Upload
others
View
30
Download
4
Embed Size (px)
Citation preview
Page1of27
TECHNICAL SPECIFICATION OFRTU
Page2of27
Index
Section1: TECHNICALSPECIFICATIONOFRTU.........................................4
1.0 General...................................................................................................4
1.1 DesignStandards...................................................................................5
1.2 RTUFunctions........................................................................................5
1.3 Communicationports..............................................................................6
1.4 Modems..................................................................................................6
1.5 LocalLogger/PrinterInterface................................................................7
1.6 LocalConfiguration&MaintenanceInterface.........................................7
1.7 LocalDataMonitoringSystem(LDMS)Interface....................................7
1.8 CommunicationinterfacebetweenRTU&MFTs....................................8
1.9 CommunicationProtocolbetweenRTU&IEDs......................................8
1.10 MasterStationCommunicationProtocol.................................................8
1.10.1 Scangroups ....................................................................................9
1.10.2 Reportingofstatuspoints................................................................9
1.10.3 ReportingofAnalogpoints............................................................10
1.10.4 Digitalcontrolcommands..............................................................10
1.11 DataConcentratorCommunicationProtocol........................................10
1.12 AnalogInputs........................................................................................10
1.13 StatusInputs.........................................................................................11
1.13.1 ContactMultiplyingRelay..............................................................12
1.13.2 MomentaryChangeDetection.......................................................12
1.14 DigitalTelemetry...................................................................................12
1.15 SequenceofEvents(SOE)feature......................................................12
1.16 ControlOutputs....................................................................................13
1.16.1 TwoStateMomentaryControl.......................................................13
1.16.2 Raise/LowerPulseOutput.............................................................13
1.16.3 TimedSupervisoryControl............................................................14
Page3of27
1.16.4 ControlOutputInterposingRelays(DoubleContactDigitalOutput) 14
1.16.5 Latching(DummyBreaker)Relay.................................................14
1.16.6 ControlSecurityandSafetyRequirements....................................14
1.16.7 Local/Remoteselectorswitch........................................................14
1.17 Timefacility...........................................................................................15
1.18 Diagnosticfeatures...............................................................................15
1.19 InputDCPowerSupply........................................................................15
1.20 EnvironmentalRequirements...............................................................16
1.21 Noiselevel............................................................................................16
1.22 RTUSizeandExpandability.................................................................16
1.23 RTUandSICpanels.............................................................................15
1.24 Interconnections...................................................................................16
1.25 Wiring/Cablingrequirements................................................................17
1.26 TerminalBlocks....................................................................................17
1.27 RTUArchitecture..................................................................................18
1.28 Transducer&WeatherSensorRequirements.....................................18
1.28.1 TransducerProtection...................................................................18
1.28.2 Multi-FunctionTransducers(MFTs)...............................................18
1.28.3 TransformerTapPositionTransducer...........................................19
1.28.4 WeatherSensors...........................................................................19
1.28.4.1 AirTemperatureSensor.........................................................20
1.28.4.2 RelativeHumiditySensor.......................................................20
1.28.4.3 RainfallSensor.......................................................................20
1.28.4.4 WeatherSensorInstallationRequirement..............................21
1.29
PortableConfigurationandMaintenanceTerminal(PCMT)..............21(a)RTUData
baseconfiguration.................................................................21(b)LocalOperat
orinterfaceand RTUdiagnostics.................................22 (c) Masterstation-
cum-RTUsimulator&protocolanalyzersoftwaretool...22
1.30 TESTING..............................................................................................23
1.30.1 RTU/SICTesting...........................................................................23
Page4of27
Section1: Section1:
TECHNICALSPECIFICATIONOFRTU
1.0 General
TheRemoteTerminalUnit(RTU),shallbeinstalledatSubstations to acquire analog data such as,
KW export, KW import, frequency, OLTC,power factor, maximum demand, planned outage
duration & numbers, forced outage duration & numbers, electricity consumed locally, MVA
capacity of Sub-Station, length of Transmission lines etc.&also digital data like status of
isolators, circuit breakers etc. at each Sub-Station under this scope of work and
transfer those information to data server at SLDC. RTU shall also be used for control of
station devices from Master station. The necessary data base creation at SLDC for integration of
RTU with control Centre i.e. SLDC is also included under this scope of work. RTU shall also
be used for control of station devices from Master station. I n a d d i t i o n w i t h t h a t
eachsubstationunderthescopeofthisprojectshallhave
aPCbasedLocalDataMonitoringSystem(LDMS).TheseDASPCsshallbe usedfor
acquisition,monitoringofvariouselectricalparametersand
generationofreportsandlogsheetsinlinewiththerequirementsof the
specification.ThesuppliedRTUsshallbeinterfacedwith the Control &Relay (C&R) panels,
communication equipment, power supply
distributionboards;forwhichalltheinterfacecablesshallbesuppliedby the Contractor.
Thisdocumentdescribesthespecificationsfor the RemoteTerminalUnit(RTU).
ContractorshallsupplyRTU,associatedequipmentsuchas transducers,relays,
weathersensors,modems,cablingetc.andrequirednumberofpanelsforhousing
ofallthehardwareenvisagedfortheRTUandsysteminterfacecubicle(SIC).
Thecontractorshallberesponsibleforsupplyingallhardware,software,installation,
cablingandfieldimplementationforRTUasdefinedin thisSpecification. The
contractorshallalsoprovidecompletedocumentation,trainingandtestingto fully
supportthehardwareandsoftwareprovided.TheRTUshallbeusedfor real-time
supervisionandcontrolof substation/powerplantthroughSCADAsystem.RTU
configuration/pointcount,transducercountandrequirementof weathersensors
quantityisgiveninschedule of works.
Itis Employer’sintentthattheContractorusesasmuchstandardhardwareandsoft-
wareaspossible;however,allofthefunctionalrequirements ofthisSpecification
mustbesatisfied.TheuseoftheContractor'sstandardhardwareandsoftwaremay
causetheContractorto concludethatthereisaneedforadditionalitemsnot specifically mentionedin
this Specification. The Contractorshall supply all such itemsandprovidea
completeRTUdesignthatmeetsalloftheEmployer’sfunctional
requirementsdefinedinthisSpecification.
It is the responsibility of the bidderto configuretheRTU to make it compatible with (i) M/s
Chemtrol make RTU to be supplied under ULDC expansion project of WBSETCL,(ii) existing
Page5of27
ALSTOM make S900 RTU, (iii) existing Net Work Management System(NMS)and/or new NMS
of Control Centre (iv) Fiber Optic terminal equipment to be supplied under this project, (v)
Existing PLCC equipment of WBSETCL, (vi) Readily available standard Fiber Optic terminal
equipment & PLCC equipment.
TheWeatherSensorsto besuppliedundertheprojectshallbefieldprovenandshall
havebeeninsuccessful operationformeteorological application foratleastone
yearasondateofBidopening.TheBiddershallfurnishthedocumentaryevidence
insupportoftheaboveandsubmitthesamealongwiththebid.
1.1 DesignStandards
TheRTUsshall bedesignedin accordancewithapplicableInternationalElectro-
technicalCommission(IEC),InstituteofElectricalandElectronicsEngineer(IEEE), American
NationalStandards Institute (ANSI), and National Equipment
Manufacturersassociation(NEMA)standards,unlessotherwisespecifiedin this
Technicalspecification.Inallcasestheprovisionsofthelatesteditionorrevisionof
theapplicablestandardsineffectshallapply.
1.2 RTUFunctions
AllfunctionalcapabilitydescribedhereinshallbeprovidedbytheContractorevenif
afunctionisnotinitiallyimplemented.Thetermmasterstationisusedtodenotethe SCADA systems.
