminal enclosure interior surface 66.3 70.8 90 P
Terminal enclosure interior air space 67.6 72.1 85 P
Field wiring terminals 62.4 66.9 220 P
Insulation of the field wiring leads 60.3 64.8 90 P
External connector bodies 53.4 57.9 85 P
Diode bodies 70.6 75.1 200 P
Ambient 35.5 40.0 20- 55 P
Module short-circuited
Measuring location : Component temperature
TOBS (°C)
Normalised temperature
TCON (°C)
Component temperature
limit (°C)
Module superstrate above the centre cell 69.8 74.3 85 P
Module substrate below the centre cell 72.3 76.8 85 P
Terminal enclosure interior surface 66.1 70.6 90 P
Terminal enclosure interior air space 67.9 72.4 85 P
Field wiring terminals 62.6 67.1 220 P
Insulation of the field wiring leads 60.8 65.3 90 P
External connector bodies 50.1 54.6 85 P
Diode bodies 70.4 74.9 200 P
Ambient 35.5 40.0 20- 55 P
Supplementary information: TCON = TOBS + (40°C – TAMB) Temperature limits are given in Table 9 of IEC 61730-2.
Page 28 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
TABLE
10.8 MST 23 FIRE TEST P
Module fire resistance class (A, B, C) .................. : Class C P
No. of modules provided to create the test assembly ................................................................. :
2
Sample No.
P11 The module complies with the requirements for the fire resistance class
P
P12 The module complies with the requirements for the fire resistance class
P
Supplementary information: /
TABLE
10.9 MST 26 REVERSE CURRENT OVERLOAD TEST P
Module over-current protection rating (A) ............. : 20
Test current (A) ....................................................... : 27
Test duration ........................................................ : 2 hours
Sample No.
P09, M07 No flaming of the module
P No flaming or charring of the cheesecloth
No flaming of the tissue paper
MST 17 requirements fulfilled (see appended Table MST17)
Supplementary information: /
TABLE
10.10 MST 32 MODULE BREAKAGE TEST P
Weight of impactor (kg) ........................................ : 45.5
Thickness of sample (mm) ................................... : 5 without frame
Mounting technique used ..................................... : According to the Installation Manual
Module breakage .................................................. :
No breakage
P Breakage at 300 mm
Breakage at 450 mm
Breakage at 1220 mm
Weight of particles in case of breakage (g) .......... :
Sample No.
P10 Breakage occurred, but no shear or opening large enough for P
Page 29 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
a 76-mm diameter sphere to pass freely has developed.
Disintegration occurred, but the ten largest crack-free particles selected 5 min subsequent to the test didn’t weigh more in grams than 16 times the thickness of the sample in millimetres.
Breakage occurred, but no particles larger than 6.5 cm² have been ejected from the sample.
Supplementary information: /
TABLE
MST 17 MST 17 WET LEAKAGE CURRENT TEST P
Maximum system voltage (V) ............................... : 1000
Test voltage applied VTEST (V d.c.) ....................... : 1000
Module area A (m²)................................................. : 1.93, 1.64
Resistivity of wetting agent (Ω·cm) ........................ : < 3500
Average wetting agent temperature (°C) .............. : 23.5
Sample No. Position in test sequence: Insulation resistance at VTEST (MΩ)
Insulation resistance x A
(Mm²)
P03 MST 54, UV Preconditioning MST 51b, Thermal Cycling (TC50) MST 52, Humidity Freeze MST 12, Cut Susceptibility
>1000 >1000 >1000 >1000
>1000 >1000 >1000 >1000
P
P07 MST 53, Damp Heat MST 34 Mechanical load test MST 12, Cut Susceptibility
>1000 >1000 >1000
>1000 >1000 >1000
P
P02, M02 P09, M07
MST 25, Bypass diode thermal test MST 22, Hot spot MST 26, Reverse Current Overload
>1000 >1000
>1000 >1000
P
Supplementary information: Size of module [m²]: Sample P02, P03, P07, P09:1.93; Sample M02, M07: 1.63
11 COMPONENT TESTS
11.1 MST 15 Partial discharge test ........................... : See appended Table 11.1 P
11.2 MST 33 Conduit bending test See appended Table 11.2 N/A
11.3 MST 44 Terminal box knockout tests See appended Table 11.3 N/A
Page 30 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
TABLE
11.1 MST 15 PARTIAL DISCHARGE TEST P
Manufacturer ........................................................ : Jolywood(suzhou) Sunwatt Co., Ltd.
