Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

Embed Size (px)

Citation preview

Page 1: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

© Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice. 1S

DC

200

06

7B0

201

- 2

0.9

.20

17

—ABB SACEA division of ABB S.p.A.L.V. BreakersVia Pescaria 5,24123 Bergamo - ItalyPhone: +39 035 395.111Fax: +39 035 395.306-433

abb.com/lowvoltage

Page 2: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

— LOW VOLTAGE

Tender Specification for electrical cloud computing system

Page 3: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

2 TE N D E R S PECI F I C ATI O N FO R EL EC TR I C A L CLO U D CO M P U TI N G S Y S TEM

— The aim of this document is to provide outline specification of a cloud computing platform architecture able to satisfy supervision of electrical system and performance, analysis of relevant data and optimization of installation, control and implementation of energy management strategy.

The system must be scalable, shall be able to collect data from main electrical LV components installed in main and sub-distribution switchboards, and shall establish cloud connection.

Web clients can access to dashboard and data on web, where is possible to configure the system and customize reports and alarms.

Page 4: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

3EL EC TR I C A L S TA N DA R DS

—Electrical Standards

Components shall be compliant to latest versions of following standards and regulations:• IEC 60947-1 “Low-voltage switchgear and controlgear – Part 1: General rules”• IEC 60947-2 “Low-voltage switchgear and controlgear – Part 2: Circuit-breakers”• IEC61131-3 “Programmable controllers – Part 3: Programming languages”• IEC 60870-5-104 “Telecontrol equipment and systems – Part 5-104: Transmission

protocols – Network access for IEC 60870-5-101using standard transport profiles”

EC directives: • “Low voltage Equipment” No. 2006/95/EC • “Electromagnetic compatibility Directive” (EMC) No.2004/108/EC

Page 5: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

4 TE N D E R S PECI F I C ATI O N FO R EL EC TR I C A L CLO U D CO M P U TI N G S Y S TEM

—Environmental characteristics

Temperature: • Operating temperature: -25 °C ...+70 °C • Storage temperature: -40 °C...+70 °C

Environmental parameters: device shall comply with IEC60721-3-6 (class 6C3) and IEC60721-3-2 (class 3C2)

Pollution degree: device shall be used in environments type PD3

Vibrations: device shall comply with IEC60068-2-6 (1 mm displacement 1-13Hz, 13-100 Hz with acceleration = 0.7 g).

Page 6: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

5FU N C TI O N A L CH A R AC TER IS TI C S

—Functional characteristics

Supervision system shall be able to collect data from the field and, though Ethernet bus, store information in one system, accessible via Cloud. Data and parameters measured depend on electrical devices connected, in addition to monitoring of electrical magnitudes; system shall provide status and maintenance indicators, alarms and alerts.

Main device of supervision system architecture is a communication module with an integrated software that behave as concentrator and gateway, allowing management of parts of electrical system located in different areas directly from web application.

ScalabilityIt shall be possible to design different architec-ture sizes, with adoption of one single communi-cation module or it shall be possible to integrate more communication modules to supervise one electrical installation, according to number of de-vices interconnected and functionalities required.

System shall have high degree of flexibility en-abling the integration on electrical systems al-ready installed with limited impact on existing ar-chitecture.

System scalability shall ensure integration of new devices without requiring re-programming or re-configuration of the connected system.

Electrical DevicesIt shall be possible to connect supervision system to electrical devices provided with communica-tion protocols supported. It shall be possible to interconnect to cloud supervision system devices of type specified below:

• Air circuit breakers • Moulded Case circuit breaker • Metering devices• Metering and monitoring device system for

miniature circuit breaker• Fusegear • Digital Meters / sensors• Analog Meters / sensors• Arc flash protection system

CommunicationProtection and metering devices shall be pro-vided with standard communication protocols Modbus RS-485 or Modbus TCP/IP.

Main communication module shall works as inter-face between electrical devices and cloud and shall be provided with Ethernet gate. System shall provide automatic monitoring of communication, and alerts shall be notified in case of communica-tion problems.

Data storage and notificationsSupervision system shall have a data logging in-terval of 30 seconds to ensure a fast reaction in case of warning or alerts and a continuous mea-sures for reliable efficiency analysis.

Supervision system shall be designed to moni-tor following data, without storage limitation capability

Consumption measures:• Real time phase currents• Voltages• Active Power • Reactive Power• Apparent Power• Active Energy• Reactive Energy• Apparent Energy• Power Factor• Peak active Power

Page 7: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

6 TE N D E R S PECI F I C ATI O N FO R EL EC TR I C A L CLO U D CO M P U TI N G S Y S TEM

Quality data• THD• Total reactive Power• Voltage Unbalance• Voltage Spike• Voltage micro-interruption• Voltage short Sage• Voltage middle Sag• Voltage long Sag• Voltage short Swell• Voltage Long Swell

Maintenance data• Contact wear• Number of trips• Total operations• Manual operations

It shall be possible to monitor status of devices and alarms. It shall be possible for web user to set up to 23 different alerts, identifying alerts for specific devices or on all devices, in order to schedule maintenance and to check health of in-stallation.

