TECHNICAL TRAINING 2007. CONTROLLER PROGRAM UPGRADE. 3 types program upgrade: ID PCB A type OD PCB B type OD PCB. PCB Program Upgrade. ID PCB Upgrade. Short the Jumper JP1, JP3 ~ JP6 on the PCB Connect the ID PCB and Gateway. Turn on the upgrade software in PC and select parameters. - PowerPoint PPT Presentation
Citation preview
Technical Training 2007Technical Training 2007
TECHNICAL TRAINING TECHNICAL TRAINING
20072007
Technical Training 2007Technical Training 2007
CONTROLLER PROGRAM CONTROLLER PROGRAM UPGRADEUPGRADE
Technical Training 2007Technical Training 2007
PCB Program Upgrade
3 types program upgrade:3 types program upgrade:
• ID PCBID PCB
• A type OD PCBA type OD PCB
• B type OD PCBB type OD PCB
Technical Training 2007Technical Training 2007
Turn off the
ID
PCB power
Power on
ID PCB Upgrade
1. Short the Jumper JP1, JP3 ~ JP6 on the PCB
2. Connect the ID PCB and Gateway
Turn on the upgrade
software in PC and
select parametersUpgrade
Revert the jumpers back to factory default setting after the completion of
upgrade
Technical Training 2007Technical Training 2007
Turn off the
OD
PCB power
Power on
Upgrade
1. Short the Jumper P1, P3 ~ P5 on the PCB
2. Connect the OD PCB and Gateway
A Type OD PCB Upgrade
Turn on the upgrade
software in PC and
select parameters
Revert the jumpers back to factory default setting after the completion of
upgrade
Technical Training 2007Technical Training 2007
Turn off the
OD
PCB power
Upgrade
Install the MCU board
& power on
B Type OD PCB Upgrade
Turn on the upgrade
software in PC and
select parameters
1. Remove MCU board & short the Jumper P1 ~ P5 on the PCB
2. Connect the OD PCB and Gateway
Revert the jumpers back to factory default setting after the completion of
upgrade
Technical Training 2007Technical Training 2007
1. Smart Commander connecting A Series unit
2. Smart Commander connecting B Series unit
Starting Up & Monitoring Software
Technical Training 2007Technical Training 2007
• Connection of OD and PCConnection of OD and PC
• Start Smart Commander, select parametersStart Smart Commander, select parameters
• Connect communicationConnect communication
• Monitor dataMonitor data
Monitoring Software with A series
Technical Training 2007Technical Training 2007
Monitoring Software with B Series
• Connection of OD and PCConnection of OD and PC
• Start Smart Commander, select parametersStart Smart Commander, select parameters
• Connect communicationConnect communication
• Monitor dataMonitor data
Technical Training 2007Technical Training 2007
Common Problems & Solutions
Possibilities of unsuccessful of upgrade:Possibilities of unsuccessful of upgrade:
• Monitoring Software is still connectingMonitoring Software is still connecting
• Wrong serial port is being selectedWrong serial port is being selected
• Wrong crystal frequency is being selectedWrong crystal frequency is being selected
• Wrong ID & OD jumper settingWrong ID & OD jumper setting
• Wrong jumper setting of GatewayWrong jumper setting of Gateway
• The transformer of Gateway is abnormalThe transformer of Gateway is abnormal
• The Gateway is abnormalThe Gateway is abnormal
• ID & OD PCB is abnormalID & OD PCB is abnormal
Technical Training 2007Technical Training 2007
Common Problems & Solutions
Operation of Smart Commander problems:Operation of Smart Commander problems:
• Wrong serial port is being selectedWrong serial port is being selected
• Wrong baud rate is being selected Wrong baud rate is being selected
• Wrong ID & OD jumper settingWrong ID & OD jumper setting
• Wrong OD address settingWrong OD address setting
• Wrong jumper setting of GatewayWrong jumper setting of Gateway
• The transformer of Gateway is abnormalThe transformer of Gateway is abnormal
• Gateway is abnormalGateway is abnormal
Technical Training 2007Technical Training 2007
Common Problems & Solutions
Malfunction of ID & OD communication:Malfunction of ID & OD communication:
• Incorrect ID & OD jumper settingIncorrect ID & OD jumper setting
• Incorrect polarity of communication wire Incorrect polarity of communication wire
• JP7 is not shorted for the last IDJP7 is not shorted for the last ID
• No power supply for IDNo power supply for ID
• Incompatible of ID & OD program version Incompatible of ID & OD program version
• ID or OD PCB is abnormal ID or OD PCB is abnormal
• Communication wire is too long. Should not Communication wire is too long. Should not more than 1000mmore than 1000m
Technical Training 2007Technical Training 2007
Precaution:
• Complete jumper setting before power on, if nComplete jumper setting before power on, if not the setting will not be changedot the setting will not be changed
• Connect the communication wire before power Connect the communication wire before power on, don’t insert or pull out it when power onon, don’t insert or pull out it when power on
• Pull out the signal output slot when testing Pull out the signal output slot when testing
• Ensure the pin and socket is corresponded Ensure the pin and socket is corresponded when installing the PCBwhen installing the PCB
• Incompatible of ID & OD program version Incompatible of ID & OD program version
• Ensure the dip-switch setting is correctEnsure the dip-switch setting is correct
• Follow the regulations & instructions in IMFollow the regulations & instructions in IM