As a minimum, the RTUs shall be capable of performing the followingfunctions:
(a) Collecting and processing the digital status inputs, analog inputs,
accumulatedvaluesandtransmittingtoat least threemaster station(s)
(b) Receiving andprocessing digital&analog controlcommands from at least three
master masterstation(s)
(c) Accepting polling messages from at least three master station(s)
simultaneouslyusingseparatelogicaldatabasesforeachmasterstation.
(d) Communication simultaneouslyon all Communication ports (as per cl.
1.3)andusingmultipleconcurrentprotocols,includingtheIEC60870-5-
101,60870-5-104&MODBUS/103protocol.
(e) Datatransmissionratesfrom300to9600baudforserialports(forboth IEC60870-5-
101&MODBUS/103)and10/100MbpsforTCP/IPEthernet ports.
(f) RTU shallbe compatible with protocol 61850 for communication with
IEDs.
(g) RTU shallhave the capability of automatic start-up and
initialisationfollowingrestorationofpowerafteran outagewithoutneedofmanual
intervention. All restartsshall be reported to the connected master station(s).
(h) RTUshallsupporttimesynchronizationthroughmessagesreceivedfrom
masterstationusingIEC60870-5-101/ IEC60870-5-104protocol.
Page6of27
(i) RTUshallsupportdownloadingofRTUdatabasefromthemasterstation
usingtheIEC60870-5-101andIEC60870-5-104protocol.
(j) RTUshallsupportSOE(Sequenceofevents)feature
(k) Actingasa dataconcentratorforacquiringdatafromSlaveRTUsand
exercisingsupervisorycontrolonslaveRTUsusingIEC60870-5-101and IEC60870-5-
104protocol.
1.3 Communicationports
The RTUsshallsupportsimultaneouscommunicationswith multipleindependent
masterstations(SCADAsystem),maintenanceandconfigurationterminal(Laptop PC),a
locallogger(printer),Multi-functiontransducersand LocalDataMonitoring
System(LDMS)/Logger.
TheRTUsshallhavecommunicationportsasfollows:
a) TwoEthernetportsforconnectivitytoMasterStationonIEC60870-5-104
andtorelaysonIEC61850.
b) 2RS232ports–forcommunicationwithmasterstationson IEC60870-5-
101
c) OneportfortheRTUmaintenanceandconfigurationterminal.
d) One port for Local Data Monitoring System (LDMS) and local logger
(printer).
e) Requirednumber(minimumtwo)ofRS485portsforpollingMulti-function
transducersusingMODBUS/103protocolinmulti-drop(partyline)mode
ItshallbepossibletoincreasethenumberofcommunicationportsintheRTUby
additionofcards,ifrequiredinfuture.TheRTUshallrespondtoindependentscans and commands
from Master Station, LDMS and Configuration &Maintenance
Terminalsimultaneously.TheRTUshallsupporttheuseofadifferentcommunica-
tiondataexchangerate(bitspersecond)andscanningcycleoneachport.
1.4 Modems
Themodemscanbeusedfor RTUcommunicatingto masterstation.The Contractor shallsupply
two(2)number modems oneatControl Centre/Stand aloneandotheratRTUend.
Themodemforremoteend,completeinallrespectsincludingpowersupplyunit&rackshallbesupplied.
ThesemodemscanbelocatedeitherintheFEPatControl
CenterendoratotherCommunicationnodes(StandAloneModem).
Themodemsshallmeetthefollowingrequirements:
a) UseCCITTStandardsincludingV.24,V.28.
b) Usefrequencyshiftkeying(FSK)modulation.
c) Communicateatdataratesof300,600and1200bps.
d) UseCCITTR.38a,andR.38bstandardtonesfortheselectedRTUdata rate.
Page7of27
e) UsePLCC bandwidthupto4khzandshall accommodate multiple data
channelsoverandabovevoicechannels.
f) Useboth2-wireand4-wirecommunicationlines.
g) Receiveleveladjustablefrom-8to-40dBm@600ohms. h)
Transmitleveladjustablefrom0to-24dBm@600ohms. i)
Haveaminimumsensitivityof-48dBm.
j) Shalloperateon48VDC powersupply, positive earthedk)
CompatiblewithIEC101/104
1.5 LocalLogger/PrinterInterface
TheRTUsshallincludethe interfaceto supportanoptionallocallogger/printer.The
interfaceshallprovideeasyaccesstoallowemployertoconnecttheloggeratthe
RTUsinstalledinthefield.
1.6 LocalConfiguration& MaintenanceInterface
TheRTUsshallincludetheinterfaceto supporttheportableconfigurationand
maintenanceterminal(PCMT).Theinterfaceshallprovideeasyaccessto allow
employertousethemaintenanceterminalattheRTUsinstalledinthefield.
1.7 LocalDataMonitoringSystem(LDMS)Interface
TheRTUsshallincludetheinterfaceforcommunicationwiththeLDMSsystem.The
LDMSshallbeusedforlocaldataacquisition,monitoringandcontrolofsubstation parameters
throughRTU. The scopeof LDMS shall include installation and
integrationofLDMSsoftwareonaPersonalcomputer.
TheLDMSshallbeaminiSCADAsystemprovidingMMIcapabilityforuseinthe sub-station
controlroom building. The LDMSsoftware shall include following functions:
I. dataacquisitionforanalog,digitalandpulseaccumulatortypedata
II. data processing – Conversion to engineering units , limit monitoring, data
validitytest,calculateddata
III. calculateddata(suchasmaximum,minimum,average valueswithassociated time-
stampingetc.)ofallthestationparameters.
IV. TimeSynchronization
V. SequenceofEventsProcessing
VI. Supervisorycontrol
VII. Alarm,tagging,trending,qualitycodesetc.
VIII. Single Line Diagrams,Trends,daily,weekly,monthlyreportsetc.shall be
preparedbythebidderandintegratedonLDMSsystem. TheLDMSshall
alsohavecapabilitytogenerateadditional displays, singlelinediagrams,
reports,andtrends.
TheLDMSshallstoreallreal-timetelemetered& calculateddataevery5 minutes
(adjustableto15,30,45,60minutes).Thesoftwareandhardwareshallbesized forstorageof
Page8of27
allabovedataatevery5minutesforatleastsixmonthsduration.
Allalarms,events,SOEetc.shallalsobestoredon regularbasis. Itshallbe
possibletodefinedaily,weekly,monthly SubstationreportsonLDMS.It shallbe
possibletogeneratereportshighlightingthemaximum,minimum,average with associated time-
stampingetc.ofallthe stationparameters.Thehistoricaldata stored
onthestoragemediumshallbeinstandardformatandnecessarytools foritsexportto
standardspreadsheetprograms(Excel)shallbeprovided.
TheLDMSshallupdateanalogdatafromRTUeverytenseconds(programmable)
andstatusdatabyexception.TheSOEstatusdatashallberecodedwithresolution of10mstimestamp.
1.8 CommunicationinterfacebetweenRTU&MFTs
TheRTUshallacquiredatafromtheMFTs.TheMFTswillactasslavetotheRTU.
TheRTUshallhavetheabilityofissuingretryscanto acquiredata fromtheMFTsin
caseofcommunicationfailurebetweenRTUandMFTs.All datafromthedevices
connectedonasingleportshallbeacquiredwithin5seconds.
1.9 CommunicationProtocolbetweenRTU&IEDs
TheRTUshallusetheIEC61850protocolforcommunicationwithIEDsoverSub-
stationLAN.TheRTUshallactasaClientandcollectdatafromtheIEDs).
TheRTUshallstorethe dataacquiredfromtheMFTs&IEDsin itsdatabaseanddo
processinglikechangedetection/deadbandprocessingonthedataforoptimizingits transmissionto
theMasterStation(SCADAControlCentre).Theprocessingshall
includerequirementsofmappingofinformationfromtheprotocolofMFT/IEDstothe
protocolrequirementforcommunicationwithControlCenter.
