72
Hospital Trunking Construction Kit for Medical Ward Units TECHNICAL INFORMATION 2001:12 P2148

TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

Hospital TrunkingConstruction Kit for Medical Ward Units

TECHNICAL INFORMATION 2001:12

P214

8

Page 2: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

P372

2

FrontLine Installation SystemFrontLine is a system for installation of service tomodern office workplaces. The system includes pro-ducts which enable the services to be supplied fromthe ceiling, the wall or the floor.

The system consists of two parts:1. Service content which includes socket outlets and

connections for power, telecommunication and datafor access to networks and other services.

2. Service carriers are the cable trunking, service-poles, floor outlet boxes, service posts and service box-es, with 80 mm front openings (F80®), which make thesocket outlets and connections accessible.

The F80® front openings ensure that the servicecontent is compatible with the various service carri-ers.

Most FrontLine service carriers can also be deliv-ered pre-wired, with the required service content,ready for connection to service gates in the main net-work. This will reduce the on-site installation timeand make rearrangement of the premises easier.

Every pre-wired product is given a serial numberand is tested prior to delivery. An individual test re-port is always included.

TrademarksThe following is a list of Thorsman's and other companies' trademarks, registered and unregis-tered, used throughout this catalogue.

Trademark CompanyAGA ................................................AGA GAS ABAMP-CO, NetConnect........................AMP IncBlolite...............................................BICC Brand-RexDräger .............................................Dräger GmbhEthernet ............................................Digital Equipment Corp./Xerox/IntelGreggersen.......................................Greggersen Gastechnik GmbhIBM..................................................International Business Machines CorpLUXO ...............................................JAC Jacobsen ASKeystone...........................................Keystone International Holdings PremisNet .........................................Krone(UK)Technique LtdLexCom ............................................LK asSystimax ...........................................Lucent Technologies LtdMEDÆS GEM 10..............................Meaæs LtdSUNNEX ..........................................Nolato Sunnex Equipment ABReichle & De-Massari .........................Reichle & De-MassariHirschmann.......................................Richard Hirschmann Radiotechnisches WerkCYB, F80, FrontLine, INKA .................Thorsman & Co AB

Other brand and product names are the trademark of their respective holders.

Page 3: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 3

Hospital TrunkingConstruction Kit for Medical Ward Units

Medical Ward Unit For All Requirements ........ 4Straightforward Construction .......................... 6Many Combinations - Freedom of Choice ........ 8Complete Access & Outlet Program.................. 10Design and Dimensions .................................. 12Medical Ward Unit in Common Ward.............. 13Medical Ward Unit in Intensive Care .............. 14Cable Trunking Design .................................. 16Composition of Lighting Profile ........................ 18Placement of Light Fitting Rail .......................... 19Lighting Techniques ........................................ 20Gas Outlet Installation Techniques.................... 22Layout Planning ............................................ 24Colour Choice .............................................. 25

Product Range Service carriers.............................................. 26Service Content

Power ........................................................ 30Communication .......................................... 38

Lighting ........................................................ 41Gas.............................................................. 44Accessory Rail .............................................. 48Tools ............................................................ 49Cable Capacity ............................................ 50Technical Data .............................................. 59Mounting Details............................................ 60Specification Guide........................................ 67

Products and technical details are subject to change during the lifetime of the brochure.© THORSMAN & CO AB, 2001.

Approval and Quality AssuranceThe Thorsman policy is to test andapprove products to applicable localand international standards. We operatequality assurance and quality control sys-tems certified according to ISO 9000.

For testing and approving we use the fol-lowing test houses:

Line drawings/photos

The number beside linedrawings and photos is inten-ded only for ordering digitalpicture material.NB: When ordering pro-ducts, use the T-number in thetable.

L317

00

Page 4: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

4 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

1. Lighting unit, full length, colour code L11.2. Trunking base, type INKA-217-2/90, colour code

L11 and L65.3. Service content, CYB.

4. Gas profile, full length, colour code L11.5. Dräger gas outlets.6. Accessory rail equipped with monitor shelf.

Medical Ward Unit in Kit Form for All Requirements

P2146

1

23

45

Page 5: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 5

Established and Approved ComponentsWith a number of established and approved compo-nents you can, on-site, construct and install MedicalWard Units adapted to unique nursing situations.

The kit allows the construction of a ward unit forthe most straightforward form of common ward up tothe most complex installations for intensive care spaces.

The cable trunking that is one of the main compo-nents can also be used to advantage as a carrier of, forexample, service content (power, telecommunications,data, etc.) in other work spaces of the hospital ornursing home such as offices or laboratories.

The Basis: Cable Trunking, INKAThe concept for the kit is built around Thorsman’scable trunking in aluminium of type INKA. This in-stallation trunking is carrier for all electricity, tele-communications, data and low-voltage current. Thesize of the trunking is chosen with regard to cable ca-pacity and equipment required. Cable trunking isavailable in several heights. Some are two-compart-ment systems, where the lower compartment isscreened off by an integral partition. The trunking isavailable in two depths, 72 mm or 90 mm. A widerange of accessories are available for all INKA cabletrunking to ease installation and offer complete solu-tions.

Outlets for Power, Telecommunications and Data ConnectionsA complete range of products for outlets and connec-tions for power, telecommunication, data etc., is avail-able, all mounted easily in the front of the installationtrunking.

General and Reading/Examining Lighting The kit includes a combined lighting unit for generaland reading/examining light. The lighting complieswith the German DIN requirements for light disper-sion in nursing spaces. The lighting unit can be fittedon the wall close to the INKA cable trunking or sep-arately. Length can be either full-length or adapted tothe choice of lighting rail. A bed/examining lamp witharm for mounting on either wall or table is available asan accessory.

GasThe assortment of gas outlets include units ofScandinavian, German and English standard for con-nection to air, oxygen, nitrous oxide, etc. The gas ductcan, as with the lighting unit, be mounted on the wallclose to the INKA trunking or separately. Gas-pipecover is available in two designs.

Colour ChoiceAll of the visible profile components can be naturalanodized or powder coated in a number of standardcolours. The colours can be combined in accordanceto the wishes of the customer to harmonize withroom decor.

6

Page 6: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

6 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

P382

6Straightforward Construction and Installation

Page 7: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 7

Basic Data

DescriptionINKA cable trunking, aluminium, 72 and 90 mmdeep, with one or two compartments, 80 mm frontcover (F80®).

Lighting profile with general (indirect), reading/examining (direct) and optional night light. Choiceof light fittings, 80 mm front cover (F80®)

Gas outlet profile to suit several gas outlet brandsand standards. Gas-pipe cover is available in two designs.

• Kit form gives flexibility• Based on Thorsman standard products• Wide assortment• Simple to specify• Easy to install according to clear instructions• Separation of power and low current,

lighting and gas• Rapid installation with snap fittings• Labelling of outlets• Easy to clean• Easy to upgrade and add new functions

Mounting and installationThe hospital trunking components are fixed directlyto the wall. The service content is installed in thefront opening.

The snap-in system makes the installation quickand easy. Detailed mounting instructions areenclosed.

Power and CommunicationThe trunking can be equipped with FrontLine Accessand Outlet Program type CYB.

Delivery lengthsStandard length of INKA trunking and front covers,2.5 m. INKA, lighting and gas pipe front coveravailable cut to length, max. 5.0 m by specialorder.

ColoursNatural anodized or powder coated aluminium1).

1) Can be painted in any shade listed in the NCS and RAL colourranges, see page 25.

Page 8: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

8 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

1. Lighting unit, length adjusted to light fitting, see Lighting pages 41-43, anodized.

2. Trunking base, INKA-101/72, see Service carriers, page 26, anodized F80® front with foil M03 red beech

3. Power and Communication type CYB.4. Gas profile, with Medaes gas outlets, see page

44, anodized5. Cover for gas pipe, TRL, see page 46, anodized.

P215

0Many Combinations Give Freedom Of Choice

1

2

3

4

5

Page 9: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 9

A12

490

A12

480

A10

030

Lighting profile and gas pipe cover in full length. Lighting profile in full length and gas pipe cover of TRL type.

A12

500

A12

470

Cut-to-length lighting profile and gas pipe cover in full length. Cut-to-length lighting profile and gas pipe cover of TRL type.

Medical Ward Unit installation with lighting profile and gas pipe cover in full length. Accessory rail for attachment of gas and otherhospital equipment.

Page 10: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

10 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Complete Access and Outlet Program

General and Reading/Examining LightingGas outlets for different standards

Our assortment includes outlets corresponding toScandinavian (AGA), German (Dräger, Greggersen)and British (Medaes) standards. The gas outlets areself-closing and the gas flow cuts off when equipmentis disconnected from the quick coupling.

The outlets are gas-specific according to the differ-ent hospital standards, which means that connectionto the wrong outlet is impossible.

The selection includes outlets for breathing oxygen,nitrous oxide, breathing air, vaccum, etc.

There are lighting rails for different light requirements.

The lighting profile can be fitted with various lightingrails for general light (indirect), reading/examiningand night light.

General light is available in various lengths withstandard fluorescent tubes type T26 or new technolo-gy tube type T5. Reading/examining light is of stan-dard compact tube type TC.

As a supplement to the permanent lighting there aretwo types of bed/examining lamps by Luxo andSunnex for table or wall mounting.

The ultimate task of a properly designed MedicalWard Unit is to offer the exact function that the nurs-ing situation calls for.

FrontLine Hospital Trunking offers a complete selection of every conceivable outlet and connectionfor electricity, telecommunications, data, gas andlighting.

P480

8P2

154

P480

9

Page 11: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 11

Power and Communication, type CYB

Call system Mix-up proof labelling

Almost any of the existing call systems can be inte-grated into the Thorsman Medical Ward units. Diff-erent types of patient call units are easily mountedinto the Thorsman Medical Ward Unit, giving thepatient quick access for emergency calls.

Outlets and connections for power, telecommunica-tions and data have distinct labelling panels. Labellingis applied to the mounting frame behind the coverplate. This means that labelling remains even if thecover plate is removed, thus eliminating risk of a mix-up when refitting.

Service content of type CYB contains outlets and con-nections for power, telecommunications and data net-works. The CYB outlet cover plate has a completelysmooth surface which facilitates cleaning.

The power outlet can be delivered colour-coded inwhite, green or red in order to differentiate normalpower from disruption-free or priority power.

P3827P215

5P2

152

Page 12: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

12 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

S133

80

Cable trunkingA1 Trunking base, INKAA2 Stop end, trunking baseA3 Front cover

LightingB1 Lighting profileB2 Stop end, lighting profileB3 Light fitting rail, TCB4 Compact flourescent tube, TCB5 Prismatic shadeB6 Front coverB7 Light fitting rail, T26, T5 (Light tube section)B8 Light fitting rail , T26, T5 (Ballast section)B9 ReflectorB10 Flourescent standard tube, T26, T5B11 Up-light cover

GasC1 Fixing profile, gas outletsC2 Mounting adapterC3 Gas outletC4 Front cover, gas outlet profileC5 Wall bracket, gas pipe profileC6 Mounting plate with pipe clampsC7 Stop end, front coverC8 Front cover, gas pipe profileC9 Stop end, front cover (gas pipe cover TRL type)C10 Base clampC11 Gas pipe cover TRL type

Design and Dimensions

D14

060

A1

A2

A3

B1

B2 B3

B4

B5

B6

B7

B8

B9B10

B11

C1C2

C3C4

C5

C6

C7C8

C9

C10C11

Page 13: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 13

Medical Ward Unit in Common Ward

Medical Ward unit with lighting profile only. The unit includesgeneral and reading light and a limited number of electrical

functions. Suitable for common wards in hospitals, nursinghomes and sanatoriums.

Medical Ward unit with lighting profile in full length and gaspipe cover of TRL type. Suitable for common wards in hospitals.

Easy to upgrade with additional electrical and gas functionsafter installation.

Medical Ward Unit with lighting profile and gas pipe cover infull length. Accessory rail for attachment of gas and other hospi-tal equipment. INKA cable trunking in two compartments,

where the lower compartment is screened off by an integral par-tition. Suitable for common wards in hospitals.

A10

050

A10040

A10

370

A10

060

A10

390

A10

380

Page 14: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

14 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Medical Ward Unit in Intensive Care

Medical Ward Unit with INKA cable trunking in two compart-ments and gas pipe cover in full length. Possibility for a large

number of electrical and gas functions. Double accessory railsystem with monitor shelf and examining lamp.

Ceiling mounted Medical Ward Unit for one or several patientbeds. The electrical, lighting and gas sections can be double-sideequipped.*

A10

400

A10

410

Wall mounted IC unit

Ceiling mounted IC unit

* Ceiling and Floor/Ceiling mounted Intensive Care units arecustomer specific solutions and are offered on special request

Page 15: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 15

Floor/ceiling mounted Medical Ward Unit with possibility ofmaximizing number of electrical and gas functions. The vertical

as well as the horizontal sections can be double-side equipped.*

A10

590

Floor/Ceiling mounted IC unit

* Ceiling and Floor/Ceiling mounted Intensive Care units arecustomer specific solutions and are offered on special request

Page 16: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

16 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Cable Trunking DesignAluminium cable trunking for wall surface and flushmounting. Cable shelves can be used to divide thetrunking into various compartments, so that powerand low current cables can be routed in the sametrunking as telecommunications and data cables.Several cable trunking products, e.g. INKA-161-2 and

INKA-217-2 are two-compartment systems, in whichthe lower compartment is screened off by an integralpartition. Both compartments have separate flushfront covers. Earthing slots are provided in trunkingbase and front cover.

For Cable capacity information, see page 50-58.

L388

80

R332

10M

L388

90

R324

80M

R332

20

L389

00

R324

30M

INKA-123/72 and -123/90For wall surface mounting.

INKA-101/72 and -101/90For wall surface mounting.

INKA-123-4/72For flush mounting.

R325

00M

R332

50M

L389

20

INKA-161-2/72 and -161-2/90For wall surface mounting. Two screened compartments with separate front covers.

R332

30M

Page 17: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 17

R327

80M

R332

60M

INKA-183-2/90For wall surface mounting. Two screenedcompartments with separate front covers.