Alerts shall include:• Phase and neutral currents• Phase to phase and phase to neutral voltages• Total active power• Total reactive power• Total apparent power• Power factor• Number of operations• Contacts wear• Trip coil disconnected• Overtemperature• Motor operator overtemperature• Circuit breakers trip• Any trip• Status Open/ close

It shall be possible to set alarms and define type of notification through SMS or e-mail for each user.

Analytics and reportsSupervision system shall be provided with web app with preconfigured widget to allow immedi-ate overlook of plant consumption and analytics

based on collection of data on selectable period of one day, one week, one month, one semester, one year or on custom period.

Widget should be designed to display single or multi-site information and shall include both power utility consumption and power generated on site.

Web app shall allow the creation and customiza-tion of “digital” representation of asset, allowing creation of synoptic representation of switch-board, importation of single line diagram or switchboards’ front view. It shall be possible to activate the graphics by connection with markers or tags, to easily access to device data.

Export of data and trends in excel shall be possi-ble both on-demand and via automatic report scheduling function. It shall be possible to gener-ate reports for all information managed or gener-ate customize reports selecting specific mea-sures and devices. Benchmark on multi-site level shall also be possible in order to compare plants and systems and identify best practices.

Commissioning and maintenanceSystem shall allow final user or panel builder to execute the commissioning with the simple use of free software provided by manufacturer. Auto-matic recognition of devices shall be ensured so that there is no needs of programming and free software shall include wizard for commissioning directly from web.Free software provided by manufacturer shall al-low execution of system implementation without requiring system integrator.

InterfaceSystem shall be supplied with pre-set graphic pages with dashboard for immediate evaluation and management of power consumption. It shall be possible to display dashboard on tablet or smartphone.

SecurityAuthentication system shall be provided to ac-cess to data. Encrypted communication channel and certification for communication to cloud and

Page 8: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

7FU N C TI O N A L CH A R AC TER IS TI C S

from cloud to web app shall be guaranteed.Encrypted communication channel and certifica-tion shall follow TSL protocol to ensure maximum safety level available. TSL protocol shall be pro-vided embedded in the module for supervision and cloud connection.

Level of usersIt shall be possible to define at least 4 different profiles for users. Only one of the users can be identified as owner. The owner shall sign up the EULA to start the data transmission and has the rights to renew licence of use. Only owner and ad-ministrator can send invitation to other users and have rights to change roles.It shall be possible to define staff profile with the rights to access to asset and device view, alerts view, analytics view and control view. It shall be possible to assign visitor profile for enabling us-ers to access only to alerts view.

Load ManagementPower ControlBreaker shall allow management of active/pas-sive loads by trip unit embedded software. Function shall be based on algorithm that al-lows a load list to be controlled.

Control shall be possible through the remote command from the air circuit breaker to rele-vant switching devices according to a user de-fault priority.

Algorithm shall be based on a foreseen average power absorption calculation which can be set over a determined time interval; whenever this forecasted value is over/below the contractual power, the function intervenes to bring it back to the limits turning off/or the devices under control.

Control system can be realized with:• air circuit breaker with advanced protection trip

unit operating as power controller and meter. Such a circuit breaker, installed as main LV breaker, implements the power control algo-rithm which manages the load connection and disconnection, equipped with auxiliary supply and electrical contacts, whose number depends on how many loads are managed;

• a variable number (from 1 to 15) of controlled LV apparatuses (air circuit breaker, molded case circuit breakers, miniature circuit break-ers, switch-disconnectors or contactors, drives), each of them installed on the supply circuit of one of the loads subject to control.

Each passive load or active generator/storage can be wired controlled in one of the following ways:• for every air circuit breaker, shunt opening/

closing releases (YO / YC), automatic charging motor operator, a contact for electrical re-lease tripped signalling and a contact for elec-trical open/closed circuit breaker signalling;

• for every molded case circuit breaker, shunt opening/closing releases (YO / YC) or motor operator, a contact for electrical release tripped signalling and a contact for electrical open/closed circuit breaker signalling;

• for every miniature breaker, motor operator;• for every switches, shunt opening/closing re-

leases (YO / YC) with automatic charging mo-tor or motor operator and a contact for elec-trical open/closed manual switching signalling;

• every contactor with an auxiliary contact;• every control/start circuit, own control inter-

face.

