technical data

SplitSky Air

air cond

itioning

systems

FDQ-B8V3B9

EEDEN08-100

Page 2: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

Split - Sky Air

EED

EN08

-100

- 02

/200

8Pr

inte

d in

Bel

gium

by

Goe

kint

Gra

phic

sCo

pyrig

ht ©

Dai

kin

Naamloze Vennootschap

Zandvoordestraat 300

B-8400 Ostend, Belgium

www.daikin.eu

BTW: BE 0412 120 336

RPR Oostende

Het ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

Daikin’s unique position as a man-ufacturer of air conditioning equip-ment, compressors and refrige-rants has led to its close involve-ment in environmental issues. Forseveral years Daikin has had the in-tention to become a leader in theprovision of products that havelimited impact on the environ-ment. This challenge demands theeco design and development of awide range of products and an en-ergy management system, result-ing in energy conservation and areduction of waste.

“ The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular pur-pose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Eu-rope N.V. explicitly rejects any liability for any direct or indirect dam-age, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”

EEDEN08- 100

Page 3: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

technical data

SplitSky Air

air conditioning systems

FDQ-B8V3B9

EEDEN08-100

Page 4: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Split Sky Air • Indoor Units 4

• Indoor Units • R-410A • FDQ-B8V3B9

TABLE OF CONTENTSFDQ-B8V3B9

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4 Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 10Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

9 Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Page 5: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Indoor Units • R-410A • FDQ-B8V3B9

11

• Split Sky Air • Indoor Units5

1 Features

Indoor Unit Split Sky FDQ-B8V3B9 R-410a • Slim design for flexible installation

• Ideal for use in larger areas

• Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible

• Maximum external static pressure (ESP) ranges from 150 till 250Pa

• Optimum air distribution

heat pump standard optional 2 steps: FDQ250, 3

steps: FDQ125,200

optional

Page 6: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

3

12

• Split Sky Air • Indoor Units 6

• Indoor Units • R-410A • FDQ-B8V3B9

2 Specifications

2-1 FOR INDOOR UNITS ONLY FDQ125B8V3B9 FDQ200B8V3B9 FDQ250B8V3B9

Nominal input (Indoor only)

Cooling kW 1,340 1,340Heating kW 1,340 1,340

2-2 TECHNICAL SPECIFICATIONS FDQ125B8V3B9 FDQ200B8V3B9 FDQ250B8V3B9

Casing Colour Non paintedMaterial Galvanised steel

Dimensions Packing Height mm 512 607 607Width mm 1,515Depth mm 795 1,055 1,055

Unit Height mm 350 450 450Width mm 1,400Depth mm 662 900 900

Weight Unit kg 59.0 89.0 94.0Packed Unit kg 74.0 108.0 113.0

Required Ceiling Void mm 350 450 450Heat Exchanger

Dimensions Length mm 1,150 1,200 1,200Nr of Rows 3 3 3Fin Pitch mm 1.75 2.00 2.00Nr of Passes 10 12 12Face Area m² 0.338 0.634 0.634Nr of Stages 14 24 24

Tube type Hi-XSS (7) Hi-XSS (8) Hi-XSS (8)Fin Type Rhombus Non-symmetric fin Non-symmetric fin

Treatment HydrophilicFan Type Sirocco fan

Quantity 2 2 2Air Flow Rate Cooling Medium m³/min 43.0 69.0 89.0

Heating Medium m³/min 43.0 69.0 89.0Fan Max High Pa 150 250 250

Standard Pa 150 250 250Low Pa 150 250 250

Motor Quantity 1 1 1Model DPA216-178NB DPC241-241NB DPC241-241NBNumber of steps 3 3 2Output (high)

W 500 650 1,000

Drive Direct driveCooling Sound Power Medium dBA 75.0 81.0 82.0

Sound Pressure High dBA 44.0 45.0 47.0Heating Sound Pressure Low dBA 44.0 45.0 47.0Refrigerant Type R-410APiping connections

Liquid (OD) Type Flare connectionDiameter (OD)

mm 9.52 9.52 12.7

Gas Type Flare connection Braze connection Braze connectionDiameter (OD)

mm 15.9 22.2 22.2

Drain Diameter (OD)

mm 25 25

Heat Insulation Both liquid and gas pipesAir Filter Resin net with mold resistanceAir direction control Up and downwardsTemperature control Microprocessor thermostat for cooling and heatingSafety Devices Fan motor thermal fuseStandard Accessories

Item Installation and operation manualQuantity 1 1 1

Page 7: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Indoor Units • R-410A • FDQ-B8V3B9

12

• Split Sky Air • Indoor Units7

2 Specifications

Notes Sound values are measured in a semi-anechoic room with correctionsThe sound pressure level is measured via a microphone at 1m distance of the unit.

Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings of this chapter.

The sound power level is an absolute value indicating the power which a sound source generates.

2-3 ELECTRICAL SPECIFICATIONS FDQ125B8V3B9 FDQ200B8V3B9 FDQ250B8V3B9

Power Supply Name V3Phase 1~Frequency Hz 50 50 50Voltage V 230 230 230

Voltage range Minimum -10%Maximum +10%

Power Supply Intake Both indoor and outdoor unitNotes FOR MORE DETAILS, REFER TO WIRING DIAGRAM, NAME PLATE AND INSTALLATION MANUAL

2-2 TECHNICAL SPECIFICATIONS FDQ125B8V3B9 FDQ200B8V3B9 FDQ250B8V3B9

Page 8: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

3

13

• Split Sky Air • Indoor Units 8

• Indoor Units • R-410A • FDQ-B8V3B9

3 Options

FDQ-B7V3B

Name of option FDQ125-200-250B7

Wiring adaptor for electrical appendices KRP4A51Adapter for wiring (interlock for fresh air intake) KRP1B54Interface adapter for Sky Air series DTA112B51Central remote control DCS302C51

unified ON/OFF control DCS301B51Schedule timer DST301B51Option PCB for electrical heater, humidifier and/or hour meter. *1 EKRP1B2Remote control Wired type BRC1D527Remote ON/OFF, forced OFF EKRORO

3TW22809-1F

*1 Electrical heater, humidifier and hour meter are field supply. These parts should not be installed inside the equipment. (Refer to installation manual EKRP1B2).

Page 9: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Indoor Units • R-410A • FDQ-B8V3B9

14

• Split Sky Air • Indoor Units9

4 Control systems

3TW23651-2

6.5 x 9 (Round end slit)

Cover open

Cover closed

5 x 7 (Round end slit) HoleJ5

5 x 10 (Round end slit)

BRC1D52

Page 10: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

3

15

• Split Sky Air • Indoor Units 10

• Indoor Units • R-410A • FDQ-B8V3B9

5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing

3TW30824-1

unit (mm)FDQ125B

View A

View A

j1 Power supply intakej2 Drain connection J25 O.D.j3 Gas pipe connection single union joint 5/8’’ or 15,9 mmj4 Liquid pipe connection single union joint 3/8’’ or 9,52 mmj5 Filter

Notes:R : Service space

3TW30844-1

unit (mm)FDQ200-250BFDYP200-250B

View A

View A

j1 Power supply intakej2 Drain connection J25 O.D.j3 Gas pipe connection

FDYP200B/250B :1 1/8’’ O.D. or 28,6 mmFDQ200/250 :7/8’’ O.D. or 22,2 mm O.D.

j4 Liquid pipe connectionFDYP200B : Single union joint 1/2’’ or 12.7mmFDYP250B : Single union joint 5/8’’ or 15.9mmFDQ200 : Single union joint 3/8’’ or 9,52 mmFDQ250 : Single union joint 1/2’’ or 12.7mm

j5 Filter

Notes:R : Service space

Model A BFDYP200B8V19/FDQ200B8V3B9 830 285

FDYP250B8V19/FDQ250B8V3B9 890 255

Page 11: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Indoor Units • R-410A • FDQ-B8V3B9

16

• Split Sky Air • Indoor Units11

6 Piping diagram

3TW26055-1AO Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

Heat exchanger

Refrigerant flow

CoolingHeating

Liquid pipe connection port

FDQ125-250B

Gas pipe connection port

Refrigerant pipe connection port diameters

Model Gas LiquidFDQ125 J15.90

J9.52FDQ200

J 22.2FDQ250 J 12.7

Page 12: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

3

17

• Split Sky Air • Indoor Units 12

• Indoor Units • R-410A • FDQ-B8V3B9

7 Wiring diagram7 - 1 Wiring diagram

2TW26036-1B

FDQ125-250B

A1P Printed circuit boardA3P Printed circuit boardT1R Transformer(230V / 218V)C1R Capacitor (fan)F1T Thermal fuse (M1F embedded)HAP Light emitting diode (service monitor

green)K1F Magnetic contactor (M1F)M1F Motor (Fan)

R1T Thermistor (air)R2T Thermistor (coil)RyF1 Magnetic relay (fan)SS1 Selector switch (emergency)X1M Terminal stripRC Signal receiver circuitTC Signal transmission circuitF5U Power setting faultQ1DI Earth leakage breaker

Wired remote controlBS1 On/Off buttonBS2 Timer mode start/stop buttonBS3,BS8 Programming time buttonBS4 Temperature setting button upBS9 Temperature setting button downBS6 Operation mode selector buttonBS7 Timer on/off buttonBS12 Inspection/test operation button

