JULY 2014 I NEW ZEALAND Technical Specification

Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

JULY 2014 I NEW ZEALAND

Technical Specification

Page 2: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 3

6 STRIACLADDINGINSTALLATION 76.1 General 76.2 FasteningMethods 76.3 FastenerDurability 7

7 JOINTS 87.1 VerticalJoint 87.2 HorizontalJoint 87.3 InternalCornerJoint 87.4 ExternalCornerJoint 8

8 FINISHES 88.1 Painting 88.2 FlexibleSealant 8

9 STORAGEANDHANDLING 8

10 MAINTENANCE 8

11 PRODUCTINFORMATION 911.1 ManufacturingandClassification 911.2 ProductMass 911.3 Durability 9

12 SAFEWORKINGPRACTICES 10

13 PRODUCTANDACCESSORIES 11

14 DETAILS 13

PRODUCTWARRANTY 35

1 APPLICATIONANDSCOPE 31.1 Application 31.2 Scope 31.3 Details 31.4 SpecificDesign 3

2 DESIGN 32.1 Compliance 32.2 Responsibility 32.3 SiteAndFoundation 32.4 Clearances 32.5 MoistureManagement 42.6 Structure 42.7 FireRatedWalls 42.8 StructuralBracing 42.9 EnergyEfficiency 4

3 FRAMING 53.1 General 53.2 TimberFraming 53.3 SteelFraming 53.4 SpecialFramingRequirements 53.5 Tolerances 5

4 PREPARATION 54.1 BuildingUnderlay/HomeRABPreCladLining 54.2 RABBoard 64.3 CavityClosure/VentStrip 64.4 Flashings 64.5 JunctionsandPenetrations 6

5 BATTENINSTALLATION 65.1 CLDStructuralCavityBatten 65.2 CLDStructuralCavityBattenFixing 65.3 BattenFasteners 65.4 IntermediateSupport 7

Contents

WEVALUEYOURFEEDBACKTocontinuewiththedevelopmentofourproductsandsystems,wevalueyourinput.Pleasesendanysuggestions,includingyourname,contactdetails,andrelevantsketchesto:

Ask James HardieTM [email protected]

Page 3: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 3

1.1 APPLICATIONStria®Claddinginstalledasperthisspecificationgivesapanelisedplasteredmasonryappearanceonbuildingfacades.StriaCladdingcanbefixedtoeithertimberorlightweightsteel-framedexternalwalls.Awiderangeofcolourscanbeusedvaryingfromlighttodark.StriaCladdingisavailablein405mmwidex4200mmlengthsandis14mmthick.

If you are a specifierOrotherresponsiblepartyforaprojectensurethattheinformationinthisdocumentisappropriatefortheapplicationyouareplanningandthatyouundertakespecificdesignanddetailingforareaswhichfalloutsidethescopeofthesespecifications.

If you are an installerEnsurethatyoufollowthedesign,moisturemanagementandassociatedfiguresandmaterialselectionprovidedbythedesignerandthisJamesHardieTechnicalSpecification.Allthedetailsprovidedinthisdocumentmustbereadinconjunctionwiththeprojectspecification.

Make sure your information is up to dateWhenspecifyingorinstallingJamesHardieproducts,ensurethatyouhavethecurrentmanual.Additionalinstallationinformation,warrantiesandwarningsareavailableatwww.jameshardie.co.nzorAskJamesHardie™on0800808868.

1.2 SCOPEThisspecificationcoverstheinstallationofStriaCladdingonbuildingsthatfallwithinthescopelimitationofNZS3604andE2/AS1oftheNewZealandBuildingCode(NZBC).

ThisspecificationalsocoverstheinstallationofStriaCladdingonprojects,whicharesubjecttospecificengineeringdesign(SED)uptoawindpressureof2.5kPa(ULS).

Thistechnicalspecificationisintendedforusebyarchitects,designersandspecifierswhomaybeinvolvedwiththespecificationofStriaCladdinganditsinstallation.Thisdocumentmustbereadinconjunctionwiththeprojectspecificdrawingsandspecifications.Thespecifierorotherresponsiblepartyfortheprojectmustensurethattheinformationanddetailsinthisspecificationisappropriatefortheintendedapplicationandthatyouundertakespecificengineeringdesignanddetailingforareas,whichfalloutsidethescopeofthesespecifications.

Note:RefertoStriaCladdingTimberCavityBattentechnicalspecificationwhenfixingtotimbercavitybattens.

1.3 DETAILSVarioustypicalStriaCladdingconstructiondetailsareprovidedintheDetailssectionofthisdocument.ThesedetailsareavailableinCAD,ArchiCAD,MODandpdffileformatandcanbedownloadedfromourwebsiteatwww.jameshardie.co.nz.

Alldimensionsshownareinmillimetresunlessnotedotherwise.

1.4 SPECIFIC DESIGNForuseoftheStriaCladdingonspecificdesignprojects,thedesigner,architectorengineermustensurethatallclausesofNZBChavebeenconsideredandaspecificdesignhasbeenundertakenfortheareaswhichfalloutsidethescopeofthisliterature.

2 Design2.1 COMPLIANCEStriaCladdinginstalledinaccordancewiththisspecificationhasbeentestedasperE2/VM1andcomplieswithExternalMoisture-E2ClauseofNZBC.ThecladdinghasalsobeentestedandcomplieswiththerequirementsofStructure-B1,Durability-B2,EnergyEfficiency-H1andHazardousBuildingMaterial-F2ClausesofNZBC.

2.2 RESPONSIBILITYThespecifierorotherpartyresponsiblefortheprojectmustensurethattheinformationanddetailsinthisspecificationareappropriatefortheintendedapplicationandthatadditionaldetailingisperformedforspecificdesignoranyareasthatfalloutsidethescopeofthistechnicalspecification.Forapplicationsoutsidethescopeofthisliteratureanddetails,whicharenotprovidedherein,thearchitect,designerorengineermustundertakespecificdesignanditshouldbeensuredthattheintentoftheirdesignmeetstherequirementsoftheNZBC.

AllNewZealandStandardsreferencedinthismanualarecurrenteditionsandmustbecompliedwith.

JamesHardieconductsstringentqualitycheckstoensurethatanyproductmanufacturedfallswithinourqualityspectrum.Itistheresponsibilityofthebuildertoensurethattheproductmeetsaestheticrequirementsbeforeinstallation.JamesHardiewillnotberesponsibleforrectifyingobviousaestheticsurfacevariationsfollowinginstallation.

2.3 SITE AND FOUNDATIONThesiteonwhichthebuildingissituatedmustcomplywithE1/AS1SurfaceWaterClauseofNZBC.

Foundationsdesignmustcomplywithrelevantregulations,standardsandmeettherequirementsofNZBC.