R331

70M

R332

90M

R332

80M

INKA-161-3/72 and -161-3/90For wall surface mounting.

L478

90L4

7920

INKA-217-2/72 and -217-2/90For wall surface mounting. Two screened compartments with separate front covers.

L283

70

Page 18: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

18 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Composition of Lighting ProfileThe Medical Ward Unit offers many possible varia-tions for installation of reading/examining light aswell as general light. This makes it possible to obtainthe right lighting environment for varying ward re-quirements.

Fitting the lighting profile around the entire roomgives maximum space and flexibility for lightinginstallation.

General LightA suitable number of lighting rails can be fitted in theupper compartment of the profile for general (indi-rect) light. The indirect light can be of standard fluor-escent tubes of type T26 (36 or 58W). Alternativelythe new technology fluorescent tubes of type T5(28W or 54W) can be chosen. The lighting rails caneither be installed with standard or electronic ballasts.There is also space for a 5W night light in these rails.

Reading/Examining LightLighting rails for reading/examining are installed inthe lower compartment over the respective beds. Thereading/examining light uses standard compact TCtubes (18 W or 36 W) with either standard or elec-tronic ballasts. The TC 36 W compact tube may alsobe installed with a dimmable feature for adjustment asa reading or examining light.

Lighting Profile DimensionsThe lighting profile can be cut to length for a smallerunit and fitted with stop ends for mounting over abed. Whether the general light is to be provided bystandard fluorescent tubes of type T26 or of type T5,the minimum length (L) for cutting the lighting pro-file can be seen in Figure 1.

Type L

T26 36W 1400

T26 58W 1700

T5 28W 1250

T5 54W 1250

L = Length of lighting profile excluding stop ends (2x2mm)

General light - Minimum dimensions (mm)

Type L1

TC 18W 200

TC 36W 400

TC 36W dimmable (1-10V) 400

Reading/Examining light (mm)

L

L1

A10

600

Figure 1 – Lighting Profile

Page 19: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 19

Placement of Light Fitting Rail

T5 TubesThe new T5 fluorescent tubes are characterized by areduced cross-sectional dimension (16 mm). Themore conventional T26 tubes are 26 mm in diameter.More important are the economical advantages of theT5 tubes:• Higher luminous efficiency• Optimized thermal behavior• Longer Lamp service life

Electronic BallastsAll fluorescent tubes can be connected to electronicballasts (35000 Hz). Lighting with electronic ballastsgives an energy saving of about 25% compared tostandard ballasts (50Hz). The lamp service life of thefluorescent tube increases by up to 50%.

A10

610

Figure 2 – Placement of Light Fitting Rail into the Lighting Profile

Type A B C

TC 18W 550

TC 36W 830

TC 36W dimmable 830

T26 36W 1300 400

T26 58W 1600 400

T5 28W 1230 400

T5 54W 1230 400

The Light Fitting Rail of type TC (A) is always in onesection and is installed in the lower compartment ofthe lighting profile.

The Light Fitting Rail of type T26 or T5 is dividedinto two sections. The Light Tube section (B) isinstalled in the upper compartment of the LightingProfile. The ballast section (C) can be installed in the

lower compartment for a short lighting profile sectionor in the upper compartment for a long lighting pro-file section.

All rails are provided with push-in termination foreasy wiring. For selection of Light Fitting Rail, seepage 41.

Length of Light Fitting Rail (mm)

Page 20: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

20 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Lighting Techniques

General LightGeneral lighting is indirect, creating a comfortableatmosphere by the use of non-dazzling illumination.Fluorescent lamps in either T26 (36 W or 58 W) or T5(28 W or 54 W) format may be used.

The use of fluorescent lamps conserves energy whileproviding the required illumination intensity. Thewarm-white colour of the light helps provide a senseof comfort and well being.

Reading LightThe reading light is placed above each bed. The choiceis either a TC 18W or 36W compact tube. The statio-

nary reading light gives a non-dazzling light withoutdisturbing other patients in the same room.

A10

630

A10

620

1) Reading level 2) Examining level 3) Bed level.

* with indirect room light T26 36W

* with indirect room light T26 36/58W

The values stated below are valid for a 2-bed room. Room dimensions are L=4.5 m, W=4 m, H=2.5 m.

1)

2)

3)

Light Dispersion Measuring Levels

DIN 5035 Part 3 2 x T26 36W 2 x T26 58W 2 x T5 28W 2 x T5 54W

Medium intensity of illumination 100 lx 103 lx 144 lx 103 lx 174 lx

DIN 5035 Part 3 1 x TC 18W* 1 x TC 36W

Medium intensity of illumination on the reading surface (75º) 200 lx 231 lx 354 lx

DIN 5035 Part 3 1 x TC 18W * 1 x TC 36W *alt. dimmable*

Medium intensity of illumination at bed length 300 lx 327/392 lx 537/622 lxaxis, 0,85m above floor

Minimum intensity of illumination at bed length axis ≥ 150 lx 155/198 lx 193/253 lx

Examining light

When examining and attending the patient in bed, acertain intensity of illumination is required. These

lighting values are achieved when both the generallight and the reading light are turned on.

Page 21: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 21

350300

250

200

150

100

50 50

General light 2 x T26 36WReading/examining light 2 x TC 36WMedium intensity of illumination 246 lx

350300

250

200

150

100

General light 2 x T5 54WReading/examining light 2 x TC 36WMedium intensity of illumination 347 lx

Isolux diagram, 2-bed roomRoom dimensions: Length 4.5 m x Width 4.0m x Height 2.5 m.

Reflexion values: 0.8 Ceiling, 0.5 Wall, 0.3 FloorMeasuring height 0.85 m.

DIN 5035 Part 3 5W bulb Light diode unit

Medium intensity of illumination at bed 5 lx ≥ 5 lx ≤ 5 lx

Night lightThe night light helps the hospital staff to move in theroom without switching on the main lighting. Thenight light can be a 5W bulb fastened on the Light

Fitting Rail. It can also be a light diode unit produc-ing 5 lx at short distance.

Page 22: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

22 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Gas Outlet Installation Techniques

The gas outlet is fixed on a wall-mounted fixing pro-file, the gas outlet cover is snap-fitted on to the fixingprofile.

The gas outlet cover profile is designed to providelarge capacity for gas piping. The cover is prepared forchoice of 1,2,3, or 4 gas outlets, see page 45. For moregas outlets a combination of these covers is possible.

The positioning of the gas outlets is prepared forc/c measure of 200 mm. This distance is suitable togive appropriate space for a smooth installation andgas pipe connection.

150

900

200 200 200 150

150

700

200 200 150

150

500

200 150

150 150

300

A10

640

The Medical Ward Unit is normally installed as one entire unit. If preferred, the gas outlet profile can be installed separately from theelectrical and lighting section.

A10

650

The Thorsman Medical Ward Unit offers the possibil-ity to include gas outlets to Scandinavian, Germanand British standards. The selection includes outlets

for breathing oxygen, nitrous oxide, breathing air, gasexit, vacuum and instrumental air, see page 44.

Figure 1 – Positioning of gas outlets

Page 23: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 23

Gas Outlet Installation TechniquesThe gas pipe cover comes in two designs, depending upon how many outlets are required.

1. For a limited amount of gas outlets the gas pipe cover can be of TRL type.

2. For a large number of gas outlets , a full length gas pipe cover is recommended for piping capacity.

500 200 600

A10

670

A10

660

900 200 600

A10

690

A10

680

Gas connection standards

Different standards for gas connection are used in var-ious countries. Common to the different standards isthe unique adaptation technique in combination witha colour code, preventing connection of the wrongtype of equipment to the wrong gas type.

The program offers gas outlets according toScandinavian, German (DIN, two types) and British(BS) standard. The flexible mounting technique alsomakes it possible to mount gas outlets according toadditional standards or local brands.

Page 24: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

24 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Layout PlanningThe Thorsman Medical Ward Unit (MWU) can to alarge extent be adapted to the existing room dimen-sions. In the layout planning phase there has to bepaid attention to certain minimum dimensions whenspecifying the Medical Ward Unit.

The graphics below visualizes a layout of a MedicalWard Unit for up to 3 beds. The length of the MedicalWard Unit is mainly depending on the lighting alter-native chosen. The dimensions marked in the graphicsare of importance when deciding the total installation.

Dimensions:A Distance from the left end of the MWU until centre of the reading light.B Distance between centre of reading lights for two beds.

Recommended minimum distance is 1600 mm.C Distance from the right end of the MWU until centre of the reading light.L Total length of the MWU.H Mounting height from floor to top end of the MWU.

Recommended distance is 1800 mm.

No of General Light Reading Minimum dimensions* mmbeds Light A B C L

1 1 x T26 36W TC 18 or 36W 700 700 14002 2 x ” ” 700 1600 700 30003 3 x ” ” 700 1600 700 4600

1 1 x T26 58W ” 850 850 17002 2 x ” ” 850 1700 850 34003 3 x ” ” 850 1700 850 5100

1 1 x T5 28/54W ” 625 625 12502 2 x ” ” 625 1600 625 28503 3 x ” ” 625 1600 625 4450

H

A10

710

The minimum dimensions per 1, 2, 3 beds is depending on the general light chosen, see table below:

*) Dimensions excluding stop ends (2 x 2 mm)

Page 25: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 25

All Thorsman service carriers maybe powder coated in any NCS orRAL colour with any gloss value.

Below you will find 19 of ourstocked colours, in which our pro-ducts can be powder coated anddelivered on short notice.

All other RAL or NCS coloursare to be offered on special request.

When ordering products in astocked colour, use the three charac-ter code which specifies both colourand gloss, eg L01 (=RAL 9010, Semigloss). Place the code immediatelyafter the article number.

P3601

RAL 9010Code: L01 Semi gloss Code: L02 High gloss, L03 Textured*

RAL 6026 Code: L71 High gloss

Stocked NCS colours

NCS S 6030-R70B Code: L56 Semi gloss

Stocked RAL colours

RAL 7035Code: L22 High gloss

NCS S 2502-YCode: L31 Semi gloss

RAL 9007 Code: L23 High gloss

RAL 1018 Code: L61 High gloss

RAL 1013 Code: L06 High gloss

Note: For technical reasons due to the printing process, the colour representations may deviate slightly from the reference colours. There mayalso be slight differences in shade between batches delivered, even with the same NCS/RAL code. If colour matching with other products isimportant, please contact Thorsman customer service.

NCS S 0580-Y10R Code: L65 Semi gloss

NCS S 3060-BCode: L55 Semi gloss

NCS 0402-B91G(≈NCS S 0500-N)Code: L11 Semi gloss

RAL 5024

A selection of non-stocked NCS coloursA selection of non-stocked RAL colours

RAL 1017 NCS S 1005-Y80RNCS S 1010-G03Y

Non-stocked RAL or NCS colours may be offered on special request.

Colour Choice

Page 26: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

26 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Service Carriers

1)Colour choice, see page 25.

Trunking bases

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Trunking base, INKA-101/72Can be divided into four compartments. With earthing slot.Available cut to length, max 5.0 m by special order.

INKA-U101 Anodized Aluminium 100/72/2500 5504 000Powder coated1) 5504 002

Trunking base, INKA-123/72Can be divided into four compartments. With earthing slot.Available cut to length, max 5.0 m by special order.

INKA-U123 Anodized Aluminium 123/72/2500 5507 000Powder coated1) 5507 002

Trunking base, INKA-123-4/72Can be divided into four compartments. With earthing slot. Available cut to length, max 5.0 m by special order. Also suitable as feeder trunking.

INKA-U123-4 Anodized Aluminium 145/72/2500 5506 310Powder coated1) 5506 319

Trunking base, INKA-161-2/72Can be divided into five compartments. Includes compartment for telephone communications, datacables, etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.Earthing slot provided. Available cut to length, max 5.0 m by special order.

INKA-U161-2 Anodized Aluminium 161/72/2500 5510 010Powder coated1) 5510 012

Trunking base, INKA-161-3/72Can be divided into four compartments. With earthing slot.Available cut to length, max 5.0 m by special order.

INKA-U161-3 Anodized Aluminium 161/72/2500 5510 020Powder coated1) 5510 022

Trunking base, INKA-217-2/72Can be divided into eight compartments. Lower compartment for telecommunications, data cables,etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.Earthing slots provided. Available cut to length, max 5.0 m by special order.

INKA-U217-2 Anodized Aluminium 217/72/2500 5514 000Powder coated1) 5514 002

Trunking base, INKA-101/90Can be divided into four compartments. With earthing slot.Available cut to length, max 5.0 m by special order.

INKA-U101 Anodized Aluminium 100/90/2500 5519 010Powder coated1) 5519 012

Trunking base, INKA-123/90Can be divided into four compartments. Earthing slot provided.Available cut to length, max 5.0 m by special order.

INKA-U123 Anodized Aluminium 123/90/2500 5506 400Powder coated1) 5506 402

L317

00L3

1400

L327

30L3

1450

L313

00L3

1250

L310

20L3

1090

Page 27: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 27

Type/ Colour/ Materal Dimensions Art. No.Description Finish A/B/C (mm)

Front coverFCA-F40, F80. Snap-fit fastening onto trunking. With earthing slots.

FCA-F40 Anodized Aluminium 40/2500 5580 030Powder coated1) 5580 039

FCA-F80 Anodized Aluminium 80/2500 5580 080Powder coated1) 5580 089

Service carriers

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Trunking base, INKA-161-2/90Can be divided into five compartments. Includes compartment for telecommunications, data cables,etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.Earthing slots provided. Available cut to length, max 5.0 m by special order.

INKA-U161-2 Anodized Aluminium 161/90/2500 5519 020Powder coated1) 5519 022

Trunking base, INKA-161-3/90Can be divided into four compartments. With earthing slot. Available cut to length, max 5.0 m by special order.

INKA-U161-3 Anodized Aluminium 161/90/2500 5512 230Powder coated1) 5512 232

Trunking base, INKA-183-2/90Can be divided into six compartments. Includes compartment for telecommunications, data cables,etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.Earthing slots provided. Available cut to length, max 5.0 m by special order.

