68
Technical Document state 11/05/2020 WP Max-HiQ and WP Max-LoQ

Technical Document...13.8 Compressor oil 60 13.9 Finder active energy meter 64 13.10 Label 66 13.11 EC declaration of conformity 67 3 TUDWPMax-HiQ2020/05-bi - Errors and changes of

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • Technical Documentstate 11/05/2020WP Max-HiQ and WP Max-LoQ

  • 2

    CONTENTS

    1. Functional description 32. Notes on the documentation 4

    2.1 Fundamental safety instructions 52.2 Used symbols 62.3 Intended use 72.4 General safety instructions 82.5 Installation and adjustments 92.6 Guidlines, Norms and laws 102.7 Qualification of personnel 112.8 Responsibility of personnel 12

    3. Technical data 133.1 WP Max-HiQ 133.2 WP Max-LoQ 143.3 Performance curve of Max-HiQ F06 15

    4. Mechanical installation 164.1 Inner part 16

    5. Hydraulic installation 175.1 Connection sizes and dimension 175.2 Scheme 185.3 Pressure loss diagram capacitor 195.4 Pressure loss diagram evaporator 205.5 Requirements for the quality of the heating water 21

    6. Electrical installation 226.1 Notes 226.2 Electrical installed power 226.3 Terminal scheme and description 236.4 CAN-bus plan 24

    7. Refrigeration installation 257.1 Refrigeration scheme 25

    8. Structure and function 268.1 Assembly and spare parts 268.2 Control logic and activation 27

    9. Operation notes 289.1 Controller operation 289.2 Settings 33

    10. Debugging 3411. Maintenance 36

    11.1 Cleaning 3611.2 Maintenance 3611.3 Tightness check 37

    12. Decommissioning & disposal 3813. Annex 39

    13.1 Electrical plan 3913.2 Pump Wilo-Para StG 4413.3 Pump Wilo Stratos Para 4813.4 Error messages frequency inverter Bonfiglioli Agile 5013.5 Technical data RSM610 5313.6 Refrigerant R134A 5513.7 Heating Rod 5913.8 Compressor oil 6013.9 Finder active energy meter 6413.10 Label 6613.11 EC declaration of conformity 67

  • 3TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    1. FUNCTIONAL DESCRIPTION

    The high temperature heat pump WP Max-HiQ is suitable for strongly varying source temperatures in the

    range of 10 to 55 °C. The flexibility is achieved by a patented procedure, which enables the system to reach

    the optimal operating point despite the changing source temperatures. Whereas the heat pump WP Max-

    LoQ is suitable for source temperaturs lower than 15 °C. The maximum of the flow temperature of both

    heat pumps amounts to 72 °C. The range of application of the heat pumps extends from sustainable district

    heating networks or rather energy grids, to the usage of electricity from photovoltaiks, to the loading process

    of large buffer storages, up to the usage as conventional water/water or brine/water heat pumps. Because

    of speed regulations a wide range of utilisations ist covered and leads to the heat pumps being ideally suited

    for the use of fluctuating energy quantities such as power from photovoltaic systems.

    BENEFITS

    • Usage of strongly varying sources possible

    • High flexibility due to speed controlled inverter

    operations

    • Flow temperatures up to 72 °C possible

    • Integrated energy management (Smart Grid

    compliant)

    • Easy installation due to a complete pre-

    assembly in the factory, no need of a licence for

    refrigeration

    • With ratiotherm components it is a completely

    coordinated, sustainable system.

  • 4

    The following indications are a guide through the whole documentation.

    Further documents besides this operating and installation instruction are valid.

    The operating and installation guide for technical staff is a part of the ratiotherm heat pump WP Max-HiQ/

    LoQ.

    The ratiotherm heat pump WP Max-HiQ/LoQ can not be used without this instruction.

    The instruction needs to be available to the technical staff at any time.

    In case of selling the ratiotherm heat pump WP Max-HiQ/LoQ the instruction has to be attached.

    No liability is assumed for damages caused by non-consideration of this instruction.

    2. NOTES ON THE DOCUMENTATION

    TARGET GROUP

    The instruction is addressed to

    • the operator and

    • the technical staff of the heat pump.

    STORAGE OF THE DOCUMENTS

    Store this instruction and all other valid documents in a way that they

    are available, when required.

    In case of moving or selling hand the documents over to the

    successor.

  • 5TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    2. NOTES ON THE DOCUMENTATION

    2.1 FUNDAMENTAL SAFETY INSTRUCTIONS

    DANGER!

    WARNING!

    NOTE!

    ATTENTION!

    Imminent danger

    which causes grievous bodily harm or leads to death.

    Potentially dangerous situation,

    which could cause grievous bodily harm or lead to death.

    Potentially dangerous situation,

    which could cause bodily harm.

    Potentially dangerous situation,

    which could cause bodily harm or could damage components of the heat

    pump or things in the surrounding area.

    Application notes

    and other useful information, which facilitate the intended use of the

    machine.

  • 6

    2. NOTES ON THE DOCUMENTATION

    2.2 USED SYMBOLS

    danger zone danger through electric current

    warning of hot surfaces and fluids STOP

    unlock before working

    read the instruction

    note: damage

    mandatory signs for wearing protective gear

  • 7TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    2. NOTES ON THE DODUMENTATION

    2.3 INTENDED USE

    The ratiotherm heat pump WP Max-HiQ/LoQ is constructed according to the state of the art and the

    certified safety regulations.

    The heat pump is only intended for the preparation of hot water and the generation of heat and cold in

    residential and / or non-residential buildings.

    Incorrect or non-intended use could result in danger to life of the operator or a third party.

    In addition impairments of the devices and other material assets can arise.

    The ratiotherm heat pump WP Max-HiQ/LoQ is not intended for being used by individuals

    (including children) with restricted physical, sensory or mental abilities.

    The heat pump also can not be operated by individuals with a lack of experience and/or

    knowledge.

    • Unless they are supervised by an individual responsible for their safety or they received

    instructions on how to use the device.

    The ratiotherm heat pump WP Max-HiQ/LoQ is exclusively intended for the preparation of

    hot water (process water) and the generation of heat and cold.

    Any other or futher use is considered improper. The manufacturer/supplier is not liable for

    damage caused by improper use.

    The operator is responsible for the risks.

    Proper use also includes observing the operating and installation instruction as well as all

    other valid documents and the conditions for inspection and maintenance.

  • 8

    2. NOTES ON THE DOCUMENTATION

    2.4 GENERAL SAFETY INSTRUCTIONS

    WARNING! DAMAGES POSSIBLE

    • Operation of the heat pump only by qualified individuals.

    • Only for intended use.

    • Any other usage is a misuse.

    ATTENTION! RISK OF SCALDING

    • The outflow temperatures at the hot water extraction points might be

    up to 60 °C.

    • Carefully check the water temperature at the hot water extraction

    points before placing your hands under the water jet.

    NOTE! DAMAGES POSSIBLE

    Damages of the heat pump and components possible.

    • Read and follow the instructions.

    • To avoid accidents and material damage observe the safety

    instructions.

    • Observe the national rules of the country in which the ratiotherm heat

    pump WP Max-HiQ/LoQ is used.

    WARNING! DAMAGES POSSIBLE

    Do not make any changes:

    • to the heat pump;

    • to the water pipes and the power lines;

    • to the safety valve;

    • to structural conditions, which could influence the operational safety of

    the device;

    • to structural conditions near the device, insofar as they could influence

    its operational safety.

  • 9TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    2. NOTES ON THE DOCUMENTATION

    2.5 INSTALLATION AND ADJUSTMENTS

    The installation, commissioning or dismantling of the device is only

    allowed to be done by technicians with specific knowledge.

    Applicable rules, requirements and guidelines as well as local

    installation specifications must be observed.

    ATTENTION!

    Safety valve and air outlet pipe

    During the heating process water volume increases. Therefore never

    close the air outlet pipe of the safety valve.

    Hot water may leak out of the air outlet pipe!

    Leakage

    Turn off the heat pump in case of any leakages in its area and

    disconnect it from the rest of the heating system.The leakage should

    be fixed immediately.

    NOTE!

    Corrosion damages

    Don‘t use sprays, solvents, chlorinated detergents, colours, glues etc.

    in the environment of the heat pump to avoid corrosion.

    Spare and wear parts

    Components, which weren‘t tested in conjunction with the heat pump,

    could cause damages at the device or affect its functions. Install

    original spare and original wear parts exclusively!

    LEAKAGE

  • 10

    2. NOTES ON THE DOCUMENTATION

    2.6 GUIDLINES, NORMS AND LAWS

    When installing the heat pump, the following requirements, rules and guidelines have to be

    observed:

    IN GERMANY:

    • VDE- as well as EVU rules and requirements (especially VDE 0100);

    • Rules and requirements of the local utilities;

    • DVGW worksheet W 382

    „Installation and operation of pressure reducers in drinking water consumption

    systems“;

    • DIN 1988 – TRWI technical rules for drinking water installation;

    • DIN 4753 – Water heating systems for drinking and operating water;

    • DIN 8947 – Ready for connection heat pumps for hot water preparation with

    electrically driven compressors;

    • Accident prevention regulations VGB 20 „refrigeration plants“ with

    operational instructions;

    • Energy saving regulations EnEV – Requirement for energy-efficient thermal

    insulation and systems in buildings from 2009

    Furthermore, local requirements and rules are valid. For example: local building

    regulations.

    In general, you have to observe the rules of the respective country!

  • 11TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    2. NOTES ON THE DOCUMENTATION

    2.7 QUALIFICATION OF PERSONNEL

    Specific knowledge is neccessary for the installation, the commissioning and

    the dismantling of the device and it has to be performed by skilled workers.

    By personnel we mean all individuals who work with the ratiotherm heat

    pump WP Max-HiQ/LoQ. With this in mind, trainees are not qualified

    personnel.

    We require that:

    • the operating personnel undergoes specific training in how to handle the

    ratiotherm heat pump WP Max-HiQ/LoQ;

    • the maintenance staff will adjust, test and repair the ratiotherm heat

    pump WP Max-HiQ/LoQ in a way that no personal and material risks

    arise.