Thegradeofadjacentfinishedgroundmustslopeawayfromthebuildingtoavoidanypossibilityofwateraccumulation.

2.4 CLEARANCESTheclearancebetweenthebottomedgeandpaved/unpavedgroundofcladdingmustcomplywithsection9.1.3ofE2/AS1.Thefinishedfloorlevelmustalsocomplywiththeserequirements.Theseclearancesmustbemaintainedthroughoutthelifeofthebuilding.

1 Application and scope

Page 4: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 5

StriaCladdingmustoverhangthebottomplatebyaminimumof50mmasrequiredbyE2/AS1.

StriaCladdingmustmaintainaminimumclearanceof100mmfrompavedground,and175mmfromunpavedground.Ontheroofsanddecks,theminimumclearancemustbe50mm.

Donotinstallexternalcladdingsuchthatitmayremainincontactwithwaterorground.ReferFigures3and4.

2.5 MOISTURE MANAGEMENTItistheresponsibilityofthespecifiertoidentifymoisturerelatedrisksassociatedwithanyparticularbuildingdesign.

Wallconstructiondesignmusteffectivelymanagemoisture,consideringbothinteriorandexteriorenvironmentsofthebuilding,particularlyinbuildingsthathaveahigherriskofwinddrivenrainpenetration.Thebuildingsshouldalsobeventilatedsufficientlytocontrolmoistureaccumulationduetocondensationespeciallyinartificiallycooled/heatedbuildings.

WallsshallincludethoseprovisionsasrequiredbyExternalMoistureClauseE2/AS1ofNZBC.Inaddition,allwallopenings,penetrations,junctions,connections,windowsills,headsandjambsmustincorporateappropriateflashingsforwaterproofing.Theothermaterials,componentsandinstallationmethodsusedtomanagemoistureinexternalwalls,mustcomplywiththerequirementsofrelevantstandardsandtheNZBC.Forfurtherguidanceondesigningforweathertightness,refertoBRANZLtd.andtheDepartmentofBuildingandHousingupdatesonthefollowingwebsitesrespectively,www.branz.co.nzandwww.dbh.govt.nz.

Inaddition,thefollowingissuesmustalsobeconsidered:

• Sealant must be installed where detailed in this literature.

• Where the walls are higher than two storeys, it is necessary to provide a horizontal flashing at the second floor level to drain the cavity.

• The installation of smoke chimneys, pipe penetrations and other fixtures etc. must not track moisture into the wall or restrict the drainage of moisture to the exterior.

2.6 STRUCTURE2.6.1 Timber FramingTimber-framedbuildingsmusteitherbedesignedinaccordancewithNZS3604(TimberFramedBuildings)orasperspecificengineeringdesign.Forabuildingrequiringaspecificengineeringdesign,theframingstiffnessmustbeequivalenttoormorethanthestiffnessrequirementsofNZS3604.

Forspecificdesignprojects,thetimberframingmustbedesignedinaccordancewithNZS3603andAS/NZS1170.

2.6.2 Steel FramingSteel-framedbuildingsmustcomplywiththerequirementsofAS/NZS3404‘SteelStructuresStandard’orspecificengineeringdesignrequirements.AlsorefertoNASHsteelframedbuildingsguidancedocumentpublishedby‘NationalAssociationofSteelHousing’(NASH).

2.6.3 Wind PressuresStriaCladdingissuitableforuseinallNewZealandwindzonesuptoandincludingEHasdefinedinNZS3604.

StriaCladdingcanbeusedforspecificdesignprojectsuptowindpressuresof2.5kPauls.

2.7 FIRE RATED WALLSAfireratingofupto60minutescanbeachievedwhenusingRAB®BoardinlieuofabuildingunderlayandinstallingStriaCladdingasperthisspecification.RefertoJamesHardieFireandAcousticDesignManualforfurtherguidanceonachievingfireratings.

2.8 STRUCTURAL BRACINGStriaCladdinginstalledasperthisspecificationcannotachieveanystructuralbracing.BracingcanbeachievedbyusingRABBoardinstalleddirecttoframinginsteadofabuildingunderlayorbyusingVillaboard®Liningbracingsystemontheinternalface.

2.9 ENERGY EFFICIENCYExternalwallsconstructedusingStriaCladdingandbulkinsulation,wheretheareaofglazingis30%orlessofthetotalwallarea,constructedasperthistechnicalspecificationcomplieswiththeinsulationrequirementsforwallsinNZBCAcceptableSolutionH1/AS1(EnergyEfficiencyClauseH1),ReplacementTable1.Tomeetthermalinsulationrequirementsfortheconstruction,thebulkinsulationasspecifiedinTable1mustbeused.ThisinsulationmaybesubstitutedwithinsulationshavinghigherR-values.Thethermalinsulationofawallchangeswhenthesizeorspacingoftimberframingisincreasedordecreased.ThecalculationusedinTable1isbasedonatimberframingsize90x45mmandusinganinternalliningmaterialsuchasJamesHardieVillaboardLiningora10mmplasterboard.

Table1Insulation capability

Climate Zone*

R-Value Requirement*

Cavity Insulation Infill Requirement

1and2 1.9m2ºC/W #R2.0

3 2.0m2ºC/W #R2.2

TotalconstructionR-Valuedependsontheinsulationmaterialusedandtheframingratio.TheinsulationmaterialR-Valuesspecifiedinthistableareforstudsspacedat600mmc/candnogsspacedat800mmc/c.

#ToachievehigherR-ValuesofconstructionthewallinsulationmaterialmustbereplacedwithaninsulationmaterialhavinghigherR-Valuestosuittherequirements.

Forfurtherguidanceoninsulationrequirementrefertothecurrenteditionof‘HouseInsulationGuide’publishedbyBRANZ.

Page 5: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 5

3 Framing

3.3 STEEL FRAMING3.3.1 Dimensions and GaugeA38mmminimumwidestudcanbeusedtoinstallStriaCladding.Thethicknessofsteelframemustbeintherange0.55to1.6mmBMT(BaseMetalThickness).Consideringtheeaseofinstallation,therecommendedminimumBMTis0.75mm.

3.3.2 DurabilityThesteelframingmusthavetheappropriatelevelofcoatingtopreventcorrosionandcomplywithdurabilityrequirementsofNZBC.

3.3.3 Frame ConstructionSteelframingmustcomplyeitherwithNASH3405orwiththespecificengineeringdesignfortheproject.Studandbattenspacingmustnotbemorethanwhathasbeenspecifiedinthisspecification.Refertoframingmanufacturer’sspecificationsorNASH3405forfurtherguidanceonsteelframe.