1.10 MasterStationCommunicationProtocol
The Contractorshall provide a communication protocol for communicating with
SCADAmasterstationsusingtheIEC60870-5-101and IEC60870-5-104
communicationprotocolstandard.Thecommunicationprotocolshallsupportallthe
requirementsofthisstandard.Thecommunicationprotocolshallbenon-proprietary andthe
Contractorshallprovidecompletedescriptionanddocumentationofthe protocoltoOwner.
TheRTUshallperformasaslavetoSCADAmasterstation.Allcommunicationshallbe
initiatedbytheSCADAmaster
stations.RTUmustnotifythemasterstationsofunusualconditionsattheRTU(such
asapowerfail/restorationorRTUmalfunction),thetransferofchangeddataetc.All the
notificationsshallbeaccomplishedwithinthe frameworkofthe periodicdata acquisitionexchanges.
TheRTUshallprocessthevariousmessages/commands forcommunicationtothe
Masterstationusingthefollowingpriority.a)
Controlcommand
b) Statusdatabyexceptionc)
Analogdatabyexception d)
Analogdataperiodic
e) Statusdataintegrityscan
Page9of27
The communication interface to the master station(s) shall allow scanning and
controlofdefinedpointswithintheRTUindependentlyforeachmasterstationusing
aseparatelogicaldatabaseintheRTU.Itshallbepossibletopickpointsfromthe
RTUdatabaserandomlyandassignitforreportingtoaMasterstation.Further,the
RTUshallsupporttheuseofadifferentcommunicationdataexchangerate(bitsper
second),scanningcycle,and/orcommunicationprotocoltoeachmasterstation.
1.10.1 Scangroups
Analoganddigitalinputpoints(includingpointsreportedby exception)shallbe assignable
toscangroups.Ascangroupshallbeaspecified setofdatapoints
withintheRTUcentraldatabasewhichwillbecommunicated toamasterstation whenrequestedbya
specific(addressed)scanrequest.Ascangroupsizeshallonly
belimitedbythecommunicationprotocolmessagelength.AnyRTUinputpointshall beassignable
toanyscangroup. TheRTUsshallsupport atleastsixteenscan groupsandallscangroupsper
communicationport(i.e.masterstation/LDMS interface). The Contractorshall provide a
convenient and flexible scheme for assigningpointsintheRTUtoscangroups.
1.10.2 Reportingofstatuspoints
TheRTUcommunicationprotocolshallbeconfiguredtoreportdigitalstatuschanges
byexceptiontomasterstation.Digitalstatusdatashallhavehigherprioritythanthe Analogdata.All the
digitalstatusdatashallalsobeassignedto scangroupsfor
integritycheckbyMasterstationsatevery10minutes.
1.10.3 ReportingofAnalogpoints
Theanalogdatashallbereportedperiodicallytoupdateallthevaluesatthemaster
stationwithin10to15seconds.Analogdatashallalsobereportedbyexceptionif
theanalogvalueexceedsitspreviousvalueby morethan20%.
1.10.4 Digitalcontrolcommands
TheRTUshallfollowtheselect-and-executesequenceforoperationofdigitalcontrol
commandsfromthemasterstation.TheRTUshallresetitscontrollogicuponany errorinthesequence.
1.11 DataConcentratorCommunicationProtocol
TheRTUshallactasaIEC60870-5-101andIEC60870-5-104protocolmasterand collectdataand
alsoperformsupervisorycontrolfrom/ontheslaveRTUsand
communicateittotheControlCenter.TheMasterprotocolimplementationshallbe
suchthatthedatapollingrequirementsmentionedat section1.10is atleast accomplished.
RTUasaDataconcentratorshallbeprovidedwithatleastthree(5)IEC101 andseven(7)IEC104 inputports/cardsandshallhavecapabilityto reportto twomasterstationsonIEC104 interface. Data
concentratorshall support at least 1,500 (fifteen hundred) data points.TheRTUasa
DataConcentratorshallbesuppliedwithGPSreceiversystem withantenna,cableetc.fortimestampingofDataconcentratorwhichinturnshall
synchronizetheIEC101and IEC104 protocolconnectedRTU/device.TheRTUasa Data Concentratorshallcomecompletewithbuiltinmonitoringmechanismtoavoidloss
ofanydata,especiallytheonereportedbyexception.Thedataconcentratorshall havedualCPUanddualPowersupplyunit. Theoveralldataupdaterequirement fromany Sub-RTUto
Controlcentreshouldnotaffectthefunctionalitydefined elsewhereinthespecification.
Page10of27
TheDataconcentratorshallhavetheprovisionforremoteloginfromControlcentre.
TheSLDCcomputersystemshallbeableto configureandpollhealthofData
concentratorfromremoteon104connectedinterfaceafterdueauthenticationofthe users.
It shallsupport diagnostic &maintenance activities remotely. Individual RTU
configurationshallbe possiblefromDataConcentratorincludingaccommodating
devicesfromheterogeneoussuppliers.TheRTUasaDataConcentratorshallhave
followingcommunicationports&supportforprotocols:
i. IEC104forSCADAcontrolcenters.ii.
IEC101forSub-RTUs.
iii. IEC104forSub-RTUs.
iv. IEC101/104forlocalSCADA
The other requirements given for RTU elsewhere in the specification shall be
applicabletoRTUasaDataconcentratoralso
1.12AnalogInputs
TheRTUshallaccommodateanaloginputswhichare unipolaror bipolar,2-wire
ungroundeddifferentialsignals.Allanaloginputsareof+4to+20mA.However,theRTUshallbecapabl
eofacceptingotherstandardanaloginputranges(0to5V,0-10V,0to10mA).
TheRTUshallmakeall appropriatesignallevelconversionand conditioningtoallow full
utilizationof analoginputsandmeaningfulreasonabilitychecking.Theanalog-to-
digitalconvertershallhaveaminimumresolutionof2048counts(signplus11data
bits).Eachtypeofanaloginputshallbeconvertedwithfullresolution.TheRTUshallmonitorthedriftinc
haracteristicsofitsADCandmarktheanalogpointswithadriftqualitycodeifadriftisdetected.Thisdrift
qualitycodeshallbesenttothemasterstationalso.
TheRTUaccuracy,foranaloginputmeasurement,shallbe99.8%or betterat 25
degreeCambienttemperature.Meanaccuracyshalldriftnomorethan0.002%per
degreeCwithinthetemperaturerangeof–5 to+55degreeC.Determinationof
accuracyshallbemadewhiletheanalogmultiplexerisoperatingatratedspeed.
Eachinputshallhavesuitableprotectionandfilteringto provideprotectionagainst
voltagespikesandresidualcurrentat50Hz,0.1ma(peak-to-peak)andoverload. Loadingupto150%of
theinputvalueshallnotsustainanyfailuresto theRTUinput.
ThetotalinputimpedanceofferedbytheRTUshallnotbegreaterthan250 (for+4 to+20mArange).
AllanaloginputsshallbescannedbytheRTUfromthefieldatleastat1second periodicity.
1.13StatusInputs
RTUshallbecapableofacceptingisolateddry (potentialfree)contactstatusinputs.
TheRTUshallprovidenecessarysensingvoltage,current,opticalisolationandde-
bouncefilteringindependentlyfor eachstatusinput.The sensingvoltageshallnot
exceed48Vdc.ThesensingvoltagesourceshallbeisolatedfromthatoftheRTUs logicpowerso
thatanynoiseora shortcircuitacrossthesensingsupplyofadigital
statusinputterminalswouldnotdisrupttheRTUoperationotherthantheshorted digitalstatusinput.
