Temperature Controller TX3 Series - Altechaltech-equipment.com/upload/file/tx3_general... · TX3 Temperature Controller TX3 Cooler Heater TX3 series are controllers to control temperature

  • Upload
    others

  • View
    25

  • Download
    0

Embed Size (px)

Citation preview

  • 34.5mm

    43mm

    Temperature ControllerTX3

    ON

    S2

    S1

    70mm

    120m

    m

    Demensions and Wiring diagram (Heating)

    Temperature Controller Installation

    How to control

    1. Connect sensors and wires at the back of temperature controller. (A sensor can be connected to whichever connection part of sensor when using 1 sensor.)3. Put the controller into the bracket. (It is removable.)

    2. Screw a bracket to the wall. (Please see the picture.)4. Screw the bottom of the controller.

    AC90-250V ~50/60Hz

    HeaterCooler

    Secondary Sensor

    RS485Commu-nication PrimarySensor

    6 5 4 3 2 1

    4 3 2 1

    The Back1

    2

    Temperature ControllerTX3

    ON

    S2

    S1

    ① ② ③ ④

    - Sensor Control Mode

    30℃

    29℃

    28℃

    ex) Heater is ON at 28.0℃ and OFF at 30.0℃ when desired temperature is 30 ℃ and

    control deviation is 2.0.

    Time

    ON

    TX3 controls heater/cooler by comparing current temperature with desired temperature.

    OFF OFF

    ● 2 Sensors : Current Temperature is detected by ratio of main sensor(70%) and

    secondary sensor(30%).

    ● 1 Sensor : Current Temperature is detected by sensor connected.

    Current Temperature

    -5℃

    -6℃

    -7℃

    ex) Cooler is ON at -5℃ and OFF at -7℃ when desired temperature is -7℃ and control deviation is 2.0.

    Time

    ONOFF OFF

    Current Temperature

    - Timer Mode

    HeaterCooler ON

    HeaterCooler OFF

    ON ON

    10 min.

    6 min.

    Heater/Cooler is ON for 6 min. and OFF for 4 min. when period is 10 min. and level is 6.

    OFF OFF

    Temperature is controlled by ON/OFF time control of Heater/Cooler after setting period and level.

    - Nature Defrost

    Control output is OFF every defrost period during defrost time if setting and using

    nature defrost function.

    ※ Switching to timer mode is enable when all sensors are removed or sensor disconnection happens.

    ● Timer Mode Operation Time : ON time : Period (1~60 min.)*(level(0~9) * 6sec.)

    OFF time : Period (1~60 min.) - ON time

    Power AC90 - 250V ~50/60Hz

    Heater

    ELCB (Earth LeakageCircuit Breaker)

    Temperature sensor

    Cooler

    Connection Heater or Cooler

    Temperature ControllerTX3

    ON

    S2

    S1

    ex) Desired temp.(ST I ) : 5.0℃ Control deviation(D I F) : 2.0℃ Defrost period(DFP) : 240min. Defrost Time(DFT) : 15min.

    8.0

    Temperature

    time

    7.06.05.0

    Defrost

    240min. 15min. 240min. 15min.

    OFFOUT1 OUT1

    Defrost

    OFF

    Heating Mode (TYP : H)

    Cooling Mode (TYP : C)

    Temperature Controller

    TX3 Series

    Some contents could be changed without prenotification / Edition 2010-06

    DOTECH,INC. http://www.dotech21.com [email protected]

    6F, JOONGANG-ILBO, 778 Wonsi-Dong, Danwon-Gu, Ansan-Si,

    Gyeonggi-Do, Korea TEL : +82-31-495-3767 / FAX : +82-31-495-3917

  • General Temperature Controller

    TX3 series Temperature ControllerTX3 Series

    TX3-00

    Application Fields

    • Heating/Cooling, Heating cable, Heating film

    • Hot water heating, Electrical panel, Snow heating

    • House, Building lobby, Tunnel entrance, Pedestrian overpass,

    Road inclined, Aquarium

    Features and Function of Product Models

    AC90-250V ~50/60Hz

    HeaterCooler

    6 5 4 3 2 1

    4 3 2 1L1L2

    NTCNTC

    NTC NTCCOMCOM

    AC90-250V ~50/60Hz

    6 5 4 3 2 1

    4 3 2 1L1L2

    NTCNTC

    NTC NTCCOMCOMTRX+ TRX-

    RS485CONVERTER

    + -

    AC90-250V ~50/60Hz

    6 5 4 3 2 1

    4 3 2 1L1L2

    NTCNTC

    NTC NTCCOMCOMSSR+ SSR-

    SSRINPUT + -

    LOAD

    Feature

    Model

    Function

    Wiring Diagram

    TX3-R4 TX3-S11 temperature sensor included

    Communication Model (communication function MODBUS RTU MODE)