3.4 SPECIAL FRAMING REQUIREMENTSThefollowingarespecialframingrequirementsforbothtimberandsteelframing:

• Double studs are required at internal corners, refer Figure 13.

• Extra packers maybe required at external corners.

3.5 TOLERANCESInordertoachievetherequiredperformanceandanacceptablewallfinish,itisimperativethatframingisstraightandtrue.FramingtolerancesshallcomplywithTable2.1ofNZS3604andthemanufacturer’sspecifications.Allframingshallbemadeflush.

4 Preparation4.1 BUILDING UNDERLAY / HOMERAB

PRECLAD LININGBuildingunderlay/HomeRAB®PreClad™LiningmustbeprovidedaspertherequirementsofExternalMoistureClauseE2ofNZBC.ThebuildingunderlayselectedforusemustcomplywithTable23ofE2/AS1.

Thebuildingunderlaymustbefixedinaccordancewithsection9.1.7E2/AS1andunderlaymanufacturer’srecommendations.

Wallswhicharenotlinedontheinsidefacee.g.garagewallsorgableendsmustincludearigidsheathingoranairbarrierbehindthecladdingwhichcomplieswithTable23ofE2/AS1.JamesHardieHomeRABPreCladLiningcomplieswiththeserequirementsandissuitableforuseinthissituation.ItmustbeinstalledinaccordancewithJamesHardieRigidAirBarriersinstallationmanual.

3.1 GENERALStriaCladdingcanbefixedeithertoatimber-frameorsteel-frame.ForfixingintosteelframeAskJamesHardieon0800808868forspecificrequirements.

• Studs must be provided at 600mm centres maximum.

• Nogs must be provided at 800mm centres maximum.

Note: For fixing Stria Cladding, fastener spacing is provided in Section 6.

3.2 TIMBER FRAMING3.2.1 DimensionsA45x90mmminimumframingsizeisrequired.

3.2.2 Structural GradeMinimumtimbergrademustbeinaccordancewithtimbergradesspecifiedinNZS3604.

3.2.3 DurabilityTheexternalframingtimbermustbetreatedtoaminimumH1.2treatment.Highertreatmentlevelsmaybeusedbutcheckforthecompatibilityoftreatmentchemicalswithothermaterials.RefertoNZBCAcceptableSolutionB2/AS1Durabilityforfurtherinformationaboutthedurabilityrequirements.

FortimbertreatmentandallowablemoisturecontentinformationrefertoNZS3602(TimberandWood-BasedProductsforuseinBuildings)andNZS3640(ChemicalPreservationofRoundSawnTimber)forminimumtimbertreatmentselectionandtreatmentrequirements.Alsorefertoframingmanufacturer’sliteratureforfurtherguidanceontimberselection.Framingmustbeprotectedfrommoistureatsitesinaccordancewiththeframingmanufacturerrecommendations.

Note: Refer to NZS 3602 for information about the allowable moisture content in timber framing.

3.2.4 Frame ConstructionUseoftimberframingmustbeinaccordancewithNZS3604andtheframingmanufacturer’sspecifications.Theframingmustberigidandnotrelyonthecladdingforstability.Timberframingsizesanditsset-outmustcomplywithNZS3604andasspecifiedinthistechnicalspecification.

Thefollowingframingisrequired:

• When studs are spaced at 600mm centres maximum, the nogs / dwangs must be provided at 800mm centres maximum

• When studs are spaced at 400mm centres then the nogs / dwangs may be provided at 1200mm centres

• An extra stud is required in internal corners

• For specific design projects exposed to wind speeds higher than 50m/sec, the stud spacing must be closed to 400mm c/c.

Page 6: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

6 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 7

4.2 RAB BOARDGeneralbuildingunderlayorHomeRABPreCladLiningissuitableforuseuptoveryhighwindspeedzone(50m/sec).

Forspecificdesignprojectswherethewindpressureishigherthan1.5kPa,orwhenanEHwindzone,JamesHardieRABBoardmustbeusedinsteadofbuildingunderlay.RABBoardissuitabletowithstandwindpressuresupto4.5kPa.

ToachievethetemporaryweathertightnessusingJamesHardierigidairbarriers,windows/doorscanbetemporarilyinstalled.RefertoJamesHardieRigidAirBarriersinstallationmanualforinformationregardingitsinstallation.

4.3 CAVITY CLOSURE / VENT STRIPTheJamesHardieStriaAluminiumCavityClosureoruPVCcavityventstripmustbeinstalledatthebottomofallwallsconstructedusingthedrainedandventilatedcavityconstructionmethod.Itisimportantthattheopeningsinthecavityclosure/ventstriparekeptclearandunobstructedtoallowfreedrainageandventilationofcavities.JamesHardiecavityclosure/ventstriphasanopeningareaof1000mm2/mlength.

4.4 FLASHINGSAllwallopenings,penetrations,intersections,connections,windowsills,headsandjambsmustbeflashedpriortoStriaCladdinginstallation.RefertomoisturemanagementrequirementsinClause2.5.Thebuildingunderlay/rigidairbarriermustbeappropriatelyincorporatedwithpenetrationandjunctionflashingsusingflashingtapes.Materialsmustbelappedinsuchawaythatwatertracksdowntotheexterioronthefaceofbuildingunderlayorrigidairbarrier.JamesHardiewillassumenoresponsibilityforwaterinfiltrationwithinthewallduetopoorinstallationofflashingsorbuildingunderlay.

TheselectedflashingmaterialsmustcomplywiththedurabilityrequirementsofNZBC.ForinformationrefertoTable20ofE2/AS1.

WhenusingJamesHardierigidairbarrierstheentireframingaroundopeningsmustbesealedwithaflashingtape.Thetapemustbefinishedoverthefaceoftherigidairbarrier.RefertoJamesHardieRigidAirBarriersinstallationmanualforfurtherinformation.

4.5 JUNCTIONS AND PENETRATIONSRefertoClause2.5ofthisspecificationformoisturemanagementrequirements.Allwindowsanddoorsmustbedetailedaspertherequirementsofthisspecification.JamesHardiehasdevelopedthewindowdetailsforStriaCladdingwhichmeettherequirementsofE2ExternalMoisture,anapproveddocumentoftheNZBC.RefertoFigures14to16.

5 Batten installation

5.1 CLD STRUCTURAL CAVITY BATTENSTheCLDStructuralCavityBattenissuitabletohaveStriaCladdingfixedintothem.Thebattensare2450mmlong,70mmwideand19mmthick.Thebattensarefullysealedonallfaces.Refertothedetailsforinformationaboutinstallation.