TheRTUshallbesettocapturecontactoperationsof20msor moreduration. Operations
oflessthan20msduration shall beconsidered nochange (contact
Page11of27
bouncecondition).TheRTUshallaccepttwotypesofstatusinputsi.e.Singlepoint
StatusinputsandDoublepointstatusinputs.
Singlepointstatusinputwillbefromanormally-open(NO)ornormally-closed(NC)
contactwhichisrepresentedby1-bitintheprotocolmessage.
Doublepointstatusinputwillbefromtwocomplementarycontacts(oneNOandone
NC)whichisrepresented by2-bitsintheprotocol message. Aswitching devicestatusis
validonlywhenone contactis closedandtheothercontactis open.Invalid
statesshallbereportedwhenbothcontactsareopenorbothcontactsareclosed.
All status inputs shall be scanned by the RTU from the field at 1 millisecond periodicity.
1.13.1 ContactMultiplyingRelay
Contactmultiplyingrelays(CMRs)arerequiredtomultiplytheauxiliarycontactsof breaker/isolators
etc.Thecontactsoftheserelaysshallbeusedtoprovidestatus inputto
theRTUs.Therelaysshallbeofselfresettype.Therelayshallhavea
minimumoftwochangeovercontactseachwithminimumcurrentcarryingcapacity
of5Aat110V/220VDC.
Therelaysshallconformtothefollowingrequirements:
a) Power frequency withstand voltage: 2 kV for 1 minute as per IEC
standards.
b) Insulationresistanceof100Mohmsat500VDC. c)
5KVImpulsetestasperIECstandards
TheCMRsshallbegenerallymountedinexistingcontrol&Relaypanelbutincase of non-availability
of space, it shall be accommodated in the System Interface
Cabinets(beingsuppliedbytheContractor).
1.13.2 MomentaryChangeDetection
Two-statestatusinputpointswith momentarychangedetectionshallbe usedby Employerfor
pointswheremultipleoperations(changesofstate) can occurbetween scansfromthe
masterstation(suchasbreakerswithauto-reclosingdevicesthat operate fasterthan the master
station scan rate). The RTUshall capture and
maintainallofthemomentarychanges,upto4perMCDdigitalstatuspoint.The
MCDstatusinputpointsshallbesettocaptureoperationsofgreaterthan20ms duration.
Alternatively,theRTUcanstoreandreportthemultiplestatechangesofadigital
inputasdiscreteevents.Itshallbeensuredthatallthechangesarereportedto the
MasterstationinthesequenceinwhichtheyoccurintheRTU.
1.14DigitalTelemetry
Digitaltelemetryinputpointsshallbeprovidedforsixteenbitinputsfromemployer telemetry contacts.
Thedigitaltelemetry mayuseBCD, (4bitdecimal character withoutsign)and/orbinary(16bit)codes.
1.15Sequenceof Events(SOE)feature
SOEisthetime-stampeddigitalstatusdata.SOEswillenableEmployer'spersonnel to
determinethesequentialoperationofdigitalstatusinputdevicesfortheirstate changes.
Page12of27
TheRTUshalltime-stampthedigitalstatusdatawithatimeresolutionof onemillisecond.
Initially,allbreakers&protectioncontactsdigitalstatusinputpointsintheRTUshall beconfigured
asSOEpoints. However itshallbepossible toassign anydigital
statusinputdatapointintheRTUasSOEpoint.Each time aSOE status input point changes state, the
RTU shall time-tag the changeandsendittotheMasterstation.TheRTUshallmaintain aSOEbuffer
withintheRTUforcommunication delaysandcommunication failure.SOEbuffer
shallbesizedtostore,asaminimum,of600events.TheRTUshalltransmitthe
SOEdatastoredinitsbuffertomasterstation.Anacknowledgement ofreceiptby
themasterstationshallbemadepriorto thelossofanydatain the RTUSOEbuffer.
Datanotreceivedatthemasterstationshallberetransmitted.TheRTUshallsenda message to the
master station to indicate the RTU SOE data buffer overflow condition.
1.16ControlOutputs
TheRTUshallprovidethecapabilityforamasterstationtoselectandchangethe stateofdigitaloutput
points. Device controlwillbeusedbyemployer tocontrol powersystemdevicesincluding:
(a) Two-stateDevices:Circuitbreakers, motor-operated switches,auto/ma-
nualswitches,relaydisable/enable,andothertwo-statedevices
(b) VariableOutputDevices:Raise/lower controlofgenerators, transformer load-tap-
changers(LTC),andothervariableoutputdevices.
TheRTUsshallhavethecapabilityforcontroloutputsasdescribedinthefollowing sections
1.16.1 TwoStateMomentaryControl
Apairofoutputsshallbesuppliedforeachtwo-state(open/close) controloutput
pointthatdrivecontrolrelays.Oneoutputshallbesuppliedforopen,theotherfor
close.Uponcommandfroma masterstationusingthecheck-before-execute
sequence,theappropriatecontroloutputshallbeoperatedforapreset(momentary)
timeperiod.Theoperationperiodshallbeadjustablefor eachpointfrom0.1to2 seconds.
1.16.2 Raise/LowerPulseOutput
Apairofoutputsshallbesuppliedforeach(raise/lower) controloutputpointthat
drivecontrolrelays.Oneoutputshallbe suppliedforraise,theother forlower.When
commandedfromthemasterstation,theappropriateraiseorloweroutputshallbe operatedfor the
selectedtimeinterval.Theclosuretime intervalforraise/lowerpulse
outputpointsshallbespecifiedintheoperatecommandfromthemasterstation.
Theraise/loweroutputforeachpointshalloperateoverarangeof0.1to4seconds
inaminimumofeightequalincrements.
Page13of27
1.16.3 TimedSupervisoryControl
The RTUshallstore TimedSupervisorycontrolcommandreceivedfromthe SCADA
system.ThissupervisorycontrolcommandfromtheSCADAsystemshallcontain
the‘time’uptoaresolutionofmillisecondsandthetypeofcontrolOperation.
TheRTUshallthenperformthesupervisorycontrolcommandatthespecifiedtime.
TheSCADAsystemshallbeabletocancelthiscommandpriortotheoccurrenceof
thespecifiedTimeofOperation.
1.16.4 ControlOutputInterposingRelays(DoubleContactDigitalOutput)
Controloutputinterposingrelaysshallbesuppliedby theContractorfor eachcontrol
outputspecifiedinappendix.Eachcontrolrelayshallconsistoftwoisolatedsingle- poledouble-
throwcontacts.Theoutputcontactsshallbe ratedtocarryminimum
currentof10ampsat220VDC,andshallprovidearcsuppressiontopermitinter-
ruptionsofaninductiveload.Relaycoilsshallbeshuntedwithdiodestosuppress
inductivetransientsassociatedwithenergizingandde-energizingoftherelaycoils.
TherelaysshallconformtotheIECstandards.
1.16.5 Latching(DummyBreaker)Relay
TheContractorshallprovidea latchingrelaytobeusedtosimulateandtest supervisory controlfrom
the RTU. The simulationrelay shall accept the control signalsto
openandclosefromtheRTU,andshallprovidethecorrectindication
responsethroughasinglecontactindicationinputpoint.Thispointisnotincludedin
theRTUpointcountinSchedule of works.
1.16.6 ControlSecurityandSafetyRequirements
TheRTUshallincludethefollowingsecurityandsafetyfeaturesasaminimumfor controloutputs:
(a) Select-and-executesequenceforcontroloutput.
(b) Nomorethanonecontrolpointshallbeselectedatanygiventime.
(c) Thecontrolselectionshallbeautomaticallycancelledifafterreceivingthe "control
selection" message, the "control execute" command is not
receivedwithinthesettimeperiod.
(d) Thecontrolselectionshallbeautomaticallycancelledifafterreceivingthe "control
selection" message, the "operate" command is not the next
receivedmessageandisnotreceivedwithinthesettimeperiod.