INKA-U183-2 Anodized Aluminium 183/90/2500 5519 060Powder coated1) 5519 062

Trunking base, INKA-217-2/90Can be divided into eight compartments. Includes compartment for telecommunications, datacables, etc. The trunking is pre-punched every 200 mm between the lower and upper compartment.Earthing slots provided. Available cut to length, max 5.0 m by special order.

INKA-U217-2 Anodized Aluminium 217/90/2500 5519 040Powder coated1) 5519 042

L441

90

Front covers

L308

40L3

0830

1)Colour choice, see page 25.

Trunking bases (cont.)L3

1170

L327

90L3

1240

Page 28: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

Service carriers

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Cable shelfUsed to divide the trunking into a maximum of eight compartments. Cable shelves are used forimproved segregation and screening between power, low current, telephone and data cables.

KH72 for 72 mm deep and KH90 for 90.

TTI-KH72 Anodized Aluminium 12/72/500 5590 312TTI-KH72 Unspecified PVC 12/72/500 5590 314TTI-KH90 Untreated Aluminium 12/90/500 5590 315TTI-KH90 White PVC 12/90/500 5590 316

Cable clipSnap-fitted on cable shelf. Prevents cables falling out of trunking compartment before front cover is installed.

TTI-KHK Brown ABS - 5590 340

Mounting washerUsed when mounting the trunking directly on the wall. The carrier is hung on a number of mountingwashers before being secured to the wall with screws.

TTI-MB Black PA 16/6/19 5590 180

28 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Stop endStop ends including screws for fixing and angle brackets (for 72 mm deep trunking only). The anglebrackets are inserted in the jointing piece rails (for INKA-101 also into the earthing rail). Stop endsare used to terminate cable trunking and to limit electric fields.

INKA-ES101/72 Powder coated1) Aluminium/Steel2) 100/72/51 5504 172

INKA-ES123/72 Powder coated1) Aluminium/Steel2) 123/72/36 5507 172

INKA-ES161/72 Powder coated1) Aluminium/Steel2) 161/72/36 5510 172

INKA-ES217/72 Powder coated1) Aluminium/Steel2) 217/72/36 5514 172

INKA-ES101/90 Powder coated1) Aluminium 100/90 5590 217

INKA-ES123/90 Powder coated1) Aluminium 123/90 5591 152

INKA-ES161-2/90 Powder coated1) Aluminium 161/90 5590 277

INKA-ES161-3/90 Powder coated1) Aluminium 161/90 5591 062

INKA-ES183-2/90 Powder coated1) Aluminium 183/90 5591 032

INKA-ES217-2/90 Powder coated1) Aluminium 217/90 5590 307

Stop endINKA-ESV123-4/72 Powder coated1) Aluminium 5590 203Left

INKA-ESH123-4/72 Powder coated1) Aluminium 5590 208Right

Stop endsL3

2010

L320

20

1) Colour choice, see page 25.2) If trunking base in anodized finish is being used, powder coated stop end in ’RAL 9007’ is recommended.

Trunking Accessories

L325

70L3

2410

L460

40L5

3540

Page 29: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Jointing pieceFor jointing trunking.

INKA-SSA Untreated Aluminium 8/32/60 5590 112

Earthing clampFor bonding the front cover, trunking base and accessories to earth.

TTI-JB Zinc passivated Steel – 5590 500

Earth wireFor bonding the front cover, trunking base and accessories to earth.

TTI-JK300 Green/Yellow Copper Length = 300 mm 5590 505

Sound insulation stripFor sound insulation of up to 53 dB where trunking passes through walls. Suitable for up to fourcompartments. Supplied in sets of four.

TTI-T3045 Black Foam rubber 30/350/45 5590 410TTI-T5070 50/350/70 5590 414

Cup washerFor covering screw heads and protecting the cable.

TTI-KB Black PE Ø 13 5590 520

GrommetTo cover edges where cables passes between trunking base and lighting profile. Provides a hole ofØ 19 mm for cable entry. (Use plunge tool ISV-HS, see page 43).

INKA-GF19 White PP Ø 20 5902 100

Edge protectionTo protect cables from sharp edges when a small gap is left between two aluminium trunking bases.

INKA-KD82 Transparent PE – 5902 120

Locking plateTo fix various equipment directly to the trunking.

TTI-GM Grey PA – 5586 600

WasherFor insertion between cable trunking/lighting profile/gas profile and wall to compensate for uneve-ness in the wall.

TTA-KM1 Grey PA 114/1/38 5583 405TTA-KM3 114/3/38 5583 408TTA-KM5 114/5/38 5583 410

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 29

L126

00Trunking Accessories (cont.)

L448

50L5

1170

L333

70L3

3380

L333

90L3

4520

L330

90L3

2140

Service carriers

Page 30: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

30 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Connection kit Single earthed socket outlets, Schuko 90°Includes box, adapter, 2x strain relief clamps, cover, label and label window. The socket has push-in terminals.

With child protectionCYB-PS White PC/ABS 84/52/84 5975 000

With child protection and LED indication, greenCYB-PS White PC/ABS 84/52/84 5975 005

Connection kit Double earthed socket outlets, Schuko 37°Includes box, adapter, 2x strain relief clamps and cover. The socket has push-in terminals.With label and label window. (The different colours may be used for special outlet designation e.g., priority power)

With child protectionCYB-PS White PC/ABS 84/46/110 5951 480

Red 5951 482Green 5951 485Orange 5951 487

Connection kit Three-gang earthed socket outlets, Schuko 37°Includes box, adapter, 2x strain relief clamps and cover. The socket has push-in terminals.With label and label window.(The different colours may be used for special outlet designation e.g., priority power)

With child protectionCYB-PS White PC/ABS 84/46/142 5951 430

Red 5951 432Green 5951 435Orange 5951 437

Power

Connection kits, Schuko

L465

10L4

6520

L589

20

1. Angled corners for simple cable entry with two adjoining boxes

2. Snap-fitting to F80™ front opening. Fits all FrontLine service car-riers.

3. Strain relief clamps without screws

4. Large label window, 66 x 10 mm, for fixed mounting in the box

5. Opening for label window

6. Bridging terminal 4 x 2.5 mm2. Push-in.

7. Outlet recesses angled at 37°

8. Child protection

ColoursWhite = NCS 0701-G46Y ≈ RAL 9016Red = RAL 3003 ≈ NCS 3163-Y97RGreen = RAL 6029 ≈ NCS 3658-G03Y

1 2

3

6

4

87

5

P215

8L5

7350

Page 31: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 31

Power

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

French Standard, for Poland and France (with Push-in terminals)CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps andspacer.

CYB-PF White PC/ABS 84/45/110 5969 215CYB-PF Red 84/45/110 5969 217

French Standard, for Belgium, Poland and France (with screw terminals) CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps andspacer.

CYB-PF White PC/ABS 84/45/110 5969 210CYB-PF Red 84/45/110 5969 212

French Standard, for Czech Rep., Poland and France (with Push-in terminals)CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps andspacer.

CYB-PF White PC/ABS 84/45/110 5969 115CYB-PF Red 84/45/110 5969 117

French Standard, for Czech Rep., Poland and France (with screw terminals) CYB-outlet. Two-gang, 16A/250V. Includes double earthed socket, box, strain relief clamps andspacer.

CYB-PF White PC/ABS 84/45/110 5969 110CYB-PF Red 84/45/110 5969 112

Connection kits, Double socket, French Standard

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Connection kit, Power, single, 13 ASnap-fastened 13 A single standard outlet, consisting of CYB-S40 box, outlet, adapter and frontplate. The outlet can be mounted either horizontally or vertically. Used as single outlet, in conjunc-tion with CYB outlets for power, telecommunication, data and blank covers.

CYB-PU, unswitched White PC/ABS 84/47/84 5961 130

CYB-PU, switched White PC/ABS 84/50/84 5961 120

CYB-PU, switched White PC/ABS 84/50/84 5961 140with indicator

Connection kit, power, twin, 13 A Snap-fastened 13 A double standard outlet, consisting of box CYB-D40, outlet, adapter and frontplate. Used as double outlet, in conjunction with CYB outlets for power, telecoms, data and blankcovers.

CYB-PU, unswitched White PC/ABS 84/47/142 5961 135

CYB-PU, switched White PC/ABS 84/50/142 5961 125

CYB-PU, switched White PC/ABS 84/50/142 5961 145with indicator

Connection kits, British Standard

L578

20L5

7830

L445

20L4

4510

L445

00L4

4550

L445

30L4

4540

Page 32: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

32 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Connection kit, Surge protection

Type/ Colour/ Material Dimensions Art. No. Description Finish A/B/C (mm)

Connection kit with overvoltage protection 16 A/230 V, TN systemCYB-PP connection kit with overvoltage protection is suitable for 230 VAC and TN system.The protection is intended for individual workplaces and not for entire buildings or installations. Theprotection has a built-in acoustic alarm and external indications for operation and overloading. Theacoustic alarm is controlled with the aid of a switch mounted in the front. The protection can alsobe monitored by a circuit-opening contact for connection to a monitoring centre, for example.

CYB-PP White PC/ABS 84/53/84 5972 010L535

10

Power

Basic kit, CEE socket outlets

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

CEE socket outletsPower socket outlets including mounting frame for 80 mm front (F80®) opening. To be used in con-junction with Thorsman MIB-box.

Single-phase CEE216-6, 250 V/16 A for cable 3x1.5 mm2

CYB-C220 Grey/blue PC 82/49/82 5960 110

Three-phase CEE416-6, 440 V/16 A, for cable 5x2.5 mm2

CYB-C380 Grey/red PC 82/57/82 5960 100

L281

90L2

8200

Connection kit, SwitchesType Closed Colour/ Material Dimensions Art. No.Description position Finish A/B/C (mm)

Connection kit, Switches, 16A/250VIncludes box, socket, adapter, two strain relief clamps, cover with rocker, label with label window.

Single-poleCYB-PB Up White PC/ABS 84/54/84 5980 002

Single-pole, spring-return rocker CYB-PB Up White PC/ABS 84/54/84 5980 007

Single-pole, red indicator lamp CYB-PB Up White PC/ABS 84/54/84 5980 012

Single-pole, green indicator lamp CYB-PB Up White PC/ABS 84/54/84 5980 017

Double-pole CYB-PB Up White PC/ABS 84/54/84 5980 032

Single-pole/two-wayCYB-PB Up White PC/ABS 84/54/84 5980 052

IntermediateCYB-PB Up White PC/ABS 84/54/84 5980 062

L573

70

Page 33: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 33

Power

Type Closed Colour/ Material Dimensions Art. No.Description position Finish A/B/C (mm)

Connection kit, switches, 16 A/250 VIncludes box, socket, adapter, two strain relief clamps, cover with two rockers and label with labelwindow.

Two-gangCYB-PB Up White PC/ABS 84/54/84 5980 072

Venetian blindCYB-PB Up White PC/ABS 84/54/84 5980 087

Venetian blind, single-pole switchCYB-PB Up White PC/ABS 84/54/84 5980 082

Double single-pole/two-wayCYB-PB Up White PC/ABS 84/54/84 5980 057

Pilot lamp 0.9 mA 250 VIntended to be mounted together with switch.

CYB-GL2 16/25/39 5972 105

Push-in plintFor single socket outlets, switches and dimmers. 16A/250V, 3x2,5 mm2.

CYB-PT White 10/10/14 5972 200

L573

60L5

7480

Connection kits, Switches (cont.)

Wiring diagrams for switches

Single-pole (1)Single-pole with spring-return (1)

Double single-pole/two-way (6/2)

D13

900

D13

920

D13

930

D13

970

D13

910

D13

940

D13

960

D13

990

Venetian blind

Venetian blind single-poleTwo-gang (5)Intermediate (7)Single-pole/two-way (6)

Double-pole (2)Single-pole with indication (1)

D13

950

D13

980

L589

40

Page 34: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

Type/ Colour/ Material Dimensions Art. No. Description Finish A/B/C (mm)

Dimmers To control fluorescent light fittings with controllable HF units. 1-50 HF units can be controlled. Thepositive and negative poles of the controller must be connected to the positive and negative polesof the HF unit. Poles 1 and 2 of the switches are wired to switch the fittings on and off. The breakfunction is rated at max 6 A (max 360 W fluorescent tube rating). If the load is higher, the breakfunction can control a relay coil instead. Note that the fluorescent tubes must not go out at the mini-mum setting of the controller. Rating 1-10 V for 1-50 HF units made by Philips, Osram, Siemens,Helvar, etc. To be connected to the plus and minus connections of the controller. Note that it is very important to observe correct polarity throughout the installation.

Controller 1-10 V (APE 10 T).CYB-PR White PC/ABS 84/53/84 5985 020

For incandescent lamps and electronic transformers, 300W (ATD 300R).CYB-PR White PC/ABS 84/53/84 5985 000

For incandescent lamps and conventional transformers, 400W, VA (AD 400UTT).CYB-PR White PC/ABS 84/53/84 5985 030

For incandescent lamps, fluorescent lamps with dimmable electronic ballast and conventional trans-formers, 900W, VA (ATTD 1000RL).

CYB-PR White PC/ABS 84/53/84 5985 050

34 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Power

Type/ Colour/ Material Dimensions Art. No. Description Finish A/B/C (mm)

Mounting boxFor the installation of power and low-current equipment in FrontLine service carriers with 80 mmfront (F80™). When fitted with screw pillars CYB-P40, the box is also suitable for standard socketoutlets with centres to BS 4662:1970 and with screw pillars CYB-P3 for 60 mm centres.

Single box with ten 16 mm knockoutsCYB-S40 White PC 79/44/84 5961 030

Double box with fourteen 16 mm knockoutsCYB-D40 White PC 79/44/142 5961 035

Blanking coverBlanking cover for snap fitting. Includes adapter and front plate. Fits CYB-S30 and CYB-S40. Toblank off mounting boxes for future expansion of electrical installations.

Blanking cover, singleCYB-PL White PC/ABS 84/12/84 5961 550

Blanking cover, doubleCYB-PL White PC/ABS 84/12/142 5961 555

Mounting boxes and blank covers

L443

50L4

4360

Connection kit, Dimmers 230V, F80 Mounting

L578

40

Type/ Colour/ Material Dimensions Art. No. Description Finish A/B/C (mm)

Light Diode KitThe light diode kit consists of 8 pcs. high intensity diode in a CYB mounting frame with protectivecasing. For night light in common ward. Available autumn 1999.