5.2 CLD STRUCTURAL CAVITY BATTEN FIXING

CLDStructuralCavityBattenmustbefixedtothestudsoverbuildingunderlayorRABBoard.Thebattensareruncontinuouslyoverthestudsbuttheymusthaveagapatthefloorjoistleveltoallowforstructuralshrinkageanddeflectioninjoists.ReferFigure22.

TheCLDStructuralCavityBattencanalsobebuttjointedoverthestudswithinthefloorheight.Thebattenendsmustbecutbetween20°-45°andbeinstalledtodeflectthemoisturetoexterior.Theendsmustbesealedandbuttedusinganadhesivesealantinthejoint,ReferFigure16.

TheminimumframingwidthrequiredtofixCLDStructuralCavityBattenis45mm,referFigure8.AllsitecutendsofCLDStructuralCavityBattensmustbesealedonsitewithDuluxAcraprime501/1sealerorReseneQuickDrybeforeinstallation.RefertoTable2forCLDStructuralCavityBattenspacingandfixingsizeandfixingcentres.

ThedesignermustensurethattheCLDStruturalCavityBattensarenotusedinsituationswheredesignwindpressuresareabove2.5kPa(uls).

CLDStructuralCavityBattensmustnotbeusedtoalengthsmallerthan300mm.

5.3 BATTEN FASTENERSCLDStructuralCavityBattenmustbefixedtothestudswithfastenersasperTable2.Thefastenersmustbedrivenataminimumdistanceof50mmfromthebattenends.

Table2Fixing Type

Wind Pressure (kPa)

CLD Structural Cavity Batten Spacing Max. (mm)

Fixing Centres (mm)

65x2.8mRounDriveringshanknailtotimberframe

Upto1.5 600or400asperframingspacing

250

1.5to2.5 400mm 200

Whenusingarigidairbarrierthebattenfixingmustbeincreasedbyminimumthicknessofrigidairbarrier.

Forfixingintosteelframeofthicknessbetween0.55–0.75mmBMT,use10gx40mmselfembeddingwingteksteelscrewatfixingcentresspecifiedinTable2.Athermalbreakisalsorequiredtobeinstalledoverthesteelframebeforeinstallingthe

Page 7: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

6 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 7

underlay/RABBoard.RefertoBRANZorDBHwebsiteforfurtherguidanceonthermalbreakrequirements.Ensureaminimum15mmpenetrationofscrewintosteelframe.

Forfastenerdurabilityinformation,refertoClause6.3ofthisdocument.

CLDStructuralCavityBattenslessthan400mminlengthmusthavefixingsatmaximum150mmcentres.

5.4 INTERMEDIATE SUPPORTWherestudsareat600mmcentresanintermediatemeansofrestrainingthebuildingunderlayandinsulationfrombulgingintothecavityshallbeinstalled.Anacceptablemethodtoachievethisisusinga:

• 75mm galvanised mesh

• polypropylene tape at 300mm centres fixed horizontally and drawn taut

Nointermediatesupportsarerequiredwhen:

• studs are spaced at maximum 400mm centres

• James Hardie Rigid Air Barriers instead of building underlay are used

6 Stria Cladding installation

6.1 GENERALStriaCladdingandCLDStructuralCavityBattensmustbekeptundercoverwhilstinstorageoratsitesandtheymustbedryatthetimeoftheirinstallation.AllsitecutpaneledgesmustbesealedwithDuluxAcraprime501/1,ReseneQuickDryorsimilarsealercompatiblewiththefinishcoatbeforeinstallation.

StriaCladdingmustbefullysupportedandfixedintoCLDStructuralCavityBattens.Ensurethatcladdingishardagainstthebattenstoavoiddrumminess.

Toacheivebestastheticresultsitisrecommendedtopositionverticaljointerbythecornerofopeningsorcoincidingwiththecentrelineofopenings.

ThistechnicalspecificationonlycoversthehorizontalinstallationofStriaCladding.RefertoJamesHardieforverticalinstallationsupplementofStriaCladding.

6.2 FASTENING METHOD6.2.1 T-Head Nails With AdhesiveThecombinationofstainlesssteelstraightT-headnailsandanadhesivesealantprovidesafastandefficientpanelinstallationmethod.Useminimumofthreenailsperstudforeachpanel.RefertoFigure10.UsePaslode30x1.6mmCSeriesStainlessSteelBradNailsonly.

Applya6mmthickcontinuousbeadofBostik‘SealnFlex1’orSika‘Sikaflex11FC’adhesivesealanttothefaceoftheCLDStructuralCavityBattenpriortofixingStriaCladding.OnlyapplyadhesivesealanttotheCLDStructuralCavityBattenstosuiteachpanelastheStriaCladdingisinstalledonthewall.SeeFigure9fordetails.

Itisagoodpracticetosetthebradnailguntofire2-3mmproudofthepanelsurfacekeepingaconsistentpressureonthepanelwhilefixing.Lettheadhesivesealantgooffforapproximately2hourswhilstcontinuingworkonthenextsectionofwall.Comebacklaterandhammerthenailsflushwithcladdingsurface.

TheedgedistancerequiredforfixingT-headbradnailsis12mm.RefertoFigure6orFigure8.

6.2.2 Window/door openingUsealuminiumwindowjambflashingonwindow/doorjambs.StriaCladdingmustbeinstalledpriortothefinalinstallationofwindows/doors.RefertoFigures17to23forfurtherinformation.

6.3 FASTENER DURABILITYFastenersusedtofixCLDStructuralCavityBattenmustmeettheminimumdurabilityrequirementsoftheNZBC.NZS3604specifiestherequirementsforfixingmaterialtobeusedinrelationtoexposureconditionsandaresummarisedinTable3.

Fastenersmustbefullycompatiblewithallothermaterialsthattheyaretobeincontactwithtoensurethedurabilityandintegrityofassembly.

Forsteelframingensurethatthefastenersusedarecompatiblewithsteelframing.

Contactfastenermanufacturersformoreinformation.

Table3Exposure conditions and nail selection prescribed by NZS 3604

Nail material

ZoneD ZoneCoutsideseaspayzoneandZoneBandgeothermalhotspots

Bracing-allzones

Grade316Stainless

Hot-dippedgalvanisedor316stainless

Grade316Stainless

(Zone C areas where local knowledge dictates that increased durability is required, appropriate selection shall be made).

Microclimate conditions as detailed in NZS 3604, paragraph 4.2.4 require SED.

Also refer to the NZBC Acceptable Solution ‘E2/AS1’ Table 20 and 22 for information regarding the selection of suitable fixing materials and their compatibility with other materials.

