    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 1

    SSEECCTTIIOONNBB33

    Technical Schedules

  • 8/13/2019 Technical Schedules

    2/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 2

    Table of Contents

    1.0 SWITCHYARD TECHNICAL DETAILS ............................................................................... 3

    2.0 EHV CIRCUIT BREAKERS .................................................................................................... 4

    3.0 EHV ISOLATORS WITH EARTH SWITCH.......................................................................... 7

    4.0 EHV CURRENT TRANSFORMERS....................................................................................... 9

    5.0 EHV VOLTAGE TRANSFORMERS .................................................................................... 10

    6.0 LIGHTNING ARRESTERS.................................................................................................... 12

    7.0 EHV SWITCHYARD CONTROL PANEL............................................................................ 13

    8.0 MISCELLANEOUS ITEMS................................................................................................... 16

    9.0 CABLES.................................................................................................................................. 19

    10.0 ILLUMINATION SYSTEM ................................................................................................... 21

    11.0 GENERAL ELECTRICAL ITEMS ........................................................................................ 22

    12.0 EARTHING LIGHTNING PROTECTION ............................................................................ 22

    13.0 TARIFF METERING PANEL (MAIN & CHECK) ............................................................... 23

    14.0 BATTERY.............................................................................................................................. 24

    15.0 BATTERY CHARGER........................................................................................................... 26

  • 8/13/2019 Technical Schedules

    3/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 3

    SECTION B3

    TECHNICAL SCHEDULES

    Bidder shall furnish the following technical particulars for the equipment offered by him.

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    1.0 SWITCHYARD TECHNICAL DETAILS

    1.1 Rated voltage kV

    1.2 1.2 / 50 micro sec impulse withstand voltage kV peak

    1.3 One min. power frequency withstand voltage kV

    1.4 Current ratings

    a. Continuous for main bus Amps

    b. Continuous for bay buses Amps

    1.5 Minimum air clearance

    a. Phase to phase mm

    b. Phase to ground mm

    c. Live point to ground mm

    d. Section clearance mm

    1.6 Bay width m

    1.7 Phase to phase spacing m

    1.8 Size of the switchyard m x m

    1.9 Design tensions

    a. Main bus kg

    b. Bay bus kg

    c. End towers (for connections to line) kg

    1.10 Total creepage distance for all equipment mm

    1.11 Protected creepage distance mm

  • 8/13/2019 Technical Schedules

    4/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 4

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    1.12 Factor of safety adopted for the structural design

    a. Normal condition

    b. Short circuit condition

    c. Seismic condition

    1.13 Visual discharge voltage for all equipment with kV

    fitting & insulator assemblies for falling power

    frequency voltage

    1.14 Radio interference voltage for all the switchyardequipment with fittings & insulator assemblies

    RIV level micro volts

    1.15 Type of design for main & bay buses

    a. Strung bus or tubular bus

    b. Material

    2.0 EHV CIRCUIT BREAKERS

    2.1 Make, type, country of manufacture

    2.2 Applicable standard

    2.3 Rated voltage kV

    2.4 Type of circuit breaker

    2.5 Reference ambient temperature C

    2.6 Rated continuous current Amp

    2.7 a. Rated short circuit breaking current

    and rated making current kA

    b. Short circuit withstand current kA / sec

    rating & duration

    2.8 Temperature rise of contacts over an

    ambient of 50C while carrying rated current C

  • 8/13/2019 Technical Schedules

    5/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 5

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    2.9 Rated operating duty

