Rooftops Level 2:

Variable AirVolume Units

COMMERCIAL HVAC EQUIPMENT

Technical Development Program

Page 2: TDP-632 Rooftop Units Level 2 Constant Volume (Preview)

Technical Development Programs (TDP) are modules of technical training on HVAC theory,

system design, equipment selection and application topics. They are targeted at engineers and designers who wish to develop their knowledge in this field to effectively design, specify, sell or apply HVAC equipment in commercial applications.

Although TDP topics have been developed as stand-alone modules, there are logical group-ings of topics. The modules within each group begin at an introductory level and progress to advanced levels. The breadth of this offering allows for customization into a complete HVAC curriculum – from a complete HVAC design course at an introductory-level or to an advanced-level design course. Advanced-level modules assume prerequisite knowledge and do not review basic concepts.

Large rooftop units are a fast-growing segment of the rooftop industry. A large VAV (vari-able air volume) rooftop unit with VAV terminals can be used in the place of multiple smaller constant volume units as a way of providing multiple zones of temperature control. With fewer rooftop units, duct systems, power supplies, and roof penetrations, cost savings are realized. The VAV rooftop unit can be incorporated with a variety of VAV terminals to form a complete sys-tem. Large VAV rooftops units are also being used in some applications traditionally reserved for applied equipment, such as central station air handlers and chiller systems. The rooftop variable air volume system offers a competitive first cost, competitive operating cost, ease of service, good indoor air quality capabilities, and good part-load humidity control. The ability to deliver these benefits has led to increased use of variable air volume systems using large tonnage rooftop units.

© 2007 Carrier Corporation. All rights reserved. The information in this manual is offered as a general guide for the use of industry and consulting engineers in designing systems. Judgment is required for application of this information to specific installations and design applications. Carrier is not responsible for any uses made of this information and assumes no responsibility for the performance or desirability of any resulting system design.

The information in this publication is subject to change without notice. No part of this publication may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Carrier Corporation. Printed in Syracuse, NY

CARRIER CORPORATION Carrier Parkway Syracuse, NY 13221, U.S.A.

Page 3: TDP-632 Rooftop Units Level 2 Constant Volume (Preview)

Table of Contents

Introduction.....................................................................................................................................................1 Market Overview........................................................................................................................................2 Large Rooftop Unit Types ..........................................................................................................................3 Variable Air Volume or Constant Volume .................................................................................................3 VAV versus VVT® Systems .......................................................................................................................4

What is a VAV Rooftop System? ...................................................................................................................5 System Description.....................................................................................................................................6

Variable Air Volume Rooftop Unit.......................................................................................................6 VAV Terminals (One per Control Zone) ...............................................................................................6 Supply Diffusers.....................................................................................................................................6 Control System.......................................................................................................................................6 Ductwork and Return Grille ...................................................................................................................7

Customer Benefits ......................................................................................................................................7 Candidate Buildings for VAV Rooftop Systems ............................................................................................8

Single-Story Industrial Building.................................................................................................................8 Two-Story Office Park Building.................................................................................................................9 Multi-Story Office Building .......................................................................................................................9

VAV Rooftop Unit Features .........................................................................................................................10 Standard Unit............................................................................................................................................10 Refrigerant ................................................................................................................................................11 Condenser Coil Construction....................................................................................................................11

Round Tube Plate Fin Coil...................................................................................................................11 Microchannel Coil................................................................................................................................12 Benefits of Microchannel Technology .................................................................................................13

Supply Fan Airflow Modulation...............................................................................................................13 Multiple Steps of Unloading.....................................................................................................................14 Economizer...............................................................................................................................................14

Minimum Ventilation...........................................................................................................................15 Economizer Control Methods ..............................................................................................................15