    SSR Outside Connection Model (Mass, Noiseless control)

    Power Supply

    Rated Consumption Current

    Output

    Input5kΩ at 25℃, Range of measurement : -40~120℃, Margin of error : ±0.3℃ at 25℃

    Connection Terminal

    Operating Condition

    Storage Condition

    AC90 - 250V ~ , 50/60Hz

    MAX 4VA

    Relay output 1-point (277Vac / 20A)

    Temperature sensor input 2-point (Dotech standard NTC sensor DPR-TH5-T1)

    Screw bolt terminal

    Temperature -10~50℃, Humidity below 90%RH

    Temperature -20~60℃, Humidity below 90%RH

    SSR operation output : 12VDC ±3V 20mA below (TX3-S1 model)

    ▲Floor heating ▲Heating film ▲Heating cable ▲Aquarium ▲Snow heating

    HeaterCooler

    Temperature ControllerTX3

    Temperature ControllerTX3

    Cooler Heater

    TX3 series are controllers to control temperature at construction site, factory and office etc.

    It is very economical because of reduction of power consumption. You can control easily because

    they are digital type. TX3 series offer High Quality/High Service at a reasonable price.

    !

    easycontrol

    ±0.3

    Easy Operation

    Simple and convenient menu composition makes it easy that users setup the device.

    Malfunction of the device can be prevented by setting LOCK and access level.

    ±0.3℃ Precise Temperature Control

    NTC temperature sensor,dotech's standard sensor, can mesure temperature range of

    -40℃ ~ 120℃ with margin of error of ±0.3℃.

    RS485 Communication

    Centralized monitoring solution to manage upto 128 devices at PC and RCU128 by adopting

    RS485 communication based on Modbus RTU/ASCII protocol.

    Integrated Control System Software for free

    Integrated control software is offered for monitoring 1~128 devices at main controller.

    Supporting Various Sensors

    Many kinds of temperature sensors can be adopted according to system construction.

    First CE certification in relevant industry field in South Korea

    TX3 series have first CE certification in floor heating temperature controller industry field

    in South Korea. TX series offer high reliability and safety.

    Display Error Messages and Alarms

    Users and engineers can easily grasp and manage condition of the device because error

    messages about problems such as disorders or malfunctions of the device are displayed.

    The Best Quality, Reasonable Price

    TX3 Series have the best quality within the same field and Its price is very reasonable.

    Nature Defrost

    User can use nature defrost function by turning off control output during defrosting every

    defrosting period time when cooling or heating system works.

    Cooling/Heating can be selected

    Optimum temperature control by selecting between cooling and heating according

    to environment.

    Easy Operation

    Simple and convenient menu composition makes it easy that users setup the device.

    Malfunction of the device can be prevented by setting LOCK and access level.

    ±0.3℃ Precise Temperature Control

    NTC temperature sensor,dotech's standard sensor, can mesure temperature range of

    -40℃ ~ 120℃ with margin of error of ±0.3℃.

    RS485 Communication

    Centralized monitoring solution to manage upto 128 devices at PC and RCU128 by adopting

    RS485 communication based on Modbus RTU/ASCII protocol.

    Integrated Control System Software for free

    Integrated control software is offered for monitoring 1~128 devices at main controller.

    Supporting Various Sensors

    Many kinds of temperature sensors can be adopted according to system construction.

    First CE certification in relevant industry field in South Korea

    TX3 series have first CE certification in floor heating temperature controller industry field

    in South Korea. TX series offer high reliability and safety.

    Display Error Messages and Alarms

    Users and engineers can easily grasp and manage condition of the device because error

    messages about problems such as disorders or malfunctions of the device are displayed.

    The Best Quality, Reasonable Price

    TX3 Series have the best quality within the same field and It's price is very reasonable.

    Nature Defrost

    User can use nature defrost function by turning off control output during defrosting every

    defrosting period time when cooling or heating system works.