    2.10 Total break time m.sec

    2.11 Total make time m.sec

    2.12 Rated transient recovery voltage for

    short line faults kV

    2.13 No. of breaks in series

    2.14 Insulation level

    a. One minute P.F withstand voltage kV peak

    b. Impulse withstand voltage kV peak

    c. Switching surge withstand voltage kV peak

    2.15 Minimum clearance in air

    a. Between live parts mm

    b. Between live parts & earth mm

    c. Centre to centre distance between phases mm

    2.16 Trip free Yes / No

    2.17 Type of operating mechanism

    2.18 Normal method of tripping

    2.19 Emergency method of tripping

    2.20 No. of trip coils

    2.21 Rated voltage and permissible variations:

    a. for Trip coils

    b. for Closing coils

    c. for Operating mechanism motor

  • 8/13/2019 Technical Schedules

    6/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 6

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    2.22 Burden (watts)

    a. Trip coils

    b. Closing coils

    2.23 Rated line charging current

    2.24 Rated cable charging current

    2.25 Maximum over voltage when switching off

    a. Unloaded transformer

    b. Unloaded lines

    c. Cable charging

    d. Capacitor banks

    2.26 When switching off asynchronous system

    a. Maximum current kA

    b. Maximum recovery voltage between contacts

    2.27 No. of operation circuit breakers can perform

    without inspection, replacement of contacts

    a. At rated breaking current

    b. At rated continuous current

    2.28 Creepage distance for the interrupter insulator mm

    2.29 Type and creepage distance for the support insulator mm

    2.30 Cantilever strength of circuit breaker at the

    terminal pad kg

    2.31 Whether pressure switches for Sulphur hexafluoride

    pressure low alarm, trip, lockout closing, lockout

    opening are provided.

  • 8/13/2019 Technical Schedules

    7/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 7

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    2.32 Leakage rate of Sulphur hexafluoride per year. % / year

    3.0 EHV ISOLATORS WITH EARTH SWITCH

    3.1 Make, type, and country

    of manufacture

    3.2 Reference standard

    3.3 Rated voltage & frequency Volts, Hz

    3.4 Rated current A

    3.5 Reference ambient temperature C

    3.6 Short time withstand current &

    duration kA Sec

    3.7 a. Dynamic withstand current kA peak

    b. Max. current isolator can safely interrupt A

    c. Transformer magnetising current breaking A

    d. Making current (for earth switch only) A

    3.8 Maximum temperature rise of current

    carrying parts

    3.9 Insulation test values

    a. One minute power frequency wet

    withstand voltage

    i. Between poles & earth kVii. Across isolating distance kV

    b. Impulse withstand voltage

    i. Between poles & earth kV peak

    ii. Across isolating distance kV peak

  • 8/13/2019 Technical Schedules

    8/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 8

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    3.10 Material

    a. Main contact

    b. Arcing contact

    c. Current carrying parts

    3.11 Whether contacts are silver faced

    3.12 Clearance

    a. Between poles mm

    b. Between live parts earth mm

    c. Between live parts when switch is open mm

    i. Between same pole mm

    ii. Between adjacent pole mm

    3.13 Phase spacing

    3.14 Type of interlock

    a. External

    b. Earth switch

    3.15 Insulators

    a. Type of insulator (solid core)

    b. Cantilever strength

    c. Total creepage distance

    d. Applicable standards

    3.16 Operating mechanism (motor / manual)

    a. Main blade

    b. Earth blade

  • 8/13/2019 Technical Schedules

    9/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 9

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    4.0 EHV CURRENT TRANSFORMERS

    4.1 Make & country of manufacture

    4.2 Applicable standards

    4.3 Rated voltage class

    4.4 Insulation withstand level :

    a. Impulse withstand voltage kV peak1.2 / 50 micro sec wave

    b. One minute power frequency kV rms

    withstand voltage

    4.5 Number of cores per CT

    4.6 Whether it is possible to adjust tap Yes / No

    setting of any core independent of

    other cores

    4.7 Relaying cores

    a. Accuracy class (for 5P20)

    b. Rated burden (for 5P20) VA

    c. Accuracy limit factor (5P20)

    d. Minimum knee point voltage Volts

    VK for PS class

    e. Maximum excitation current mA

    at VK, VK/2 volts (PS class)f. Maximum secondary resistance (PS class) Ohms

    4.8 For metering cores:

    a. Accuracy class

    b. Rated burden VA

    c. Rated power factor

  • 8/13/2019 Technical Schedules

    10/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 10

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    d. Instrument security factor