(e) Nocontrolcommandshallbegeneratedduringpoweruporpowerdown ofRTU.
1.16.7 Local/Remoteselectorswitch
A manualLocal/RemoteselectorswitchshallbeprovidedforeachRTUtodisableall control
outputsbybreaking the power supply connection tothe control outputs.
Page14of27
Wheninthe"Local"position,theLocal/Remoteswitchshallallowtestingofallthe control outputsof
RTU without activating thecontrol outputs tofield devices. A
statusinputindicationshallbeprovidedfortheLocal/Remoteswitchto allowthe SCADAsystemto
monitorthepositionoftheswitch.Thispointisnotincludedin the RTUpointcountdefinedinSchedule
of works.
1.17Timefacility
TheRTUshallhaveaninternalclockwiththestabilityasdefinedinTable-1.The
RTUshallbesynchronisedthroughsynchronisationmessagefrommasterstationat every10
minutesusingIEC60870-5-101/104protocol.TheRTUshallsupportthe
calculationofthepropagationdelaydynamicallybytheMasterstation.However,all
theRTUsshallhaveasuitableinterfaceforreceivingsynchronizationsignalsfroma localGPSreceiver.
TheRTUscommunicatingoverIEC-60870-5-
101/104shallbesuppliedwithaGPSreceiverforsynchronizationofRTUclock.
TheRTUshallsynchronizeitsinternalclockwiththemasterstationsystemclock when time
synchronization messages are available and shall mark all the time stampedinformation/data
asinvalidwhentheRTUclockisnotsynchronisedwith theMasterstation.
1.18Diagnosticfeatures
TheRTUdesignshallfacilitateisolationandcorrectionofallfailures.Thefollowing features which
promote rapid problem isolation and replacement of failed componentsshallbeprovided:
a) Self-diagnosticcapabilitieswithineachRTUwhichcanbeinitiatedatthe RTUsite.The
diagnosticsoftwareshall check for memory,processor,and
input/outputportserrorsandfailuresofotherfunctionalareasdefinedin
thespecificationoftheRTU.
b) On-lineerrordetectioncapabilitieswithintheRTUanddetailedreporting
totheconnectedmasterstationofdetectederrors.Itshallbepossibleto
choosetheerrorstobesenttotheMasterstationwithintheframeworkof
thecommunicationprotocol.
c) LocalindicationofmajorRTUfailures
d) Anon-volatileeventbufferthatshallrecordallfatalerrors/restarts/faults.
1.19InputDCPowerSupply
TheRTUwill bepoweredfroma 48VDC(+veearthed)system.TheRTUshallnot
placeadditionalgroundontheinputpowersource.Thecharacteristicsoftheinput
DCpowersupplyshallbe
(a) Nominalvoltageof48Vdcwithoperationbetween41and60Vdc.
Page15of27
(b) MaximumACcomponentoffrequencyequaltoorgreaterthan100Hz
and0.012timestheratedvoltagepeak-to-peak.
TheRTUshallhaveadequateprotectionagainstreversedpolarity,overcurrentand
undervoltageconditions,to preventtheRTUinternallogicfrombeingdamagedand
becomingunstablecausingmal-operation.
1.20 EnvironmentalRequirements
The RTU will be installed in control room buildings with no temperature or
humiditycontrol.TheRTUsshallbecapableofoperatingin ambienttemperature from-
5to+55degreeCwithrateoftemperaturechangeof20degreeC/hour and relativehumidityless
than95%,non-condensing.At somelocations, environmentaltemperaturemaygobelow–
5degreeCforwhichthecontractor shalltakesuitablemeasuresforsuccessfuloperationofRTU.
1.21Noiselevel
TheaudiblenoisegeneratedbytheRTUequipmentshallnotexceed50dbAone
meterfromtheenclosure.
1.22RTUSizeandExpandability
The softwareandthedatabaseshallbe sizedtoaccommodategrowthwithinthe ultimate sizing
parameters as defined in this specification for the RTU without
requiringsoftwareordatabasestructureregeneration.
ThepointcountsfortheRTUshavebeendefinedin theSchedule of works.TheRTUshall
haveadditionalwiredavailablereservecapacityoftwentypercent(20%)foreach
typeofpointsdefinedintheBOQ. Thisreservecapacityshallbeusedwithoutany
additionalhardwaresuchasI/Ocardsandterminalblocks.
The RTUs delivered shall have the capability to accommodate additional I/O
modulestoexpandtheoverallpointcountoftheRTUbyaminimumoffiftypercent (50%) i.e. 80%
more than the actual pointcount defined in the BOQ. The I/O modules
heremeansStatusInputmodule, AnaloginputmoduleandtheControl
outputmodule.Othermodules,suchasprocessormodule,racksetc.asrequiredto
meettheoverallexpandabilityrequirementdefinedaboveshallalsobesuppliedby thecontractor.
1.23RTUandSICpanels
TheContractorshallprovideRTU&SystemInterfaceCabinet(SIC)panels.TheSIC shall primarily
house all MFTs, interposing control relays and interface terminal blocks.
Generally,theSICshallbemountedadjacenttotheRTUpanel.However,in
somecases,theSICmaybemountedseparatelyatadifferentlocations.AllRTU
signalsshallbeconnectedtotheMFTs,interposingrelays,andfieldsignalsinthe
interfacecabinet.Thepanelsshallmeetthefollowingrequirements:
(a) Shallbefree-standing,floormountedandheightshallnotexceed2100 mm.
Page16of27
(b) Shallhavemaintenanceaccesstothehardwareandwiringthroughlock-
ablefullheightdoors.
(c) Shallhavetheprovisionsforbottomcableentry
(d) The safetygroundshallbe isolatedfromthesignalgroundandshallbe
connectedtothegroundnetwork.Safetygroundshallbeacopperbus bar.
Thecontractorshallconnectthepanel’ssafetygroundofto the
Employer’sgroundingnetwork.Signalgroundshallbeconnectedto the
communicationequipmentsignalground.
(e) Allpanelsshallbesuppliedwith230Vac,50Hz,single-phaseswitchand
15/5Aduplexsocketarrangementformaintenance.
(f) Allpanelsshallbeprovided withaninternal maintenance lamp, space
heatersandgaskets.
(g) Allpanels shallbeindoor, dust-proof withrodent protection, andmeet
IP41classofprotection.
(h) Thereshallbenosharpcornersoredges.Alledgesshallberoundedto preventinjury.
(i) DocumentHoldershallbeprovidedinsidethecabinettokeeptestreport,
drawing,maintenanceregisteretc.
(j) All materials used in the enclosures including cable insulation or
sheathing,wiretroughs,terminalblocks,andenclosuretrimshallbemade
offlameretardantmaterialandshallnotproducetoxicgassesunderfire conditions.
1.24Interconnections
AllcablingbetweencomponentunitsoftheRTU,RTUtointerfacecabinet,RTUto MFTsandto the
Employercontrolandrelaypanels(locatedin thesubstationcontrol room)shallbe
suppliedandinstalledbytheContractorandshallbe shownon Contractorsupplieddrawings.Plug-
typeconnectorswith captivefastenersor compressiontypeconnectorsshallbeused forall
internalinterconnections.The
connectorsshallbepolarizedtopreventimproperassembly.Eachendofintercon-
nectioncablesshallbeidentifiedbyamarkerwhichincludesthecablenumberand the identifying
number and location of each of the cable's terminations. This
informationshallmatchwiththeContractor'sdrawings.
Adequatespaceandhardwareshallbeprovidedforroutingofthefieldwiringwithin theenclosures.