Page 8: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

8 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 9

7 Joints

Wherepanelsarefixedwithbradnails,thenailheadsmustbefinishedflushwithpanelsurface.Thenailheadscanbeskimmedoverwithanexteriorgradetwopartbuildersfill,ifrequired.Theskimmedareamustbeprimedpriortopainting.

JamesHardierecommendsaminimumoftwocoatsofexteriorgradeacrylicpaint.Followthepaintmanufacturer’srecommendationstopreparethesurfaceandtoadequatelycoverandconcealthepanelfixings.

8.2 FLEXIBLE SEALANT SealantusedmustcomplywiththerelevantrequirementsofNZBC.Applicationanduseofsealantsmustcomplywiththemanufacturer’sinstructions.Checkwiththesealantmanufacturerpriortocoatingoversealant.Somesealantmanufacturersdonotrecommendcoatingovertheirproduct.

9 Storage and handling

StriaCladdingmustbelaidflatonasmoothlevelsurface.Edgesandcornersmustbeprotectedfromchipping.

Toensureoptimumperformance,storepanelsundercoverandkeepdrypriortofixing.Ifthepanelsbecomewet,allowthemtodrythoroughlybeforefixing.

DonotcarrypanelsorCLDStructuralCavityBattensontheflat,carryintheverticalpositiontoavoidexcessivebending.

7.1 VERTICAL JOINTStriaCladdingcanbejointedusingaverticaljointflashing.RefertoFigure6.

Thesecondoptionistoformabuttjointbyallowinga3mmgapbetweenthetwopanelswithanadhesivesealantappliedtotheedgeofthepanelpriortobuttingwiththenextpanel,itisrecommendedthatthejointsareformedinastraightline.RefertoFigure8.

7.2 HORIZONTAL JOINTStriaCladdingpanelsarehorizontallyshiplappedoverthepanelbelowasperFigure10.Thereisaminimum25mmlapbetweenthetwopanels.EnsurethatStriaCladdingpanelsaresecurelyinterlockedbeforenailing.StriaCladdingcanruncontinuousoverfloorjoistswithoutanyhorizontaljointwhenusingaLVLtimberfloorjoists.RefertoFigure25.

Whenanengineeredjoistisnotused,amovementjointmustbeformedatfloorjoist,refertoFigure26.

7.3 DRAINAGE JOINTAftereverytwofloorsahorizontaldrainagejointflashingisrequired,refertoFigure26.

7.4 INTERNAL CORNER JOINTAninternalcornerflashingistobeusedtoformaninternalcornerjoint,refertoFigure14.

Alternatively,thepanelscanalsobemitrejoinedtoformaninternalcorner,refertoFigure15.

7.5 EXTERNAL CORNER JOINTAnexternalboxcornerflashingisusedtofixtheexternalcorners,refertoFigure11and13.

Alternatively,thepanelscanbemitrejoinedtoformanexternalcorner,refertoFigure12.

8 Finishes8.1 PAINTINGPaintingofStriaCladdingismandatorytomeetthedurabilityrequirementsofNZBCand15yearJamesHardieproductwarranty.StriaCladdingmustbedryandfreeofanydustorgrimebeforepainting.Thepanelsmustbepaintedwithin90daysoftheirinstallation.ThereisnorestrictionontheLRVofpainttobeappliedontheStriaCladding.

StriaCladdingispre-primedandissuitableforsiteappliedacrylicpaints.

Inordertosealcutedgesorsandedpatches,DuluxPrimacryl,ReseneQuickDryorasimilarproductshouldbeapplied.Theprimershouldbecompatiblewiththepainttobeused.

Page 9: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

8 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 9

10 Maintenance

11.2 PRODUCT MASSStriaCladdingismanufacturedin14.0mmthicknessandhasamassof13.8kg/m2atEMC.

StriaCladdingisdefinedasaLightWeightWallCladding(notexceeding30kg/m2)asperNZS3604.

11.3 DURABILITYStriaCladding,RABBoardandCLDStructuralCavityBatteninstalledandmaintainedasperthistechnicalspecificationwillmeetthedurabilityrequirementforcladdingasperDurabilityB2clauseofNZBC.

11.3.1 Resistance to Moisture/Rotting StriaCladdinghastestedtocheckitsresistancetopermanentmoistureinduceddeterioration(rotting)bypassingthefollowingtestsinaccordancewithAS/NZS2908.2:

• Water Permeability (Clause 8.2.2)

• Warm Water (Clause 8.2.4)

• Heat Rain (Clause 6.5)

• Soak Dry (Clause 8.2.5)

11.3.2 Resistance to FireStriaCladdingisclassifiedas'Non-CombustibleMaterial'whichissuitableforuseasexternalwallcladdingandcomplieswithPerformanceC3.7oftheNZBCClauseC3FireAffectingAreasBeyondtheFireSource.

11.3.3 Alpine RegionsInregionssubjecttofreeze/thawconditions,StriaCladding,RABBoardandCLDStructuralCavityBattensmustnotbeindirectcontactwithsnoworicebuildupforextendedperiods,e.g.externalwallsinalpineregionsmustbeprotectedwheresnowdriftsoverwinterisexpected.

TheseproductshavebeentestedinaccordancewithAS/NZS2908.2Clause8.2.3.

Itistheresponsibilityofthespecifiertodeterminenormalmaintenancerequirementstomaintaintheeffectivenessofthecladding.Theextentandnatureofmaintenancerequiredwilldependonthegeographicallocationandexposureofthebuilding.

Asaguide,itisrecommendedthatthebasicnormalmaintenancetasksshallinclude,butnotbelimitedto:

• Washing down exterior surfaces every 6-12 months*• Re-coating exterior protective finishes**• Regular inspection and repair if necessary of the cladding,

sealants, etc.• Cleaning out gutters, down pipes and overflow pipes as

required.• Pruning back vegetation which is close to or touching the

building as well as ensuring the NZBC ground clearance requirements are maintained especially where gardens are concerned.

• The clearance between the bottom edge of the Stria Cladding and the finished/unfinished ground must always be maintained.

*Do not use a water blaster to wash down the cladding.

* In extreme coastal conditions or sea spray zones, wash every 3-4months.

** Refer to your paint manufacturer for washing down and recoating requirements related to paint performance.

11 Product information

11.1 MANUFACTURING AND CLASSIFICATION

StriaCladdingisanadvancedlightweightcementcompositecladdingmanufacturedusingJamesHardieScyonformulation.BasiccompositionisPortlandcement,groundsand,cellulosefibreandwater.