    4.9 Short time thermal current rating

    a. Current kA

    b. Rated time sec

    4.10 Dynamic current rating kA peak

    4.11 Maximum temperature rise of

    winding at rated primary current and

    rated burden, when referred to specifiedambient temperature C

    4.12 Class of insulation of winding

    4.13 Cantilever strength at terminal kg

    4.14 Type and creepage distance of insulator housing m

    5.0 EHV VOLTAGE TRANSFORMERS

    CVT EMVT

    -------------- ------------

    5.1 Manufacturer & country of manufacture

    5.2 Applicable standards

    5.3 Type of VT

    5.4 Insulation withstand level

    a. Impulse withstand voltage kV peak

    1.20/50 micro sec. wave

    b. One minute power frequency kV rms

    withstand voltage

    5.5 Number of secondary windings for each VT

    5.6 Rated primary voltage kV

    5.7 Rated secondary voltage V

  • 8/13/2019 Technical Schedules

    11/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 11

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    CVT EMVT

    -------------- ------------

    5.8 Rated VA burden for each

    each secondary winding VA

    5.9 Rated power factor

    5.10 Accuracy class for each secondary winding

    a. Winding 1

    b. Winding 2

    5.11 Method of connection

    a. Primary winding

    b. Each secondary winding

    i. Winding 1

    ii. Winding 2

    5.12 Rated voltage factor

    5.13 Maximum temperature rise of winding C

    at 110% excitation and rated burden when

    referred to specified ambient temperature

    5.14 Class of insulation of windings

    5.15 Capacitor data

    a. High voltage capacitance PF

    b. Intermediate voltage capacitance PF

    c. Nominal intermediate voltage kV

    d. Equivalent capacitance for carrier coupling PF

    e. Maximum permissible impedance at power

    frequency of carrier coupling device Ohms

    5.16 Insulator type and total creepage distance mm

  • 8/13/2019 Technical Schedules

    12/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 12

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    CVT EMVT

    -------------- ------------

    5.17 Radio interference voltage Volts

    5.18 Details of high speed switch(es) on secondary

    winding (alternative to fuses)

    a. Make, type, coil rating other technical details A

    5.19 Cantilever strength kg

    6.0 LIGHTNING ARRESTERS

    6.1 Make, type & country of

    manufacture

    6.2 Arrester type

    6.3 Applicable standards

    6.4 Arrester class

    6.5 Rated arrester voltage kV

    6.6 Rated frequency Hz

    6.7 Nominal discharge current

    (8/20 micro sec wave) kA

    6.8 Minimum discharge capability KJ / kV

    6.9 Residual voltage corresponding to kV peak

    a. Steep current impulseb. Lightning impulse

    6.10 Reference current (IEC TC37-WG-4 1985) A

    6.11 Reference current (IEC TC37-WG-4 1985) kV rms

    6.12 Over voltage withstand capability for

    a. 10 cycles kV rms

    b. 1 second kV rms

    c. Continuous kV rms

  • 8/13/2019 Technical Schedules

    13/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 13

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    6.13 Energy discharge capacity KJ / kV

    6.14 Maximum residual voltage at nominal

    discharge current kV rms

    6.15 Discharge voltage at 5 kA kV peak

    discharge current

    6.16 Discharge voltage at 10 kA

    discharge current kV peak

    6.17 Discharge voltage at 20 kAdischarge current kV peak

    6.18 Impulse current withstand

    a. High current short duration

    (4 / 10 micro second wave) kA peak

    b. Low current long duration A peak

    c. Virtual duration of rectangular wave micro-second

    6.19 One minute power frequency (dry) kV rmswithstand voltage of arrester housing

    6.20 Impulse withstand test voltage of

    arrester housing with 1.2/50 micro-second wave kV peak

    6.21 Total creepage distance of whole arrester housing mm

    6.22 Cantilever strength of complete arrester kg

    6.23 Pressure relief class (as per IEC 99)

    7.0 EHV SWITCHYARD CONTROL PANEL

    7.1 Make

    7.2 a. Degree of protection for

    enclosure of panel

    b. Sheet steel thickness mm

  • 8/13/2019 Technical Schedules

    14/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 14

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    7.3 Applicable standards