  • 12

    2. NOTES ON DOCUMENTATION

    2.8 RESPONSIBILITY OF PERSONNEL

    ATTENTION!

    To avoid injuries of any type under any circumstances you have to comply

    with the general accident prevention regulations and have to use protective

    equipment.

    To guarantee a safe installation, the responsible technician has to ensure

    that:

    • the personnel has the neccessary qualifications and training courses;

    • the personnel has read and understood the instructions;

    • the personnel is able to read the instructions at any time;

    • the local accident prevention regulations as well as the environmental

    regulations are complied;

    • the personnel was instructed by a supervisor and that unauthorised

    individuals are kept away from the ratiotherm heat pump WP Max-HiQ/

    LoQ;

    • the ratiotherm heat pump WP Max-HiQ/LoQ is handed over and

    operated in a safe and working condition and that damages to the heat

    pump are removed immediatly or that the damaged heat pump gets shut

    down right away.

    Technical changes

    Technical changes to the machine are prohibited.

    The subsequent installation of safety devices as well as welding at

    supporting parts is also prohibited.

    Safety devices are not to be disabled. In general, it is only allowed to use

    original spare and component parts from the manufacturer.

  • 13TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    3. TECHNICAL DATA

    3.1 WP MAX-HiQ

    Max-HiQ F06 F14 F21power data heat modeW20/W55 heat output 3.06 to 8.7 5.9 to 19.8 7.8 to 25.1 kWpower consumption 0.66 to 2.2 1.5 to 5.2 1.9 to 5.9 kWcoefficient of performance 4.91 4.53 4.75compressor

    typefully hermetic, rotary piston,

    inverterfully hermetic, scroll, inverter

    stalling current LRA 32 40 45 Aamount of oil 0.63 2 2 Ltr.evaporatortype cooper soldered plate heat exchangermaterial stainless steel / coopervolume flow brine 0.4 to 1 0.8 to 2 1 to 4 m3/hpressure loss 0.2 0.3 0.3 bartemperature difference 3 5 5 Kconnection dimension 1 1/2“, AGcapacitortype cooper soldered plate heat exchangermaterial stainless steel / coopervolume flow water 0.8 to 2.2 1.2 to 2.5 1.6 to 4.8 m3/hpressure loss 0.2 0.3 0.3 bartemperature difference 5 to 10 Kconnection dimension 1 1/2“, AGrefrigeration cycleworking substance R134 Afilling quantitiy 1.4 1.9 2.2 kgmax. operating pressure 26 barelectricitygrid connection 230 V / 1~ / 50 Hz 400 V / 3~ / 50 Hzprotection 25 20 25 Amax. operating pressure

    compressor15 15,8 19 A

    device datasound pressure levelinner part at a distance of 1m 40 dB(A)

    dimensions inner part 777 x 1800 x 512 wxhxd (mm)weight 210 230 250 kgmax. operating pressure water 10 barmax. flow temperature 72 °C

  • 14

    3. TECHNICAL DATA

    3.2 WP MAX-LoQ

    Max-LoQ F06 F14 F21power data heat modeW10/W55 heat output 2.5 to 7.2 4.9 to 16.4 6.5 to 20.8 kWpower consumption 0.66 to 2.2 1.5 to 5.2 1.9 to 5.9 kWcoefficient of performance 3.77 3.33 3.33compressor

    typefully hermetic, rotary piston,

    inverterfully hermetic, scroll, inverter

    stalling current LRA 32 40 45 Aamount of oil 0.63 2 2 Ltr.evaporatortype cooper soldered plate heat exchangermaterial stainless steel / coopervolume flow brine 0.4 to 1 0.8 to 2 1 to 4 m3/hpressure loss 0.2 0.3 0.3 bartemperature difference 3 5 5 Kconnection dimension 1 1/2“, AGcapacitortype cooper soldered plate heat exchangermaterial stainless steel / coopervolume flow water 0.8 to 2.2 1.2 to 2.5 1.6 to 4.8 m3/hpressure loss 0.2 0.3 0.3 bartemperature difference 5 to 10 Kconnection dimension 1 1/2“, AGrefrigeration cycleworking substance R134 Afilling quantitiy 1.4 1.9 2.2 kgmax. operating pressure 26 barelectricitygrid connection 230 V / 1~ / 50 Hz 400 V / 3~ / 50 Hzprotection 25 20 25 Amax. operating pressure

    compressor15 15,8 19 A

    device datasound pressure levelinner part at a distance of 1m 40 dB(A)

    dimensions inner part 777 x 1800 x 512 wxhxd (mm)weight 210 230 250 kgmax. operating pressure water 10 barmax. flow temperature 72 °C

  • 15TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    3. TECHNICAL DATA

    3.3 PERFORMANCE CURVE OF MAX-HIQ F06

    Coefficient of performance, heat output and power consumption at varying speeds:

    Coefficient of performance at Heat output in kW at Power consumption in kW at100 % 75 % 50 % 25 % 100 % 75 % 50 % 25 % 100 % 75 % 50 % 25 %

    W10/W35 4.41 4.59 5.25 6.05 8.30 7.30 4.20 2.60 1.88 1.59 0.80 0.43W10/W55 3.08 3.05 3.52 3.44 7.00 6.10 3.80 2.10 2.27 2.00 1.08 0.61W20/W35 5.52 5.98 7.47 9.21 10.70 9.80 5.90 3.50 1.94 1.64 0.79 0.38W20/W55 3.73 3.79 4.57 4.53 9.30 8.30 5.30 2.90 2.49 2.19 1.16 0.64W30/W35 6.37 6.75 11.00 14.84 12.80 11.20 7.70 4.60 2.01 1.66 0.70 0.31W30/W55 4.65 4.71 5.75 6.00 12.00 11.20 6.90 3.90 2.58 2.38 1.20 0.65

    0

    2

    4

    6

    8

    10

    12

    14

    16

    W10/W35 W10/W55 W20/W35 W20/W55 W30/W35 W30/W55

    Coefficient of performance

    Coefficient of performance at 100 % Coefficient of performance at 75 %

    Coefficient of performance at 50 % Coefficient of performance at 25 %

    0

    2

    4

    6

    8

    10

    12

    14

    W10/W35 W10/W55 W20/W35 W20/W55 W30/W35 W30/W55

    Heat output

    Heat output in kW at 100 % Heat output in kW at 75 %

    Heat output in kW at 50 % Heat output in kW at 25 %

    0

    0,5

    1

    1,5

    2

    2,5

    3

    W10/W35 W10/W55 W20/W35 W20/W55 W30/W35 W30/W55

    Power consumption

    Power consumption in kW at 100 % Power consumption in kW at 75 %

    Power consumption in kW at 50 % Power consumption in kW at 25 %

  • 16

    Storage conditions:

    • Care must be taken to ensure frost-free storage.

    Installation conditions:

    • A floor drain must be provided as protection against water damage.

    • The ratiotherm heat pump WP Max-HiQ/LoQ has to be installed at a

    clean, ventilated and dry location. The ambient temperature must be > 10

    °C and < 35 °C year round.

    • The specified minimum distances must be observed for maintenance

    purposes.

    • Depending on the installation site a soundproof base is recommended.

    Dimensions:

    4. MECHANICAL INSTALLATION

    4.1 INNER PART

    Distance dimensions:

    50

    50

    130

    800

    ratiotherm

    3

    3

    2

    2

    1

    Datum: Name: Änderung: Dateipfad:Datum: Name:

    Gezeichnet:Geprüft:Genehmigt:

    Maßstab:

    4

    4

    5

    5

    Wänden

    [email protected] | www.ratiotherm.de

    HabermeyerWP Max-HiQ mit

    Blatt:

    6

    01.10.2019Format:

    WP Max-HiQ

    BB

    A

    F

    8

    8

    7

    7

    6

    CC

    D D

    E E

    F

    Heizung + Solartechnik GmbH & Co. KG

    Bezeichnung:

    AProjekt:

    Fax. +49 (0)8422 / 9977 - 30Tel. +49 (0)8422 / 9977 - 0D- 91795 Wellheimer Str. 34

    1

    max

    . 55

    177

    8

    882 512

    A A

    B B

    C C

    D D

    E E

    F F

    8

    8

    7

    7

    6

    6

    5

    5

    4

    4

    3

    3

    2

    2

    1

    1

    Datum: Name: Änderung: Dateipfad:Datum: Name:

    Gezeichnet:Geprüft:Genehmigt:

    Maßstab: Blatt: Format:Projekt: Bezeichnung:

    ratiotherm Heizung + Solartechnik GmbH & Co. KGD- 91795 Wellheimer Str. 34Tel. +49 (0)8422 / 9977 - 0Fax. +49 (0)8422 / 9977 - [email protected] | www.ratiotherm.de

    26.03.2020 HabermeyerAbmaßeWP Max-HiQ

  • 17TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    5. HYDRAULIC INSTALLATION

    5.1 CONNECTION SIZES AND DIMENSION

    • Barriers as well as ventilations are intended on site.

    • Sludge separators and magnetite separators must also be provided on

    site.

    • Tubes are recommended to be connected vibration-freely.

    Recommandation: Eckstein TWS 25 (F06), TWS 32 (F14), TWS 40 (F21)

    • The capacitor/sink pump is integrated in the device; a grid pump can be

    integrated optionally.

    • Fill the installation by the return flow.

    • A drain valve is installed in the machine.

    • Please hold the connections while tightening!