CLDStructuralCavityBattenaremanufacturedusingalowdensityfibrecementformulation.ThebasiccompositionisPortlandcement,groundsand,cellulosefibre,waterandproprietaryadditives.Thebattensarefactorysealedonallsides.

StriaCladdingandCLDStructuralCavityBattenproductsaremanufacturedtoAustralian/NewZealandStandardAS/NZS2908.2‘Cellulose-CementProducts’(ISO8336‘Fibre-CementFlatSheet’).

StriaCladdingisclassifiedTypeA,Category2inaccordancewithAS/NZS2908.2“Cellulose-CementProducts”.

ForSafetyDataSheets(SDS)visitwww.jameshardie.co.nzorAskJamesHardieon0800808868.

Page 10: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

10 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 11

12 Safe working practices

DO NOT BREATHE DUST AND CUT ONLY IN WELL VENTILATED AREAJamesHardieproductscontainrespirablecrystallinesilicawhichisconsideredbysomeinternationalauthoritiestobeacauseofcancerfromsomeoccupationalsources.Breathingexcessiveamountsofrespirablesilicadustcanalsocauseadisablingandpotentiallyfatallungdiseasecalledsilicosis,andhasbeenlinkedwithotherdiseases.Somestudiessuggestsmokingmayincreasetheserisks.Duringinstallationorhandling:(1)workinoutdoorareaswithampleventilation;(2)minimisedustwhencuttingbyusingeither'ScoreandSnap'knife,fibrecementshearsor,wherenotfeasible,useaHardieBlade™SawBladeanddust-reducingcircularsawattachedtoaHEPAvacuum;(3)warnothersintheimmediateareatoavoidbreathingdust;(4)wearaproperly-fitted,approveddustmaskorrespirator(e.g.P1orP2)inaccordancewithapplicablegovernmentregulationsandmanufacturerinstructionstofurtherlimitrespirablesilicaexposures.Duringclean-up,useHEPAvacuumsorwetcleanupmethods-neverdrysweep.Forfurtherinformation,refertoourinstallationinstructionsandSafetyDataSheetsavailableatwww.jameshardie.co.nz.

FAILURE TO ADHERE TO OUR WARNINGS, SAFETY DATA SHEETS, AND INSTALLATION INSTRUCTIONS MAY LEAD TO SERIOUS PERSONAL INJURY OR DEATH.

Working Instructions• Refer to Recommended Safe Working

Practices before starting any cutting or machining of product.

HardieBlade™ Saw BladeTheHardieBlade™SawBladeusedwithadust-reducingsawisidealforfast,cleancuttingofJamesHardiefibrecementproducts.Adust-reducingsawusesadustdeflectororadustcollectorconnectedtoavacuumsystem.Whensawing,clampastraight-edgetothesheetasaguideandrunthesawbaseplatealongthestraightedgewhenmakingthecut.

Hole-FormingFor smooth clean cut circular holes:

• Mark the centre of the hole on the sheet.

• Pre-drill a ‘pilot’ hole.

• Using the pilot hole as a guide, cut the hole to the appropriate diameter with a hole saw fitted to a heavy duty electric drill.

For irregular holes:

• Small rectangular or circular holes can be cut by drilling a series of small holes around the perimeter of the hole then tapping out the waste piece from the sheet face.

• Tap carefully to avoid damage to sheets, ensuring that the sheet edges are properly supported.

Handling and StorageAllmaterialsshouldbestoredtoavoiddamage,withedgesandcornersoftheStriaCladdingprotectedfromchipping.

StriaCladdingmustbeprotectedfromrainduringtransportandstorage.StriaCladdingmustbelaidflatundercoveronasmoothlevelsurfaceclearofthegroundtoavoidexposuretowaterormoistureetc.StriaCladding,RABBoardandCLDStructuralCavityBattenisresistanttopermanentwaterdamagewheninstalledasdirected,andmustonlybeinstalledinadrystate.

WhenhandlingStriaCladding,carrypanelsontheedgetakingcarenottochipedgesandcorners.

RefertothecurrentinstallationmanualforrecommendedSafeWorkingPractices.

QualityJamesHardieconductsstringentqualitycheckstoensurethatanyproductmanufacturedfallswithinourqualityspectrum.Itistheresponsibilityofthebuildertoensurethattheproductmeetsaestheticrequirementsbeforeinstallation.JamesHardiewillnotberesponsibleforrectifyingobviousaestheticsurfacevariationsfollowinginstallation.

James Hardie recommended safe working practices

CUTTING OUTDOORS

1. Position cutting station so wind will blow dust away from the user or others in working area.

2. Use one of the following methods based on the required cutting rate:

BEST• Dust reducing circular saw equipped with HardieBlade™

Saw Blade and HEPA vacuum extraction.GOOD• Dust reducing circular saw with HardieBlade™ Saw Blade.

SANDING/REBATING/DRILLING/OTHER MACHINING

When sanding, rebating, drilling or machining you should always wear a P1 or P2 dust mask and warn others in the immediate area.

IMPORTANT NOTES

1. For maximum protection (lowest respirable dust production), James Hardie recommends always using “Best” — level cutting methods where feasible.

2. NEVER use a power saw indoors.3. NEVER use a circular saw blade that does not carry

the HardieBlade™ logo.4. NEVER dry sweep — Use wet suppression or HEPA vacuum.5. NEVER use grinders.6. ALWAYS follow tool manufacturers’ safety recommendations.

P1 or P2 respirators should be used in conjunction with above cutting practices to further reduce dust exposures. Additional exposure information is available at www.jameshardie.co.nz to help you determine the most appropriate cutting method for your job requirements. If concern still exists about exposure levels or you do not comply with the above practices, you should always consult a qualified industrial hygienist or contact James Hardie for further information.

Page 11: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

10 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 11

13 Product and accessories

Note:Alldimensionsandmassesprovidedareapproximateonlyandsubjecttomanufacturingtolerances.

Stria Cladding information

Product Description Size (mm)Code

Thickness Length Width

Stria CladdingA14mmprofiledpanelforexpressedjointedresidentialfacades.Factorysealedonallsixsides.Eachpanelhasamanilawhitecolourprimerappliedonitsface,whichacceptsawiderangeofpaintfinishes.

14 4200 405 404263

RAB Board Usedasarigidairbarrier.Ithasgreencoloursealerappliedoveroneface.Installedwithgreensidefacingout.

6 2450 1200 402980

6 3000 1200 402981

HomeRAB PreClad LiningUsedasarigidairbarrier.Ithasgreencoloursealerappliedoveroneface.Installedwithgreensidefacingout.