Unit Options and Accessories .......................................................................................................................17 Outdoor Air Damper.................................................................................................................................17 Barometric Relief .....................................................................................................................................18 Power Exhaust ..........................................................................................................................................18 Return Fan ................................................................................................................................................19 Minimum Outdoor Air Control.................................................................................................................20 Single-Point Power Connection................................................................................................................20 Service Disconnect ...................................................................................................................................20 Horizontal Supply and Return ..................................................................................................................21 High Capacity Cooling Coils.....................................................................................................................21 Filter Choices............................................................................................................................................22 High-Static Supply Fan.............................................................................................................................22 Supply Fan Motor Choices .......................................................................................................................23 Direct Expansion (DX) Reheat Coils........................................................................................................23 Hot Gas Bypass ........................................................................................................................................24 Corrosion-Resistant Coil Options.............................................................................................................24 Heating Types...........................................................................................................................................25 Staged Gas Control ...................................................................................................................................25 LP Gas Conversion Kit.............................................................................................................................26 Interior Casing Options.............................................................................................................................26 Low Ambient Control...............................................................................................................................26

Page 4: TDP-632 Rooftop Units Level 2 Constant Volume (Preview)

Air Terminals and Diffusers ......................................................................................................................... 27 Single-Duct Terminal ............................................................................................................................... 27 Fan-Powered Terminal Units.................................................................................................................... 28 Parallel Fan-Powered Terminal ................................................................................................................ 28

Series Fan-Powered Terminal .............................................................................................................. 29 Choosing a Fan-Powered Terminal...................................................................................................... 30 Integral-Diffuser Air Terminal............................................................................................................. 30

Diffuser Types .......................................................................................................................................... 31 Indoor Air Quality Features .......................................................................................................................... 32

VAV Rooftop Unit ................................................................................................................................... 32 Filters ................................................................................................................................................... 32 Part Load Humidity Control................................................................................................................. 33

Air Terminals............................................................................................................................................ 35 Application Topics........................................................................................................................................ 35

Central Heat in a VAV Rooftop ............................................................................................................... 35 Unit Installation and Clearances............................................................................................................... 37 Building Pressurization, Exhaust and Return Fans................................................................................... 37

Exhaust Fans ........................................................................................................................................ 38 Return Fans .......................................................................................................................................... 38

Smoke Control Modes.............................................................................................................................. 39 Building Evacuation Mode................................................................................................................... 40 Building Pressurization Mode.............................................................................................................. 40 Smoke Purge ........................................................................................................................................ 40 Fire Shutdown ...................................................................................................................................... 40

Airflow Limitations .................................................................................................................................. 41 Cooling................................................................................................................................................. 41 Heating................................................................................................................................................. 41

Ventilation ................................................................................................................................................ 41 ASHRAE 62.1...................................................................................................................................... 42 Ventilation Rate Procedure .................................................................................................................. 42 IAQ Procedure ..................................................................................................................................... 43 Demand Controlled Ventilation ........................................................................................................... 43

Energy Recovery ...................................................................................................................................... 45 Controls......................................................................................................................................................... 46

Variable Air Volume Rooftop Control Objectives ................................................................................... 46 Typical Variable Air Volume Rooftop System Control....................................................................... 46

Equipment Level Sequences..................................................................................................................... 48 Occupancy Period Scheduling ............................................................................................................. 48 Occupied Cooling................................................................................................................................. 49 Unoccupied Cooling............................................................................................................................. 49 Night Time Free Cooling ..................................................................................................................... 49 Occupied Heating................................................................................................................................. 49 Unoccupied Heating............................................................................................................................. 50 Dehumidification ................................................................................................................................. 50

Acoustic Considerations ............................................................................................................................... 51 Noise Control – Rooftop Units ................................................................................................................. 51 Noise Control – Variable Air Volume Terminals..................................................................................... 52

Codes and Standards ..................................................................................................................................... 53 UL/ETL .................................................................................................................................................... 53 ARI ........................................................................................................................................................... 53 ASHRAE.................................................................................................................................................. 54 Leadership in Energy and Environmental Design (LEED™)................................................................... 54