CYB-PO angled White PC/ABS 84/50/84 5974 010

Connection kitL5

9000

L443

80L4

4370

Page 35: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 35

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Screw pillarsScrew pillars which snap-fit to CYB-D40 and CYB-S40 boxes, so that standard socket outlets can befitted. CYB-P40 to British standard, and CYB-P3 for 60 mm centres.

CYB-P40 White PA 14/12/37 5961 505CYB-P3 10/11/42 5961 506

Adapter, for flexible conduitFor snap-fitting flexible conduit as a protective cable conduit. CYB-D20 is used for 20 mm, CYB-D25 for 25 mm flexible conduit.

CYB-D20 Black PA,PP Ø 26/24 5956 250CYB-D25 Ø 29/26 5956 255

Earthing terminalUsed in CYB-S30/D30 and S40/D40 mounting boxes. The earthing terminal can take 2x4 mm2

cable.

CYB-ET Natural Brass – 5961 500

Conduit bushFor use between CYB mounting boxes, mounted directly beside each other for protection of cables.

CYB-CT PC/ABS 5961 510

Strain relief Used when connecting power cable to box. Snap-fits in the recess of the CYB box.

FDS Orange 25/27/17 5956 150

Installation boxesSingle and double installation box intended for mounting of standard devices in front F80® servicecarriers, MIB-A1 for devices with a c/c distance of 60 mm and MIB-A2 for a c/c distance of 71mm. Can be combined with junction box MIB-J.

MIB-A1 White PC/ABS 79/45/71 5586 150

MIB-A2 White PC/ABS 79/45/152 5586 155

L443

90

Power

L163

10L4

6080

Accessories for Mounting boxes and Mounting kitsL3

4510

L454

00L5

9810

L598

00

Page 36: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

36 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Power

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Mounting kit for other types of socket outletsIncludes mounting box and universal adapter for socket outlets according to DIN 49075.

CYB-MB White PC/ABS 84/50/84 5971 790

CYB-MB White PC/ABS 84/50/84 5971 794L133

00L4

6940

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Equipotential connectionEquipotential connection in front cover F80®. For potential balancing, max. 63A or according toDIN standard. Pole marking yellow/green.

CYB-PO, (max 63 A) Anodized Aluminium 80/-/110 5971 302Powder coated1) 5971 301

CYB-PO, DIN Anodized Aluminium 80/-/110 5971 307Powder coated1) 5971 306

Equipotential connection kitEquipotential connection kit for snap-in mounting in service carriers with front cover F80®. For potential balancing according to DIN standard 42801.

CYB-PO, DIN White PC/ABS 84/28/84 5971 315

Plug for equipotential connection. DIN type

CTA-PO 5914 050

L505

40L5

0820

Mounting kit for accessories (other suppliers)

Equipotential connection

1)Colour choice, see page 25.

L642

30L6

4280

Page 37: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 37

Type/ Colour Dimensions Art. No. Description A/B/C (mm)

Circuit breakersMiniature circuit breakers (MCB) 6 kA according to DIN VDE 0641, Part 11/08.92 and EN 60 898, B- and C- characteristics. Rated current 10 A and 16 A. 1, 2, 3-poles (1-2-3 DIN modules). To be mounted in CYB-PN DIN-enclosure. Material: ABS.

CYB-PN, 1-pole, C10A Grey 90/74,5/18 5960 480CYB-PN, 1-pole, C16A 5960 485CYB-PN, 2-pole, B10A Grey 90/74,5/36 5960 460CYB-PN, 2-pole, C10A 5060 490CYB-PN, 2-pole, B16A 5960 465CYB-PN, 2-pole, C16A 5960 495CYB-PN, 3-pole, B10A Grey 90/74,5/54 5960 470CYB-PN, 3-pole, C10A 5960 500CYB-PN, 3-pole, B16A 5960 475CYB-PN, 3-pole, C16A 5960 505

Earth leakage breakerResidual-current circuit breakers for pulsating direct and altering earth-leakage current according toDIN VDE 0644, Part 1/10.85. Resistance to surge current up to 250 A. Rated current 25 A. Ratedresidual current 0,03 A.2 and 4 poles (2 and 4 DIN modules). To be mounted in CYB-PN DIN-enclosure. Material: ABS. Colour: Grey.

CYB-PN, 2-pole Grey 84/74/36 5960 415CYB-PN, 4-pole Grey 84/74/72 5960 410

Power

Type/ Material Colour Dimensions Art. No. Description A/B/C (mm)

DIN enclosure4-module DIN enclosure intended for snap-in mounting in service carriers with front F80®. Theenclosure is suitable for 1-4 DIN modules and has a hinged lid to protect the devices.

CYB-PN PC/ABS White 84/86/168 5960 251

Same as above but with keylock and keys to lock the lid.

CYB-PN PC/ABS White 84/86/168 5960 256

L615

30DIN enclosures

L468

70

Circuit breakers

L615

40

Page 38: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Connection kit, LexCom 250, 125 UTP and STPFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

1 x Cat6 UTP, A/B White PC/ABS 84/50/84 5974 0902 x Cat6 UTP, A/B 5974 0951 x Cat6 STP, A/B 5974 1002 x Cat6 STP, A/B 5974 1051 x Cat5e UTP, A/B White PC/ABS 84/30/84 5970 9002 x Cat5e UTP, A/B 5970 9051 x Cat5e STP, A/B 5970 9102 x Cat5e STP, A/B 5970 915

Connection kit, Avaya (Lucent) MPS300, 100 UTPFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions. With built-in shut-ters.

1 x Cat6 UTP, A White PC/ABS 84/33/84 5970 960 2 x Cat6 UTP, A 5970 965 1 x Cat6 UTP, B 5970 870 2 x Cat6 UTP, B 5970 9751 x Cat5e UTP, A White PC/ABS 84/33/84 5970 800 2 x Cat5e UTP, A 5970 805 1 x Cat5e UTP, B 5970 810 2 x Cat5e UTP, B 5970 815

Connection kit, AMP110, Netconnect UTP and STPFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions. With built-in shutters.

1 x Cat6 UTP A/B White PC/ABS 84/33/84 5970 9302 x Cat6 UTP A/B 5970 9351 x Cat5e UTP A/B White PC/ABS 84/33/84 5970 8402 x Cat5e UTP A/B 5970 8451 x Cat5e STP A 5970 8502 x Cat5e STP A 5970 8601 x Cat5e STP B 5970 8552 x Cat5e STP B 5970 865

Connection kit, IBM ACS type C, UTP and FTPFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

1x Cat5, UTP White PC/ABS 84/50/84 5970 3552x Cat5, UTP 5970 3601x Cat5, FTP 5970 3652x Cat5, FTP 5970 370

38 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Communication

1. Extra distinct label 66x10 mm2 Label window to protect label (snap-fits into mounting frame)3. Connectors4. Snap-fitting cover5. Mounting frame for F80®. Suitable for horizontal or vertical

snap-fitting.6. Mounting frame which allows a full visual check of the complet-

ed installation 7. Modular mounting plate for angled or flush snap-fitting. With

facility for extra marking 21x4.7 mm8. Silk-matt glare-free easy-clean surface9. Protective cover for data connectors. Additional.

ColoursWhite = NCS 0701-G46Y ≈ RAL 9016P2

159

L553

10L5

5220

Connection kits, Data

L552

20L5

5300

1 23

6

4

8

7

5

L553

00

9

Page 39: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 39

Communication

Type/ Colour Material Dimensions Art. NoDescription A/B/C (mm)

Connection kit, LexCom fibre, multimode for fibre-based cable systemsFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, SC/SC adapter, label with label window, and termination instructions.

1 x SC-duplex, multimode White PC/ABS 84/50/84 5974 0002 x SC-duplex, multimode 5974 005

Connection kit, AMP SC and Avaya (Lucent) ST, multimode for fibre-based cablesystemsFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

2x ST, Multimode White PC/ABS 84/50/84 5970 3751 x SC-duplex, multimode 5970 3802 x SC-duplex, multimode 5970 385

Protective casing for fibre opticsFor mounting in FrontLine service carriers together with two CYB-BK sockets. Suitable for horizontalor vertical mounting, since outlets can be rotated in the casing.Copper and fibre cables can be connected to the casing. In the short side there is a breakout notchfor a cable nipple type BICC Brand-Rex Blolite system.

CYB-DF White PP 79/39/168 5971 220

Connection kits, fibre optics

Type/ Colour Material Dimensions Art. NoDescription A/B/C (mm)

Connection kit, IBM type 1, STP for structured cable systemsFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

1 x IBM type 1, STP White PC/ABS 84/50/84 5970 345

Connection kit, IBM type 2, STP for structured cable systemsFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

1x IBM type 2, STP and1 x 8-way modular socket White PC/ABS 84/50/84 5970 350

Connection kit, Krone Keystone for PremisNET structured cable systemsFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate with built-in dust shutter, label with label window, connector and termination instruc-tions. With built-in dust shutters.

1 x Cat5e UTP, B White PC/ABS 84/33/84 5970 760 2 x Cat5e UTP, B 5970 7651 x Cat5e STP, B 5970 7702 x Cat5e STP, B 5970 775

L552

70L5

5360

L552

20L5

5250

L552

60L5

5260

Connection kits, Data (cont.)

Page 40: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

40 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Communication

Type/ Colour/ Material Dimensions Art. NoDescription Finish A/B/C (mm)

Connection kits, modular socket Cat 5eFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

1x RJ45 White PC/ABS 84/26/84 5970 5202x RJ45 84/26/84 5970 525

Connection kits, modular socketFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

1x RJ11 White PC/ABS 84/26/84 5970 5102x RJ11 84/26/84 5970 515

Connection kits, TelephoneL5

5310

Type/ Colour/ Material Dimensions Art. NoDescription Finish A/B/C (mm)

Connection kit, radio/TV aerialFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting boxCYB-S40 and connectors with centre plate.

1 x radio/TV White PC/ABS 84/51/84 5970 595

CAN-A75, termination resistor 5954 120

Connection kit, D-connectorsFor mounting in FrontLine service carriers with 80 mm front (F80®). Includes cover, mounting frame,mounting plate, label with label window, connector and termination instructions.

1 x D-sub 9-pole White PC/ABS 84/50/84 5970 310 1 x D-sub 15-pole 5970 3151 x D-sub 25-pole 5970 320

Connection kits, Low current and Coaxial cable networks, Aerial, Radio/TV

L508

90L5

5290

L282

50

Type/ Colour/ Material Dimensions Art. NoDescription Finish A/B/C (mm)

Protective CasingFor data connectors and cable connections. To be mounted on the back of the mounting frame.

CYB-RK, high Red PP 63/38/63 5971 200CYB-RK, low Red 63/26/63 5971 205

Accessories

L553

00

Page 41: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 41

Type/ Colour/ Dimensions Art. No. Description Finish A/B/C (mm)

Lighting profileProvides general light, reading/examining light and night light. To be equipped with Thorsman lightfitting rails in combinations of your own choice. Two separate compartments. With earthing slot.F80® front cover and CYB outlets will snap fit into the 80 mm front (F80®) opening of the profile.Available cut to length, max 5.0 m by special order. For cutting of profile in correct length to suitchosen light fitting rail, see Figure 1 page 18. Material: Aluminium.

MWU-LP Anodized 72/180/2500 6200 002Powder coated1) 6200 001Anodized 72/180/1250 6200 006Powder coated1) 6200 005

Light fitting railTo be fixed into the lighting profile. Provides for general light, reading/examining light and nightlight. Complete with standard or electronic ballasts and reflectors, ready to use. All wiring on therail is provided for. Push-in termination. Prepared for earthing. Screw fixed, supplied with screws.The rails type T26 and T5 are two-section rails to be installed in separate compartments in the lightingprofile, see Figure 2 page 19. Fluorescent tubes to be ordered separately. Material: Zinc coated steel.

MWU-LR, Type TC 18W, fluorescent compact tube, standard ballasts 40/77/550 6200 150MWU-LR, Type TC 18W, fluorescent compact tube, electronic ballasts 40/77/550 6200 151MWU-LR, Type TC 36W, fluorescent compact tube, standard ballasts 40/77/830 6200 210MWU-LR, Type TC 36W, fluorescent compact tube, electronic ballasts 40/77/830 6200 211MWU-LR, Type TC 36W, fluorescent compact tube, electronic ballasts

dimmable (1-10V) 40/77/830 6200 212

MWU-LR, Type T26 36W,fluorescent standard tube, standard ballasts 40/77/1300+ 40/77/400 6200 205

MWU-LR, Type T26 36W,fluorescent standard tube, electronic ballasts ” 6200 206MWU-LR, Type T26 58W,fluorescent standard tube, standard ballasts 40/77/1600+

40/77/400 6200 200MWU-LR, Type T26 58W,fluorescent standard tube, electronic ballasts ” 6200 201

MWU-LR, Type T5 28W, fluorescent standard tube, electronic ballasts 40/77/1230+40/77/400 6200 160

MWU-LR, Type T5 54W, fluorescent standard tube, electronic ballasts ” 6200 165

T26, fluorescent std. Tube 36W L=1200 6200 225T26, fluorescent std. Tube 58W L=1500 6200 230T5, fluorescent std. Tube 28W L=1149 6200 245T5, fluorescent std. Tube 54W L=1149 6200 250TC, fluorescent compact Tube 18W L=217 6200 240TC, fluorescent compact Tube 36W L=410 6200 220

Pull-cord switchPull-cord switch, 1-pole 2A 250V, to be mounted on light fitting rail of type TC, 18W and 36W.Length of cord = 100 cm. Suitable for: MWU-LR Type TC.

MWU-LS 30/11,5/22 6200 301

Night LightLamp holder for night light. Suitable for lamp bulbs with E14 socket. To be fixed on the light tubesection of the general rails type T26 or T5 (fixation prepared). Lamp to be ordered separately.

MWU-LA 6200 291

IBP/F 5 W bulb (dim) 6200 605

Light Diode KitThe light diode kit consists of 8 pcs. high intensity diodes in a CYB mounting frame with protectivecasing. For night light in common ward. Available autumn 1999. Material: PC/ABS

CYB-PO angled White 84/50/84 5974 010

Lighting profile, Light fitting rail, Covers, Stop ends

1) Colour choice, see page 25.