3.5 2460 1200 404100

3.5 2760 1200 404101

Accessories/tools supplied by James Hardie

Accessories Description Size/Quantity Code

CLD Structural Cavity Batten19mmthickfibrecementcavitybatteninstalledoverJamesHardierigidairbarrierorabuildingunderlay.StriaCladdingisfixedtothebattens.

19mmx70mm,2450mmlong

Packof96battens403870

Vertical Joint FlashingAluminiumextrusionusedbehindcladdingatverticaljoints. 3000mmlong 305507

Internal Corner FlashingAnodisedaluminiumextrusionusedtocreateinternalcorners. 3000mmlong 304871

External Corner FlashingAnodisedaluminiumextrusionusedtocreateexternalcorners. 3000mmlong 304872

Aluminium Window Jamb FlashingAluminiummouldingusedbesidewindowopeningtoendbutttheStriaCladding.

3000mmlong 305430

Stria Aluminium Cavity ClosureAluminiummouldingusedasverminproofing.

3000mmlong 305431

Aluminium External Box CornerAboxcornermouldtoformtheexternaljoints.9mmetchprimed.

2450mmlong2750mmlong3000mmlong

304509 304510305150

uPVC Vent Strip PVCmouldingusedasverminproofing. 3000mmlong 302490

Tools

HardieBlade™ Saw Blade Diamondtip185mmdiameterfibrecementcircularsawblade.Spacersnotincluded.

Each 300660

Page 12: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

12 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 13

Accessories/tools not supplied by James HardieJamesHardierecommendsthefollowingproductsforuseinconjunctionwithStriaCladding,RABBoardandCLDStructuralCavityBatten.JamesHardiedoesnotsupplytheseproductsanddoesnotprovideawarrantyfortheiruse.Pleasecontactcomponentmanufacturerforinformationontheirwarrantiesandfurtherinformationontheirproducts.

Product Description

Building underlayMustcomplywithTable23ofE2/AS1.

Flexible Window Opening Flashing Tape Aflexibleself-adhesivetapeusedinpreparationofawindow.Refertothewindowinstallationsectioninthismanualformoreinformation.

e.g.ProtectobyProtectoWraporAluband®byThermakraftProtecto:08007769727Thermakraft:0800806595

RAB Board Vertical Joint Sealing TapeThetapetobeusedtosealRABBoardverticaljoints.

ProtectobyProtectoWraporAluband®byThermakraftProtecto:08007769727Thermakraft:0800806595

Adhesive SealantSikaflex11FCPolyurethaneadhesivesealantmanufacturedbySikaforapplyingbetweenthepanelsandbattens.Refertosection7formoreinformation.

SIKA0800SIKANZ.

‘SealNFlex-1’PolyurethaneadhesivesealantmanufacturedbyBOSTIKforapplyingbetweenthepanelsandbattens.Refertosection7formoreinformation.

BOSTIK:AKL:(09)5796253,WGTN:(04)5675119,CHCH:(03)3662583.

Flexible SealantRequiredtosealtheverticaljoints.BostikSealNFlex-1,SikaflexATFacade,SikaflexMSorsimilar.

30 x 1.6mm C Series Brad Nails304SSbradnailsusedtoinstallStriaCladdingtotheJamesHardieCLDStructuralCavityBatten.Usedinastraightbradder.Paslode:(09)4773000

65x2.87mmRounDriveRingShankNail.ForfixingCLDStructuralCavityBattenstotheframing.Paslode:(09)4773000

200mm wide Polypropylene Tape Productusedoverbuildingunderlayatexternalandinternalcorners.

Electra Meter BoxReferElectricalSuppliers

Adhesive

Sealant

Page 13: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

12 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 13

14 Details

Thefollowinggenericdetailshavebeenprovidedinthisdocumentforcavityconstructionmethods.

Table5Details

DescriptionCavity Construction

Figure No. Page No.

Framingsetout Figure1 14

Battenfixingsetout Figure2 15

Foundationdetail–option1 Figure3 16

Foundationdetail–option2 Figure4 16

Soffitdetail Figure5 17

Verticaljointingoption Figure6 17

StriaCladdinginstallation Figure7 18

Verticaljointingoption Figure8 19

Buttjointingonstud Figure9 19

Fixingdetail Figure10 20

Externalaluminiumboxcorner Figure11 20

Externalmitredcorner Figure12 21

Alternativeexternalaluminiumboxcorner Figure13 21

Internalaluminiumcorner Figure14 22

Internalmitredcorner Figure15 22

JointingofCLDStructuralCavityBatten Figure16 23

Windowsill Figure17 24

Windowjamb Figure18 24

Windowheadwithfullcladdingacrossheadflashing Figure19 25

Windowheadtofullboard Figure20 25

Windowjambflashing Figure21 26

Windowheadwithcladdingcutaroundheadflashing Figure22 26

WindowheadtoStriaCladdingcutboard Figure23,24 27

WindowheadtoCLDStructuralCavityBatten Figure25 28

Engineeredfloorjoist Figure26 29

Drainedflashingjoint Figure27 30

Drainedflashingjointatfloorlevel Figure28 31

Apronflashingdetail Figure29 32

Parapetflashing Figure30 32

Rooftowalljunction Figure31 33

Meterboxatsill Figure32 33

Meterboxatjamb Figure33 34

Meterboxathead Figure34 34

Encloseddeck Figure35 35

Doorsill Figure36 36

Page 14: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

14 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 15

Figure1:Framingsetout

Page 15: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

14 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 15

Figure2:Battenfixingsetout

Page 16: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

16 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 17

Figure4:Foundationdetail–option2

Figure3:Foundationdetail–option1

Page 17: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

16 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 17

Figure6:Verticaljointingoption

Figure5:Soffitdetail

Page 18: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

18 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 19

Figure7:StriaCladdinginstallation

Page 19: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

18 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 19

Figure9:Buttjointingonstud

Figure8:Verticaljointingoption

Page 20: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

20 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 21

Figure11:Externalaluminiumboxcorner

Figure10:Fixingdetail

Page 21: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

20 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 21

Figure12:Externalmitredcorner

Figure13:Alternativeexternalaluminiumcorner

Page 22: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

22 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 23

Figure14:Internalaluminiumcorner

Figure15:Internalmitredcorner

Page 23: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

22 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 23

Figure16:JointingofCLDStructuralCavityBatten

Page 24: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

24 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 25

Figure18:Windowjamb

Figure17:Windowsill

Page 25: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

24 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 25

Figure19:Windowheadwithfullcladdingacrossheadflashing

Figure20:Windowheadtofullboard

Page 26: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

26 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 27

Figure21:Windowjambflashing

Figure22:Windowheadwithcladdingcutaroundheadflashing

Page 27: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

26 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 27

Figure23:WindowheadtoStriaCladdingcutboard

Figure24:WindowheadtoStriaCladdingcutboard

Page 28: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

28 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 29

Figure25:WindowheadtoCLDStructuralCavityBatten

Page 29: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

28 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 29

Figure26:Engineeredfloorjoist

Page 30: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

30 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 31

Figure27:Drainedflashingjoint

Page 31: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

30 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 31

Figure28:Drainedflashingjointatfloorlevel

Page 32: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

32 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 33

Figure30:Parapetflashing

Figure29:Apronflashingdetail

Page 33: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

32 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 33

Figure31:Rooftowalljunction

Figure32:Meterboxatsill

Page 34: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

34 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 35

Figure33:Meterboxatjamb

Figure34:Meterboxathead

Page 35: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

34 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 35

Figure35:Encloseddeck

Page 36: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

36 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 3736 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 37