    7.4 Indicating meters

    a. Meter size

    b. Accuracy

    c. Type

    7.5 KWH METER

    a. Accuracy

    b. Whether pulse transmitting facility provided Yes / No

    7.6 TRI VECTOR METER

    a. Make

    b. Type

    7.7 TRANSDUCERS

    a. Accuracyb. Output current mA DC

    c. No. of channels

    d. Type no. & make

    7.8. Describe annunciators scheme,

    features, sequence and size as

    offered (please attach write-up) Yes/No

    7.9 Mimic material and width mm

    7.10 Indication lamps

    a. Make

    b. Type

    c. Rating, voltage / watts V/W

  • 8/13/2019 Technical Schedules

    15/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 15

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    7.11. Push buttons

    a. Make

    b. Number included

    c. No. of NO + NC contacts

    d. Function

    7.12. Semaphore indicator

    a. Make

    b. Rating Watts

    c. No. of coils No.

    d. Size offered

    i. for CB

    ii. for isolator main & earth switch

    e. nos. offered

    7.13. Control Switch. / Selector Switch.

    a. Make

    b. Rating (DC inductive breaking capacity) V/ Amps

    7.14. Hooter / Bell

    a. Make

    7.15. EHV Switchyard Relay Panel

    a. Panel make and country of manufacture

    b. - Degree of protection for

    enclosure of panel

    - Sheet steel thickness mm

    c. Mounting of relays

  • 8/13/2019 Technical Schedules

    16/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 16

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    d. Relay Particulars

    (furnish following data

    as applicable for all the relays offered.

    Attach necessary sheets as required)

    - Control voltage V

    - Current rating A

    - Voltage rating V

    - Operating temperature range C

    - Applicable standards

    - Aux. supply operating range

    - Online automatic testing facility provided

    - Online manual testing facility provided

    e. Relay types offered (list each relay and

    furnish the data for each relay used)

    f. All the relays offered are type tested Yes/No

    8.0 MISCELLANEOUS ITEMS

    8.1 ACDB / DCDB (fill in separately for ACDB & DCDB)

    a. Make

    b. Type (Draw-out / non drawout)

    c. Sheet steel thickness mmd. Degree of protection

    e. Busbar details

    - Material

    - Rated voltage

    - No. of phases

  • 8/13/2019 Technical Schedules

    17/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 17

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    - Current rating

    - Fault level withstand

    f. No. of switch fuse feeders x

    ratings :

    1 x incomer x .A

    X outgoing x .A

    8.2 Insulator and hardware (fill in forbus post insulator as well as

    insulator string)

    a. Insulator / Insulator string

    - Manufacture & country of manufacture

    - Applicable standard

    - Type of insulator (antifog / normal)

    - Insulating material

    - No. of units per string

    - Creepage distance

    i. Disc unit mm

    ii. String assembly mm

    - One minute power frequency

    withstand (dry)

    i. Single disc kV

    ii. String assembly / buspost kV

    - One minute power frequency

    (wet) withstand

    i. Disc unit kV

    ii. String assembly / buspost kV

  • 8/13/2019 Technical Schedules

    18/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 18

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    - Impulse withstand voltage (dry)

    i. Disc unit kV peak

    ii. String assembly / buspost kV peak

    - impulse withstand voltage (wet) kV peak

    i. Disc unit kV peak

    ii. String assembly / buspost kV peak

    - Electro mechanical strength of

    each disc kg

    - Live parts to earth clearance

    (sparkover distance) mm

    - Cantilever strength (for bus post

    insulator only) kg

    - Tensile strength (for bus post

    insulator only) kg

    - Visual discharge voltage for falling

    power frequency voltage (string and

    bus post insulators) kV

    - Compression strength (for bus post

    insulator only) kg

    - Radio interference voltage for string

    and bus post insulator

    i. Test voltage kV

    ii. Radio interference voltage micro volt

    8.3 INSULATOR HARDWARE

    a. Manufacture

    b. Applicable standard

    c. All ferrous parts are hot dip galvanised Yes/No

  • 8/13/2019 Technical Schedules

    19/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 19

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    8.4 BUS CONDUCTORS, CLAMPS AND CONNECTORS