LightingL5

0700

L575

50L5

7570

L505

00L5

0870

L504

90

L575

40L5

9000

L643

30

Page 42: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

42 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Jointing pieceUsed to joint lighting profile. Supplied with screws.

FED-SSJ Aluminium 4/11/50 5440 810

Earthing clampFor bonding lighting profile, light fitting rail, and accessories to earth.

TTI-JB Zinc passivated Steel 5590 500

Earth wireFor bonding lighting profile, light fitting rail and accessories to earth.

TTI-JK 300 Green/Yellow Copper Length = 300mm 5590 505

Lighting accessories

L359

60L3

4520

L511

70

Lighting

Type/ Colour/ Material Dimensions Art. No. Description Finish A/B/C (mm)

Up-light coverTo cover upper part of lighting profile. To be positioned in track of the profile. Material: PMMA

MWU-LC Transparent 3/100/2500 6200 805

Front coverSnap-fit fastening onto lighting profile. With earthing slots.

FCA-F80 Anodized Aluminium 80/2500 5580 080Powder coated1) 5580 089

Prismatic shadeTransparent front cover with a linear prismatic back-side to direct the light. Snap-fit fastening ontolighting profile.

MWU-LF Transparent (TC 36W) PMMA 80/400 6200 800Transparent (TC 18W) 80/200 6200 801

Stop end, lighting profileThe stop end is fixed with screws. Supplied with screws 2).

MWU-LE, left Powder coated1) Aluminium 72/180/2 6200 051MWU-LE, right Powder coated1) 6200 056

Lighting profile, Light fitting rail, Covers, Stop ends, cont.

1) Colour choice, see page 25. 2) If lighting profile in anodized finish is being used, powder coated stop end in ’RAL 9007’ is recommended.

L507

80L5

0670

L308

40L5

0710

Page 43: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 43

Type/Description Colour/ Dimensions Art. No. Finish A/B/C (mm)

Bed/Examining lamp, LuxoSupplement to the lamp unit MWU-LP. To be fixed on wall. Provided in 1100 mm armlength.

13W compact flourescent tube. MWU-L13W White L=1100 6200 401

18W compact flourescent tube. With a two level switch for reading and night light.MWU-L18W White L=1100 6200 411

Standard light bulb (max 40W), socket E27MWU-LE27 White L=1100 6200 416

Wall fixingMWU-L White 130/70/130 6200 501

Bed/Examining lamp, SunnexSupplement to the MWU lighting unit. With flexible arm. Built-in 12 V transformer for 20 W halo-gen. Separate 12 V transformer (plug-in) for 50 W halogen. To be fixed on wall or on desk (screwfixed or with clamp). Halogen lamp included.

12 V/20W halogen lamp, built-in transformer White L=900 6200 420

12V/50W halogen lamp, plug-in transformer White L=900 6200 425

Wall fixing White 6200 505

Desk fixing (clamped) White 6200 535

12 V/20 W halogen lamp (spare part) 6200 61012 V/50 W halogen lamp (spare part) 6200 615

Bed/Examining lamps

Lighting

L505

90L5

0600

L505

10L5

0520

L508

60L6

6020

L660

30

Page 44: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

44 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Type/ Dimensions Art. No. Description A/B/C (mm)

Gas outlets, AGA MC 70Gas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of thegas type. The outlets are supplied with a protective plug to prevent impurities from penetrating intothe outlets when they are not connected.To be mounted onto the fixing profile. A mounting adaptor is to be used (ordered separately). Gaspipe, copper ∆ 8 mm, soldered on the inlet tube of the gas outlet.

Breathing oxygen 90/68/90 6100 500Nitrous oxide 6100 505Breathing air, 4 bar 6100 510Gas exit 6100 515Vacuum 6100 520Instrumental air, 7 bar 6100 525

Gas outlet, GreggersenGas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of thegas type according to DIN. To be mounted onto the fixing profile. A mounting adaptor is to beused (ordered separately). Gas pipe, copper ∆ 8 mm, soldered on the inlet tube of the gas outlet.

Breathing oxygen 40/57/40 6100 530Nitrous oxide 6100 535Breathing air, 4 bar 6100 540Vacuum 6100 545Instrumental air, 7 bar 6100 550CO2 6100 555

Gas outlet, DrägerGas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of thegas type according to DIN. To be mounted onto the fixing profile. Mounting adaptor is to be used(ordered separately). Gas pipe, copper ∆ 8 mm, soldered on the inlet tube of the outlet.

Breathing oxygen 64/72/74 6100 560Nitrous oxide 6100 565Breathing air, 4 bar 6100 570Vacuum 6100 575CO2 6100 580

Gas outlet, MEDÆS, GEM 10Gas outlet with self-closing gas-type coded outlet valve and name plate in the colour code of gastype according to BS 5682. To be mounted directly onto the fixing profile (no mounting adaptor isrequired). Gas pipe, copper ∆ 12 mm, soldered on the inlet tube of the gas outlet.

Breathing oxygen 56/67/90 6100 590Nitrous oxide 6100 595Breathing air, 4 bar 6100 600Vacuum 6100 605Instrumental air, 7 bar 6100 620Entonox 6100 625

Mounting adaptor kitTo be used when fixing AGA, Dräger or Greggersen gas outlets to the fixing profile. Complete withscrews. Mounted between gas outlet and the fixing profile. Material PA

MWU-GA for AGA MC65 Black 72/6,5/50 6100 801for AGA MC70 Black 77/8,5/71 6100 802for Dräger Black 77/8,5/71 6100 803for Greggersen Black 77/8,5/71 6100 804

L507

30L5

0740

L505

70L5

0720

Gas outlets

OXYGEN

L575

30L5

0640

Gas

Page 45: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 45

Fixing profile and Front covers

Type/ Colour/ Dimensions Art. No.Description Finish A/B/C (mm)

Fixing profile, gas outletsTo mount gas outlets on to. Wall mounted. For AGA, Greggersen and Dräger gas outlets a mount-ing adapter is used between the gas outlets and the fixing profile. Medæs outlets are fixed directlyto the fixing profile. For 1–4 gas outlets. Material: Aluminium.

MWU-GF1, for1 outlet Untreated 104,2/11,5/300 6100 200MWU-GF2, for 2 outlets 104,2/11,5/500 6100 201MWU-GF3, for 3 outlets 104,2/11,5/700 6100 202MWU-GF4, for 4 outlets 104,2/11,5/900 6100 203

Front cover, gas outlet, AGA Ø = 75 mmFront cover to suit AGA MC70 gas outlets. Snap-fitted on to fixing profile2). For 1-4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.

MWU-GU1, for 1 outlet Anodized 110/71,5/300 6100 222Powder coated1) 6100 221

MWU-GU2, for 2 outlets Anodized 110/71,5/500 6100 227Powder coated1) 6100 226

MWU-GU3, for 3 outlets Anodized 110/71,5/700 6100 232Powder coated1) 6100 231

MWU-GU4, for 4 outlets Anodized 110/71,5/900 6100 237Powder coated1) 6100 236

Front cover, gas outlet, Greggersen Ø = 42 mmFront cover to suit Greggersen gas outlets. Snap-fitted on to fixing profile2).For 1–4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.

MWU-GU1, for 1 outlet Anodized 110/71,5/300 6100 252Powder coated1) 6100 251

MWU-GU2, for 2 outlets Anodized 110/71,5/500 6100 257Powder coated1) 6100 256

MWU-GU3, for 3 outlets Anodized 110/71,5/700 6100 262Powder coated1) 6100 261

MWU-GU4, for 4 outlets Anodized 110/71,5/900 6100 267Powder coated1) 6100 266

Front cover, gas outlet, Dräger Ø = 60 mmFront cover to suit Dräger and AGA MC65 gas outlets. Snap-fitted on to fixing profile2). For 1-4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.

MWU-GU1, for 1 outlet Anodized 110/71,5/300 6100 282Powder coated1) 6100 281

MWU-GU2, for 2 outlets Anodized 110/71,5/500 6100 287Powder coated1) 6100 286

MWU-GU3, for 3 outlets Anodized 110/71,5/700 6100 292Powder coated1) 6100 291

MWU-GU4, for 4 outlets Anodized 110/71,5/900 6100 297Powder coated1) 6100 296

Front cover, gas outlet, MEDÆS, GEM 10 Ø = 52 mmFront cover to suit Medæs gas outlets. Snap-fitted on to fixing profile2).For 1–4 gas outlets with a c/c measure of 200 mm. Material: Aluminium.

MWU-GU1, for 1 outlet Anodized 110/71,5/300 6100 312Powder coated1) 6100 311

MWU-GU2, for 2 outlets Anodized 110/71,5/500 6100 317Powder coated1) 6100 316

MWU-GU3, for 3 outlets Anodized 110/71,5/700 6100 322Powder coated1) 6100 321

MWU-GU4, for 4 outlets Anodized 110/71,5/900 6100 327Powder coated1) 6100 326

L507

50L5

0830

L508

40L5

0770

L507

70

1) Colour choice, see page 25.2) For gas outlet installation techniques, see page 22.

Gas

Page 46: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

46 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Type/ Colour/ Dimensions Art. No.Description Finish A/B/C (mm)

Front cover, gas pipeTo conceal gas pipe installation. Front cover is snap-fitted to the wall brackets. Available cut to length, max 5.0 m by special order. Material: Aluminium.

MWU-GP Anodized 110/71,5/2500 6100 002Powder coated1) 6100 001

Wall bracket, gas pipe front coverFront cover to gas pipe is snap-fitted to the wall bracket. Recommended distance between the wallbrackets 600 mm. Stud partition wall – adjust the bracket distance according to the studding. Gaspipes to be fixed on the wall brackets. Material: Aluminium.

MWU-GB Untreated 104,2/11,5/50 6100 090

Stop endsTo be fixed on to the gas pipe cover or on to the gas outlet front cover2). The stop end is fixed withscrews. Supplied with screws. Material: Aluminium.

MWU-GE, left Powder coated1) 109,6/71,6/2 6100 051MWU-GE, right Powder coated1) 6100 056

Stop endsTo be fixed on to the gas pipe cover or on to the gas outlet front cover2). With outlet for TRL gaspipe cover. The stop end is fixed with screws. Supplied with screws. Material: Aluminium.

MWU-GE, left TRL5630 Powder coated1) 109,6/71,6/2 6100 071MWU-GE, right TRL5630 Powder coated1) 6100 076

MWU-GE, left TRL5656 Powder coated1) 6100 061MWU-GE, right TRL5656 Powder coated1) 6100 066

MWU-GE, left TRL7640 Powder coated1) 6100 081MWU-GE, right TRL7640 Powder coated1) 6100 086

Cover for gas pipe To conceal gas pipe installation. Cover is snap-fitted on TRL socket clamps. Material: Aluminium.

TRL-D5630 Anodized 56/30/2500 5321 100TRL-D5656 Anodized 56/56/2500 5321 120TRL-D5656 Powder coated1) 56/56/2500 5321 122TRL-D7640 Anodized 76/40/2500 5321 210

Base clamp (with ties)To fix gas pipes and to mount cover onto. The bracket is screw fixed to the wall surface. Material: PA.

TRL-H56 Black –/–/– 5322 010TRL-H76 5322 020

Tie (loose)

TRL-T Black 7/140/- 5322 050

Stop endFor terminating TRL gas pipe covers. Material: ABS.

TRL-ES5656 Grey 60/57/30 5322 122

Gas

Front cover, Wall bracket, Stop ends L5

0790

L507

60L5

0660

L506

90L1

2740

L127

50L1

2770

1) Colour choice, see page 25. 2) If front cover, gas profile in anodized finish is being used, powder coated stop end in ’RAL 9007’ is recommended.

Page 47: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 47

Gas accessories

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Mounting plate with pipe clampsGas pipes are snap-fitted into the clamps. For gas pipes in dimensions of Ø 8, 10 and 12 mm.Pipe clamps are fixed by screws onto the mounting plate. The complete pipe clamp unit is screwfixed to wall brackets. Supplied with screws.

MWU-GA 4 x Ø 8 mm PE 77/24/53 6100 810

MWU-GA 2 x 2 Ø 10 mm 77/27/53 6100 811

MWU-GA 2 x 2 Ø 12 mm 77/29/53 6100 812

Earthing clampFor bonding the front cover gas outlet profile, gas outlets and accessories to earth.

TTI-JB Zinc passivated Steel 5590 500

Earth wireFor bonding the front cover, gas outlet profile, gas outlets and accessories to earth.

TTI-JK300 Green/Yellow Copper L = 300 mm 5590 505

L508

10L5

0800

L506

30L3

4520

L511

70

Gas

Page 48: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

48 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Accessory rail, Scandinavian typeFor hanging hospital equipment or instruments on. The rail must not be mounted on the hospitaltrunking. To be mounted directly on the wall surface, preferably below the hospital trunking, byusing mounting brackets,which are screwed to the wall. The Accessory rail is snap-fitted to themounting bracket. Recommended distance between mounting brackets; 400 mm. Stud partition wall– adjust the bracket distance according to studding.The Accessory rail is compatible with the AGA Accessory rail system. Dimension 30 x 10 mm.

MWU-AP, rail Anodized Aluminium 30/9,8/2500 6100 820

MWU-AB, bracket Anodized Aluminium 30/38/50 6100 830

MWU-AA, cap Grey PP 37/16/20 6100 825

Accessory rail, DIN typeFor hanging hospital equipment or instruments on. The rail must not be mounted on the hospitaltrunking. To be mounted directly on the wall surface, over or below the hospital trunking. The railbrackets are pre-mounted on the wall. Complete with screws. The rail is compatible with the DIN-standards. Dimension 25 x 10 mm. Maximum load 100 kg/mmounted on a solid wall. Available autumn 1999.

MWU-AP, rail Untreated SS 25/10/2000 6100 840

DIN-rail shelfTo be mounted on the accessory rail, DIN type. For hospital equipment such as monitors. Carries upto 40 kg (400 N). Available autumn 1999.