    99

    195

    377

    155

    5

    62 c

    a. 3

    5 bi

    s 55

    mm

    Quelle Austritt

    Heizung VL

    Quelle Eintritt

    Heizung RL

    Anschluss Sicherheitsgruppe

    A A

    B B

    C C

    D D

    E E

    F F

    8

    8

    7

    7

    6

    6

    5

    5

    4

    4

    3

    3

    2

    2

    1

    1

    Datum: Name: Änderung: Dateipfad:Datum: Name:

    Gezeichnet:Geprüft:Genehmigt:

    Maßstab: Blatt: Format:Projekt: Bezeichnung:

    ratiotherm Heizung + Solartechnik GmbH & Co. KGD- 91795 Wellheimer Str. 34Tel. +49 (0)8422 / 9977 - 0Fax. +49 (0)8422 / 9977 - [email protected] | www.ratiotherm.de

    26.03.2020 HabermeyerAnschlussmaßeWP Max-HiQ

    security group connection

    source exits

    heating flow

    source entry

    heating return

  • 18

    5. HYDRAULIC INSTALLATION

    5.2 SCHEME

    TT

    M

    Hoc

    htem

    pera

    tur

    Hei

    zkre

    is

    Trin

    kwas

    ser

    Kom

    pakt

    stat

    ion

    rZR

    16x

    2

    0 - 1

    0VA

    uto

    - O -

    Han

    d

    I

    O

    230V

    Han

    d - O

    - A

    uto

    Net

    z

    000

    ∑m

    ³

    Osk

    ar° 4

    00l

    110

    32

    89

    64

    75

    Osk

    ar° 4

    00l

    110

    32

    89

    64

    75

    T T

    M

    A 1

    A 1

    S 6

    S 6

    S 7

    S 7

    S 15

    S 15

    A 16

    PWM

    A 16

    PWM

    A 1

    A 1

    S 1

    S 1

    A2 /

    230V

    A14

    / PW

    MA2

    / 23

    0VA1

    4 / P

    WM

    A2 /

    230V

    A14

    / PW

    MA2

    / 23

    0VA1

    4 / P

    WM

    S 2

    S 2

    S 3

    S 3

    S 11

    S 11

    Auße

    nfüh

    ler

    S 4

    S 4

    S 13

    S

    13

    A 3 A

    8/9

    rZR

    16x

    2Kn

    oten

    1

    E

    A 1/

    A 2/

    A 3

    S 1

    Nam

    eD

    atum

    13.0

    5.20

    19Pl

    anbe

    zeic

    hnun

    g:rZ

    R 1

    6x2

    Stan

    dard

    WP

    Max

    -HiQ

    Acht

    ung:

    Die

    ses

    Sche

    ma

    ist n

    ur

    eine

    Em

    pfeh

    lung

    und

    erh

    ebt i

    n je

    glic

    her H

    insi

    cht k

    eine

    n An

    spru

    ch a

    uf V

    olls

    tänd

    igke

    it.G

    eprü

    ft G

    ezei

    chne

    tL.

    Böh

    eim

    27.0

    5.20

    19L.

    Böh

    eim

    Sche

    ma

    Nr.:

    M

    T

    S16

    000

    ∑m

    ³

    Absp

    erre

    inric

    htun

    g

    Absp

    erre

    inric

    htun

    gm

    it Si

    cher

    ungs

    klap

    pe

    Mot

    orve

    ntil

    3-W

    ege-

    Mis

    cher

    mit

    Stel

    lmot

    or

    (Sum

    men

    tor o

    ben)

    Absp

    erre

    inric

    htun

    g m

    it En

    tleer

    ung

    M

    F3-

    Weg

    e-M

    isch

    er m

    it Fe

    stst

    ellv

    entil

    (S

    umm

    ento

    r obe

    n)

    Sich

    erhe

    itsve

    ntil

    Man

    omet

    er

    (Dru

    ckm

    esse

    r)

    Pum

    pe in

    Flie

    ßric

    htun

    g

    Rüc

    ksch

    lagk

    lapp

    e

    Plat

    tenw

    ärm

    etau

    sche

    r

    Dur

    chflu

    ssm

    enge

    n Ei

    nste

    llven

    tilSt

    röm

    ungs

    scha

    lter

    / -ge

    ber

    Ther

    mom

    eter

    Wär

    mez

    ähle

    r

    Sens

    or

    Ausd

    ehnu

    ngsg

    efäß

    Entle

    erun

    g

    SJ.

    Kru

    ck13

    .05.

    2019

    Geä

    nder

    t G

    eänd

    ert

    T

    A

    TT

    KW

    WW

    M

    M

    TT

    S9S9

    TT

    DL 3

    /6DL

    3/2

    DL 3

    /6DL

    3/2

    000

    ∑m

    ³

    S10

    S10

    M

    Reset

    Possible coupling of the air source heat pump WP Max-Air and the high-temperature heat pump Max-HiQ

    for existing buildings.

    WP

    Max

    -Air

    WP

    Max

    -HiQ

  • 19TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    5. HYDRAULIC INSTALLATION

    5.3 PRESSURE LOSS DIAGRAM CAPACITOR

    012345678910

    010

    0020

    0030

    0040

    0050

    0060

    0070

    0080

    0090

    0010

    000

    Druckverlust [mwc]

    Durc

    hflu

    ss [l

    /h]

    Druc

    kver

    lust

    diag

    ram

    m K

    onde

    nsat

    or

    F 06

    : tot

    aler

    Dru

    ckve

    rlust

    [mw

    c]F

    14: t

    otal

    er D

    ruck

    verlu

    st [m

    wc]

    F 21

    : tot

    aler

    Dru

    ckve

    rlust

    [mw

    c]

    Pres

    sure

    loss

    dia

    gram

    cap

    acito

    r

    Pressure loss [mwc]

    Flow

    rat

    e [l/

    h]

    F06:

    tot

    al p

    ress

    ure

    loss

    [mw

    c]F1

    4: t

    otal

    pre

    ssur

    e lo

    ss [m

    wc]

    F21:

    tot

    al p

    ress

    ure

    loss

    [mw

    c]

  • 20

    012345678910

    050

    010

    0015

    0020

    0025

    0030

    0035

    0040

    0045

    0050

    00

    Druckverlust [mwc]

    Durc

    hflu

    ss [l

    /h]

    Druc

    kver

    lust

    diag

    ram

    m V

    erda

    mpf

    er u

    nd Fe

    rnw

    ärm

    even

    tile

    F06:

    Dru

    ckve

    rlust

    Ver

    dam

    pfer

    [mw

    c]F0

    6: D

    ruck

    verlu

    st V

    erda

    mpf

    er u

    nd F

    ernw

    ärm

    even

    til [m

    wc]

    F14:

    Dru

    ckve

    rlust

    Ver

    dam

    pfer

    [mw

    c]F1

    4: D

    ruck

    verlu

    st V

    erda

    mpf

    er u

    nd F

    ernw

    ärm

    even

    til [m

    wc]

    F21:

    Dru

    ckve

    rlust

    Ver

    dam

    pfer

    [mw

    c]F2

    1: D

    ruck

    verlu

    st V

    erda

    mpf

    er u

    nd F

    ernw

    ärm

    even

    til [m

    wc]

    5. HYDRAULIC INSTALLATION

    5.4 PRESSURE LOSS DIAGRAM EVAPORATOR Pr

    essu

    re lo

    ss d

    iagr

    am e

    vapo

    rato

    r an

    d di

    stric

    t he

    at v

    alve

    s

    Pressure loss [mwc]

    Flow

    rat

    e [l/

    h]

    F06:

    pre

    ssur

    e lo

    ss e

    vapo

    rato

    r [m

    wc]

    F14:

    pre

    ssur

    e lo

    ss e

    vapo

    rato

    r [m

    wc]

    F21:

    pre

    ssur

    e lo

    ss e

    vapo

    rato

    r [m

    wc]

    F06:

    pre

    ssur

    e lo

    ss e

    vapo

    rato

    r an

    d di

    stric

    t he

    at v

    alve

    [mw

    c]

    F14:

    pre

    ssur

    e lo

    ss e

    vapo

    rato

    r an

    d di

    stric

    t he

    at v

    alve

    [mw

    c]

    F21:

    pre

    ssur

    e lo

    ss e

    vapo

    rato

    r an

    d di

    stric

    t he

    at v

    alve

    [mw

    c]

  • 21TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    5. HYDRAULIC INSTALLATION

    5.5 REQUIREMENTS FOR THE QUALITY OF THE HEATING WATER

    Parameter Unit Concentration Copper brazed

    pH level /

    < 6.06.0 - 7.57.5 - 8.5

    8.5 - 10.0> 10

    -°+°°

    Conductivity µS/cm< 10

    10 - 500500 - 1,000

    > 1,000

    ++°-

    Chloride mg/L

    < 1010 - 5050 - 8080 - 100

    100 - 1,000> 1,000

    ++++°-

    Free chlorine mg/L< 0.5

    0.5 - 1.01.0 - 5.0

    > 5.0

    ++°-

    Total hardness °dH< 5

    5 - 1515 - 30> 30

    ++°-

    Ammonia (NH3, NH4+) mg/L

    < 22 - 20> 20

    +°-

    Alkalinity (HCO3) mg/L< 60

    60 - 300> 300

    ++°

    Sulphate (SO42-) mg/L

    < 100100 - 300

    > 300

    +°/--

    HCO3 / SO42- mg/L > 1.5< 1.5

    +°/-

    Nitrates (NO3) mg/L< 100> 100

    Hydrogen sulphide (H2S) mg/L< 0.05> 0.05

    +°/-

    Free carbon dioxide (CO2) mg/L< 5

    5 - 20> 20

    +°-

    Manganese mg/L < 0.1> 0.1+°

    Iron (Fe) mg/L < 0.2> 0.2+°

    Aluminium mg/L < 0.2> 0.2+°

    It must be ensured that the heating water meets all the requirements. If two or more criterias are not optimal (°) or if one criteria does not meet the requirements (-), no claim under guarantee will be considered.

    A maximum of 50 % glycol may be present in the system water.

  • 22

    6. ELECTRICAL INSTALLATION

    6.1 NOTES

    • The power supply of the heater is controlled by the control cabinet and it

    has to be protected by a fault-current circuit breaker with a trip current of

    not more than 30mA (RCD) and with the fitting power.

    • The ground fault circuit interrupter for the heater has to be labeled

    separatly (for example:“HP“). Please note the right wiring of phase/neutral

    conductor.