Contractor wiringwithinenclosures shallbeneatlyarranged and shallnotbedirectlyfastened
totheenclosure frame. Allinternal interconnectionwiringandcablesshallbe
routedseparatelyfromfieldwiringtothe RTUterminals&powerwiring.All wiring
shallusecopperconductorsandhaveflameretardant insulation.Conductorsinmulti-
conductorcablesshallbeindividuallycolourcoded.
Page17of27
Theuseofnon-flammable, self-extinguishing, plastic wiretroughs ispermissible. Metal clamps
must have insulating inserts between the clamps and the wiring. Wiringbetweenstationaryand
movablecomponents,suchas wiringacrossdoor
hingesortocomponentsmountedonextensionslides,shallallowforfullmovement
ofthecomponentwithoutbindingorchafingofthewiring.
1.25Wiring/Cablingrequirements
Shielded(screened)cablesshallbe usedforexternalCablingfromtheRTU/SIC panels. These
externalcables (except communication cables) shall have the followingcharacteristics:
a) Allcablesshallhavestrandedcopperconductor.
b) Minimum corecross-section of2.5mm2
forPTcables,4mm2
forCT cablesand2.5
mm2
forPower& Controloutputsand1.5mm2
forDigital
Statusinputs,transducermAcurrentoutput
c) RatedvoltageUo/Uof0.6/1.1KV
d) Externalsheathingofcableshallhaveoxygenindexnot lessthan29 &temperature indexnot
less than 250. Cable sheathshall meet fire resistancetestasperIS1554Part-I.
e) Shielding,longitudinallylaidwithoverlap.
f) Dielectricwithstand2.5kVat50Hzfor5minutes
g) External markingwith manufacture's name, type, core quantity, cross-
section,andyearofmanufacture.
TheCommunicationcableshallbeofshielded,twistedpairsandofminimum0.22sq mmsize.
1.26TerminalBlocks
Terminalblocksshallbe havingprovisionfor disconnection(isolation),withfull-depth
insulatingbarriersmadefrommouldedself-extinguishing material.Terminalblocks
shallbeappropriately sizedandratedfortheelectricalcapacityofthecircuitand wireused.No
morethantwowiresshallbeconnectedto anyterminal.Eachanalog
inputsignal,digitalstatusinputanddigitaloutputsignalsshallrequiretwoterminals
perpointplusacommonshieldterminationforeachcable.
Allterminalblocksshallbesuitablyarrangedforeasyidentification ofitsusages such as CT circuits,
PT circuits, analog inputs, status inputs, control outputs,
auxiliarypowersupplycircuits,communicationsignalsetc.
TerminalBlocksfor CTcircuitsshallhavefeaturefor CTshorting(on
CTside)&disconnection(fromloadside)tofacilitatetestingbycurrentinjection.Similarly,TBs for
PTcircuitshallhavefeaturefor disconnectionto facilitatevoltageinjectionfor testing.
Page20of29
1.27RTUArchitecture
BidderhastheoptiontoofferRTUshavingfollowingarchitecturaldesign:
a) CentralizedRTUdesignwhereallI/OmodulesarehousedinRTUpanels
andcommunicatingwithmasterstationthroughcommunicationport.
b) DistributedRTUdesignwhereI/Omodulesarehousedinrespectivebay
C&Rpanels.AllthesedistributedI/O modulesshallbe connectedtoa central
processorfor further communication with master station. The
biddershallassestherequirement ofRTU/SIC panelsforsuchdesign
andsupplypanelsaccordingly.
1.28Transducer&WeatherSensorRequirements
Alltransducersshallusea48Vdcauxiliarypowersupplyasprovided fortheRTU.
Alltransducersshallhaveamaximumpowerconsumptionof10watts.
1.28.1 TransducerProtection
Theinput,outputandauxiliarycircuitsshallbe isolatedfromeachotherandearth
ground.Thetransduceroutputshallbeungroundedandshallhaveshortcircuitand
opencircuitprotection.Thetransducersshallcomplytothefollowingrequirements,
inadditiontotherequirementofIEC60688,withoutdamagetothetransducer:
(a) ElectromagneticCompatibility:IEC61000-4-3,Level1 (b)
ElectromagneticCompatibility:IEC61000-4-4,Level1
(c) ShockResistance:Minimumseverity50A,IEC68-2-27requirements
(d) VibrationStrength:Minimumseverity55/05,IEC68-2-6requirements.
(e) Input CircuitConsumption:Less than 0.5 VA for voltage and current circuits.
1.28.2 Multi-FunctionTransducers(MFTs)
Thecontractorshallprovidethemulti-functiontransducersforacquiringtherealtime
analoginputsthrough3phase4wireCT/PTscircuits.Themulti-functiontransducer
shallbedesignedfornominal110V (Ph-Phvoltage)and1A/5A(perphasecurrent). TheMFTshallbe
suitablefor 20%continuousoverloadandshallbeableto
withstanding20timesthenormalcurrentratingforaperiodonesecond.TheMFT
shallbeabletoaccepttheinputvoltagesupto120%ofthenominalvoltage.The
MFTsshallhavelowVAburden.TheseMFTsshallbemounted intheinterface cabinettobesuppliedby
thecontractor.
Mutlifunction transducers shall provide at least the following parameters as a
minimumwiththespecifiedaccuracies.
Page21of29
Sl.No.Parameters Accuracy
(i) Voltage ±0.5%
(ii) (iii)
Current
Frequency
±0.5%
± 0.2%
(iv) (v)
ActivePower/Reactivepower
Import&ExportEnergy(active/reactive)
±0.5%/ ±1%
±1%/± 2%
(vi) PowerFactor(measuringrangeshallbe0.6to1.0lag&lead)
Theparameterstobeacquiredfrommultifunctiontransducersshallbeselectable.
MFTshallprovidethe15 minutevalues(configurable15 minute/1hour)ofActive
EnergyImport,ActiveEnergyExport,ReactiveEnergyImportandReactiveEnergy Export.
Multi functiontransducers shall accept nominal -48 V DC (positive earthed) as auxiliary power
supply. Multi functiontransducer shall be provided with RS485
interfacetocommunicatewithRTUoverModbus/103protocolinmulti-dropmode.
TheMFTs shallbesuitable formounting onDINrails. TheMFT terminalsshall
acceptuptotwo2.5mm2
/4 mm2
forPT/CTcircuitterminationsasapplicable.
1.28.3 TransformerTapPositionTransducer
Theexistingtransformertappositionindicationsareoftwotypes.(i)
Variableresistancetype
(ii) Lamptype
TheContractorshallprovidesuitableresistancetappositiontransducerswhichshall
havethefollowingcharacteristics
(a) Theinputmeasuringrangesshallbefrom2to1000ohmsperstep,which
istuneableatsitewithatleast25steps.
(b) Dualoutputsignalof4to20mADC,0.5%accuracyclassasperIEC688 shall beprovided.
One outputwill be used for driving a local digital
indicator(tobeprovidedbythecontractor)andtheotherwillbeusedfor
interfacingwiththeRTU.
(c) In case of lamp type, additional resistance/potentiometer unit shall be provided to
convert the dry type contacts to a variable resistance as
definedin(a)above,suitablefortheremoteindication.
1.28.4 WeatherSensors
AllweathersensorsshallbemaintenancefreeandofIndustrystandarddesign.The
designofsensorsshallpermitcalibrationonsite.Thesensingmechanismshallbe
ruggedenoughtoavoidfrequentrecalibration.
The sensor,supportstructureshallhave built-inprotectionagainstlightning stroke/electricalsurges.
Page22of29
Theoutputofallthesensorsexceptrainfallsensorshallbe4to20mA at0-500 ohmimpedance.
Theoutputofrainfallsensorshallbeintheformofpotentialfreecontactandit’s closure shall be
accumulated (over aconfigurable time period) and reported at master station through RTU. The
sensorsshall be located in open and in the
electricalenvironmentsuchas400KVEHVoutdoorstations.Theequipmentoffered
shouldbesuitableforsatisfactoryoperationinaboveenvironment.
