2
Tank Safety & Protection Devices Emergency Vent Cover 54 Vent Operation Construction The KSES emergency pressure relief vent provides pressure relief only. Vacuum relief must be supplied by normal venting devices, or use our KSESV emergency pressure and vacuum relief vent covers. When excessive pressure builds within the storage tank the KSES series emergency pressure relief vent begin to open at a predetermined set pressure relieving excessive pressure. When the overpressure has dissipated the cover reseat onto the base. The series KSES is available in several materials that are corrosion resistant to most petroleum product applications. See Standard material of construction table for available material. Predetermined setting range is from a minimum of 700mm W.C to a maximum of 9,050mmW.C Sizes are 400, 450, 500 and 600mm with flange drilling according to ANSI 150lb or API650. The series KSES is designed to provide emergency pressure relief for storage tanks when exposed to overpressures that are not handled by standard tank vents. These vents provide the capacity to meet API standard 2000 for emergency venting due to fire exposure when properly sized. According to API 2000 Code : EMERGENCY PRESSURE RELIEF VENT COVER KSES Section 4.2

Tank Safety & Protection Devices Emergency Vent Coveraurora-works.com/wp-content/uploads/2016/11/KSES.pdf · Tank Safety & Protection Devices Emergency Vent Cover 54 ... These vents

  • Upload
    builiem

  • View
    224

  • Download
    3

Embed Size (px)

Citation preview

Page 1: Tank Safety & Protection Devices Emergency Vent Coveraurora-works.com/wp-content/uploads/2016/11/KSES.pdf · Tank Safety & Protection Devices Emergency Vent Cover 54 ... These vents

Tank Safety & Protection Devices Emergency Vent Cover

54

Vent Operation

Construction

The KSES emergency pressure relief vent provides pressure relief only.

Vacuum relief must be supplied by normal venting devices, or use our KSESV emergency pressure and vacuum relief vent covers.

When excessive pressure builds within the storage tank the KSES series emergency pressure relief vent begin to open at a predetermined set pressure relieving excessive pressure.

When the overpressure has dissipated the cover reseat onto the base.

The series KSES is available in several materials that are corrosion resistant to most petroleum product applications.

See Standard material of construction table for available material.

Predetermined setting range is from a minimum of 700mm W.C to a maximum of 9,050mmW.C

Sizes are 400, 450, 500 and 600mm with flange drilling according to ANSI 150lb or API650.

The series KSES is designed to provide emergency pressure relief for storage tanks when exposed to overpressures that are not handled by standard tank vents.

These vents provide the capacity to meet API standard 2000 for emergency venting due to fire exposure when properly sized.

According to API 2000 Code :

EMERGENCY PRESSURE RELIEF VENT COVER KSES

Section 4.2

Page 2: Tank Safety & Protection Devices Emergency Vent Coveraurora-works.com/wp-content/uploads/2016/11/KSES.pdf · Tank Safety & Protection Devices Emergency Vent Cover 54 ... These vents

Tank Safety & Protection Devices Emergency Vent Cover

55

EMERGENCY PRESSURE RELIEF VENT COVER KSES

Unit = mm

16” 18” 20” 24”N.D 400 450 500 600

AAPI 650 597 635 660 762

ANSI 150# 597 635 700 815

APP.HMIN. 320 320 320 320MAX. 550 550 550 550

* CERTIFIED DIMENSIONS AVAILABLE UPON REQUEST. (STD : API650)

KSES TYPE

Materials of Construction

Dimension Table

ITEMNO COMPONENT

BODY ALUMINIUM C.S SS304 SS316TRIM SS304 SS304 SS304 SS316L

1 BODY B26-319.F A216-WCB A351-CF8 A351-CF8M2 COVER (DISC) C.S C.S 304SS SS316L3 SPRING PAD SS304 SS304 SS304 SS3044 SPRING STEM SS304 SS304 SS304 SS3045 SPRING SS304 SS304 SS304 SS3046 O-RING VITON OR REQUIRED7 LIFTING EYE BOLT SS304 SS304 SS304 SS3048 HEX. NUT SS304 SS304 SS304 SS3049 SPRING WASHER SS304 SS304 SS304 SS304

N.D

APP.H

A

APP.H

N.D

A

3

26

54

1

89

7

3

2

5

4

1

6

8

7

9

10

KSES FRONT CROSS SECTION VIEW KSES FRONT CROSS SECTION VIEW

Section 4.2