    • Observe the rotating field orientation (right turning).

    • The machine has to be grounded.

    • Use cable diameters fitting to the power of the heater.

    • The electrical installation has to comply with the valid standards and the

    generally accepted rules of engineering.

    • Do not work on hydraulic or mechanical parts of the machine while under

    voltage.

    • The same applies to filling or subsequent pressurisation.

    • Even if the main switch of the device is turned off, there will be voltage at

    the cable clamp.

    • To separate the device from the grid galvanically, the ground fault circuit

    interrupter in the switch cabinet has to be turned off.

    • Maintenance work can only be performed by authorised individuals.

    • Never short-circuit the safety pressure limiter of the heat pump.

    6.2 ELECTRICAL INSTALLED POWER

    230 V Compressor F06 B25

    400 V Compressor F14 B16

    400 V Compressor F21 B35

    230 V Controlling B6

    Adviced Protection:

  • 23TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    6. ELECTRICAL INSTALLATION

    6.3 TERMINAL SCHEME AND DESCRIPTION

    • Clamping range X1 is intended for the compressor and the electrical heating rod. Depending on the

    power output (for example F06) a single-phase connection is possible. The connection is delivered with

    bridges (electrical heating rod only active when the compressor is locked). The bridges can be removed

    with a separate supply line.

    • X2.2 is the output of a source pump. If this is already integrated in the housing, the clamping point is

    omitted.

    • X3.3 and X3.4 are processing the signal coming from the grid operator/energy supplier. The connection

    from X3.3 to the power supply company is downward compatible.

    • Wire this connection as a NO (normally open) contact (barrier aktive -> closed).

    X1L1 L1 L2 L2 L3 L3 N N PE PE

    Compressor Heating rod Compressor Heating rod Compressor Heating rod Compressor Heating rod Compressor Heating rod

    400 V Grid

    (Jointly bridged in the factory, remove bridges if the supply lines are separately!)

    X31 GND GND 2 3 GND GND 4

    Enable Contact

    (potential-free)

    Speed-Signal

    (0 - 10 V)

    Smart Grid 1 /

    EVUSmart Grid 2

    X3GND 12 V CAN-H CAN-L CAN-H CAN-L

    CAN-Bus

    (connection to RT-GLT)

    CAN-Bus

    (connection to RT-GLT)

    X2L1 N PE 1 N PE 2 N PE

    230 V Grid

    Regulation/Pumps

    230 V

    Error Output

    230 V Output

    Source Pump

  • 24

    6. ELECTRICAL INSTALLATION

    6.4 CAN-BUS PLAN

    OPEN

    TERM

    TERM

    MAIN CONTROLLER 16x2

    CMI

    HEAT PUMP

    CAN-L CAN-H 12 V GND

    WALL CONTROLLER

    Pay attention to the correct wiring

    of the CAN-Bus!

    No star-shaped gird!

    Use a shielded, 4-pole cable!

    Pay attention to the instructions of

    the technische Alternative!

    Non-binding cable advice:

    Unitronic Bus CAN FD P 2x2x0.34

  • 25TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    7. REFRIGERATION INSTALLATION

    7.1 REFRIGERATION SCHEME

    Que

    lle E

    intri

    tt

    Que

    lle A

    ustri

    tt

    TCE

    KühlplatteInverter

    Hei

    zung

    VL

    Hei

    zung

    RL

    PTPT

    TT

    TT

    TT

    K11

    S2

    K11

    S5

    K11

    S3

    K11

    S6

    K12

    S4

    K12

    S1

    K11

    S4

    K12

    S3

    K11

    A1

    + A

    8

    K11

    A1

    + A

    9

    K11

    A6

    + A

    7

    K12

    A8

    Sou

    rce

    entr

    y

    Sou

    rce

    exit

    Hea

    ting

    flow

    line

    Hea

    ting

    retu

    rn fl

    ow

    InverterCooling plate

  • 26

    The ratiotherm heat pump WP Max-HiQ/LoQ possesses a complete refrigeration cycle and uses a source

    circle as the primary energy source.

    The refrigeration cycle is hermetically completed and consists of a rotary compressor (F06) or a scroll

    compressor (F14, F21), a condenser (plate heat exchanger), an evaporator (plate heat exchanger) and an

    electronical expansion valve, which controls the inflow of the refrigerant. The working fluid, which is used, is

    the enviromentally friendly R134A.

    The ratiotherm heat pump WP Max-HiQ/LoQ is shipped out ready for use. A further refrigeration commissioning

    is not necessary.

    The ratiotherm heat pump WP Max-HiQ/LoQ is operated by the controller RSM610 by the company Technische

    Alternative. On a separate display you can find all parameters and operating states of the heat pump.

    The heat pump WP Max-HiQ/LoQ is compatible with most of the electric radiators, gas and oil boilers.

    8. STRUCTURE AND FUNCTION

    8.1 ASSEMBLY AND SPARE PARTS

  • 27TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    Control logic:

    • The heat pump is requested using a potential-free, digital signal. Thereupon pumps and valves are

    activated. After 45 seconds the compressor will be started.

    • To avoid an unintentional start the enable signal is delayed by 10 seconds.

    • When the device is activated, the minimum running time amounts to 5 minutes. An error turns off the

    machine immediately.

    • The reference speed of the compressor is able to be controlled by an external management tool with the

    help of a 0-10 V signal.

    • If there is no 0 - 10 V signal, the compressor will run with a constant, configurable speed (factory setting:

    75 %).

    • While starting the compressor, the running speed is limited. Only after 4 x 1.5 minutes the compressor

    is accelareted to full speed.

    • If the source temperature inside the evaporator falls below 11 °C for longer than one minute, the machine

    will be shut down because of frost protection. If the evaporator temperature exceeds 55 °C, the starting

    of the machine is prevented. When the temperatures are back to normal, the machine starts as usual.

    • If the temperature on the source site falls below 8 °C, a frost protection malfuntion will be triggered and

    the installation will be blocked for 7 minutes or will be locked completely after several malfunctions.

    • The condensator pump controls deltaT between heating flow line and heating return flow (factory setting:

    6 K).

    • If the heating flow line temperature exceeds 69 °C, the pump will begin to raise the speed to prevent a

    shut down.

    • If the heating flow line temperature exceeds 72 °C, the machine will shut off automatically for 20 minutes.

    If the temperature falls meanwhile, the installation will start after 20 minutes again.

    • The evaporator pump controls deltaT between source entrance and exit (factory setting: 3 K).

    • If an anomalie is detected (high pressure, low pressure, frost protection), an error will be triggered and

    the installation will be blocked for 5 or 7 minutes. This can not be undone by the reset button! If the same

    error arises three times within one hour, the heat pump will be locked. The reset button is able to undo

    the lock!

    • To preempt an anomaly, high pressure, low pressure and compressor temperature are observed and if

    necessary, the speed is reduced for at least 8 minutes.

    8. STRUCTURE AND FUNCTION

    8.2 CONTROL LOGIC AND ACTIVATION

  • 28

    9. OPERATION NOTES

    9.1 CONTROLLER OPERATION

    • The rZR16x2 is operated by a 4,3“ Touch-Screen.

    • For an easier handling a touch pen is attached below the controller.

    • With the touch pen you can operate the surface and scroll by moving the scroll bar.

    • By clicking on one of the windows you get to the corresponding submenu.

    The controlling lamp is able to show different states:

    • red permanent light- controller is booting (= standard routine after turning the heat pump on, a reset

    or an update) or is showing a report, which isn‘t deleted yet.

    • orange permanent light - hardware initialisation after booting.

    • green permanent light - controllers standard operation.

    • green „blinking“ - After hardware initialisation, the controller is waiting for 30 seconds to get the

    necessary information (sensor values, network entrances).

    Controls:

    main menuprevious page next page

    Operating Buttons:

    on/off-button reset-button

  • 29TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    9. OPERATION NOTES

    9.1 CONTROLLER OPERATION

    Overview of the menu structure:

  • 30

    9. OPERATION NOTES

    9.1 CONTROLLER OPERATION

    Heating rod: ON

    Switching on the heating rod is possible

    independent of the bivalence temperature.

    Release: ON

    Heat pump is allowed to start upon request.

    Enter password

    Enter the expert password to get to the

    expert menu.

    Manual mode: ON

    Forced start of the heat pump is possible

    independend of the request signal.

  • 31TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    9. OPERATION NOTES

    9.1 CONTROLLER OPERATION

    K11 S2 T-evaporator entry

    K11 S3 T-evaporator exit

    K11 S4 high pressure

    K11 S5 T.heat pump flow line

    K11 S6 T.heat pump reset flow/reset

    K11 A7 compressor 0-10 V

    K11 A8 evaporation pump PWM

    K11 A9 capacitor pump PWM

    K11 A10 district heat valve 0-10 V

    K12 S3 inverter disruption/hot gas

    K12 S4 low pressure

    K12 A8 ex-valve PWM

    K12 DL1 volume flow source

    K12 Fkt 11 evaporation temperature

    SH K12 Fkt 9 actual-overheating

    E-Stab S1 heating rod level 1

    E-Stab S2 heating rod level 2

    E-Stab S3 heating rod level 3

  • 32

    9. OPERATION NOTES

    9.1 CONTROLLER OPERATION

    Minor menu

    To get to the minor menu you have to press

    the display for 5 seconds. In the minor

    menu you are able to change the basic

    settings and get to the controller menu.

    Controller menu

    Link to the controller menu.

    Basic settings

    Set language, brightness and timeout of the

    display here.

    Date/time of the day/location

    Set time zone and date here.