Unit Selection ............................................................................................................................................... 54 Summary....................................................................................................................................................... 57 Work Session ................................................................................................................................................ 58 Work Session Answers ................................................................................................................................. 61 Glossary ........................................................................................................................................................ 63

Page 5: TDP-632 Rooftop Units Level 2 Constant Volume (Preview)

ROOFTOPS, LEVEL 2: VARIABLE AIR VOLUME UNITS

Commercial HVAC Equipment

1

Introduction Packaged rooftop units comprise the largest segment of the commercial HVAC marketplace

in the United States. The focus of this TDP is large packaged rooftop units that are used in vari-able air volume applications. These units are typically available in capacities ranging from 20 to 100 tons or more. Each unit includes a compressor section, filter section, evaporator coil, air-cooled condenser coil, indoor fan sec-tion, and controls designed for VAV (variable air volume) duty, all in a packaged design for outdoor installa-tion.

Large packaged VAV rooftop units, as shown in Figure 1, are de-signed to meet current industry trends. The procedure for selecting an appro-priate unit and system for a commercial building has changed. Four major concerns now drive the HVAC unit and system choice in to-day’s marketplace:

• Full and part-load energy efficiency

• Part-load temperature and humidity control

• Indoor air quality (IAQ) within the building

• Acoustic considerations

A VAV rooftop unit can deliver high efficiencies at full and part load with good temperature and humidity control. Available features provide for desirable indoor air quality, and the unit de-sign allows for flexibility in location to allow for better acoustical performance.

There are several building types that are good candidates for VAV rooftop units. There is also a variety of options and accessories available that will customize the VAV rooftop to the applica-tion. VAV terminals for zone control are also available in several configurations: series and parallel fan-powered terminals, single-duct terminals, and integral-diffuser units.

Overall, the resulting building indoor air quality benefits from the use of a VAV rooftop sys-tem. The ability to meet the four design requirements has led to increased use of variable air volume systems based on large tonnage rooftop units.

Figure 1 Typical Variable Air Volume Packaged Rooftop

Page 6: TDP-632 Rooftop Units Level 2 Constant Volume (Preview)

ROOFTOPS, LEVEL 2: VARIABLE AIR VOLUME UNITS

Commercial HVAC Equipment

2

Common information applicable to this TDP is also contained in TDP-631, Rooftops Level 1: Constant Volume. This TDP will reference that publication as a source of further information.

As a final note, this TDP is meant to complement the Carrier System Design Guide on VAV Rooftop Sys-tems. The Design Guide develops system-related topics like VAV roof-top layout, heating and cooling loads, duct design, operating cost analysis, and jobsite suggestions. These docu-ments are shown in Figure 2.

Market Overview

The rooftop market has experienced a number of changing trends in design choices. One trend is toward fewer, larger tonnage units instead of large numbers of smaller sized units, as shown in Figure 3. One of the primary reasons is due to the cost of preventative maintenance. Other reasons are that the number of roof penetrations, electrical power supplies, and separate duct systems can be reduced with fewer, large-sized units.

For example, consider a structure with multiple small rooftop units. A simple task, such as changing filters, could take a technician a minimum of several hours. The air conditioning needs of the same building may be met with a single large rooftop unit distributing air to VAV terminals for zone control. The filter maintenance could now be accomplished in min-utes. Scenarios like this are one reason for a general increase in the use of larger capacity rooftop units.

Figure 2 Other Carrier Publications that Complement This TDP

Figure 3 Changing Trend in Design Choices

Page 7: TDP-632 Rooftop Units Level 2 Constant Volume (Preview)

ROOFTOPS, LEVEL 2: VARIABLE AIR VOLUME UNITS

Commercial HVAC Equipment

3

Large Rooftop Unit Types

Large rooftops are available in two configurations: packaged air-conditioner (PAC), or gas-fired heating and cooling year round air conditioner (YAC).