    Cooling/Heating can be selected

    Optimum temperature control by selecting between cooling and heating according

    to environment.

    heating/cooling output, precise

    temperature control, sensor compensa-

    tion, sensor error detection function,

    easy-to-use, min. off maintaining time

    setup, nature defrost, switch to alarm and

    timer modewhen sensor error occurs,

    display to first decimal place

    communication function, heating/cooling

    output,precise temperature control, sensor

    compensation,sensor error detection

    function, min. off maintaining time setup,

    easy-to-use, free software for controlling at

    RCU128/PC, switch to alarm and timer mode

    when sensor error occurs

    SSR outside connection control, heating/cooling output, precise temperature control, sensor compensation, sensor error detection function, min. off maintaining time setup, high load switchgear by small signal, switch to alarm and timer mode when sensor error occurs, nature defrost, display to first decimal place

  • General Temperature Controller

    TX3 series Temperature ControllerTX3 Series

    TX3-00

    Application Fields

    • Heating/Cooling, Heating cable, Heating film

    • Hot water heating, Electrical panel, Snow heating

    • House, Building lobby, Tunnel entrance, Pedestrian overpass,

    Road inclined, Aquarium

    Features and Function of Product Models

    AC90-250V ~50/60Hz

    HeaterCooler

    6 5 4 3 2 1

    4 3 2 1L1L2

    NTCNTC

    NTC NTCCOMCOM

    AC90-250V ~50/60Hz

    6 5 4 3 2 1

    4 3 2 1L1L2

    NTCNTC

    NTC NTCCOMCOMTRX+ TRX-

    RS485CONVERTER

    + -

    AC90-250V ~50/60Hz

    6 5 4 3 2 1

    4 3 2 1L1L2

    NTCNTC

    NTC NTCCOMCOMSSR+ SSR-

    SSRINPUT + -

    LOAD

    Feature

    Model

    Function

    Wiring Diagram

    TX3-R4 TX3-S11 temperature sensor included

    Communication Model (communication function MODBUS RTU MODE)

    SSR Outside Connection Model (Mass, Noiseless control)

    Power Supply

    Rated Consumption Current

    Output

    Input5kΩ at 25℃, Range of measurement : -40~120℃, Margin of error : ±0.3℃ at 25℃

    Connection Terminal

    Operating Condition

    Storage Condition

    AC90 - 250V ~ , 50/60Hz

    MAX 4VA

    Relay output 1-point (277Vac / 20A)

    Temperature sensor input 2-point (Dotech standard NTC sensor DPR-TH5-T1)

    Screw bolt terminal

    Temperature -10~50℃, Humidity below 90%RH

    Temperature -20~60℃, Humidity below 90%RH

    SSR operation output : 12VDC ±3V 20mA below (TX3-S1 model)

    ▲Floor heating ▲Heating film ▲Heating cable ▲Aquarium ▲Snow heating

    HeaterCooler

    Temperature ControllerTX3

    Temperature ControllerTX3

    Cooler Heater

    TX3 series are controllers to control temperature at construction site, factory and office etc.

    It is very economical because of reduction of power consumption. You can control easily because

    they are digital type. TX3 series offer High Quality/High Service at a reasonable price.

    !

    easycontrol

    ±0.3

    Easy Operation

    Simple and convenient menu composition makes it easy that users setup the device.

    Malfunction of the device can be prevented by setting LOCK and access level.

    ±0.3℃ Precise Temperature Control

    NTC temperature sensor,dotech's standard sensor, can mesure temperature range of

    -40℃ ~ 120℃ with margin of error of ±0.3℃.

    RS485 Communication

    Centralized monitoring solution to manage upto 128 devices at PC and RCU128 by adopting

    RS485 communication based on Modbus RTU/ASCII protocol.

    Integrated Control System Software for free

    Integrated control software is offered for monitoring 1~128 devices at main controller.

    Supporting Various Sensors

    Many kinds of temperature sensors can be adopted according to system construction.

    First CE certification in relevant industry field in South Korea

    TX3 series have first CE certification in floor heating temperature controller industry field

    in South Korea. TX series offer high reliability and safety.

    Display Error Messages and Alarms

    Users and engineers can easily grasp and manage condition of the device because error

    messages about problems such as disorders or malfunctions of the device are displayed.

    The Best Quality, Reasonable Price

    TX3 Series have the best quality within the same field and Its price is very reasonable.

    Nature Defrost

    User can use nature defrost function by turning off control output during defrosting every

    defrosting period time when cooling or heating system works.

    Cooling/Heating can be selected

    Optimum temperature control by selecting between cooling and heating according

    to environment.

    Easy Operation

    Simple and convenient menu composition makes it easy that users setup the device.

    Malfunction of the device can be prevented by setting LOCK and access level.

    ±0.3℃ Precise Temperature Control

    NTC temperature sensor,dotech's standard sensor, can mesure temperature range of

    -40℃ ~ 120℃ with margin of error of ±0.3℃.

    RS485 Communication

    Centralized monitoring solution to manage upto 128 devices at PC and RCU128 by adopting

    RS485 communication based on Modbus RTU/ASCII protocol.