  • 33TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    9. OPERATION NOTES

    9.2 SETTINGS

    Fixed values Description Setting

    possibilities

    Default

    UserTarget T-Diff capacitor target temperature difference at the capacitor 1 °C to 10 °C 8 °CTarget-speed Verdi. Fix target speed of the compressor, if there is no

    external speed signal0 % to 100 % 75 %

    ExpertT-evaporator maximum maximum permissable evaporator temperature 35 °C to 70 °C 55 °CT-evaporator minimum minimum permissable evaporator temperature 8 °C to 20 °C 11 °CTarget-overheating target-overheating of the expansion valve in the

    outdoor part while operating normally0 °C to 10 °C 5,3 °C

    Start-opening ex-valve start-opening of the expansion valve in the

    outdoor partlevel 0 to 500 level 280

    T-target evaporator

    entrance

    target-evaporator entrance temperature (mixed

    temperature injection circuit)10 °C to 30 °C 30 °C

    Target-T-Diff evaporator target-temperature difference between

    evaporator entrance and exit1 °C to 8 °C 3,5 °C

    Speed power reduction compressor speed while power reduction is

    activatedlevel 0 to 100 level 45

    Limit high pressure maximum pressure at which a high pressure

    error/disruption will be triggered

    20 bar to

    26 bar24 bar

    Limit low pressure minimum pressure at which a low pressure

    error/disruption will be triggered0,8 bar to 5 bar 1 bar

    Limit frost protection frost protection error/disruption will be

    triggered at this minimum temperature4 °C to 12 °C 8 °C

    Electrical heating rod own

    power supply

    Activation of parallel operation of electrical

    heating rod and compressor. Only possible if

    the electrical heating rod has its own supply

    line.

    OFF / ON OFF

    Time HP/LP-error time blockade until restart, after HP/LP-error

    has occurred0 to 24 h 5 min

    LP emergency mode minimum pressure at which a temporary

    power reduction is triggered1 bar to 10 bar 1,5 bar

    HP emergency mode maximum pressure at which a temporary

    power reduction is triggered15 bar to 25 bar 22 bar

  • 34

    Error message HP error HP disruption

    Error description High pressure protection of the refrigeration circuit is triggered. Behaviour of the heat

    pump

    • Heat pump is locked for 5 min.

    • If there are 3 errors in one hour, the

    HP error changes to HP diruption.

    • Heat pump is locked.

    • Unlocking of the heat pump by

    using the reset-button.Error reason • Missing heat dissipation

    • Blockage in refrigeration circuit

    • Heat sink too hotDebugging • Examination of the sink temperature or rather target temperatures

    • Temperature below max. water temperatur according to label

    • Examination of heat dissipation to medium (pump, heat exchanger)

    • Venting and examination of heating pressure

    • E xamination of cooling technology

    HIGH PRESSURE

    Error message Inverter disruption

    Error description Malfunction contact of the inverter does not lock.Behaviour of the heat

    pump

    • Heat pump is locked.

    • Unlocking of the heat pump by using the reset-button.Error reason • Missing power supply

    • Other inverter disruptionDebugging • Check the power supply (rotary field, phase failure)

    • Check the error codes (see appendix)

    INVERTER

    10. DEBUGGING

    9. OPERATION NOTES

    9.2 SETTINGS

    T.-compressor-exit

    emergency mode

    maximum exit temperature at which a

    temporary power reduction is triggered80 °C to 130 °C 110 °C

    Time frost protection error time blockade until restart, when a frost

    protection error has been triggered0 to 24 h 7 min

    Time until disruption If there are three errors within one hour,

    machine will turn off.0 to 24 h 60 min

    Fixed values Description Setting

    possibilities

    Default

    Expert

  • 35TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    10. DEBUGGING

    LOW PRESSUREError message LP error LP disruption

    Error description Low pressure protection of the refrigeration circuit is triggered. Behaviour of the heat

    pump

    • Heat pump is locked for 5 min.

    • If there are 3 errors in one hour, the

    HP error changes to HP diruption.

    • Heat pump is locked.

    • Unlocking of the heat pump by

    using the reset-button.Error reason • Missing heat absorption

    • Not enough refrigerant in the refrigeration circuit

    • Blockage of the refrigeration circuitDebugging • Examination of heat absorption in the evaporator (flow, temperature); venting

    (maybe)

    • Examination of cooling technology

    FROST PROTECTIONError message Frost protection error Frost protection disruption

    Error description Frost protection of the hydraulic circuit is triggered.Behaviour of the heat

    pump

    • Heat pump is locked for 10 min.

    • If there are 3 errors in one hour, the

    HP error changes to HP diruption.

    • Heat pump is locked.

    • Unlocking of the heat pump by

    using the reset-button.Error reason • Missing heat absorption at the inner part

    • Heat source too coldDebugging • Examination of heat source (temperatures, pumps, heat exchangers)

    • Venting

  • 36

    Cleaning of the heating side:

    • Cleaning: has to be performed by an installer

    • Rinsing device: connections at the flow and return flow of the capacitor

    • Capacitor: rinsing against the normal flow direction (observe gravitation brake)

    11. MAINTENANCE

    The device‘s surface could get damaged by wrong cleaning agents.

    • Don‘t use scouring or cleaning agents, which could damage the cladding, the

    instruments or other operating elements made of plastic.

    • Don‘t use sprays, solvents or chlorinated cleaning agents.

    • Clean the cladding of the heat pump with a wet cloth and a bit of soap.

    • Avoid putting and leaning things against and on the heat pump.

    NOTE! DAMAGES POSSIBLE

    11.1 CLEANING

    Prerequisite for a lengthy operational readiness, operational safety and for a high reliability are

    maintenances of the device on a regular basis by an accepted, qualified and by ratiotherm authorised

    technician. We suggest to execute the maintenance once a year.

    11.2 MAINTENANCE

    NOTE!

    Safety valve could be stuck due to lime deposits.

    • Manually operate the safety valve of the heat installation once a month.

  • 37TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    11. MAINTENANCE

    11.2 MAINTENANCE

    WARNING!

    Risk of material and personnel damages due to improper handling!

    • Never try to do maintenance or repair work at the heat pump yourself.

    • For maintenance or repair work commission an accepted, qualified and by ratiotherm

    authorised technician.

    • We suggest the conclusion of a maintenance agreement.

    • Neglected maintenance might adversely affect the operational safety of the device

    and lead to material and personnel damages.

    11.3 TIGHTNESS CHECK

    Tightness check of the heat pump:

    According to the (EG) Nr. 842/2006 regulation (specific fluorinated greenhouse gases) the heat pump has

    to be checked for tightness regularly. This test can be done by a qualified technician (tested in refrigeration

    plant construction or certified technician with a specialisation in refrigeration technique).

    Attention should be paid to:

    • DIN EN 378:2000 „refrigeration plants and heat pumps - safety-related and environmentally relevant

    requirements“

    • VDMA standard sheet 24243 (august 2005) „refrigeration machines and plants - tightness of

    refrigeration plants and heat pumps - leakage detection/tightness check“

    NOTE!

    • The test has to be made according to the asset ledger.

    • The results of the test have to be documented properly and stored for at least 5

    years. In the „asset ledger for heat pumps“ you find the system log.

  • 38

    When terminating the operation of the heat pump, the dismantling of the machine can only be done by

    qualified personnel. It should be ensured, that hazardous substances and waste are disposed of properly.

    Beachten Sie bei Demontage der Wärmepumpe die Hinweise zu Beginn der Technischen Unterlage sowie

    die unten aufgeführten Sicherheitshinweise.

    12. DECOMMISSIONING & DISPOSAL

    DANGER!Danger through electricity.

    Close to electrical equipment heavy or rather deadly electric shocks are possible.

    • Remove voltage before decommissioning/dismantling of the machine.

    • Secure against restart.

    TEMPORARY DECOMMISSIONINGShift the main switch to the position „OFF“.

    ATTENTION!

    Damages to components and functions

    Incorrect decommissining could cause damages to components and functions.

    Damages caused by frost possible

    • Water freezes below 0 °C outdoor temperature.

    • Without emptying the heating circuit decommissioning is only allowed at

    temperatures higher than 0 °C.

    FINAL DECOMMISSIONING/DISPOSAL• Only a specialized company is allowed to execute the final decommissioning/disposal.

    • Environmentally relevant requirements relating to recycling and disposal of operating materials and

    components have to be observed according to the established norms.

    ATTENTION!

    Environmental pollution due to improper disposal.

    Improper disposal of components and operating materials might lead to environmental

    damages.

    • Dispose electrical and electronical components of the heat pump properly.

    • Dispose refrigerants properly.

  • 39TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.1 ELECTRICAL PLAN

  • 40

    13. ANNEX

    13.1 ELECTRICAL PLAN

  • 41TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.1 ELECTRICAL PLAN

  • 42

    13. ANNEX

    13.1 ELECTRICAL PLAN

  • 43TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.1 ELECTRICAL PLAN

  • 44

    13. ANNEX

    13.2 PUMP WILO-PARA STG

    Technical dataConnection voltage 1 ~ 230 V +10 %/-15 %, 50/60 HzProtection class IP X4DEnergy efficiency index EEI See rating plate (6)Fluid temperatures at max. ambient

    temperature

    -20 °C to +95 °C (Heating/GT)

    -10 °C to +110 °C (ST)Ambient temperature 0 °C to +70 °CMax. operating pressure 10 bar (1000 kPa)Minimum inlet pressure at

    +95 °C/+110 °C

    0,5 bar/1,0 bar (50 kPa/100 kPa)

    Indicator lights (LEDs)

    Signal display

    • LED is lit up in green in normal operation

    • LED lights up/flashes in case of fault

    Display of selected control mode Δp-v, Δp-c and

    constant speed

    Display of selected pump curve (I, II, III) within the

    control mode

    Ext.

    Ext.

    Bedientaste

    Press

    • Select control mode

    • Select pump curve (I, II, III) within the control mode

    Press and hold

    • Activate the pump venting function (press for 3

    seconds)

    • Activate manual restart (press for 5 seconds)

    • Lock/unlock button (press for 8 seconds)

  • 45TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.2 PUMP WILO-PARA STGCONTROL MODES AND FUNCTIONS

    Recommended for underfloor heating or for large-sized

    pipes, applications without a variable pipe network

    curve (e.g. storage charge pumps) or single-pipe

    heating systems with radiators.

    The control keeps the set delivery head constant

    irrespective of the pumped volume flow.

    There are three pre-defined pump curves (I, II, III) to

    choose from.