Type reference ..................................................... : FFC-JW30
Materials and thicknesses .................................... : 0.3mm
Supplementary information: Test result refer to ANNEX 4
TABLE
11.2 MST 33 CONDUIT BENDING TEST N/A
Manufacturer and type reference of conduit......... : N/A
Trade size of conduit (mm) .................................. : N/A
Distance between the ends of the conduit in the box (mm) ........................................................ :
N/A
Distance between supports (mm) ........................ : N/A
Force load in accordance with Table 10 of IEC 61730-2 (N) ................................................... :
N/A
Sample No.
No rupture of the attachment walls of the junction box N/A
No separation of junction box from the conduit
Supplementary information: Distance between supports = 760 mm + Distance between the ends of the conduit in the box
TABLE
11.3 MST 44 TERMINAL BOX KNOCKOUT TEST N/A
Manufacturer of terminal box ............................... : N/A
Type reference ..................................................... : N/A
Number of knockouts in the junction box ............. : N/A
Force applied to knockout (N) .............................. : N/A
Knockout No.
The knockout remains in place N/A
The clearance between knockout and opening is < 0.75 mm
The knockout remains in place N/A
The clearance between knockout and opening is < 0.75 mm
Page 31 of 34 Report No. SHES170400348203
IEC 61730-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61730_2A
The knockout remains in place N/A
The clearance between knockout and opening is < 0.75 mm
The knockout remains in place N/A
The clearance between knockout and opening is < 0.75 mm
Supplementary information:
Page 32 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
List of measurement equipment
Description Identification # Application
Test finger ES21-39 MST11
Hybrid recorder TT21-03 MST21
TT21-04 MST26
Contact thermodetector TT20-12 MST16
Luminometer OI20-02 MST01, MST26
Withstanding voltage/Insulation resistance tester
EV20-40 MST16
Steady-state solar simulator ES21-24 MST21
Digital Multimeter EV20-19 MST13, MST11
DC power supply ES20-11 MST13, MST26
Pulse Voltage Generator ES21-126-01 MST14
Digital phosphor oscilloscopes ES21-126-02 MST14
Breakage tester ES20-45 MST32
Insulation resistance tester EV20-35 MST17
Conductive meter CC20-01 MST17
Cut Susceptibility Tester ES20-43 MST12
Page 33 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
ANNEX 1: PRODUCT DESCRIPTION SHEET (MANUFACTURERS AND TYPE REFERENCES)
REFER TO ANNEX 5
A1.1 MODULES TYPE/S
— —
A1.2 SOLAR CELL
Cell type reference ............................................... : —
Cell dimensions L x W (mm) ................................: —
Cell thickness (µm) ...............................................: —
Cell area (cm²)......................................................: —
A1.3 IDENTIFICATION OF MATERIALS
Front cover ........................................................... : —
Rear cover ............................................................ : —
Encapsulant .......................................................... : —
Frame ................................................................... : —
Adhesive for frame .............................................. : —
Adhesive for junction box .................................... : —
Potting material .................................................... : —
Internal wiring ....................................................... : —
Soldering material ................................................ : —
Other .................................................................... : —
A1.4 IDENTIFICATION OF COMPONENTS
Junction box ......................................................... : —
Cable .................................................................... : —
Connector ............................................................. : —
Bypass diode ........................................................ : —
A1.5 MODULE DESIGN –DIMENSIONS
Module dimensions L x W x H (mm)
—
A1.6 MODULE DESIGN - MINIMUM DISTANCES
Between cells —
Between cell and edge of laminate —
Between any current carrying part and edge of laminate
—
A1.7 MODULE DESIGN - ELECTRICAL CONFIGURATION
Page 34 of 34 Report No. SHES170400348203
TRF No. IEC61730_2A
Total number of cells —
Serial-parallel connection of cells
—
Cells per bypass diode —
No. of bypass diodes —
----------------- End of Test Report ------------------
Page 1 of 2 Report No. SHES170400348203
ANNEX 2: Summary of compliance with IEC 61730-2 A1:2012 Differences:
Differences according to ................ : EN 61730-2:2007+A1:2012
Clause Requirement + Test Result - Remark Verdict
4.5 FIRE HAZARD TESTS N/A
Table 4 Fire hazard tests
Add to: MST 25 test, under IEC 61646 column, 10.18
N/A
5 APPLICATION CLASSES AND THEIR NECESSARY TEST PROCEDURES N/A
Table 7 Required tests, depending on the application class
Replace: MST 54 UV resistance by MST 54 UV pre-conditioning
N/A
8 TESTING P
Figure 1 Test sequences
Replace: UV resistance test by UV pre-conditioning test.