MWU-AS Grey SS 170/369/540 6100 845

L506

80L5

0650

L508

50L5

9020

L590

10Accessory rail

Page 49: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 49

Type/ Colour/ Material Dimensions Art. No.Description Finish A/B/C (mm)

Electrical cutting sawUsed to cut aluminium profiles. Maximum cutting 90x220mm. Spare blade available. Jepson Dry Cutter V-Power, type KA-M335.

ISV-KS Steel 5900 055Blade 5900 056

Radial arm cutting saw with work-tableUsed to cut aluminium profiles. Maximum cutting height x depth = 90 x 300 mm. DeWalt DW 8003.

ISV–SG217 Steel 5900 040

Mitre boxTo cut aluminium profiles at any angle. Complete with saw. Maximum cutting height x depth = 120x170 mm.

ISV-G400 Aluminium 490/260/645 5900 000

Saw bladeReplacement blade for saw ISV-G400.

ISV-GS550 Steel 550/45/1 5900 001

Plunge toolTo make a Ø 18.6 mm hole for the edge protection grommet INKA-GF19. The plunge tool is usedto make a hole for cables between trunking base and lighting profile.

ISV-HS Steel 5900 020

Jig templateFor the mounting of cable trunking. Prevents scratching when drilling machine is used.

INKA-JT Steel 80/40/12 5900 130

Front cover openerFor removing the front cover without damaging the trunking base or front cover.

ISV Blue PA 100/160 5900 900

ToolsL3

2330

L354

80L1

0770

L107

20D

1113

0L5

0620

L125

60

Page 50: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

50 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Cable Capacity Guide (CCG)The CCG diagram is a quick and simple way of working out the mini-mum dimensions of the installation trunking for a given number of ca-bles. If the cables are to be laid in different compartments in the sametrunking, the total height of the trunking will be the sum of the compart-ment heights.

This is how to use the CCG diagram:1. Read the diagram clockwise2. Choose the number of cables (N) on the upper vertical scale in the

middle of the diagram3. Go to the right in the diagram up to the red line that corresponds to

the relevant cable diameter (D). Directly below the intersection pointyou can read off the total cable area (A) on the right-hand horizon-tal scale. If there are cables with different diameters, the total cablearea (A) is the sum of the cable areas for the various cable diame-ters.

4. Now continue down from the intersection point for total cable areato the line that corresponds to the desired fill factor.

5. Directly to the left of the intersection point you can read off a suita-ble trunking area (S) on the lower vertical scale.

6. Then continue to the left from the value for trunking area to the linethat corresponds to the desired trunking depth for trunking with orwithout flush boxes (if the trunking is used as feeder trunking).

7. Go straight up from the intersection point and read off on the left-hand horizontal scale the smallest trunking height (H) that is requi-red to run the cables.

ExampleA number of cables are to be laid in installation trunking fitted with acable shelf so that power cables and low-current cables can be keptseparate.Known data:Power cables: 10 cables of 20 mm diameter (the lower green line inthe upper part of the diagram)Low-current cables: 22 cables of 12 mm diameter (the upper greenline)The installation trunking must be 90 mm deep, without boxes and be60 % filled.Calculated data:The cable area (A) for the low-current will be about 3350 mm2. For a60% fill factor this cable area gives a compartment area (S) of about5600 mm2. This means that the minimum height (H) of the compartmentwhere the cables will run is about 60 mm (trunking without box).The cable area (A) for the power cables will be about 4600 mm2. Fora 60% fill factor this cable area (S) gives a compartment area of about7700 mm2. This means that the minimum height (H) of the compartmentwhere the cables will run is about 85 mm (trunking without box).Suitable installation trunking should therefore be higher than 145 mm(the sum of 60 mm for the low current cable compartment and 85 mmfor the power cable compartment).The final choice of installation trunking is made with the aid of the listof our range of trunking (page 16-17) and the associated detailedcable capacity tables (pages 52-58).

52

72

90

130

250 200 150 100 50250 200 150 100 50

52

72

90

130

Approximate calculation for dimensioning cable trunking

Trunking without box

Trunking with box

H (mm)Trunkingheight

Trunkingdepth (mm)

Page 51: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 51© THORSMAN & CO AB, 1997.

5048464442403836343230282624222018161412108642

123456789

10111213141516171819202122232425

1000 2000 3000 4000 5000 6000 7000 8000 90001000 2000 3000 4000 5000 6000 7000 8000 9000

ø3 ø4 ø5 ø6 ø7ø8

ø9

ø10

ø11

ø12

ø13

ø14

ø15

ø16

ø17

ø18

ø19

ø20

80%

60%

40%

Ø

50%

5048464442403836343230282624222018161412108642

123456789

10111213141516171819202122232425

D (mm)Cable diameter

A (mm2)Total cablearea

Trunkingfill factor

NNumber ofcables

S x 1000 (mm2)

Trunking/Com-partment area

Page 52: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

R375

80

52 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Cable Capacity

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes 1 96 7152 2861 3576 42912 Not applicable3 Not applicable4 Not applicable5 23 1521 608 761 9136 25 1641 656 821 9857 25 1641 656 821 9858 23 1764 706 882 1058

With standard mounting boxes1 40 5010 2004 2505 30062 Not applicable3 Not applicable4 Not applicable5 20 1218 487 609 7316 20 975 390 488 5857 20 975 390 488 5858 20 1389 556 695 833

With mounting box CYB 30 mm deep (Fig C, B, A)1 50 5754 2302 2877 34522 Not applicable3 Not applicable4 Not applicable5 20 1348 539 674 8096 20 1198 479 599 7197 20 1198 479 599 7198 20 1506 602 753 904

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 96 5565 2226 2783 33392 Not applicable3 Not applicable4 Not applicable5 23 1303 521 652 7826 25 1199 480 600 7197 25 1199 480 600 7198 23 1308 523 654 785

With standard mounting boxes1 20 3580 1432 1790 21482 Not applicable3 Not applicable4 Not applicable5 15 1037 415 519 6226 15 522 209 261 3137 15 522 209 261 3138 20 1025 410 513 615

With mounting box CYB 30 mm deep1 30 4171 1668 2086 25032 Not applicable3 Not applicable4 Not applicable5 20 1102 441 551 6616 20 752 301 376 4517 20 752 301 376 4518 20 1092 437 546 655

R375

80

R324

30

R332

10

INKA-101/72 INKA-101/90

* Internal compartment height * Internal compartment height

R375

80

R375

80

Page 53: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

R375

80

R375

80R3

7580

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 53

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 118 6857 2743 3429 41142 Not applicable3 Not applicable4 Not applicable5 33 1865 746 933 11196 25 1199 480 600 7197 25 1199 480 600 7198 33 2089 836 1045 1253

With standard mounting boxes1 25 4706 1882 2353 28242 Not applicable3 Not applicable4 Not applicable5 20 1597 639 799 9586 15 522 209 261 3137 15 522 209 261 3138 20 1669 668 835 1001

With mounting box CYB 30 mm deep1 35 5499 2200 2750 32992 Not applicable3 Not applicable4 Not applicable5 30 1717 687 859 10306 20 752 301 376 4517 20 752 301 376 4518 25 1794 718 897 1076

Cable Capacity

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 118 6301 2520 3151 37812 Not applicable3 Not applicable4 Not applicable5 34 1912 765 956 11476 25 1199 480 600 7197 25 1199 480 600 7198 34 1709 684 855 1025

With standard mounting boxes1 20 4786 1914 2393 28722 Not applicable3 Not applicable4 Not applicable5 20 1637 655 819 9826 15 522 209 261 3137 15 522 209 261 3138 20 1664 666 832 998

With mounting box CYB 30 mm deep1 30 5362 2145 2681 32172 Not applicable3 Not applicable4 Not applicable5 25 1701 680 851 10216 20 752 301 376 4517 20 752 301 376 4518 25 1718 687 859 1031

R324

80

R332

20

INKA-123/72 INKA-123-4/72

* Internal compartment height* Internal compartment height

R375

80

Page 54: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

R375

80

54 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 118 8823 3529 4412 52942 Not applicable3 Not applicable4 Not applicable5 34 2388 955 1194 14336 25 1199 480 600 7197 25 1199 480 600 7198 34 2602 1041 1301 1561

With standard mounting boxes (Fig C, B, A)1 40 6680 2672 3340 40082 Not applicable3 Not applicable4 Not applicable5 20 2087 835 1044 12526 20 975 390 488 5857 20 975 390 488 5858 20 2227 891 1114 1336

With mounting box CYB 30 mm deep (Fig C, B, A)1 50 7424 2970 3712 44542 Not applicable3 Not applicable4 Not applicable5 20 2215 886 1108 13296 20 1198 479 599 7197 20 1198 479 599 7198 20 2344 938 1172 1406

Cable Capacity

R332

30

INKA-123/90

* Internal compartment height

R375

80

Page 55: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

R379

20

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 55

Cable Capacity

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 108 6101 2440 3051 36612 Not applicable3 Not applicable4 Not applicable5 34 1925 770 963 11556 25 1199 480 600 7197 25 1199 480 600 7198 23 1273 509 637 7649 48 2740 1096 1370 1644

With standardmounting boxes1 20 3914 1566 1957 23482 Not applicable3 Not applicable4 Not applicable5 20 1651 660 826 9916 15 522 209 261 3137 15 522 209 261 3138 20 1001 400 501 601

With mounting box CYB 30 mm deep1 30 4704 1882 2352 28222 Not applicable3 Not applicable4 Not applicable5 25 1713 685 857 10286 20 752 301 376 4517 20 752 301 376 4518 20 1052 421 526 631

R325

00

INKA-161-2/72 INKA-161-2/90

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 108 7982 3193 3991 47892 Not applicable3 Not applicable4 Not applicable5 34 2388 955 1194 14336 25 1199 480 600 7197 25 1199 480 600 7198 23 1747 699 874 10489 48 3468 1387 1734 2081

With standard mounting boxes1 40 5839 2336 2920 35032 Not applicable3 Not applicable4 Not applicable5 20 2087 835 1044 12526 20 975 390 488 5857 20 975 390 488 5858 20 1372 549 686 823

With mounting box CYB 30 mm deep1 50 6584 2634 3292 39502 Not applicable3 Not applicable4 Not applicable5 20 2215 886 1108 13296 20 1198 479 599 7197 20 1198 479 599 7198 20 1489 596 745 893

R379

20

R332

50

* Internal compartment height * Internal compartment height

R379

20

R379

20

Page 56: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

56 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

R375

80

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 157 12149 4860 6075 72892 Not applicable3 Not applicable4 Not applicable5 34 2433 973 1217 14606 25 1632 653 816 9797 25 1632 653 816 9798 72 5888 2355 2944 3533

With standard mounting boxes1 67 10115 4046 5058 60692 Not applicable3 Not applicable4 Not applicable5 31 1658 663 829 9956 23 958 383 479 5757 23 958 383 479 5758 67 5562 2225 2781 3337

With mounting box CYB 30 mm deep1 67 10750 4300 5375 64502 Not applicable3 Not applicable4 Not applicable5 31 1754 702 877 10526 23 1185 474 593 7117 23 1185 474 593 7118 67 5640 2256 2820 3384

R332

60

Cable Capacity

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 157 9369 3748 4685 56212 Not applicable3 Not applicable4 Not applicable5 34 1909 764 955 11456 25 1199 480 600 7197 25 1199 480 600 7198 72 4556 1822 2278 2734

With standard mounting boxes1 20 7372 2949 3686 44232 Not applicable3 Not applicable4 Not applicable5 20 1620 648 810 9726 15 522 209 261 3137 15 522 209 261 3138 40 4273 1709 2137 2564

With mounting box CYB 30 mm deep1 30 7978 3191 3989 47872 25 1545 618 773 9273 25 876 350 438 5264 40 4552 1821 2276 27315 25 1699 680 850 10196 20 752 301 376 4517 20 752 301 376 4518 40 4343 1737 2172 2606

R327

80

INKA-161-3/72 INKA-161-3/90

R375

80

* Internal compartment height* Internal compartment height

R375

80

R375

80

Page 57: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 57

Cable Capacity

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 108 7982 3193 3991 47892 - 4 Not applicable5 34 2388 955 1194 14336 25 1199 480 600 7197 25 1199 480 600 7198 22 1747 699 874 10489 70 5391 2156 2696 323510 32 2130 852 1065 127811 39 3054 1222 1527 1832

With standard mounting boxes1 40 5839 2336 2920 35032 - 4 Not applicable5 20 2087 835 1044 12526 20 975 390 488 5857 20 975 390 488 5858 20 1372 549 686 8239 30 5391 2156 2696 323510 25 2130 852 1065 127811 30 3054 1222 1527 1832

With mounting box CYB 30 mm deep1 50 6584 2634 3292 39502 - 4 Not applicable5 20 2215 886 1108 13296 20 1198 479 599 7197 20 1198 479 599 7198 20 1489 596 745 8939 30 5391 2156 2696 323510 25 2130 852 1065 127811 30 3054 1222 1527 1832

R373

60

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 105 5962 2385 2981 35772 - 4 Not applicable5 33 1905 762 953 11436 25 1199 480 600 7197 25 1199 480 600 7198 20 1130 452 565 6789 105 6010 2404 3005 360610 - 11 Not applicable12 30 1766 706 883 106013 20 1082 433 541 64914 25 1199 480 600 71915 25 1199 480 600 71916 33 1985 794 993 1191

With standard mounting boxes1 20 3980 1592 1990 23882 - 4 Not applicable5 20 1614 646 807 9686 15 476 190 238 2867 15 476 190 238 2868 20 843 337 422 5069 20 4014 1606 2007 240810 - 11 Not applicable12 25 1409 564 705 84513 15 807 323 404 48414 15 476 190 238 28615 15 476 190 238 28616 25 1699 680 850 1019

With mounting box CYB 30 mm deep1 30 4568 1827 2284 27412 - 4 Not applicable5 25 1696 678 848 10186 20 752 301 376 4517 20 752 301 376 4518 25 911 364 456 5479 30 4616 1846 2308 277010 - 11 Not applicable12 25 1580 632 790 94813 15 883 353 442 53014 15 752 301 376 45115 15 752 301 376 45116 25 1766 706 883 1060

R377

00

R331

70

R332

80

INKA-183-2/90 INKA-217-2/72

* Internal compartment height

* Internal compartment height

R373

60

R373

60

Page 58: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

58 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Cable CapacityR3

7700

Comp Height* Cross section Cable capacity mm2

No area mm2 40% 50% 60%

Without mounting boxes1 105 7745 3098 3873 46472 - 4 Not applicable5 33 2388 955 1194 14336 25 1199 480 600 7197 25 1199 480 600 7198 20 1567 627 784 9409 105 7819 3128 3910 469110 -12 Not applicable13 20 1358 543 679 81514 25 1199 480 600 71915 25 1199 480 600 71916 33 2619 1048 1310 1571

With standard mounting boxes1 40 5602 2241 2801 33612 - 4 Not applicable5 20 1087 435 544 6526 20 975 390 488 5857 20 975 390 488 5858 20 1191 476 596 7159 40 5676 2270 2838 34062 - 4 Not applicable13 15 1055 422 528 63314 20 975 390 488 58515 20 975 390 488 58516 30 2244 898 1122 1346

With mounting box CYB 30 mm deep1 50 6346 2538 3173 38082 - 4 Not applicable5 20 2215 886 1108 13296 20 1198 479 599 7197 20 1198 479 599 7198 20 1309 524 655 7859 40 6472 2589 3236 38832 - 4 Not applicable13 15 1186 474 593 71214 20 1198 479 599 71915 20 1198 479 599 71916 30 2361 944 1181 1417

R332

90

INKA-217-2/90

* Internal compartment height

R377

00

Page 59: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 59

Aluminium(Al) is resistant to most first acids and organic solvents. Aluminium is not resistant to most strong acids (except nitric acid) andalkali.

