Upload
squelche
View
214
Download
1
Embed Size (px)
Citation preview
Copyright Information andAlteration of Content
The 2003 NETA Acceptance Testing Specifications are protected under the copyright laws of the United States, and all rights are reserved. Further, the Specifications may not be copied, modified, sold, or used except in accordance with such laws and as follows:
Purchasers may reproduce and use all or a portion of the Specifications after paying the charges so long as the 2003 NETA Acceptance Specifications are clearly and obviously identified in writing as the source of all such uses or reproductions.
In all events, the following sections of the 2003 NETA Acceptance Testing Specifications are incorporated by reference in each subsection of the 2003 NETA Acceptance Testing Specifications as though set out in full in each subsection:
3.0 Qualifications of Testing Organization and their Personnel3.1 Testing Organization3.2 Testing Personnel
4.0 Division of Responsibility4.1 The Owner’s Representative4.2 The Testing Organization
5.0 General5.1 Safety and Precaution5.2 Suitability of Test Equipment5.3 Test Instrument Calibration5.4 Test Report
The purchaser is advised to include the above sections along with any section(s) of 7.0.
NETA intends that Section 7.0 of the 2003 NETA Acceptance Testing Specifications be reproduced and used on a “cut and paste” basis for the particular type of equipment to be tested, in all events so long as the clear and obvious identification of the course described above is provided in writing.
© Copyright 2003InterNational Electrical Testing Association
PO Box 687, 106 Stone StreetMorrison, CO 80465
Voice: 303.697.8441 Facsimile: 303.697.8431E-mail: [email protected] • Web: www.netaworld.org
NETA ATS–2003
Table 100.18
Thermographic SurveySuggested Actions Based on Temperature Rise
Temperature difference (T) based on comparisons between similar
components under similar loading.
Temperature difference (T) based upon comparisons between component and ambient air
temperatures. Recommended Action
1ºC - 3ºC 1ºC - 10ºC Possible deficiency; warrants investigation
4ºC - 15ºC 11ºC - 20ºCIndicates probable deficiency; repair as time permits
- - - - - - 21ºC - 40ºCMonitor until corrective measures can be accomplished
>15ºC >40ºC Major discrepancy; repair immediately
Temperature specifications vary depending on the exact type of equipment. Even in the same class of equipment (i.e., cables) there are various temperature ratings. Heating is generally related to the square of the current; therefore, the load current will have a major impact on T. In the absence of consensus standards for T, the values in this table will provide reasonable guidelines.
An alternative method of evaluation is the standards-based temperature rating system as discussed in Chapter 8.9.2, Conducting an IR Thermographic Inspection, Electrical Power Systems Maintenance and Testing, by Paul Gill, PE, 1998.
It is a necessary and valid requirement that the person performing the electrical inspection be thoroughly trained and experienced concerning the apparatus and systems being evaluated as well as knowledgeable of thermographic methodology.