Remove box: Hot-spot test.
Insert a new box: Hot-spot test into the test sequence, at right hand side after bypass diode thermal test.
Remove from box IEC 61215/IEC 61646: 10.2.
Remove 10.2 previous to MST 23 and MST 32.
Add a new box MST 13 “ground continuity test” between “Cut susceptibility test” and “” Accessibility test”, at the end of test sequence.
Change MST 34 and MST 25 boxes to blue colour.
P
10 TEST PROCEDURES N/A
10.3.1 Purpose
Delete: This test is derived from ANSI/UL 1703
N/A
10.3.4 Final measurements
Delete: MST 13
P
10.3.5 Pass criteria
Delete: MST 13
P
10.5.3 Procedures
Add to first paragraph: The impulse test shall be performed in accordance with IEC 60060-1.
c P
Page 2 of 2 Report No. SHES170400348203
10.5.3 b)
Replace: Conducting glue (conductivity < 1Ω,
measuring area 625 mm2).
By: Conducting glue (resistance < 1Ω, measuring area
625 mm2).
P
10.5.3 c)
Replace: The waveform of the pulse shall be observed by an oscilloscope and the rise time and the pulse duration shall be checked for each test. By:The waveform of the pulse shall be observed by an oscilloscope with the module connected and the rise time and the pulse duration shall be checked for each test.
10.8 Fire test MST 23 P
Replace throughout the subclause: Roof deck by sample(s).
P
10.9 Reverse current overload Test MST 26 P
10.9.2 Replace 9 mm by 19mm. P
11 COMPONENT TESTS
11.1 MST 15 Partial discharge test P
11.1.2 Replace:
It is advisable to perform the partial discharge-test before inserting the reverse side foil into the PV modules.
By:It is advisable to perform the partial discharge-test before using the polymeric material in the PV module construction.
P
11.1.4 Replace: The initial value of the test voltage is therefore 1.5 Uoc (system voltage given by the module manufacturer).
By : The initial value of the test voltage is therefore 1.5 Voc (system voltage given by the module manufacturer).
P
----------------- End of Annex 2 ------------------
Page 1 of 3 Report No. SHES170400348203
ANNEX 3: Summary of compliance with EN 61730-2:2007+A1:2012 Differences:
ATTACHMENT TO TEST REPORT IEC 61730-2
EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES
(Photovoltaic (PV) module safety qualification - Part 2: Requirements for testing)
Differences according to ................ : EN 61730-2:2007+A1:2012
Attachment Form No. ..................... : EU_GD_IEC61730-2A
Attachment Originator ................... : TÜV SÜD Product Service GmbH
Master Attachment ......................... : 2011-07
Copyright © 2008 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
Clause Requirement + Test Result - Remark Verdict
General Replace all references to “IEC 61730-1”, “IEC 61730-2” and “this part of IEC 61730”by “EN 61730-1”, “EN 61730-2” and “ this part of EN 61730”.
P
3.2 CLASS A: GENERAL ACCESS, HAZARDOUS VOLTAGE, HAZARDOUS
POWER APPLICATIONS
P
Replace the text by:
Modules rated for use in this application class may be used in systems operating at greater than
120 V DC. Modules qualified for safety through EN 61730-1 and this part of EN 61730 within this application class are considered to meet the requirements for safety class II.
P
Voltage (V)…………………………………………: 1000 P
3.4 CLASS C: LIMITED VOLTAGE N/A
Replace the text by:
Modules rated for use in this application class are restricted to systems operating at less than 120 V DC.