PVCAccording to ISO Technical report 7473 1981, PVC (polyvinylchloride, uPVC) is resistant to most acids, lyes, salt solutionsand hydrous organic combinations. PVC is not resistant to aromatic and chlorinated solvents, e.g. acetone, thinner, trichlore-ethylene, ethyl acetate, tetrahydrofurane, metylene chloride, metyl ethyl ketone.

Technical DataChemical Resistance

Material data Material data PCDensity 1.17 g/cm3

Longitudinal expansion 70x10-6 m/m°CWater absorption 0.6%Volume resistivity >1013 Ω cmElectrical strength 18 kV/mmFire class UL 94 V-2, 1.6 mm halogen-free

Material data PADensity 1.39 g/cm3

Longitudinal expansion 100x10-6 m/m°CWater absorption 2.8%Volume resistivity >1015 Ω cmElectrical strength 60 kV/mmFire class UL 94 HB, halogen-free

Material data PC/ABSDensity 1.14 g/cm3

Longitudinal expansion –Water absorption 0.6%Volume resistivity >1013 Ω cmElectrical strength 19 kV/mmFire class UL 94 V-0, 1.6 mm halogen-free

Material data PMMA Density 1.19 g/cm3

Longitudinal expansion 80x10-6 m/m°CWater absorption 0.3%Volume resistivity >1015 Ω cmElectrical strength 30 kV/mm (DIN 53481)Fire class UL 94 HB, 1.6 mm halogen-free

Material data PPDensity 0.905 g/cm3

Longitudinal expansion 100x10–6 m/m°CWater absorption <0,1%Volume resistivity 1012 Ω cmElectrical strength >30 kV/mmFire class UL 94 HB halogen-free, with-

stands glow wire test 750°

Material data AluminiumDensity 2.7 g/cm3

Longitudinal expansion 24x10–6m/m°C (0.024 mm/m°C)Water absorption -Volume resistivity -Electrical strength -Fire class -

Material data PVCDensity ISO 1183 1.5 g/cm3

Longitudinal expansion 60x10–6 m/m°C (0.06 mm/m°C)Water absorption -Volume resistivity -Electrical strength -Temperature resistance: Maximum 60°C

Page 60: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

TTA-KM 1TTA-KM 3TTA-KM 5

60 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Mounting Details

M38540

Page 61: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 61

Mounting details

ISV-FO

Page 62: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

62 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

TTI-JB

Mounting details

Page 63: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

12

x2

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 63

Mounting details

Page 64: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

64 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Mounting details

225

10 mm

225

=

=

MWU-LSOptional

MI2

072

Page 65: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 65

MWU-GA

Mounting details

Page 66: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

66 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

MI2

073

Page 67: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 67

Specification GuideDue to the great flexibility of the FrontLine HospitalTrunking system and the many possibilities for com-bining the various products, we recommend the fol-lowing procedure when specifying/ordering:

GeneralAll items are presented in the same order they appearin this brochure.

Information given in the order form underType/Description is somewhat restricted due to spaceconsiderations.

For colour choice, fill in the corresponding colourcode (for example L11), see page 25.

Numbers in parentheses, for example (p. 26-27), referto pages in this brochure.

Begin by copying the Specification/Order form,then choose:1. Service carrier2. Service Content3. Lighting4. Gas5. Accessory rail6. Tools

P382

6

Page 68: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

68 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

Specification/Order form(Copy this form before filling in)

Art. No. T- Type/Description Qty (pcs)

1. Service carrierArt. No. T- Type/Description Qty (pcs)

2. Service content

(p 30) Connection kits, SchukoSingle socket outlets, Schuko 90°

5975 000 CYB-PS, white5975 005 CYB-PS, white

Double socket outlets, Schuko 37°

5951 480 CYB-PS, white5951 482 CYB-PS, red5951 485 CYB-PS, green5951 487 CYB-PS, orange

Three-gang socket outlets, Schuko 37°

5951 430 CYB-PS, white5951 432 CYB-PS, red5951 435 CYB-PS, green5951 437 CYB-PS, ornage(p 31) Connection kits, French Standard

For Poland and France

5969 215 CYB-PF, Two-gang, push-in terminals, white5969 217 CYB-PF, Two-gang, push-in terminals, red

For Belgium, Poland, France

5969 210 CYB-PF, Two-gang, screw terminals, white5969 212 CYB-PF, Two-gang, screw terminals, red

For Czech Rep., Poland, France

5969 115 CYB-PF, Two-gang, push-in terminals, white5969 117 CYB-PF, Two-gang, push-in terminals, red5969 110 CYB-PF, Two-gang, screw terminals, white5969 112 CYB-PF, Two-gang, screw terminals, red(p 31) Connection kits, British Standard

Single, 13 A

5961 130 CYB-PU, switched, white5961 120 CYB-PU, switched, white5961 140 CYB-PU, switched with indicator, white

Twin, 13 A

5961 135 CYB-PU, unswitched, white5961 125 CYB-PU, switched , white5961 145 CYB-PU, switched with indicator, white(p 32) Basic kit, CEE socket outlets5960 110 CYB-C220, 250 V/16 A, grey/blue5960 100 CYB-C380, 440 V/16 A, grey/red

(p 32) Connection kit, Overvoltage protection5972 010 CYB-PP, white(p 32-33) Connection kits, Switches5980 002 CYB-PB, Single-pole5980 007 CYB-PB, Single-pole, spring-return rocker5980 012 CYB-PB, Single-pole, red indicator lamp5980 017 CYB-PB, Single-pole, green indicator lamp5980 032 CYB-PB, Double-pole5980 052 CYB-PB, Single-pole/two-way5980 062 CYB-PB, Intermediate5980 072 CYB-PB, Two-gang5980 082 CYB-PB, Venetian blind5980 087 CYB-PB, Venetian blind, single-pole5980 057 CYB-PB, Double single-pole/two-way

Pilot lamp 0.9 mA 250 V

5972 105 CYB-GL2, to be mounted together with switchPush-in plint for16A/250V

5972 200 CYB-PT, For single socket, 3x2,5 mm2

(p 34) Light diode kit5974 010 CYB-PO, angled, white

(p 34) Connection kit, Dimmers 230 V,F80® Mounting

5985 020 CYB-PR, dimmer, white (APE 10T)5985 000 CYB-PR, dimmer, white (ATD 300R)5985 030 CYB-PR, dimmer, white (AD 400UTT)5985 050 CYB-PR, dimmer, white (ATTD 1000RL)

(p 26-27) Trunking bases72 mm deep

5504 000 INKA-U101, anodized5504 002 INKA-U101, colour code:5507 000 INKA-U123, anodized5507 002 INKA-U123, colour code: 5506 310 INKA-U123-4, anodized5506 319 INKA-U123-4, colour code:5510 010 INKA-U161-2, anodized5510 012 INKA-U161-2, colour code:5510 020 INKA-U161-3, anodized5510 022 INKA-U161-3, colour code:5514 000 INKA-U217-2, anodized5514 002 INKA-U217-2, colour code:

90 mm deep

5519 010 INKA-U101, anodized5519 012 INKA-U101, colour code:5506 400 INKA-U123, anodized5506 402 INKA-U123, colour code:5519 020 INKA-U161-2, anodized5519 022 INKA-U161-2, colour code:5512 230 INKA-U161-3, anodized5512 232 INKA-U161-3, colour code:5519 060 INKA-U183-2, anodized5519 062 INKA-U183-2, colour code:5519 040 INKA-U217-2, anodized5519 042 INKA-U217-2, colour code:

(p 27) Front covers5580 030 FCA-F40, anodized5580 039 FCA-F40, colour code:5580 080 FCA-F80, anodized5580 089 FCA-F80, colour code:

(p 28) Stop ends*5504 172 INKA-ES101/72, colour code:5507 172 INKA-ES123/72, colour code:5510 172 INKA-ES161/72, colour code:5514 172 INKA-ES217/72, colour code:5590 217 INKA-ES101/90, colour code:5591 152 INKA-ES123/90, colour code:5590 277 INKA-ES161-2/90, colour code:5591 062 INKA-ES161-3/90, colour code:5591 032 INKA-ES183-2/90, colour code:5590 307 INKA-ES217-2/90, colour code:5590 203 INKA-ESV123-4/72, left, colour code:5590 208 INKA-ESH123-4/72, right, colour code:

(p 28-29) Trunking accessories5590 312 TTI-KH72, Cable shelf, aluminium5590 314 TTI-KH72, Cable shelf, PVC5590 315 TTI-KH90, Cable shelf, aluminium5590 316 TTI-KH90, Cable shelf, PVC5590 340 TTI-KHK, Cable clip5590 180 TTI-MB, Mounting washer5590 112 INKA-SSA, Jointing piece5590 500 TTI-JB, Earthing clamp5590 505 TTI-JK300, Earth wire5590 410 TTI-T3045, Sound insulation strip5590 414 TTI-T5070, Sound insulation strip5590 520 TTI-KB, Cup washer5902 100 INKA-GF19, Grommet5902 120 INKA-KD82, Edge protection5586 600 TTI-GM, Locking plate5583 405 TTA-KM1, Washer5583 408 TTA-KM3, Washer5583 410 TTA-KM5, Washer

* If anodized trunking is chosen, stop ends in colour code L23 (RAL 9007) are recommended.

Page 69: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

(p 38-39) Connection kits, Data (cont.)Avaya (Lucent) MPS 300, 100 UTP

5970 960 1 x Cat6 UTP, A, white5970 965 2 x Cat6 UTP, A, white5970 970 1 x Cat6 UTP, B, white5970 975 2 x Cat6 UTP, B, white5970 800 1 x Cat5e UTP, A, white5970 805 2 x Cat5e UTP, A, white5970 810 1 x Cat5e UTP, B, white5970 815 2 x Cat5e UTP, B, white

AMP110, Netconnect UTP and STP

5970 930 1 x Cat6 A/B UTP, white5970 935 2 x Cat6 A/B UTP, white5970 840 1 x Cat5e A/B UTP, white5970 845 2 x Cat5e A/B UTP, white5970 850 1 x Cat5e A, STP, white5970 860 2 x Cat5e A, STP, white5970 855 1 x Cat5e B, STP, white5970 865 2 x Cat5e B, STP, white

IBM ACS type C, Reichle de Massari UTP and FTP

5970 355 1x Cat5, UTP, white5970 360 2x Cat5, UTP, white5970 365 1x Cat5, FTP, white5970 370 2x Cat5, FTP, white

IBM type 1, STP for structured cable systems

5970 345 1x IBM type 1, whiteIBM type 2, STP for structured cable systems

5970 350 1x IBM type 2, whiteKrone Keystone for PremisNET struct. cable syst.

5970 760 1 x Cat5 UTP, B, white5970 765 2 x Cat5 UTP, B, white5970 770 1 x Cat5 STP, B, white5970 775 2 x Cat5 STP, B, white

(p 39) Connection kits, fibre opticsLexCom fibre multimode for fibre-based cable syst.