Adapter for wiringRyC,RyF Magnetic relayConnector for optional partsX60AX61A

Connector (interface adaptor for SKY AIR /US series)

X33A Connector (adapter for wiring)X35A Connector (group control adapter)X40A Connector (remote ON/OFF, forced off, only

SKY-AIR Pàseries)

IndoorOutdoorWired remotecontrol

Terminals foroperation indicator

Switch box

Details of wired remote control(optional accessory)

Adapter for wiring

Fano

perat

ion

com

pres

sor

opera

tion

Notes

1. When using the central remote control, see manual for connectionto the unit.

2. Be sure that the power supply is switched off before opening theswitch box.* L-tap is not available for 250 class.

g Field wiring D Terminala : Connectorc : Wire clampb : Protective earth (screw)ColoursBLK: Black / BRN: brown / WHT: WhiteRED: Red / BLU: Blue / GRY: GreyORG: Orange / YLW: Yellow

BS14 Filter sign reset buttonH1P Light emitting diode (service monitor

red)LCD Liquid crystal displaySS1 Selector switch (main/sub)

Remote ON/OFF,forced OFF

Page 13: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Indoor Units • R-410A • FDQ-B8V3B9

18

• Split Sky Air • Indoor Units13

8 Sound data8 - 1 Sound pressure spectrum

3TW22807-1

Soun

dpr

essu

rele

vel(

dB)

Octave band center frequency (Hz)

FDQ125B

Legend

High speed

Low speed

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition (at 62 Pa ESP, 90m3/min)3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)4 Reference acoustic pressure 0dB = 20μPa5 the indicated sound pressure is the casing radiated sound

pressure.

3TW22817-1

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition (50 Pa ESP, 72m

3/min)

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)4 Reference acoustic pressure 0dB = 20Pa5 the indicated sound pressure is the casing radiated sound pressure.

Soun

dpr

essu

rele

vel(

dB)

FDQ200B

Octave band center frequency (Hz)

Suction Unit discharge

Location of microphone

Microphone

Metalducts insulated inside

3TW22827-1

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition (62 Pa ESP, 90m

3/min)

3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)4 Reference acoustic pressure 0dB = 20Pa5 the indicated sound pressure is the casing radiated sound pressure.

Soun

dpr

essu

rele

vel(

dB)

FDQ250B

Octave band center frequency (Hz)

Suction Unit discharge

Location of microphone

Microphone

Metalducts insulated inside

Page 14: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

3

18

• Split Sky Air • Indoor Units 14

• Indoor Units • R-410A • FDQ-B8V3B9

8 Sound data8 - 2 Sound power spectrum

3TW26057-1

Soun

dop

erat

ion

leve

l(dB

)

Octave band center frequency (Hz)

FDQ125B

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition3 dBA A-weighted sound operation level. (A-scale according to

IEC)4 Reference acoustic pressure 0dB = 20Pa5 Curve for FDQ125B in cooling mode

3TW26957-1

Soun

dop

erat

ion

leve

l(dB

)

Octave band center frequency (Hz)

FDQ200B

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition3 dBA A-weighted sound operation level. (A-scale according to

IEC)4 Reference acoustic pressure 0dB = 20Pa5 Curve for FDQ200B in cooling mode

3TW26967-1

Soun

dop

erat

ion

leve

l(dB

)

Octave band center frequency (Hz)

FDQ250B

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition3 dBA A-weighted sound operation level. (A-scale according to

IEC)4 Reference acoustic pressure 0dB = 20Pa5 Curve for FDQ250B in cooling mode

Page 15: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Indoor Units • R-410A • FDQ-B8V3B9

19

• Split Sky Air • Indoor Units15

9 Fan characteristics

3TW22808-1

FDQ125B

highmedium

low

3TW22818-1

FDQ200B

lowmedium

high

3TW22828-1

FDQ250B

medium

high

Page 16: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

3

110

• Split Sky Air • Indoor Units 16

• Indoor Units • R-410A • FDQ-B8V3B9

10 Installation10 - 1 Installation method

Number Description

1 Indoor unit

2 Outdoor unit

3 Remote control

4 Inlet air

5 Discharged air

6 Refrigerant piping, connection electric wire

7 Drain pipe

8Ground wireWire to ground from the outdoor unit to preventelectrical shocks.

9 Air filter

Page 17: technical data - daikintech.co.ukFDA)/2010/FDQ-B...technical data Split Sky Air FDQ-B8V3B9 air conditioning systems EEDEN08-100

• Indoor Units • R-410A • FDQ-B8V3B9

110

• Split Sky Air • Indoor Units17

10 Installation10 - 1 Installation method