Technical Training 2007Technical Training 2007
Thank YouThank You
Technical Training 2007Technical Training 2007
Short JP1, JP3 ~ JP5
Graphic of ID PCB
Connect to Gateway
Technical Training 2007Technical Training 2007
ID Jumper Setting
Factory Default Setting
Jumpers being shorted
Technical Training 2007Technical Training 2007
Gateway Connection
9Vdc power supply
Serial port
Connect to ID PCB
Open jumper J11 & J13
RS-485 Connection
Technical Training 2007Technical Training 2007
Selection of Parameters
1. MCU selection. MB89F538/L is being used.
2. The frequency of ID is 8MHz.
3. Select ID programming file.
5. Click to run full operation.
4. Select serial port.
Technical Training 2007Technical Training 2007
Upgrade Process
Upgrade process complete
Upgrade in progress
Start to upgrade
Technical Training 2007Technical Training 2007
Graphic of the A Type OD PCB
Connect to Gateway
MCU
Short P1, P3 ~ P5
Technical Training 2007Technical Training 2007
A Type OD Jumper Setting
Factory Default Setting
Jumpers being shorted
Technical Training 2007Technical Training 2007
Selection of Parameters
1. MCU selection. MB89F538/L is being used.
2. The frequency of OD is 4.9152MHz.
3. Select ID programming file.
5. Click to run full operation.
4. Select serial port.
Technical Training 2007Technical Training 2007
Graphic of B Type OD PCB
Connect to Gateway
MCU
Short JP1~ JP5
MCU board
Technical Training 2007Technical Training 2007
B Type OD Jumper Setting
Factory Default Setting
Jumpers being shorted
Technical Training 2007Technical Training 2007
Selection of Parameters
1. MCU selection. MB89F538/L is being used.
2. The frequency of OD is 4.9152MHz.
3. Select ID programming file.
5. Click to run full operation.
4. Select serial port.
Technical Training 2007Technical Training 2007
Wiring Connection (A Series)
A type OD PCB
Electrical outlet
9Vdc power supply
Gateway
Serial port
ID & OD communication wire * A to A ; B to B
Red & Black pairs connect to A;
Yellow & Green pairs connect to B
Communication wires of Monitoring Software
Technical Training 2007Technical Training 2007
Selection of Parameters
1. Select the correct serial port
2. Select baud rate (19200)
3. Select the numbers of OD
4. Select data record cycle
5. Click the button
Technical Training 2007Technical Training 2007
Graphic Interface of Monitoring Software
Discharge Temp
Ambient Temp
Suction Temp
Total required capacity
Output % of digital comp.
Opening of OD EXV
To check ID
Inlet Temp of OD condenser
Midlet Temp of OD condenser
Outlet Temp of OD condenser
Technical Training 2007Technical Training 2007
Graphic Interface of Monitoring Software
Starting status of compressor
OD fan speed
4WV status
Defrost parameters
To monitor slave unit
OD setting parameter
Technical Training 2007Technical Training 2007
Parameters can be observed for ID
ID selection column
Single ID required capacity
Selection of operating parameters
Click “Apply” to operate
Monitor Data
Technical Training 2007Technical Training 2007
Selection of OD Parameters
EXV opening setting
Adjust target super heat. The default value for R22 is 5 whereas 3 for R410A
Critical point of defrost curve
Defrost stop when reach this temp (TH9)
If TH9 ≤ TscA1, target sub-cool is TscT1
If TscA1 < TH9 < TscA2, target sub-cool is TscT2
If TH9 ≥ TscA2, target sub-cool is TscT3
Heating EXV motion coefficient.
Connecting pipe compensate coefficient
Midlet temp setting for all ID (heating)
Technical Training 2007Technical Training 2007
Special Command Button
Manual defrost. The master unit will turn into defrost mode
All EXV will open to 480 steps.
Technical Training 2007Technical Training 2007
Selection of Parameters (Slave OD)
Change slave unit parameter
Technical Training 2007Technical Training 2007
Wiring Connection (B Series)
B type OD PCB
9Vdc power supply
Serial port
ID & OD communication wire * A to A ; B to B
Communication wires of Monitoring Software
Technical Training 2007Technical Training 2007
Signal Output Slot
Remove the Signal Output Slot when testing