Modules qualified for safety through EN 61730-1 and this part of EN 61730 within this application class are considered to meet the requirements for safety class Ill.
N/A
Voltage (V)…………………………………………: N/A
Note: Safety class are defined within EN 61140
Page 2 of 3 Report No. SHES170400348203
5 APPLICATION CLASSES AND THEIR NECESSARY TEST PROCEDURES
Table 7 Delete “MST 23” from the row referring to “Fire test” and replace the content of footnote ** by:
** A European fire test is under consideration.
N/A
8 TESTING
Figure 1 Delete “MST 23” from the box referring to “Fire test” and add “*” referring to a footnote reading:
* A European fire test is under consideration.
N/A
10 TEST PROCEDURES
10.4 Ground continuity test MST 13 P
10.4.2 Renumber the note into NOTE 1. P
Add the following notes:
NOTE 2: The maximum over-current protection rating of a module can be interpreted as the module series fuse rating. A series fuse may be required in the installation of PV arrays. According to subclause 12.2 of EN 61730-1 the maximum over-current protection rating has to be provided by the manufacturer.
P
NOTE 3: A procedure for determination of maximum reverse current is described in EN 50380.
P
10.8 Fire test MST 23 P
Replace entire subclause by:
10.8 Fire test
Under consideration.
P
10.9 Reverse current overload Test MST 26 P
10.9.2 Renumber the note into NOTE 1. P
Add the following notes:
NOTE 2: The maximum over-current protection rating of a module can be interpreted as the module series fuse rating. A series fuse may be required in the installation of PV arrays. According to subclause 12.2 of EN 61730-1 the maximum over-current protection rating has to be provided by the manufacturer.
P
10.10 Module breakage test MST 32 P
Page 3 of 3 Report No. SHES170400348203
Add the following notes:
NOTE: If the glass is qualified in accordance with EN 12150-1 this test can be omitted.
P
11 COMPONENT TESTS
11.1 MST 15 Partial discharge test P
11.1.2 Replace the text by:
It is advisable to perform the partial discharge-test before using the back sheet foil in the PV module construction.
P
NOTE: In order to achieve a certain statistical relevance 10 pieces should undergo the test. The size of the specimen depends on requirement originating from the test apparatus.
P
11.1.3 Add the following sentence:
The geometry of the electrodes shall be in conformance with EN 60243-1.
P
11.1.4 In item a) add the following notes:
NOTE 1: Any voltage below maximum systems voltage can be used but the test should start at zero voltage because it may happen that maximum systems voltage is not stated or unknown.
NOTE 2: When increasing the test voltage partial discharges may appear periodically. In that case, the inception voltage is the test voltage at which permanent discharges occur for a duration of at least 60 s.
P
In item b) add the following notes:
NOTE 3: Because partial discharges can disappear periodically, partial discharges at extinction voltage should stay below 1 pC for minimum of 60 s
P
In item e) replace “Uoc” by “Voc” P
----------------- End of Annex 3 ------------------
Page 1 of 6 Report No. SHES170400348203
ANNEX 4: Partial Discharge Report from TÜV Rheinland
Page 2 of 6 Report No. SHES170400348203
Page 3 of 6 Report No. SHES170400348203
Page 4 of 6 Report No. SHES170400348203
Page 5 of 6 Report No. SHES170400348203
Page 6 of 6 Report No. SHES170400348203
----------------- End of Annex 4 ------------------
Page 1 of 13 Ref. No. SHES170400348203
Annex 5: Constructional Data Form (CDF) for Photovoltaic (PV) Modules
Page 2 of 13 Ref. No. SHES170400348203
Page 3 of 13 Ref. No. SHES170400348203
Page 4 of 13 Ref. No. SHES170400348203
Page 5 of 13 Ref. No. SHES170400348203
Page 6 of 13 Ref. No. SHES170400348203
Page 7 of 13 Ref. No. SHES170400348203
Page 8 of 13 Ref. No. SHES170400348203
Page 9 of 13 Ref. No. SHES170400348203
Page 10 of 13 Ref. No. SHES170400348203
Page 11 of 13 Ref. No. SHES170400348203
Page 12 of 13 Ref. No. SHES170400348203
Page 13 of 13 Ref. No. SHES170400348203
---------------- End of Annex 5 ------------------