The main air circuit breaker uses the following input/output digital signals for every wired-controlled load:• 1 digital input (mandatory) to get information

about the open/closed state of the down-stream device;

• 1 digital input (optional) to get information about the enabled/disabled state of the downstream device (or tripped state or redun-dant contact of state);

• 1 digital output to give the opening/closing command to the downstream device when it is a contactor or a control circuit;

• 2 digital outputs to give the opening/closing command to the downstream device when it is a circuit breaker or a switch-disconnector;

• 1 digital input can be optionally used for time synchronization with the smart meter of the Distribution System Operator.

Page 9: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

8 TE N D E R S PECI F I C ATI O N FO R EL EC TR I C A L CLO U D CO M P U TI N G S Y S TEM

In addition, the new family of air circuit- breaker or switch disconnector can be controlled via ABB property protocol (Ethernet Cable). By a dedicated software for PC, tablet, smart-phone, the User must set a list of parameters:

- enable/disable, enabling or disabling power controller function;

- power limits, showing which is the average power (Pm) absorption not to be exceeded; setting this value is mandatory, whereas the others are optional and are needed to differ-entiate the power consumed in the various daily tariff bands;

- week scheduling, indicating the four tariff bands in which week days (Monday to Friday) are divided;

- saturday scheduling, indicating the four tar-iff bands in which Saturday is divided;

- sunday scheduling, indicating the four tariff bands in which Sunday is divided;

- synch configuration, indicating the presence and the reception channel for the synchroni-zation signal of the smart meter;

- start-up behaviour, indicating which loads must be inserted in the list of the loads that can be managed at start-up;

- connection type, selecting the number of in-put for each load;

- - open/closed input, indicating to which kind of contacts the inputs for the open/closed state of the switching device are connected;

- optional input, indicating to which contacts the auxiliary input is connected;

- enable/disable, allowing load control to be disabled;

- shed priority, defining the priority with which the related load must be managed; it is repre-sented by a number from 1 to 15 with de-creasing priority of disconnection. There may also be more loads with the same priority: in that event, the algorithm proceeds to discon-nect them alternately;

- ton_min, minimum time during which the load/generator must remain connected in or-der to protect it against too frequent start/stop operations; it is possible to set a null time or a time in the range from 1 to 360 min-utes with 1-minute step;

- toff_min, minimum time during which the load/generator must remain disconnected in order to protect it against too frequent start/stop operations; it is possible to set a null time or a time in the range from 1 to 360 minutes with 1-minute step;

- toff_max , maximum time during which the load can remain disconnected in order to pro-tect the process managed against the dam-ages caused by a prolonged lack of supply; it is possible to set a null time or a time in the range from 1 to 360 minutes with 1-minute step

- time window, time window in the space of the day during which the load cannot be dis-connected; it is possible to set a time interval from 1 to 24 hours with 1-hour step;

- user type, type of user (load/generator); - nickname, a string of 8 digits identifying the user.

Page 10: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

9M ECH A N I C A L CH A R AC TER IS TI C S

This part of outline specification describes the requirements for hardware to build up and perform functionalities in previous paragraph.

To satisfy all installation conditions, it shall be possible to achieve monitoring and controlling functions by using a module embedded in air circuit breaker or by adoption of external module.

—Mechanical characteristics

Solution embedded in Air Circuit BreakerModule for supervision and cloud connection shall be provided as cartridge-type module to be mounted in terminal box of air circuit breaker, without requiring additional space in electrical switchboard.The module shall be connected to Ethernet switch via Ethernet cable.

Solution with external moduleModule for supervision and cloud connection shall be provided as external module for DIN rail mounting.

The module shall be connected to Ethernet switch via Ethernet cable.

License and firmware updateTransmission and access to data and analytics is set per license. License shall include automatic firmware upgrade and maintenance.

Connection It shall be possible to connect to one embedded cloud module up to 50 devices through Modbus TCP communication protocol, 32 devices through Modbus RTU and 8 digital inputs. It shall be possi-ble to connect to one external cloud module up to 100 devices through Modbus TCP communication protocol, 32 devices through Modbus RTU, 8 digi-tal inputs and 8 analog input. System shall allow multi hub architecture to enable no limitation to number of devices monitored.

Page 11: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

10 TE N D E R S PECI F I C ATI O N FO R EL EC TR I C A L CLO U D CO M P U TI N G S Y S TEM

Additional informationWe reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatso-ever for potential errors or possible lack of information in this document.

We reserve all rights in this document and in the subject matter and illustra-tions contained therein. Any reproduc-tion, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG.

Page 12: Tender Specification for electrical cloud computing system · PDF file6 TENDER SPECIFICATION FOR ELECTRICAL CLOUD COMPUTING SYSTEM Quality data • THD • Total reactive Power •

11