    a. Flexible conductor ACSR

    - Size of conductor for main bus &

    bus coupler bay buses

    - Size of conductor for other bay buses

    - The temperature rise of the conductor

    while carrying the rated current

    - Purity of aluminium / copper %

    8.5 Clamps and Connectors

    a. Whether material specification of the Yes/ No

    clamping and connectors are

    as per specification

    b. Temperature rise of the clamp while

    carrying the rated current C

    c. Minimum thickness at any part of the clamps mm

    d. Coronal extinction voltage for

    falling power frequency voltage V

    9.0 CABLES

    9.1 Make

    9.2 Type

    9.3 Applicable standard

    9.4 Voltage grade

    9.5 Maximum conductor temperature

    a. Continuous C

    b. Short time C

  • 8/13/2019 Technical Schedules

    20/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 20

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    9.6 Conductor

    a. Material

    b. Size sq.mm

    c. No. & diameter of wire in

    each conductor No. / mm

    9.7 Insulation

    a. Material

    b. Type

    c. Thickness mm

    9.8 Inner sheath

    a. Material

    b. Type

    c. Thickness mmd. Extruded?

    e. Approx. outside dia over sheath mm

    9.9 Armouring

    a. Material

    b. Size

    c. D.C resistance at 20 ohm / km

    9.10 Outer sheath

    a. Material

    b. Type

    c. Thickness

  • 8/13/2019 Technical Schedules

    21/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 21

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    9.11 Approx. overall diameter mm

    9.12 Standard drum length with tolerance mm

    9.13 Net weight of cables kg / km

    10.0 ILLUMINATION SYSTEM

    10.1 Lighting Fixtures

    a. For outdoor switchyard

    i. Type

    ii. Make

    iii. Quantity x Watts

    iv. Designed lux level

    b. For switchyard control room

    i. Type

    ii. Make

    iii. Quantity & wattsiv. Designed lux level

    c. For Battery room

    i. Type

    ii. Make

    iii. Quantity & watts

    iv. Designed lux. level

    10.2 Lighting Panel

    a. Make

    b. No. of ways / circuits

    c. Incoming TPN MCB with ELCB rating / make

    d. Outgoing SP MCBs.

    i. Number

    ii. Rating

  • 8/13/2019 Technical Schedules

    22/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 22

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    10.3 WIRING

    a. Main cables type / size

    b. Cables to fixtures type / size

    c. Method of cabling conduit / size

    11.0 GENERAL ELECTRICAL ITEMS

    11.1 Cable Trays

    a. Makeb. Type

    c. Width

    11.2 Cable ties, clamps,

    identification tags, etc. provided?

    11.3 Rigid metal conduits, RCC hume pipes

    offered for Trench / rail crossing / in

    equipment foundations?

    11.4 Fence height / material details

    11.5 Granite metal work

    a. Size of metal

    b. Depth of spreading

    11.6 All other standard items like hand

    gloves, shock treatment charts, rubber

    mats caution boards etc. furnished? Yes/No

    12.0 EARTHING LIGHTNING PROTECTION

    12.1 Earthing

    a. Main grid conductor

    i. Material

    ii. Cross section

    b. Equipment connections

    i. Material

    ii. Cross section

  • 8/13/2019 Technical Schedules

    23/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 23

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Unit Particulars /

    Data

    ------------------------------------------------------------------------------------------------------------------------