    Constant speed (I, II, III)

    Recommended for systems with fixed system

    resistance requiring a constant volume flow.

    The pump runs in three prescribed fixed speed stages

    (I, II, III).

    NOTICE!

    Factory setting:

    Constant speed, pump curve III

    External control via a iPWM signal

    The required setpoint/actual value comparison for

    control is performed by an external controller.

    A PWM signal (pulse-width modulation) is fed as a

    correcting variable to the pump.

    The PWM signal generator gives the pump a periodic

    sequence of impulses (the duty cycle) in accordance

    with DIN IEC 60469-1.

    Constant differential pressure Δp-c (I, II, III)

  • 46

    13. ANNEX

    13.2 PUMP WILO-PARA STG

    iPWM 1 mode (heating application):

    In iPWM 1 mode, the pump speed is controlled

    according to the PWM input signal.

    Behaviour in the event of a cable break:

    If the signal cable is separated from the pump, e.g. due

    to a cable break, the pump accelerates to maximum

    speed.

    PWM signal input [%]> 5: Pump runs at maximum speed5 - 85: The speed of the pump decreases linearly

    from nmax to nmin85 - 93: Pump runs at minimum speed (operation)85 - 88: Pump runs at minimum speed (starting)93 - 100: Pump stops (standby)

    iPWM 2 mode:

    In iPWM 2 mode, the pump speed is controlled

    according to the PWM input signal.

    Behaviour in the event of a cable break:

    If the signal cable is separated from the pump, e.g. due

    to a cable break, the pump stops.

    PWM signal input [%]0 - 7: Pump stops (standby)7 - 15: Pump runs at minimum speed (operation)12 - 15: Pump runs at minimum speed (starting)15 - 95: The speed of the pump increases linearly from

    nmin to nmax> 95: Pump runs at maximum speed

  • 47TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.2 PUMP WILO-PARA STG

    Venting

    The pump venting function is activated by

    pressing and holding the operating button (for 3

    seconds) and automatically vents the pump.

    The heating system is not vented.

    Manual restart

    A manual restart is initiated by pressing and

    holding the operating button (for 5 second) and

    unblocks the pump if required (e.g. after long

    standstill period in summer).

    Lock/unlock the button

    The key lock is activated by pressing and holding

    the operating button (for 8 seconds) and locks

    the pump’s current settings. It protects against

    undesired or unauthorised adjustment of the

    pump.

  • 48

    13. ANNEX

    13.3 PUMP WILO STRATOS PARA

    Stra

    tos

    PAR

    A

    E

    lect

    roni

    cally

    con

    trol

    led

    Hig

    h Ef

    ficie

    ncy

    pum

    p

    25

    T

    hrea

    ded

    conn

    ectio

    n D

    N 2

    5

    1-8

    1-8

    = d

    eliv

    ery

    head

    in [m

    ] at Q

    = 0

    m3 /h

    Stra

    tos

    PAR

    A 25

    /1-8

    T1

    Dat

    ashe

    et S

    trato

    s PA

    RA

    **/1

    -802

    /10

    T1

    Stra

    tos

    PAR

    A **

    /1-8

    Fiel

    d of

    app

    licat

    ion

    H

    eatin

    g/ G

    eoth

    erm

    al /S

    olar

    The

    pum

    p is

    con

    trolle

    d by

    Red

    Kno

    b te

    chno

    logy

    P-

    v, fo

    r var

    iabl

    e di

    ffere

    ntia

    l pre

    ssur

    e

    P-

    c, fo

    r con

    stan

    t diff

    eren

    tial p

    ress

    ure

    br

    eake

    det

    ectio

    n

    C

    olle

    ctiv

    e fa

    ult s

    igna

    l SSM

    Hyd

    raul

    ic o

    pera

    tiona

    l are

    a -v

    (var

    iabl

    e)

    03/1

    0 D

    atas

    heet

    Stra

    tos

    PAR

    A **

    /1-8

  • 49TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.3 PUMP WILO STRATOS PARA04

    /10

    Hyd

    raul

    ic o

    pera

    tiona

    l are

    a -c

    (con

    stan

    t)

    Dat

    ashe

    et S

    trato

    s PA

    RA

    **/1

    -806

    /10

    Hyd

    raul

    ic o

    pera

    tiona

    l are

    a ex

    tern

    al c

    ontr

    ol P

    WM

    Dat

    ashe

    et S

    trato

    s PA

    RA

    **/1

    -8

  • 50

    13. ANNEX

    13.4 ERROR MESSAGES FREQUENCY INVERTER BONFIGLIOLI AGILE

  • 51TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.4 ERROR MESSAGES FREQUENCY INVERTER BONFIGLIOLI AGILE

  • 52

    13. ANNEX

    13.4 ERROR MESSAGES FREQUENCY INVERTER BONFIGLIOLI AGILE

  • 53TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.5 TECHNICAL DATA RSM610

  • 54

    13. ANNEX

    13.5 TECHNICAL DATA RSM610

  • 55TU_D_WP_Max-HiQ_2020/05-bi - Errors and changes of all information, pictures and drawings remain reserved.Compliance with the generally valid and recognized rules of technology must be strictly adhered to!ATTENTION! Installation and wiring only by authorized specialists.

    13. ANNEX

    13.6 REFRIGERANT R134AP

    age

    : 1SA

    FETY

    DAT

    A SH

    EET

    Rev

    ised

    edi

    tion

    no :

    3

    Dat

    e : 2

    8 / 1

    1 / 2

    017

    Sup

    erse

    des

    : 25

    / 1 /

    2016

    Tetr

    aflu

    oroe

    than

    e (R

    -134

    a)W

    AG-1

    33

    2.

    2 : N

    on-fl

    amm

    able

    , non

    -to

    xic

    gase

    s

    W

    arni

    ng

    SEC

    TIO

    N 1

    . Id

    entif

    icat

    ion

    of th

    e su

    bsta

    nce/

    mix

    ture

    and

    of t

    he c

    ompa

    ny/u

    nder

    taki

    ng

    1.1.

    Pro

    duct

    iden

    tifie

    rTr

    ade

    nam

    e:

    Tetra

    fluor

    oeth

    ane

    (R-1

    34a)

    SDS

    no:

    WA

    G-1

    33C

    hem

    ical

    des

    crip

    tion

    :Te

    traflu

    oroe

    than

    e (R

    134a

    )C

    AS

    No

    :811

    -97-

    2E

    C N

    o :2

    12-3

    77-0

    Inde

    x N

    o :--

    -R

    egis

    trat

    ion-

    No.

    :01

    -211

    9459

    374-

    33-

    Che

    mic

    al fo

    rmul

    a:

    C2H

    2F4

    1.2.

    Rel

    evan

    t ide

    ntifi

    ed u

    ses

    of th

    e su

    bsta

    nce

    or m

    ixtu

    re a

    nd u

    ses

    advi

    sed

    agai

    nst

    Rel

    evan

    t ide

    ntifi

    ed u

    ses

    :U

    se a

    s re

    frige

    rant

    .In

    dust

    rial a

    nd p

    rofe

    ssio

    nal.

    Per

    form

    risk

    ass

    essm

    ent p

    rior t

    o us

    e.Te

    st g

    as/C

    alib

    ratio

    n ga

    s. L

    abor

    ator

    y us

    e.C

    onta

    ct s

    uppl

    ier f

    or m

    ore

    info

    rmat

    ion

    on u

    ses.

    1.3.

    Det

    ails

    of t

    he s

    uppl

    ier o

    f the

    saf

    ety

    data

    she

    etC

    ompa

    ny id

    entif

    icat

    ion

    :W

    estfa

    len

    AG

    Indu

    strie

    weg

    43

    4815

    5 M

    UE

    NS

    TER

    Deu

    tsch

    land

    Tel :

    004

    9 2

    51 6

    95

    0Fa

    x: 0

    049

    2 51

    6 9

    5 1

    94E-

    Mai

    l add

    ress

    (com

    pete

    nt p

    erso

    n):

    sdb@

    wes

    tfale

    n-ag

    .de

    1.4.

    Em

    erge

    ncy

    tele

    phon

    e nu

    mbe

    rEm

    erge

    ncy

    tele

    phon

    e nu

    mbe

    r:

    Tel.

    (+49

    ) 545

    9/80

    625

    SEC

    TIO

    N 2

    . H

    azar

    ds id

    entif

    icat

    ion

    2.1.

    Cla

    ssifi

    catio

    n of

    the

    subs

    tanc

    e or

    mix

    ture

    Haz

    ard

    Cla

    ss a

    nd C

    ateg

    ory

    Cod

    e R

    egul

    atio

    n EC

    127

    2/20

    08 (C

    LP)

    • Phy

    sica

    l haz

    ards

    :G

    ases

    und

    er p

    ress

    ure

    - Liq

    uefie

    d ga

    s - W

    arni

    ng -

    (CLP

    : P

    ress

    . Gas

    Liq

    .) - H

    280

    2.2.

    Lab

    el e

    lem

    ents

    Labe

    lling

    Reg

    ulat

    ion

    EC 1

    272/

    2008

    (CLP

    )

    • Haz

    ard

    pict

    ogra

    ms

    W

    estfa

    len

    AGIn

    cas

    e of

    em

    erge

    ncy

    : Tel

    . (+4

    9) 5

    459/

    8062

    5In

    dust

    riew

    eg 4

    3 4

    8155

    MU

    EN

    STE

    R D

    euts

    chla

    ndTe

    l : 0

    049

    2 51

    6 9

    5 0

    Fax:

    004

    9 2

    51 6

    95

    1 94

    Pag

    e : 2

    SAFE

    TY D

    ATA

    SHEE

    TR

    evis

    ed e

    ditio

    n no

    : 3

    Dat

    e : 2

    8 / 1

    1 / 2

    017

    Sup

    erse

    des

    : 25

    / 1 /

    2016

    Tetr

    aflu

    oroe

    than

    e (R

    -134

    a)W

    AG-1

    33

    SEC

    TIO

    N 2

    . H

    azar

    ds id

    entif

    icat

    ion

    (con

    tinue

    d)

    • Haz

    ard

    pict

    ogra

    ms

    code

    :G

    HS

    04• S

    igna

    l wor

    d:

    War

    ning

    • Haz

    ard

    stat

    emen

    ts:

    H28

    0 - C

    onta

    ins

    gas

    unde

    r pre

    ssur

    e; m

    ay e

    xplo

    de if

    hea

    ted.