1.28.4.1 AirTemperatureSensor
Sensor : AirTemperatureSensor
Output : Asperspecification1.29.4
TemperatureRange : -5 oC to+60
oC
Resolution : 0.1oC
Accuracy : <0.5 oC orbetter
RadiationShield : RadiationShieldmadeofweather
resistant materialand suitable to sensor used.
1.28.4.2 RelativeHumiditySensor
Sensor : RelativeHumiditySensor
Output : Asperspecification1.28.4
Range : 0to 99%
Resolution : 1%
Accuracy : 3%or better
RadiationShield : RadiationShieldmadeofweatherresistant
materialandsuitableto sensorused.
OperatingTemperature : -5 o
C to+60o
C
Range
Note: TheAirTemperature andRelative Humidity sensors maybesupplied ina
singleenclosureorseparately.
1.28.4.3 RainfallSensor
Sensor : TippingBucketRainGauge
Output : Asperspecification1.29.4
Capacity/Range : Unlimited
Page23of29
Resolution : 0.2mmpertipor better
Accuracy : 4%
CollectingArea : Minimum200sq.mm
OperatingTemperature : -5 o
C to+60o
C
1.28.4.4 WeatherSensorInstallationRequirement
Theweathersensorshallbesuppliedalongwithnecessaryaccessories(e.g.tripod,
stand,clampsetc.)forinstallation/fixingofsensors,signal/powercablesetc.aspart
ofweathersensorsstation.Alltheaccessoriesshallbemadeofstainlesssteelor other suitable material
having sufficient mechanical strength and corrosion
resistancetowithstandatmospherictemperature,pressure,windspeedandrelative humidityupto
theworkingrange(MinimumtoMaximum)ofsensorsforthese parametersasdefined.
The Employer will prefer toinstall the sensors on roof top of substationorotherbuilding.
Themountingarrangementforallthesensors shallbedesignedsuitablyforinstallationontherooftop.
1.29PortableConfigurationandMaintenanceTerminal(PCMT)
ContractorshallsupplyaPortableConfigurationandmaintenanceTerminal(Laptop
PC)whichshallprovidefollowingscapabilities:
(a)RTUDatabaseconfiguration&Maintenance
(b)LocalOperatorInterface&RTUDiagnostics
(c)MasterStationandRTUsimulatorcumprotocolanalyzer
(a)RTUDatabaseconfiguration
TheRTUdatabase Configurationsoftware beingsupplied withthePCMTshall
havethefollowingfeatures
i) FullgraphicswindowsUserInterface
ii) Standardeditingcapabilitiese.g.cut,paste,copy,sortingetc.
iii)Capable ofcontrolling revisions of various RTU database files and
storingmultipleversionsofdatabasesforalltheRTUs.
iv)CapableofuploadingdatabasefromtheRTUandcomparethatwith
anotherversionofdatabasestoredinthePCMT.
v) Provide standardtemplate for database modellingrequired for I/O
modules,MFTs&IEDs,communicationsetting.
vi)Provide mapping of the individual data points acquired from one protocol
toanotherprotocolfortransmission.
Page24of29
The database configuration software shall usethe same terminology for
configurationofthevariousprotocolparametersasspecifiedinthecommunication
protocolstandardi.e.it shallbepossibletodefinetheseparametersby theuser discreetly. Also it shall
be possible to select an ASDU type to be used for
transmissionofameasurande.g.measuredvaluetobetransmittedasASDU9or ASDU11.
(b)LocalOperatorinterfaceandRTUdiagnostics
TheLocalOperatorinterfacesoftwareshallsupportoperatorinquiriesto demand
currentstatusanddatavaluesof variousRTUpoints,or anoverallsubstationsnap-
shot,orofthestatuschangebuffer.
Thelocaloperatorinterfacesoftwareshallprovidethefollowingreports:
i) Status Reports:Display ofallsubstation status indications, of alltele-
meteredvalues,andtheRTU'sstatus.
ii) EventReport:DisplayallthestoredeventsintheeventbufferoftheRTU.
iii) Print Request: Provide user interface for requesting print out of the
ReportsontheLogger
iv) Maintenanceactivities:Userinterfaceforinteractingwiththe
RTUformaintenanceactivitieslikediagnostics,databaseonlinerequests.
The RTU shall have inbuilt features for monitoring the healthiness of the RTU
modulesanddetectingthe typeoferror.Thediagnosticssoftwareshallhave
diagnosticsfortheRTU'sprocessor(s),memory,I/Oports,andanyotherfunctional
areasoftheRTU.Itshalllisttheerrorsrecordedby theRTUandprovide
troubleshootingtoolsfortheRTU.
(c) Masterstation-cum-RTUsimulator&protocolanalyzersoftwaretool
TheMasterstationandRTUsimulatorcumProtocolAnalysersoftwareshallbeused to
monitorandtesttheRTU'soperationusingthe masterstationcommunication
protocol.Itshallhavethefollowingfeatures
i) capableofemulatingboththemasterstationandtheRTUmessagesin
thecommunicationprotocols(IEC60870-5-101,104&MODBUS/103). When the
Master station and RTU simulator cum Protocol Analysersoftwarehasreceivedor
transmitteda message,itshallbe possibleto
immediately"turnaround"andtransmitorreceivearesponsemessage.
ii) capabilityofinterfacingtodigitalsideoftheRTUfortheabovepurpose.
iii) capable ofreceiving singleandrepeated messages usingthesupplied
RTUcommunicationprotocol.Eachreceivedmessageshallbechecked for validity,
including the checksum code. The messagesshall be
displayedinHEXformatorinthe‘interpretedform’asdesiredbytheuser.
Page25of29
Itshallmaintainanddisplayerrorcounterssothatthenumberoferrors
duringaperiodofunattendedtestingcanbeaccuratelydetermined.
iv) capable of formatting and transmitting, both as one-time and periodic
transmissions,anymasterstation-to-RTUcommand.
v) capableof preparingillegalmessages,suchasmessageshavinginvalid
checkcodes,fortransmission.
TheMasterstationand RTUsimulatorcumProtocolAnalysersoftwareshallalsobe
capableofpassivelymonitoringallcommunicationtrafficonachannelwithoutinter-
feringwithchanneloperation.
Channel traffic captured in the active or passive modes of operation shall be
displayed.Allfieldsofa messageshallbedisplayed.A pass/failindicationforthe
securitycheckcodeshallbeincludedwitheachcodedisplayed.
1.30 TESTING
1.30.1 RTU/SICTesting
(a) TypeTesting
A completeintegratedoffered unitmust be fully type tested toassurefullcompliancewiththe
functionalandtechnicalrequirementsoftheSpecification.Thetestingsampleshall
includeatleastoneofeachtypeofcards/modules anddevices. Photocopy of such type test
reports/certificates must be submitted along with the tender bid. The type test certificates of
prototype manufactured and tested by foreign collaborators of the tenderers at their works shall
not be acceptable for indigenously manufactured equipment.ThelistofType tests to be performed
on the RTU/SIC is mentioned in Table-2 &type test requirementsarementionedinTable-3.
Bidder shall quote price for type tests as per Schedule of type test charges so that the same can be
carried out as per option of WBSETCL. This price shall be considered for the purpose of
evaluation of bid. However, if type test reports of any type test/tests is/are not submitted by the
proposed sub-vendor carried out within last 5 (five) years, the same shall be conducted in
presence of WBSETCL representative at vendor’s cost. This cost shall be inclusive of Fooding
and lodging cost of WBSETCL representatives (min two persons).