    Integrated Control System Software for free

    Integrated control software is offered for monitoring 1~128 devices at main controller.

    Supporting Various Sensors

    Many kinds of temperature sensors can be adopted according to system construction.

    First CE certification in relevant industry field in South Korea

    TX3 series have first CE certification in floor heating temperature controller industry field

    in South Korea. TX series offer high reliability and safety.

    Display Error Messages and Alarms

    Users and engineers can easily grasp and manage condition of the device because error

    messages about problems such as disorders or malfunctions of the device are displayed.

    The Best Quality, Reasonable Price

    TX3 Series have the best quality within the same field and It's price is very reasonable.

    Nature Defrost

    User can use nature defrost function by turning off control output during defrosting every

    defrosting period time when cooling or heating system works.

    Cooling/Heating can be selected

    Optimum temperature control by selecting between cooling and heating according

    to environment.

    heating/cooling output, precise

    temperature control, sensor compensa-

    tion, sensor error detection function,

    easy-to-use, min. off maintaining time

    setup, nature defrost, switch to alarm and

    timer modewhen sensor error occurs,

    display to first decimal place

    communication function, heating/cooling

    output,precise temperature control, sensor

    compensation,sensor error detection

    function, min. off maintaining time setup,

    easy-to-use, free software for controlling at

    RCU128/PC, switch to alarm and timer mode

    when sensor error occurs

    SSR outside connection control, heating/cooling output, precise temperature control, sensor compensation, sensor error detection function, min. off maintaining time setup, high load switchgear by small signal, switch to alarm and timer mode when sensor error occurs, nature defrost, display to first decimal place

  • 34.5mm

    43mm

    Temperature ControllerTX3

    ON

    S2

    S1

    70mm

    120m

    m

    Demensions and Wiring diagram (Heating)

    Temperature Controller Installation

    How to control

    1. Connect sensors and wires at the back of temperature controller. (A sensor can be connected to whichever connection part of sensor when using 1 sensor.)3. Put the controller into the bracket. (It is removable.)

    2. Screw a bracket to the wall. (Please see the picture.)4. Screw the bottom of the controller.

    AC90-250V ~50/60Hz

    HeaterCooler

    Secondary Sensor

    RS485Commu-nication PrimarySensor

    6 5 4 3 2 1

    4 3 2 1

    The Back1

    2

    Temperature ControllerTX3

    ON

    S2

    S1

    ① ② ③ ④

    - Sensor Control Mode

    30℃

    29℃

    28℃

    ex) Heater is ON at 28.0℃ and OFF at 30.0℃ when desired temperature is 30 ℃ and

    control deviation is 2.0.

    Time

    ON

    TX3 controls heater/cooler by comparing current temperature with desired temperature.

    OFF OFF

    ● 2 Sensors : Current Temperature is detected by ratio of main sensor(70%) and

    secondary sensor(30%).

    ● 1 Sensor : Current Temperature is detected by sensor connected.

    Current Temperature

    -5℃

    -6℃

    -7℃

    ex) Cooler is ON at -5℃ and OFF at -7℃ when desired temperature is -7℃ and control deviation is 2.0.

    Time

    ONOFF OFF

    Current Temperature

    - Timer Mode

    HeaterCooler ON

    HeaterCooler OFF

    ON ON

    10 min.

    6 min.

    Heater/Cooler is ON for 6 min. and OFF for 4 min. when period is 10 min. and level is 6.

    OFF OFF

    Temperature is controlled by ON/OFF time control of Heater/Cooler after setting period and level.

    - Nature Defrost

    Control output is OFF every defrost period during defrost time if setting and using

    nature defrost function.

    ※ Switching to timer mode is enable when all sensors are removed or sensor disconnection happens.

    ● Timer Mode Operation Time : ON time : Period (1~60 min.)*(level(0~9) * 6sec.)

    OFF time : Period (1~60 min.) - ON time

    Power AC90 - 250V ~50/60Hz

    Heater

    ELCB (Earth LeakageCircuit Breaker)

    Temperature sensor

    Cooler

    Connection Heater or Cooler

    Temperature ControllerTX3

    ON

    S2

    S1

    ex) Desired temp.(ST I ) : 5.0℃ Control deviation(D I F) : 2.0℃ Defrost period(DFP) : 240min. Defrost Time(DFT) : 15min.

    8.0

    Temperature

    time

    7.06.05.0

    Defrost

    240min. 15min. 240min. 15min.

    OFFOUT1 OUT1

    Defrost

    OFF

    Heating Mode (TYP : H)

    Cooling Mode (TYP : C)

    Temperature Controller

    TX3 Series

    Some contents could be changed without prenotification / Edition 2010-06