    • Pre

    caut

    iona

    ry s

    tate

    men

    ts

    - S

    tora

    ge:

    P40

    3 - S

    tore

    in a

    wel

    l-ven

    tilat

    ed p

    lace

    .

    2.3.

    Oth

    er h

    azar

    ds:

    Asp

    hyxi

    ant i

    n hi

    gh c

    once

    ntra

    tions

    .C

    onta

    ct w

    ith li

    quid

    may

    cau

    se c

    old

    burn

    s/fro

    stbi

    te.

    SEC

    TIO

    N 3

    . C

    ompo

    sitio

    n/in

    form

    atio

    n on

    ingr

    edie

    nts

    3.1.

    Sub

    stan

    ce /

    3.2

    . Mix

    ture

    Subs

    tanc

    e /

    3.2.

    Mix

    ture

    CA

    S N

    oSu

    bsta

    nce

    nam

    eC

    onte

    nts

    EC N

    oC

    lass

    ifica

    tion(

    DSD

    )C

    lass

    ifica

    tion(

    CLP

    )In

    dex

    No

    Reg

    istr

    atio

    n no

    Tetr

    aflu

    oroe

    than

    e (R

    134a

    ):

    100

    %P

    ress

    . Gas

    Liq

    . (H

    280)

    811-

    97-2

    212-

    377-

    0--

    ---

    01-2

    1194

    5937

    4-33

    -

    Con

    tain

    s no

    oth

    er c

    ompo

    nent

    s or

    impu

    ritie

    s w

    hich

    will

    influ

    ence

    the

    clas

    sific

    atio

    n of

    the

    prod

    uct.

    * 1:

    Lis

    ted

    in A

    nnex

    IV /

    V R

    EA

    CH

    , exe

    mpt

    ed fr

    om re

    gist

    ratio

    n.*

    2: R

    egis

    tratio

    n de

    adlin

    e no

    t exp

    ired.

    * 3:

    Reg

    istra

    tion

    not r

    equi

    red:

    Sub

    stan

    ce m

    anuf

    actu

    red

    or im

    porte

    d <

    1t/y

    .Fu

    ll te

    xt o

    f H-p

    hras

    es s

    ee s

    ectio

    n 16

    .Fu

    ll te

    xt o

    f H-s

    tate

    men

    ts s

    ee s

    ectio

    n 16

    .

    SEC

    TIO

    N 4

    . Fi

    rst a

    id m

    easu

    res

    4.1.

    Des

    crip

    tion

    of fi

    rst a

    id m

    easu

    res

    - Inh

    alat

    ion

    :R

    emov

    e vi

    ctim

    to u

    ncon

    tam

    inat

    ed a

    rea

    wea

    ring

    self

    cont

    aine

    d br

    eath

    ing

    appa

    ratu

    s. K

    eep

    vict

    im w

    arm

    and

    rest

    ed. C

    all a

    doc

    tor.

    App

    ly a

    rtific

    ial r

    espi

    ratio

    n if

    brea

    thin

    g st

    oppe

    d.- S

    kin

    cont

    act

    :In

    cas

    e of

    fros

    tbite

    spr

    ay w

    ith w

    ater

    for a

    t lea

    st 1

    5 m

    inut

    es. A

    pply

    a s

    teril

    e dr

    essi

    ng. O

    btai

    nm

    edic

    al a

    ssis

    tanc

    e.- E

    ye c

    onta

    ct:

    Imm

    edia

    tely

    flus

    h ey

    es th

    orou

    ghly

    with

    wat

    er fo

    r at l

    east

    15

    min

    utes

    .- I

    nges

    tion

    :In

    gest

    ion

    is n

    ot c

    onsi

    dere

    d a

    pote

    ntia

    l rou

    te o

    f exp

    osur

    e.

    4.2.

    Mos

    t im

    port

    ant s

    ympt

    oms

    and

    effe

    cts,

    bot

    h ac

    ute

    and

    dela

    yed

    :In

    hig

    h co

    ncen

    tratio

    ns m

    ay c

    ause

    asp

    hyxi

    atio

    n. S

    ympt

    oms

    may

    incl

    ude

    loss

    of m

    obili

    ty/

    cons

    ciou

    snes

    s. V

    ictim

    may

    not

    be

    awar

    e of

    asp

    hyxi

    atio

    n.In

    low

    con

    cent

    ratio

    ns m

    ay c

    ause

    nar

    cotic

    effe

    cts.

    Sym

    ptom

    s m

    ay in

    clud

    e di

    zzin

    ess,

    head

    ache

    , nau

    sea

    and

    loss

    of c

    o-or

    dina

    tion.

    4.3.

    Ind

    icat

    ion

    of a

    ny im

    med

    iate

    med

    ical

    atte

    ntio

    n an

    d sp

    ecia

    l tre

    atm

    ent n

    eede

    d:

    Non

    e.

    Wes

    tfale

    n AG

    In c

    ase

    of e

    mer

    genc

    y : T

    el. (

    +49)

    545

    9/80

    625

    Indu

    strie

    weg

    43

    481

    55 M

    UE

    NS

    TER

    Deu

    tsch

    land

    Tel :

    004

    9 2

    51 6

    95

    0Fa

    x: 0

    049

    2 51

    6 9

    5 1

    94

  • 56

    13. ANNEX

    13.6 REFRIGERANT R134AP

    age

    : 3SA

    FETY

    DAT

    A SH

    EET

    Rev

    ised

    edi

    tion

    no :

    3

    Dat

    e : 2

    8 / 1

    1 / 2

    017

    Sup

    erse

    des

    : 25

    / 1 /

    2016

    Tetr

    aflu

    oroe

    than

    e (R

    -134

    a)W

    AG-1

    33

    SEC

    TIO

    N 5

    . Fi

    refig

    htin

    g m

    easu

    res

    5.1.

    Ext

    ingu

    ishi

    ng m

    edia

    - Sui

    tabl

    e ex

    tingu

    ishi

    ng m

    edia

    :W

    ater

    spr

    ay o

    r fog

    .- U

    nsui

    tabl

    e ex

    tingu

    ishi

    ng m

    edia

    :D

    o no

    t use

    wat

    er je

    t to

    extin

    guis

    h.

    5.2.

    Spe

    cial

    haz

    ards

    aris

    ing

    from

    the

    subs

    tanc

    e or

    mix

    ture

    Spec

    ific

    haza

    rds

    :E

    xpos

    ure

    to fi

    re m

    ay c

    ause

    con

    tain

    ers

    to ru

    ptur

    e/ex

    plod

    e.H

    azar

    dous

    com

    bust

    ion

    prod

    ucts

    :If

    invo

    lved

    in a

    fire

    the

    follo

    win

    g to

    xic

    and/

    or c

    orro

    sive

    fum

    es m

    ay b

    e pr

    oduc

    ed b

    y th

    erm

    alde

    com

    posi

    tion:

    Car

    bon

    mon

    oxid

    e. H

    ydro

    gen

    fluor

    ide.

    Car

    bony

    l flu

    orid

    e.

    5.3.

    Adv

    ice

    for f

    ire fi

    ghte

    rsSp

    ecifi

    c m

    etho

    ds:

    Mov

    e co

    ntai

    ners

    aw

    ay fr

    om th

    e fir

    e ar

    ea if

    this

    can

    be

    done

    with

    out r

    isk.

    If po

    ssib

    le, s

    top

    flow

    of p

    rodu

    ct.

    Use

    fire

    con

    trol m

    easu

    res

    appr

    opria

    te fo

    r the

    sur

    roun

    ding

    fire

    . Exp

    osur

    e to

    fire

    and

    hea

    tra

    diat

    ion

    may

    cau

    se g

    as re

    cept

    acle

    s to

    rupt

    ure.

    Coo

    l end

    ange

    red

    rece

    ptac

    les

    with

    wat

    ersp

    ray

    jet f

    rom

    a p

    rote

    cted

    pos

    ition

    . Pre

    vent

    wat

    er u

    sed

    in e

    mer

    genc

    y ca

    ses

    from

    ent

    erin

    gse

    wer

    s an

    d dr

    aina

    ge s

    yste

    ms.

    Use

    wat

    er s

    pray

    or f

    og to

    kno

    ck d

    own

    fire

    fum

    es if

    pos

    sibl

    e.Sp

    ecia

    l pro

    tect

    ive

    equi

    pmen

    t for

    fire

    :U

    se s

    elf-c

    onta

    ined

    bre

    athi

    ng a

    ppar

    atus

    .fig

    hter

    sS

    tand

    ard

    prot

    ectiv

    e cl

    othi

    ng a

    nd e

    quip

    men

    t (S

    elf C

    onta

    ined

    Bre

    athi

    ng A

    ppar

    atus

    ) for

    fire

    fight

    ers.

    Sta

    ndar

    d E

    N 4

    69 -

    Pro

    tect

    ive

    clot

    hing

    for f

    irefig

    hter

    s. S

    tand

    ard

    - EN

    659

    : Pro

    tect

    ive

    glov

    es fo

    rfir

    efig

    hter

    s.S

    tand

    ard

    EN

    137

    - S

    elf-c

    onta

    ined

    ope

    n-ci

    rcui

    t com

    pres

    sed

    air b

    reat

    hing

    app

    arat

    us w

    ith fu

    llfa

    ce m

    ask.

    SEC

    TIO

    N 6

    . Ac

    cide

    ntal

    rele

    ase

    mea

    sure

    s

    6.1.

    Per

    sona

    l pre

    caut

    ions

    , pro

    tect

    ive

    equi

    pmen

    t and

    em

    erge

    ncy

    proc

    edur

    es:

    Try

    to s

    top

    rele

    ase.