    13.0 TARIFF METERING PANEL (MAIN & CHECK)

    13.1 Make of tri-vector meter

    13.2 Rated voltage & frequency (110V / 50 Hz) V / Hz

    13.3 Rated current (1 amp) Amp

    13.4 Type (Digital type)

    13.5 Accuracy class (0.2)

    13.6 Burden at rated voltage VA

    13.7 Is the Tri-vector meter bi-directional type

    13.8 Is the Tri-vector meter suitable for 2 part tariff

    13.9 Auxiliary power supply requirement (110V DC 10%) V DC

    13.10 Does the tri-vector meter have maximum demand indicatoras called for in the specification

    i) Does the tri-vector meter have

    ii) A serial port suitable for Ethernet protocol

    iii) A telemetry port for future communication through

    telephone lines

    13.11 Construction of panel :

    i) Panel sheet steel thickness mm5

    ii) Cable entry

    iii) Access to the panel

    iv) Ingress protection class

    v) Panel space heater (hygrostatically controlled)

    vi) Panel illumination & small power socket

    vii) Size of panel wiring mm

  • 8/13/2019 Technical Schedules

    24/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 24

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    14.0 BATTERY

    14.1 Battery

    14.2 Manufacturer

    14.3 Type of battery

    14.4 No. of batteries

    14.5 Number of cells

    14.6 Voltage rating

    - Nominal cell voltage rating

    - Nominal float charging voltage

    - Nominal boost charging voltage

    - Nominal cell discharge voltage

    14.7 10 hour rating at 27C to 1.85 V / cell

    14.8 One (1) minute rating to 1.85 V cell

    14.9 Rated capacity at maximum ambient

    temperature (50C) AH

    14.10 Rated capacity at minimum ambient

    temperature (8.5C) AH

    14.11 Continuous load and duration

    14.12 a. Type of plates

    - Positive

    - Negative

    b. Type and material of container

    14.13 Type of rack

    14.14 Number of racks / battery

  • 8/13/2019 Technical Schedules

    25/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 25

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    14.15 Number of cells / rack

    14.16 Type of rack rows / tiers

    14.17 Inter row, inter tier connectors

    and end take off furnished? Yes/ No

    14.18 Connection hardware with 5%

    extra furnished? Yes/ No

    14.19 Cable termination at positivenegative and intermediate tap

    provided?

    14.20 Recommended specific gravity of

    electrolyte at the end of full charge Yes/ No

    and at first filling

    14.21 Type of separator

    Material and thickness of separator

    14.22 Float charging current

    14.23 Boost charging current

    (initial & final)

    14.24 Internal resistance of one cell

    14.25 Short circuit current for dead short

    Across battery terminals at

    14.25.1 Float charge voltage (in kA)

    14.25.2 Boost charge voltage (in kA)

    14.25.3 Equalising charge voltage

    14.25.4 Only due to battery (in kA)

    14.26 Cell voltage characteristics during

    charging furnished? Yes/No

  • 8/13/2019 Technical Schedules

    26/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 26

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    14.27 Charging current of a fully

    discharged battery at 12 hours

    charging rate

    14.28 Charging efficiency of the battery

    14.29 Overall dimension of

    14.29.1 Each cell (L x B x H)

    14.29.2 Battery(L x B x H)

    14.29.3 Battery layout furnished Yes/ No

    14.30 Approximate weight (kgs)

    1430.1 Each cell

    14.30.2 Complete battery

    14.31 List of accessories

    14.32 Spare parts as specified

    provided with equipment

    14.33 Ventilation requirements

    15.0 BATTERY CHARGER

    Float cum

    Boost Charger

    15.1 Manufacturer type and ref.

    standard

    15.2 Input voltage with % variation

    15.3 Input frequency with % variation

    15.4 Output DC voltage

    15.5 Output current

  • 8/13/2019 Technical Schedules

    27/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 27

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    15.6 Time required to fully charge the

