Upload
bcram-chandran
View
220
Download
2
Embed Size (px)
Citation preview
Temperature Measurement INDUSTRIAL INSTRUMENTATION
1 | P a g e BCRAM
RESISTANCE THERMOMETER
(Change in electrical property)
Variation of Resistance in metallic conductors with change in
temperature – principle of Resistance Temperature Detector
(RTD)
The relation between electrical resistance of a metal and the
corresponding temperature T is generally given as
Resistance at Temperature T = 0˚C
Resistance at Temperature ‘T’
Constants
Although this is a nonlinear relationship, it can be seen from
figure that the curve is nearly linear for copper and platinum
over a fairly long range. However, copper being easily
susceptible to chemical reactions such as oxidation, sulphate
formation, etc., platinum is chosen for RTDs. The Platinum
Resistance Thermometers are also referred to as PRTs.
Temperature Measurement INDUSTRIAL INSTRUMENTATION
2 | P a g e BCRAM
PLATINUM RESISTANCE THERMOMETER
The ends of this wire are joined to terminals A and B on the top
of the instrument. Another exactly similar lead, with its lower
end shorted to B is connected to terminal C to compensate for
the resistance of the leads.
The Pt-100 RTD has a sensitivity of 0.385 /˚C.
Range: -40˚C to 1200˚C.
Accuracy: 0.2% to 1.2% at different ranges.
Errors:
Self-Heating: E.g. 1 ma current through 100Ω RTD
generates 100µW power. Error will be 1˚C/mW in free air.
It can be reduced to 0.1˚C/mW in air flowing at 1m/s.
Reduction of this effect:
1) Pulses can be given instead of continuous supply.
2) Circuit is designed such that very current flows in it.
Lead Wire Resistance: E.g. 1Ω connected to 100Ω PRT
causes 1% measurement error
MEASUREMENT WITH RTDs
Two Wire Connection:
Temperature Measurement INDUSTRIAL INSTRUMENTATION
3 | P a g e BCRAM
The simplest resistance measurement configuration uses two
wires to connect the thermometer to a Wheatstone bridge.
In this configuration, the resistance of the connecting wires is
always included with that of the sensor leading to errors in the
signal. So, it is mainly used when high accuracy is not required.
Using this configuration, about 10 m of cable can be used.
Three Wire Connection:
In order to minimize the effects of lead resistances, a three wire
configuration can be used.
Here, the two leads to the sensor are on the adjoining arms.
There is a lead resistance in each arm of the bridge
Temperature Measurement INDUSTRIAL INSTRUMENTATION
4 | P a g e BCRAM
They cancel out as can be seen from the following analysis:
High quality connection cables should be used for this type of
configuration because we have assumed that the two lead
resistances are equal.
This configuration allows for up to 600m of cable.
Four Wire Compensation:
See note for diagram and analysis
The four-wire resistance thermometer configuration even further
increases the accuracy and reliability of the measurement of
resistance.
It provides full cancellation of spurious effects and cable
resistance of up to 15Ω can be handled, though in principle, the
resistance error due to lead wire resistance is zero in four-wire
measurements.
Temperature Measurement INDUSTRIAL INSTRUMENTATION
5 | P a g e BCRAM
TEMPERATURE COMPUTATION:
From Callendar-Van Deuson Relation:
With the advent of computers, the temperature corresponding to
a measured resistance can be found by the method of iteration
from the Callendar-Van Deuson Relations.
From Callendar and Griffiths’ method:
Callander and Griffiths’ observed that the following simple
relation gives true readings up to 630˚C:
where, c is the mean temperature coefficient of Resistance
between 0˚C and 100˚C, and is given by,
The difference between the true temperature and that obtained
from the above equation is given by
where, is a constant for a particular specimen of wire and its
value varies between 1.488 and 1.498. So, the procedure is
given as follows:
Temperature Measurement INDUSTRIAL INSTRUMENTATION
6 | P a g e BCRAM
Step 1: Find Platinum temperature from Equation (1), by
measuring . The last two quantities are to be
determined only once and for all.
Step 2: Substitute this value for on the left and for T on the
right-hand side of equation (3) to obtain a revised value of T.
Step 3: Substitute the value of T obtained from Step 2 in the
right hand side of Equation (3) to obtain a more accurate value
of T
Step 4: Repeat Step 3 until the value of T converges. This
iterative procedure is also called the successive approximation
method.