5974 000 1 x SC-duplex, multimode, white5974 005 2 x SC-duplex, multimode, white

AMP SC and Lucent Technologies ST

5970 375 2 x ST, multimode, white5970 380 1 x SC-duplex, multimode, white5970 385 2 x SC-duplex, multimode, white

Protective casing for fibre optics

5971 220 CYB-DF, white(p 40) Connection kits, Telephone

AMP 8-way modular socket Cat 3

5970 520 1x RJ45, white5970 525 2x RJ45, white

AMP 6-way modular socket

5970 510 1x RJ11, white5970 515 2x RJ11, white

(p 40) Connection kits, low current and co- axial cable networks, aerial, radio/TVConnection kit, radio/TV aerial

5970 595 1 x radio/TV, white5954 120 CAN-A75, termination resistor

Connection kit, D-connectors

5970 310 1 x D-sub 9-pole, white5970 315 1 x D-sub 15-pole, white5970 320 1 x D-sub 25-pole, white(p 40) Accessories5971 200 CYB-RK, high, Protective Casing, red5971 205 CYB-RK, low, Protective Casing, red

(p 34) Mounting boxes and blank covers5961 030 CYB-S40, Single box5961 035 CYB-D40, Double box 5961 550 CYB-PL, Blanking cover, single5961 555 CYB-PL, Blanking cover, double

(p 35) Accessories for Mounting boxes and Mounting kitsScrew pillars

5961 505 CYB-P40, for British standard5961 506 CYB-P3, for 60 mm centres

Adapter for flexible conduit

5956 250 CYB-D20, Adapter5956 255 CYB-D25, Adapter

Earthing terminal

5961 500 CYB-ET, can take 2x4 mm2 wiresConduit bush

5961 510 CYB-CTStrain relief

5956 150 FDS

(p 35) Installation boxes5586 150 MIB-A15586 155 MIB-A2

(p 36) Mounting kit for access. (other suppliers)

5971 790 CYB-MB5971 794 CYB-MB

(p 36) Equipotential connection5971 302 CYB-PO, (max 63 A), anodized5971 301 CYB-PO, colour code:5971 307 CYB-PO DIN, anodized5971 306 CYB-PO DIN, colour code:

Equipotential connection Kit5971 315 CYB-PO DIN5914 050 CTA-PO

(p 37) DIN enclosures5960 251 CYB-PN 5960 256 CYB-PN

(p 37) Circuit breakers5960 480 CYB-PN, 1-pole, C10A5960 485 CYB-PN, 1-pole, C16A5960 460 CYB-PN, 2-pole, B10A5060 490 CYB-PN, 2-pole, C10A5960 465 CYB-PN, 2-pole, B16A5960 495 CYB-PN, 2-pole, C16A5960 470 CYB-PN, 3-pole, B10A5960 500 CYB-PN, 3-pole, C10A5960 475 CYB-PN, 3-pole, B16A5960 505 CYB-PN, 3-pole, C16A5960 415 CYB-PN 2 pole, Earth leakage breaker5960 410 CYB-PN 4 pole, Earth leakage breaker

(p 38-39) Connection kits, DataLexCom 250, 125 UTP and STP

5974 090 1 x Cat6 UTP, A/B, white5974 095 2 x Cat6 UTP, A/B, white5974 100 1 x Cat6 STP, A/B, white5974 105 2 x Cat6 STP, A/B, white5970 900 1 x Cat5e UTP, A/B, white5970 905 2 x Cat5e UTP, A/B, white5970 910 1 x Cat5e STP, A/B, white5970 915 2 x Cat5e STP, A/B, white

FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112 69

2. Service content (cont.)

Art. no. T- Type/Description Qty (pcs) Art. No. T- Type/Description Qty (pcs)

2. Service content (cont.)

Specification/Order form

Page 70: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

70 FrontLine Hospital Trunking/Thorsman/MC1823INT/GB/0112

(p 44) Gas outletsAGA MC 70

6100 500 Breathing oxygen6100 505 Nitrous oxide6100 510 Breathing air, 4 bar6100 515 Gas exit6100 520 Vacuum6100 525 Instrumental air, 7 bar

Greggersen

6100 530 Breathing oxygen6100 535 Nitrous oxide6100 540 Breathing air, 4 bar6100 545 Vacuum6100 550 Instrumental air, 7 bar6100 555 CO2

Dräger

6100 560 Breathing oxygen6100 565 Nitrous oxide6100 570 Breathing air, 4 bar6100 575 Vacuum6100 580 CO2

MEDÆS, GEM 10

6100 590 Breathing oxygen6100 595 Nitrous oxide6100 600 Breathing air, 4 bar6100 605 Vacuum6100 620 Instrumental air, 7 bar6100 625 Entonox

(p 44) Mounting adaptor kit6100 801 MWU-GA for AGA MC656100 802 MWU-GA for AGA MC706100 803 MWU-GA for Dräger6100 804 MWU-GA for Greggersen

(p 45) Fixing profile and Front covers

Fixing profile, gas outlets

6100 200 MWU-GF1, for 1 outlet6100 201 MWU-GF2, for 2 outlets6100 202 MWU-GF3, for 3 outlets6100 203 MWU-GF4, for 4 outlets

Front cover, gas outlet, AGA, Ø = 75 mm

6100 222 MWU-GU1, for 1 outlet, anodized6100 221 MWU-GU1, for 1 outlet, colour code:6100 227 MWU-GU2, for 2 outllets, anodized 6100 226 MWU-GU2, for 2, colour code:6100 232 MWU-GU3, for 3, outlets, anodized6100 231 MWU-GU3, for 3, colour code:6100 237 MWU-GU4, for 4 outlets, anodized6100 236 MWU-GU4, for 4 outlets, colour code:

Front cover, gas outlet, Greggersen, Ø = 42 mm

6100 252 MWU-GU1, for 1 outlet, anodized6100 251 MWU-GU1, for 1 outlet, colour code:6100 257 MWU-GU2, for 2 outlets , anodized6100 256 MWU-GU2, for 2 outlets, colour code:6100 262 MWU-GU3, for 3 outlets, anodized6100 261 MWU-GU3, for 3 outlets, colour code:6100 267 MWU-GU4, for 4 outlets, anodized6100 266 MWU-GU4, for 4 outlets, colour code:

Front cover, gas outlet, Dräger, Ø = 60 mm

6100 282 MWU-GU1, for 1 outlet, anodized6100 281 MWU-GU1, for 1 outlet, colour code:6100 287 MWU-GU2, for 2 outlets, anodized6100 286 MWU-GU2, for 2 outlets, colour code:6100 292 MWU-GU3, for 3 outlets, anodized6100 291 MWU-GU3, for 3 outlets, colour code:6100 297 MWU-GU4, for 4 outlets, anodized6100 296 MWU-GU4, for 4 outlets, colour code:

Art. No. T- Type/Description Qty (pcs)

3. Lighting

(p 41-42) Lighting profile, Light fitting rail, Covers, Stop endsLighting profile

6200 002 MWU-LP, anodized6200 001 MWU-LP, colour code:6200 006 MWU-LP, L=1250 mm, anodized6200 005 MWU-LP, L=1250 mm, colour code:

Light fitting rail

6200 150 MWU-LR, Type TC 18W6200 151 MWU-LR, Type TC 18W, HF**6200 210 MWU-LR, Type TC 36W6200 211 MWU-LR, Type TC 36W, HF**6200 212 MWU-LR, Type TC 36W, HF dimm.**6200 205 MWU-LR, Type T26 36W6200 206 MWU-LR, Type T26 36W, HF**6200 200 MWU-LR, Type T26 58W6200 201 MWU-LR, Type T26 58W, HF**6200 160 MWU-LR, Type T5 28W, HF**6200 165 MWU-LR, Type T5 54W, HF**6200 225 T26, fluorescent std. Tube 36W, L=12006200 230 T26, fluorescent std. Tube 58W, L=15006200 245 T5, fluorescent std. Tube 28W, L=11496200 250 T5, fluorescent std. Tube 54W, L=11496200 240 TC, fluorescent compact Tube 18W, L=2176200 220 TC, fluorescent compact Tube 36W, L=410

Pull-cord Switch

6200 301 MWU-LSNight Light

6200 291 MWU-LA6200 605 IBP/F 5 W bulb (dim)

Light Diode Kit

5974 010 CYB-PO, angled, whiteUp-light cover

6200 805 MWU-LC, transparent(p 42) Front cover

5580 080 FCA-F80, anodized 5580 089 FCA-F80, colour code:

Prismatic shade

6200 800 MWU-LF, transparent (TC 36W)6200 801 MWU-LF, transparent (TC 18W)

Stop end*, lighting profile

6200 051 MWU-LE, left, colour code: 6200 056 MWU-LE, right, colour code:

(p 42) Lighting accessories5440 810 FED-SSJ, Jointing piece5590 500 TTI-JB, Earthing clamp5590 505 TTI-JK 300, Earth wire

(p 43) Bed-Examining lampsLuxo

6200 401 MWU-L13W compact flourescent tube 6200 411 MWU-L18W compact flourescent tube 6200 416 MWU-L 40W bulb6200 501 Wall fixing

Sunnex

6200 420 12 V/20W halogen lamp, built-in transformer 6200 425 12V/50W halogen lamp, plug-in transformer6200 505 Wall fixing6200 535 Desk fixing (clamped)6200 610 12 V/20 W halogen lamp6200 615 12 V/50 W halogen lamp

Art. No. T- Type/Description Qty (pcs)

4. Gas

* If anodized lighting profile is chosen, stop ends in colour code L23 (RAL 9007) are recommended.

** HF=Electronic ballasts

Specification/Order form

Page 71: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

Art. No. T- Type/Description Qty (pcs) Art. No. T- Type/Description Qty (pcs)

4. Gas (cont.)

(p 45) Front cover ,gas outlet, MEDÆS, GEM 10, Ø = 52 mm

6100 312 MWU-GU1, for 1 outlet, anodized6100 311 MWU-GU1, for 1 outlet, colour code:6100 317 MWU-GU2, for 2 outlets, anodized6100 316 MWU-GU2, for 2 outlets, colour code:6100 322 MWU-GU3, for 3 outlets, anodized6100 321 MWU-GU3, for 3 outlets, colour code:6100 327 MWU-GU4, for 4 outlets, anodized6100 326 MWU-GU4, for 4 outlets, colour code:

(p 46) Front cover, Wall bracket, Stop ends Front cover, gas pipe

6100 002 MWU-GP, anodized6100 001 MWU-GP, colour code:

Wall bracket, gas pipe front cover

6100 090 MWU-GB, untreatedStop ends*

6100 051 MWU-GE, left, colour code:6100 056 MWU-GE, right, colour code:

Stop ends with outlet for TRL gas pipe cover*

6100 071 MWU-GE, left TRL5630, colour code:6100 076 MWU-GE, right TRL5630, colour code:6100 061 MWU-GE, left TRL5656, colour code:6100 066 MWU-GE, right TRL5656, colour code:6100 081 MWU-GE, left TRL7640, colour code:6100 086 MWU-GE, right TRL7640, colour code:

Cover for gas pipe

5321 100 TRL-D5630, anodized5321 120 TRL-D5656, anodized5321 122 TRL-D5656, colour code:5321 210 TRL-D7640, anodized

Base clamp (with ties)

5322 010 TRL-H565322 020 TRL-H765322 050 TRL-T

Stop end (for terminating TRL gas pipe covers)

5322 122 TRL-ES5656, grey

THORSMAN INTERNATIONALThorsman & Co AB, Box 1010, SE-611 29 Nyköping, Sweden

Telephone +46-155 26 50 00. Telefax +46-155 26 63 66E-mail: [email protected] Web Site: www.thorsman.com

Project: ....................................................................................................................................................................

Sub-specification: ......................................................................................................................................................

Company: ....................................................................................................................................................................

Reference: ....................................................................................................................................................................

Address: ......................................................................................................................................................................

Phone: ..........................................................................................................................................................................

Telefax: ........................................................................................................................................................................

Fax or mail the Specification/Order form to Thorsman Internationalor to your local Thorsman representative.

5. Accessory rail

(p 48) Accessory railAccessory rail, Scandinavian type

6100 820 MWU-AP, rail, anodized6100 830 MWU-AB, bracket, anodized6100 825 MWU-AA, cap, grey

Accessory rail, DIN type

6100 840 MWU-AP, rail, untreatedDIN-rail shelf

6100 845 MWU-AS, untreated/grey

6. Tools

(p 49) Tools5900 055 ISV-KS, Electrical cutting saw5900 056 Blade, for Electrical cutting saw5900 040 ISV-SG217, Radial arm cutting saw

with work-table5900 000 ISV-G400, Mitre box5900 001 ISV-GS550, replacement blade for ISV-G4005900 020 ISV-HS, Plunge tool5900 130 INKA-JT, Jig template5900 900 ISV, Front cover opener

(p 47) Gas accessoriesMounting plate with pipe clamps

6100 810 MWU-GA 4 x Ø 8 mm6100 811 MWU-GA 2 x 2 Ø 10 mm6100 812 MWU-GA 2 x 2 Ø 12 mm

Earthing clamp

5590 500 TTI-JBEarth wire

5590 505 TTI-JK300

4. Gas (cont.)

* If anodized gas profile is chosen, stop ends in colour code L23 (RAL 9007) are recommended.

Specification/Order form

Art. No. T- Type/Description Qty (pcs)

Art. No. T- Type/Description Qty (pcs)

Page 72: TECHNICAL INFORMATION 2001:12argo-contar.com/download/passive/schneider/HospitalSystem.pdf · P3722 FrontLine Installation System FrontLine is a system for installation of service

MC

1823

/IN

T/G

B/01

12. ©

TH

ORS

MA

N &

CO

AB.

Lexel in BriefThe Lexel Group is one of Europe’s leading suppliersof installation solutions for power, telecom, datacomand control applications with special focus on 'smartbuildings', i.e. buildings equipped with technologyproviding increased levels of comfort, economy andsecurity.

The Lexel product programme includes everythingfrom switches, outlets, installation materials andinstallation systems for cable management to commu-nication networks, security systems, and systems andsoftware for control of building functions.

Respect for the environment is an integral part ofall Lexel activities. One example is the developmentand certification of environmental management sys-tems complying with ISO 14000. In the field of poly-mers Lexel is working to eliminate the use of heavymetals and ozone-depleting substances.

The Lexel Group is owned by Schneider Electric ofFrance and has its operational head office inStockholm, Sweden. The Group has a turnover ofover EUR 650 million and employs some 6000 people.

Lexel is a market leader in the Nordic countries,Poland and the Baltic States, but is also stronglyplaced in Russia and a number of Central Europeancountries. Sales are effected through subsidiaries in 18countries and distributors in more than 30.

International representation, brand ThorsmanThorsman International is the marketing organization re-sponsible for marketing in all non-subsidiary markets byworking with a large network of agents and distributorsthroughout the world.

EuropeAustria, Belgium, Bosnia and Herzegovina, Bulgaria, Belarus, Croatia,Cyprus, France, Greece, Hungary, Iceland, Italy, Macedonia, Portugal,Romania, Slovenia, Spain, Switzerland, Ukraine, Yugoslavia.

Other marketsArgentina, Australia, Bahrain, Hong Kong, Israel, Japan, Jordan,Kazakhstan, Kuwait, Lebanon, Malaysia, Mexico, Oman, Qatar, SaudiArabia, Singapore, Turkey, U.A.E., U.S.A.

Thorsman & Co AB • Box 1010 • SE-611 29 Nyköping, Sweden • Telephone +46-155-26 50 00 • Telefax +46-155-26 63 66 • www.thorsman.com

Electricity the professional wayTHORSMAN INTERNATIONAL

Öst

erbe

rgs

& S

örm

land

stry

ck, 2

3550