Further, type test reports for transducers and relays shall be submitted as per relevant
standards. All weather sensors shall be calibrated as per Indian
MetrologicalDepartmentstandardsandcertificateshallbesubmittedinthisregard.
(b) RoutineTesting
Eachcompleteunitshallundergoroutinetesting.ThelistofRoutineteststo be
performedinthefactoryismentionedinTable-2.
(c) FieldTests
Page26of29
AfterRTU/SICpanelinstallationand interfacecablingwith C&Rpanelsand
communicationequipment,theContractorshallcarryoutthefield-testing.Thelistof
fieldtestsismentionedinTable-2.
(d) AvailabilityTests
Afterfieldtesting,RTU/SICshallexhibit98%availabilityduringtestperiodof500
hours.AvailabilitytestsshallbeperformedalongwithMasterstation.TheRTU/SIC shall be considered
available only when all its functionality and hardware is operational.Thenon-
availableperiodduetoexternalfactorssuchasfailureofDC powersupply,communication
linketc.,shallbetreatedashold-time&availability testdurationshallbeextendedbysuchholdtime.
Table-1:TechnicalParticularsofRTU
Sl.
no.
ItemDescription
Value
Remarks
1
Datatransmissionrate
300 to 9600 bps for
serial port &
10/100 Mbps for
Ethernetport.
Configurable
2
Communicationports
Minimum8Ports
• 2 Ethernetport for
comm.with master
stations on 104 &IEDs
on 61850 and
alsoforconfiguration. • 2 RS232ports –for
comm.with master
stationson101. • 1 Port– for RTU
configuration
&Maintenancetool • 1portforLDMSand
localLogger • 2 RS 485 ports for polling
MFTs/Energy Meters
3
Communicationprotocolwith
Masterstations
IEC60870-5-101/
104
4
CommunicationProtocolwith
LDMS
IEC60870-5-101/
104
5
CommunicationProtocolwith
MFTs
MODBUS/103
Page27of29
6
CommunicationProtocolwith
IEDs
IEC61850
7
StatusdatatransfertoMaster station
byexception
8
AnalogdatatransfertoMaster station
Normally Periodic
Formajorchange
–byexception 9
No.ofScanGroupssupported
16
10
SeparateLogicalDatabasefor
eachMasterStation
11
RTUshallbeabletocapture
contactoperations
of20msormore
duration.
12
SOEbuffersize
atleast600
events
13
Timestampingaccuracyfor
SOE
1ms
14
SupportingControlofDevices
Twostate&OLTCc
apacitors
15
DownloadingofRTU
databasefrommasterstation
Supported
16
RTUinternalclockstability
Atleast1ppm
17
NominalPowersupplyvoltage
48VDC
18
Compliancetocl.1.29.1–
TransducerProtection
Page28of29
Table-2:ListofTestsonRTU/SIC
Test
Nos.
DESCRIPTIONOFTHETEST
Typetest
Routine
test
Field
test
FUNCTIONALTESTSFORRTU/SIC
1. CheckforBOQ,Technicaldetails,Construction &Wiringas
perRTU/SICdrawings
√ √ √
2. CheckforRTUdatabase&configurationsettings √ √ √
3. Check
theoperationofallAnaloginputs,Statusinput&Controloutput
pointsofRTU/SIC
√ √ √
4. CheckoperationofallcommunicationportsofRTU √ √ √
5. Checkforcommunicationwithmasterstationsormaster
stationsimulatorforRTU/RTU
√ √ √
6. TestfordownloadingofRTUdatabasefromMasterstation √ √ √ 7. TestforRTUtimesynchronizationfromMaster √ √ √
8.
TestPowerSupplyVoltageMargin,RippleLevelsandShort
CircuitProtection
√ √ (except
short circuit
protection)
9. TestforRTUoperationwithDCpowersupplyvoltagevariation √ √
10. CheckforautorestorationofRTUonDCpowerrecoveryafter
itsfailure
√ √ √
11. TestforRTU/FRTUdiagnosticfeature √ √
12. TestforRTUSOEfeature √ √ √ 13. RTUAnalogaccuracytestforanaloginput √ √ √
14. Transduceraccuracytest √ √
15. TestforIEC60870-5-104,61850&Modbusprotocol
implemented
√ √
16. TestforRTUinternalClockstability √ √ 17. TestforRTUNoiselevelmeasurement √ 18. TestforControlSecurityandSafetyforControloutputs √ √
19.
Otherfunctionaltestsaspertechnicalspecification
requirements
√ √
20.
Endtoendtest(betweenRTU&Masterstation)forall
I/Opoints
√
EMI/EMCIMMUNITYTESTSFORRTU/FRTU 21. SurgeImmunityTestasperIEC60870-2-1 √
22. ElectricalFastTransientBurstTestasperIEC-60870-2-1 √ 23. DampedOscillatoryWaveTestasperIEC60870-2-1 √ 24. ElectrostaticDischargetestasperIEC60870-2-1 √
25. RadiatedElectromagneticFieldTestasperIEC60870-2-1 √ 26. DampedOscillatorymagneticFieldTestasperIEC-60870-2-1 √
27. PowerFrequencymagneticFieldTestasperIEC-60870-2-1 √ INSULATION TESTFORRTU/FRTU
28. PowerfrequencyvoltagewithstandTestasperIEC60870-2-1 √
29. 1.2/50µsImpulsevoltagewithstandTestasperIEC60870-2-
1
√
30. Insulationresistancetest √ ENVIRONMENTAL TESTFORRTU/FRTU
31. DryheattestasperIEC60068-2-2/2-3 √
32. Dampheat testasperIEC60068-2-78 √
33. ColdTestasperIEC60068-2-1 √
Note:TestlevelsforabovetypetestsareelaboratedinTable3
Page29of27
Table-3:RTUTypeTestRequirements
Test
Nos
.
TestName EUT
Status
Test
Level
PowerSupply
Points
I/O
Points
Passing
Criteria CM DM CM
1 SurgeImmunityTest ON Level
3
2kV 1kV 2kV A
2 ElectricalFast
TransientBurstTest
ON Level
3
2KV - 1kV A
3 DampedOscillatory
WaveTest
ON Level
3
2.5kV 1kV 2.5kV A
4 Electrostatic
DischargeTest
ON Level
3
+/-6 kVinContactdischarge
mode or+/-8kVinAir
dischargemode
A
5 Radiated
ElectromagneticField
Test
ON Level
3
10V/melectricfieldstrength A
6 DampedOscillatory
MagneticFieldTest
ON Level
3
30A/m at1MHzofmagnetic
fieldstrength
A
7 Powerfrequency
magneticfield
ON Level
3
30A/mofmagneticfieldstrength
(Continuousdurationsinewave)
A
8 Powerfrequency
voltagewithstand
OFF - 1KVrmsfor1 minute Nobreak
downor
flashover
shall
occur 9 1.2/50µsimpulse
voltagewithstand
OFF -
2kVp
Nobreak
downor
flashover
shall
occur 11 InsulationResistance
Test
OFF - Measure Insulation resistance
using500VDC Meggerbefore
&after Power Freq&Impulse
voltagewithstandtests
Asper
manufact
urer
standard 12 Dryheattest ON - Continuous operation at 550 C
for16hrs 0
13 Dampheattest ON - at95%RHand400Cfor16hrs 0 14 Coldtest ON - Continuousoperationat00Cfor
96hrs 0
Note:-
1. EUT -EquipmentUnderTest
2. CM -CommonMode;DM-Differentialmode
3. I/OpintsdonotincludeCommunicationports
4. PassingCriteria
0-nofailure:normalperformancewithinthespecifiedlimits
A:minorfailure:temporarydegradationorlossoffunctionorperformancewhich isself-recoverable
5. Functionaltestasperthesl.nos.1-18ofTable-2shallalsobedoneduringtype testing.