    completely discharged battery under

    boost charging

    Float cum

    Boost Charger

    15.7 Maximum AC input during boost charging

    15.8 Ripple in DC output

    15.9 Charger efficiency at rated output

    15.10 Temperature rise above ambient of 50C

    15.11 Regulation for 0-100% rated load

    with 10% voltage variation and

    - 5% to + 5% frequency variation

    15.12 Power factor at rated load

    15.13 Charger provided with

    a. Automatic voltage Yes/No

    b. Current limiting circuitry and constant current regulator Yes/No

    c. Smoothing filter circuit Yes/No

    d. Soft start feature Yes/No

    15.14 SCR elements provided with

    a. Surge protection

    b. Fast acting semi conductor fuses

    15.15 AC Switch

    a. Make

    b. Type

    c. Rating

  • 8/13/2019 Technical Schedules

    28/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 28

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    15.16 AC Contactor

    a. Make

    b. Type

    c. Rating

    d. Coil rating

    Float cum

    Boost Charger

    15.17 AC / DC fuse

    a. Make

    b. Type

    15.18 Rectifier transformer

    a. Make

    b. Type

    c. Rating

    d. Insulation classe. Voltage ratio

    15.19 Blocking diodes

    a. Make

    b. Type

    c. Current rating for 1 minute / 1 hour

    d. Peak inverse voltage continuous / surge

    15.20 SCR

    a. Make

    b. Type

    c. RMS current rating

    d. Peak inverse voltage continuous / surge

    e. Max. temp rise above an ambient of 50C

  • 8/13/2019 Technical Schedules

    29/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 29

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    15.21 DC Contactor

    a. Make

    b. Type

    c. Rating

    15.22 Indicating lamps

    a. Make

    b. Wattagec. Rating

    15.23 Push Button

    a. Make

    b. Type

    c. Rating

    d. No. of contacts

    15.24 Meters

    a. Make

    b. Type

    c. Accuracy

    d. Size

    15.25 Control terminals

    a. Make

    b. Type

    c. Rating

  • 8/13/2019 Technical Schedules

    30/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B3-Swyd

    Rev. : R0 Page : B3 : 30

    ------------------------------------------------------------------------------------------------------------------------

    Sl. No. Description Particulars/

    Data

    ------------------------------------------------------------------------------------------------------------------------

    15.26 Annunciator

    a. Make

    b. Type

    c. No. of windows

    15.27 DC Switch

    a. Makeb. Type

    c. Rating

    15.28 Panel

    a. Make

    15.29 List of accessories

    15.30 Heat output of the panel

    (furnish calculations)

    15.31 Overall dimensions of

    battery charger panel

    15.32 Approximate weight of charger panel

    15.33 Schematic diagram and write up Yes/ No

    of charger enclosed?

    15.34 Spare parts as specified

    provided with equipment

    SIGNATURE OF BIDDER _________________________

    NAME _________________________

    DESIGNATION _________________________

    COMPANY SEAL DATE _________________________

  • 8/13/2019 Technical Schedules

    31/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    FICHTNER India Doc. No.6104-EL-SPC-610-001P2Sec B4-Swyd

    Rev. : R0 Page : B4: 1

    SSEECCTTIIOONNBB44

    Approved Vendor List

  • 8/13/2019 Technical Schedules

    32/32

    5.8 MGD Seawater Desalination Project

    Tender Enquiry Document for 110 kV Switchyard

    P2S B4 S d

    SECTION B4

    APPROVED VENDOR LIST

    1. 110 kV circuit breakers - ABB / CGL / Siemens / Alstom

    2. 110 kV isolators - Hivelm / Elpro / Versatek

    3. 110 kV current transformer - ABB / CGL / Alstom

    4. 110 kV voltage transformer - ABB / CGL / Alstom

    5. 96 kV surge arrestors - Oblum / Lamco / CGL / Alstom / Elpro

    6. Control and relay panels - ABB / Elpro / Alstom / Enpro

    7. Protection relays - ABB / Siemens / Alstom

    8. Tariff meters - L&T / SEMS

    9. Insulators - WSI / JSI / Modern

    10. Battery & battery charger - Exide / HI-rel / Power Electronics / SAFT

    NIFE / Amararaja