    Eva

    cuat

    e ar

    ea.

    Ens

    ure

    adeq

    uate

    air

    vent

    ilatio

    n.W

    ear s

    elf-c

    onta

    ined

    bre

    athi

    ng a

    ppar

    atus

    whe

    n en

    terin

    g ar

    ea u

    nles

    s at

    mos

    pher

    e is

    pro

    ved

    tobe

    saf

    e.P

    reve

    nt fr

    om e

    nter

    ing

    sew

    ers,

    bas

    emen

    ts a

    nd w

    orkp

    its, o

    r any

    pla

    ce w

    here

    its

    accu

    mul

    atio

    nca

    n be

    dan

    gero

    us.

    Act

    in a

    ccor

    danc

    e w

    ith lo

    cal e

    mer

    genc

    y pl

    an.

    Sta

    y up

    win

    d.

    6.2.

    Env

    ironm

    enta

    l pre

    caut

    ions

    :Tr

    y to

    sto

    p re

    leas

    e.

    6.3.

    Met

    hods

    and

    mat

    eria

    l for

    con

    tain

    men

    t and

    cle

    anin

    g up

    :V

    entil

    ate

    area

    .

    6.4.

    Ref

    eren

    ce to

    oth

    er s

    ectio

    ns:

    See

    als

    o se

    ctio

    ns 8

    and

    13.

    Wes

    tfale

    n AG

    In c

    ase

    of e

    mer

    genc

    y : T

    el. (

    +49)

    545

    9/80

    625

    Indu

    strie

    weg

    43

    481

    55 M

    UE

    NS

    TER

    Deu

    tsch

    land

    Tel :

    004

    9 2

    51 6

    95

    0Fa

    x: 0

    049

    2 51

    6 9

    5 1

    94

    Pag

    e : 4

    SAFE

    TY D

    ATA

    SHEE

    TR

    evis

    ed e

    ditio

    n no

    : 3

    Dat

    e : 2

    8 / 1

    1 / 2

    017

    Sup

    erse

    des

    : 25

    / 1 /

    2016

    Tetr

    aflu

    oroe

    than

    e (R

    -134

    a)W

    AG-1

    33

    SEC

    TIO

    N 7

    . H

    andl

    ing

    and

    stor

    age

    7.1.

    Pre

    caut

    ions

    for s

    afe

    hand

    ling

    Safe

    use

    of t

    he p

    rodu

    ct:

    Onl

    y ex

    perie

    nced

    and

    pro

    perly

    inst

    ruct

    ed p

    erso

    ns s

    houl

    d ha

    ndle

    gas

    es u

    nder

    pre

    ssur

    e.Th

    e su

    bsta

    nce

    mus

    t be

    hand

    led

    in a

    ccor

    danc

    e w

    ith g

    ood

    indu

    stria

    l hyg

    iene

    and

    saf

    ety

    proc

    edur

    es.

    Use

    onl

    y pr

    oper

    ly s

    peci

    fied

    equi

    pmen

    t whi

    ch is

    sui

    tabl

    e fo

    r thi

    s pr

    oduc

    t, its

    sup

    ply

    pres

    sure

    and

    tem

    pera

    ture

    . Con

    tact

    you

    r gas

    sup

    plie

    r if i

    n do

    ubt.

    Do

    not s

    mok

    e w

    hile

    han

    dlin

    g pr

    oduc

    t.E

    nsur

    e th

    e co

    mpl

    ete

    gas

    syst

    em w

    as (o

    r is

    regu

    laril

    y) c

    heck

    ed fo

    r lea

    ks b

    efor

    e us

    e.C

    onsi

    der p

    ress

    ure

    relie

    f dev

    ice(

    s) in

    gas

    inst

    alla

    tions

    .D

    o no

    t bre

    athe

    gas

    .A

    void

    rele

    ase

    of p

    rodu

    ct in

    to a

    tmos

    pher

    e.Sa

    fe h

    andl

    ing

    of th

    e ga

    s re

    cept

    acle

    :R

    efer

    to s

    uppl

    ier's

    con

    tain

    er h

    andl

    ing

    inst

    ruct

    ions

    .S

    uck

    back

    of w

    ater

    into

    the

    cont

    aine

    r mus

    t be

    prev

    ente

    d.D

    o no

    t allo

    w b

    ackf

    eed

    into

    the

    cont

    aine

    r.P

    rote

    ct c

    ylin

    ders

    from

    phy

    sica

    l dam

    age;

    do

    not d

    rag,

    roll,

    slid

    e or

    dro

    p.W

    hen

    mov

    ing

    cylin

    ders

    , eve

    n fo

    r sho

    rt di

    stan

    ces,

    use

    a c

    art (

    trolle

    y, h

    and

    truck

    , etc

    .)de

    sign

    ed to

    tran

    spor

    t cyl

    inde

    rs.

    Leav

    e va

    lve

    prot

    ectio

    n ca

    ps in

    pla

    ce u

    ntil

    the

    cont

    aine

    r has

    bee

    n se

    cure

    d ag

    ains

    t eith

    er a

    wal

    lor

    ben

    ch o

    r pla

    ced

    in a

    con

    tain

    er s

    tand

    and

    is re

    ady

    for u

    se.

    If us

    er e

    xper

    ienc

    es a

    ny d

    iffic

    ulty

    ope

    ratin

    g cy

    linde

    r val

    ve d

    isco

    ntin

    ue u

    se a

    nd c

    onta

    ctsu

    pplie

    r.N

    ever

    atte

    mpt

    to re

    pair

    or m

    odify

    con

    tain

    er v

    alve

    s or

    saf

    ety

    relie

    f dev

    ices

    .D

    amag

    ed v

    alve

    s sh

    ould

    be

    repo

    rted

    imm

    edia

    tely

    to th

    e su

    pplie

    r.K

    eep

    cont

    aine

    r val

    ve o

    utle

    ts c

    lean

    and

    free

    from

    con

    tam

    inan

    ts p

    artic

    ular

    ly o

    il an

    d w

    ater

    .R

    epla

    ce v

    alve

    out

    let c

    aps

    or p

    lugs

    and

    con

    tain

    er c

    aps

    whe

    re s

    uppl

    ied

    as s

    oon

    as c

    onta

    iner

    isdi

    scon

    nect

    ed fr

    om e

    quip

    men

    t.C

    lose

    con

    tain

    er v

    alve

    afte

    r eac

    h us

    e an

    d w

    hen

    empt

    y, e

    ven

    if st

    ill c

    onne

    cted

    to e

    quip

    men

    t.N

    ever

    atte

    mpt

    to tr

    ansf

    er g

    ases

    from

    one

    cyl

    inde

    r/con

    tain

    er to

    ano

    ther

    .N

    ever

    use

    dire

    ct fl

    ame

    or e

    lect

    rical

    hea

    ting

    devi

    ces

    to ra

    ise

    the

    pres

    sure

    of a

    con

    tain

    er.

    Do

    not r

    emov

    e or

    def

    ace

    labe

    ls p

    rovi

    ded

    by th

    e su

    pplie

    r for

    the

    iden

    tific

    atio

    n of

    the

    cylin

    der

    cont

    ents

    .

    7.2.

    Con

    ditio

    ns fo

    r saf

    e st

    orag

    e, in

    clud

    ing

    any

    inco

    mpa

    tibili

    ties

    :K

    eep

    cont

    aine

    r bel

    ow 5

    0°C

    in a

    wel

    l ven

    tilat

    ed p

    lace

    .O

    bser

    ve a

    ll re

    gula

    tions

    and

    loca

    l req

    uire

    men

    ts re

    gard

    ing

    stor

    age

    of c

    onta

    iner

    s. C

    onta

    iner

    ssh

    ould

    be

    stor

    ed in

    the

    verti

    cal p

    ositi

    on a

    nd p

    rope

    rly s

    ecur

    ed to

    pre

    vent

    them

    from

    falli

    ngov

    er. S

    tore

    d co

    ntai

    ners

    sho

    uld

    be p

    erio

    dica

    lly c

    heck

    ed fo

    r gen

    eral

    con

    ditio

    n an

    d le

    akag

    e.C

    onta

    iner

    val

    ve g

    uard

    s or

    cap

    s sh

    ould

    be

    in p

    lace

    . Sto

    re c

    onta

    iner

    s in

    loca

    tion

    free

    from

    fire

    risk

    and

    away

    from

    sou

    rces

    of h

    eat a

    nd ig

    nitio

    n.C

    onta

    iner

    s sh

    ould

    not

    be

    stor

    ed in

    con

    ditio

    ns li

    kely

    to e

    ncou

    rage

    cor

    rosi

    on. K

    eep

    away

    from

    com

    bust

    ible

    mat

    eria

    ls.

    7.3.

    Spe

    cific

    end

    use

    (s)

    :N

    one.

    SEC

    TIO

    N 8

    . Ex

    posu

    re c

    ontr

    ols/

    pers

    onal

    pro

    tect

    ion

    8.1.

    Con

    trol

    par

    amet

    ers

    Occ

    upat

    iona

    l Exp

    osur

    e Li

    mits

    Tetr

    aflu

    oroe

    than

    e (R

    134a

    ):

    AG

    W (8

    h) -

    Ger

    man

    y [m

    g/m

    ³] TR

    GS

    900

    : 42

    00:

    AG

    W (8

    h) -

    Ger

    man

    y [p

    pm] T

    RG

    S 9

    00 :

    1000

    :E

    xcee

    ding

    fact

    or A

    GW

    - G

    erm

    any

    TRG

    S 9

    00 :

    8:

    KZG

    W/V

    LE-C

    H [m

    g/m

    3] :

    4200

    DN

    EL: D

    eriv

    ed n

    o ef

    fect

    leve

    l (W

    orke

    rs)

    Tetr

    aflu

    oroe

    than

    e (R

    134a

    ):

    Inha

    latio

    n-lo

    ng te

    rm (s

    yste

    mic

    ) [m

    g/m

    3] :

    1400

    0

    We