Figure36:DoorSill

Page 37: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

Notes

36 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 3736 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 37

Page 38: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

Notes

38 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 39

Page 39: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

Product Warranty

38 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand 39

July 2014JamesHardieNewZealand(“JamesHardie”)warrantsforaperiodof15yearsfromthedateofpurchasethattheStria®CladdingandCLD®StructuralCavityBatten(the“Product”),willbefreefromdefectsduetodefectivefactoryworkmanshipormaterialsand,subjecttocompliancewiththeconditionsbelow,willberesistanttocracking,rotting,fireanddamagefromtermiteattackstotheextentsetoutinJamesHardie’srelevantpublishedliteraturecurrentatthetimeofinstallation.JamesHardiewarrantsforaperiodof15yearsfromthedateofpurchasethattheaccessoriessuppliedbyJamesHardiewillbefreefromdefectsduetodefectivefactoryworkmanshipormaterials.

NothinginthisdocumentshallexcludeormodifyanylegalrightsacustomermayhaveundertheConsumerGuaranteesActorotherwisewhichcannotbeexcludedormodifiedatlaw.

CONDITIONS OF WARRANTY: Thewarrantyisstrictlysubjecttothefollowingconditions:

a) JamesHardiewillnotbeliableforbreachofwarrantyunlesstheclaimantprovidesproofofpurchaseandmakesawrittenclaimeitherwithin30daysafterthedefectwouldhavebecomereasonablyapparentor,ifthedefectwasreasonablyapparentpriortoinstallation,thentheclaimmustbemadepriortoinstallation;

b) thiswarrantyisnottransferable;

c) theProductmustbeinstalledandmaintainedstrictlyinaccordancewiththerelevantJamesHardieliteraturecurrentatthetimeofinstallationandmustbeinstalledinconjunctionwiththecomponentsorproductsspecifiedintheliterature.Further,allotherproducts,includingcoatingandjointingsystems,appliedtoorusedinconjunctionwiththeProductmustbeappliedorinstalledandmaintainedstrictlyinaccordancewiththerelevantmanufacturer’sinstructionsandgoodtradepractice;

d) theprojectmustbedesignedandconstructedinstrictcompliancewithallrelevantprovisionsofthecurrentNewZealandBuildingCode(“NZBC”),regulationsandstandards;

e) theclaimant’ssoleremedyforbreachofwarrantyis(atJamesHardie’soption)thatJamesHardiewilleithersupplyreplacementproduct,rectifytheaffectedproductorpayforthecostofthereplacementorrectificationoftheaffectedproduct;

f) JamesHardiewillnotbeliableforanylossesordamages(whetherdirectorindirect)includingpropertydamageorpersonalinjury,consequentialloss,economiclossorlossofprofits,arisingincontractornegligenceorhowsoeverarising.WithoutlimitingtheforegoingJamesHardiewillnotbeliableforanyclaims,damagesordefectsarisingfromorinanywayattributabletopoorworkmanship,poordesignordetailing,settlementorstructuralmovementand/ormovementofmaterialstowhichtheProductisattached,incorrectdesignofthestructure,actsofGodincludingbutnotlimitedtoearthquakes,cyclones,floodsorothersevereweatherconditionsorunusualclimaticconditions,efflorescenceorperformanceofpaint/coatingsappliedtotheProduct,normalwearandtear,growthofmould,mildew,fungi,bacteria,oranyorganismonanyProductsurfaceorProduct(whetherontheexposedorunexposedsurfaces);

g) allwarranties,conditions,liabilitiesandobligationsotherthanthosespecifiedinthiswarrantyareexcludedtothefullestextentallowedbylaw;

h) ifmeetingaclaimunderthiswarrantyinvolvesre-coatingofProducts,theremaybeslightcolourdifferencesbetweentheoriginalandreplacementProductsduetotheeffectsofweatheringandvariationsinmaterialsovertime.

Disclaimer:TherecommendationsinJamesHardie’sliteraturearebasedongoodbuildingpractice,butarenotanexhaustivestatementofallrelevantinformationandaresubjecttoconditions(c),(d),(f)and(g)above.JamesHardiehastestedtheperformanceoftheStria®CladdingandCLD®StructuralCavityBattenwheninstalledinaccordancewiththeStria®CladdingandCLD®StructuralCavityBattentechnicalspecification,inaccordancewiththestandardsandverificationmethodsrequiredbytheNZBCandthosetestresultsdemonstratetheproductcomplieswiththeperformancecriteriaestablishedbytheNZBC.However,asthesuccessfulperformanceoftherelevantsystemdependsonnumerousfactorsoutsidethecontrolofJamesHardie(e.g.qualityofworkmanshipanddesign)JamesHardieshallnotbeliablefortherecommendationsmadeinitsliteratureandtheperformanceoftherelevantsystem,includingitssuitabilityforanypurposeorabilitytosatisfytherelevantprovisionsoftheNZBC,regulationsandstandards,asitistheresponsibilityofthebuildingdesignertoensurethatthedetailsandrecommendationsprovidedintherelevantJamesHardieinstallationmanualaresuitablefortheintendedprojectandthatspecificdesignisconductedwhereappropriate.

CopyrightJuly2014.©JamesHardieNewZealand.TMand®denotesaTrademarkorRegisteredMarkownedbyJamesHardieTechnologyLimited.

Page 40: Technical Specification…4 James Hardie Stria® Cladding Technical Specification July 2014 New Zealand James Hardie Stria® Cladding Technical Specification July 2014 New Zealand

Ask James HardieTM I Call 0800 808 868 I jameshardie.co.nz

Copyright July 2014. © James Hardie New Zealand. TM and ® denotes a Trademark or Registered Mark owned by James Hardie Technology Limited.