A packaged air-conditioner may provide cooling only or be equipped with gas-fired heaters, electric resistance heat-ers, hot water heat, or steam heating coils, depending on the size and manufacturer. When capable of heating, the unit may be used for “year round” heating and cooling duty. Tra-ditionally, the YAC is given the year round designation by virtue of the fact it is factory-equipped with gas heat. Gas historically has been less expensive as a heating source than electric resistance heaters.

Variable Air Volume or Constant Volume

VAV units have the ability to vary the supply airflow. The most popular method utilizes a variable frequency drive (VFD) to control the rpm of the supply fan motor. See Figure 4. Vary-ing the airflow as a function of space load requirements saves fan energy. The larger the rooftop unit motor is, the larger the potential for fan energy savings. Installing inlet guide vanes (IGV) on the supply fan can also provide fan modulation. Today, inlet guide vanes are used less frequently than in the past, primarily because they are less efficient and less reliable than VFDs. Also, the price of VFDs has de-creased. For a complete discussion of fan modulation methods, see TDP-613, Fans in VAV Systems.

Variable air volume systems ad-just the unit operation based on the volume and temperature of air re-quired by the system. A VAV system can utilize an air handler, rooftop, or self-contained indoor unit to produce the required airflow.

VAV units typically use a multi-step discharge air controller to stage the compressors to maintain a constant air temperature off the cooling coil. VAV units may also incorporate a supply air temperature reset function. This feature automatically resets the supply air temperature up-wards when the return air temperature (RAT) reaches the occupied space temperature set point. If the RAT equals the space temperature set point, all space demands should be satisfied. At that point, the controls can reset the supply temperature up a few degrees (usually from 55 to 60° F) to save compressor energy. Another reset function associated with VAV systems is zone demand reset. The cold air temperature can be reset based upon the requirement to satisfy the average occupied zone space temperature.

VAV Rooftop Unit Capacities

At one time, 100 tons of capacity was seen as the practical maximum for a rooftop unit. Today, 130 tons is common, with a few manufacturers offering units as big as 200 tons.

Figure 4 VAV Rooftop Unit – Key Features

Page 8: TDP-632 Rooftop Units Level 2 Constant Volume (Preview)

ROOFTOPS, LEVEL 2: VARIABLE AIR VOLUME UNITS

Commercial HVAC Equipment

4

VAV units usually have more steps of cooling capacity than constant volume units, allowing them to maintain better control of the discharge air temperature. Some units that have a limited number of capacity steps may require hot gas bypass to protect the refrigeration system during low-load conditions. Hot gas bypass allows the compressor to operate even when the load re-quirements are less than the minimum step of compressor capacity reduction. Often hot gas bypass is not needed, as the VAV rooftop unit will control the discharge air set point and cycle last stage of compression to maintain set point even at low-load conditions.

Constant volume units base their operation on a thermostat in the oc-cupied space (see Figure 5). Hence, constant volume units supply a fixed volume of air. Only the temperature of the air provided varies. They do not utilize a VFD or discharge air control.

VAV versus VVT® Systems

The percentage of large variable air volume rooftops sold versus the number of large constant volume sized rooftops continues to increase. The ratio is tonnage-dependent. For example, the larger the unit, the greater the percentage of variable air volume units sold. At least 50 percent of the 30 to 50-ton large rooftops are variable air volume. Above 50 tons, the ratio approaches 90 percent. This is because VAV systems are equipped to serve large cooling demands.

In the HVAC industry, VAV-equipped rooftop units are available starting about 20 tons in capacity. Be-low 20 tons, systems called variable volume and temperature (VVT) are often used. A VVT system is capable of supplying multiple zones of control from a constant volume rooftop. In-stead of using a VFD to vary the airflow through the unit, unused sup-ply airflow is bypassed from the main supply duct back to the unit return. See Figure 6.

Hot Gas Bypass

The energy draw of a compressor when operating on hot gas bypass is the same as when operating on the minimum step of unloading.

Figure 5 Constant Volume Rooftop – Key Features

Figure 6 Typical VVT System